Roberts Gorden DualAir DAT100, DualAir DAT75, DualAir DAT115, DualAir DAT90 Operation And Service Manual

Page 1
WARNING
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Leave the building.
6. Immediately call your local gas supplier after leaving the building. Follow the gas suppliers instructions.
7. If you cannot reach your gas supplier, call the Fire Department.
Fire Hazard
Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appliance.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
Roberts-Gordon Europe Limited
Oxford Street Bilston, West Midlands WV14 7EG UK Telephone: +44(0) 1902 494425 Fax: +44(0) 1902 403200 Service Telephone: +44(0) 1902 498733 Service Fax: +44(0) 1902 401464 E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
www.rg-inc.com
WARNING
Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the installation, operation and service manual thoroughly before installing or servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
© Copyright 2005 Roberts-Gordon
Quality in Any Language™
DualAir
®
Installation, Commissioning,
Operation & Service Manual
DAT75
DAT90 DAT100 DAT115
P/N X527 Rev B 10/05
Heating and Cooling Units
Page 2
Page 3
© 2005
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon.
Printed in U.K.
TABLE OF CONTENTS
SECTION 1: Heater Safety......................................................2
SECTION 2: Installer Responsibility .....................................2
2.1 Clearances to Combustibles ........................................2
2.2 Corrosive Chemicals....................................................2
2.3 National Standards and Applicable Codes .................. 2
SECTION 3: Critical Considerations......................................3
3.1 Basic Information.........................................................3
3.2 Location and Suspension ............................................3
3.3 Minimum Required Installation Clearances .................3
3.4 Clearances to Combustibles ........................................3
3.5 Ventilation .................................................................... 3
3.6 Gas Supply ..................................................................3
3.7 Electrical Supply .......................................................... 3
3.8 Flue..............................................................................3
3.9 Coil Condense Drain.................................................... 3
SECTION 4: Specifications .................................................... 5
4.1 DAT (all models) ..........................................................5
4.2 General Technical Data Table (all models) .................. 6
4.3 Technical Data Table - Heater Section (all models) .....7
4.4 DualAir
®
Performance Data -
Graph of Air Flows v Static Pressure ........................... 8
SECTION 5: Heater Installation.............................................. 9
5.1 General........................................................................ 9
5.2 Handling ......................................................................9
5.3 Shelf Mounting and Suspension.................................. 9
SECTION 6: Flue Installation ...............................................10
6.1 Flue Installation.......................................................... 10
6.2 Type C
12
, C32 & C62 Appliance..................................... 10
6.3 Type B22 Appliance..................................................... 10
6.4 Converting from Top to Side Terminations
for Flue and Air Intake. .............................................. 10
SECTION 7: Air Supply......................................................... 13
7.1 Room Sealed Installation ........................................... 13
7.2 Open Flued Installation .............................................. 13
7.3 Building Ventilation ..................................................... 13
7.4 Isolated Equipment Rooms ........................................13
SECTION 8: Optional Heater Configurations...................... 14
8.1 Distribution Duct ........................................................14
SECTION 9: Gas Piping........................................................15
9.1 Connections............................................................... 15
SECTION 10: Wiring and Electrical Information.................16
10.1 Electrical Supply ...................................................... 16
10.2 Remote Control........................................................ 16
10.3 DAT Main Circuit Board Terminal Identification ........ 17
10.4 DAT Wiring Diagram Models 75-115 ........................ 18
10.5 DAT Wiring Diagram Models 75-115 ........................ 19
10.6 DAT Site Connections at Main Circuit Board............ 20
SECTION 11: Commissioning .............................................. 21
11.1 Pre Commission Checks...........................................21
11.2 Gas Supply............................................................... 21
11.3 Mechanical Checks................................................... 21
11.4 Begin Commissioning...............................................21
11.5 Combustion Testing (all models)............................... 23
11.6 Turning Off the DualAir
®
Unit.....................................24
11.7 External Controls ......................................................24
11.8 Complete the Commissioning...................................24
11.9 Instruction to the User ..............................................24
SECTION 12: User Instructions............................................25
12.1 User Instructions......................................................25
12.2 Heater Operation......................................................25
12.3 Common User Controls (all models) ........................25
12.4 Cooling Section Operation .......................................26
12.5 Heating Section Lighting Instructions.......................26
12.6 Simple Fault Finding (all models) .............................26
SECTION 13: Servicing.........................................................27
13.1 Servicing Instructions...............................................27
13.2 Burner Maintenance.................................................27
13.3 Fan/Motor Assembly Maintenance...........................27
13.4 Heat Exchanger Maintenance..................................27
13.5 Gas Control Valve Maintenance (all models) ...........28
13.6 Flue Fan ...................................................................28
SECTION 14: Conversion Between Gases ..........................29
14.1 General ....................................................................29
14.2 Burner Conversion ...................................................29
14.3 Gas Valves ...............................................................29
SECTION 15: Troubleshooting .............................................30
15.1 General ....................................................................30
15.2 Troubleshooting For Automatic Ignition
Burner Systems .......................................................31
15.3 Troubleshooting for Flame Supervision System .......32
15.4 Troubleshooting for Solenoid Valves ........................33
15.5 Troubleshooting for Main Fan...................................33
15.6 Troubleshooting for Fan Contactor ...........................34
SECTION 16: Removal and Replacement Parts..................35
16.1 Gas Valve .................................................................35
16.2 Burner Compartment ...............................................36
16.3 Ignition Electrode and Flame Probe.........................37
16.4 Flue Fan ...................................................................38
16.5 Heater Pressure Switch............................................39
16.6 Cooling Coil Safety Devices.....................................40
16.7 Ignition Control .........................................................41
16.8 Fan Motor Removal ..................................................41
16.9 Combination Fan/Limit Thermostat..........................42
Page 4
Page 5
TABLE OF FIGURES
Figure 1: Condense Drain ......................................................... 3
Figure 2: Installation Clearances and Clearances to
Combustibles............................................................. 4
Figure 3: Suspension Methods ................................................. 9
Figure 4: Flue and Roof Detail................................................ 10
Figure 5: Control Section & Upper Panel ................................ 11
Figure 6: Alternate .................................................................. 11
Figure 7: Vertical and Horizontal Flue Termination -
Ty pe B
22
Appliance................................................... 12
Figure 8: Vertical and Horizontal Flue Termination -
Ty pe C12 C32 & C62 Appliances.................................. 12
Figure 9: DualAir
®
Units Installed in Isolated
Equipment Rooms................................................... 13
Figure 10: Ducting................................................................... 14
Figure 11: Gas Connection with Stainless Steel
Flex Connector ....................................................... 15
Figure 12: Automatic Burner Control Box Sequence............... 22
Figure 13: Modureg Gas Valve................................................22
Figure 14: Heater Operating Sequence ..................................25
Figure 15: Fan/Limit Thermostat ............................................. 25
Figure 16: Belt Tension ...........................................................27
Figure 17: Standard Regulator Removal................................. 35
Figure 18: Cooling Coil Safety Devices. ..................................40
Figure 19: Combination Fan/Limit Thermostat........................ 43
Page 6
Page 7
1
Product Approval
ROBERTS GORDON® appliances have been tested and CE certified as complying with the essential requirements of the Gas Appliance Directive, The Low Voltage Directive, The Electromagnetic Compatibility Directive and the Machinery Directive for use on natural gas and L.P. gas when installed, commissioned and maintained in accordance with these instructions.
These instructions refer to appliances designed to operate in the European Union. Appliances designed for other countries (Non European Union) are available on request. This appliance must be installed in accordance with the local and national codes in force and used
only in a sufficiently ventilated space, as specified in these instructions. Before installation, check that the local gas distribution systems, nature of gas and pressure, and
adjustment of the appliance are compatible.
Page 8
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
2
SECTION 1: HEATER SAFETY
Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections.
Installation, Service and Annual Inspection of the DualAir
®
unit must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment.
Read this manual carefully before installation, operation, or service of this equipment.
This DualAir
®
unit is designed for heating and cooling non-residential indoor spaces. Do not install in residential spaces. These instructions, the layout drawing, local codes and ordinances, and applicable standards that apply to gas piping, electrical wiring, venting, refrigerant installation, etc., must be thoroughly understood before proceeding with the installation.
SECTION 2: INSTALLER RESPONSIBILITY
• To supply and install a suitable condenser unit along with associated refrigerant circuits in accordance with the requirements of all relevant local and national codes.
• To install the DualAir
®
unit, as well as the gas and electrical supplies, in accordance with appli­cable specifications and codes. Roberts-Gordon recommends the installer contact a local building inspector, Fire Officer or insurance company for guidance.
• To use the information given in the manual together with the local and national codes to perform the installation.
• To install the DualAir
®
unit in accordance with the
Clearances to Combustibles of this DualAir
®
unit.
• To furnish all needed materials not furnished as standard equipment.
• To plan location of supports, flues and air intakes.
• To provide access for servicing.
• To provide the owner with a copy of this installation, commissioning, operation and service manual.
• To never use the DualAir
®
unit as support for lad­der or other access equipment and never hang or suspend anything from heater.
• To ensure that there is sufficient ventilation in the area to comply with the requirements of all relevant local and national codes.
2.1 Clearances to Combustibles
In all situations, clearances to combustibles must be maintained. Caution must be used when running the DualAir
®
unit near combustible materials such as wood, paper, rubber, etc. A wall tag is on the back cover of this manual as a permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Affix the tag on a wall near the DualAir
®
unit.
2.2 Corrosive Chemicals
Roberts-Gordon cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility of the installer. It is essential that the contractor, the sub-contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemical compounds characterized by the presence of halogen elements (fluorine, chlorine, bromine, etc.). These com­pounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the lifespan of the DualAir
®
unit
components will be greatly reduced. Warranty will be invalid if the heater is exposed to halogenated hydrocar­bons.
2.3 National Standards and Applicable Codes
All Appliances must be installed in accordance with the latest revision of applicable standards and local and national codes. This refers also to the electric, gas, refrigerant and venting installation. Note: Additional standards for installations in Public Garages, Aircraft Hangars, etc. may be applicable.
CAUTION
Do not use heater in an area containing corrosive chemicals.
Corrosive chemicals will damage the burner and heat exchanger parts.
Failure to follow these instructions can result in property damage.
Page 9
SECTION 3: CRITICAL CONSIDERATIONS
3
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
The CTUD heater that forms the heating section of the DualAir
®
unit has an automatic ignition burner and may be operated as fully modulating or ON/OFF operation.
The standard unit has the air flow from left to right when viewed from the controls side.
A special order version with the opposite air flow is available where the combustion air intake and flue will be at the front of the unit.
3.2 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position.
• May be mounted on the floor or on a shelf of non-combustible material. (See Page 5, Section 4 and Page 9, Figure 3 for support points)
• May be suspended from above (See Page 9, Figure 3),on the floor, or from wall brackets of sufficient strength to support the DualAir
®
unit as listed in the Dimension Data Table on Page 6, Section 4.2. Drop rods must be a minimum of 12 mm diameter mild steel. Six suspension points are located on top of the DualAir
®
unit.
• Must be installed in a manner which allows the hinged door to be fully opened to provide access to all serviceable components.
3.3 Minimum Required Installation Clearances
Clearances around the DualAir
®
unit and flue must be as indicated on Page 4, Figure 2, Page 10, Figure 4 through Page 12, Figure 8 to ensure access for servicing, and correct operation.
3.4 Clearances to Combustibles
Clearances must be as indicated on Page 4, Figure
2. If no clearances to combustibles are indicated
then installation clearances apply.
3.5 Ventilation
It is important to ensure that there is adequate air circulation around the DualAir
®
unit to supply air for combustion, ventilation and distribution in accordance with local and national codes.
3.6 Gas Supply
It is important that the gas supply pipe is sized correctly to provide the inlet pressure as stated on the heater data plate. The gas supply pipe and electrical connections must not support any of the heater's weight.
3.7 Electrical Supply
A permanent 400v 3ø 50Hz electrical supply is required at the main electrical terminals. The heater also requires suitable energy controls in accordance with Section 10.
3.8 Flue
Choose a location to allow for the proper alignment of the flue. Each DualAir
®
unit must be fitted with an individual and correctly sized sealed flue system (See Page 10, Section 6).
No other appliance may be connected to the flue. For room sealed installation the air intake must be
the same size sealed system and the flue/air intake must terminate at an approved concentric wall or roof terminal.
3.9 Coil Condense Drain
The cooling coil must be fitted with a suitable condense drain. The condense pipe work should be in plastic or copper piping in accordance with the latest revision of applicable standards and local and national codes.
Figure 1: Condense Drain
Failure to install the condense drain correctly may cause water carry over into the fan compartment, which may then escape and cause property damage.
100 mm min.
Install to Suitable Drain
Drain to Open Funnel
Trap must be filled with water to be effective and prevent air being drawn backwards into the drip tray.
Page 10
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
4
Figure 2: Installation Clearances and Clearances to Combustibles
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapours the required distance away from the heater.
Failure to follow these instructions can result in death, injury or property damage.
Clearances to Combustibles
Alternative
Wall
Terminal
Roof Terminal
Air
Intake
Flue
15 cm
2.5 - 3.5 m*
3 m
60 cm
Installation Clearances
Customers
Suitable
Condenser
Unit
Insulated
Refrigerant pipes
to cooling coil
by Customer
Condense
Drain
Install to
suitable drain,
See Page 3,
Figure 1.
Air Flow
50 cm
50 cm**
30 cm
15 cm
If installed at low levels where individuals can come in contact with hot heat exchanger components, adequate guarding must be provided.
All distances are minimum clearance requirements for service access, air flow and safety.
Free blowing DualAir
®
units must always be installed at least 1.8 m above the floor. Ducted installations may be floor mounted. The flue pipe must have clearance from combustibles by 5 cm.
**80 cm is necessary to service heater.
* Free blowing DualAir
®
units may be mounted at a higher level if destratification fans and/or turn down nozzles are installed.
Page 11
SECTION 4: SPECIFICATIONS
5
SECTION 4: SPECIFICATIONS
4.1 DAT (all models)
225
Air Intake
Flue
Heater Section Fan Compartment
Electrical
Connections
(behind door)
Filter CompartmentCondense Drain
Air Outlet Spigot (35 mm flange)
Air Intake 130 mm dia
Coil Protection,
Frost Thermostat
& Pressure Switch
Alternate Flue & Air Intake Position
Cooling Coil
Air Inlet Spigot
(35 mm flange)
3010
896 225
1239
Internal
Spigot Height
1417
Flue 130 mm dia
Lockout
Reset
Green
Burner
On
Red
Lockout
Warning
Amber
Dirty Filter
Warning
734
Gas
Connection
112 7
20 mm Conduit Entry for Electrical Connections
1494
671
2070 532
1239
Internal
Spigot
Height
1250 Internal Spigot Width
Alternate Flue & Air Intake Position
315
89051 399
1340
1590
Extension Cover for Refrigerant Pipe-work
538
1032
Standard Flue & Air Intake Position
Side View
Front View
Rear View
Front View (Left Version)
Rear View (Left Version)
Page 12
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
6
4.2 General Technical Data Table (all models)
Electrical load at 230v 50Hz measured by calculating from total run current of appliance.
* Do not exceed the maximum length of flue stated or heater may not operate properly.
Reduce the maximum length stated by 1 m for each 90° bend installed.
**If minimum air flow requirements are not met then temperature limit devices will shut down the heater.
Model
Designed Air Flow # with Clean Filters
m
3
/sec
Min Air Flow at Coil
m
3
/sec
Max Air Flow at Coil
m
3
/sec
Fan Unit
Fan Pulley mm PCD
Motor Pulley mm PCD
Vee Belts
Total Electrical Load kW
Motor Size kW
Full Load Current A
Run Current at Designed Air Flow # A
Start Current A
Inlet Connection in
Outlet Connection in
Condensate Connection ISO 7-R
Refrigerant
°C Dry Bulb
°C Wet Bulb
°C Dry Bulb
°C Wet Bulb
All Models
Initial Pressure Loss
mbar
Max. Recommended Pressure Loss
mbar
Weight kg
NR dB(A)
SPL dB(A)
NR dB(A)
SPL dB(A)
NR dB(A)
SPL dB(A)
68 68 73 75
5.4
1
23.0 24.0
7.0 / 7.5
57.74 71.54
2.88
1.66
3.71
2A x 112 / 2A x 118
115
3.7
2.60
5.34
75 90
2 x A 63
2A x 180 / 2A x 200
2A x 100 / 2A x 95
Fan Data
457-486 Double Inlet Belt Drive
2A x 180
2 x A 64
100
kW
Max Cooling Load Split into Two Equal
Circuits
Design Temp. ON
Design Temp. OFF
27
R407C
612 621
1 5/8 copper
638 647
65
0.4
1.5
Qty. 6 - Farr 30/30 grade 100 x 635 x 406
Filters - All Models
7/8 copper
1 3/8 copper
18.07
14.66
Electrical Data - All models need 400v 50Hz 3N supply. Single phase supply output for control circuit 230v 50Hz fused at 5 Amp. All alarm and status signals 230v 50Hz. Modulation input 0-10vDC.
Cooling Coil - DX
4.0
7.5
2.2
4.45
4.0 / 4.5
3.3
Physical Data
Noise from Cabinet at 1 m 67.5
72
13.72
13
12.3
19.4
25
Noise from Air Inlet at 1 m
77 75
Noise from Air Outlet at 1 m
81 7776
Page 13
SECTION 4: SPECIFICATIONS
7
4.3 Technical Data Table - Heater Section (all models)
Appliance Category II
2H/L 3B/P
Gas rates corrected to standard conditions 1013.25 mbar 15°C. *See Page 43, Figure 19 for detailed Combination Fan/Limit Thermostat settings.
Model
Heat Input kW
Gross Calorific Value
Btu/h x 1000
Heat Input kW
Net Calorific Value
Btu/h x 1000
Approximate kW
Max Heat Output
Btu/h x 1000
Min Heat Input - Low Fire kW
Gross Calorific Value
Btu/h x 1000
Min Heat Input - Low Fire kW
Net Calorific Value
Btu/h x 1000
kW
Btu/h x 1000
Set Point 1 Fan OFF Temp.
°C
Set Point 2 Fan ON Temp.
°C
Set Point 3 Limit Temp. °C
Secondary Limit Thermostat
°C
Max Burner Pressure mba
r
m
3
/
h
ft
3
/
h
Min Burner Pressure - Low Fire mbar
m
3
/
h
ft
3
/
h
Max Burner Pressure mba
r
m
3
/
h
ft
3
/h
Min Burner Pressure - Low Fire mbar
m
3
/h
ft
3
/h
Max Burner Pressure mba
r
m
3
/
h
Max Gas Flow Rate
kg/h
liquid l/h
Min Burner Pressure - Low Fire mbar
m
3
/
h
Min Gas Flow Rate
kg/h
liquid l/h
Max Burner Pressure mba
r
m
3
/
h
Max Gas Flow Rate
kg/h
liquid l/h
Min Burner Pressure - Low Fire mbar
m
3
/
h
Min Gas Flow Rate
kg/h
liquid l/h
68.6 234
77.7 265
Min Heat Output - Low Fire
54.6 186
63.7 217
9.24
1.86
4.53
7.91
2.16
5.29
11.209.87
2.32
5.66
2.63
6.42
9.2
3.75
9.17
13.2 14.1 16.0
3.09 3.32
7.55 8.09
9.0 9.5 9.0
18.3 19.4 18.3
11.3
6.5
2.65
18.7
8.96 10.43 11.20 12.67
4.55 5.31 5.69 6.45
2.46 2.86 3.07 3.48
12.5 13.4 12.4 12.7
12.8 14.9 16.0 18.1
6.5 7.58 8.13 9.21
3.51 4.09 4.39 4.97
25.6 27.3 25.3 25.9
7.74
273.4
6.64
234.6
9.40
332.0293.2
8.30
4.9 5.04.54.6
335.1 391 419 474
9.49 11.06 11.86 13.43
279.3 316.4
10.0 9.3 9.2 10.2
6.30 7.4 7.9 9.0
3.23 2.9 3.0 3.1
319 371 398 451
9.0 10.5 11.3 12.8
45
6.6 6.0 6.2 6.3
121
457
134
115
119
90 100
289
84.7
320
93.8
379
111
413
111
256
74.9
284
83.3
334
98
365
107
406
75
239
70
265
77.7
311
91
341
100
379
293
86
324
95
227
66.5
266
78
LPG Gas Propane (G31) Data - Inlet Pressure 37 mbar (Alternative where permitted 50 mbar) Minimum 25 mbar Maximum 57.5 mbar
LPG Butane (G30) Data - Inlet Pressure 29 mbar Min 20 mbar Max 35 mbar
205
60.2
30
50 45 85
222.5 259.6
*Combination Fan/Limit Thermostat Settings
Min Gas Flow Rate
Min Gas Flow Rate
Max Gas Flow Rate
Max Gas Flow Rate
Natural Gas (G20) Data - Inlet Pressure 20 mbar Min 17 mbar Max 25 mbar
Natural Gas (G25) Data - Inlet Pressure 25 mbar Min 20 mbar Max 30 mbar
70 75
75
Page 14
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
8
4.4 DualAir
®
Performance Data - Graph of Air Flows v Static Pressure
4.4.1 DAT75 and 90 (2.2 kW or 4 kW motor)
4.4.2 DAT100 and 115 (4 kW motor)
350
300
250
200
150
100
50
0
2.4 2.6 2.8 3.0 3.2
3.4
2.2
400
Air Flow m3/sec
95 mm motor pulley x 180 mm fan pulley 100 mm motor pulley x 200 mm fan pulley
Static Pressure Pa
350
300
250
200
150
100
50
0
3.0 3.2 3.4 3.6 3.8
4.0
2.8
400
Air Flow m3/sec 118 mm Pulley 112 mm Pulley
Static Pressure Pa
Page 15
SECTION 5: HEATER INSTALLATION
9
SECTION 5: HEATER INSTALLATION
5.1 General
DualAir
®
units are designed for installation above 2.5 m. When connected to duct delivery systems any suitable location will be acceptable.
For floor mounting, the DualAir
®
unit may stand
directly on its base.
5.2 Handling
All DualAir
®
units have steel channel sections at the base to be used to support the equipment. Three steel sections are also provided across the top of the unit for support. The DualAir
®
unit may be
suspended from these top sections. The DualAir
®
unit is heavy and proper handling
equipment must be used by trained engineers.
5.3 Shelf Mounting and Suspension
For typical suspension See Page 9, Figure 3.
Figure 3: Suspension Methods
WARNING
Crush Hazard
Use 12 mm steel drop rod minimum.
Failure of the supports can result in death, injury or property damage.
12 mm
Steel
Drop Rod
Nut
Washers
Nut
Locknut
Rolled Steel
Channel
Floor
Base
Page 16
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
10
SECTION 6: FLUE INSTALLATION
6.1 Flue Installation
The flue must terminate outside of the building. Flues and air intakes must be fully sealed and correctly sized for the model. Flues should be assembled as detailed on Page 10, Figure 4 through Page 12, Figure 8. The joints between the flue terminal and the roof or wall must be sealed. If the flue passes through a wall or ceiling of combustible material it must be enclosed by a sleeve of non­combustible material and be separated from the sleeve by at least a 25 mm air gap.
Flues and air intakes must be adequately supported so that the DualAir
®
unit does not
bear the weight of the pipes.
For flue termination See Page 10, Figure 4 through Page 12, Figure 8.
6.2 Type C
12
, C32 & C62 Appliance
Room Sealed. The heaters are designed to be installed as room
sealed appliances. The flue and air intake are run as separate pipes to the concentric wall or roof terminal. See Page 12, Figure 8.
6.3 Type B
22
Appliance
The flue must terminate outside the building and be fitted with a low resistance terminal.
See Page 10, Figure 4 through Page 12, Figure 7.
6.3.1 Air Intake Terminal Cover
For Type B
22
appliance installations, an Air Intake Terminal Cover is an available option. The cover is scored flat sheet metal that must be bent into shape. See Page 12, Figure 7. Remove and retain the screws for the Air Inlet spigot. Use these screws to attach the cover in position over the spigot.
Figure 4: Flue and Roof Detail
6.4 Converting from Top to Side Terminations for Flue and Air Intake.
1. Remove the control section lower door and upper panel. See Page 11, Figure 5 through Figure 6 for details.
6.4.1 Flue Conversion
1. Remove the inner and outer flue spigots from the top. Retain the spigot and internal seal.
2. Disassemble the flue back to spigot "A". See Page 11, Figure 6. Ensure all seals are still in place.
3. Fit 90° bend directly into spigot "A" pointing forwards.
4. Cut a 90 mm length from the 360 mm flue that was removed.
5. Attach this piece to the 90° bend, then attach the inner spigot that was removed.
6.4.2 Air Intake Conversion
1. Remove the flexible hose from the air intake spigot.
2. Remove the spigot from the top.
3. Move the blanking plate from the upper panel (previously removed) to the top to cover the original flue and air intake holes.
4. Refit the upper panel feeding the air intake flex­ible hose through the upper hole and aligning the flue with the lower hole.
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to the heater section.
Keep all flammable objects, liquids and vapours the required distance away from the heater section.
Failure to follow these instructions can result in death, injury or property damage.
Roof
Flue
Terminal
Metal Sleeve
Masterflash
soaker flashing
or Rain Collar.
Flue
25mm Air Gap to
Combustible Material
Page 17
SECTION 6: FLUE INSTALLATION
11
5. Refit the air intake spigot to the flexible hose re­using the hose clamp and to the upper panel using the original screws.
6. Align the flues’ inner and outer spigots and attach through the holes in the upper panel re­using the original screws.
7. Refit the lower door.
Figure 5: Control Section & Upper Panel
Figure 6: Alternate
Upper Panel
Lower Door
Blanking Plate
Hose Clamp
360 mm Lenght of 130 mm dia Flue
Flexible Hose
Inner and Outer Flue Spigots
Air Intake Spigot
Control Section
Spigot "A"
90° Bend
90mm Flue
Inner Spigot
Hose Clamp
Flexible Hose
Upper Panel
Outer Spigots
Page 18
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
12
Figure 7: Vertical and Horizontal Flue Termination - Type B
22
Appliance
Figure 8: Vertical and Horizontal Flue Termination - Type C
12 C32
& C62 Appliances
Flue
Masterflash
Roof Terminal
Metal Sleeve
(25 mm air gap to
combustible material)
Air Intake
Terminal Cover
Fold leg
down
Fold foot
out
Flue
Roof Terminal
Air Intake
Manifold
Masterflash
Page 19
SECTION 7: AIR SUPPLY
13
SECTION 7: AIR SUPPLY
7.1 Room Sealed Installation
When installed as a room sealed heater the air for combustion is drawn in from outside the building. It is important to ensure that there is adequate ventilation to provide air for the distribution fan/s.
7.2 Open Flued Installation
Ensure adequate air supply at all times for both combustion and heating requirements in accordance with local and national codes. The air supply to the heater must be fitted with a low resistance terminal to prevent the ingress of debris. See Page 12, Figure 7.
7.2.1 Heaters Installed Within the Heated Space
Where the volume of the heated space is greater than 4.7 m
3
per kilowatt of total rated heat input and the air change rate is at least 0.5/h, additional high and low level ventilation will not be required.
For a building having an air change rate less than
0.5/h, ventilation will be necessary in accordance with local and national codes. Ventilation direct to outside must be provided as follows:
• Heaters above 70 kW heat input = 350 cm
2
+
2.5 cm
2
per kW of rated heat input above 70 kW
7.3 Building Ventilation
Where ventilation is required air must be taken from an outside point where it is not likely to be contaminated or obstructed.
Where natural ventilation is used, suitable ventilation with outside air at low level must be provided in accordance with Section 7.2.1 and local and national codes.
Where mechanical ventilation is used, extract rate must be 5% - 10% less than the inlet rate. The mechanical ventilation must be interlocked with the burner on the heater.
7.4 Isolated Equipment Rooms
Ventilation must prevent the isolated equipment room temperature from exceeding 32°C as well as prevent any negative air pressure within the room. See Page 13, Figure 9. Any isolated equipment room containing air heaters will require permanent air vents direct to outside air in compliance with local codes.
Where natural ventilation is used, suitable permanent openings at low and high level, communicating directly with the outside air, must be provided.
Where mechanical ventilation is used, extract rate must be 5% - 10% less than the inlet rate. The mechanical ventilation must be interlocked with the burner on the heater.
Figure 9: DualAir
®
Units Installed in Isolated Equipment Rooms.
Wall
Outside
Wall
High level ventilation
Low level
ventilation
Max Temperature 32° C Room air pressure must not be negative.
Duct distribution system or discharge to heated space.
Return air duct from heated space or fresh air from outside
Flue
Air Intake
Manifold
Page 20
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
14
SECTION 8: OPTIONAL HEATER CONFIGURATIONS
8.1 Distribution Duct
DualAir
®
units are designed to be connected to
distribution and air inlet ducting. It is recommended that flexible duct connectors and/
or attenuators are used to reduce duct born noises. It is recommended that the inlet ducting is arranged
with both fresh air and recirculating air dampers to take advantage of the "free cooling" stage provided.
Distribution ducting must be insulated to prevent heat gain during cooling mode.
The air flow must be in the direction as stated for the version being installed with the heater at the discharge end.
The duct must be designed as described on Page 14, Section 8.1 and Figure 10 to ensure that there is a homogenous air flow across the whole heat exchanger. Failure to provide a properly distributed air flow will reduce the life of the heat exchanger.
Contact Roberts-Gordon Europe Ltd. Design Department for recommendations regarding duct resistance and design. Tel: +44 (0) 1902 494425
Figure 10: Ducting
Dimension
X
*Minimum-
Twice
Dimension
X
Airflow Indicator
Flexible Flange
Ducting
NOTE: Duct size will be full size of inlet and outlet. All joints between the heater and duct work should be made as air tight as possible. *Inlet Duct Minimum Dimension same as Outlet Duct Minimum Dimension
Page 21
SECTION 9: GAS PIPING
15
SECTION 9: GAS PIPING
It is important that the gas supply pipe and the electrical connections do not support any of the heater’s weight.
A gas meter is connected to the service pipe by the Gas Supply Company. An existing meter should be checked, preferably by the Company, to ensure that the meter is adequate for the rate of gas supply required. Installation pipes must be fitted in accordance with local and national codes. Pipe work from the meter to the heater(s) must be of adequate size.
9.1 Connections
Connect the heater to the gas supply ensuring that the final connections are as follows:
• The gas supply pipe is adequately sized to carry the total volume of gas for the complete installation.
• An isolating valve and union connection should be used and fitted into the supply adjacent to the heater.
• For suspended heaters use an approved metal flexible connection between the isolating valve and the heater. To reduce pressure loss, use
one pipe size larger than the heater gas connection.
IMPORTANT - the complete installation must be purged and tested for gas soundness in accordance with local and national codes.
Figure 11: Gas Connection with Stainless Steel Flex Connector
WARNING
Fire Hazard
Connect gas supply according to Figure 11.
Gas can leak if not installed properly.
Failure to follow these instructions can result in death, injury or property damage.
Gas Isolating Valve
Cap
Union
Connection
Option B:
Medium or Heavy Guage Tubing Gas Connection
Option A:
Stainless Steel Flex Gas Connector
Drip Leg
Hold gas nipple securely
with pipe wrench when attaching the flex gas connector.
Do not twist flexible
gas connector.
Ensure all joints are
gas tight.
Do not bend flexible gas connector sharply.
Page 22
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
16
SECTION 10: WIRING AND ELECTRICAL INFORMATION
10.1 Electrical Supply
All heater models need a constant 400 V 50 Hz 3 ø supply connected to terminals L
1,L2
, L3, N & Earth.
Polarity "L
1
& N" must be correct. The voltage between neutral and earth should be 0 and never exceed 15 volts.
All heaters and controls must be correctly earthed. All external wiring must comply with the relevant
local codes. Wire specification H05VV-F. External controls must have a constant 230 V 50 Hz
1 Ø supply.
An isolator with a contact separation of at least 3 mm on all poles must be installed adjacent to, but not attached to the DualAir
®
unit to disconnect all
supplies to the heater and any remote control.
The final connection to the heater should be made by flexible cable or conduit to the main terminal block in the control section using 1 mm
2
cable on all
models.
All cables entering through the top of the heater should be routed via the metal shield to prevent inadvertent contact with the flue.
Models .................Fuse Size
DAT 75 & 90...............5 A
DAT 100 & 115 ...........10 A
10.2 Remote Control
Roberts Gordon market a dedicated DualAir
®
control that will operate all the available features of the unit. The DualAir
®
unit requires a 230 V remote control to provide a time control and Multistage heating/ cooling temperature control. See Page 20, Section
10.6.
To operate the modulating gas burner a further input of 0-10 V DC is required with 0V giving minimum fire and a 10V giving full fire, wired in screened cable (Belden 8451 or equivalent).
10.2.1 Remote Frost Thermostat
When required, connect to terminals 2 and 3 in the main terminal block.
Locate within the heated space adjacent to the most vulnerable equipment that requires protection.
See Page 17, Section 10.3 through Page 18, Section
10.4.
10.2.2 Remote Fan Controls
The fan will operate automatically. A switch or control wired between terminals 2 & 1 in
the terminal block will allow external control of the fan(s).
The fan may be operated continuously from an external control, with the burner/cooling cycling on and off.
WARNING
Electrical Shock Hazard
Disconnect electrical power before servicing.
Failure to follow these instructions can result in death or electrical shock.
Page 23
SECTION 10: WIRING AND ELECTRICAL INFORMATION
17
10.3 DAT Main Circuit Board Terminal Identification
Termina l
Number
Use Relay/Function Operation
1 Input or Output External Fan Control
Input for Remote Fan Opera-
tion Output for Fan Operation
Monitor
Optional - Main Fan Runs from
External Control
2 Output 230 V to external control
230 V 50 Hz supply of external
thermostat or control
3 Input Burner On
Burner Fires.
R1 energizes with gas valve
Burner Operates.
Fan Operates via R1
4 Output 230 V Burner ON Signal
Optional Remote Indication of
Burner ON.
5 Output
Neutral for Signals & External Control
7 Output 230 V Burner Lockout Signal
Optional Remote Indication of
Burner Lockout
8 Input
Burner Lockout Reset from N
(5)
Optional Remote Burner Lock-
out Reset (must be from N)
9 & 10
Volt Free Safety Circuits for
External Condensers
Site Wiring to Condensers Normally Closed Controls
Break on Fault Position
DualAir
®
units contains Coil
Frost Thermostat, Coil Pres-
sure Switch & Auxiliary Contact
on Contactor
11 Input
230 V 1st Stage of Cooling
(Free Cooling)
R2 On
Burner OFF
Fan ON from R2
Dampers Output to T16
12 Input
230 V 2nd Stage of Cooling
Cooling Coil Stage 1
R2 OFF
R3 ON
Burner OFF
Fan ON from R3
Dampers Output to T15
Output to Condenser 1 at T17
& 18
13 Input
230 V 3rd Stage of Cooling
Cooling Coil Stage 2
R3 ON R4 ON
All input 12 Operations
Output to Condenser 2 at T19
& 20
14, 15 & 16 Output
230 V Output for Optional
Damper
From R2
14 = Neutral
15 = Recirculated Air
16 = Fresh Air
17 & 18
Volt Free Control Circuit
Condenser 1
R3 ON Normally Open Contact
for Condenser 1
19 & 20
Volt Free Control Circuit
Condenser 2
R3 ON R4 ON
Normally Open Contact
for Condenser 2
21 & 22 Output
230 V Output to
Remote Dirty Filter Warning
21 = L
22 = N
23 & 24
Volt Free Output to
Remote Dirty Filter Warning
Alternative Dirty Filter Indica­tion for BMS or DualAir
®
Con-
trol
Normally Open Contact
for Dirty Filter Indication
25 & 26 Input
0 - 10 V DC Input for
Modulating Burner
T3 Must Be Live to Operate
Burner
0 V = Minimum Fire
10 V = Maximum Fire
Page 24
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
18
10.4 DAT Wiring Diagram Models 75-115
S 4563 C Honeywell
L
N
E
COMBUSTION FAN
PRESSURE SWITCH
BLUE
Secondary Limit
Thermostat N/C
PINK
GREY
PURPLE
RESET
PUSH
LOCKOUT
RUN
GREEN/YELLOW
BLACK
WHITE
YELLOW
GREEN/YELLOW
BROWN
BLUE
BROWN
BLUE
MAINS FILTER
BLACK
SENSE
IGNITION
BLACK
BROWN
BLUE
LIMIT
FAN
BROWN
BROWN
SITE WIRING
N L 1 2 3 7 8
RED
RED
Grey
Pink
Red
Black
White
Brown
Blue
NC\P(2)
Pressure Switch
Detail
NO\P(3)
C \P(1)
BLACK
YELLOW
WHITE
Yellow
Continued on Next Page
NOTE:
For external fan wiring, See Page 20, Section 10.6.
If any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C and 600 volts.
Page 25
SECTION 10: WIRING AND ELECTRICAL INFORMATION
19
10.5 DAT Wiring Diagram Models 75-115
7
R1 230 V
motor
fan
main
R1/1
Condensor control circuit
limit devices
9
Aux contact
A2
overload &
Fuse 5A
2
4
6
96
95
contactor
14 13
2
4
1
3
6
5
A1
Relay
1
Remote fan controls 230 V
This appliance
must be Earthed
10
N
400 V 50 Hz 3 N Suppy
L1
L2
L3
Heating Stage 230 V
230 V output to controls
2
3
Heat ON 230 V
4
5
Heat ON (Green)
Lockout (Red)
Dirty filter warning (Amber)
1
Coil
3 1 3
ON
Burner
Coil Safety
Filter pressure Sw
3
2
Green
Pressure Switch
Filter
Limit
Heat On
Neutral
Common
Red
Reset
Lock Out
4
R2/1
R2 230 V
7
2
7
2
R3/1
4
10
1
2
1
3
9
R3/3
1
11
3
Damper supply 230 V
Remote Lockout reset 230 V
8
N
N
1st stage cool (free cool)
11
12
13
14
Dirty filter warning 230 V
Recirc' air
Fresh air
cooling condenser
17
16
15
18
19
22
21
20
Honeywell Modureg Valve 0-28 V DC
Burner Modulation control
0 - 10 V DC signal
System ground
+
282726
25
Control inputs 230 V
Press
Sw
Coil
Frost
Stat
Warning lamps (230 V)
Heater Supply
Orange
Brown-white
Red-white
White
Black
Brown
Blue
Violet
Yellow
Pink
Grey
2
24
23
2
R5 230 V
7
R5/1
3
1
Grey
Blue
H7
H8
Pink
Lock Out
TH
H3
H1
Red
Violet
N
L
R2/2
R3/2
Lockout 230 V
R3 230 V
R4 230 V
R4/1
2nd stage cool 3rd stage cool
1st stage
2nd stage
cooling condenser
Site wiring connections shown
Volt free dirty filter signal
Grey
Black
White
Brown
Blue
Yellow
Red
Page 26
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
20
10.6 DAT Site Connections at Main Circuit Board
9
10
1
L1
N
L3
L2
3
2
4
5
7
8
11
12
13
14
15
16
17
18
19
20
21
22
27
25
26
28
23
24
cooling condenser
Lockout Warning 230 V
Remote Lockout Reset
Heat ON
MUST be
This appliance
3 N Suppy
400 V 50 Hz
Earthed
Indication 230 V
1st stage cooling condenser
Damper Supply
Recirc' air
N
Fresh air
2nd stage
Dirty Filter Warning 230 V
System Ground
+
Optional Frost Thermostat 230 V
Time Switch Control 230 V
Optional External Fan Control 230 V
N
L
N
+
-
Screen
-
Volt Free Dirty Filter Warning
Volt Free Condenser Control Circuit Safety Devices
Heating Stage for ON/OFF and Burner Modulation
MultiStage Temperature Control (or similar)
Cooling Stage 1 (free cooling when fresh air is connected and dampers fitted)
Cooling Stage 2 (1st stage cooling coil)
Cooling Stage 3 (2nd stage cooling coil)
Burner Modulating Signal
0 - 10 DC 0 V = Minimum Fire
Screened Cable Belden 8451 (or equivalent) Earthed at one end
Volt Free Condenser Control Circuits
Page 27
SECTION 11: COMMISSIONING
21
SECTION 11: COMMISSIONING Gas Fired Heater
Installation, service, commissioning and annual inspection of the heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Read this manual carefully before installation, commissioning, operation, or service of this equipment. All components are accessed via the hinged door. Opening the door exposes live electrical connections and hot components.
Cooling Coils/Condensers
Installation, service, commissioning and annual inspection of the cooling equipment must be done by a contractor qualified in the installation and service of refrigeration equipment. Read condenser manufacturers manual carefully before installation, commissioning, operation, or service of this equipment.
11.1 Pre Commission Checks All pre commission checks must be carried out
before lighting the heater.
Ensure that the heater and all controls are suitable for the gas, pressure and electrical supply to which they are to be connected.
11.1.1 Louvers
Where fitted, the air delivery louvers need to be set during commissioning to give the required air distribution.
11.1.2 Electrical Checks
1. Check that all site wiring is connected in accordance with the appropriate wiring dia­grams on Page 17, Section 10.3 through Page 20, Section 10.6.
2. Check the correct fuse size is fitted; See Page 16, Section 10.1.
11.2 Gas Supply
All aspects of the gas installation including the gas meter must be inspected, tested for soundness and purged in accordance with local and national codes.
11.3 Mechanical Checks
1. Check that the fan is free to run and that the fan rotates in the correct direction. To reverse rota­tion transpose two of the incoming phase con­nections.
2. Check that the flue and air intake are installed in accordance with these instructions and local regulations.
3. Check that the settings of the Combination Fan/ Limit thermostat are correct - See Page 7, Sec- tion 4.3 and Page 8, Figure 4.4.
NOTE: The second limit thermostat is preset and sealed at the factory and is not adjustable.
11.4 Begin Commissioning
11.4.1 Before Operating the Heater
To ensure that all the controls are in safe working order, operate the heater for the first time with the isolating gas valve turned off.
1. Turn off the isolating gas valve
2. Using the installed external control, turn on the burner. The automatic sequence will now begin as described on Page 22, Figure 12.
There will be no ignition of the burner and lockout will occur, proving the controls are operating correctly.
WARNING
Electrical Shock Hazard
Use extreme caution while commissioning.
Failure to follow these instructions can result in death or electrical shock.
WARNING
Cut Hazard
Turn off gas and electrical supply before maintenance.
Fan can start automatically at any time.
Failure to follow these instructions can result in severe injury or product damage.
Page 28
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
22
Figure 12: Automatic Burner Control Box Sequence
Figure 13: Modureg Gas Valve
Burner sequence for Honeywell S4563 or S4565C
Flame Signal
Start Gas Valve
Ignition Spark
Supply 230v
CLOSE DOWNRUNSTART
ts
Signals Output By Control
Required Incoming Signals
Flue Fan
Pressure Switch
P
C
NO
NC
30 Sec. Purge*
*Purge time begins at pressure switch change over. ts=Safety time S4563C 3 seconds (alternate 5 seconds) S4565C 5 seconds
If at any stage the flame fails, the control will go to "lockout". The red light will illuminate and the control must be manually reset before further start attempt.
Inlet Pressure
Gas Outlet
Outlet Pressure
Plug for
Main Gas Valve
Gas Inlet
Plug for
Main Gas Valve
Max Pressure Adjustment
Min Pressure Adjustment
6.3mm AMP
Terminals for
Modulation
Modureg Modulating Regulator
Honeywell Gas Valve
Moving Shaft
Page 29
SECTION 11: COMMISSIONING
23
11.4.2 Commissioning the Gas Valves
All DualAir
®
units are fitted with fully modulating burner operation. The Honeywell automatic gas valves are fitted with the Honeywell Modureg modulating regulator. See Page 22, Figure 13.
The Modureg device provides the adjustments for maximum and minimum firing and is set using the two adjustments. See Page 22, Figure 13.
The external control will operate the burner between these two limits depending on heat demand.
The minimum set point must not be set lower than the minimum burner pressure stated on Page 6, Section 4.2.
11.4.3 Commissioning the Gas Valve
There are two stages to commissioning the modulation equipment.
The minimum pressure setting must be adjusted first, any adjustment of the minimum pressure setting will affect the maximum pressure setting.
For ON/OFF non-modulating operation set the minimum firing rate to be the maximum burner pressure as on Page 6, Section 4.2
11.4.3.1 Set Minimum Pressure
1. Disconnect the leads from the coil of the Modureg regulator.
2. Connect a suitable manometer to the burner pressure test point of the main gas valve.
3. Turn on any external controls and allow the burner to fire for at least five minutes.
4. Remove cap and using a suitable 9mm span­ner adjust the burner minimum set pressure to the value shown on Page 6, Section 4.2.
11.4.3.2 Set Maximum Pressure (Not Required for ON/OFF burners)
1. Press in the moving shaft of the Modureg valve and hold in this position while adjusting the burner maximum pressure to the value shown on Page 6, Section 4.2. For adjustments See Page 22, Figure 13. NOTE: If the correct burner pressure cannot be reached, then check the inlet pressure to the valve, with the burner firing. See Page 6, Sec- tion 4.2 for inlet pressure requirements.
Do not continue to adjust the regulator if the pressure is not changing.
If the inlet pressure is too low to allow a correct burner pressure setting, then the gas inlet pres­sure must be corrected before completing the commission.
2. Release the moving shaft and observe that the burner pressure returns to the minimum setting.
3. Turn off the external controls and reconnect the electrical leads to the Modureg regulator.
4. Turn on the external controls and allow the burner to fire once again observing the burner pressure.
5. Using the temperature set point device of the installed control system, set for maximum burner firing and observe that the burner pres­sure slowly rises to the maximum as set.
6. Reset the temperature set point by small steps until the burner pressure slowly drops to the minimum pressure set. Repeat Step 5 and observe that the maximum set point is again achieved.
Check Gas Rate
1. After burner pressure adjustment, allow the heater to operate for at least 15 minutes and then re-check settings.
2. Remove the manometer and refit all covers to the valve and tighten the screw of the outlet pressure tap.
3. Check gas flow rate at gas meter.
11.5 Combustion Testing (all models)
The only adjustment to alter combustion performance is burner pressure. Combustion quality must be tested to prove correct heater operation. Incorrect results will indicate faults with the installation or appliance.
Combustion testing must be carried out at full fire with all covers in place. The flue gas is sampled in the flue, within 1 meter of the heater. The values of CO
2
should be between 6.5% to 8.0% for natural gas and 7.0% to 9.1% for LPG dependant upon model.
The CO will be up to 80 ppm (0.008%) dry, air free dependant upon model. Temperature rise of the flue gases above ambient should be approximately 160° C to 180° C. Seal test hole in flue after testing.
Following the above operate the heater for 30 minutes at the minimum firing rate. Following this time the temperature of the products of combustion in the flue should be measured. If the flue products temperature is below 80° C then the minimum firing rate should be increased. Continuous operation of the burner with flue gas temperature of below 80° C will cause condensation to form in the heat exchanger and flue system. This will cause nuisance water collection and a shortened heat exchanger life.
Page 30
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
24
Pressure Switch
The pressure switch is factory pre-set for each model and is not adjustable.
11.6 Turning Off the DualAir
®
Unit
Set the external controls to the off position and the main burner will stop.
The fans will run until they are stopped automatically by the fan thermostat.
Do not use Electrical Isolator for control of heater. Electrical Isolator will switch off the fan. Heat exchanger could be damaged. Warranty will not cover damage to the heat exchanger if operated improperly.
11.7 External Controls
External Controls may include time switch, room thermostat and frost thermostat. Operate each control to ensure that they function correctly. Set the time switch (if fitted) and room thermostat to the users’ requirements. Operate the external controls and ensure that the installed cooling stages operate correctly as described on Page 17, Section 10.3.
11.8 Complete the Commissioning
Ensure that all covers are fitted correctly and all test points are properly sealed.
11.9 Instruction to the User
Explain the controls of the DualAir
®
unit to the user including how to turn it on and off, using the controls fitted on site.
Give this manual to the user. Ensure that the user is shown and understands the
importance of maintaining clearances to combustibles and the user instructions on Page 25, Section 12 through Page 26, Section 12.6 and all warnings defined in this manual.
Page 31
SECTION 12: USER INSTRUCTIONS
25
SECTION 12: USER INSTRUCTIONS
12.1 User Instructions
The DualAir
®
units are fully automatic and operate
from the external controls fitted on site. The only user controls at the heater are the: Burner lockout
reset button ................See Page 26, Section 12.3.3
Limit thermostat
reset...........................See Page 25, Section 12.3.1
Second limit thermostat
reset button ..............See Page 25, Section 12.3.2
12.2 Heater Operation
When the heater has been switched on by the remote controls installed, the main burner will automatically turn on. The burner control box will control the ignition of the flame. All heaters require a constant gas and electricity supply which must not be interrupted during the normal operation of this heater.
12.2.1 Warning Lights
The DualAir
®
unit has three warning lights; GREEN = Heater ON, burner attempting to fire RED = Burner LOCKOUT, see Section 12.3.3. AMBER = Dirty Filter, replace filter, air flow is dropping to an unacceptably low value.
Figure 14: Heater Operating Sequence
12.3 Common User Controls (all models)
12.3.1 Combination Fan/Limit Thermostat
The Combination Fan/Limit Thermostat is located inside the access door at the top of the heater. See Page 37, Section 16.3.
This control ensures the heater does not blow cold air in the normal heating cycle and protects the heat exchanger against overheating.
Figure 15: Fan/Limit Thermostat
12.3.2 Secondary Limit Thermostat
WARNING
Electrical Shock Hazard
Disconnect electrical power before servicing.
Failure to follow these instructions can result in death or electrical shock.
ON
RUN ON
CLOSE DOWN
THERMOSTAT
CALL FOR
HEAT
BURNER
RUN
FAN
ON
ON
White fan button
Pull out for normal operation.
Press in for constant fan.
Red limit reset button
(Press to reset)
The combination fan/limit thermostat is preset during commissioning.
See Page 7, Section 4.3 and Page 8, Figure 4.4. NOTE: To reset, the heat exchanger must be cool.
If the air flow is reduced due to power failure the limit thermostat will cause the burner to lockout.
Description Part Number
Combination Fan/Limit Thermostat K017A
Press to reset
These are hand reset devices to give further protection against fan failure.
NOTE: To reset, the heat exchanger must be cool.
Description Part Number
CTUA 40 & 50; CTUB 50 & 60 90412101 All Other Models 90412100
WARNING
Explosion Hazard
If control locks out, do not make more than 3 attempts to restart the heater.
Dangerous gas mixtures can build up.
The fault must be traced and repaired by a registered installer or service engineer.
Failure to follow these instructions can result in death, injury or property damage.
Page 32
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
26
12.3.3 Burner Lockout Reset Button
The red warning light will illuminate when the control has gone to lockout. This may be caused by flame failure. Press the reset button,(See Page 5, Section
4.1), or the remote reset if installed on site.
12.4 Cooling Section Operation
The temperature control will bring on the fan to operate the DualAir
®
unit in cooling mode dependant on the current temperature and set point. Once the temperature rises above the set point there are three stages of cooling available dependant on site installation.
Cooling Stage 1 (optional free cooling). The fan runs and change over dampers (if fitted) allow fresh air to be drawn from outside.
If the temperature continues to rise then Cooling Stage 2 operates. The fan runs, the dampers (if fitted) return to recirculating air and the first condenser operates to provide cooling at half load. Should the temperature continue to rise, Cooling Stage 3 operates. The fan runs, the dampers (if fitted) remain in recirculating air and the second condenser operates to provide cooling at full load.
12.4.1 Filters
Air cleaning filters are fitted to the DualAir
®
unit to protect the cooling coil and provide improved environmental conditions.
The filters will require to be replaced at least three time per year and in dirty environments cleaning of the filters may be required at more frequent intervals.
When the filters are dirty the warning light will show see Page 25, Section 12.2.1. The filters must be cleaned or replaced immediately.
Do not operate the DualAir
®
unit without filters as the cooling coil may become blocked and impossible to clean.
12.5 Heating Section Lighting Instructions
12.5.1 To Turn On Heater
1. Ensure that the electrical and gas supplies to the heater are on. Check that the on site con­trols are “ON”.
NOTE: The thermostat setting must be above the ambient temperature for the heater to operate.
2. The green light will be on and the automatic fir­ing sequence will begin as described on Page 22, Figure 12. The heater will now operate automatically under the control of the on site controls. Following long shut down periods, the control may go to lockout. See Page 26, Sec- tion 12.3.3.
12.5.2 To Turn the Heater Off
Set the installed remote controls to “OFF”. The burner will turn off immediately.
The fan will continue to run for a few minutes. To restart turn the control used above to “ON”.
12.6 Simple Fault Finding (all models)
Possible reasons for the heater not operating are:
1. Gas supply not turned ON.
2. Electricity supply not turned ON.
3. The time and/or temperature controls are not “ON”.
4. One or both of the Limit Thermostats may have operated. This may be caused by an interrup­tion of the electrical supply or failure of the distribution fan.
If the Limit Thermostats persistently operate, there is a fault which must be investigated by a contractor qualified in the installation and service of gas-fired heating equipment.
12.6.1 Simple Fault Finding (burner faults)
If the burner fails to ignite for any reason, it will go to lockout. This will be indicated by the red light on the heater or at the remote indicator (if fitted).
1. Press in and release the lockout reset button. If a remote reset is not fitted a reset button is on the side panel of the heater. See Page 5, Sec- tion 4.1.
WARNING
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Leave the building.
6. Immediately call your local gas supplier after leaving the building. Follow the gas suppliers instructions.
7. If you cannot reach your gas supplier, call the Fire Department.
Fire Hazard
Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appliance.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
Page 33
SECTION 13: SERVICING
27
SECTION 13: SERVICING
13.1 Servicing Instructions
After commissioning, the DualAir
®
unit will require maintenance to be carried out annually. If the DualAir
®
unit is used in a dirty or dusty area, more
frequent maintenance may be necessary.
Installation, Service and Annual Inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment.
NOTE 1: After any maintenance or repair work always test fire the heater in accordance with the commissioning instructions on Page 21, Section 11 through Page 24, Section 11.9 to ensure all safety systems are in working order before leaving the heater to operate. Minor faults may be traced by using the troubleshooting charts on Page 30, Section 15 through Page 33, Section 15.5.
NOTE 2: Check all gas pipes and pipe joints to ensure there are no cracks or gas leaks.
NOTE 3: Inspect all suspended components and hardware. Insure that they are in good condition, properly tightened, and corrosion free.
13.1.1 Cooling Equipment
The cooling coil does not require maintenance except that during filter replacement it is recommended to clean the surface of the coil with a soft brush and vacuum cleaner. Carry out any maintenance recommended by the condenser manufacturer.
13.1.2 Filters
The air filters should be inspected regularly to ensure that no excessive build up of deposit is being experienced. If heavy deposit is being formed, then the filters may be cleaned using a vacuum cleaner. Filters should be replaced at least every four months to ensure that adequate air flow.
The cooling equipment will automatically turn off should the air flow drop to a preset low value even though the fan will still run. The maximum resistance across a dirty filter should be no more than 150 Pa (1.5 mbar) and the dirty filter warning light will be on. A resistance higher than this indicates that the filters must be replaced.
13.2 Burner Maintenance
1. Open the hinged door and remove the burner compartment cover. See Page 36, Section
16.2.
2. Clean any deposits from the main burner which may have formed in the injectors or venturi of the burner. See Page 36, Section 16.2.
3. Remove the ignition electrode and flame probe. Check condition of ignition electrode and flame probe. Clean off any deposits which may have been formed, check condition of ceramic insulators. Replace as necessary.
13.3 Fan/Motor Assembly Maintenance
The main fan bearings are permanently sealed and do not need lubrication. Before cleaning, turn off gas and electrical supply. Remove the fan compartment covers and use a small brush or duster to clean the fan blades from each side. Replace fan(s) when done.
Figure 16: Belt Tension
Check the condition and tension of the drive belts. The condition is best inspected with the belts removed. Check for chaffing or lateral cracks. Replace belts as a matched pair as necessary. Do not over-tighten belts, as this may cause bearing damage.
13.4 Heat Exchanger Maintenance
The heat exchanger will remain clean unless a problem has developed with combustion. Inspect the heat exchanger. Look for signs of overheating at the front tubes which may indicate burner over firing or persistently low air flows.
WARNING
Cut Hazard
Turn off gas and electrical supply before maintenance.
Fan can start automatically at any time.
Failure to follow these instructions can result in severe injury or product damage.
Motor
Pulley
Fan
Pulley
8 mm to 10 mm
Page 34
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
28
13.5 Gas Control Valve Maintenance (all models)
No regular maintenance is required on these devices. To change gas control valves, See Page 35, Step 16.1 and Page 39, Section 16.5.
Do not repair or disassemble on site. Replace faulty gas valves with genuine
ROBERTS GORDON
®
replacement parts.
13.6 Flue Fan
The flue fan should not require maintenance. However, If the air pressure switch is causing burner lockout then remove the flue fan from the vent box. See Page 38, Section 16.4. Ensure that the fan is free to run and that the fan wheel is clean.
Page 35
SECTION 14: CONVERSION BETWEEN GASES
29
SECTION 14: CONVERSION BETWEEN GASES
14.1 General
Conversion between gasses will require a change of burner injectors and the gas valve re-commissioning to the new conditions.
14.2 Burner Conversion
Conversion of the burner assembly from one gas to the other is the same for all types of heaters.
1. Remove the burner compartment cover as shown on Page 36, Section 16.2.
2. Remove the connection between the gas valve outlet and the manifold. See Page 35, Section
16.1 for gas valve removal.
3. Remove the manifold from the burner assembly by removing the screws at the top and bottom. See Page 36, Section 16.2.1.
4. Remove the main burner injectors.
5. Replace with the injectors for the new gas ensuring a gas tight seal.
6. Refit all components in reverse order.
14.3 Gas Valves
All gas valves used on the DualAir
®
units have pressure regulators that may be set to operate on Natural gas or LPG.
Conversion is carried out by re-setting the burner pressure to the value in the data table during commissioning. See Page 7, Section 4.3.
Ensure that the gas inlet pressure to the heater is correct for the new gas, and that the gas supply has been purged of the old gas.
Page 36
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
30
SECTION 15: TROUBLESHOOTING
15.1 General
WARNING
Explosion Hazard
Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Failure to follow these instructions can result in death, injury or property damage.
If problems persist, contact
ROBERTS GORDON
®
at
Tel: +44 (0)1902 498733
or www.rg-inc.com
Heater Operating
TROUBLESHOOT ENDS.
No
Adjust or replace
as necessary.
Is combination fan/limit
thermostat set correctly?
See sections 5.3 &11.3.
No
Use 15.2 to test burner.
Replace combination
fan/limit thermostat.
See sections 5.3 & 11.3 to
check combination
fan/limit thermostat settings.
Does the fan run?
No
Has burner Locked Out?
Yes
No
With external controls on,
does the burner continue
through the heating cycle?
No
Ye s
Press the white button on
the combination fan/limit
thermostat. Does the
fan run now?
Yes
No
Does the fan run?
No
Use 15.5 to test fan.
Ye s
Yes
Use 15.2 to test burner.
Is Red lockout
warning light on?
Yes
No
Turn on supplies.
Are gas & electrical
supplies on?
No
Ye s
Start
Ye s
For your safety and optimum heater performance use only ROBERTS GORDON® replacement parts.
Conduct Commissioning procedure as shown on Page 21, Section 11
Page 37
SECTION 15: TROUBLESHOOTING
31
15.2 Troubleshooting For Automatic Ignition Burner Systems
If problems persist, contact
ROBERTS GORDON
®
at
Tel: +44 (0) 1902 498733
or www.rg-inc.com
Heater Operating
TROUBLESHOOT ENDS.
No
Trace fault in supervision
system. See Section 16.3.
No
Ye s
Is red lockout light on?
No
Is the flame current at
least 1 µAmp DC when
the flame lights?
Ignition control faulty
replace.
See Section 15.6.
Is HT lead okay and
connected?
Is spark electrode okay?
Ye s
Replace valve.
Is the gas valve operating?
To test valve,
see Section 15.4.
No
Does the flame light?
No
Ye s
Wait 30 - 40 seconds.
Is ignition spark operating?
No
Ye s
Flue fan faulty replace
Burner control faulty or plug in connections faulty. Repair
or replace as necessary
Check for too much flue/air inlet
duct. Check for blockage in
combustion air circuit.
Check for faulty air pressure
switch. See section 16.5.
Does air pressure switch
change over?
No
Yes
Have limit thermostats
operated or light faulty?
Reset or replace as
necessary.
Is 230v supply at fan
connections?
Does flue fan run?
No
Are external controls on?
Yes
Ye s
Is the green light on?
No
Yes
Is red lockout light on?
No
Yes
Press in lockout reset button
on rear of heater or remote
reset button if fitted.
Turn on supplies.
Are gas & electrical
supplies on?
Yes
Start
No
Ye s
No
WARNING
Electrical Shock Hazard
Do not touch ignition components.
Voltage from ignition components is high.
Failure to follow these instructions can result in death or electrical shock.
There are two burner controls used. Honeywell S4563C and S4565C. They both have similar operating sequences. To measure flame current, connect a 0 - 50 μA DC meter in series with the flame probe. If the meter reads negative values, then reverse the test leads.
For your safety and optimum heater performance use only ROBERTS GORDON
®
replacement parts.
Conduct Commissioning procedure as shown
on Page 21, Section 11
Page 38
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
32
15.3 Troubleshooting for Flame Supervision System
Repair or replace as
necessary.
If problems persist, contact
ROBERTS GORDON
®
at
Tel: +44 (0) 1902 498733
www.combat.co.uk or www.rg-inc.com
Control box faulty.
Replace with correct type.
Use section 15.1 to
trace the fault.
Heater Operating
TROUBLESHOOT ENDS.
No
Repair or replace as
necessary.
Is inlet burner gas pressure
correct? Is live and neutral
polarity correct? Is
flame probe circuit correct?
Is there a current flowing in
the flame probe circuit with no
flame present?
Yes
No
Does lockout occur when
there is a flame present?
Yes
Is the connecting lead damaged? Is the flame probe damaged or touching earthed
components?
No
Is the green light on and
at least 1 µA DC fame
current?
Connect a DC ammeter in
series with the flame probe.
Yes
No
Yes
Yes
No
START
NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.
Page 39
SECTION 15: TROUBLESHOOTING
33
15.4 Troubleshooting for Solenoid Valves
15.5 Troubleshooting for Main Fan
Valve faulty.
Replace with one of
correct type.
Fault elsewhere
Fault elsewhere
If problems persist, contact
ROBERTS GORDON
®
at
Tel: +44 (0) 1902 498733
or www.rg-inc.com
Valve Operating
TROUBLESHOOT ENDS.
No
Ye s
Valve faulty.
Replace with one of
correct type.
Does gas pressure at
outlet of valve return to zero or
lower when valve turns off?
No
Yes
Does gas pressure at outlet
of the valve rise when
valve turns on?
No
Ye s
Is gas pressure at inlet of the
valve correct for gas type?
Note pressure found.
No
Yes
START
Is 230v at the valve
terminals at the
appropriate time.
Yes
No
If problems persist, contact
ROBERTS GORDON
®
at
Tel: +44 (0) 1902 498733
or www.rg-inc.com
Fan Operating
TROUBLESHOOT ENDS.
No
Fan motor or contactor faulty.
Replace with correct type.
Use Section 15.6 to
trace fault.
Combination fan/limit
thermostat faulty.
Replace with correct type.
Is there 230v between
terminals 1 and N of the
main terminal block?
Does fan run when the white
button of combination fan/limit
thermostat is pushed in?
Use Section 5.3 & 11.3 to
check combination fan/limit
thermostat settings. Reset or
replace as necessary.
Fault elsewhere.
Check wiring.
Is Power supply 400 V
between any two phases or
230 V between any Phase and
N at the main terminal block?
No
Yes
Ye s
START
No
No
Yes
Does fan turn on and
off while burner is firing
continously?
No
Yes
Does fan run
automatically?
No
Yes
For your safety and optimum heater performance use only ROBERTS GORDON® replacement parts.
Conduct Commissioning procedure as shown on Page 21, Section 11
Page 40
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
34
15.6 Troubleshooting for Fan Contactor
Replace
combination thermostat.
Wiring faulty or faulty
combination thermostat.
Investigate.
If problems persist, contact
ROBERTS GORDON
®
at
Tel: +44 (0) 1902 498733
or www.rg-inc.com
Relay R3 faulty.
Replace.
Does fan run at cooling
stage 2 (T12 live)?
No
Does fan run at cooling
stage 1 (T11 live)?
Ye s
No
No
Ye s
Replace or tighten belts.
Transpose two incoming
phase connections.
Is fan/motor rotation
correct?
No
Overload Faulty
Replace.
Are fan belts
loose or broken?
Ye s
No
No
Ye s
Has fuse 1 on the
printed circuit board
blown?
No
Ye s
No
Ye s
Press in overload reset
button and retest.
Fan Operating
TROUBLESHOOT ENDS.
No
Does fan run when white
button of combination
thermostat is pushed in?
Fault elsewhere
Is power supply 400v at
three phase and N at the
main terminal?
No
Yes
START
No No
Yes
Does main fan run
automatically
in heating mode?
No
Is there 230v at contactor
coil terminal A1 and A2?
Does fan motor run with
little or no air flow?
Yes
Yes
No
Is there 230v between
terminals 96 and A1 on
the contactor?
Contactor faulty.
Replace.
Replace fuse and
investigate.
Ye s
Overload operated. Check for
three phases at mains
terminals, loose electrical
terminals and motor overload.
Check filters and
ducting for blockage.
Does fan run
as burner fires?
No
Ye s
Relay R1 faulty.
Replace.
Ye s
Does main fan run
automatically
in cooling mode?
Relay R2 faulty.
Replace.
Ye s
For your safety and optimum heater performance use only ROBERTS GORDON® replacement parts.
Conduct Commissionin
g p
rocedure as on Page 21, Section 11
Page 41
SECTION 16: REMOVAL AND REPLACEMENT PARTS
35
SECTION 16: REMOVAL AND REPLACEMENT PARTS
See warnings and notes on Page 27, Section 13 before removing or replacing parts.
Burner Components
All serviceable burner parts are accessed by the door on the side of the heater. See Page 5, Section 4.
16.1 Gas Valve
The VR4605 gas valve is fitted with the V7335A modureg regulator (P/N L512) supplied as a separate component.
When replacing the gas valve the modureg will need to be fitted on site. To fit the modureg, remove the standard regulator by removing the two screws retaining the rubber sealing washer. See Page 35,
Figure 17
Figure 17: Standard Regulator Removal
Fit the modureg ensuring that the rubber seal is in place and the two screws are tight. See Page 35, Section 16.1.1. Once fitted follow commissioning procedure in Section 11.
16.1.1 Gas Valve Replacement - (all models)
16.1.2 Gas Valve Replacement continued- (all models)
Replace in reverse order. Verify that the gas flow direction of the valve is correct. Re-use the "O" ring seal in the outlet flange where fitted. Check that all the joints are leak free. Reset gas valve. See Page 23, Section 11.4.2.
IT IS IMPORTANT THAT ONLY THE CORRECT GAS VALVES SPECIFIED FOR EACH MODEL
TYPE ARE USED WHEN REPLACING THESE CONTROLS.
Remove Standard
Regulator
Sealing Washer
Step 1 Unscrew gas pipe from the
valve inlet.
Step 2
Unscrew valve from the
burner manifold
or
unscrew the screws for
the inlet and outlet flanges.
Ignition Control
Rubber
Seal
Modureg Modulating
Regulator
Description Part Number
Gas Valve VR4605 90033404 Ignition Control 90434020
Page 42
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
36
16.2 Burner Compartment
16.2.1 Burner Injectors
Remove flexible
air duct from spigot
Remove
access plate
Remove screws and
pull off burner cover
Viewing port
for flame probe
Viewing port
for ignition electrode
Flame probe
Burner
compartment
cover
Rubber Seal
Ignition electrode
The burner compartment is a sealed compartment. Following any work, re-seal the compartment with the gas pipe rubber seal fully in place and all screws fitted and tight.
Remove manifold
screws and pull
out manifold
Manifold
Burners
Injectors
Burner
screws
Burner venturi
Unscrew
Injectors
Manifold
Marking
Ensure gas tight fitting of injectors. Ensure correct alignment with burners. Ensure all pipe joints are gas tight.
75 90 100 115
12 14 15 17
mm dia 2.71 2.71 2.71 2.71
in dia 0.1067 0.1067 0.1067 0.1067
36 36 36 36
91930036 91930036 91930036 91930036
mm dia 1.51 1.51 1.51 1.51
in dia 0.0594 0.0594 0.0594 0.0594
53 53 53 53
91930053 91930053 91930053 91930053
Marking RG P/N
Injector Size
Injector Quantity
LPG Gas Propane (G31) and LPG Gas Butane (G30)
MODEL
Injector Size
Marking RG P/N
Natural Gas (G20) and (G25)
Page 43
SECTION 16: REMOVAL AND REPLACEMENT PARTS
37
16.3 Ignition Electrode and Flame Probe.
Flame
Probe
Ignition
Electrode
Remove
Screw
Ignition
Electrode
Burners
Flame Probe
Burners
Burner Compartment
Front Views
Remove all
burner compartment
screws to remove
the burner
compartment and
access the
Front View.
Fan/Limit Thermostat
Secondary
Limit
Thermostat
(3 mm)
.120"
spark
gap
Description Part Number
Spark Electrode 90427411 Automatic Ignition Flame Probe 90439300 Burners (all models) 92000000
To replace the Ignition Electrode or Flame probe, remove the electrical lead and screw. Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the Front View of the Burner Compartment.
Page 44
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
38
16.4 Flue Fan
IT IS IMPORTANT THAT ONLY THE CORRECT FLUE FAN SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS.
Carry out a commission after working on or changing a flue fan. See Page 25, Section 12.
Vent Box
Outlet Gasket
Flue Fan
Vent Box
screws
Flue
Adapter
Flue Adapter
to Flue Fan
screws
Rear Panel
Hole
Disconnect
electrical connections
at plug in tabs.
Mounting Plate
to Vent Box
screws
Mounting
Plate
Gasket
Air Plate
Mounting Plate
to Flue Fan
screws
Vent Box
Gasket
Remove screws securing outlet flange to the flue adapter.
Remove screws securing flue fan mounting plate to vent box Remove screws securing mounting plate to fan. Refit in reverse. Use new gaskets. Ensure sealed joints. Ensure mounting plate orifice is clear and not obstructed.
MODEL 75 90 100 115
Flue Fan
AO Smith
JFIG07INS
AO Smith
JFIG07INS
AO Smith
JFIG07INS
Torin DSF
146-052
077274
RG P/N
90710001 90710001 90710001 90710450 Air mm dia 97.0 103.6 110.5 152.4 Plate in dia 3.82 4.08 4.35 6 RG P/N 11011134 11011133 11011132 11011131
Page 45
SECTION 16: REMOVAL AND REPLACEMENT PARTS
39
16.5 Heater Pressure Switch
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure switch for model. The pressure switches are colour coded for each pressure setting.
Carry out a commission after working on or changing a pressure switch. See Page 21, Section 11.
Carbon Monoxide Hazard
Use correct pressure switch specified for each model.
Use of incorrect pressure switch could cause unsafe condition.
Failure to follow these instructions can result in death or serious injury.
WARNING
75 90 100 115
90439811 90439807 90439811 90439807
grey brown grey brown
Pressure Switch
RG P/N
Colour Code
Page 46
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
40
16.6 Cooling Coil Safety Devices
16.6.1 Cooling Coil Frost Thermostat
The sensing element for this device is inserted into the pocket of the cooling coil situated through the access hole in the coil cover.
The frost thermostat has two settings marked as set point with an arrow head and "diff". The control should be set at 5° C with a 1° C differential.
To replace, remove screw and pull off knob. Remove cover. Disconnect wires. Pull the sensing element out of the pocket in the coil. Replace in reverse order.
16.6.2 Pressure Switches
The coil and dirty filter pressure switches are preset and different. They are differential pressure switches measuring the pressure loss across the coil or filter.
Coil Pressure Switch
(Normally open contact) used to prove adequate air flow for safe operation of cooling coil.
Filter Pressure Switch
(Normally open contact) used to give indication of filter becoming blocked.
To replace, remove coil compartment cover. Disconnect wires noting their position. Remove the flexible tubing noting the position of the tube connection. Replace in reverse order and check operation.
Figure 18: Cooling Coil Safety Devices.
Coil Frost Thermostat
set at 5°C with 1°C diff.
Filter
White
White
Red
Red
Coil Pressure Switch
set at 0.57 mbar (.23 in wc)
Filter Pressure Switch
set at 1.17 mbar (.47 in wc)
Negative
Pressure
Positive
Pressure
Set
Point
N.O
Connections
Description Part Number
Coil Pressure Switch 90439801 Filter Pressure Switch 90439804 Coil Frost Thermostat K018
Page 47
SECTION 16: REMOVAL AND REPLACEMENT PARTS
41
16.7 Ignition Control IT IS IMPORTANT THAT ONLY THE CORRECT
IGNITION CONTROL SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS.
16.7.1 S4563C Models 75 to 115
This control is mounted at the electrical mounting plate. Pull out the 3 cable connectors.
Pull out ignition cable, ignition earth and flame probe cable noting their positions. Remove the screws. Refit in reverse. Ensure correct location of ignition and flame probe cables.
16.8 Fan Motor Removal
1. Disconnect the electrical connections at the contactor and pull the cable back to the fan motor.
2. Slacken the belt tensioning nuts and remove the drive belts.
3. Unscrew the motor mounting bolt. (motor is heavy, may need two people)
4. Remove the motor pulley by using a hexagonal key to remove the taper lock screws. Use one of these screws to fit into the centre jacking screw and tighten into this position to separate the taper lock bush and the pulley.
5. Replace in reverse order. Use a straight edge to ensure both pulleys line up. Ensure the pulley fixing screws are tight and belt tension is correct (use new belts if required). Ensure motor rotation is correct.
Locknut
(ensure tight)
Belt Tension Adjustment
Taper Lock
Screws
Jacking Screw
Position
Motor Fixing
Bolts
Pivot Bolts
(ensure tight)
(adjust both ends
the same to ensure
motor is parallel
to fan case)
Page 48
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
42
16.8.1 Fan Removal and Replacement
1. Remove motor leaving the pulley in place. See Page 41, Section 16.8.
2. Remove screws securing the fan outlet flange to the fan panel. (captive nuts)
3. Remove nuts and bolts securing the fan feet to the mounting brackets.
4. Slide the fan out. (fan is heavy, may need two people)
5. Remove the fan mounting brackets from the fan. Retain components to fit to new fan.
6. Remove the Fan pulley by using a hexagonal key to remove the taper lock screws. Use one of these screws to fit into the centre jacking screw and tighten into this position to separate the taper lock bush and the pulley.
7. Refit the components above to the new fan and refit in reverse order.
8. Check belt alignment and tension.
9. Check fan rotation is correct.
16.9 Combination Fan/Limit Thermostat
16.9.1 Removal and Replacement
1. Remove wires.
2. Remove the mounting screws.
3. Fit a new thermostat ensuring that the correct temperature setting and type are selected. See Page 7, Section 4.3 through Page 8, Figure 4.4.
4. Reconnect wires and test operation.
Mounting Rail
Fan Foot
Screws
Fan Mounting
Brackets
(re-use on new fan)
Fan Outlet Flange
Securing Screws
Fan Plate
Bracket Screws
(re-use on new fan)
Description Part Number
Torin Fan DDC 270-270 A047 Torin Fan DDC 241-241 A049
Page 49
SECTION 16: REMOVAL AND REPLACEMENT PARTS
43
Figure 19: Combination Fan/Limit Thermostat
Dial
Set Point 3 Limit Temp.
Set Point 1 Fan Off
Set Point 2 Fan On
Fan Terminals
Manual Fan Switch
(White)
BREAK-OFF LINK MUST BE REMOVED
Limit Terminals
Limit Stat
Manual
Reset Button (Red)
Push in Lock
Wire to Controlled Equipment
Push Screwdriver in and hold to release
Pull out for normal operation.
Push in for continuous fan.
WARNING
Fire Hazard
Break-off link must be removed from replacement thermostat.
Heat exchanger damage may result.
Failure to follow these instructions can result in death, injury, property damage or product damage.
Page 50
Page 51
Page 52
www.rg-inc.com Printed in the U.S.A.
Attach this information to the wall near the ROBERTS GORDON® heater
Installation Code and Annual Inspections: All installations of ROBERTS GORDON® products must be performed by a contractor qualified in the installation and service of gas-fired heating equipment
and conform to all requirements of all applicable governmental authorities pertaining to the installation and operation of the equipment.
For optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON® products and perform service where necessary, using only ROBERTS GORDON
®
replacement parts.
© 2005 ROBERTS GORDON
®
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical,
including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon.
Read the installation, Commissioning, Operation and Service Manual thoroughly before installation, operation or service.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting (above ambient temperature). The automatic starting sequence begins. NOTE: Following long shutdown periods, the burner control may go to to 'LOCKOUT' during the start sequence. Push the reset button to recommence firing. Contact service department if 'LOCKOUT' continues (see manual for details).
1. Turn the thermostat/time switch to 'OFF'. The burner will turn 'OFF' immediately, but fans will continue to cool heat exchanger until the fan thermostat switches off.
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your registered installer/contractor qualified in the installation and service of gas-fired heating equipment.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
Fire Hazard
Some objects can catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
TO TURN OFF THE HEATER
Service Telephone: +44(0) 1902 498733 Service Fax: +44(0) 1902 401464 E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
WARNING
Roberts-Gordon, LLC
1250 William Street P.O. Box 44 Buffalo, NY 14240-0044 USA
Roberts-Gordon Europe Limited
Oxford Street Bilston, West Midlands WV14 7EG UK Telephone: +44(0) 1902 494425 Fax: +44(0) 1902 403200
®
Clearances to Combustibles
**80 cm is necessary to service heater.
50 cm
50 cm**
30 cm
15 cm
Alternative
Wall
Terminal
Roof Terminal
Air
Intake
Flue
15 cm
2.5 - 3.5 m*
3 m
60 cm
Installation Clearances
Customers
Suitable
Condenser
Unit
Insulated
Refrigerant pipes
to cooling coil
by Customer
Condense Drain
Install to
suitable drain
Air Flow
Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
Loading...