Roberts Gorden DAT75, DAT90, DAT115, DAT100 User Manual

WARNING
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Leave the building.
6. Immediately call your local gas supplier after leaving the building. Follow the gas suppliers instructions.
7. If you cannot reach your gas supplier, call the Fire Department.
Fire Hazard
Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appliance.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
WARNING
Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the installation, operation and service manual thoroughly before installing or servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
®
DualAir
Heating and Cooling Units
Installation, Commissioning,
Operation & Service Manual
DAT75
DAT90 DAT100 DAT115
Quality in Any Language™
© Copyright 2007 Roberts-Gordon, LLC
Roberts-Gordon Europe Limited
Unit A, Kings Hill Business Park Darlaston Road, Wednesbury West Midlands WS10 7SH UK Telephone: +44 (0)121 506 7700 Fax: +44 (0)121 506 7701 Service Telephone: +44 (0)190 249 8733 Service Fax: +44(0)190 240 1464 E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
www.rg-inc.com
P/N X527 Rev C 10/07
© 2007 Roberts-Gordon, LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon, LLC.
TABLE OF CONTENTS
SECTION 1: Heater Safety...................................................... 2
SECTION 2: Installer Responsibility ..................................... 2
2.1 Clearances to Combustibles ........................................2
2.2 Corrosive Chemicals.................................................... 2
2.3 National Standards and Applicable Codes .................. 2
SECTION 3: Critical Considerations ..................................... 3
3.1 Basic Information ......................................................... 3
3.2 Location and Suspension ............................................3
3.3 Minimum Required Installation Clearances ................. 3
3.4 Clearances to Combustibles ........................................3
3.5 Ventilation .................................................................... 3
3.6 Gas Supply..................................................................3
3.7 Electrical Supply..........................................................3
3.8 Flue..............................................................................3
3.9 Coil Condense Drain....................................................3
SECTION 4: Specifications ....................................................5
4.1 DAT.............................................................................. 5
4.2 General Technical Data Table .....................................6
4.3 Technical Data Table - Heater Section.........................7
4.4 DualAir
SECTION 5: Heater Installation..............................................9
5.1 General........................................................................ 9
5.2 Handling ...................................................................... 9
5.3 Shelf Mounting and Suspension.................................. 9
SECTION 6: Flue Installation ............................................... 10
6.1 Flue Installation.......................................................... 10
6.2 Type C
6.3 Type B
6.4 Converting from Top to Side Terminations for Flue
SECTION 7: Air Supply......................................................... 13
7.1 Room Sealed Installation ........................................... 13
7.2 Open Flued Installation .............................................. 13
7.3 Building Ventilation ..................................................... 13
7.4 Isolated Equipment Rooms ........................................13
SECTION 8: Optional Heater Configurations...................... 14
8.1 Distribution Duct ........................................................ 14
SECTION 9: Gas Piping........................................................15
9.1 Connections............................................................... 15
SECTION 10: Wiring and Electrical Information................. 16
10.1 Electrical Supply ...................................................... 16
10.2 Remote Control ........................................................ 16
10.3 DAT Main Circuit Board Terminal Identification........ 17
10.4 DAT Wiring Diagram................................................. 18
10.5 DAT Wiring Diagram................................................. 19
10.6 DAT Site Connections at Main Circuit Board............20
SECTION 11: Commissioning.............................................. 21
11.1 Pre-Commission Checks .......................................... 21
11.2 Gas Supply ............................................................... 21
11.3 Mechanical Checks...................................................21
11.4 Begin Commissioning...............................................21
11.5 Combustion Testing ..................................................23
11.6 Turning Off the DualAir
11.7 External Controls ...................................................... 24
11.8 Complete the Commissioning................................... 24
11.9 Instruction to the User ..............................................24
®
Performance Data - Graph of Air Flows v
Static Pressure.............................................................8
, C32 & C62 Appliance.................................... 10
12
Appliance..................................................... 10
22
and Air Intake ............................................................ 10
®
Unit .................................... 24
SECTION 12: User Instructions............................................25
12.1 User Instructions ......................................................25
12.2 Heater Operation......................................................25
12.3 Common User Controls............................................25
12.4 Cooling Section Operation .......................................26
12.5 Heating Section Lighting Instructions.......................26
12.6 Simple Fault Finding.................................................26
SECTION 13: Servicing.........................................................28
13.1 Servicing Instructions...............................................28
13.2 Burner Maintenance.................................................28
13.3 Fan/Motor Assembly Maintenance...........................28
13.4 Heat Exchanger Maintenance ..................................28
13.5 Gas Control Valve Maintenance ...............................29
13.6 Flue Fan ...................................................................29
SECTION 14: Conversion Between Gases ..........................30
14.1 General ....................................................................30
14.2 Burner Conversion ...................................................30
14.3 Gas Valves ...............................................................30
SECTION 15: Troubleshooting .............................................31
15.1 General ....................................................................31
15.2 Troubleshooting For Automatic Ignition Burner
Systems ...................................................................32
15.3 Troubleshooting for Flame Supervision System .......33
15.4 Troubleshooting for Solenoid Valves ........................34
15.5 Troubleshooting for Main Fan ...................................34
15.6 Troubleshooting for Fan Contactor ...........................35
SECTION 16: Removal and Replacement Parts..................36
16.1 Gas Valve.................................................................36
16.2 Burner Compartment ...............................................37
16.3 Ignition Electrode and Flame Probe. ........................38
16.4 Flue Fan ...................................................................39
16.5 Heater Pressure Switch............................................40
16.6 Cooling Coil Safety Devices .....................................41
16.7 Ignition Control .........................................................42
16.8 Fan Motor Removal ..................................................42
16.9 Combination Fan/Limit Thermostat ..........................43
Printed in U.K.
TABLE OF FIGURES
Figure 1: Condense Drain.........................................................3
Figure 2: Installation Clearances and Clearances to
Combustibles .............................................................4
Figure 3: Suspension Methods .................................................9
Figure 4: Flue and Roof Detail ................................................ 10
Figure 5: Control Section & Upper Panel ................................ 11
Figure 6: Alternate .................................................................. 11
Figure 7: Vertical and Horizontal Flue Termination -
Type B Figure 8: Vertical and Horizontal Flue Termination -
Type C12 C32 & C62 Appliances ................................. 12
Figure 9: DualAir
Rooms......................................................................13
Figure 10: Ducting................................................................... 14
Figure 11: Gas Connection with Stainless Steel Flex
Figure 12: Automatic Burner Control Box Sequence...............22
Figure 13: Modureg Gas Valve................................................ 22
Figure 14: Heater Operating Sequence ..................................25
Figure 15: Fan/Limit Thermostat .............................................25
Figure 16: Belt Tension ...........................................................28
Figure 17: Standard Regulator Removal................................. 36
Figure 18: Cooling Coil Safety Devices. ..................................41
Figure 19: Combination Fan/Limit Thermostat........................44
Appliance...................................................12
22
®
Units Installed in Isolated Equipment
Connector............................................................... 15
Product Approval
ROBERTS GORDON® appliances have been tested and CE certified as complying with the essential requirements of the Gas Appliance Directive, the Low Voltage Directive, the Electromagnetic Compatibility Directive and the Machinery Directive for use on natural gas and LPG when installed, commissioned and maintained in accordance with these instructions.
These instructions refer to appliances designed to operate in the European Union. Appliances designed for other countries (Non-European Union) are available on request. This appliance must be installed in accordance with the local and national codes in force and used
only in a sufficiently ventilated space, as specified in these instructions. Before installation, check that the local gas distribution systems, nature of gas and pressure, and
adjustment of the appliance are compatible.
1
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
CAUTION
Do not use heater in an area containing corrosive chemicals.
Corrosive chemicals will damage the burner and heat exchanger parts.
Failure to follow these instructions can result in property damage.
SECTION 1: HEATER SAFETY
Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections.
Installation, service and annual inspection of the DualAir
®
unit must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment.
2.1 Clearances to Combustibles
In all situations, clearances to combustibles must be maintained. Caution must be used when running the
DualAir
®
unit near combustible materials such as wood, paper, rubber, etc. A wall tag (P/N 91040089) is on the back cover of this manual as a permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Affix the tag on a wall near the
DualAir
®
unit.
Read this manual carefully before installation, operation, or service of this equipment.
®
This DualAir
unit is designed for heating and cooling non-residential indoor spaces. Do not install in residential spaces. These instructions, the layout drawing, local codes and ordinances, and applicable standards that apply to gas piping, electrical wiring, venting, refrigerant installation, etc. must be thoroughly understood before proceeding with the installation.
SECTION 2: INSTALLER RESPONSIBILITY
• To supply and install a suitable condenser unit along with associated refrigerant circuits in accordance with the requirements of all relevant local and national codes.
• To install the DualAir
®
unit, as well as the gas and electrical supplies, in accordance with appli­cable specifications and codes. Roberts-Gordon recommends the installer contact a local building inspector, Fire Officer or insurance company for guidance.
• To use the information given in the manual together with the local and national codes to perform the installation.
• To install the DualAir
®
unit in accordance with the
clearances to combustibles of this DualAir
• To furnish all needed materials not furnished as standard equipment.
• To plan location of supports, flues and air intakes.
• To provide access for servicing.
• To provide the owner with a copy of this Installation, Commissioning, Operation and Service Manual.
• To never use the DualAir
®
unit as support for lad­der or other access equipment and never hang or suspend anything from heater.
• To ensure that there is sufficient ventilation in the area to comply with the requirements of all relevant local and national codes.
®
unit.
2.2 Corrosive Chemicals
Roberts-Gordon cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility of the installer. It is essential that the contractor, the sub-contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemical compounds characterized by the presence of halogen elements (fluorine, chlorine, bromine, etc.). These com­pounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air
supply of the burner, the lifespan of the DualAir components will be greatly reduced. Warranty will be invalid if the heater is exposed to halogenated hydrocar­bons.
®
unit
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with the latest revision of applicable standards and local and national codes. This refers also to the electric, gas, refrigerant and venting installation. Note: Additional standards for installations in public garages, aircraft hangars, etc. may be applicable.
2
SECTION 3: CRITICAL CONSIDERATIONS
100 mm min.
Install to Suitable Drain
Drain to Open Funnel
Trap must be filled with water to be effective and prevent air being drawn backwards into the drip tray.
3.1 Basic Information
The CTUD heater that forms the heating section of
®
the DualAir
unit has an automatic ignition burner and may be operated as fully modulating or ON/OFF operation.
The standard unit has the air flow from left to right when viewed from the controls side.
A special order version with the opposite air flow is available where the combustion air intake and flue will be at the front of the unit.
3.2 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position.
• May be mounted on the floor or on a shelf of non-combustible material. (See Page 5, Section 4 and Page 9, Figure 3 for support points)
• May be suspended from above (See Page 9, Figure 3), on the floor, or from wall brackets of
sufficient strength to support the DualAir
®
unit as listed in the Dimension Data Table on Page 6, Section 4.2. Drop rods must be a minimum of 12 mm diameter mild steel. Six suspension points
are located on top of the DualAir
®
unit.
• Must be installed in a manner which allows the hinged door to be fully opened to provide access to all serviceable components.
SECTION 3: CRITICAL CONSIDERATIONS
3.7 Electrical Supply
A permanent 400v 3ø 50Hz electrical supply is required at the main electrical terminals. The heater also requires suitable energy controls in accordance with Section 10.
3.8 Flue
Choose a location to allow for the proper alignment of the flue. Each DualAir
®
unit must be fitted with an individual and correctly sized sealed flue system (See Page 10, Section 6).
No other appliance may be connected to the flue. For room-sealed installation, the air intake must be
the same size sealed system and the flue/air intake must terminate at an approved concentric wall or roof terminal.
3.9 Coil Condense Drain
The cooling coil must be fitted with a suitable condense drain. The condense pipe work should be in plastic or copper piping in accordance with the latest revision of applicable standards and local and national codes.
Figure 1: Condense Drain
3.3 Minimum Required Installation Clearances
Clearances around the DualAir be as indicated on Page 4, Figure 2, Page 10, Figure 4 through Page 12, Figure 8 to ensure access for servicing, and correct operation.
3.4 Clearances to Combustibles
Clearances must be as indicated on Page 4, Figure
2. If no clearances to combustibles are indicated,
then installation clearances apply.
3.5 Ventilation
It is important to ensure that there is adequate air circulation around the DualAir
combustion, ventilation and distribution in accordance with local and national codes.
3.6 Gas Supply
It is important that the gas supply pipe is sized correctly to provide the inlet pressure as stated on the heater data plate. The gas supply pipe and electrical connections must not support any of the heater's weight.
®
unit and flue must
®
unit to supply air for
Failure to install the condense drain correctly may cause water carry over into the fan compartment, which may then escape and cause property damage.
3
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapours the required distance away from the heater.
Failure to follow these instructions can result in death, injury or property damage.
Clearances to Combustibles
Alternative
Wall
Terminal
Roof Terminal
Air
Intake
Flue
15 cm
2.5 - 3.5 m*
3 m
60 cm
Installation Clearances
Customers
Suitable
Condenser
Unit
Insulated
refrigerant pipes
to cooling coil
by customer.
Condense
Drain
Install to
suitable drain,
See Page 3,
Figure 1.
Air Flow
50 cm
50 cm**
30 cm
15 cm
If installed at low levels where individuals can come in contact with hot heat exchanger components, adequate guarding must be provided.
All distances are minimum clearance requirements for service access, air flow and safety.
Free blowing DualAir
®
units must always be installed at least 1.8 m above the floor. Ducted installations may be floor mounted. The flue pipe must have clearance from combustibles by 5 cm.
**80 cm is necessary to service heater.
* Free blowing DualAir
®
units may be mounted at a higher level if destratification fans and/or turn down nozzles are installed.
Figure 2: Installation Clearances and Clearances to Combustibles
4
SECTION 4: SPECIFICATIONS
225
Air Intake
Flue
Heater Section Fan Compartment
Electrical
Connections
(behind door)
Filter CompartmentCondense Drain
Air Outlet Spigot (35 mm flange)
Air Intake 130 mm dia
Coil Protection,
Frost Thermostat
& Pressure Switch
Alternate Flue & Air Intake Position
Cooling Coil
Air Inlet Spigot
(35 mm flange)
3010
896 225
1239
Internal
Spigot Height
1417
Flue 130 mm dia
Lockout
Reset
Green
Burner
On
Red
Lockout
Warning
Amber
Dirty Filter
Warning
734
Gas
Connection
112 7
20 mm Conduit Entry for Electrical Connections
1494
671
2070 532
1239
Internal
Spigot Height
1250 Internal Spigot Width
Alternate Flue & Air Intake Position
315
89051 399
1340
1590
Extension Cover for Refrigerant Pipe-work
538
1032
Standard Flue & Air Intake Position
Side View
Front View
Rear View
Front View (Left Version)
Rear View (Left Version)
4.1 DAT
SECTION 4: SPECIFICATIONS
5
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
Electrical load at 230v 50Hz measured by calculating from total run current of appliance.
* Do not exceed the maximum length of flue stated or heater may not operate properly.
Reduce the maximum length stated by 1 m for each 90° bend installed.
**If minimum air flow requirements are not met then temperature limit devices will shut down the heater.
Model
Designed Air Flow # with Clean Filters
m
3
/sec
Min Air Flow at Coil
m
3
/sec
Max Air Flow at Coil
m
3
/sec
Fan Unit
Fan Pulley mm PCD
Motor Pulley mm PCD
Vee Belts
Total Electrical Load kW
Motor Size kW
Full Load Current A
Run Current at Designed Air Flow # A
Start Current A
Inlet Connection in
Outlet Connection in
Condensate Connection ISO 7-R
Refrigerant
°C Dry Bulb
°C Wet Bulb
°C Dry Bulb
°C Wet Bulb
All Models
Initial Pressure Loss
mbar
Max. Recommended Pressure Loss
mbar
Weight kg
NR dB(A)
SPL dB(A)
NR dB(A)
SPL dB(A)
NR dB(A)
SPL dB(A)
68 68 73 75
5.4
1
23.0 24.0
7.0 / 7.5
57.74 71.54
2.88
1.66
3.71
2A x 112 / 2A x 118
115
3.7
2.60
5.34
75 90
2 x A 63
2A x 180 / 2A x 200
2A x 100 / 2A x 95
Fan Data
457-486 Double Inlet Belt Drive
2A x 180
2 x A 64
100
kW
Max Cooling Load Split into Two Equal
Circuits
Design Temp. ON
Design Temp. OFF
27
R407C
612 621
1 5/8 copper
638 647
65
0.4
1.5
Qty. 6 - Farr 30/30 grade 100 x 635 x 406
Filters - All Models
7/8 copper
1 3/8 copper
18.07
14.66
Electrical Data - All models need 400v 50Hz 3N supply. Single phase supply output for control circuit 230v 50Hz fused at 5 Amp. All alarm and status signals 230v 50Hz. Modulation input 0-10vDC.
Cooling Coil - DX
4.0
7.5
2.2
4.45
4.0 / 4.5
3.3
Physical Data
Noise from Cabinet at 1 m 67.5
72
13.72
13
12.3
19.4
25
Noise from Air Inlet at 1 m
77 75
Noise from Air Outlet at 1 m
81 7776
4.2 General Technical Data Table
6
4.3 Technical Data Table - Heater Section
Gas rates corrected to standard conditions 1013.25 mbar 15°C. *See Page 44, Figure 19 for detailed Combination Fan/Limit Thermostat settings.
Model
Heat Input kW
Gross Calorific Va lue
Btu/h x 1000
Heat Input kW
Net Calorific Value
Btu/h x 1000
Approximate kW
Max Heat Output
Btu/h x 1000
Min Heat Input - Low Fire kW
Gross Calorific Va lue
Btu/h x 1000
Min Heat Input - Low Fire kW
Net Calorific Value
Btu/h x 1000
kW
Btu/h x 1000
Set Point 1 Fan OFF Temp.
°C
Set Point 2 Fan ON Temp.
°C
Set Point 3 Limit Temp. °C
Secondary Limit Thermostat
°C
Max Burner Pressure mbar
m3/h
ft3/h
Min Burner Pressure - Low Fire mbar
m3/h
ft3/h
Max Burner Pressure mbar
m3/h
ft3/h
Min Burner Pressure - Low Fire mbar
m
3
/h
ft
3
/h
Max Burner Pressure mbar
m3/h
Max Gas Flow Rate
kg/h
liquid l/h
Min Burner Pressure - Low Fire mbar
m3/h
Min Gas Flow Rate
kg/h
liquid l/h
Max Burner Pressure mbar
m3/h
Max Gas Flow Rate
kg/h
liquid l/h
Min Burner Pressure - Low Fire mbar
m3/h
Min Gas Flow Rate
kg/h
liquid l/h
68.6 234
77.7 265
Min Heat Output - Low Fire
54.6 186
63.7 217
9.24
1.86
4.53
7.91
2.16
5.29
11.209.87
2.32
5.66
2.63
6.42
9.2
3.75
9.17
13.2 14.1 16.0
3.09 3.32
7.55 8.09
9.0 9.5 9.0
18.3 19.4 18.3
11.3
6.5
2.65
18.7
8.96 10.43 11.20 12.67
4.55 5.31 5.69 6.45
2.46 2.86 3.07 3.48
12.5 13.4 12.4 12.7
12.8 14.9 16.0 18.1
6.5 7.58 8.13 9.21
3.51 4.09 4.39 4.97
25.6 27.3 25.3 25.9
7.74
273.4
6.64
234.6
9.40
332.0293.2
8.30
4.9 5.04.54.6
335.1 391 419 474
9.49 11.06 11.86 13.43
279.3 316.4
10.0 9.3 9.2 10.2
6.30 7.4 7.9 9.0
3.23 2.9 3.0 3.1
319 371 398 451
9.0 10.5 11.3 12.8
45
6.6 6.0 6.2 6.3
121
457
134
115
119
90 100
289
84.7
320
93.8
379
111
413
111
256
74.9
284
83.3
334
98
365
107
406
75
239
70
265
77.7
311
91
341
100
379
293
86
324
95
227
66.5
266
78
LPG Gas Propane (G31) Data - Inlet Pressure 37 mbar (Alternative where permitted 50 mbar) Minimum 25 mbar Maximum 57.5 mbar
LPG Butane (G30) Data - Inlet Pressure 29 mbar Min 20 mbar Max 35 mbar
205
60.2
30
50 45 85
222.5 259.6
*Combination Fan/Limit Thermostat Settings
Min Gas Flow Rate
Min Gas Flow Rate
Max Gas Flow Rate
Max Gas Flow Rate
Natural Gas (G20) Data - Inlet Pressure 20 mbar Min 17 mbar Max 25 mbar
Natural Gas (G25) Data - Inlet Pressure 25 mbar Min 20 mbar Max 30 mbar
70 75
75
Appliance Category II
2H/L 3B/P
SECTION 4: SPECIFICATIONS
7
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
350
300
250
200
150
100
50
0
2.4 2.6 2.8 3.0 3.2
3.4
2.2
400
Air Flow m3/sec
95 mm motor pulley x 180 mm fan pulley 100 mm motor pulley x 200 mm fan pulley
Static Pressure Pa
350
300
250
200
150
100
50
0
3.0 3.2 3.4 3.6 3.8
4.0
2.8
400
Air Flow m3/sec 118 mm Pulley 112 mm Pulley
Static Pressure Pa
4.4 DualAir
®
Performance Data - Graph of Air Flows v Static Pressure
4.4.1 DAT75 and 90 (2.2 kW or 4 kW motor)
4.4.2 DAT100 and 115 (4 kW motor)
8
SECTION 5: HEATER INSTALLATION
WARNING
Crush Hazard
Use 12 mm steel drop rod minimum.
Failure of the supports can result in death, injury or property damage.
12 mm
Steel
Drop Rod
Nut
Washers
Nut
Locknut
Rolled Steel
Channel
Floor
Base
SECTION 5: HEATER INSTALLATION
5.1 General
®
DualAir
units are designed for installation above
2.5 m. When connected to duct delivery systems any suitable location will be acceptable.
®
For floor mounting, the DualAir
unit may stand
directly on its base.
5.2 Handling
All DualAir
®
units have steel channel sections at the base to be used to support the equipment. Three steel sections are also provided across the top of the
unit for support. The DualAir
®
unit may be
suspended from these top sections.
®
The DualAir
unit is heavy and proper handling
equipment must be used by trained engineers.
Figure 3: Suspension Methods
5.3 Shelf Mounting and Suspension
For typical suspension See Page 9, Figure 3.
9
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to the heater section.
Keep all flammable objects, liquids and vapours the required distance away from the heater section.
Failure to follow these instructions can result in death, injury or property damage.
Roof
Flue
Terminal
Metal Sleeve
Masterflash
soaker flashing
or Rain Collar.
Flue
25mm Air Gap to
Combustible Material
SECTION 6: FLUE INSTALLATION
6.1 Flue Installation Figure 4: Flue and Roof Detail
The flue must terminate outside of the building. Flues and air intakes must be fully sealed and correctly sized for the model. Flues should be assembled as detailed on Page 10, Figure 4 through Page 12, Figure 8. The joints between the flue terminal and the roof or wall must be sealed. If the flue passes through a wall or ceiling of combustible material, it must be enclosed by a sleeve of non­combustible material and be separated from the sleeve by at least a 25 mm air gap.
Flues and air intakes must be adequately supported so that the DualAir
®
unit does not
bear the weight of the pipes.
For flue termination See Page 10, Figure 4 through Page 12, Figure 8.
6.4 Converting from Top to Side Terminations for Flue and Air Intake
1. Remove the control section lower door and upper panel. See Page 11, Figure 5 through Figure 6 for details.
6.4.1 Flue Conversion
1. Remove the inner and outer flue spigots from
6.2 Type C
, C32 & C62 Appliance
12
Room Sealed. The heaters are designed to be installed as room
sealed appliances. The flue and air intake are run as separate pipes to the concentric wall or roof terminal. See Page 12, Figure 8.
6.3 Type B
The flue must terminate outside the building and be
Appliance
22
fitted with a low resistance terminal. See Page 10, Figure 4 through Page 12, Figure 7.
6.3.1 Air Intake Terminal Cover
For Type B
appliance installations, an air intake
22
terminal cover is an available option. The cover is scored flat sheet metal that must be bent into shape. See Page 12, Figure 7. Remove and retain the screws for the air inlet spigot. Use these screws to attach the cover in position over the spigot.
10
the top. Retain the spigot and internal seal.
2. Disassemble the flue back to spigot "A". See Page 11, Figure 6. Ensure all seals are still in place.
3. Fit 90° bend directly into spigot "A" pointing forwards.
4. Cut a 90 mm length from the 360 mm flue that was removed.
5. Attach this piece to the 90° bend, then attach the inner spigot that was removed.
6.4.2 Air Intake Conversion
1. Remove the flexible hose from the air intake spigot.
2. Remove the spigot from the top.
3. Move the blanking plate from the upper panel (previously removed) to the top to cover the original flue and air intake holes.
4. Refit the upper panel feeding the air intake flex­ible hose through the upper hole and aligning the flue with the lower hole.
Loading...
+ 36 hidden pages