Roberts Gorden CRV-B-12, CRV-B-12A, CRV-B-4, CRV-B-8, CRV-B-10 User Manual

...
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Leave the building.
6. Immediately call your local gas supplier after leaving the building. Follow the gas suppliers instructions.
7. If you cannot reach your gas supplier, call the Fire Department.
®
CoRayVac
Custom-Engineered,
Low-Intensity Infrared
WARNING
Fire Hazard
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
Heating Systems
Installation, Operation &
Service Manual
CRV-B-2 CRV-B-4 CRV-B-6 CRV-B-8
CRV-B-9 CRV-B-10 CRV-B-12
CRV-B-12A
WARNING
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and Service Manual thoroughly before installing or servicing this equipment.
Installation must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Quality in Any Language™
© Copyright 2006 Roberts-Gordon
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
Roberts-Gordon, LLC
1250 William Street P.O . B ox 44 Buffalo, New York 14240-0044 Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
www.rg-inc.com
P/N 127102NA Rev. F 05/06
TABLE OF CONTENTS
SECTION 1: Heater Safety...................................................... 1
1.1 Manpower Requirements .............................................1
SECTION 2: Installer Responsibility ..................................... 2
2.1 Wall Tag.......................................................................2
2.2 Corrosive Chemicals.................................................... 2
2.3 National Standards and Applicable Codes ..................2
SECTION 3: Critical Considerations......................................3
3.1 Required Clearances to Combustibles.........................3
SECTION 4: National Standards and Applicable Codes .....7
4.1 Gas Codes................................................................... 7
4.2 Aircraft Hangars ........................................................... 7
4.3 Public Garages ............................................................7
4.4 Electrical ......................................................................7
4.5 Venting.........................................................................7
4.6 High Altitude ................................................................ 7
SECTION 5: Major Components ............................................ 8
5.1 Standard Parts List .................................................... 11
SECTION 6: Design Requirements......................................13
SECTION 7: Heater Installation............................................ 15
7.1 Tube Installation ........................................................ 16
7.2 Coupling and Tube Assembly....................................16
7.3 Elbow Package Configuration..................................... 17
7.4 Reflector Installation .................................................. 18
7.5 Burner Installation...................................................... 20
SECTION 8: Optional Heater Accessories.......................... 21
8.1 Tee Installation .......................................................... 21
8.2 Reflector Joint............................................................ 21
8.3 Reflector Side Extension............................................23
8.4 Universal Shield.........................................................24
8.5 Barrier Shield............................................................. 24
8.6 Two-Foot Decorative Grille Installation....................... 25
8.7 One-Foot Decorative Grille Installation......................26
8.8 Protective Grille Installation........................................ 29
8.9 Classic Cast-Iron Components.................................30
SECTION 9: Pump Installation and Venting ....................... 31
9.1 Pump Installation .......................................................31
9.2 General Venting Requirements Model EP-100,
EP-200 and EP-300 Series Pumps............................ 32
9.3 Horizontal Venting 4" (10 cm) Pipe ............................ 34
SECTION 10: Outside Air Supply.........................................37
10.1 Pressurized ..............................................................37
10.2 Non-Pressurized ...................................................... 37
10.3 Outside Air Blower Internal Wiring ........................... 38
SECTION 11: Gas Piping ......................................................41
SECTION 12: Control Methods ............................................ 42
12.1 ROBERTS GORDON
12.2 ROBERTS GORDON
12.3 SPST Transformer Relay (P/N 90417600)............... 42
12.4 DPST Transformer Relay (P/N 90436300)............... 42
SECTION 13: Starting The System ...................................... 49
13.1 Checking the Gas Line ............................................ 49
13.2 Checking the Electrical System ............................... 49
13.3 Starting the System ................................................. 49
13.4 Setting the Vacuum.................................................. 49
SECTION 14: Operation and Maintenance.......................... 51
14.1 Sequence of Operation............................................ 51
14.2 To Shut Off Heater................................................... 51
14.3 To Start Heater ........................................................ 51
14.4 Pre-Season Maintenance and Annual Inspection.... 51
14.5 Maintenance Checklist............................................. 52
SECTION 15: Troubleshooting............................................. 55
15.1 Troubleshooting Flow Chart..................................... 55
SECTION 16: Replacement Parts ........................................ 57
SECTION 17: General Specifications .................................. 58
17.1 Material Specification ............................................... 58
17.2 Heater Specifications ............................................... 58
17.3 Suspension Specifications ....................................... 58
17.4 Controls Specifications............................................. 58
SECTION 18: The ROBERTS GORDON
Limited Warranty............................................ 61
®
System Control ................... 42
®
ULTRAVACTM..................... 42
®
CORAYVAC®
© 2006
ROBERTS GORDON, LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon, LLC.
Prin te d in U.S.A.
TABLE OF FIGURES
Figure 1: Standard Reflector .....................................................4
Figure 2: One Side Reflector..................................................... 4
Figure 3: Two Side Reflectors ...................................................4
Figure 4: Universal Shield, Position 1 ....................................... 5
Figure 5: Universal Shield, Position 2 ....................................... 5
Figure 6: Universal Shield, Position 3 ....................................... 5
Figure 7: 2-Foot Deco Grille...................................................... 6
Figure 8: Barrier Shield ............................................................. 6
Figure 9: 1-Foot Deco Grille ...................................................... 6
Figure 10: Major Component Descriptions................................ 8
Figure 11: Heater Assembly Overview ...................................14
Figure 12: Critical Hanger Placement ..................................... 15
Figure 13: Reflector Joint Detail .............................................. 22
Figure 14: EP-200 Condensate Valve Assembly ..................... 31
Figure 15: Vertical Venting Configuration................................33
Figure 16: EP-100 Horizontal Venting Configurations ............. 34
Figure 17: EP-200 Series Horizontal
Venting Configurations...........................................35
Figure 18: EP-300 Series Horizontal
Venting Configurations...........................................36
Figure 19: Duct Sizing ............................................................ 37
Figure 20: Outside Air Blower Internal Wiring Diagram...........38
Figure 21: Filter Housing Assembly ........................................38
Figure 22: Air Supply Blower Support .....................................39
Figure 23: Pressurized Outside Air Supply..............................39
Figure 24: Non-Pressurized Outside Air Supply......................40
Figure 25: Gas Connection with Flexible Gas Hose................ 41
Figure 26: One Zone Operation without Control Panel ...........43
Figure 27: One Zone Operation (with Outside Air Blower)
without Control Panel.............................................44
Figure 28: Two Zone Operation without Control Panel............ 45
Figure 29: General System Wiring .......................................... 46
Figure 30: External Wiring Diagram EP-100 and EP-201
120 V 1 Ø Pump ....................................................46
Figure 31: External Wiring Diagram EP-301
120 V 1 Ø Pump ....................................................47
Figure 32: External Wiring Diagram EP-203 or
EP-303 208 V - 230 V (or 460 V) 3 Ø Pump .......... 47
Figure 33: Burner Internal Wiring ............................................48
Figure 34: Burner Internal Ladder Diagram ............................ 48
Figure 35: Vacuum Reading....................................................50
SECTION 1: HEATER SAFETY
Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these
sections. Installation, service and annual inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Read this manual carefully before installation, operation or service of this equipment. This heater is designed for heating nonresidential indoor spaces. Do not install in residential spaces. These instructions, the layout drawing, local codes and ordinances, and applicable standards that apply to gas piping, electrical wiring, venting, etc. must be thoroughly understood before proceeding with the installation. Thin sheet metal parts, the aluminum reflector portion of the heater and the various venting components, have sharp edges. To prevent injury, the use of work gloves is recommended. The use of gloves will also prevent the transfer of body oils from the hands to the surface of the reflector. Before installation, check that the local distribution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.
1.1 Manpower Requirements
To prevent personal injury and damage to the heater, two persons will be required for installation.
SECTION 1: HEATER S AFETY
1
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To ensure the system is designed in accordance with the parameters of the CRV-Series
Design
Manual (P/N 127500NA).
• To install the heater, as well as the gas and electrical supplies, in accordance with applicable specifications and codes. Roberts-Gordon recommends the installer contact a local Building Inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing and in the manual together with the cited codes and regulations to perform the installation.
• To install the heater in accordance with the clearances to combustibles requirements.
• To furnish all needed materials not furnished as standard equipment.
• To plan location of supports.
• To provide access to burners on all sides for servicing or burner removal.
• To provide the owner with a copy of this Installation, Operation and Service Manual.
• To never use heater as a support for ladder or
other access equipment and to never hang or suspend anything from heater.
• To ensure there is adequate air circulation around
the heater and to supply air for combustion, ventilation and distribution in accordance with local codes.
• To safely and adequately install heater using
materials with a minimal working load of 75 lb (33 kg).
2.1 Wall Tag
A laminated wall tag is available for the heater as a permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Please contact Roberts-Gordon or your ROBERTS GORDON
®
independent distributor to obtain the wall tag. Affix the tag by peeling off the backing of the adhesive strips on the rear surface and position the tag on a wall near the CRV-Series heater (e.g. thermostat or controller). A copy of the wall tag (P/N 91037912) is illustrated on the back cover. For an immediate solution, you may affix this copy on the wall near the heater. Know your model number and installed configuration. Model number and installed configuration are found on the burner and in the Installation, Operation and
Service Manual. See Page 4, Figure 1 through Page 6, Figure 9. Write the proper clearance dimensions in permanent ink according to your model number and configuration in the open spaces on the tag.
2.2 Corrosive Chemicals
CAUTION
Do not use heater in an area containing corrosive chemicals.
Avoid the use of corrosive chemicals to ensure a longer life of the burner, tubing and other parts.
Failure to follow these instructions can result in property damage.
Roberts-Gordon cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility of the installer. It is essential that the contractor, the sub-contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemical compounds characterized by the presence of halogen elements (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the life span of the heater components will be greatly reduced. An outside air supply must be provided to the burners whenever the presence of these compounds is suspected. Warranty will be invalid if the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with the latest revision of the applicable standards and national codes. This refers also to the electric, gas and venting installation. Note: Additional standards for installations in public garages, aircraft hangars, etc. may be applicable.
2
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Required Clearances to Combustibles
Clearances are the required distances that combustible objects must be away from the heater to prevent serious fire hazards. Combustibles are materials that may catch fire and include common items such as wood, paper, rubber, fabric, etc.
Maintain clearances to combustibles at all times for safety.
Clearances for all heater models are located on the burner of the heater and on Page 4, Figure 1 through Page 6, Figure 9 in this manual. Check the clearances on each burner for the model heater being installed to make sure the product is suitable for your application and the clearances are maintained. Read and follow the safety guidelines below:
• Keep gasoline or other combustible materials including flammable objects, liquids, dust or vapors away from this heater or any other appliance.
• Maintain clearances from heat sensitive material, equipment and workstations.
• Maintain clearances from vehicles parked below the heater.
SECTION 3: CRITIC AL C ONSIDERATIONS
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
• Maintain clearances from swinging and overhead doors, overhead cranes, vehicle lifts, partitions, storage racks, hoists, building construction, etc.
• In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain required clearances from the heater to the combustibles. Signs must be posted adjacent to the heater thermostat. In the absence of a thermostat, signs must be posted in a conspicuous location.
• Consult local Fire Marshal, Fire Insurance Carrier or other authorities for approval of proposed installation when there is a possibility of exposure to combustible airborne materials or vapors.
• Hang heater in accordance to the minimum suspension requirements on Page 15, Figure 12.
• If the radiant tubes must pass through the building structure, be sure that adequate sleeving and fire stop is installed to prevent scorching and/or fire hazard.
3
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the combustion chamber and the tube connect.
* Protective Grille clearances are the same as Standard Reflector.
FIGURE 1: STANDARD REFLECTOR
Model ABCDABCD
CRV-B-2 4 20 48 20 11 51 122 51
A
CRV-B-4 4 20 48 20 11 51 122 51
CRV-B-6 4 20 48 20 11 51 122 51
CRV-B-8 4 20 48 20 11 51 122 51
B
C
D
CRV-B-9 4 36 60 36 11 92 153 92
CRV-B-10 4 366036119215392
CRV-B-12 4 36 60 36 11 92 153 92
CRV-B-12A 4 36 60 36 11 92 153 92
.
FIGURE 2: ONE SIDE REFLECTOR
Model ABCDABCD
A
B
C
D
CRV-B-2 4 12 56 20 11 31 143 51
CRV-B-4 4 12 56 20 11 31 143 51
CRV-B-6 4 12 56 20 11 31 143 51
CRV-B-8 4 12 56 20 11 31 143 51
CRV-B-9 4 12 60 42 11 31 153 107
CRV-B-10 4 12 60 42 11 31 153 107
CRV-B-12 4 12 60 42 11 31 153 107
CRV-B-12A 4 12 60 42 11 31 153 107
(inches) (centimeters)
(inches) (centimeters)
FIGURE 3: TWO SIDE REFLECTORS
Model ABCDABCD
A
B
C
D
CRV-B-2 4 12 56 12 11 31 143 31
CRV-B-4 4 12 56 12 11 31 143 31
CRV-B-6 4 12 56 12 11 31 143 31
CRV-B-8 4 12 56 12 11 31 143 31
CRV-B-9 4 12 60 12 11 31 153 31
CRV-B-10 4 12 60 12 11 31 153 31
CRV-B-12 4 12 60 12 11 31 153 31
CRV-B-12A 4 12 60 12 11 31 153 31
4
(inches) (centimeters)
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the combustion chamber and the tube connect.
FIGURE 4: UNIVERSAL SHIELD, POSITION 1
Model ABCDABCD
A
B
C
D
CRV-B-2 4 12 12 12 11 31 31 31
CRV-B-4 4 12 12 12 11 31 31 31
CRV-B-6 4 12 12 12 11 31 31 31
CRV-B-8 4 12 12 12 11 31 31 31
CRV-B-9 8 18 24 18 21 46 61 46
CRV-B-10 8 18241821466146
CRV-B-12 8 18 24 18 21 46 61 46
CRV-B-12A 8 18241821466146
SECTION 3: CRITIC AL C ONSIDERATIONS
(inches) (centimeters)
FIGURE 5: UNIVERSAL SHIELD, POSITION 2
Model ABCDABCD
A
B
C
D
CRV-B-2 4 24 48 24 11 61 122 61
CRV-B-4 4 24 48 24 11 61 122 61
CRV-B-6 4 24 48 24 11 61 122 61
CRV-B-8 4 24 48 24 11 61 122 61
CRV-B-9 4 36 48 36 11 92 122 92
CRV-B-10 4 36 48 36 11 92 122 92
CRV-B-12 4 36 48 36 11 92 122 92
CRV-B-12A 4 36 48 36 11 92 122 92
FIGURE 6: UNIVERSAL SHIELD, POSITION 3
Model ABCDABCD
A
B
C
D
CRV-B-2 4 12 56 30 11 31 143 77
CRV-B-4 4 12 56 30 11 31 143 77
CRV-B-6 4 12 56 30 11 31 143 77
CRV-B-8 4 12 56 30 11 31 143 77
CRV-B-9 8 12 60 42 21 31 153 107
CRV-B-10 8 12 60 42 21 31 153 107
CRV-B-12 8 12 60 42 21 31 153 107
CRV-B-12A 8 12 60 42 21 31 153 107
(inches) (centimeters)
(inches) (centimeters)
5
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the combustion chamber and the tube connect.
FIGURE 7: 2-FOOT DECO GRILLE
Model ABCDABCD
A
C
B
D
CRV-B-2 4 12 48 12 11 31 122 31
CRV-B-4 4 12 48 12 11 31 122 31
CRV-B-6 4 12 48 12 11 31 122 31
CRV-B-8 4 12 48 12 11 31 122 31
CRV-B-9 4 18 56 18 11 46 143 46
CRV-B-10 4 18 56 18 11 46 143 46
CRV-B-12 4 18 56 18 11 46 143 46
CRV-B-12A 4 18 56 18 11 46 143 46
(inches) (centimeters)
FIGURE 8: BARRIER SHIELD
Model ABCDABCD
CRV-B-2 4 12 12 12 11 31 31 31
A
CRV-B-4 4 12 12 12 11 31 31 31
CRV-B-6 4 12 12 12 11 31 31 31
CRV-B-8 4 12 12 12 11 31 31 31
B
C
D
CRV-B-9 - UNAPPROVED - - UNAPPROVED -
CRV-B-10 - UNAPPROVED - - UNAPPROVED -
CRV-B-12 - UNAPPROVED - - UNAPPROVED -
CRV-B-12A - UNAPPROVED - - UNAPPROVED -
FIGURE 9: 1-FOOT DECO GRILLE
Model ABCDABCD
A
C
B
D
CRV-B-2 4 12 48 12 11 51 122 51
CRV-B-4 4 12 48 12 11 51 122 51
CRV-B-6 4 12 48 12 11 51 122 51
CRV-B-8 4 12 48 12 11 51 122 51
CRV-B-9 4 18 56 18 11 92 153 92
CRV-B-10 4 18 56 18 11 92 153 92
CRV-B-12 4 18 56 18 11 92 153 92
CRV-B-12A 4 18 56 18 11 92 153 92
(inches) (centimeters)
(inches) (centimeters)
6
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
SECTION 4: NATIONAL STANDARDS AND APPLICABLE C ODES
4.1 Gas Codes
The type of gas appearing on the nameplate must be the type of gas used. Installation must comply with national and local codes and requirements of the local gas company.
United States: Refer to National Fuel Gas Code, ANSI Z223.1 - latest revision (same as NFPA
54).
Canada: Refer to CAN/CGA B149.1 and B149.2: Installation Codes for Gas Burning Appliances.
4.2 Aircraft Hangars
Installation in aircraft hangars must be in accordance with the following codes:
United States: Refer to Standard for Aircraft Hangars, ANSI/NFPA-409 - latest revision.
Canada: Refer to Standard CAN/CGA B149.1 and B149.2: Installation Codes for Gas Burning Appliances.
• In aircraft storage and servicing areas, heaters shall be installed at least 10' (3 m) above the upper surface of wings or of engine enclosures of the highest aircraft which may be housed in the hangar. The measurement shall be made from the wing or engine enclosure (whichever is higher from the floor) to the bottom of the heater.
• In shops, offices and other sections of aircraft hangars communicating with aircraft storage or servicing areas, heaters shall be installed not less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so located in all spaces of aircraft hangars that they shall not be subject to injury by aircraft, cranes, movable scaffolding or other objects. Provisions shall be made to assure accessibility to suspended heaters for recurrent maintenance purposes.
4.3 Public Garages
Installation in garages must be in accordance with the following codes:
United States: Standard for Parking Structures NFPA-88A - latest revision or the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision. Canada: Refer to CAN/CGA B149.1 and B149.2: Installation Codes for Gas Burning Appliances.
• Heaters must not be installed less than 8' (2.4 m) above the floor. Minimum clearances to combustibles must be maintained from vehicles parked below the heater.
• When installed over hoists, minimum clearances to combustibles must be maintained from the uppermost point of objects on the hoist.
4.4 Electrical
The heater must be electrically grounded in accordance with the following codes:
United States: Refer to National Electrical
®
Code
, ANSI/NFPA-70 - latest revision. Wiring must conform to the most current National Electrical Code
®
, local ordinances and any
special diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest revision.
4.5 Venting
The venting must be installed in accordance with the requirements within this manual and the following codes:
United States: Refer to NFPA-54/ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CAN/CGA B149.1 and B149.2: Installation Codes for Gas Burning Appliances.
4.6 High Altitude
These heaters are approved for installations up to 2000' (610 m) (US), 4500' (1370 m) (Canada) without modification. Consult factory if US installation is above 2000' (610 m) or Canadian installation is above 4500' (1370 m).
7
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 5: MAJOR COMPONENTS
The figures in this section provide a general overview of component placement in a CRV-Series system. The location of some components such as supports and couplings is crucial for proper installation. Assemble the heater components as shown on Page 14, Figure 11.
FIGURE 10: Major Component Descriptions
Optional reflector configurations are shown on Page 4, Figure 1 through Page 6, Figure 9. Install
appropriate suspension hardware, beam clamps, chain or rod at predetermined locations. Adjustments of chain length will provide uniform pitch.
Burner
Reflector (Aluminum or Stainless Steel)
Alternate overlap as shown on overview. Minimum overlap is 6" (16 cm).
Tube
Hot rolled, heat treated or coated aluminized tube supplied in 10' (3 m) lengths.
Reflector with Hole (Aluminum or Stainless Steel)
Alternate overlap as shown on overview. Minimum overlap is 6" (16 cm).
Flex Gas Line with shut-off cock
Combustion Chamber
Coupling Assembly with Lock
45° Elbow
Tee
Tube Adapter
90° Elbow
Cross
End Vent
8
FIGURE 10: Major Component Descriptions (Continued)
Reflector Joint
SECTION 5: MAJOR COMPONENTS
Reflector End Cap (Aluminum or Stainless Steel)
Punch out center section to accommodate heat exchanger tube when necessary.
Tube and Reflector Hanger with Clamp Package
Position this hanger no more than 4" (10 cm) away from the burner.
Tube and Reflector Hanger
Suspend system from these hangers.
Reflector Support Strap & Wire Form
Barrier Shield
Reflector Side Extension
Deco Grille
S-Hook
Reflector Side Extension Bracket
Bracket Assembly
Turn buc kl e
Protective Grille
Condensate Valve Assembly
Universal Shield
Universal Shield with Holes
9
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 10: Major Component Descriptions (Continued)
DANGER
Danger de Choc Électrique
le courant
Débrancher
avant toute électrique révision.
doit être
de
Cet appareil
must be
can result
S O L
C N E
E
M E
G A N
/N P
à une source
connecter
avec mise á terre.
courant
source.
shock.
.c
c n i
-
g r .
w
w
w
Y G
R
E
N
T
E
N E
D
M
E
P I
U Q E
T N
B
S 8 5
e
R 5 0
0 8 0
0 1 9
ces
de suivre
Faute
peut entraîner la
instructions
ou les choc électriques.
mort
8
0 0 1
9 N /
P A .
S .
U e h
t n i
d
te n i r
P
s i n
U
­s t
ta
E x u
a
é im r p
Im
m o
B v
ROBERTS GORDON
UltraVac
Part Number:
uméro de la Pièce:
N
Serial Num
No. de Série:
Ratings: In
-G rts e
b o
R
x o
. B
.O
P
, N
lo a ff
u
B
o
h p le
e
T
1 x: 7
a F
re ll F
o T
.rg
w w
w
©
®
ber:
put 120V AC, 25A Outputs 120V AC
e
b o R
M 6 7
n
o rd o
it n U
4
4
4 0
4
0
-
im
r
0 4
G
2 4
0
1
0
Y
4
.4
2
n
5
a C
.8
6
1 : 7 e
n
le
4
e
5
T
8
.0
2
0
5
5
.8
4
6
.7
a
8
F
2 .8 0
0
: 8
e
m
o
.c c
in
-
e
t n ri P
DANGER
Electrical
Disconnect power before
appliance
This connected grounded
Failure to follow these instructions in death or electrical
©
Controller
n o
d r o
-G
t
s
ts
e
r
t W
e tre
S in a
R
1 M 3
0
L
1
io
r ta n
, O y b
s
0 4
.5
5
a
4 d a
.9
5
0
: 9 e n
o
1
h
1
p
5
.0
5
4 .9 5
0 : 9 x
E
x u a
é im r p
m
/I A .
S .
U in d
6
3
a t
Shock Hazard
electrical
servicing.
to a properly electrical
(8 total)
, 3A
A
M
s i n
U
­ts
ROBERTS GORDON
1 0 0
®
D
k Hazard
Shoc
Electrical
electrical
nect
Discon
re servicing.
befo
er
pow
be
ust
m
appliance
This
a properly
to
nected
con
urce.
so
electrical
ded
groun
ese
w th
follo
to
Failure
result
can
instructions
k.
oc
sh
r electrical
o
death
in
m I
m
o c . c
in
-
g r .
w
w
w
©
ue
lectriq
hoc É
e C
ger d
Dan
urant
o
er le c
anch
Débr
te
ou
vant t
a
ue
ctriq
éle
.
sion
révi
e
oit êtr
areil d
Cet app
e de
rc
une sou
er à
ect
nn
co
e.
err
á t
ise
m
t avec
uran
co
es
e c
ivr
e su
te d
Fau
r la
aîne
t entr
eu
ons p
structi
in
.
ues
lectriq
hoc é
u les c
rt o
mo
A
. S .
1
U
0 0
e
8
th
0
0
n i
1
d
9 e t
N /
n i r
P
P
s
i n U
­s t
a
t E x
u
a
é im r
p
R
E
NG
DA
R
E
G
AN
ULTRAVAC™ Controller
®
ROBERTS GORDON ULTRAVAC™ Variable Frequency Drive
EP-100 Pump Package - 4" dia For more information, refer to the EP-100 Installation, Operation and Service Manual (P/N 127201NA).
System Control
ROBERTS GORDON® ULTRAVAC™ Adjustable Indoor Sensor
EP-201 Pump Package - 4" dia EP-203 Pump Package - 4" dia For more information, refer to the EP-200 Series Installation, Operation and Service Manual (P/N 127200NA).
EP-301 Pump Package - 4" dia EP-301 Pump Package - 6" dia EP-303 Pump Package - 4" dia EP-303 Pump Package - 6" dia For more information, refer to the EP-300 Series Installation, Operation and Service Manual (P/N 127202NA).
10
SECTION 5: MAJOR COMPONENTS
5.1 Standard Parts List
Table 1: Contents of CRV-Series Burner Carton
Part No. Description
0270XXXX Burner (Rate and Fuel Varies)
*91412200 Flexible Stainless Steel Gas Hose, 1/2" NPT
(US models only) 013676XX End Vent Plate 01397300 Accessory Package
01361200 Filter Support Disk 01367800 Combustion Chamber Gasket 02724901 Door Assembly w/ Hole 91115100 Screw #10 - 24 x 5/8 91119500 U-Clip 91905500 Filter Support 92123900 Nut 5/16 - 18 92511601 Wing Nut #10 - 24 96411600 Lock Washer 5/16" 01312401 Filter and Gasket
* Canadian Models: Rubber (Type 1) Gas Hoses available as an accessory, see Page 41.
Table 2: Common CRV-Series Components
Part No. Description
Combustion Chamber: 02722300-1P Hot Rolled Steel Combustion Chamber 02722301-1P Heat-Treated Aluminized Steel Combustion Chamber
0272230D-1P Porcelain Coated Steel Combustion Chamber
02721200-1P Cast Iron Combustion Chamber
Tubing and Related Accessories
01312700 Coupling, 4" (10 cm) Plain 01312706 Coupling, 6" (15 cm) Plain
0131270I Coupling, 4" (10 cm) Lined 01331900 Coupling, 4" (10 cm) Damper E0009356 Coupling, 6" (15 cm) Damper
0133022D Tee, 4" (10 cm) Coated
01330203 Tee, 4" (10 cm) Aluminized 01330204 Tee, 6" (15 cm) Aluminized
0133092D Cross, 4" (10 cm) Coated
01330903 Cross, 4" (10 cm) Aluminized 01330904 Cross, 6" (15 cm) Aluminized 01335801 Elbow, 4" (10 cm) Aluminized 90° T0100320 Elbow, 6" (15 cm) Aluminized 90°
0133580D Elbow, 4" (10 cm) Coated 90°
01336101 Elbow, 4" (10 cm) Aluminized 45°
0133610D Elbow, 4" (10 cm) Coated 45°
91409300 Tube, Hot Rolled Steel 4" (10 cm) dia 10' (3 m) 91409403 Tube, Non-Heat Treated Aluminized 4" (10 cm)
dia 10' (3 m) 91409408 Tube, Heat Treated Aluminized 4" (10 cm) dia 10' (3 m) 91409420 Tube, Non-Heat Treated Aluminized 6" (15 cm)
dia 10' (3 m)
9141030D Tube, Coated 4" (10 cm) dia 10' (3 m)
E0009105 Tube, Heat Treated Aluminized 6" (15 cm) dia 10' (3 m) 91418200 Tube Adapter, Aluminized
6" (15 cm) dia x 4" (10 cm) dia
02722100 Adapter, 4" (10 cm) Cast Iron 91240010 Tube Hanger, 6" (15 cm) 91308001 High Temperature Pipe Compound, 1lb. can
Venting Accessories 01324401 Outside Air Supply Takeoff, 4" (10 cm) 01326801 Outside Air Filter Housing 90707501 Air Supply Blower/Power Venter 91409601 Outside Air Flex Duct, 4" (10 cm)
(Box of 8 - 8' [2.4 m] sections)
Reflectors and Related Accessories 01329910 Reflector Side Extension Support 03050010 Reflector Support Package (Tubing) 02712700 Reflector Side Extension, 2 Clips, 2 Screws 02716400 Reflector Support Package (Schedule 40 Pipe) 02750303 Reflector, Aluminum
027503SS Reflector, Stainless Steel 02750304 Reflector, Aluminum with Hole 027503SH Reflector, Stainless Steel with Hole 02750800 Reflector End Cap, Aluminum 027508SS Reflector End Cap, Stainless Steel 027508SH Reflector End Cap, Stainless Steel with Hole 02750900 Reflector Joint 027509SS Reflector Joint, Stainless Steel 027127SS Reflector Side Extension, Stainless Steel 03090100 Tube and Reflector Hanger 02790300 Tube and Reflector Hanger, Cast Iron 91907302 S-Hook 91903201 Turnbuckle 91903300 Spring Hook 91903202 Turnbuckle with Eyebolt 02712100 Universal Shield Support 02751800 Universal Shield with Holes 02751801 Universal Shield 027518SS Universal Shield, Stainless Steel
11
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Control Packages and Accessories
10001501 Water Resistant Sensor 02770002 System Control
URVCCM
ROBERTS GORDON® ULTRAVAC™ Central Controller (with Modem Chip & Software) Includes:
URVSC
ROBERTS GORDON
®
ULTRAVAC™ Controller 10080142 Modem Chip 10081501 Outdoor Sensor 10080410 PC Connection Cable Package
URVCCR
ROBERTS GORDON
®
ULTRAVAC™ Central Controller
(with RS-485 Converter & Software) Includes:
URVSC
ROBERTS GORDON
®
ULTRAVAC™ Controller 10080430 RS-485 Converter with 9 V Power Supply 10081501 Outdoor Sensor 10080410 PC Connection Cable Package
URVCCL
ROBERTS GORDON
®
ULTRAVAC™ Central Controller (with TCP/IP Communication Module & Software) Includes:
URVSC
ROBERTS GORDON
®
ULTRAVAC™ Controller 10080440 TCP/IP Communication Module 10081501 Outdoor Sensor 10080410 PC Connection Cable Package
URVSC
Controller, ROBERTS GORDON
®
ULTRAVAC™ , 1
Pump 3 Zones (Satellite Control) VFD75115 Variable Frequency Drive Assembly, 75 HP, 115 V Input VFD75230 Variable Frequency Drive Assembly, 75 HP, 230 V Input VFD20230 Variable Frequency Drive Assembly, 2 HP, 230 V Input 10080142 Modem, Plug-In Chip 10080410 Cable Package, PC Connection 10080430 RS-485 Converter with 9V Power Supply 10080440 TCP/IP Communication Module 10081500
Sensor, Adjustable Indoor, Deg F, ROBERTS GORDON
ULTRAVAC™ Controller 10081501 Sensor, Outdoor, ULTRAVAC™ 10081502 Sensor, Adjustable Indoor, Deg C, ULTRAVAC™
Thermostats
05023000 Load Relay Package 90417600 Transformer Relay - SPST (12 A) 90436300 Transformer Relay - DPST (12 A) 90423000 24 V Low Voltage Thermostat (Marked 1-5) 90424300 Thermostat Guard
Deco Grille (1' x 8' [.3 m x 2.4 m])
01363003 Bracket 01365901 End Piece 01326801 Reinforcement 01365903 Joint Piece 91406700 1' (.3 m) x 8' (2.4 m) Protective Grille
Protective Grille
08050001 Protective Grille, 40" (1 m) 08050002 Protective Grille End Cap
Shields
02750303 Barrier Shield 02751801 Universal Shield 027518SS Universal Shield, Stainless Steel 02751800 Universal Shield with Holes
Pump Packages and Accessories
02719105 EP-100 Pump Package
02719100 EP-100 Pump 02724700 Accessory Package 02716305 EP-201 Pump Package 01312001 EP-201 Pump 01317805 Accessory Package 02712034 EP-203 Pump Package 01312002 EP-203 Pump 01317805 Accessory Package 02723014 EP-301 Pump Package 4" 02730101 EP-301 Pump Assembly 02730104 Accessory Package 02723016 EP-301 Pump Package 6" 02730101 EP-301 Pump Assembly 02730106 Accessory Package 02723034 EP-303 Pump Package 4" 02730103 EP-303 Pump Assembly 02730104 Accessory Package 02723036 EP-303 Pump Package 6" 02730103 EP-303 Pump Assembly
®
02730106 Accessory Package
Pump Accessories
90430600K Pressure Switch
01327001 Condensate Check Valve Assembly 02718851 Drain Cap, 4" (10 cm) 02718852 Drain Cap, 6" (15 cm)
Starters
10050001 Starter, 120 Vac for EP-203, 3 Ø 10050002 Starter, 12 Vdc for EP-201, 1Ø 10050003 Starter, 120 Vac for EP-201, 1 Ø 10050008 Starter, 120 Vac for EP-301, 1 Ø 10050009 Contactor Package-230 Vac Coil for EP-301, 2 HP 10050010 Starter, 120 Vac for EP-303, 3 Ø
Deco Grille (2' x 4' [.6 m x 1.2 m])
01365900 Shield Frame 01370408 Reflector Side Extension 8" x 48" (20.3 cm x 122 cm) 01370412 Reflector Side Extension 12" x 48" (30.5 cm x 122 cm) 01370416 Reflector Side Extension 16" x 48" (40.6 cm 122 cm) 91407000 Grille, Aluminum 2' x 4' (.6 m x 1.2 m)
12
SECTION 6: DESIGN REQUIREMENTS
The CRV-Series system’s design is related to the system operation and performance required by the building being heated. Every effort should be made to follow the dimensions on the layout drawing. If deviations are necessary, either contact the company responsible for the layout design, your ROBERTS GORDON
®
independent distributor, or consult the CRV-Series Design Manual (P/N 127500NA).
SECTION 6: DESIGN R EQUIREMENTS
13
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 11: Heater Assembly Overview
®
Controller
System Control
ULTRAVAC
or ROBERTS GORDON
Relay*
Exhaust
to Outside
Pressure Switch
Pump
Flexible
Boot
Tube &
Hanger
Reflector
Reflector
with Hole
Support
Reflector
requires zone sensors
ULTRAVAC
®
U-Clips
Tube
Reflector
14
Burner
End
Vent
Coupling
S
Chamber
Combustion
End Cap
Reflector
Zone 1 Sensor or Thermostat**
controller's Installation, Operation and Service Manual for details.
* May not be needed with certain pumps and controllers. Refer to wiring diagram in the appropriate
**System Control requires thermostats. ROBERTS GORDON
and additional control equipment. See the appropriate controller installation manual for details.
SECTION 7: HEATER INSTALLATION
WARNING
Suspension Hazard
Hang heater with materials with a minimum working load of 75 lbs (33 kg).
Failure of the supports can result in death, injury or property
To ensure your safety and comply with the terms of the warranty, all units must be installed in accordance with these instructions.
The gas or the electrical supply lines must not be used to support the heater.
FIGURE 12: Critical Hanger Placement
Typical Suspension Details
Beam Clamp
damage.
SECTION 7: HEATER I NSTALLATION
Do not locate the gas or electric supply lines directly over the path of the flue products from the heater. The heater must be installed in a location that is readily accessible for servicing. The heaters must be installed in accordance with clearances to combustibles as indicated on the rating plate and in this instruction manual. The minimum and maximum gas inlet pressures must be maintained as indicated on the rating plate. Typical installation configurations are shown in Figure 12. Expansion and contraction of the tube dictates that the minimum suspension lengths in the table on Figure 12 be maintained.
Concrete Beam
Anchor
Screw Hook 3/8"
Locknut
Wood Beam
Rod 3/8"
24" min.
(61 cm)
"X" (See Table)
Side View Towards Pump
Chain size
3/16" minimum
Turnbuckle
Locknut (Typical)
7'6" (2.3 m)
Washers
S-Hook
Turnbuckle
Hanger
Reflector
Front View
Description Part Number
Turnbuckle 91903201 S-Hook 91907302 Tube/Reflector Hanger 03090100
Run Length Typical Expansion Minimum “X” Length
50' (15 m) ±1" (3 cm) 12" (30 cm) 100' (31 m) ±2" (5 cm) 24" (61 cm) 150' (46 m) ±3" (8 cm) 36" (91 cm) 200' (61 m) ±4" (10 cm) 46" (122 cm) 250' (76 m) ±5" (13 cm) 57" (145 cm)
15
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 7.1 Tube Installation
Combustion
Chamber
NOTE: Tubing requires a downward slope of
1/2" (13 mm) per 20' (6 m) away from burner. Tailpipe tubing requires a downward slope of 1" (26 mm) per 20' (6 m) away from burner.
End View
Weld
Seam
Bottom of Tube
7' 6"
(229 cm)
Description Part Number
Tube 91409XXX Turnbuckle 91903201 Tube/Reflector Hanger 03090100
Step 7.2 Coupling and Tube Assembly
Close coupling with tab.
A
Open
maximum
Tab
Tube
10'
(3 m)
Hanger
Turnbuckles
Combustion
Chamber
Start slide bar/coupling lock
B
onto coupling.
3" (8 cm) to
4" (10 cm)
Slide Bar/Coupling Lock
Wide End
Coupling
Insert tubes into coupling.
C
16
Closed
Tube
Orient coupling so that
the impact block is in the
2:00 or 10:00 oclock
positions.
Tube
Tighten coupling to join tubes.
D
Tube
Description Part Number
Coupling 01329600 Slide Bar/Coupling Lock 01329700 Tube 91409XXX
Slide Bar/Coupling Lock
Coupling
Step 7.2.1 Coupling and Tube Assembly (Continued)
Tighten slide bar as shown below.
Drive slide bar until tight. End of slide bar should be within tolerance listed below.
± 2" (5 cm)
SECTION 7: HEATER I NSTALLATION
Correct Slide Bar
Dimensions
Repeat Step 7.2, A - D until all tubes are assembled. NOTE: If coupling is not tight, loss of vacuum can occur.
7.3 Elbow Package Configuration Step 7.3.1 Elbow Installation
Tube
Description Part Number Elbow Package 02718702
90° Elbow 01335801 Coupling 01312700 Reflector End Cap 02750800 Reflector Joint Piece 02750900 U-Clip Package 91107720
Coupling
Incorrect Slide Bar
Position
Minimum Distance Required Between
9Elbow
Burner and Elbow Model Minimum Distance
CRVB-2 5' (1.5 m) CRVB-4 5' (1.5 m) CRVB-6 10' (3 m) CRVB-8 10' (3 m) CRVB-9 10' (3 m) CRVB-10 15' (4.5 m) CRVB-12A 15' (4.5 m) CRVB-12 15' (4.5 m)
Step 7.3.2 Elbow Installation
Tube
Coupling
17
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 7.4 Reflector Installation Step 7.4.1 Reflector Installation with Hole
Reflector with Hole
Slide Reflector
with hole
through hanger. Unhook combustion chamber from chain
and insert through hole.
Reconnect chain.
Hanger
Tube
Description Part Number
Tube/Reflector Hanger 03090100 Tube 91409XXX Reflector with Hole 02750304
Step 7.4.2 Reflector Installation
Wire Form
Reflector
Reflector Support
Strap
Description Part Number
Reflector Support Package 03050010 U-Clip Package 91107720 Reflector End Cap 027508XX
Sheet Metal
Screw
Tube
Combustion
Chamber
U-Clip
(2 Clips per
Alternate Overlaps
per Side)
18
Step 7.4.3 Reflector, U-Clip and Reflector Support Installation
The pictorial drawings of the heater construction in Section 7 are schematic only and provide a general guideline of where hangers, reflector supports and U-clips are to be installed. To ensure proper expansion and contraction movement of the reflectors, a combination of U-clips
reflector supports and U-clips depend on the individual installation. Use either pop rivets or sheet metal screws instead of u-clips when installing end caps and joint pieces in areas where impact and high wind may be a factor. The following rules must be observed.
and reflector supports are used. The positioning of
SECTION 7: HEATER I NSTALLATION
1. The first reflector after the burner must be affixed in the middle of the reflector with a reflector support and tight screws.
Reflector End Cap
First Reflector
U-Clips
Overlap must be a
minimum of 6" (16 cm)
2. The overlap at the first and second reflector is a slip overlap. Thereafter, every third reflector joint is a slip overlap. A slip overlap is achieved by either: a.) both reflectors lay inside a hanger.
(No reflector support needed).
b.) using a reflector support with
loose screws at the reflector overlap.
6
"
(16 cm)
2 A
Slip Overlap
Wire Form
Reflector Support
2 B
Slip Overlap
Tight
Sheet Metal
Screw
Strap
Reflector Reflector
Support
Loose screws loosened 1/16" (1.6 mm) to allow slippage.
3. The remaining reflector overlaps require a non-slip overlap connection. To affix the reflectors together in a non-slip overlap either: a.) use reflector support and tight screws. b.) if both reflectors lay inside a hanger, u-clips or
sheet metal screws may be used.
This section of three reflectors joined together must be affixed to the tube with at least one reflector support with tight screws.
Description Part Number Reflector Support Package 03050010
Wire Form 91908004 Reflector Support Strap 03050000
Screw #8 x 3/4 94320812 U-Clip Package 91107720 Reflector End Cap 027508XX
3 A
Non-Slip Overlap
Reflector
Tight
Screws
3 B
Non-Slip Overlap
U-Clip
(2 Clips per Non-slip Overlap inside a Hanger)
19
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 7.5 Burner Installation
Burner
Description Part Number
Bolt 94273914 Burner 0270XXXX Lock Washer 96411600 Gasket 01367800 End Vent 013676XX
Combustion
End
Vent
Clips
End Vent
Burner
Combustion
Chamber
Gasket
End
Vent
Chamber
NOTE:
Install end vent at end combustion chamber position only.
Rating
Number
20
SECTION 8: OPTIONAL HEATER ACCESSORIES Step 8.1 Tee Installation
Description Part Number
Tee 01330XXX Tube/Reflector Hanger 03090100 Tube 91409XXX Coupling 01312700
SECTION 8: OPTIONAL H EATER A CCESSORIES
Tube
Coupling
Tee
Step 8.2 Reflector Joint Step 8.2.1 Reflector Joint Installation
Reflector
Scribe Contour
Reflector
Joint
Flatten Edge
1" (2.5 cm) Maximum
21
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 8.2.2 Reflector Joint Installation
Step 8.2.3 Reflector Joint Detail
Cut away contour with tin snips.
Punch/drill six 3/32" (2 mm) holes.
Install reflector end cap.
FIGURE 13: Reflector Joint Detail
Attach reflector joint with six #8 sheet metal screws.
Reflector
Reflector Joint
22
8.3 Reflector Side Extension Step 8.3.1 Bracket Installation
SECTION 8: OPTIONAL H EATER A CCESSORIES
Tube
Reflector
Tube and Reflector Hanger
Reflector Support
Reflector Side
Extension Bracket
(2 per reflector)
Use additional supports
in high air movement
applications.
Description Part Number Reflector Side Extension Package 02712700
Reflector Side Extension 01368000 Retainer Clips 02751200 Sheet Metal Screws 94118106
Order Separately
Reflector Side Extension Bracket 01329910
Step 8.3.2 Side Reflector Installation
#8 x 3/8 (3.9 x 9.5 mm) Sheet Metal Screw
Cut relief notches for supports and hangers.
Retainer Clip (2 per Side)
Reflector Side Extension
23
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
8.4 Universal Shield
Universal shields are adjustable aluminum reflectors whose angle and height can be adjusted to direct heat to or away from a desired area.
See Page 5, Figure 4 through Page 5, Figure 6 for positions.
Tube
Universal Shield
Description Part Number
Universal Shield 02751801 Universal Shield with Holes 02751800
Universal Shield Support Package 02712100
Tube and Reflector Support Assembly 01329802 Universal Shield Support 02751700 Shield Bracket Assembly 02721400 Stud 02790900 Hex Nut 92114800
Flattened
Section
Bracket Assembly*
Standard Reflector
Tube and Reflector Support Assembly*
Stud*
Shield Support Bracket*
Hex Nut*
* Included in universal shield
support package.
8.5 Barrier Shield
Do not install barrier shield less than 20' (6 m) downstream of any burner. Do not attach end caps to the ends of the barrier shields. For lengths greater than 8' (2.6 m), use universal shields. Do not use barrier shields for burner sizes larger than 80,000 Btu/h.
Tube and Reflector Hanger
Flatten Reflector Edges
Reflector Support Strap Cut Relief Notch
Attach U-Clips
Standard Reflector
Barrier Shield
Description Part Number
Barrier Shield 02750303 U-Clip Package 91107720
24
8.6 Two-Foot Decorative Grille Installation Step 8.6.1 Grille Installation
Reflector
Heat Exchanger Tube
SECTION 8: OPTIONAL H EATER A CCESSORIES
Tube and Reflector Hanger
2' x 4' (60 cm x 120 cm) Aluminum Grille
Suspended Ceiling Frame
Step 8.6.2 Frame Shield Installation
Shield
Description Part Number
Aluminum Grille 2' x 4' (60 cm x 120 cm) 91407000
Description Part Number
Deco Grille Shield 01365900
25
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 8.6.3 Reflector Side Extension Installation for Decorative Grilles
NOTE: If the decorative grille system is to be installed in an area with considerable air movement, it is recommended that one #8 x 3/8" sheet metal screw be installed per reflector extension to prevent it from blowing over.
Cut relief notches for tube and reflector hangers.
A
6" (15 cm) Minimum
Allow 6" (15 cm) minimum clearance between burner box and overhead obstructions for service.
Insert screw here (see note).
Reflector Side Extension
Description Part Number
Reflector Side Extension 01370412
8.7 One-Foot Decorative Grille Installation Step 8.7.1 One-Foot Decorative Grille Bracket
#8 Sheet Metal Screws
Decorative Grille Bracket
Cut relief notches for supports and hangers.
Distance "A" Extension
Minimum Maximum Part No. Width
2" (4 cm) 6" (15 cm) 01370408 8" (20 cm)
6" (15 cm) 10" (26 cm) 01370412 12" (30 cm)
10" (26 cm) 14" (37 cm) 01370416 16" (40 cm)
In order to maintain reflector shape, do not fasten brackets together. Do not fasten bracket to adjoining reflectors. Maintain same slipjoint position as reflectors.
2" (5 cm) Minimum Bracket Overlap
Description Part Number
Bracket 01363003
26
Step 8.7.2 Decorative Grille
Spread apart brackets and install decorative grille.
#8 Sheet Metal Screws
Joint Piece
Reinforcement
Slip joint piece into support bracket and fasten to bracket on one side of the joint only.
Joint Piece
Description Part Number
Decorative Grille 8' x 1' (2.4 m x .3 m) 91406700
SECTION 8: OPTIONAL H EATER A CCESSORIES
Step 8.7.3 Joint Piece and Reinforcement
Description Part Number
Joint Piece 01365903 Reinforcement 01365902
27
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Fasten end piece to brackets using two #8 sheet metal screws and replace reflector end cap.
Insert end piece between grille and brackets.
End Piece
Reflector End Cap
Step 8.7.4 End Piece and Reflector End Cap
Description Part Number
End Piece 01365901
Step 8.7.5 90° Elbow
Inside
Corner
Grille Brackets
Joint Piece
Insert end piece between grille and brackets.
28
Decorative Grille
Brackets
Cut grille bracket at
Joint Piece
reflector joint piece.
8.8 Protective Grille Installation Step 8.8.1 Silicone Cap Installation
Silicone Cap
SECTION 8: OPTIONAL H EATER A CCESSORIES
Grille Finger
Step 8.8.2 Grille End Cap Installation
A
Grille
Grille End Cap
C
Pull outward
Step 8.8.3 Grille Installation
Description Part Number
Grille Section 08050001 Grille End Cap 08050002 Silicone Cap 91915951-6P
B
D
Bend up 90°
40"
(101 cm)
Reflector
Final Grille Section
Grille
Grille End Cap
29
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 8.9 Classic Cast-Iron Components
WARNING
Suspension Hazard
Hang heater with materials with a minimum working load of 750 lbs. (340 kg).
Use special tube and reflector hangers when suspending the schedule 40 steel pipe system.
Schedule 40 steel pipe is heavy and will fall if not supported properly.
Distance between supports must be 7' (2.13 m) or less.
Failure to follow these instructions can result in death, injury or property damage.
Special Tube and Reflector Hanger
7' (2.13 m) Maximum
Schedule 40 Steel Pipe
Cast-Iron Combustion Chamber with Schedule 40 Steel Pipe
The total weight of each burner and combustion chamber is 40.25 lbs (18 kg). 4" Schedule 40 pipe weighs 10.9 lbs. (5 kg) per foot.
Coupling
4" Tube
ROBERTS-GORDON
CORAYVAC® Classic Cast-Iron Combustion
Chamber
ROBERTS-GORDON
Turnbuckle Hang cast-iron combustion chamber with a turnbuckle (spring clips will not fit around cast-iron hanging loop).
End Vent
Clips
®
Cast-Iron Adapter
End Vent Plate for
End Burner Only
End Vent
Clips
®
Cast-Iron Combustion Chamber with Standard 4" O.D. Infrared Tubing
The total weight of each burner and combustion chamber is 40.25 lbs (18 kg). 4" O.D. 16 Ga. tubing weighs 2.8 lbs. (1.3 kg) per foot.
30
Cast-Iron Adapter
End Vent Plate for
End Burner Only
Description Part Number
Special Tube & Reflector Hanger 02790300 Turnbuckle 91903201 Cast-Iron Combustion Chamber 02721200-1P Cast-Iron Adapter 02722100 Coupling 01312700
SECTION 9: PUMP INSTALLATION AND VENTING
SECTION 9: PUMP INSTALLATION AND VENTING
9.1 Pump Installation
For complete pump installation, please refer to the EP-100, EP-200 or EP-300 Series Installation, Operation and Service Manuals.
FIGURE 14: EP-200 Condensate Valve Assembly
Description Part Number
Wall
1" NPT threaded hole.
Use 1" x ¾" reducer.
(not supplied)
Copper or
galvanized pipe
between pump
and condensate
valve.
Condensate Valve Assembly 01327001
3/4" female
Condensate
Valve
Assembly
3/4" female
36" (.9 m)
Minimum
vertical drop
between pump and condensate valve assembly.
flow
Must be connected
to a drain system
in accordance with
local codes.
31
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
9.2 General Venting Requirements Model EP-100, EP-200 and EP-300 Series Pumps
WARNING
Carbon Monoxide Hazard
Heaters installed unvented must be interlocked with sufficient building exhaust.
Heaters must be installed according to the installation manual.
Failure to follow these instructions can result in death or injury.
This heater must be vented in accordance with the rules contained in this manual and with the following national codes and any state, provincial or local codes which may apply: United States: Refer to ANSI Z223.1 (NFPA 54) - latest revision; Canada: Refer to CAN/CGA-B149.1 and B149.2 - latest revision.
Any portion of vent pipe passing through a combustible wall must have an approved thimble to conform with the above listed codes.
Vent pipe must be sloped downward away from the pump ¼'' every 10' (3 m).
The bottom of the vent or air intake terminal shall not be located less than 1
The vent shall not terminate less than 7
' (.3 m) above grade level.
' (2.1 m)
above grade where located adjacent to public walkways.
Vent terminal must be installed at a height sufficient to prevent blockage by snow, and building materials protected from degradation by flue gases.
Secure all joints with #8 x 3/8 sheet metal screws.
9.2.2 Horizontal Venting
See Page 34, Figure 16 through Page 36, Figure 18 for recommended horizontal venting options.
9.2.3 United States Requirements
Vent must terminate at least 3 forced air inlet located within 10
Vent must terminate at least 4
' (1.2 m) horizontally from, or 1' (.3 m) above any
4
' (.9 m) above any
' (3.1 m).
' (1.2 m) below,
door, operable window, or gravity air inlet into any building.
9.2.4 Canadian Requirements
The vent shall not terminate within 6
' (1.8 m) of a
mechanical air supply inlet to any building.
The vent shall not terminate within 3
' (.9 m) of a
window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other appliance.
Length Requirements
See Page 33, Figure 15 through Page 36, Figure 18 for recommended vent lengths and sizes.
Seal all joints with high temperature silicone sealant.
Vent terminal must be beyond any combustible overhang.
9.2.1 Vertical Venting
See Page 33, Figure 15 for recommended vertical venting options.
32
Seal all pipe joints with high temperature silicone sealant in the vent pipe. Insulation and additional sealing measures will be required.
Optional heat exchanger lengths are considered as vent length for length determination.
Subtract 15' (4 m) of maximum allowed vent or outside air duct length per vent elbow if more than three are used.
FIGURE 15: Vertical Venting Configuration
SECTION 9: PUMP INSTALLATION AND VENTING
Approved Vent Cap
2' (.6 m)
Minimum
Approved
Thimble
Flexible Boot
1" (2.5 cm)
P.V.C to drain
system in
accordance
with local
codes.
Clamps
Aluminized Tee
Drain Cap
6"(1.5 cm) 20"(5.1 cm) for EP-300
Part Number Description Part Number Description
01330203 Tee, 4" (10 cm) Aluminized
01330204 Tee, 6" (15 cm) Aluminized
01331900 Damper Coupling, 4" (10 cm)
01335801 Elbow, 4" (10 cm) Aluminized 90°
02718851 Drain Cap, 4" (10 cm)
02718852 Drain Cap Assembly, 6" (15 cm)
90502300 Vent Cap, 4" (10 cm) Metalbestos
90502302 Vent Cap, 6" (15 cm) Metalbestos
91409403 Tube, Aluminized 4" (10 cm) dia. 10' (3 m)
91409420 Tube, Aluminized 6" (15 cm) dia. 10' (3 m)
91412800 Flexible Boot, 4" (10 cm)
91412801 4 - Flexible Boot, 1/2" (1.3 cm)
91412802 Flexible Boot, 6" (15 cm)
91901300 Boot Clamp, 4" (10 cm)
91913703 Boot Clamp, 6" (15 cm)
E0009356 Damper Coupling, 6" (15 cm)
90505600 Wall Thimble, 4" (10 cm)
T0100320 Elbow, 6" (15 cm) Aluminized 90°
33
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
9.3 Horizontal Venting 4" (10 cm) Pipe FIGURE 16: EP-100 Horizontal Venting Configurations
18" (46 cm) Minimum ­40" (102 cm) Maximum
4" (10 cm) Single Wall Pipe
25' (8 m) and 3 Elbows Maximum
Pitch single wall pipe downward away from pump 1/4" (6 mm) for every 10' (3 m).
5" to 4" Reducer
(12.5 cm to 10 cm)
5" (12.5 cm) Single Wall Pipe
50' (15 m) and 3 Elbows Maximum
6" to 5" Reducer
(15 cm to 12.5 cm)
Screen
Approved Thimbles
18" (46 cm) Minimum ­40" (102 cm) Maximum
Vent Terminal Tjernlund VH1-4
Vent Terminal Tjernlund VH1-6
Bird
4" (10 cm) Band Clamp
Part Number Description Part Number Description
01330203 Tee, 4" (10 cm) Aluminized 90505600 Wall Thimble, 4" (10 cm)
01331900 Damper Coupling, 4" (10 cm) 91409403 Tube, Aluminized 4" (10 cm) dia. 10' (3 m)
01335801 Elbow, 4" (10 cm) Aluminized 90° 91412800 Flexible Boot, 4" (10 cm)
01365400 Bird Screen, 4" (10 cm) 91901300 Boot Clamp, 4" (10 cm)
02537801-1P Vent Terminal (Non-Combustible Wall) Not Supplied Tube, Aluminized 5" (12.7 cm) dia. 10' (3 m)
02718851 Drain Cap, 4" (10 cm) Not Supplied Tube Adapter, 5" (12.7 cm) dia. x 4" (10 cm) dia.
90502100 Vent Terminal, 4" (10 cm) (Combustible Wall) Not Supplied Tube Adapter, 6" (15.2 cm) dia. x 5" (12.7 cm) dia.
90502101 Vent Terminal, 6" (15 cm) (Combustible Wall)
34
FIGURE 17: EP-200 Series Horizontal Venting Configurations
m
SECTION 9: PUMP INSTALLATION AND VENTING
18" (46 cm) Minimum ­40" (102 cm) Maximum
4" (10 cm) Single Wall Pipe
10' (3 m) Maximum and No Elbows
Pitch single wall pipe downward away from pump 1/4" (6 mm) for every 10' (3 m).
5" to 4" Reducer
(12.5 cm to 10 cm)
5" (12.5 cm) Single Wall Pipe
25' (8 m) and 3 Elbows Maximum
6" to 4" Reducer (15 cm to 10 cm)
6" to 5" Reducer
(15 cm to 12.5 cm)
Approved Thimbles
18" (46 cm) Minimum ­40" (102 cm) Maximum
4" (10 cm) Vent Terminal
Vent Terminal Tjernlund VH1-4
Vent Terminal Tjernlund VH1-6
Bird
Screen
4" (10 cm) Band Cla
6" (15 cm) Single Wall Pipe
50' (15 m) and 3 Elbows Maximum
Part Number Description Part Number Description
01330203 Tee, 4" (10 cm) Aluminized 91409403 Tube, Aluminized 4" (10 cm) dia. 10' (3 m)
01331900 Damper Coupling, 4" (10 cm)
01335801 Elbow, 4" (10 cm) Aluminized 90° 91412801 4 - Flexible Boot, 1/2" (1.3 cm)
01365400 Bird Screen, 4" (10 cm)
02537801-1P Vent Terminal (Non-Combustible Wall)
02718851 4" Drain Cap
90502100 Vent Terminal, 4" (10 cm) (Combustible Wall)
90502101 Vent Terminal, 6" (15 cm) (Combustible Wall)
90505600 Wall Thimble, 4" (10 cm)
91409420 Tube, Aluminized 6" (15 cm) dia. 10' (3 m)
91418200 Tube Adapter, 6" (15.2 cm) dia. x 4" (10 cm) dia.
91901300 Boot Clamp, 4" (10 cm)
91906900 Silicone Ring
Not Supplied Tube, Aluminized 5" (12.7 cm) dia. 10' (3 m)
Not Supplied Tube Adapter, 5" (12.7 cm) dia. x 4" (10 cm) dia.
Not Supplied Tube Adapter, 6" (15.2 cm) dia. x 5" (12.7 cm) dia.
Vent Terminal Tjernlund VH1-6
35
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 18: EP-300 Series Horizontal Venting Configurations
10' (3 m) Maximum and 1 Elbow
18" (46 cm) Minimum ­40" (102 cm) Maximum
10' (3 m) Maximum and 1 Elbow
6" (15 cm)
Bird Screen
(Included)
Single Wall Pipe/Tube 6" (15 cm)
6" (15 cm)
Band Clamp
Pitch single wall pipe downward away from pump 1/4" ( 6 mm) for
Approved
Thimble
every 10' (3 m).
Vent Terminal
Tjernlund VH1-
6" (15 cm)
or Equivalent
(Not Included)
Part Number Description Part Number Description
01330203 Tee, 4" (10 cm) Aluminized 91409403 Tube, Aluminized 4" (10 cm) dia. 10' (3 m)
01330204 Tee, 6" (15 cm) Aluminized 91409420 Tube, Aluminized 6" (15 cm) dia. 10' (3 m)
01331900 Damper Coupling, 4" (10 cm) 91412800 Flexible Boot, 4" (10 cm)
01335801 Elbow, 4" (10 cm) Aluminized 90° 91412802 Flexible Boot, 6" (15 cm)
01397400 Bird Screen, 6" (15 cm) 91418200 Tube Adapter, 6" (15.2 cm) dia. x 4" (10 cm) dia.
02537801-1P Vent Terminal (Non-Combustible Wall) 91901300 Boot Clamp, 4" (10 cm)
02718851 Drain Cap, 4" (10 cm) 91913703 Boot Clamp, 6" (15 cm)
02718852 Drain Cap, 6" (15 cm) E0009356 Damper Coupling, 6" (15 cm)
90502100 Vent Terminal, 4" (10 cm) (Combustible Wall) T0100320 Elbow, 6" (15 cm) Aluminized 90°
90502101 Vent Terminal, 6" (15 cm) (Combustible Wall)
90502302 Vent Cap, 6" (15 cm) Metalbestos
90505600 Wall Thimble, 4" (10 cm)
36
SECTION 10: OUTSIDE AIR SUPPLY
The CRV-Series system is approved for use with an outside air system. Halogenated hydrocarbons or other corrosive chemicals in the air can be drawn into the equipment and seriously damage the system components. Avoid the use of such chemical compounds near the air inlet to the heaters. IMPORTANT: If the building has a slight negative pressure or contaminants are present in the air, an outside combustion air supply to the heaters is strongly recommended. All joints and seams in the air supply system must be airtight. Attach the filter housing to the burner assembly using the wing nut provided.
10.1 Pressurized
See Page 39, Figure 23 for a typical layout of a pressurized air supply system. For pressurized outside air supplies, the outside air
FIGURE 19: Duct Sizing
SECTION 10: OUTSIDE AIR S UPPLY
blower motor has a pressure switch interlock that must be used. Wire this switch in series with the pump pressure switch. When using an outside air blower with a ROBERTS GORDON
®
or ROBERTS GORDON
ULTRAVAC™ control or
®
System Control
relay transformer, a separate load relay package is required. Wire the control for the relay in parallel with the pump. The outside air blower must have a separate 20A, 120V power supply. See Page 38, Figure 21 for outside air blower internal wiring requirements.
10.2 Non-Pressurized
For a non-pressurized outside air supply, a 4" (O.D.) single wall pipe duct may be attached to the burner and end vent. For length and duct sizing requirements, see duct design rules in Figure 19. To prevent condensation, insulate the outside air duct.
Outside Air System Design Requirements:
Blower Performance (90707501): 112 Flow Units
One outside air blower is required per each EP-100 or EP-200 series pump and two outside air blowers may be required for each EP-300 series pump. Outside air blowers cannot be shared between two separate CRV­Series systems.
Duct Design Rules:
- System should be designed so that the blower is positioned closest to the highest flow requirements (end vents).
- When a duct is carrying more than 40 flow units, it must be at least 6" (15 cm) diameter.
Pressurized Systems
- 6" (15 cm) diameter duct must not exceed 120'
(36 m) total per system.
- 4" (10 cm) diameter duct must not exceed 120'
(36 m) per radiant branch.
Non Pressurized
- 6" (15 cm) diameter duct must not exceed 90'
(27 m) maximum 100 flow units
- 4" (10 cm) diameter duct must not exceed 90'
(27 m)
- Elbows are equivalent to 10' (3 m) of duct length.
37
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
10.3 Outside Air Blower Internal Wiring FIGURE 20: Outside Air Blower Internal Wiring Diagram
Outside air blower is shipped with the blower manufacturer’s standard internal wiring. For use with Roberts-Gordon heaters, the outside air blower must be rewired with existing wires by the electrical contractor. See diagram.
Internal 24 V transformer provided will not be used and can be discarded.
MOTOR
BLOWER
PRESSURE
SWITCH
C
NO
FIGURE 21: Filter Housing Assembly
Door-Control
Housing
Filter
BLK
L
WHT
MN
Filter
Support
BLU BLU
T1 T3T2
4" (10 cm)
Air Flex Duct
38
Filter Housing
Wing Nut
Clamp
Bottom Gasket
Top Gasket
and Disk
Description Part Number
Filter Housing 01326801 Filter and Gaskets 01312401 Filter Support 91905500 Wing Nut 92511601 4" (10 cm) Air Flex Duct (box of eight 8' (2.4 m) sections) 91409601
FIGURE 22: Air Supply Blower Support
Outside
Air Supply
Blower
Wall
5" (12.5 cm)
Inlet Pipe
5" (12.5 cm)
Outlet Pipe
SECTION 10: OUTSIDE AIR S UPPLY
Vent
or
Bird
Screen
Outside
Wall
Description Part Number
Blower 90707501 5" (12.7 cm) Vent Cap 90502302 6" (15 cm) Bird Screen 01397400 6" (15 cm) Band Clamp 91913703
Cap
FIGURE 23: Pressurized Outside Air Supply
Vent Cap or Bird Screen
Burner
Outside
Air Supply
Blower
Outside
Wall
4" (10 cm)
Air Flex Duct
4" (10 cm)
Take Off
Filter
Housing
Clamp
Sheet Metal
or PVC
Description Part Number
Filter Housing 01326801 4" (10 cm) Take Off 01324401 Blower 90707501 5" (12.7 cm) Vent Cap 90502301 6" (15 cm) Bird Screen 01365400 6" (15 cm) Band Clamp 91913703
39
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 24: Non-Pressurized Outside Air Supply
Vent Cap
or
Bird Screen
6' (1.8 m)
Maximum
Outside Wall
Description Part Number
Pressure Switch Kit 90434501 4" (10 cm) Bird Screen 01365400 4" (10 cm) Vent Cap 90502300 6" (15 cm) Vent Cap 90502302
Pressure Switch
Lock Nuts
7/16" (11.1 mm) Diameter Hole
40
SECTION 11: GAS P IPING
SECTION 11: GAS PIPING
WARNING
Fire Hazard
Fire Hazard
Tighten gas hose fittings to connect gas supply
Tighten gas hose fittings to connect gas supply
according to Figure 25.
according to Figure 24.
Gas hose can crack when twisted.
Gas hose can crack when twisted.
Gas hose moves during normal operation.
Gas hose moves during normal operation.
Failure to follow these instructions can result in death, injury or property damage.
Failure to follow these instructions can result in death, injury or property damage.
Install the gas hose as shown in Figure 25. The gas hose accommodates expansion of the heating system and allows for easy installation and service of the burner. Before connecting the burners to the supply system, verify that all high pressure testing of the gas piping has been completed.
There is an expansion of the tube with each firing cycle. This will cause the burner to move with respect to the gas hose. This can cause a gas leak resulting in an unsafe condition if the gas connection is not made in strict accordance with Figure 25. Meter and service must be large enough to handle all the burners being installed plus any other connected load. The gas hose which feeds the system must be large enough to supply the required gas with a maximum pressure drop of 1/2" w.c. When gas piping is not included in the layout drawing, the local gas supplier will usually help in planning the gas piping.
• Do not high pressure test the gas piping with the burner connected. Failure to follow these instructions can result in property damage.
• Check the pipe and tubing ends for leaks before placing heating equipment into service. When checking for gas leaks, use a soap and water solution; never use an open flame.
FIGURE 25: Gas Connection with Flexible Gas Hose
Shut-Off Valve must be
3/4" NPT Pipe
Shut-Off Valve
(Included
With Gas Hose)
12"
2" (5 cm)
parallel to burner gas inlet. The 2" (50 mm) displacement shown is for the cold condition. This displacement may reduce when the system is fired.
(30 cm)
Flexible
Gas
Hose
Hold gas nipple securely with pipe wrench when attaching the gas hose. Failure to follow these instructions can result in product damage.
45°
Horizontal
Rear ViewBurner
Description Part Number
1/2" Flexible Stainless Steel Gas Hose (US Models) 91412200 3/4" Flexible Stainless Steel Gas Hose (US Models) 91412203 1/2" Rubber (Type 1) Gas Hose (Canadian Models) 91412206 3/4" Rubber (Type 1) Gas Hose (Canadian Models) 91412207
41
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 12: CONTROL METHODS
WARNING
Electrical Shock Hazard
Disconnect electrical power and gas supply before servicing.
This appliance must be connected to a properly grounded electrical source.
Failure to follow these instructions can result in death or electrical shock.
There are several methods of controlling CRV-Series systems. The options are as follows:
12.1 ROBERTS GORDON
The System Control is an electronic control panel designed to control CRV-Series heating systems. The System Control wiring is shown on Page 46, Figure 29 through Page 47, Figure 32 and in the System Control Installation Manual (P/N 10091601NA). The System Control can be used to control an EP-100 or EP-201 pump from the control panel. Other pumps such as the EP-301 and 3 phase models may be controlled by a relay or motor starter. The System Control can control up to four zones of burners. The electrical circuit is a 120V AC (20A) supply. The output for the thermostat is 12V DC. Do not use thermostats that draw power from the low voltage supply. A System Control operated system has two minutes post purge pump operation to completely exhaust products of combustion from the system. A system control provides indication of power to the pump and the zones as well as indicating the status of the pressure switch with lights. The System Control is UL listed in accordance with UL873 – Temperature Indicating and Regulating Equipment.
®
System Control
12.2 ROBERTS GORDON
®
ULTRAVAC
TM
The ROBERTS GORDON® ULTRAVACTM is a micro processor based control package designed for modulating control of CRV-Series heaters based on outdoor temperatures. The controls offer full modulation between 60% and 100% of system maximum rated input. This controller is capable of giving control outputs to one pump and three heating zones. The controller also features inputs which are used for indoor and outdoor signal condition monitoring. System status and settings are viewed and altered from a PC (not supplied) running ROBERTS GORDON ROBERTS GORDON requires a PC (not supplied) running Windows higher, with a Pentium
®
ULTRAVACTM Software.
®
ULTRAVACTM Software
®
class processor and at least
®
95 or
64k of RAM.
Special design requirements apply for CRV-
®
Series systems using the ROBERTS GORDON ULTRAVAC
TM
Controller.
12.3 SPST Transformer Relay (P/N 90417600)
The transformer relay wiring diagram is shown on Page 43, Figure 26. The transformer relay can be
used to control an EP-100 or EP-201 pump CORAYVAC
®
system. The single pole relay can only be used to control one zone of burners. The electrical circuit is a 120V AC (20 A) supply. The transformer 24V AC output for the thermostat is rated at 40 V A. Thermostats used with the transformer must not exceed this power requirement. A transformer relay operated system will not give any post purge pump operation to completely exhaust products of combustion from the system or provide indication of operating conditions.
12.4 DPST Transformer Relay (P/N 90436300)
The transformer relay wiring diagram is shown on Page 45, Figure 28. The transformer relay can be
used to control an EP-100 or EP-201 pump
®
CORAYVAC
system. The double pole relay can only be used to control two zones of burners. The electrical circuit is a 120V AC (20A) supply. The transformer 24V AC output for the thermostat is rated at 40VA. Thermostats used with the transformer must not exceed this power requirement. A transformer relay operated system will not give any post purge pump operation to completely exhaust products of combustion from the system or provide indication of operating conditions.
42
FIGURE 26: One Zone Operation without Control Panel
SPST (12A)
Transformer
Thermostat
Relay
SECTION 12: CONTROL METHODS
C
R
W
G
Y
120 V
1 Ø
60 Hz
Ground
Pump Motor
Black
L
N
Black
White
1
4
COIL COIL
3
2
6
5
Red
LN
NL
Description Part Number
SPST Transformer Relay 90417600
Pressure
Switch
(Pump)
Zone 1
Burners
Nine Burners Maximum
43
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 27: One Zone Operation (with Outside Air Blower) without Control Panel
SPST (12 A)
Transformer
Relay
R
W
G
Thermostat
C
Y
Outside Air
Blower
N
L
120 V
1 Ø
60 Hz
L
N
Ground
Pressure Switch
(Outside Air Blower)
Black
1
3
2
4
COIL COIL
6
5
Black
White
Red
LN
NL
44
Pressure
Switch
(Pump)
Pump Motor
Zone 1
Burners
Nine Burners Maximum
FIGURE 28: Two Zone Operation without Control Panel
SECTION 12: CONTROL METHODS
Zone 1
Thermostat
120 V
1 Ø
60 Hz
L
COIL
White
DPST (12 A)
Transformer
Relay
C
R
G
W
Y
Purple Red
1
3
2
6
4
COIL
5
Red
Black
Black Black
Zone 2
Thermostat
Purple
Red/Yellow
Black
DPST (12 A) Transformer
Relay
R
C
G
W
1
3
2
4
5
6
COIL
COIL
Y
Red/YellowWhite
N
Description Part Number
DPST Transformer Relay 90436300
NL
Pump Motor
Pressure
Switch
(Pump)
LNLN
Zone 1
Burners
Nine Burners Total
Maximum Between Zones
Zone 2
Burners
45
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 29: General System Wiring
Burner Receptacles 4 Zone Max
Thermostats
120 V
1 Ø
60 Hz
L
N
120 Vac
Maximum 20 Amps Total
Pressure Switch
Pump Motor 115 Vac Operation
(230 Vac Operation­separate power circuit required for EP-203 or EP-300 series pumps)
Motor Starter
(Needed for EP-203 and EP-300 Series Pump)
Outside Air Supply Blower Motor and Pressure Switch
FIGURE 30: External Wiring Diagram EP-100 and EP-201 120 V 1 Ø Pump
All burners must be connected to Ground (Not shown)
Zone 1
Zone 2 Zone 3 Zone 4
Pump
Low voltage thermostats
located in heated zone
Zone1Zone
2
120 V 1 Ø 60 Hz
L
N
120 V 1 Ø 60 Hz
Ground
Zone
3
Zone
4
Pressure switch located at pump
12 Vdc
46
Ground
GLN
NLL
NN
Z1
Z2
N
L
Z3 Z4
L
System Control
NL
PUMP
CT1C
CCC
T3T2T4
PS
FIGURE 31: External Wiring Diagram EP-301 120 V 1 Ø Pump
EP 301
Pump
Do not directly connect the controller relay terminals to the pump motor. Product damage will result.
All burners must be connected to Ground. (Not shown.)
Zone 1 Zone 2 Zone 3 Zone 4
64
M
3
5
120 V 1 Ø
120 V
60 Hz
1 Ø 60 Hz
L
N
Ground
IEC contactor (P/N
10050009) rated for the EP 301 pump motor
The power supply for the
2
pump must be separate from the controller supply.
1
N
L
Low voltage thermostats
located in heated zone.
Zone1Zone
Zone
2
3
230 V 1 Ø 60 Hz
Zone
4
SECTION 12: CONTROL METHODS
Individual supply for pump rated for total full load current.
Pressure switch located at pump.
12 Vdc
Ground
GLN
NN
Z1
Z2
N
Z3 Z4
NLLLL
NL
PUMP
C
T1T3T2
C
CCC
T4
PS
System Control
FIGURE 32: External Wiring Diagram EP-203 or EP-303 208 V - 230 V (or 460 V) 3 Ø Pump
Motor starter (P/N 10050001) rated for EP-203 pump motor; motor starter (P/N 10050010) rated for EP-303 pump motor.
All burners must be connected to Ground. (Not shown.)
Zone 1
Zone 2 Zone 3 Zone 4
EP-203 or
EP- 303 3 Ø Pump
The power supply for the pump must be separate from the controller supply.
OL
Do not directly connect the controller relay terminals to the pump motor. Product damage will result.
208 - 230 V (or 460 V) 3 Ø 60 Hz
L3
L2 L1
Zone
2
3
Individual supply for pump rated for total full load current.
Zone
4
Pressure switch located at pump.
120 V 1 Ø 60 Hz
M
120 V 1 Ø 60 Hz
L
N
Low voltage thermostats
located in heated zone.
Zone1Zone
Ground
Ground
GLN
NN
Z1
Z2
L
N
Z3 Z4
NLL
System Control
L
NL
PUMP
CT1C
CCC
T3T2T4
12 Vdc
PS
47
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 33: Burner Internal Wiring
Black
120 V
Power Supply
Green
TRANSFORMER
White
1
3
5
Yellow
4
Blue
Green
GAS
VALVE
Yellow
Brown
Yellow
Black
TH
V1 S1 V2/GND
IGNITION
MODULE
BURNER
If any of the original wire as supplied with the heater must be replaced, it must be replaced with
wiring material having a temperature rating of at least 105°C and 600 volts.
FIGURE 34: Burner Internal Ladder Diagram
L1
TRANSFORMER
Black
L2
White
Yellow
48
ELECTRODE
Gap
Black
V2
Gnd
Blue
S1 V1
TH
Yellow
Brown
GAS VALVE
IGNITION MODULE
SECTION 13: STARTING THE SYSTEM
Start with the main gas valve closed and the electric power off.
13.1 Checking the Gas Line
1. Open the main valve and verify that no gas is flowing through the meter.
2. Purge the line if this was not done following pressure testing with air.
3. Verify that the gas pressure is not above 14'' w.c. (1/2 PSIG).
4. Close the main gas valve.
13.2 Checking the Electrical System
1. See that all temperature setpoints are set below room temperature.
2. Turn on power supply to system controls.
3. Check to see that no part of the system (i.e. burners, pump or air supply blower) is powered.
4. Individually check each zone by raising the zone temperature set points separately. Raising each zone temperature set point above room temperature should start the pump immediately. After a 45 second delay, the burners will begin their ignition sequence by sparking at the electrode (visible through the burner window).
5. Make a preliminary vacuum check at burners in branches that have an adjustable damper coupling. See Page 50, Figure 35 for manome- ter hookup to check vacuum. This check is to insure that all dampers are open before the system is fired. Vacuum, as measured at the end vents, should be approximately 3.5'' w.c. or slightly above (cold).
13.3 Starting the System NOTE: During the initial firing, the protective oil on
the tubing may smoke for 30 to 60 minutes and adequate ventilation should be provided.
1. Start with all temperature setpoints below room temperature.
2. Open main gas valve.
3. Turn up temperature setpoints one zone at a time, waiting to see that all burners in a zone start. When the burner ignites, a blue flame will be observed through the viewer window.
4. If any abnormal operation occurs, see the trou­bleshooting section of the service instructions.
13.4 Setting the Vacuum
1. Set temperature setpoints above room tempera­ture. See that all burners are operating properly.
SECTION 13: STARTING THE S YSTEM
2. Allow at least ½ hour operation for temperature to normalize, then check system vacuum bal­ance. Vacuum can be measured by inserting a manometer hose into the end vent as shown on Page 50, Figure 35. Normal end vent vacuum should w.c.
be set at approximately 2.5'' w.c. to 3.0''
(hot). Vacuum adjustments are made by means of the damper in the pump inlet and the adjustable damper coupling(s) in the system. Check the vacuum at all end vents and then adjust the damper coupling to obtain equal vacuum readings of
2.5'' w.c. to 3.0'' w.c.
If end vent vacuum exceeds 3.0" w.c., adjust the pump inlet damper until vacuum readings are
2.5'' w.c. to
3.0'' w.c. With systems designed to operate at maximum vacuum, it may not be possible to obtain vacuum differential readings at or slightly above
2.5'' w.c. If so, adjust the damper couplings to maximum but equal vacuum reading. Be sure to lock all dampers securely after adjustment.
3. Reset temperature setpoints to desired room temperature.
4. If heat is not required, turn off main switch and close the main gas valve.
49
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 35: Vacuum Reading
Combustion Chamber
at end position
End Vent
Insert tubing
about 6" (15 cm).
6
Manometer
5
4
3
2
1
0
1
2
3
4
5
6
Approximate reading after
adjusting damper couplings and
pump inlet. ( 2.5"- 3.0" w.c.)
~
~
50
SECTION 14: OPERATION AND MAINTENANCE
The heater is equipped with a direct-spark ignition system.
14.1 Sequence of Operation
1. Turn the thermostat up. When the thermostat calls for heat, the pump will start immediately. After a short period, the burners will begin their ignition sequence. Sparking will begin at the electrodes and the gas valve will be energized 45 seconds later.
2. The flame will be sensed by the flame sensing rod and the electrode is de-energized.
3. If a flame is detected, the gas valve remains open. When the call for heat is satisfied, the burner shuts off. On CRV-Series systems equipped with the optional ROBERTS
®
GORDON GORDON
System Control, or ROBERTS
®
ULTRAVACTM, the pump will continue operation for a post-purge period of two minutes.
4. If no flame is detected, the module will close and a purge period begins. If a flame is not established, a second purge and warm-up will take place and then a third trial cycle will begin. After three trials, the module will lockout for one hour or until reset.
5. A reset is accomplished by removing power from the module for at least 5 seconds (thermo­stat cycle is required) or automatically after 1 hour.
14.2 To Shut Off Heater
Set thermostat to lowest setting. Turn OFF electric power to heater. Turn OFF manual gas valve in the heater supply line.
14.3 To Start Heater
Turn gas valve and electric power OFF and wait five minutes for unburned gases to vent from heater. Turn ON main gas valve. Turn ON electric power. Set thermostat to desired temperature. Burner should light automatically.
SECTION 14: OPERATION AND MAINTENANCE
14.4 Pre-Season Maintenance and Annual Inspection
WARNING
Explosion Hazard
Service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
To ensure your safety and years of trouble-free operation of the heating system, service and annual inspections must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Turn off gas and electric supplies before performing service or maintenance. Allow heater to cool before servicing. Before every heating season, a contractor qualified in the installation and service of gas-fired heating equipment must perform a thorough safety inspection of the heater. For best performance, the gas, electrical, thermostat connections, tubing, venting, suspensions and overall heater condition should be thoroughly inspected. NOTE: Gas flow and burner ignition are among the first things that should be inspected. Please see Page 52, Section 14.5 for suggested items to inspect.
51
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
14.5 Maintenance Checklist Installation Code and Annual Inspections:
WARNING
All installations and service of ROBERTS GORDON products must be performed by a contractor qualified in the installation and service of products sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON manuals and all applicable governmental authorities pertaining to the installation, service and operation of
Explosion Hazard
Service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
the equipment. To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON
®
products and
perform service where necessary, using only
®
ROBERTS GORDON
replacement parts.
The Vicinity of the Heater Do not store or use flammable objects, liquids or vapors near the heating sys-
tem. Immediately remove these items if they are present.
See Page 3, Section 3.
®
®
Vehicles and Other Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes or in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
See Page 3, Section 3.
Reflector Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped. See Page 19, Figure 7.4.3.
Clean outside surface with a damp cloth.
Vent Pipe Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe or gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
Outside Air Inlet Inlet must be intact. Look for obstructions, cracks on the pipe or gaps in the
sealed areas or corrosion.
52
The area must be free of dirt and dust. Clean and reinstall as required.
Tube s Make sure there are no cracks.
Make sure tubes are connected and suspended securely.
See Page 15, Figure 12 through Page 17, Section 7.2.1.
Make sure there is no dirt, sagging, bending or distortion.
Clean or replace as required.
Gas Line Check for gas leaks. See Page 41, Figure 25.
SECTION 14: OPERATION AND MAINTENANCE
Combustion Chamber Window
Blower Scroll, Wheel and
Make sure it is clean and free of cracks or holes.
Clean or replace as required.
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
Motor
Burner Head and Orifice Make sure it is clear of obstructions. (Even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Electrode Replace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8" (3 mm).
Thermostat or Sensor There should be no exposed wire or damage to the thermostat or sensor.
Suspension Points Make sure the heater is hanging securely. Look for signs of wear on the chain
or ceiling.
See Page 15, Figure 12.
Decorative and Protective Grille (optional)
The grille must be securely attached.
Check that side reflector extensions are installed correctly and secured in place if necessary. (Decorative grille only.)
See Page 25, Section 8.6.1 through Page 28, Section 8.7.5
Make sure shield is installed correctly and secured in place if necessary. (Decorative grille only.) See Page 25, Section 8.6.2.
53
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Pump With pump operating, check for excessive vibration or noise. Vibration is usu-
ally a sign that the impeller is out of balance. Turn off the system, insure power is shut off and remove the inlet plate. Check the shaft seal and replace it if worn or missing.
With the Power off:
Check the inlet and outlet of the pump for blockage or excessive soot and clean as necessary.
Check boots for cracking or deterioration and replace if necessary.
If a condensate trap is installed, check the condition of the trap and the drain line attached. Note: the condensate trap should be filled with water at the beginning of each heating season.
Check the condition of the motor mounts. Lift the motor from the rear; look for breaks in the rubber and replace if necessary.
Check the condition and operation of the pressure switch.
54
SECTION 15: TROUBLESHOOTING
15.1 Troubleshooting Flow Chart
SECTION 15: TROUBLESHOOTING
Is the motor connected properly?
Refer to the wiring diagrams on the
motor and in the installation manual.
No
Motor may have tripped
overload switch. Wait 10-15
Ye s
Is the motor hot?
Ye s
minutes for automatic reset.
obstructed?
Is the pump impeller
No
No
turn freely?
motor. Does the motor
Disconnect power to the
No
at end vent.
Check for proper vacuum
Ye s
failed. Replace motor.
Motor bearings may have
No
Correct gas problem.
module begin ignition
seconds, then plug it in
sequence by sparking?
again. Does the ignition
Unplug the burner, wait 10
Ye s
and flow to the burners?
Is there proper gas pressure
Ye s
Troubleshoot Ends
Ye s
No
Do the burners light?
Check LED on module and
Pre-purge. Wait 45 seconds.
Replace ignition module.
Ye s
No
and yellow wires)?
refer to LED codes below.
Is there 24V at the burner
Replace burner transformer.
transformer secondary (blue
No
Module Diagnostic Codes:
within module
LED Problem Solution
4 second steady
flash at start of cycle Normal Wait for valve to open
Steady on Microprocessor failure Replace module
Lockout of module spark and valve opening and
after 3 tries replace:if none, replace module
Three flashes Ignition lockout Recycle unit: check for
replace thermostat if
Check thermostat wiring and
No
necessary.
Refer to control
panels listed below.
Does pump turn on?
Ye s
No
the control?
(panel or relay)
Is there power (120V) to
No
fuse on panel supply circuit.
Check circuit breaker and/or
START
Turn up thermostat.
Does the pump turn on?
Check wiring to the burner.
Make sure the burner is
No
plugged in.
Ye s
burner receptacle?
Is there power (120V) at the
Ye s
manuals list.
Refer to control panel
Is there power to the zone?
No
After 45 seconds pre-purge
period, do the burners light?
No
panel list.
Refer to control
vacuum at the end vent.
Adjust system for proper
Ye s
No
too high?
Is the vacuum setting
No
Ye s
Ye s
smoothly?
Do all the burners ignite
Wrong end vent plate may
be installed. Make sure plate
and burner match.
55
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Troubleshooting Flow Chart
Couplings may be installed
should be used for tailpipe.
improperly. Lined couplings
No
Yes
burners dirty?
failed. Replace module.
Ignition module may have
No
Are the filters on the
Yes
ULTRAVAC P/N: 10081601NA
®
Pump IOS Manuals:
- EP-100 P/N: 127201NA
- EP-200 P/N: 127200NA
- EP-300 P/N: 127202NA
leaks in the system.
outside air supply or for
Replace filters as necessary.
Check for blockage in the
No
Control Panel IOS Manuals:
- For systems with no control panel, refer
- System Control P/N: 10091601NA
to appropriate control manufacturers instructions.
- ROBERTS GORDON
Yes
Adjust the gap or
Electrode gap should be
1/8". Is the gap too small?
No
burned or damaged?
affected burners. Are they
Inspect the electrodes on the
Yes
replace the electrode.
Yes
Replace the electrodes.
No
Is the rotation of the
pump motor correct?
No
Yes
Are there any "dead"
burners in a branch?
No
Yes
too low?
Is the vacuum setting
Yes
burners dirty?
for reversal instructions.
pump manuals listed below
Consult wiring instructions in
Follow burner check
procedure given above.
vacuum at the end vent.
Adjust system for proper
Are the filters on the
Yes
Is the rotation of the
pump motor correct?
No
too low?
Is the vacuum setting
Yes
Yes
Replace filters as necessary.
No
for reversal instructions.
pump manuals listed below
Consult wiring instructions in
Yes
vacuum at the end vent.
Adjust system for proper
listed below.
panel manuals
Refer to control
Yes
Make sure that all
sensors are satisfied.
thermostats or internal
No
listed below.
panel manuals
Refer to control
Yes
Make sure that all
sensors are satisfied.
thermostats or internal
No
Contact
www.rg-inc.com
Roberts-Gordon at
No
56
Yes
intermittently?
Do the burners lockout
No
Is the system leaking water?
No
Is the flame low?
No
call for heat is satisfied?
Do burners shut off after the
Yes
period?
Does the pump shut down
after a 2 minute post-purge
Independent
®
Yes
your
TROUBLESHOOT ENDS.
If problems persist, contact
ROBERTS GORDON
Distributor.
SECTION 16: REPLACEMENT PARTS Use only genuine ROBERTS GORDON
®
replacement parts. Use of parts not specified by Roberts-Gordon voids warranty. Failure to follow these instructions can result in property damage.
Gasket (Burner to Mixing Chamber)
SECTION 16: REPLACEMENT PARTS
Burner Head
Ignition Cable
Electrode
Electrode Gasket
Mixing Chamber
Combustion
Chamber
Gasket
F OF
ON
Gas Valve
Transformer
Ignition Module
Regulator
Description Part Number
Gas Valve (All Burners) 90032502 Gasket (Burner to Mixing Chamber) 01351100 Burner Head Assembly Replacement Package 02713000 Mixing Chamber 02790400 Transformer 90436900K Regulator 90207100 Gasket (Combustion Chamber) 01367800 Electrode Replacement Kit (includes electrode, electrode gasket and mounting screws) 02713200 Ignition Module 90439500 Ignition Cable 90427706 Filter Cartridge with Gasket (not shown) 01312401
57
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 17: GENERAL SPECIFICATIONS
17.1 Material Specification
17.1.1 Reflectors
.024
Aluminium (Optional - 024 Stainless Steel Type 304).
17.2 Heater Specifications
17.2.1 Ignition
Fully Automatic, Three-Try, Direct Spark, Electronic Ignition Control, 100% Safety Shut-Off.
17.3 Suspension Specifications
Hang heater with materials with a minimum working load of 75 lbs (33 kg). See Page 15, Figure 12.
17.4 Controls Specifications
Time switches, thermostats, etc. can be wired into the electrical supply. External controls supplied as an option.
General Specifications for CRV-Series heaters are as follows:
9 1/2"
(24 cm)
6 1/2"
(16 cm)
14 1/4"
(36 cm)
6 7/8"
(17 cm)
5/32"
(.4 cm)
10 3/4"
(27 cm)
4"
(10 cm)
20"
(51 cm)
10"
(24.4 cm)
7 5/8"
(19 cm)
3 1/2"
(9 cm)
Reflector
Heat Input Rate Length “A”
Length "A"
Recommended Minimum
Mounting Height*
Model (Btu/h) x (1000) Minimum Maximum Spot Heating
CRV-B-2 (NG only) 20 10' (3 m) 20' (6.1 m) 8' (2.4 m)
CRV-B-4 40 12.5' (3.8 m) 25' (7.6 m) 8' (2.4 m)
CRV-B-6 60 20' (6.1 m) 35' (10.7 m) 8' (2.4 m)
CRV-B-8 80 20' (6.1 m) 45' (13.7 m) 10' (3 m)
CRV-B-9 90 25' (7.6 m) 50' (15.2 m) 10' (3 m)
CRV-B-10 100 30' (9.1 m) 60' (18.3 m) 15' (4.5 m)
CRV-B-12A (NG only) 110 35' (10.7 m) 70' (21.3 m) 15' (4.5 m)
CRV-B-12 (LP only) 120 35' (10.7 m) 70' (21.3 m) 15' (4.5 m)
*See Page 3, Section 3 for clearances to combustibles.
PIPE CONNECTION:
1/2" NPT
DIMENSIONS:
Vent Connection Size: 4" (10 cm) or 6" (15 cm) Outside Air Connection Size: 4" (10 cm) Refer to figure above for dimensional information.
GAS INLET PRESSURE:
Natural Gas: 4.5" w.c. Minimum 14.0" w.c. Ma x imum LP Gas: 10.5
" w.c. Minimum 14.0" w.c. Maximum
ELECTRICAL RATING:
120 V - 60 Hz, 0.3 A
58
SECTION 17: GENERAL SPECIFICATIONS
General Specifications for pumps are as follows:
Pump Dimensional Data (in.) Model A B C D E F G EP-100 17 14.5 21 3.75 10 4 4 EP-201/203 17.75 17 20.25 3.25 10 4.5 4.5 EP-301/303 25.6 24.8 22.7 4.8 15.2 6 6
A
C
G
D
B
F
dia.
E
Pump Specifications
Model EP-100 EP-201 EP-203 EP-301 EP-303
Horsepower (Hp) 1/3 3/4 3/4 2* 2* Phase (Ø) 11313
Hertz (Hz) 60 60 60 60 60
Voltage (V) 115/230 115/230 208-230/460 208-230 208-230/460
Full Load Amp (Amps) 4.8/2.4 6.6/3.3 2.4-2.2/1.1 12.8-11.5 5.5-5.2/2.6
R.P.M. 3450 3450 3500 3450 3450
Motor Frame 56 56 56 90 90
Motor Enclosure TENV TENV TEFC TEFC TEFC
Noise Level @ 5' (DBA) - 70 70 - -
Inlet/Outlet (In.) 4/4 4/4 4/4 6/6 6/6
Weight (lbs.) 62 112 112 170 170
* For starter, see National Electric Code (NEC) requirement for motors 1 hp or higher.
Air Supply Blower Specifications
Capacity 240 CFM @ 0.75 in wc
Power (W) 167
Phase 1
Hertz (Hz) 60
Voltage (V) 120
Full Load Amp (Amps) 1.5
R.P.M. 3000
Motor Enclosure OPEN FC
Inlet/Outlet (In.) 5/5
Weight (lbs.) 10
59
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
60
SECTION 18: THE ROBERTS GORDON® CORAYVAC® LIMITED WARRANTY
SECTION 18: THE ROBERTS GORDON
®
CORAYVAC® LIMITED WARRANTY
ROBERTS-GORDON WILL PAY FOR:
Within 42 months from date of shipment from Roberts­Gordon, replacement parts will be provided free of charge for any part of the product which fails due to a manufacturing or material defect.
Roberts-Gordon will require the part in question to be returned to the factory. Roberts-Gordon will, at its sole discretion, repair or replace after determining the nature of the defect and disposition of part in question.
®
ROBERTS GORDON combustion chamber of the CORAYVAC
warrants the cast iron
®
Classic System will be free from defects in material and workmanship. This warranty is limited to twenty-five (25) years from the date of shipment by Roberts­Gordon. All other components of the CORAYVAC
®
Classic System adhere to the standard warranty listed in the paragraph above.
®
ROBERTS GORDON
Replacement Parts are warranted for a period of 18 months from date of shipment from Roberts-Gordon or the remaining CORAYVAC
®
warranty.
ROBERTS-GORDON WILL NOT PAY FOR:
Service trips, service calls and labor charges. Shipment of replacement parts. Claims where the total price of the goods have not
been paid.
Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the CORAYVAC
• Use of the CORAYVAC
®
in any way.
®
for other than its intended
purpose.
• Incorrect gas or electrical supply, accident, fire, floods, acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or accessories not specified by Roberts-Gordon.
®
• Failure to install or maintain the CORAYVAC
as directed in the Installation, Operation and Service Manual.
®
• Relocation of the CORAYVAC
after initial
installation
®
• The use of the CORAYVAC
in a corrosive
atmosphere containing contaminants.
®
• The use of the CORAYVAC
in the vicinity of a
combustible or explosive material.
®
• Any defect in the CORAYVAC
arising from a drawing, design, or specification supplied by or on behalf of the consumer.
• Damage incurred during shipment. Claim must be filed with carrier.
WARRANTY IS VOID IF:
The CORAYVAC® is not installed by a contractor qualified in the installation and service of gas fired heating equipment.
You cannot prove original purchase date and required annual maintenance history.
The data plate and/or serial number are removed, defaced, modified or altered in any way.
The ownership of the CORAYVAC
®
is moved or
transferred. This warranty is nontransferable.
Roberts-Gordon is not permitted to inspect the damaged controller and/or component parts.
READ YOUR INSTALLATION, OPERATION AND SERVICE MANUAL
If you have questions about your controller, contact your installing professional. Should you need Replacement Parts or have additional questions, call or write Roberts­Gordon:
U.S.A.
1250 William Street P. O . B ox 44 Buffalo, New York 14240-0044
716.852.4400
On the web at: www.rg-inc.com
Roberts-Gordon's liability, and your exclusive remedy, under this warranty or any implied warranty (including the implied warranties of merchantability and fitness for a particular purpose) is limited to providing replacement parts during the term of this warranty.
Some jurisdictions do not allow limitations on how long an implied warranty lasts, so this limitation may not apply to you. There are no rights, warranties or conditions, expressed or implied, statutory or otherwise, other than those contained in this warranty.
Roberts-Gordon shall in no event be responsible for incidental or consequential damages or incur liability for damages in excess of the amount paid by you for the CORAYVAC
®
. Some jurisdictions do not allow the
exclusion or limitation of incidental or consequential damages, so this limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from jurisdiction to jurisdiction.
Roberts-Gordon shall not be responsible for failure to perform under the terms of this warranty if caused by circumstances out of its control, including but not limited to war, fire, flood, strike, government or court orders, acts of God, terrorism, unavailability of supplies, parts or power. No person is authorized to assume for Roberts-Gordon any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF REPRESENTATIVES:
No representative of Roberts-Gordon, other than an Executive Officer, has authority to change or extend these provisions. Changes or extensions shall be binding only if confirmed in writing by Roberts-Gordon's duly authorized Executive Officer.
61
OWNER WARRANTY REGISTRATION CARD
®
Roberts Gordon, LLC 1250 William Street, P.O. Box 44  Buffalo, NY 14240-0044  Phone: 716-852-4400  Fax: 716-852-0854
About the Owner:
Name: Address: City: State: Zip Code: Phone: Fax: E-mail:
About the Installer:
Name: Address: City: State: Zip Code: Phone: Fax: E-mail:
Purchased From (if different than installer):
Name: Address: City: State: Zip Code: Phone: Fax: E-mail:
About your Heater:
Model#: Serial #: Fuel: Installation Date:
Type of Installation (check one):
o Automotive o Manufacturing o Warehouse o Recreational o Aircraft o Public Building o Office o Retail o Agricultural o Other
Toll Free: 800-828-7450  www.rg-inc.com
Mail or Fax to:
Installation Code and Annual Inspections: All installations and service of ROBERTS GORDON® products must be performed by a
contractor qualified in the installation and service of products sold and supplied by Roberts-Gordon and conform to all requirements
®
set forth in the ROBERTS GORDON
manuals and all applicable governmental authorities pertaining to the installation, service and
operation of the equipment.
To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your
®
ROBERTS GORDON
products and perform service where necessary, using only ROBERTS GORDON® replacement parts.
This product is not for residential use.
This product is intended to assist licensed professionals in the exercise of their professional judgement.
© 2006 Roberts-Gordon, LLC - All rights reserved. No part of this work covered by the copyrights herein my be reproduced or copied
in any form or by any means  graphic, electronic, or mechanical, including photcopying, recording, taping, or information storage and retrieval systems  without written permission of Roberts Gordon, LLC. Printed in the U.S.A.
®
Attach this information to a wall near the ROBERTS GORDON
heater.
®
Infrared Heating
Read the Installation, Operation, and Service Manual thoroughly before installation, operation, or service.
Know your model number and installed configuration.
Model number and installed configuration are found on the burner and in the Installation, Operation and Service Manual.
Write the largest clearance dimensions with permanent ink according to your model number and configuration in the open spaces below.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting.
TO TURN OFF THE HEATER
1. Set the thermostat to off or the lowest setting.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your registered installer/contractor qualified in the installation
and service of gas-fired heating equipment.
Some objects can catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
WARNING
Fire Hazard
Maintain ???? cm clearance
to the side and
???? cm clearance below
the heater from vehicles
and combustible materials.
Roberts-Gordon, LLC
1250 William Street P.O. Box 44 Buffalo, NY 14240-0044 USA Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
Installation Code and Annual Inspections:
All installations and service of ROBERTS GORDON in the ROBERTS GORDON recommends that a qualified contractor annually inspect your ROBERTS GORDON
© 2006 Roberts-Gordon, LLC All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means  graphic, electronic, or mechanical, including photocopying,
www.rg-inc.com Printed in U.S.A. P/N 91037912 Rev. C
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon
recording, taping, or information storage and retrieval systems  without written permission of Roberts-Gordon, LLC.
Roberts-Gordon Europe Limited
Oxford Street Bilston, West Midlands WV14 7EG UK Telephone: +44(0) 1902 494425 Fax: +44(0) 1902 403200
®
products must be performed by a contractor qualified in the installation and service of products sold and supplied by Roberts-Gordon and conform to all requirements set forth
®
products and perform service where necessary, using only ROBERTS GORDON® replacement parts.
Service Telephone: +44(0) 1902 498733 Service Fax: +44(0) 1902 401464 E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
Loading...