Roberts Gorden CRT-10, CRT-15, CRT-30, CRT-20, CRT-25 Installation, Operation & Service Manual

Page 1
WARNING
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Leave the building.
6. Immediately call your local gas supplier after leaving the building. Follow the gas suppliers instructions.
7. If you cannot reach your gas supplier, call the Fire Department.
Fire Hazard
Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appliance.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
Roberts-Gordon
Oxford Street
Bilston, West Midlands WV14 7EG UK
Telephone: +44(0) 1902 494425 Fax: +44(0) 1902 403200 Service Telephone: +44(0) 1902 498733 Service Fax: +44(0) 1902 401464 E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
www.rg-inc.com
WARNING
Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the installation, operation and service manual thoroughly before installing or servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
© Copyright 2004 Roberts-Gordon
Quality in Any Language™
CoRayVac
®
Custom-Engineered,
Low-Intensity Infrared
Heating Systems
Installation, Operation &
Service Manual
CRT-10 CRT-15 CRT-20 CRT-25 CRT-30
128100UK Rev. B 09/04
Page 2
Page 3
© 2004
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon.
Printed in U.K.
TABLE OF CONTENTS
SECTION 1: Heater Safety ............................................2
1.1 Manpower Requirements ...................................2
SECTION 2: Installer Responsibility ...........................2
2.1 Low Level User Instructions................................2
2.2 Corrosive Chemicals...........................................3
2.3 National Standards and Applicable Codes .........3
SECTION 3: Critical Considerations............................4
3.1 Required Clearances to Combustibles ...............4
3.2 Clearance Data...................................................5
SECTION 4: Major Components ..................................7
4.1 Standard Parts List .............................................9
SECTION 5: Heater Installation..................................10
5.1 Tube Installation ...............................................12
5.2 Coupling and Tube Assembly...........................12
5.3 Reflector Installation .........................................13
5.4 Burner Installation.............................................16
SECTION 6: Optional Heater Accessories ................17
6.1 Elbow Configuration .........................................17
6.2 Reflector Side Extension ..................................18
6.3 One Foot Decorative Grille ...............................19
6.4 Protective Grille Installation ..............................21
6.5 Sports Hall Guard Installation...........................22
6.6 Sports Hall Filter...............................................23
SECTION 7: Pump Installation and Venting .............24
7.1 Mounting Wall Bracket Assembly .....................24
7.2 Building Ventilation ...........................................26
7.3 Condensate Drain Assembly ............................27
7.4 Acoustic Enclosure (Optional) ..........................28
SECTION 8: Outside Air Supply.................................30
SECTION 9: Gas Piping ..............................................31
SECTION 10: Wiring....................................................32
SECTION 11: Operation and Maintenance................34
11.1 Sequence of Operation...................................34
11.2 Commissioning and Testing............................35
11.3 System Checks...............................................35
11.4 User Instructions.............................................35
11.5 ECA Approved Systems .................................35
SECTION 12: Servicing Instructions .........................36
12.1 Annual Service Procedure..............................36
12.2 Component Removal ......................................36
12.3 Maintenance Checklist ...................................37
SECTION 13: Troubleshooting ...................................39
13.1 Troubleshooting Flow Chart ............................39
SECTION 14: Replacement Parts...............................42
SECTION 15: Specifications ......................................43
15.1 Material Specifications....................................43
15.2 Burner Specifications......................................43
15.3 Venting Specifications ....................................43
15.4 Suspension Specifications..............................43
15.5 Controls Specifications ...................................43
15.6 CORAYVAC
®
Heater.......................................43
15.7 Burner Specifications......................................44
15.8 Pump Dimensions and Specifications ...........45
Page 4
Page 5
TABLE OF FIGURES
Figure 1: Standard Reflector ...........................................5
Figure 2: One Side Reflector ..........................................5
Figure 3: Two Side Reflectors .........................................5
Figure 4: 2-Foot Deco Grille............................................6
Figure 5: Protective Grille and 1 Foot Deco Grille...........6
Figure 6: Major Component Descriptions .......................7
Figure 7: Major Component Descriptions (Continued)....8
Figure 8: Critical Hanger Placement.............................10
Figure 9: CORAYVAC
®
Assembly Overview ................11
Figure 10: Wall Bracket Assembly ................................24
Figure 11: Mounting Platform Options ..........................24
Figure 12: Pressure Switch Installation .........................25
Figure 13: Pump Discharge Side ..................................25
Figure 14: Pump Inlet Side 100 mm (4") .......................26
Figure 15: Pump Inlet Side 150 mm (6") .......................26
Figure 16: Condensate Drain Assembly -
Horizontal Flue .............................................27
Figure 17: Condensate Drain Assembly -
Vertical Flue .................................................28
Figure 18: Silencer ........................................................28
Figure 19: Acoustic Enclosure ......................................29
Figure 20: Junction Box Wiring Diagrams .....................29
Figure 21: Filter Housing Assembly ..............................30
Figure 22: Outside Air Supply .......................................30
Figure 23: Gas Connection with Stainless Steel
Flex Gas Connector .....................................31
Figure 24: External System Wiring ...............................32
Figure 25: CRT Burner Internal Wiring .........................33
Figure 26: CORAYVAC
®
System
Sequence of Operation Chart ......................34
Figure 27: Burner Sequence of Operation Chart ..........34
Figure 28: Vacuum Reading..........................................41
Page 6
Page 7
1
Product Approval
ROBERTS GORDON® appliances have been tested and CE certified as complying with the essential requirements of the Gas Appliance Directive, The Low Voltage Directive, The Electromagnetic Compatibility Directive and the Machinery Directive for use on natural gas and L.P. gas when installed, commissioned and maintained in accordance with these instructions.
These instructions refer to appliances designed to operate in the European Union. Appliances designed for other countries (Non European Union) are available on request. This appliance must be installed in accordance with the local and national codes in force and used
only in a sufficiently ventilated space, as specified in these instructions. Before installation, check that the local gas distribution systems, nature of gas and pressure, and
adjustment of the appliance are compatible.
Page 8
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
2
SECTION 1: HEATER SAFETY
Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possi­ble fire, electrical or burn hazards. Please pay special attention when reading and following the warn­ings in these sections.
Installation, Service and Annual Inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment.
Read this manual carefully before installation, oper­ation or service of this equipment.
This heater is designed for heating nonresidential indoor spaces. Do not install in residential spaces. These instructions, the layout drawing, local codes and ordinances, and applicable standards that apply to gas piping, electrical wiring, venting, etc., must be thoroughly understood before proceeding with the installation.
Thin sheet metal parts, such as the reflector portion of the heater and the various venting components, have sharp edges. To prevent injury, the use of work gloves is recommended. The use of gloves will also prevent the transfer of body oils from the hands to the surface of the reflector.
Before installation, check that the local distribution conditions, nature of gas and pressure, and adjust­ment of the appliance are compatible.
1.1 Manpower Requirements
To prevent personal injury and damage to the heater, two persons will be required for installation.
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To ensure the system is designed in accordance with the parameters of the CORAYVAC
®
design
manual (P/N 128500UK).
• To install the heater, as well as the gas and elec­trical supplies, in accordance with applicable specifications and codes. Roberts-Gordon rec­ommends the installer contact a local building inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing and in the manual together with the local and national codes to perform the installation.
• To install the heater in accordance with the Clearances to Combustibles.
• To furnish all needed materials not furnished as standard equipment.
• To plan location of supports.
• To provide access to burners for servicing on all sides, for burner removal.
• To provide the owner with a copy of this installation, operation and service manual.
• To never use heater as support for ladder or
other access equipment and never hang or suspend anything from heater.
• To ensure there is adequate air circulation
around the heater and to supply air for combus­tion and ventilation in accordance with local and national codes.
• To safely and adequately install heater using
materials with a minimum working load of 33 kg (75 lbs).
2.1 Low Level User Instructions
In all situations, clearances to combustibles must be maintained. Signs should be posted in storage areas to specify the maximum stacking height of items placed below heater to maintain required clearances to combustibles. Minimum clearances must be maintained from vehicles parked below the heater. Caution should be used when running the system near combustible materials such as wood, paper, rubber, etc. Consideration should be given to partitions, storage racks, hoists, building construc­tion,etc.
A laminated wall tag is available for the CORAY­VAC
®
heater as a permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Please contact Rob­erts-Gordon or your ROBERTS GORDON
®
inde­pendent distributor to obtain the wall tag. Affix the tag by peeling off the backing of the adhesive strips on the rear surface and position the tag on a wall near the CORAYVAC
®
heater (e.g. thermostat or
ROBERTS GORDON
®
BZC Controller).
A copy of the wall tag (P/N 91037912) is illustrated on the back cover. This copy of the wall tag can be affixed on the wall near the heater. Know your model number and installed configuration. Model number and installed configuration are found on the burner and in the Installation, Operation and Service Man­ual. Write the largest clearance dimensions with permanent ink according to your model number and configuration in the open spaces on the tag.
See Page 5, Section 3.2.
Page 9
SECTION 2: INSTALLER RESPONSIBILITY
3
2.2 Corrosive Chemicals
Roberts-Gordon cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility of the installer. It is essential that the contractor, the sub-contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the pre­mises.
* Halogenated Hydrocarbons are a family of chemical com­pounds characterized by the presence of halogen elements (flu­orine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the life span of the heater components will be greatly reduced. An out­side air supply must be provided to the burners whenever the presence of these compounds is suspected. Warranty will be invalid if the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All Appliances must be installed in accordance with the latest revision of the applicable standards and local and national codes. This refers also to the electric, gas and venting installation. Note: Addi­tional standards for installations in Public Garages, Aircraft Hangars, etc. may be applicable.
CAUTION
Do not use heater in an area containing corrosive chemicals.
Avoid the use of corrosive chemicals to ensure a longer life of the burner, tubing and other parts.
Failure to follow these instructions can result in property damage.
Page 10
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
4
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Required Clearances to Combustibles
Clearances are the required distances that combus­tible objects must be away from the heater to pre­vent serious fire hazards. Combustibles are materials, which may catch on fire and include com­mon items such as wood, paper, rubber, fabric, etc.
Maintain clearances to combustibles at all times for safety.
Clearances for all heater models are located on Page 5, Figure 1 through Page 6, Figure 5 in this
manual. Check the clearances for the model heater being installed to make sure the product is suitable for your application and the clearances are main­tained. Read and follow the safety guidelines below:
• Keep gasoline or other combustible materials including flammable objects, liquids, dust or vapours away from this heater or any other appliance.
• Maintain clearances from heat sensitive material, equipment and workstations.
• Maintain clearances from vehicles parked below the heater.
• Maintain clearances from swinging and overhead doors, overhead cranes, vehicle lifts, partitions, storage racks, hoists, building construction, etc.
• In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to main­tain required clearances from the heater to the combustibles. Signs must be posted adjacent to the heater thermostat. In the absence of a thermostat, signs must be posted in a conspicuous location.
• Consult local Building Inspector, Fire Insurance Carrier or other authorities for approval of pro­posed installation when there is a possibility of exposure to combustible airborne materials or vapours.
• Hang heater in accordance to the minimum suspension requirements on Page 10, Figure 8.
• If the radiant tubes must pass through the building structure, be sure that adequate sleeving and fire stop is installed to prevent scorching and/or fire hazard.
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapours the required distance away from the heater.
Failure to follow these instructions can result in death, injury or property damage.
Page 11
SECTION 3: CRITICAL CONSIDERATIONS
5
3.2 Clearance Data NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, tees, elbows and
crosses.
2. Clearances B, C and D can be reduced by 50% after 7.5 m (25') of tubing downstream from where the burner and burner tube connect.
3. All measurements are in Millimeters.
CLEARANCES TO COMBUSTIBLES
Figure 1: STANDARD REFLECTOR
Model A B C D
CRT-10 150 510 1220 510
CRT-15 150 510 1220 510
CRT-20 150 510 1220 510
CRT-25 150 920 1530 920
CRT-30 150 920 1530 920
B
C
D
A
Figure 2: ONE SIDE REFLECTOR
Model A B C
|
D
CRT-10 150 305 1430 510
CRT-15 150 305 1430 510
CRT-20 150 305 1430 510
CRT-25 150 305 1530 1070
CRT-30 150 305 1530 1070
A
B
C
D
Figure 3: TWO SIDE REFLECTORS
Model A B C D
CRT-10 150 305 1430 305
CRT-15 150 305 1430 305
CRT-20 150 305 1430 305
CRT-25 150 305 1530 305
CRT-30 150 305 1530 305
A
B
C
D
Page 12
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
6
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, tees, elbows and
crosses.
2. Clearances B, C and D can be reduced by 50% after 7.5 m (25') of tubing downstream from where the burner and burner tube connect.
3. All measurements are in Millimeters.
23
CLEARANCES TO COMBUSTIBLES
Figure 4: 2-FOOT DECO GRILLE
Model A B C D
CRT-10 150 305 1220 305
CRT-15 150 305 1220 305
CRT-20 150 305 1220 305
CRT-25 150 460 1430 460
CRT-30 150 460 1430 460
A
B
C
D
Figure 5: PROTECTIVE GRILLE AND 1 FOOT DECO GRILLE
Model A B C D
CRT-10 150 510 1220 510
CRT-15 150 510 1220 510
CRT-20 150 510 1220 510
CRT-25 150 920 1530 920
CRT-30 150 920 1530 920
A
B
C
D
Page 13
SECTION 4: MAJOR COMPONENTS
7
SECTION 4: MAJOR COMPONENTS
The figures in this section provide a general over­view of component placement in a CORAYVAC
®
system. The location of some components such as supports and couplings is crucial for proper installa­tion. Assemble the heater components as shown on Page 11, Figure 9.
Optional reflector configurations are shown on Page 5, Figure 1 through Page 6, Figure 5. Install appro­priate suspension hardware, beam clamps, chain or rod at predetermined locations.
Figure 6: Major Component Descriptions
Burner
Tube
Heat Treated Aluminized Tube supplied in 3 m (10’) lengths.
45° Elbow
90° Elbow
End Vent
Coupling Assembly with Lock
Flex Gas Line
Combustion Chamber
Tee
Reflector (Aluminum or Stainless Steel)
Reflector with Hole (Aluminum or Stainless Steel)
Reducer
Cross
Page 14
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
8
Figure 7: Major Component Descriptions (Continued)
Reflector Side Extension Bracket
Reflector Side Extension
Non Return Val ve (ISO-7Rc)
Reflector End Cap (Aluminum or Stainless Steel)
Remove center section to accommodate heat exchanger tube when necessary.
Bow Shackle
Tube and Reflector Hanger
Reflector Support Package
Deco Grille
Turn buck le
Protective Grille Sports Hall Guard
ROBERTS GORDON® BZC 700 Controller ROBERTS GORDON
®
BZC 300 Controller ROBERTS GORDON
®
BZC 100 Controller with Sensor
RG-30 and RG-45 Pump
Page 15
SECTION 4: MAJOR COMPONENTS
9
4.1 Standard Parts List
Table 1: Contents of CORAYVAC® Burner Carton
Table 2: Common CORAYVAC
®
Components
Part No. Description Quantity
E000XXXX
CORAYVAC
®
Burner (Rate and Fuel Varies)
1
E0007565 Accessory Package -
01361200 Filter Support Disk 1
01367800 Combustion Chamber Gasket 1
02904000 Door Assembly w/ Hole 1
91119500 U-Clip 4
91905500 Filter Support 1
E0007588 Nut M8 Brass 2
92511601 Wing Nut #10 - 24 1
96411600 Lockwasher 5/16" 2
01312401 Filter and Gasket 1
Part No. Description
Combustion Chamber:
02722302-1P Aluminised Combustion Chamber
E0009400 1/2" Flex Gas Line Kit
E00094XX End Vent Plate
Tubing and Related Accessories
01312700 100 mm Coupling and Lock
01312700 150 mm Coupling and Lock
01331900 100 mm Coupling with Damper and Lock
E0009356 150 mm Coupling with Damper and Lock
01330203 100 mm Aluminised Tee
01330204 150 mm Aluminised Tee
01330903 100 mm Aluminised Cross
E0009167 150 mm Aluminised Cross
01335801 100 mm Aluminised 90° Elbow
T0100320 150 mm Aluminised 90° Elbow
01336101 100 mm Aluminised 45° Elbow
91409408 16 Ga. Heat Treated Aluminised 100 mm dia 3048 mm Tube
E0009105 16 Ga. Heat Treated Aluminised 150 mm dia 3048 mm Tube
E0009326 100 mm Tail Pipe Tube Hanger
03020700 150 mm Tail Pipe Tube Hanger
Venting and Fresh Air Supply Accessories
C1376B 100 mm Outside Air Flex Duct (10 m)
F323 150 mm Roof & Wall Masterflash
F322 100 mm Roof & Wall Masterflash
F074A Roof & Wall Terminal
F116 Roof & Wall Terminal
Reflectors and Related Accessories
01329910 Reflector Side Extension Support
91107720 U Clip Package - 20 off
02750303 Aluminium Reflector
S5163W Stainless Steel Reflector
02750304 Aluminium Reflector with Hole
S5164W Stainless Steel Reflector with Hole
02750800 Aluminium Reflector End Cap
C2331B Stainless Steel Reflector End Cap
C2332B Stainless Steel Reflector End Cap with Hole
01329910 Reflector Side Extension Support
02751200 Retainer Side Extension Reflector
03090100 Tube and Reflector Hanger
E0007575 Turnbuckle Assembly
Controls and Thermostats
BZC100
ROBERTS GORDON
®
BZC 100 Controller
BZC300
ROBERTS GORDON
®
BZC 300 Controller
BZC700
ROBERTS GORDON® BZC 700 Controller
C2343B BZC Sensor
S7418K Starter RG-30 Pump
S7445K Starter RG-45 Pump
Deco Grille 305mm x 2438mm
01363003 Bracket
91406700 305 x 2438 mm Protective Grille
Deco Grille 610mm x 1219mm
01365900 Shield Frame
01370412 Reflector Side Extension 305 x 1219 mm
91407000 Aluminium Grille 610 x 1219 mm
Protective Grille
08050001 40" Protective Grille
08050002 Protective Grille End Cap
Pump Packages and Accessories
S7421K Vacuum Pump Kit RG30-3Ø
S7423K Vacuum Pump Kit RG45-3Ø
S7425K Vacuum Pump Kit RG30-1Ø
S7426K Vacuum Pump Kit RG45-1Ø
Accessories
E0007074 Pressure Switch
02718851 100 mm Drain Cap
02718852 150 mm Drain Cap
90201200 Non Return Valve
Page 16
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
10
SECTION 5: HEATER INSTALLATION
To ensure your safety, and comply with the terms of the warranty, all heaters must be installed in accor­dance with these instructions.
The gas or the electrical supply lines must not be used to support the heater.
Do not locate the gas or electric supply lines directly over the path of the flue products from the heater.
The heater must be installed in a location that it is readily accessible for servicing.
The heater must be installed with clearances to combustibles as indicated in this instruction manual.
The minimum and maximum gas inlet pressures must be maintained as indicated in this manual. Typical installation configurations are shown in Figure 8.
For mounting height and tube lengths See Page 43, Section 15.6.
Figure 8: Critical Hanger Placement
WARNING
Crush Hazard
Hang heater with materials with a minimum working load of 33 kg (75 lbs).
Failure of the supports can result in death, injury or property damage.
Side View Towards Pump
Typical Suspension Details
Turnbuckle
Rod (10 mm)
Beam Clamp
Concrete Beam
Wood Beam
Washers
Locknut
Screw Hook (10 mm)
610 mm
min.
(24")
"X"
(see table)
Locknut (Typical)
Anchor
Hanger
Front View
Bow Shackle
Turnbuckle
Reflector
2.3 m (7'6" )
Chain size
5 mm minimum
Description Part Number
Turnbuckle 91903201 Bow Shackle E0007576 Tube/Reflector Hanger 03090100
Run Length Typical Expansion Minimum “X” Length
15m (50’) ±25 mm (1") 300 mm (12") 31m (100’) ±50 mm (2") 600 mm (24") 46m (150’) ±75 mm (3") 900 mm (36") 61m (200’) ±100 mm (4") 1200 mm (46") 76m (250’) ±125 mm (5") 1450 mm (57")
Page 17
SECTION 5: HEATER INSTALLATION
11
Figure 9: CORAYVAC
®
Assembly Overview
End
Vent
Combustion
Chamber
Tube &
Reflector
Hanger
Burner
Reflector
Tube
Coupling
Reflector
End Cap
Reflector
Support
Flexible
Boot
Reflector
with Hole
Pump
Exhaust
to Outside
Pressure Switch
S
Zone 1 Sensor
Starter and
Overload
ROBERTS GORDON
®
BZC Controller,
Economy Controller or
Building Management System
(consult ROBERTS GORDON
®
)
U-Clips
Minimum reflector
overlap 180 mm
Damper
Coupling
Power Supply
Pump
Page 18
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
12
Step 5.1 Tube Installation
Step 5.2 Coupling and Tube Assembly
Combustion
Chamber
2.3 m
(7' 6")
Combustion
Chamber
3 m (10')
maximum
End View
Weld
Seam
Bottom of Tube
Hanger
Turnbuckles
Tube
3 m (10')
maximum
Towards
Pump
NOTE: Tubing requires a downward
slope of 13 mm (1/2") per 6 m (20') away from burner. Tailpipe tubing requires a downward slope of 25 mm (1") per 6 m (20') away from burner.
Description Part Number
Tube 91409XXX Turnbuckle 91903201 Tube/Reflector Hanger 03090100
Tube
Tube
Orient coupling so that
the impact block is in the
2:00 or 10:00 oclock
positions
Closed
Open
Tab
76 mm to 101 mm
Slide Bar
Coupling
Wide end
Coupling
Tube
Slidebar
A
Close Coupling with tab
B
Start Slide Bar/Coupling Lock onto Coupling
C
Insert Tubes into Coupling
D
Tighten Coupling to join Tubes
Description Part Number
Coupling 01329600 Slide Bar/Coupling Lock 01329700 Tube 91409XXX
Page 19
SECTION 5: HEATER INSTALLATION
13
Step 5.2.1 Coupling and Tube Assembly (Continued)
Step 5.3 Reflector Installation Step 5.3.1 Reflector Installation with Hole
Incorrect Slide Bar
position
Correct slidebar
dimensions
± 50 mm
(2")
Drive Slide Bar until tight. End of slidebar should be within tolerance listed below.
Repeat Step 5.2 on Page 12, A - D until all tubes are assembled.
NOTE: If Coupling is not tight, loss of vacuum can occur.
Tighten Slide Bar as shown below.
Tube
Hanger
Combustion
Chamber
Slide Reflector
with hole
through hanger. Unhook combustion chamber from chain
and insert through hole.
Reconnect chain.
Reflector with Hole
Description Part Number
Tube/Reflector Hanger 03090100 Tube 91409408 Reflector with Hole 02750304
Page 20
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
14
Step 5.3.2 Reflector Installationg
Reflector
Wire Form
Tube
Reflector Support
Strap
Sheet Metal
Screw
U-Clip
(2 clips per
alternate overlaps
per side)
NOTE: Minimum reflector overlap must be 180 mm.
Description Part Number Reflector Support Package 03050010
Wire Form 91908004 Reflector Support Strap 03050000
Screw #8 x 3/4 94320812 U-Clip Package 91107720 Reflector End Cap 027508XX
Page 21
SECTION 5: HEATER INSTALLATION
15
Step 5.3.3 Reflector, U-Clip and Reflector Support Installation
The pictorial drawings of the heater construction in Section 5 are schematic only and provide a general guideline of where hangers, reflector supports and U-clips are to be installed.
To ensure proper expansion and contraction movement of the reflectors, a combination of U-clips and reflector
supports are used. The positioning of reflector supports and U-clips depend on the individual installation. Use either pop rivets or sheet metal screws instead of U-clips when installing end caps and joint pieces in areas where impact and high wind may be a factor.The following rules must be observed:
Tight
screws
Loose screws loosened 2 mm (1/16") to allow slippage.
Reflector End Cap
U-Clips
Wire Form
Reflector Support
Strap
Tight
Sheet Metal
Screw
The first reflector after the burner must be affixed in the middle of the reflector with a reflector support and tight screws.
First Reflector
1.
The joint at the first and second reflector is a slip joint. Thereafter every third reflector joint is a slip joint. A slip joint is achieved by: a.) both reflectors lay inside a hanger.
(no reflector support needed).
b.) using a reflector support with
loose screws.
Slip Joint
Option A
2.
The remaining reflector overlaps require a non-slip joint connection. To affix the reflectors together in a non-slip overlap, use reflector supports and tight screws. *If both reflectors lay inside a hanger, U-clips or sheet metal screws may be used. This section of three reflectors joined together must be affixed to the tube with at least one reflector support with tight screws.
Non-slip Joint
*U-Clip
(2 clips per
non-slip overlap
inside a hanger)
3.
Reflector
Support
Slip Joint
Option B
Reflector
Reflector
Description Part Number Reflector Support Package 03050010
Wire Form 91908004 Reflector Support Strap 03050000
Screw #8 x 3/4 94320812 U-Clip Package 91107720 Reflector End Cap 027508XX
Page 22
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
16
Step 5.4 Burner Installation
Gasket
Burner
Combustion
Chamber
End
Vent
NOTE:
Install End Vent at end combustion chamber position only
Burner
Combustion
Chamber
End Vent
End Vent Clips
Rating
Number
Description Part Number
Bolt E0007588 Burner E000XXXX Lock Washer 96411600 Gasket 01367800 End Vent E00094XX
Page 23
SECTION 6: OPTIONAL HEATER ACCESSORIES
17
SECTION 6: OPTIONAL HEATER ACCESSORIES
6.1 Elbow Configuration Step 6.1.1 Elbow Installation
Step 6.1.2 Elbow Installation
Step 6.1.3 Tee Installation
Tube
90° Elbow
Coupling
Description Part Number
90° Elbow 01335801 Coupling and Lock 01312700
Tube
Coupling
Tee
Tube
Coupling
Description Part Number
Tee 01330XXX Tube/Reflector Hanger 03090100 Tube 91409408 Coupling 01312700
Page 24
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
18
6.2 Reflector Side Extension Step 6.2.1 Bracket Installation
Step 6.2.2 Side Reflector Installation
Reflector Side
Extension Bracket
(2 per reflector)
Use additional supports
in high air movement
applications.
Tube and Reflector Hanger
Reflector
Tube
Reflector Support
Description Part Number Reflector Side Extension Package S7377K
Reflector Side Extension 01368000 Retainer Clips 02751200 Sheet Metal Screws 94118106
Order Separately
Reflector Side Extension Bracket 01329910
Retainer Clip (2 per side)
Cut relief notches for Supports and Hangers
Reflector Side Extension
#8 x 3/8 (3.9 x 9.5 mm) Sheet Metal Screw
Page 25
SECTION 6: OPTIONAL HEATER ACCESSORIES
19
Step 6.3 One Foot Decorative Grille Step 6.3.1 Decorative Grille Bracket (One Foot Grille)
Step 6.3.2 One Foot Decorative Grille
Step 6.3.3 Joint Piece and Reinforcement (One Foot Grille)
Sheet Metal Screws
Cut relief notches for supports and hangers.
Decorative Grille Bracket
50 mm
Minimum
Bracket Overlap
Description Part Number
Bracket 01363003
Spread apart brackets and install Decorative Grille.
Description Part Number
Decorative Grille 2440mm x 305mm 91406700
Sheet Metal Screws
Joint Piece
Reinforcement
Slip joint piece into support bracket and fasten to bracket on one side of the joint only.
Joint Piece
Description Part Number
Joint Piece 01365903 Reinforcement 01365902
Page 26
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
20
Step 6.3.4 End Piece and Reflector End Cap (One Foot Grille)
Fasten end piece to brackets using two sheet metal screws and replace reflector end cap.
Insert end piece between grille and brackets.
End Piece
Reflector End Cap
Description Part Number
End Piece 01365901
Page 27
SECTION 6: OPTIONAL HEATER ACCESSORIES
21
6.4 Protective Grille Installation Step 6.4.1 Silicone Cap Installation
Step 6.4.2 Grille End Cap Installation
Step 6.4.3 Grille Installation
Silicone Cap
Grille Finger
Description Part Number
Grille Section 08050001 Grille End Cap 08050002 Silicone Cap 91915951-6P
Bend up 90°
Pull outward
Grille
Grille End Cap
A
B
C
D
Grille
Grille End Cap
Reflector
Final Grille Section
101 cm
(40 ")
Page 28
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
22
6.5 Sports Hall Guard Installation Step 6.5.1 Grille Installation
Step 6.5.2 Fastener Installation
Step 6.5.3 Mesh Guard Connection
Tube and
Reflector Hanger
Reflector
Tube
Reflector Support
Strap - Stainless Steel
Mesh Guard
Description Part Number
Mesh Guard 2438 mm E0009855 Mesh Guard 1524 mm C2329B Strap Stainless Steel S5218W
Tube and Reflector Hanger
Reflector
Tube
Strap - Stainless Steel
Mesh Guard
Nut Spire
Screw 3.9 x 9.5 mm (#8 x 3/8)
Description Part Number
Nut Spire C1088B Screw #8 x 3/8 (3.9 x 9.5 mm) C1089B
Page 29
SECTION 6: OPTIONAL HEATER ACCESSORIES
23
6.6 Sports Hall Filter Step 6.6.1 Remove Standard Door
Step 6.6.2 Install New Door Filter
Cylindrical
Filter
Door
Remove the burner door with the cylindrical filter.
Filter
Media
Peel off
Remove backing of the adhesive strips from the filter and affix to the inside of the burner door with louvers. Use existing screws to install new filter door.
Page 30
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
24
SECTION 7: PUMP INSTALLATION AND VENTING
7.1 Mounting Wall Bracket Assembly 7.1.1 Mounting Platform
The standard method of mounting the RG-30 and RG-45 pump is on an outside wall and venting directly through the wall or roof.
The pump may be mounted by using mounting angles as shown in Figure 10 and Figure 11. The two mounting angles form a mounting platform to which the pump will be attached using the anti­vibration mounts.
Fix the mounting frame to the wall using anchors. Select an anchor that will give equal to or greater than 907 kg (2000 lbs) ultimate pull-out strength.
Figure 10: Wall Bracket Assembly
Figure 11: Mounting Platform Options
WARNING
Crush Hazard
Mount pump with materials with a minimum working load of 181 kg (400 lbs).
Failure of the supports can result in death, injury or property damage.
Mounting Angle
Hex Head Bolt
Flat Washer
Lockwasher
Hex Nut
Flat Washer
Description Part Number
Mounting Angle 01365000 Bolt M8 x 25 mm S280 Nut M8 S248 Washer S264 Lockwasher S260
27 cm
(10 5/8)
20.5 cm (8)
Anti-Vibration
Mount
Anti-Vibration
Mount
Anti-Vibration
Mount
Description Part Number Anti Vibration Mounting Kit E0009238
Anti Vibration Mount 91906100 Hex Nut 92113900 Washer 95211600 Lockwasher 96411600
Page 31
SECTION 7: PUMP INSTALLATION AND VENTING
25
7.1.2 Attaching Pressure Switch
Drill two holes in the fan base housing to accept the pressure switch mounting bracket and attach the switch by means of 2 self-tapping screws. The switch should be mounted vertically with the cable restraint gland on top.
The silicone tubing is installed according to Figure
12. Care must be taken that the tubing cannot kink or be squeezed together.
Figure 12: Pressure Switch Installation
7.1.3 Flue Installation
The fan outlet must always discharge horizontally. Mount the 150 mm (6") pump boot to the pump out­let using the 6" 150 mm (6") band clamp provided. See Figure 15.
Connection should be made using 150 mm mini­mum diameter aluminium or stainless steel flue material. All flue material must conform to the rele­vant National Standards.
Mount the 150 mm flue to the pump boot securing it with the 150 mm band clamp. The flue length must not exceed 15 m including 2 x 45° offset bands. The flue must be self supporting.
Figure 13: Pump Discharge Side
Pressure
Switch
Cable Restraint Gland
Description Part Number
Pressure Switch E0007074
Band Clamp 150 mm (6")
Pump Boot
150 mm (6")
CONNECT
TO SYSTEM
TUBING
150 mm (6")
Description Part Number
Pump Boot 150 mm (6") 91412802 Band Clamp 150 mm (6") 91913703
Page 32
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
26
7.1.4 Pump Inlet Adapter for 100 mm (4") Tubing
Apply a bead of silicone sealant 316° C to the 150 mm (6") inside of the reducer (150 mm x 100 mm) (6" x 4"). Mount the reducer to the inlet of the pump scroll using the 3 - #10 self drilling screws provided. See Figure 14.
IMPORTANT: To prevent leakage of condensate, do not install screws at the 6 o’clock position.
Mount the pump boot to the inlet reducer using the band clamp provided. See Page 26, Figure 14.
7.1.5 Pump Inlet for 6" (15 cm) Tubing
Attach 150 mm (6") pump boot to the inlet See Fig­ure 15, then See Section 7.1.3.
7.2 Building Ventilation
The space containing the heaters must have a permanent outside air vent with a minimum effective area of 4.5 cm
2
per kW of heat input. If mechanical ventilation is employed, the minimum proven airflow rate shall be 2.35 m
3
/h per kW of heat input. If venti­lation is required, air must be taken from an outside point where it is not likely to be contaminated. The building ventilation must be in accordance with local and national codes.
Figure 14: Pump Inlet Side 100 mm (4")
Figure 15: Pump Inlet Side 150 mm (6")
Inlet
Assembly
Band Clamp
100 mm (4")
Pump Boot
100 mm (4")
CONNECT
TO SYSTEM
TUBING
100 mm (4")
100 mm x 150 mm
Adapter
Condensate
Te e
Band Clamp 150 mm (6")
Description Part Number
Pressure Switch 90430600 Pump Boot 100 mm (4") 91412800 Band Clamp 100 mm (4") 91901300 Inlet Assembly 90713454 101 mm (4") x 150 mm (6") Adapter 02719903
Band Clamp 150 mm (6")
Pump Boot
150 mm (6")
CONNECT
TO SYSTEM
TUBING
150 mm (6")
Description Part Number
Pressure Switch 90430600 Pump Boot 150 mm (6") 91412802 Band Clamp 150 mm (6") 91913703
Page 33
SECTION 7: PUMP INSTALLATION AND VENTING
27
7.3 Condensate Drain Assembly
The condensate drain assembly is composed of a tee, draincap, and a non return valve.
A condensate drain assembly must be installed on the inlet side of the pump assembly if there is horizontal venting of the pump, See Figure 16.
A seperate condensate drain on the pump dis­charge side is required if there is vertical venting of the pump or if there is a vertical rise in the discharge line away from the pump. See Figure 17.
The condensate drain assembly in the pump discharge line can be eliminated if the discharge line is horizontal through the wall and pitched down at least 6 mm per 3 m (1/4" per 10'). This arrangement will permit drainage of condensate through the pump and outside via the horizontal (pitched) dis­charge line.
Figure 16: Condensate Drain Assembly - Horizontal Flue
Te e
Drain Cap
Pump
Inlet
Wall
1" BSP threaded hole.
Use 1" x ¾" reducer.
(not supplied)
Must be connected to a drain system in accordance with local codes.
1 m (36") minimum
vertical drop between pump and non-return
valve.
3/4" CPVC Pipe
flow
Non-Return
Valve
3/4" CPVC
Pipe
3/4" female
Description Part Number
Tee 100 mm (4") 01330203 Tee 150 mm (6") 01330204 Drain Cap 100 mm (4") 02718851 Drain Cap 150 mm (6") 02718852 Non-Return Valve C2383B
Page 34
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
28
Figure 17: Condensate Drain Assembly - Vertical Flue
7.4 Acoustic Enclosure (Optional)
The acoustic enclosure is used to reduce noise from the pump installed inside the building. The enclo­sure can also be used as a weatherproof enclosure if the pump is installed outside. For outside applica­tions a master flash must be attached over the tail pipe and flue discharge connection. In some appli­cations the noise from the pump discharge needs to be reduced. A silencer attached to the discharge side must be used. See Page 28, Figure 18.
Figure 18: Silencer
The acoustic enclosure comes fully assembled with an electrical junction box on its side. Pressure switch control wires and electrical power connection need to be connected here. A wiring diagram is
inside the junction box. See Page 29, Figure 19.
The mounting of the enclosure must be done as described in Section 7.1.
Flue
150 mm (6") Minimum
Roof
Te e
150 mm (6")
Drain Cap
150 mm (6")
Pump
Discharge
Wall
Approved Vent Cap
1" BSP threaded hole.
Use 1" x ¾" reducer.
(not supplied)
Must be connected to a drain system in accordance with local codes.
flow
Non-Return
Valve
3/4" CPVC
Pipe
3/4" female
3/4" CPVC Pipe
300 mm
(12")
Description Part Number
Tee 150 mm (6") 01330204 Drain Cap 150 mm (6") 02718852
Pump
Discharge
Silencer
600 mm
725 mm
250 mm
Description Part Number
Silencer C0996B
Page 35
SECTION 7: PUMP INSTALLATION AND VENTING
29
Figure 19: Acoustic Enclosure
Figure 20: Junction Box Wiring Diagrams
7.4.1 Noise Data
All noise data has been determined according to EN ISO 3746:1995, survey method "Parallelepiped measurement surface". Values given below are at 3 m distance from the object.
Tailpipe
Connection
Flue
Discharge
Junction Box
(wiring diagram
inside)
From
Pressure Switch
From Fan Motor
Blue Brown Brown BlueBlack Earth
Common NO U1 V1 W1
3 Ø Motors
From
Pressure Switch
From Fan Motor
Blue Brown Brown Blue Earth
Common NO
1 Ø Motors
RG30 and RG45 Pump Data
Sound Pressure Level
dB (A)
NR
No acoustic enclosure 59 53
No acoustic enclosure with 600 mm silencer 59 53
With acoustic enclosure 57 51
With acoustic enclosure and 600 mm silencer 55 49
Flue Data
Straight outlet duct 69 63
Straight outlet duct with 600 mm silencer 60 54
Burner Data
CRT 10 - 30 located at end vent plate 58 52
CRT 10 - 30 located in middle of branch 49 43
Page 36
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
30
SECTION 8: OUTSIDE AIR SUPPLY
The CORAYVAC® system is approved for use with an outside air system. Halogenated hydrocarbons or other corrosive chemicals in the air can be drawn into the equipment and seriously damage the sys­tem components. Avoid the use of such chemical compounds near the air inlet to the heaters.
IMPORTANT: If the building has a slight negative pressure or contaminants are present in the air, an outside combustion air supply to the heaters is strongly recommended.
All joints and seams in the air supply system must be airtight. The filter housing attaches to the burner assembly by using the wing nut provided.
Figure 21: Filter Housing Assembly
Figure 22: Outside Air Supply
Wing Nut
Filter Housing
Filter
Top Gasket
and Disk
Bottom Gasket
Door-Control
Housing
Filter
Support
Description Part Number
Filter Housing 01326801 Filter and Gaskets 01312401 Filter Support 91905500 Wing Nut 92511601
Vent Cap or Bird Screen
Outside Wall
Burner
Spiral Duct
or PVC
Clamp
100 mm (4")
Take Off
100 mm (4")
Air Flex Duct
Filter
Housing
Description Part Number
Filter Housing 01326801 100 mm (4") Take Off C1361B 100 mm (4") Air Flex Duct (10 m sections) C1376B 100 mm (4") Bird Screen 01365400 100 mm (4") Vent Cap 90502300 150 mm (6") Vent Cap 90502302
Page 37
SECTION 9: GAS PIPING
31
SECTION 9: GAS PIPING
A gas meter is connected to the service pipe by the Gas Supply Company. An existing meter should be checked, preferably by the gas company, to ensure that the meter is adequate for the rate of gas supply required.
Installation pipes should be fitted in accordance with National Standards. Pipe work from the meter to the heater(s) must be of adequate size. Pipes of smaller size than the heater inlet gas connection should not be used.
Connect the heater to the gas supply using an approved flexible gas hose of 1 m (39") length and a shut-off valve. See Page 31, Figure 23.
IMPORTANT - the complete installation must be tested for gas soundness and be purged in accor­dance with local and national codes.
Figure 23: Gas Connection with Stainless Steel Flex Gas Connector
WARNING
Fire Hazard
Connect gas supply according to Figure 21.
Gas line moves during normal operation.
Gas can leak if not installed properly.
Failure to follow these instructions can result in death, injury or property damage.
Horizontal
45°
Rear ViewBurner
50 mm (2")
Stainless
Steel Flex
Gas Connector
Shut-Off Valve
300 mm
(12")
Hold gas nipple securely with pipe wrench when attaching the flex gas connector.
Shut-Off Valve must be parallel to burner gas inlet. The 50 mm (2") displacement shown is for the cold condition. This displace­ment may reduce when the system is fired.
Do not bend flexible gas connector sharply.
Description Part Number
1/2" Flex Gas Line E0009397 Shut Off Valve C0514B
Page 38
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
32
SECTION 10: WIRING
Connect to the electrical supply using a 3 pin plug
via a locally mounted double pole fused switch hav­ing a minimum disconnection of 3 mm on each pole. The burner is fused at 1 A. There are no control con­nections in the standard burner. Control is effected by interruption of the main power inlet. See Page 32, Figure 24 for external and Page 33, Figure 25 for internal wiring.
All wiring must comply with current wiring regula­tions and any local regulations which may apply. Always switch off the supply to the burner and dis­connect by removing the plug before removing the burner side panel.
3 phase motors can be reversed by interchanging 2 phase connections.
The control of the CORAYVAC
®
system must via a Roberts Gordon approved control to ensure that the necessary safety systems are in place and proper post purge occurs at close down.
Figure 24: External System Wiring
WARNING
Electrical Shock Hazard
Disconnect electrical power and gas supply before servicing.
This appliance must be connected to a properly earthed electrical source.
Failure to follow these instructions can result in death or electrical shock.
Burner Receptacles 4 Zone Max
Maximum 10 A Total
Sensors
Pump Motor 400 V Operation, 3 Ø 230 V Operation, 1 Ø
Pressure Switch
BZC Controller,
Economy Controller or
Building Management System
(consult ROBERTS GORDON
®
)
IEC contactor and overload rated for the pump motor
L
N
E
L
N
E
L
N
E
Pump Power Supply
L
Power
Supply
N
Page 39
SECTION 10: WIRING
33
Figure 25: CRT Burner Internal Wiring
If any of the original wire as supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C and 600 V.
32 1 576 43 2 1
sense
FILTER
RECTIFIER/ GAS VALVE
ELECTRODE
MIXING CHAMBER
IGNITION MODULE
Yellow
Green/
Green/Yellow
Brown
Blue
Blue
Brown
Yellow
Green/
SPARK
Brown
Blue
yellow
yellow
blue
brown
Blue
MAIN INLET
Blue
Brown
Brown
DOTTED LINE WIRES ARE AN OPTION
RUN START
CONNECTOR VOLT FREE
RELAY
1
2
4
3
2
A1
A2
Page 40
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
34
SECTION 11: OPERATION AND MAINTENANCE Figure 26: CORAYVAC
®
System Sequence of Operation Chart
Figure 27: Burner Sequence of Operation Chart
11.1 Sequence of Operation
On connection of the power supply, the pump will start creating a suction in the tube. The pressure switch at the pump will change contacts when suc­tion is created. A pre-purge cycle which lasts 30
seconds is initiated. Once complete, power to the burners is enabled.
The burner sequence begins with the red lockout neon illuminated. This indicates that the burner has begun the ignition sequence.
KEY TO
SYMBOLS
T
0
T
8
T
3
T
5
T
4
T
6
T
2
T
1
2 minute
post purge
Loss of Pressure
Switch Signal
30 sec approx.
T
7
Pressure Switch
PS
Thermostat
Pump Operating
Power to Burners
PS
T
9
KEY TO
SYMBOLS
Start/Run
T
0
T
8
T
3
T
5
T
4
T
6
T
2
T
1
T
S
T
S
10
sec
45
sec
Interuption of main
flame sensing
55 sec approx.
Thermostat
Ignition
Gas Valve
Flame Sensing
Lockout Alarm (optional)
Neon
Lockout
T
7
3 try
10
sec
Page 41
SECTION 11: OPERATION AND MAINTENANCE
35
Power to the burner sequence controller initiates an approximate 45 second purge period. Following the purge period, the solenoid valve opens. This allows the vacuum, created in the tube to lift the diaphragm in the zero governor thereby allowing the passage of gas to the burner. At the same time, a spark is cre­ated and ignition should take place. If ignition of the gas is not successful, the spark will cease and the solenoid will close after approximately 10 seconds. The ignition sequence is repeated for 2 more times before lockout occurs. The lockout neon will remain lit indicating the condition. When the gas is ignited, the detection circuit is energised and switches off the ignition circuit. The run neon (green) will illumi­nate indicating full running condition.
The system will continue to run until the power sup­ply or gas supply is interrupted. Interruption of the electrical supply results in shutdown of the burners, after which, the pump will continue to run for two minutes to clear products of combustion from the system. Restoration will restart the whole sequence. Interruption of the gas supply will result in loss of flame followed by 3 attempts to reignite, if unsuc­cessful, lockout occurs.
11.2 Commissioning and Testing
Commissioning of the system must be carried out by a registered installer/contractor qualified in the installation and service of gas-fired heating equip­ment or your gas supplier.
11.2.1 Establish that a satisfactory purged gas sup­ply and an electrical supply is available to the heater.
11.2.2 Ensure that all dampers are in the fully open position.
11.2.3 Turn off the electrical supply to the heaters.
11.2.4 Switch on the electrical supply at the main
isolator. This will start the exhaust fan.
11.2.5 Ensure that all time clocks and thermostats are set to call for heat.
11.2.6 Balancing Cold Suction
Starting at the branch furthest from the pump, check the end vent vacuum. Do this by connecting a manometer by inserting the test probe a minimum of 150 mm into the hole. See Page 41, Figure 28. Adjust the damper at the end of the radiant run so that the suction is approximately 9 mbar. Repeat for each branch.
11.2.7 Switch off the electrical supply at the main isolator. The exhaust fan will stop.
11.2.8 Turn on the electrical supply to the heater.
11.2.9 Switch on the electrical supply at the main
isolator.
11.2.10 Balancing Hot Suction
The start up sequence described on Page 34, Sec- tion 11.1 should take place. Allow the system to
reach full temperature (approximately 30 minutes). Set the dampers at each branch to achieve the set­tings for the installed burner model as listed in
11.2.11.
11.2.11 Suction Settings
Model Heat Input Hot Suction
all Gas Types
(mbar)
CRT10 10 kW 5.7
CRT15 15 kW 6.5
CRT20 20 kW 7.0
CRT25 25 kW 6.7
CRT30 30 kW 7.0
Repeat this procedure for each branch of the system.
11.3 System Checks
Turn the system off and restart it to ensure smooth ignition. Carry out the following system checks.
11.3.1 When running, turn off the gas supply at the appliance isolating cock. The heater will immedi­ately shut down followed by 3 attempts at restoration followed by lockout.
11.3.2 When running, disconnect the fan electrical supply. The burner should shut down within a few seconds proving operation of the pressure switch.
11.3.3 When running, turn down the thermostat to a point below room temperature. Check that the fan continues to run on for two minutes after shut down of the burners.
11.4 User Instructions
After satisfactory testing, ensure that the client is fully aware of the operation of the system. Bring this manual to the attention of the user or purchaser; instruct them in the safe operation of the heater(s).
11.5 ECA Approved Systems
On ECA approved systems, it must be verified that the requirement of 91% net combustion efficiency is met. Measurements of temperature and CO2 con-
centration in the exhaust gasses have to be done. The net combustion efficiency calculates as follows;
100 - [ (t
E
- tR) (A/CO2m - B) ] = net comb. efficiency
t
E
- Exhaust Temperature °C
t
R
- Room Temperature °C
A - G20 = 0.37, G31 = 0.42
B - G20 = 0.009, G31 = 0.008
CO
2m
-Measured CO2 Concentration %
Page 42
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
36
SECTION 12: SERVICING INSTRUCTIONS IMPORTANT: Never use the heater as a support for
ladders or other access equipment. Always test for gas soundness with a suitable detection fluid after completing any servicing or exchange of gas carry­ing component. On completion of any service/fault finding tasks which require the breaking and remak­ing of electrical connections, recheck the following: A:Earth Continuity, B:Polarity and C:Resistance to Earth.
12.1 Annual Service Procedure
Carry out the following service procedure annually. The preferred time would be immediately before the winter heating period. If very dirty conditions arise, it may be necessary to carry out this procedure more often. If the unit takes in air through an air duct or filter assembly, less frequent service may be necessary.
12.1.1 Isolate the heater from the gas and electricity supply by shutting off the appliance cock and dis­connecting the union connector, switching off the local electrical supply and removing the appliance plug.
12.1.2 Remove the mains plug from the burner. Remove the two nuts that secure the burner head to the combustion chamber. The burner can now be removed.
12.1.3 Remove the burner to the floor level and clean internally using a soft brush and compressed air if available. Take care not to damage the internal parts of the burner. When removing the burner, take care not to disturb the gasket on the combustion chamber.
12.1.4 The electrode is an integral part of the burner head. Check that the spark gap is approximately 3 mm.
12.1.5 With the burner removed, clean the outer sur­faces of the tubes using a brush and wipe the inner surface of the reflector with a soft damp cloth - use a household detergent if necessary. Never use abra­sive cleaners on the reflectors.
12.1.6 Reassemble the burner in reverse order. Carry out the Commissioning and Testing Proce­dure on Page 35, Section 11.2.
12.2 Component Removal
First, isolate the heater from the gas and electricity supply; shut off appliance cock and disconnect the gas union connection. Switch off the local electrical supply and remove the appliance plug.
Entry to the burner assembly is gained by removing the two (2) door screws and removing the side cover.
12.2.1 Electrode (See Page 36, Section 12.1.4)
Remove the electrode cover and the two allen screws that secure the electrode to the burner head. Inspect the electrode gasket; replace as required.
12.2.2 Injector Jet
When the side cover is removed completely, the burner assembly is exposed. The jet is located in the mixing block behind the pipe plug. Remove brass injector jet (orifice). Replace in reverse sequence.
12.2.3 Solenoid Valve/Governor
Remove the electrode cover from the burner head and unplug spark and sensor leads. Remove burner head by unscrewing the two allen screws. Remove the tagged wires from the burner run neon. Remove the cross-head screw retaining the valve connec­tion. Withdraw the connection block. Remove the ground wire from the gas valve and from the air shutter screw. The gas train can now be withdrawn from the compartment. The gas train can now be dismantled. Replace part and reassemble in reverse order. NOTE: When reassembling, a suitable sealant must be used to ensure that no gas leaks occur. Further to this, the assembly must be square so that all the components are upright.
12.2.4 Automatic Flame Control Unit
Remove ignition lead, sense wire and other connectors. Unscrew two (2) screws from the cover. Replace if faulty. Refit in reverse sequence.
12.2.5 Neons
Remove the two push connectors from the neon. Remove the neons by depressing the retaining tabs inward. Replace in reverse sequence.
Page 43
SECTION 12: SERVICING INSTRUCTIONS
37
12.3 Maintenance Checklist
Installation, Service and Annual Inspection of the heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment.
Read this manual carefully before installation, operation, or service of this equipment.
The Vicinity of the Heater Do not store or use flammable objects, liquids or vapours near the heating
system. Immediately remove these items if they are present.
See Page 4, Section 3.
Vehicles and Other Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes or in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
See Page 4, Section 3.
Reflector Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped.
Clean outside surface with a damp cloth.
Vent Pipe Venting must be intact. Using a flashlight, look for obstructions, cracks on
the pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
Outside Air Inlet Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the
sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
Tube s Make sure there are no cracks.
Make sure tubes are connected and suspended securely.
See Page 10, Figure 8 through Page 13, Section 5.2.1.
Make sure there is no dirt, sagging, bending or distortion.
Clean or replace as required.
Gas Line Check for gas leaks. See Page 31, Figure 23.
Combustion Chamber Window
Make sure it is clean and free of cracks or holes.
Clean or replace as required.
Burner Head and Orifice Clear of obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Page 44
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
38
Electrode Replace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8” (3 mm).
Thermostat There should be no exposed wire or damage to the thermostat.
Suspension Points Make sure the heater is hanging securely. The chains must hang vertical.
Look for signs of wear on the chain or ceiling.
See Page 10, Figure 8.
Protective Grille (optional) The grille must be securely attached.
See Page 19, Section 6.3.1 through Page 20, Section 6.3.4.
Pump With pump operating, check for excessive vibration or noise. Vibration is
usually a sign that the impeller is out of balance. Turn off the system, insure power is shut off and remove the inlet plate. Check the shaft seal and replace it if worn or missing.
With the Power off:
Check the inlet and outlet of the pump for blockage or excessive soot and clean as necessary.
Check boots for cracking or deterioration and replace if necessary.
If a condensate drain is installed, check the condition of the drain and the non return valve attached.
Check the condition of the motor anti vibration mounts. Lift the motor from the rear; look for breaks in the rubber and replace if necessary.
Check the condition and operation of the pressure switch.
Page 45
SECTION 13: TROUBLESHOOTING
39
SECTION 13: TROUBLESHOOTING
13.1 Troubleshooting Flow Chart
Inspect the electrodes on
the affected burners. Are
they burned or damaged?
Ye s
Replace electrode.
(P/N 90430700)
Troubleshoot Ends
Does the burner light?
No
Ye s
Check fan for rotation,
reverse wiring (3 Ø only),
if required.
Pump motor must have
failed. Replace motor.
Remove obstruction.
Is there an obstruction
in the pump impeller?
No
Ye s
Is the motor connected
properly? Refer to the wiring
diagrams on the motor and
in the installation manual.
Motor may have tripped
overload switch. Wait 10-15
minutes and activate reset.
No
Check external wiring
for continuity.
Disconnect power to the
motor. Does the motor
turn freely?
No
Is there power output
(230/400 V) to the
pump?
No
Yes
Troubleshoot Ends.
Adjust damper to obtain
correct vacuum. After
adjustment does burner
operate?
Yes
No
Check wiring to the burner.
Make sure the burner is
plugged in.
Check clock program.
Reset as required.
Check circuit breaker and/or
fuse on panel supply circuit.
Is the clock set to on?
Yes
Is there power (230 V) to
the control panel?
Yes
No
START
No
Ignition module may have
failed. Replace module.
(P/N 90435201)
Yes
No
No
Yes
No
Yes
No
Yes
After 45 seconds pre-purge
period, do the burners light?
No
Turn up thermostat.
Does the fan turn on?
No
Yes
Ye s
Is there power (230 V) at
the burner receptacle?
Is there proper gas pressure
and flow to the burners?
No
Check fuse in main inlet.
Replace as required.
Correct gas problem. See Gas
Piping Section for details.
Unplug the burner, wait 10
seconds, then plug it in
again. Does the ignition
module begin ignition
sequence by sparking?
Is there 9 mbar vacuum at
the end vent?
Page 46
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
40
Troubleshooting Flow Chart
No
TROUBLESHOOT ENDS.
If problems persist, contact
your
ROBERTS GORDON
®
Independent Distributor.
Contact
ROBERTS GORDON
®
at www.rg-inc.com
Re-establish continuity.
No
Ye s
Is the insulation on the
igniter/sensor leads OK?
Re-establish connections.
No
Ye s
Ignition module may have
failed. Replace module.
(P/N 90435201)
Is there power to the
solenoid coil after the
purge period?
No
Restart burner ignition cycle.
Troubleshooting ends.
Using a manometer, check
vacuum at the mixing
chamber. Is the vacuum 1-3
mbar?
No
Ye s
Is the vacuum setting
too high?
Yes
Adjust system for proper
vacuum at the end vent.
Re-establish continuity.
Reverse polarity.
Is the wiring at the module
properly connected?
Are the Live and the
Neutral reversed?
No
Ye s
Is the continuity of the
earth wire established?
No
Ye s
Verify that the couplings have
been installed properly.
Ye s
No
Is the rotation of the
pump motor correct?
Adjust system for proper
vacuum at the end vent.
Follow burner check
procedure given above.
No
Ye s
Are there any "dead"
burners in a branch?
Is the vacuum setting
too low?
No
Ye s
Is the system leaking water?
No
Ye s
Does the burner stay on?
Ye s
No
Consult wiring instructions in
pump manuals listed below
for reversal instructions.
No
Do all the burners ignite
smoothly?
No
Ye s
No
Wrong end vent plate may
be installed. Make sure plate
and burner match.
Adjust the gap or replace
electrode. (P/N 90430700)
Ensure ignition lead is
securely fitted and that
electrode gap is correct. Is the
gap 3 mm?
Ye s
No
Regulator may have failed.
Replace regulator.
(P/N 90207102)
Ye s
Ignition module may have
failed. Replace module.
(P/N 90435201)
Yes
Page 47
SECTION 13: TROUBLESHOOTING
41
Figure 28: Vacuum Reading
Manometer
6
5
4
3
2
1
0
1
2
3
4
5
6
6
5
4
3
2
1
0
1
2
3
4
5
6
Insert tubing
about 150 mm (6").
Combustion Chamber
at end position
Cold Suction
Approximate reading after adjusting
damper couplings. (9 mbar)
Hot Suction
Approximate reading after adjusting
damper couplings. (7 mbar)
End Vent
Page 48
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
42
SECTION 14: REPLACEMENT PARTS Use only genuine ROBERTS GORDON
®
replacement parts. Use of parts not specified by Roberts-Gordon voids warranty. Failure to follow these instructions can result in property damage.
Item Description Part Number Item Description Part Number
A Ignition Module 90435201 N/S Rectifier Harness 02950001 B Gas Valve 90033400 N/S Ignition Wire 90427704 C Regulator 90207102 N/S Fuse (250 V, 1 A, 5 mm x 20 mm) E0007915 D Mixing Block 02790400 N/S Filter 90707000 E Burner Head Assembly 02721702 N/S Filters (box of 24 with gaskets) 01312400
F
Gasket - 2 required (Burner Head to Mixing Block)
01351100 N/S
Gasket (Burner Head to Combustion Chamber)
01367800
N/S Replacement Burner Head 02721700 N/S Mica Window Assembly 02553203
G Electrode 90430700 J
Relay Volt Free Contact (optional)
Relay Volt Free Base (optional)
C1049B
C1050B
H Electrode Gasket 02558501 N/S Combustion Chamber Gasket 01367800
I
Jet (see Section 2) located behind pipe plug
K Electrode Cover E0008108
N/S Main Wire Harness 02950004 N/S Sense Lead Wire 02950003
F
A
B
C
I
E
D
H
G
J
K
RELAY
Page 49
SECTION 15: SPECIFICATIONS
43
SECTION 15: SPECIFICATIONS
15.1 Material Specifications
15.1.1 Combustion and Tubes
100 mm dia 16 gauge heat treated aluminised mild steel.
15.1.2 Reflectors
NS3 H14 aluminium or 1.4016 2R stainless steel (option).
15.2 Burner Specifications
15.2.1 Sequence Controller
Fully automatic three try direct spark 100% shut off ignition flame rectification module.
15.2.2 Electrical
Rating: 230 V, 50/60 Hz, 1 Ø, 1 A
Connection: 3 pin moulded plug.
15.2.3 Gas Supply
Connection: Rc-1/2 (1/2" BSP int)
Natural G20: Minimum - Inlet 11 mbar (4.4 in wc)
Maximum - Inlet 50 mbar (20 in wc)
Natural G25: Minimum - Inlet 15 mbar (6 in wc)
Maximum - Inlet 50 mbar (20 in wc)
LP Gas (Propane or Butane):
Minimum - Inlet 32 mbar (13 in wc)
Maximum - Inlet 50 mbar (20 in wc)
15.3 Venting Specifications
15.3.1 Pumps
RG-30-1 Ø RG-30-3 Ø
RG-45-1 Ø RG-45-3 Ø
Consult the manufacturer for availability of alternate pumps.
15.3.2 Flue
Flue will be 150 mm dia duct. Flue material must conform to National Codes. The flue must be self supporting.
15.4 Suspension Specifications
Galvanised straight link welded chain.
Working load of 33 kg (75 lbs).
15.5 Controls Specifications
Factory assembled control panels, time switches and thermostats are available. Consult your factory representative for proper connection to electrical supply circuits.
* Based on Gross Calorific Value.
15.6 CORAYVAC
®
Heater
CRT10
CRT15
CRT20
CRT25
CRT30
Input - Gross (kW) 10 15 20 25 30
Input - Net (kW) 9 13.51822.527
Heated Area (m
2
) 16-105 24-158 32-210 40-263 48-316
Minimum Installation Height (m) 2.5 3.0 3.5 4.0 4.5
Weights:
Burner and Combustion Chamber 9.5 kg / burner
Radiant Tube with reflector, brackets, etc.
4.3 kg/m
Flow Units/burner 1.0 1.5 2.0 2.5 3.0
Flow Units/end vent 2.0 2.0 3.0 4.0 5.0
Maximum Burners/Branch 65433
Maximum Flow Units/Branch 8.0 10.5 12.0 12.5 15.0
Gas Consumption*
G20 (m
3
/h)
0.95 1.43 1.91 2.38 2.86
G25 (m
3
/h)
1.11 1.66 2.22 2.77 3.32
G30 (m
3
/h)
0.37 0.56 0.75 0.94 1.13
G31 (m
3
/h)
0.28 0.43 0.57 0.72 0.86
Page 50
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
44
15.7 Burner Specifications
General Specifications for CORAYVAC® heaters are as follows:
*See Page 4, Section 3 for clearances to combustibles.
BURNER COMPONENTS
NOTE: fluor = fluorescent.
Air Shutter
End Vent
Plate
Orifice Size
G20 G25 G31 G30
CRT 10
#01 #2 #35 (black)
3.0 mm
(fluor yellow)
2.4 mm
(fluor red) #44 (silver)
CRT 15
#15 #2
3.4 mm
(fluor orange)
3.7 mm
(fluor pink)
#35 (black)
2.6 mm
(fluor green)
CRT 20
#6 #3 #22 (rose) #19 (red) #30 (yellow)
3.0 mm
(fluor yellow)
CRT 25
#8 #4 #14 (purple) #10 (orange)
3.7 mm
(fluor pink)
3.5 mm
(fluor blue)
CRT 30 #30 #5 #7 (white) #3 (drk green) #22 (rose) #25 (brown)
51 cm
(20")
24.4 cm (10")
9 cm
(3 1/2")
19 cm
(7 5/8")
36 cm
(14 1/4")
24 cm
(9 1/2")
.4 cm
(5/32")
19 cm
(7 1/2")
17 cm
(6 7/8")
32 cm
(12 1/2")
10 cm
(4")
Page 51
SECTION 15: SPECIFICATIONS
45
15.8 Pump Dimensions and Specifications
A
150 mm
C
D
62 mm
205 mm
(mounting holes)
B
F
E
150 mm
230 mm
(mounting holes)
Pump Specifications
Model RG30-1 RG45-1 RG30-3 RG45-3
Part No.
90710108 90710109 90710111 90710112
Weight (kg)
41.5 43.5 41.5 43.5
Power (W)
750 1100 750 1100
Run Current (A)
3.25 4.8 2.75 2.75
Start Current (A)
14.25 23.0 8.5 13.2
Supply (V)
230 V 1 Ø 50 Hz 230 V 1 Ø 50 Hz 400 V 3 Ø 50 Hz 400 V 3 Ø 50 Hz
Pump Dimensional Data (mm)
Model A B C D E F
RG30-1
650 630 386 430 124 545
RG30-3
650 630 386 430 124 545
RG45-1
674 650 396 435 121 567
RG45-3
674 650 396 435 121 548
Page 52
CORAYVAC® INSTALLATION OPERATION AND SERVICE MANUAL
46
Page 53
Page 54
Infrared Heating
Maintain ???? cm clearance
to the side and
???? cm clearance below
the heater from vehicles
and combustible materials.
www.rg-inc.com Printed in the U.S.A. P/N 91037912
Attach this information to a wall near the ROBERTS GORDON
®
heater.
Installation Code: ROBERTS GORDON® products are to be installed only in accordance with local laws, codes and regulations, and only by a contractor qualified in the installation and service of gas-fired heating equipment.
For optimum product performance and safety, installation, service and annual inspections must be completed by a contractor qualified in the installation and service of gas-fired heating equipment.
© 2004 ROBERTS GORDON® All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon.
Read the Installation, Operation, and Service Manual thoroughly before installation, operation, or service.
Know your model number and installed configuration.
Model number and installed configuration are found on the burner and in the Installation, Operation and Service Manual.
Write the largest clearance dimensions with permanent ink according to your model number and configuration in the open spaces below.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting.
1. Set the thermostat to off or the lowest setting.
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your registered installer/contractor qualified in the installation and service of gas-fired heating equipment.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
Fire Hazard
Some objects can catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
TO TURN OFF THE HEATER
Service Telephone: +44(0) 1902 498733 Service Fax: +44(0) 1902 401464 E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
WARNING
Roberts-Gordon
1250 William Street P.O. Box 44 Buffalo, NY 14240-0044 USA Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
Roberts-Gordon
76 Main Street West, Unit 10 Grimsby, Ontario L3M 1R6 Canada Telephone: 905.945.5403 Fax: 905.945.0511
Roberts-Gordon
Oxford Street Bilston, West Midlands WV14 7EG UK Telephone: +44(0) 1902 494425 Fax: +44(0) 1902 403200
®
Loading...