Rheem R801TA050314MSA, (-)(-)80MSX100C50SA, (-)(-)80MSX075B40SA, (-)(-)80MSX050A30SA, R801TA075417MSA Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
FOR UPFLO W/HORIZONTAL SINGLE STA GE GAS FURNA CES
(-)801S UPFLOW/HORIZONTAL SERIES (-)801P UPFLOW/HORIZONTAL SERIES (-)(-)80MSS UPFLOW/HORIZONTAL SERIES (-)(-)80MSP UPFLOW/HORIZONTAL SERIES
U.L. and/or C.S.A. recognized fuel gas and CO (carbon monoxide) detectors are rec­ommended in all applications, and their installation should be in accordance with the manufacturer’s recommendations and/or local laws, rules, regulations, or customs.
92-24161-142-04
SUPERSEDES 92-24161-142-03
Factory Use Only
ISO 9001:2008
ST-A1220-01-X0
2
Contents
TABLE OF CONTENTS
1 TABLE OF CONTENTS. . . . . . . . . . . . . . . . . . . . . . . 2
2 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . 3
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
California Proposition 65 Note . . . . . . . . . . . . . . . . . . 4
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 SAFETY INFORMATION. . . . . . . . . . . . . . . . . . . . . . 6
Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Important Information About Ef ficiency and Quality. . 7
4 LOCATION REQUIREMENTS . . . . . . . . . . . . . . . . . 8
Site Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Clearance –Accessibility . . . . . . . . . . . . . . . . . . . . . . 8
Upflow Dimensions and Clearance Table . . . . . . . . . 9
5 DUCTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Upflow Installations. . . . . . . . . . . . . . . . . . . . . . . . . . 11
Horizontal Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6 COMBUSTION AND VENTILA TION AIR. . . . . . . . 14
Combustion Air Requirements. . . . . . . . . . . . . . . . . 14
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
“B-1” Vertical Venting . . . . . . . . . . . . . . . . . . . . . . . . 19
Special Vent Systems (SVS) . . . . . . . . . . . . . . . . . . 20
Power Vent Systems . . . . . . . . . . . . . . . . . . . . . . . . 22
Existing Vent Systems . . . . . . . . . . . . . . . . . . . . . . . 22
7 GAS SUPPLY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Gas Supply and Piping. . . . . . . . . . . . . . . . . . . . . . . 23
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Setting Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . 26
Supply Gas Pressure Measurement . . . . . . . . . . . . 26
Manifold Gas Pressure Measurement. . . . . . . . . . . 26
8 LP CONVERSION . . . . . . . . . . . . . . . . . . . . . . . . . . 27
9 ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . 28
Reversing The Electrical Connection. . . . . . . . . . . . 28
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Field Installed Option Accessories. . . . . . . . . . . . . . 30
Electronic Air Cleaner. . . . . . . . . . . . . . . . . . . . . . . . 30
Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
RXGW-B01 Chimney Adapter . . . . . . . . . . . . . . . . . 30
RXGW-C01 Four Inch Flue Adapter . . . . . . . . . . . . 30
11 TWINNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Furnace T winning Installations. . . . . . . . . . . . . . . . . 32
Control Boards . . . . . . . . . . . . . . . . . . . . . . . . . . 33-34
12 HIGH ALTITUDE . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Natural Gas at High Altitudes. . . . . . . . . . . . . . . . . . 35
LP Gas at High Altitudes. . . . . . . . . . . . . . . . . . . . . . 37
13 STARTUP PR OCEDURES . . . . . . . . . . . . . . . . . . . 38
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . 38
14 DIAGNOSTICS AND F AULT CODES. . . . . . . . . . . 39
15 LOCKOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
16 FIELD SELECTIONS & ADJUSTMENTS . . . . . . . 41
Field Selections – Dipswitches. . . . . . . . . . . . . . . . . 41
17 FA ULT CLEAR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
18 FA ULT RECALL. . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
19 FLAME STATUS L.E.D.. . . . . . . . . . . . . . . . . . . . . . 42
20 TIMING DIAGRAM. . . . . . . . . . . . . . . . . . . . . . . . . . 42
21 ADJUSTING OR CHECKING FURNACE INPUT . 43
22 SETTING INPUT RATE. . . . . . . . . . . . . . . . . . . . . . 44
23 AIRFLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Blower Speed Selection. . . . . . . . . . . . . . . . . . . . . . 46
24 SAFETY FEATURES. . . . . . . . . . . . . . . . . . . . . . . . 47
25 MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
26 SYSTEM OPERATION INFORMATION . . . . . . . . . 49
27 ANNUAL INSPECTION. . . . . . . . . . . . . . . . . . . . . . 49
28 REPLACEMENT P AR TS. . . . . . . . . . . . . . . . . . . . . 49
24 TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . 50
30 WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . 51
IMPORTANT: TO INSURE PROPER INSTALLATION AND OPERATION OF THIS PRODUCT, COMPLETELY READ ALL INSTRUC-
TIONS PRIOR TO ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE, MAINTAIN OR REP AIR THIS PRODUCT. UPON UNPACKING OF THE FURNA CE, INSPECT ALL PARTS FOR DAMAGE PRIOR TO INSTALLATION AND START-UP.
3
General Information
GENERAL INFORMATION
NOTE: A heat loss calculation should be performed to properly
determine the required furnace BTU size for the structure. Also, the duct must be properly designed and installed for proper air­flow. Existing ductwork must be inspected for proper size and to make sure that it is properly sealed. Proper airflow is necessary for both user comfort and equipment performance.
Before opening the furnace carton, verify that the data tags on the carton specify the furnace model number that was ordered from the distributor and are correct for the installation. If not, return the unit without opening the carton. If the model number is correct, open the carton and verify that the furnace rating label specifies the same furnace model number that is speci­fied on the carton label. If the model numbers do not match, re­turn the furnace to the distributor .
IMPORTANT: Proper application, installation and maintenance of
this furnace and system is a must if consumers are to receive the full benefits for which they have paid.
The (-)801S/(-)801P series furnaces are design certified by CSA for use with natural and propane gases as follows:
As a Category I furnace, it may be vented vertically with type B­1 vent pipe and also may be common vented as described in these instructions.
This furnace should be installed in accordance with the American National Standard Z223.1 - latest edition booklet entitled “National Fuel Gas Code” (NFPA 54), and the requirements or codes of the local utility or other authority having jurisdiction including local plumbing or waste water codes.
With the introduction of higher efficiency furnaces, special attention must be paid to the venting system. Only listed venting systems may be used as stated in the installation instructions and the
Na-
tional Fuel Gas Code, ANSI Z223.1 (NFPA 54),.
Since furnace technology and venting requirements are changing, awareness of local, state, and federal codes and industry changes is imperative.
ST-A1220-02
FIGURE 1
FURNACE COMPONENTS
14
15
16
17
21
18
19
1
2
3
4
20
5
13
ITEM NO.
12
11
10
9
8
DESCRIPTION
1
DOOR SWITCH
2
TRANSFORMER
3
JUNCTION BOX
4
LOW VOLTAGE TERMINAL
5
SOLID METAL BASE PAN ((-) 801P ONLY)
6
FURNACE CONTROL
7
CONTROL MOUNTING PLATE
8
CAPACITOR
9
BLOWER
10
IGNITER
11
GAS VALVE
12
INDUCED DRAFT BLOWER
13
4” FLUE ADAPTER (OPTIONAL)
14
COMBUSTION AIR INLET
15
MAIN LIMIT
16
COMBUSTION AIR DIFFUSER
17
MAIN PRESSURE SWITCH
18
BURNER
19
FLAME SENSOR
20
HEAT ASSISTED LIMIT CONTROL (HALC)
21
OVER TEMPERATURE SWITCH
7
6
ST-A1220-02-03
4
Install this furnace in accordance with the American National Stan­dard Z223.1 – latest edition entitled “National Fuel Gas Code” (NFPA54) and requirements or codes of the local utilities or other authorities having jurisdiction. This is available from the following:
National Fire Protection Association, Inc. Batterymarch Park Quincy, MA 02269
RECEIVING
Immediately upon receipt, all cartons and contents should be in­spected for transit damage. Units with damaged cartons should be opened immediately. If damage is found, it should be noted on the delivery papers, and a damage claim filed with the last carrier.
• After unit has been delivered to job site, remove carton taking care not to damage unit.
• Check the unit rating plate for unit size, electric heat, coil, volt­age, phase, etc. to be sure equipment matches what is re­quired for the job specification.
• Read the entire instructions before starting the installation.
• Some building codes require extra cabinet insulation and gas­keting when unit is installed in attic applications.
• If installed in an unconditioned space, apply caulking around the power wires, control wires, refrigerant tubing and conden­sate line where they enter the cabinet. Seal the power wires on the inside where they exit conduit opening. Caulking is re­quired to prevent air leakage into and condensate from forming inside the unit, control box, and on electrical controls.
• Install the unit in such a way as to allow necessary access to the coil/filter rack and blower/control compartment.
• Install the unit in accordance with any local code which may apply and the national codes. Latest editions are available from: “National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269.” These publications are:
• ANSI/NFPA No. 70-(Latest Edition) National Electrical Code.
• NFPA90A Installation of Air Conditioning and Ventilating Sys­tems.
• NFPA90B Installation of warm air heating and air conditioning systems.
• The equipment has been evaluated in accordance with the Code of Federal Regulations, Chapter XX, Part 3280.
CALIFORNIA RESIDENTS ONLY
IMPORTANT: All manufacturer products meet current Federal
OSHA Guidelines for safety. California Proposition 65 warnings are required for certain products, which are not covered by the OSHA standards.
California's Proposition 65 requires warnings for products sold in California that contain, or produce, any of over 600 listed chemi­cals known to the State of California to cause cancer or birth de­fects such as fiberglass insulation, lead in brass, and combustion products from natural gas.
All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facilitates manufacturing and shipping. We cannot always know “when, or if” products will be sold in the California market.
You may receive inquiries from customers about chemicals found in, or produced by, some of our heating and air-conditioning equip­ment, or found in natural gas used with some of our products. Listed below are those chemicals and substances commonly as­sociated with similar equipment in our industry and other manu­facturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene More details are available at the Websites for OSHA (Occupa-
tional Safety and Health Administration), at www.osha.gov
and the State of California's OEHHA (Office of Environmental Health Haz­ard Assessment), at www.oehha.org.
Consumer education is im­portant since the chemicals and substances on the list are found in our daily lives. Most consumers are aware that products pres­ent safety and health risks, when improperly used, handled and maintained.
GENERAL INFORMATION (cont.)
General Information
5
Installation Checklist
REFER TO INSTALLATION INSTRUCTIONS
GAS SUPPLY
______ Correct pipe size (record size) ______ Correct supply pressure (during furnace operation) (record pressure) ______ Manifold pressure (record upstream pressure) ______ No gas leaks ______ L.P. Kit Number (if applicable) (record kit number)
ELECTRICAL
______ 115 V.A.C. supply (Dedicated Circuit) (record voltage) ______ Polarity observed ______ Furnace properly grounded ______ Correct wire size (record type and gauge)
FURNACE INSTALLATION
______ Correct clearance to combustibles (record clearance) ______ Correct clearance for service (at front) (record clearance)
DUCT STATIC PRESSURE
______ in. w.c. on heating speed (record static pressure) ______ in. w.c. on cooling speed (record static pressure) ______ Air temperature rise in heat (record air temperature rise) ______ Air temperature rise in cool (record air temperature rise)
VENTING
______ Correct vent pipe diameter and length (according to NFGC tables) _________________ Vent connection size ______ Correct venting material (according to NFGC tables) ______ Correct lining for masonry chimneys ______ Adequate clearance from combustibles ______ Proper negative pressure reading in the vent ______ Vent pipe secured to induced draft blower housing
COMBUSTION AIR
______ Proper source of combustion air ______ Correct combustion air opening size ______ Optional attic combustion air pull ______ Non-attic combustion air pull
Checklist
Installation Instructions remain with the furnace as a reference guide to the servicing contractor. We recommend that performance and installation data be recorded for future ref erence on this sheet to meet service and warranty obligations so that job site information is available when required.
Safety Information
SAFETY INFORMATION
!
WARNING
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS REC­OMMENDED THAT AN AUXILIARY DRAIN PAN BE IN­STALLED UNDER THIS FURNACE AND ANY INSTALLED EVAPORATOR COIL THAT IS LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGE TO THE BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT OF AN OVERFLOW OF THE A/C COIL DRAIN PAN.
!
WARNING
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME!! THIS FURNACE IS NOT APPROVED FOR INSTALLATION IN A MOBILE HOME. DOING SO COULD CAUSE FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
!
WARNING
INSTALL THIS FURNACE ONLY IN A LOCATION AND PO­SITION AS SPECIFIED IN THE LOCATION REQUIRE­MENTS AND CONSIDERATIONS SECTION OF THESE INSTRUCTIONS.
!
WARNING
IMPROPER INSTALLATION CAN RESULT IN UNSATISFAC­TORY OPERATION AND/OR DANGEROUS CONDITIONS AND ARE NOT COVERED BY THE MANUFACTURER’S WARRANTY.
!
WARNING
DO NOT BYPASS, JUMPER, OR REMOVE ANY SAFETY SWITCH FROM THE FURNACE CONTROL CIRCUIT. IF A SAFETY SWITCH CAUSES THE FURNACE TO SHUT DOWN OR OPERATE INTERMITTENTLY, IT IS AN INDICA­TION OF A POTENTIAL SAFETY HAZARD THAT MUST BE ADDRESSED BY A QUALIFIED TECHNICIAN, SERVICE AGENCY OR THE GAS SUPPLIER. DO NOT RESET SAFETY CONTROLS WITHOUT CORRECTIVE ACTION AND/OR VERIFICATION OF PROPER SAFE OPERATION BY A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
REPLACE ANY SAFETY CONTROL COMPONENT ONLY WITH IDENTICAL OEM REPLACEMENT PARTS. WHEN A NEW SAFETY SWITCH IS INSTALLED, IT MUST BE TESTED FOR A MINIMUM OF 15 MINUTES WITH THE FURNACE OPERATING AT MAXIMUM INPUT RATE AND WITH BOTH BLOWER AND BURNER DOOR INSTALLED. IF THE FURNACE IS INSTALLED IN A CLOSET, THE CLOSET DOOR MUST ALSO BE CLOSED FOR THIS TEST. REPEAT THE TEST AT THE MINIMUM INPUT RATE IF THE FURNACE IS A MULTI-STAGE FURNACE.
!
WARNING
USE ONLY WITH THE TYPE OF GAS APPROVED FOR THIS FURNACE. REFER T O THE FURNACE RATING PLATE.
!
WARNING
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME. USE A COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS TO CHECK ALL CONNECTIONS, AS SPECIFIED IN GAS SUPPLY AND PIPING SECTION OF THESE INSTRUC­TIONS.
!
WARNING
COMBUSTION PRODUCTS MUST BE DISCHARGED OUT­DOORS. CONNECT THIS FURNACE TO AN APPROVED VENT SYSTEM ONLY, AS SPECIFIED IN THE VENT PIPE INSTALLATION SECTION OF THESE INSTRUCTIONS.
!
WARNING
WHEN A FURNACE IS INSTALLED SO THAT SUPPLY DUCTS CARRY AIR CIRCULATED BY THE FURNACE TO AREAS OUTSIDE THE SPACE CONTAINING THE FUR­NACE, THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT(S) SEALED TO THE FURNACE CASING AND TERMI­NATING OUTSIDE THE SPACE CONTAINING THE FUR­NACE.
!
WARNING
WHENEVER THE FACTORY RETURN-AIR CONNECTION IS NOT USED IT MUST BE SEALED. A SOLID METAL BASE PLATE MUST BE INSTALLED AND SEALED. FAC­TORY BASE PLATES ARE AVAILABLE AS ACCESSORY ITEMS. (PART NUMBERS ARE LISTED IN THE SPEC SHEET FOR THE FURNACE.) FAILURE TO INSTALL AND SEAL THE BASE PLATE AND RETURN AIR DUCT CON­NECTIONS MAY ALLOW CARBON MONOXIDE AND OTHER CONTAMINANTS TO BE DRAWN INTO THE CON­DITIONED AIR SPACE AND DISTRIBUTED THROUGHOUT THE HEATED SPACE.
!
WARNING
DO NOT OPERATE THE SYSTEM WITHOUT FILTERS. A PORTION OF THE DUST ENTRAINED IN THE AIR MAY TEMPORARILY LODGE IN THE AIR DUCT RUNS AND AT THE SUPPLY REGISTERS. ANY CIRCULATED DUST PAR­TICLES WILL BE HEATED AND CHARRED BY CONTACT WITH THE FURNACE HEAT EXCHANGER. THIS SOOTY RESIDUE WILL SOIL CEILINGS, WALLS, DRAPES, CAR­PETS AND OTHER HOUSEHOLD ARTICLES. SOOT DAM­AGE MAY ALSO RESULT WITH, OR WITHOUT, FILTERS IN PLACE, WHEN CERTAIN TYPES OF CANDLES ARE BURNED, OR CANDLEWICKS ARE LEFT UNTRIMMED.
6
!
WARNING
COMBUSTION AND VENTILATION AIR MUST BE PRO­VIDED TO THE FURNACE AS REQUIRED BY THE NA­TIONAL FUEL-GAS CODE (U.S.) AND CSA B149.1 (CANADA) AND THE COMBUSTION AND VENTILATION AIR SECTION OF THESE INSTRUCTIONS.
7
SAFETY
Safety Information
IMPORTANT INFORMATION ABOUT EFFICIENCY AND INDOOR AIR QUALITY
Central cooling and heating equipment is only as efficient as the duct system that carries the cooled or heated air. To maintain effi­ciency, comfort and good indoor air quality, it is important to have the proper balance between the air being supplied to each room and the air returning to the cooling and heating equipment.
Proper balance and sealing of the duct system improves the effi­ciency of the heating and air conditioning system and improves the indoor air quality of the home by reducing the amount of air­borne pollutants that enter homes from spaces where the duct­work and / or equipment is located. The manufacturer and the U.S. Environmental Protection Agency’s Energy Star Program recommend that central duct systems be checked by a qualified contractor for proper balance and sealing.
FIGURE 2
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES
Adapted from
Residential Duct Diagnostics and Repair
, with permission of Air Conditioning
Contractors of America (ACCA).
!
WARNING
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM AND DRAW POLLUTANTS SUCH AS DIRT, DUST, FUMES AND ODORS INTO THE HOME CAUSING PROPERTY DAMAGE. FUMES AND ODORS FROM TOXIC, VOLATILE OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMO­BILE EXHAUST AND CARBON MONOXIDE (CO), CAN BE DRAWN INTO THE LIVING SPACE THROUGH LEAKING DUCTS AND UNBALANCED DUCT SYSTEMS CAUSING PERSONAL INJURY OR DEATH (SEE FIGURE 2).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LO­CATED IN GARAGES OR OFF-GARAGE STORAGE AREAS - ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS IN­CLUDING CARBON MONOXIDE FROM MIGRATING INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LO­CATED IN SPACES CONTAINING FUEL BURNING AP­PLIANCES SUCH AS WATER HEATERS OR BOILERS ­ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIP­MENT AND DUCT MUST ALSO BE SEALED TO PRE­VENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPROD­UCTS INCLUDING CARBON MONOXIDE INTO THE LIV­ING SPACE.
!
WARNING
BLOWER AND BURNERS MUST NEVER BE OPERATED WITHOUT THE BLOWER DOOR IN PLACE. THIS IS TO PREVENT DRAWING GAS FUMES (WHICH COULD CON­TAIN HAZARDOUS CARBON MONOXIDE) INTO THE HOME THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
!
WARNING
ALWAYS INSTALL THE FURNACE TO OPERATE WITHIN THE FURNACE’S INTENDED TEMPERATURE-RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTER­NAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE, AS SPECIFIED IN THE DUCTING SECTION OF THESE INSTRUCTIONS. SEE ALSO FURNACE RATING PLATE.
THE FURNACE MAY BE USED FOR HEATING OF BUILD­INGS OR STRUCTURES UNDER CONSTRUCTION.
INSTALLATION MUST COMPLY WITH ALL INSTALLATION INSTRUCTIONS INCLUDING:
PROPER VENT INSTALLA TION;
FURNACE OPERATING UNDER THERMOSTAT CONTROL; RETURN AIR DUCT SEALED TO THE FURNACE;
AIR FILTERS IN PLACE; SET FURNACE INPUT RATE AND TEMPERATURE RISE PER RATING PLATE MARKINGS; MEANS FOR PROVIDING OUTDOOR AIR RE-
QUIRED FOR COMBUSTION; RETURN AIR TEMPERATURE MAINTAINED BE-
TWEEN 55°F (13°C) AND 80°F (27°C); AND CLEAN FURNACE, DUCT WORK AND COMPO-
NENTS UPON SUBSTANTIAL COMPLETION OF THE CONSTRUCTION PROCESS, AND VERIFY THAT THE FURNACE OPERATING CONDITIONS INCLUDING IGNITION, INPUT RATE, TEMPERA­TURE RISE AND VENTING, ACCORDING TO THE INSTRUCTIONS AND CODES.
8
1. IMPORTANT: If using a cooling evaporator coil with this fur- nace, be sure the air passes over the heat exchanger before passing over the cooling coil. The cooled air passing over the warm ambient air inside the heat exchanger tubes can cause condensation inside the tubes resulting in corrosion and even­tual failure. An auxiliary drain pan should extend under any evaporator coil installed with the furnace.
If there are manual dampers, they must be equipped to prevent heating or cooling operation unless the damper is in the full heat or cool position.
2. NOTE: This furnace is shipped with heat exchanger support brackets installed under the back of the heat exchanger. These may be removed before installation, but it is not required.
3. IMPORTANT:
This furnace is not approved or recommended
for installation on its back, with access doors facing upwards.
4. This furnace is suitable for installation in buildings constructed on-site. This heating unit should be centralized with respect to the heat distribution system as much as practicable.
5. NOTE: These furnaces are approved for installation in attics, as well as alcoves, utility rooms, closets and crawlspaces.
6. IMPORTANT:
Support this unit when installed. For attic or cra wl space installation, horizontal furnaces may be installed on com­bustible wood flooring or by using support brackets. See Figure
3.
7. IMPORTANT:
If installing in a utility room, be sure the door is
wide enough to:
a. allow the largest part of the furnace to pass; or
b. allow any other appliance (such as a water heater) to pass.
SITE SELECTION
1. Select a site in the building near the center of the pro­posed, or existing, duct system.
2. Give consideration to the vent system piping when se­lecting the furnace location. Be sure the venting system can get from the furnace to the termination with minimal length and elbows.
3. Locate the furnace near the existing gas piping. Or, if running a new gas line, locate the furnace to minimize the length and elbows in the gas piping. See Figure 3.
4. Locate the furnace to maintain proper clearance to combustibles as shown in following Figure 4.
CLEARANCE – ACCESSIBILITY
The design of forced air furnaces with input ratings as listed in the tables under Figure 4 are to combustible mate­rials shown in inches.
See name/rating plate and clearance label for specific model number and clearance information.
Service clearance of at least 24 inches (30 cm) is recom­mended in front of all furnaces.
NOTE: Use recommended 24” (30 cm) clearance if accessi­bility clearances are greater than fire protection clearances.
ACCESSIBILITY CLEARANCES, WHERE GREATER, MUST TAKE PRECEDENCE OVER FIRE PROTECTION CLEAR­ANCES.
GENERAL INFORMATION
LOCATION REQUIREMENTS
Location
!
WARNING
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE, IT MUST BE INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN 18 INCHES [450MM] ABOVE THE FLOOR. THIS IS TO PRE­VENT THE RISK OF IGNITING FLAMMABLE VAPORS WHICH MAY BE PRESENT IN A GARAGE. ALSO, THE FUR­NACE MUST BE LOCATED OR PROTECTED TO AVOID PHYSICAL DAMAGE BY VEHICLES. FAILURE TO FOLLOW THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
!
WARNING
THIS FURNACE IS NO T APPROVED OR RECOMMENDED FOR INSTALLATION ON ITS BACK, WITH ACCESS DOORS F ACING UPWARDS.
!
WARNING
DO NOT LIFT THE UNIT BY THE HEAT EXCHANGER TUBES. DOING SO CAN D AMAGE THE HEAT EX­CHANGER ASSEMBLY.
9
Location
GENERAL INFORMATION (cont.)
LOCATION REQUIREMENTS
ST-A1220-03
FIGURE 3
!
WARNING
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE JACKET. THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQ­UIDS. PLACEMENT OF COMBUSTIBLE MATERIALS ON, AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROP­ERTY DAMAGE, PERSONAL INJURY OR DEATH. THE HOMEOWNER SHOULD BE CAUTIONED THAT THE FUR­NACE AREA MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PURPOSES.
!
WARNING
UPFLOW AND HORIZONTAL FURNACES ARE DESIGN­CERTIFIED FOR INSTALLATION ON COMBUSTIBLE FLOORS. NO TE, HOWEVER, THAT FURNACES MUST NOT BE INSTALLED DIRECTLY ON CARPETING, TILE OR OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD FLOORING. INSTALLATION ON A COMBUSTIBLE MATE­RIAL CAN RESULT IN FIRE, CAUSING PROPERTY DAM­AGE, PERSONAL INJURY OR DEATH.
NOTE:
HORIZONTAL LEFT ORIENTATION DEPICTED IN ILLUSTRATION. HORIZONTAL RIGHT ORIENTATION IS SIMILAR IN INSTALLATION.
AIR FLOW
10
BOTTOM
TOP
LEFT SIDE FRONT RIGHT SIDE
GAS
CONNECTION
ELECTRICAL CONNECTION
LINE VOLTAGE
ELECTRICAL CONNECTION
LOW VOLTAGE
OPTIONAL
GAS CONNECTION
OPTIONAL LOW
VOLTAGE WIRING
OPTIONAL LINE VOLTAGE
WIRING
A
I
R
F
L
O
W
RETURN
AIR
SUPPLY
AIR
HOT
MODEL A B C D E F RIGHT SIDE BACK TOP FRONT VENT
5 14 13 27/32 10 5/8 11 1/2 1 7/8 0 4༄ 01 36༅ 85 lbs.
7 17 1/2 16 11/32 12 3/8 15 2 1/2 0 3༄ 01 36༅ 105 lbs.
10 21 19 27/32 14 1/8 18 1/2 2 1/2 0 0 0 1 3 6༅ 120 lbs.
12 24 1/2 23 11/32 15 7/8 22 2 1/2 0 0 0 1 3 6༅ 140 lbs.
15 24 1/2 23 11/32 15 7/8 22 2 1/2 0 0 0 1 3 6༅ 150 lbs.
༃MAY REQUIRE 3" TO 4" OR 3" TO 5" ADAPTER.
4" ADAPTER INCLUDED WITH (-)801P UNITS.
༄MAY BE 0" WITH TYPE B VENT.
༅MAY BE 1" WITH TYPE B VENT.
LEFT SIDE
REDUCED CLEARANCE (IN.)
SHIP
WGTS.
FIGURE 4
UPFLOW/HORIZONTAL DIMENSIONS
Location
REDUCED CLEARANCE (IN.)
Input A B C D E F
Left Right
Back Top Front Vent
Ship.
Side Side Wgts.
050 14 12
27
/32 10
5
/8 11
1
/2 1
7
/8 0 4 0 1 3 685 lbs.
070 17
1
/2 16
11
/32 12
3
/8 15 2
1
/2 0 30 1 3 6105 lbs.
100 21 19
27
/32 14
1
/8 18
1
/2 2
1
/2 0 0 0 1 3 6120 lbs.
120 24
1
/2 23
11
/32 15
7
/8 22 2
1
/2 0 0 0 1 3 6140 lbs.
150 24
1
/2 23
11
/32 15
7
/8 22 2
1
/2 0 0 0 1 3 6150 lbs.
CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
UPFLOW/HORIZONTAL MODELS
May require 3” to 4” or 3” to 5” adapter.
4” adapter optional.
May be 0” with type B vent.
May be 1” with type B vent.
*See furnace speck sheet for availability.
ST-A1220-04
11
Proper air flow is required for the correct operation of this furnace. Restricted air flow can cause erratic operation and can damage the heat exchanger. The duct system must carry the correct amount of air for heating and cooling if summer air conditioning is used.
IMPORTANT: When using outside air, design and adjust the system to maintain a return air temperature ABOVE 55° F during the heating season.
NOTE: Return air grilles and warm air registers must not be obstructed or closed.
UPFLO W INSTALLATIONS
1. Position the unit to minimize long runs of duct or runs of duct with many turns and elbows.
2. For side return: Cut an opening in the side. The open­ing should be cut the full width and height of the knockouts on the unit. See Figure 6.
3. If summer air conditioning is desired, position the in­door coil on the supply-air side of the unit. Ensure that no air can bypass the coil.
4. Connect the furnace to the supply air plenum. See Fig­ure 7.
5. Connect the return air ducting to the return-air opening at the bottom and/or side of the unit. Make the connec­tions air-tight to prevent the migration of toxic fumes and odors including carbon monoxide from migrating into the living space.
6. If a filter is installed near the furnace, be sure to have adequate space for installation and removal of the unit filter.
7. NOTE: Where the maximum airflow is 1800 CFM or more, BOTH sides or the bottom must be used for the return air. Do not take return air from the back of the unit.
NOTE: DO NOT take return air from furnace rooms, garages or cold areas. Avoid return air from utility rooms, kitchens, laundry rooms and bathrooms.
DUCTING
Ducting
!
WARNING
BLOWER AND BURNERS MUST NEVER BE OPERATED WITHOUT THE BLOWER DOOR IN PLACE. THIS IS TO PREVENT DRAWING GAS FUMES (WHICH COULD CON­TAIN HAZARDOUS CARBON MONOXIDE) INTO THE HOME THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
!
WARNING
THE SOLID METAL BASE (SHIPPED WITH THE 801P FURNACE) PLATE MUST BE INSTALLED IN THE FURNACE BOTTOM WHEN USING SIDE AIR RE­TURN. FAILURE TO INSTALL A BASE PLATE COULD CAUSE THE PRODUCTS OF COMBUSTION TO CIR­CULATE INTO THE LIVING SP ACE AND CREATE POTENTIAL LY HAZARDOUS CONDITIONS, INCLUD­ING CARBON MONOXIDE POISONING OR DEATH. FOR BOTTOM RETURN, A SOLID METAL BASE PAN MUST NOT BE INSTALLED. SEE FIGURE 5.
!
WARNING
SOME HEATING AIRFLOW VALUES MAY BE HIGHER THAN THOSE REQUIRED FOR COOLING. BE SURE TO SIZE DUCT FOR THE MAXIMUM POS­SIBLE AIRFLOW VALUE.
SIZE AIRFLOW DISTRIBUTION SYSTEM TO AC­CEPTABLE INDUSTRY STANDARDS AND METH­ODS. TOTAL STATIC PRESSURE DROP OF THE AIR DISTRIBUTION SYSTEM SHOULD NOT EXCEED .8 INCHES W.C. THIS WILL INCLUDE ANY AIR CONDI­TIONER COIL, AIR FILTRATION SYSTEM, ZONING SYSTEM, DUCTWORK, ETC. REFER TO ADDED EQUIPMENT TECHNICAL INFORMATION TO OBTAIN PRESSURE DROP INFORMATION WHEN EQUIP­MENT IS OPERATING AT RECOMMENDED HEAT­ING OR COOLING CFMS.
12
Ducting
DUCTING
FIGURE 5
FIGURE 6
FIGURE 7
ST-A1220-10
ST-A1220-11
ST-A1220-08
LIFT UP, PULL OUT
NOTE:
SOLID BASE PLATE PROVIDED WITH (-)801P MODELS ONLY.
WHEN SOLID BASE PLATE IS USED . TAPE AROUND BOTTOM FLANGES OF CABINET BEFORE THE UNIT IS INSTALLED.
SOLID BASE FLANGE
FITS UNDER
CABINET BOTTOM
1. REMOVE 2 SCREWS, LIFT BASE UP, SLIDE FORWARD TO REMOVE.
2. INSTALLATION IS REVERSE OF REMOVAL. ** VERIFY REAR FLANGE IS SEALED PROPERLY AS SHOWN IN DETAIL.
ST-A1220-10-X0
13
HORIZONTAL UNITS
1.Position the unit to minimize long runs of duct or runs of duct with many turns and elbows.
2.Unit can be mounted left or right side airflow configura­tion.
3.Position the unit on adequate supports or by using sup­port brackets (see Figure 8) and connect supply plenum.
4.If summer air conditioning is desired, position the indoor coil on the supply air side of the unit. Insure that no air can bypass this coil.
5.Secure the four angle brackets (shipped with (-)801P units) to the return air opening. See Figure 9. Connect the return air ducting to the return air opening at the top of the unit. Make the connection air tight to prevent en­training combustion gases from an adjacent fuel-burning appliance.
NOTE: Do not block furnace access with support rods. Maintain clearances recommended in Figure 8. Allow enough space for proper service maintenance or re­placement of the heat exchanger and blower assembly.
DUCTING
FOUR ANGLE BRACKETS, SHIPPED WITH (-)801P UNITS, CAN BE INSTALLED HORIZONTALLY. THESE BRACKETS MAY BE USED TO SECURE THE RETURN AIR DUCT TO A HORIZONTAL UNIT.
RETURN
AIRFLOW
REAR VIEW
FIGURE 9
HORIZONTAL RETURN AIR DUCT (LEFT-HAND AIRFLOW POSITION SHOWN)
NOTE:
HORIZONTAL LEFT ORIENTATION DEPICTED IN ILLUSTRATION. HORIZONTAL RIGHT ORIENTATION IS SIMILAR IN INSTALLATION.
AIR FLOW
NOTE: DO NOT BLOCK FURNACE ACCESS WITH SUPPORT RODS, ALLOW SPACE FOR PROPER SERVICE MAINTIENCE OR REPLACEMENT OF THE HEAT EXCHANGER AND BLOWER ASSEMBLY .
FIGURE 8
HORIZONTAL FURNACE INSTALLED W/SUPPORT BRACKETS
ST-A1220-03
Ducting
14
Combustion Air
COMBUSTION AND VENTILATION AIR
1. IMPORTANT:
Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to corro­sive elements in the atmosphere is excluded from warranty coverage.
2. Combustion air must be free of acid forming chemicals; such as sulphur, fluorine and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint and varnish removers, refrigerants and many other commercial and household products. Vapors from these products when burned in a gas flame form acid compounds. The acid compounds increase the dew point temperature of the flue products and are highly corrosive after they condense.
3. The following types of installation may require OUTDOOR AIR for combustion, due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical storage areas.
4. If combustion air is exposed to the following substances (but not limited to the following), it should not be used and the fur­nace may require outdoor air for combustion.
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine-based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry curing and acid washing materials
Combustion air requirements are determined by whether the fur­nace is in an open (unconfined) area or in a confined space such as a closet or small room.
When the furnace is installed in the same space with other gas ap­pliances, such as a water heater, be sure there is an adequate supply of combustion and ventilation air for the furnace and the other appliances. Do not delete or reduce the combustion air sup­ply required by the other gas appliances in this space. See Z223.1, National Fuel Gas Code (NFPA 54). An unconfined space must have at least 50 cubic feet (volume) for each 1,000 BTUH of the total input of all appliances in the space. If the open space contain­ing the appliances is in a building with tight construction (contem­porary construction), outside air may still be required for the appliances to burn and vent properly. Outside air openings should be sized the same as for a confined space.
IMPORTANT: ONLY THE CURRENT VENT INSTRUCTIONS
APPLY. All gas furnaces cannot be common-vented.
OVERTEMPERATURE SAFETY SWITCHES
Furnaces are equipped with safety switches in the burner com­partment to protect against over-temperature conditions caused by inadequate combustion air supply. The switches are located in the burner compartment. If a switch is tripped it must be manu­ally reset after clearing the fault condition which caused it to open.
IMPORTANT:
This is not a direct vent furnace. Review venting
instructions before installing.
!
WARNING
THIS FURNACE AND ANY OTHER FUEL-BURNING APPLI­ANCE MUST BE PROVIDED WITH ENOUGH FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF THE FLUE GASES. MOST HOMES WILL REQUIRE THAT OUT­SIDE AIR BE SUPPLIED INTO THE FURNACE AREA. FAIL­URE TO DO SO CAN CAUSE DEATH FROM CARBON MONOXIDE POISONING.
!
WARNING
ADEQUATE FACILITIES FOR PROVIDING AIR FOR COM­BUSTION AND VENTILATION MUST BE PROVIDED IN AC­CORDANCE WITH SECTION 5.3, AIR FOR COMBUSTION AND VENTILATION, OF THE NATIONAL FUEL GAS CODE, ANSI, Z223.1 LATEST EDITION OR APPLICABLE PROVI­SIONS FOR THE LOCAL BUILDING CODES, AND NOT OBSTRUCTED SO AS TO PREVENT THE FLOW OF AIR TO THE FURNACE.
COMBUSTION AIR REQUIREMENTS
!
WARNING
ALL FURNACE INSTALLATIONS MUST COMPLY WITH THE NATIONAL FUEL GAS CODE AND LOCAL CODES TO PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE. FAILURE TO DO SO CAN CRE­ATE HAZARDOUS CONDITIONS RESULTING IN PROP­ERTY DAMAGE, BODILY INJURY OR DEATH FROM SMOKE, FIRE OR CARBON MONOXIDE.
!
WARNING
DO NOT BYPASS, JUMPER, OR REMOVE ANY SAFETY SWITCH FROM THE FURNACE CONTROL CIRCUIT. IF A SAFETY SWITCH CAUSES THE FURNACE TO SHUT DOWN OR OPERATE INTERMITTENTLY, IT IS AN INDICA­TION OF A POTENTIAL SAFETY HAZARD THAT MUST BE ADDRESSED BY A QUALIFIED TECHNICIAN, SERVICE AGENCY OR THE GAS SUPPLIER. DO NOT RESET SAFETY CONTROLS WITHOUT CORRECTIVE ACTION AND/OR VERIFICATION OF PROPER SAFE OPERATION BY A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
REPLACE ANY SAFETY CONTROL COMPONENT WITH IDENTICAL OEM REPLACEMENT PARTS ONLY.
15
COMBUSTION AND VENTILATION AIR (cont.)
For improved indoor air quality, added safety and product per­formance we recommend direct vent type installations. If non-di­rect type vent system is used, the requirements for combustion air must be provided as identified in the National Fuel Gas Code.
Combustion air requirements are determined by whether the fur­nace is in an open (unconfined) area or in a confined space such as a closet or small room.
FURNACE LOCATED IN AN UNCON­FINED SPACE
USING INDOOR AIR FOR COMBUSTION:
An unconfined space must have at least 50 cubic feet for each 1,000 BTUH of total input for all appliances in the space. Table 1 below specifies minimum space requirements and a few exam­ples of the room sizes required for different inputs. The sizes are based on 8-foot ceilings.
If the open space containing the furnace is in a building with tight construction, outside air may still be required for the furnace to operate and vent properly. Outside air openings should be sized the same as for a confined space.
FURNACE LOCATED IN A CONFINED SPACE
A confined space is defined as any space for a given furnace input rating which is smaller than that which is specified in Table 1 as minimum for an “unconfined” space. If the space is less than that specified in this table, the space is defined as
“confined”.
If the space is small enough to be designated as “confined”, it must have openings into the space which are located in accor­dance with the requirements set forth in the following subsections A and B. Size connected to the heated area or to the outside, and by the input of ALL appliances in the space.
If the confined space is within a building with tight construction, combustion air must be taken from outdoors or from an area freely communicating with the outdoors.
A. USING INDOOR AIR FOR COMBUSTION:
IMPORTANT: Air should not be taken from a heated space
with a fireplace, exhaust fan or other device that may pro­duce negative pressure.
If combustion air is taken from the heated area, the openings must each have at least 100 square inches of free area. Each opening must have at least one square inch of free area for each 1,000 BTUH of total input in the space. Table 2 shows some typical examples of openings required for com­bustion air openings required for a confined space.
B. USING OUTDOOR AIR FOR COMBUSTION:
IMPORTANT: Do not take air from an attic space that is
equipped with power ventilation. The confined space must communicate with the outdoors in
accordance with Methods 1 or 2 below. The minimum dimen­sion of air openings shall not be less than 3 inches. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
METHOD 1:
Two permanent openings, one located within 12 inches of the top and one located within 12 inches of the bottom of the en­closure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Combustion Air
COMBUSTION AIR REQUIREMENTS: CONFINED AND UNCONFINED SPACES
!
WARNING
ALL FURNACE INSTALLATIONS MUST COMPLY WITH THE NATIONAL FUEL GAS CODE, NFPA 54 AND LOCAL CODES TO PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE. FAILURE TO DO SO CAN RESULT IN EXPLOSION, FIRE, PROPERTY DAM­AGE, CARBON MONOXIDE POISONING, PERSONAL IN­JURY OR DEATH.
!
WARNING
READ AND FOLLOW THE GENERAL VENTING REQUIRE­MENTS AND GUIDELINES OF THIS MANUAL FOR ADDI-
TIONAL VENTING REQUIREMENTS PERTAINING TO ALL FURNACE INSTALLATIONS (INCLUDING DIRECT AND NON-DIRECT VENTING). FAILURE TO FOLLOW ALL IN­STRUCTIONS IN THIS MANUAL CAN RESULT IN EQUIP­MENT FAILURE, EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
150,000 7,500 940 32 x 30
TABLE 1: MINIMUM SPACE REQUIREMENTS FOR UNCONFINED SPACE, NON-DIRECT VENT
150,000 150
TABLE 2: MINIMUM FREE AREA OPENING REQUIRED FOR A FURNACE LOCATED IN A CONFINED SPACE USING INDOOR AIR FOR COMBUSTION.
TABLE 7: MINIMUM SPACE REQUIREMENTS FOR UNCONFINED SPACE, NON-DIRECT VENT*
Input
(BTUH)
50,000 2,500 313 16 x 20
75,000 3,750 470 24 x 20
100,000 5,000 625 32 x 20
125,000 6,300 790 36 x 30
Minimum
Space
(Cubic Ft)
Minimum Area
with 8
Ceilings (sq )
Typical Room
Size w/ 8'
Ceilings ( x )
TABLE 8: MINIMUM FREE AREA OPENING REQUIRED FOR A FURNACE LOCATED IN A CONFINED SPACE USING INDOOR AIR FOR COMBUSTION.
Input (BTUH)
50,000 100
75,000 100
100,000 100
125,000 130
Free Area for Each
Opening (sq inches)
A. Where directly communicating with the outdoors through an
opening or where communicating to the outdoors through vertical ducts as shown in Figure 11, each opening shall have a minimum free area of 1 square inch for each 4,000 BTUH of total appliance input rating of all equipment in the enclosure. Table 3 specifies the minimum area for each of the 2 combustion air openings and minimum round duct diameter for direct openings and vertical ducting only.
B. Where communicating with the outdoors through horizon­tal ducts, each opening shall have a minimum free area of 1 square inch for each 2,000 BTUH of total appliance input rat­ing of all equipment in the enclosure (see Figure 12). Table 4
specifies the minimum area for each of the 2 combustion air openings and minimum round duct diameter for horizontal ducting only.
METHOD 2:
One permanent opening located within 12 inches of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 inch from the sides and back and 6 inches from the front of the appliance. The opening shall di­rectly communicate with the outdoors or communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors, and shall have a minimum of:
150,000 38 8
TABLE 3: MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE THROUGH AN OPENING OR
3. THROUGH A VERTICAL DUCT.
16
Combustion Air
COMBUSTION AND VENTILATION AIR (cont.)
150,000 75 10
TABLE 4: MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE THROUGH A HORIZONTAL DUCT.
150,000 75 10
TABLE 5: MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE THROUGH A HORIZONTAL DUCT.
COMBUSTION AIR REQUIREMENTS: CONFINED AND UNCONFINED SPACES
GAS
WATER
HEATER
FURNACE
12”
MAX
12”
MAX
NOTE: EACH OPENING SHALL HAVE A FREE AREA OF NOT LESS THAN ONE SQUARE INCH PER 1,000 BTU PER HOUR OF THE TOTAL INPUT RATING OF ALL EQUIPMENT IN THE ENCLOSURE, BUT NOT LESS THAN 100 SQUARE INCHES.
ST-A1227-01
FIGURE 10
NON-DIRECT VENT AIR FROM HEATED SPACE
VENT PENETRATIONS
FOR NON DIRECT VENT FURNACES
AIR FROM HEATED SPACE
TABLE 9 : MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE OUTSIDE THROUGH AN OPENING OR T H R O U G H A V E R T I C A L V E N T D U C T . *
Total Input for
ALL Gas
Appliances
(BTUH)
50,000 13 5
75,000 19 5
100,000 25 6
125,000 32 8
TABLE 1 0: MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE OUTSIDE THROUGH A H ORIZONTAL DUCT.
Total Input for
ALL Gas
Appliances
(BTUH)
50,000 25 6
75,000 38 8
100,000 50 8
125,000 63 10
Free Area for
Each Opening
w h e n 2 S e p a r a t e
Openings are
used (sq inches)
Free Area for
Each Opening
when 2 Separate
Openings are
used (sq inches)
R o u n d P i p e D u c t
Diameter ( Vercal
Duct Only) (inches)
Round Pipe Duct
Diameter
(Horizontal Duct
Only) (inches)
TABLE 1 1: MINIMUM FREE AREA REQUIRED FOR AN OPENING (WHEN O N E OPENING IS USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE OUTSIDE.
Total Input for
ALL Gas
Appliances
(BTUH)
50,000 25 6
75,000 38 8
100,000 50 8
125,000 63 10
*
Free Area for an Opening when 1 Opening is used
(sq inches)
Round Pipe Duct
Diameter (inches)