REMKO VRS, VRS 40, VRS 210, VRS 250, VRS 60 Operation,technology,spare Parts

...
Page 1
REMKO VRS Universal oil/gas automatic heaters
Operation Technology Spare Parts
Edition GB – M10
REMKO – powerful like a bear.
Page 2
Page 3
Operating Instructions
Read these instructions carefully before setting up/operating the unit!
Our guarantee becomes null and void if the unit is used, set up
or maintained improperly,
or if modifications are made to the supplied unit without our prior consent.
Subject to alterations!
Stationary Warm Air Heating Systems
REMKO VRS
Contents Page
Safety Instructions 4 Description of the Unit 4 Prior to Assembly 5 Setup and Assembly 7 Prior to Initial Operation of the 400 V Series 10 Before Starting 10 Starting 11 Unit Shut Down 11 Maintenance and Service 11 Troubleshooting 13 Service and Guarantee 13 Technical Data VRS INOX 14 Technical Data VRS B 15 Technical Data VRS B 16
Contents Page
Wiring Diagram VRS 20 INOX 17 Wiring Diagram 230 V 18 Wiring Diagram 400 V Direct Start 19 Wiring Diagram 400 V / Y Start 20 Wiring Diagram Fan Motor 21 Exploded View VRS 20 INOX 22 Spare Part List VRS 20 INOX 23 Exploded View VRS INOX 24 Spare Part List VRS INOX 25 Exploded View VRS B 26 Spare Part List VRS B 27 Unit Dimensions VRS INOX 28 Unit Dimensions VRS B 28
Always keep these operating instructions near or on the unit!
G
G
Page 4
Safety Instructions
Make sure to observe relevant local building and fire protection codes and abide by professional association regulations when the units are in operation!
Before performing any maintenance or repair work,
make sure to unplug the units from the power supply.
Remove fuses or switch off the customer-supplied main switch.
It is not sufficient to switch off the units with the operating switch!
G
The units may only be operated by persons who
have received proper training in their operation.
Description of the Unit
The units (automatic heaters) have been designed for universal, fully-automatic and smooth operation. They are fired directly with heating oil, diesel or natural/liquid gas. The VRS 20 INOX has only been designed for op­eration with heating oil or diesel.
Function and Design The units have been designed for operation with a
separate forced-air burner in single-stage operation. 2­stage burners may only be operated to prevent conden­sation from accumulating during startup in partial load range.
The units must be installed and operated in such a
way that people are not exposed to radiant heat and fires cannot occur.
The units may only be installed and operated in
closed rooms where the units have adequate air supply for combustion.
If this cannot be guaranteed, a separate burner­driven device that sucks in fresh air from the outside must be installed.
The units may only be set up on a non-flammable
surface.
The units may only be attached to non-flammable,
sturdy structures or ceilings made from the materials with sufficient load-bearing capacity.
The units are to be attached with sturdy mounts which are fixed on the unit.
The units may not be set up or operated in surround-
ings susceptible to fire or explosions.
The units must be set up outside of traffic zones,
e.g. away from cranes.
A safety zone of 1 m is to be maintained around the units.
The protective air suction grille must always be kept
free of dirt and loose objects.
Never insert foreign objects into the units.Do not expose the units to a direct stream of water.Never let water get inside the units. All of the units’ electrical cords are to be protected
from damage (e.g. caused by animals, etc.).
It is essential to connect the units to an exhaust system approved by the state building authorities.
The units are equipped with single setting, quiet axial ventilators with drive motors requiring little maintenance and with integrated switches and control devices de­pending on the type of unit.
The units meet the basic safety and health require­ments found in the relevant EU regulations. They are safe and easy to operate.
The robust design and clean processing of these high­quality units ensure a long service life and smooth op­eration. They can also be assembled quickly, easily and affordably and are easy to service.
Operating Locations of the Units
The units are direct-fired devices that supply instantane­ous heat. They are only used for industrial and commer­cial purposes. There are generally no restrictions as to where they can be used.
REMKO automatic heaters supply heat or regulate the temperature of:
Workshops
Warehouses
Exhibition spaces
Trade show spaces
Temporary structures for warehousing
Showrooms
Greenhouses etc.
These units have not been designed for heating private residences or similar spaces.
G
Do not bypass or block safety mechanisms while the unit is in operation.
G
Proper Use
The units have been designed and equipped exclusively for industrial and commercial heating and ventilation purposes.
The manufacturer assumes no liability for damage re­sulting from non-compliance with manufacturer specifi­cations and legal requirements, or if modifications are made to the units.
Page 5
Operation
After switching on the unit by setting the operating switch to “Heizen” (heating), the forced-air burner turns on automatically. The combustion chamber with heat­exchanger now heats up until the target temperature is reached.
After the set target temperature is reached, the air sup­ply fan switches on automatically. Warm air is blown out.
If heating mode is controlled via a room thermostat or other temperature regulating device (operating switch set to “Heizen” (heating), the units function fully­automatically based on amount of heat required.
All of the unit functions are performed automatically and monitored by the automatic burner relay (part of the forced-air burner) and the integrated temperature con­trol thermostat.
After the device is switched off with the operating switch or the room thermostat, the air supply fan runs for a cer­tain amount of time to cool the combustion chamber with heat-exchanger and then switches off. This proc­ess can be repeated several times.
Never interrupt (except in emergency situations) the power supply until the cool-down phase is completely finished.
G
Our guarantee does not cover damages caused to the unit by overheating.
Safety Facility
If the flame burns irregularly or goes out, the unit is switched off by the automatic burner relay. The unit may only be restarted after the automatic burner has been manually released.
The temperature monitor (TW) regulates the tempera­ture of the unit as well as the outgoing air current via the burner in heating mode. The temperature control ther­mostat (TR) regulates the fan.
The safety temperature limiter (STB) interrupts opera­tion of the unit or burner when extreme overheating oc­curs or if the TW ceases functioning. The STB can only be manually released after the unit has cooled.
Before the STB is released (to restart operation), the reason the STB was activated must be deter-
G
mined.
For units in the 400 V series, the fan motor is also moni­tored by a thermal overcurrent relay. If the motor be­comes overloaded, operation is interrupted by the relay and the red malfunction lamp “Ventilator” (fan) on the control box lights up. Release is only possible after the control box has been opened.
It is not necessary to limit the capacity in single­stage burner operation for the warm air generator.
G
Prior to Assembly
When setting up the units, the relevant regional building and fire protection codes of the respective region must be observed.
Selecting the Setup Location
When selecting a location to set up the units, the re­quirements must be adjusted with respect to:
Fire protection and operating hazards. Function.
When the units are used to heat rooms, when it is necessary to adjust to the amount of pressure in the room, etc.
Operating needs.
Heating requirements, rated air output, need for cir­culation or outside air, humidity, room temperature, air distribution, space needs, etc.
How the unit is connected to the exhaust system. Access for monitoring, assembly, repair and mainte-
nance work.
Ratio of room volume to total rated air capacity espe-
cially for naturally ventilated rooms.
The unit must be set up and assembled in such a way that it is easily accessible for monitoring, re-
G
pair and maintenance work.
Units with a rated heat output of up to 50 kW may usu­ally be set up outside of heating rooms when the Ger­man ordinance on heating systems is observed. Units with a rated heat output of more than 50 kW must be set up in heating rooms.
As an exception to this, heating appliances for solid, liq­uid or gaseous fuels with a total rated heat output of more than 50 kW may also be set up in other rooms if their use requires this (e.g. single heating appliances such as fan heaters) and these heating appliances can be safely operated.
Here, the German state building authorities’ “Guidelines for setting up furnaces with a total rated heat output of more than 50 kW in rooms other than heating rooms” must be observed.
The guidelines prohibit erecting furnaces when poten­tially dangerous concentrations of hazardous sub­stances are present in accordance with the substance ordinance.
The dangerous concentration must be checked in the setup room and any accessible adjacent rooms to see whether the prohibition applies.
In rooms where highly flammable materials or mixtures are being processed, stored or produced in quantities that are hazardous should they ignite, exceptions may be made if appropriate measures are taken to ensure that the heating appliances cannot cause the materials or mixtures to catch fire.
Page 6
Important Information about Safe Setup
Air Supply for Combustion
The units may only be set up and operated in rooms
where there is enough air for combustion and the ex­pelled air is guided to the outside via an exhaust sys­tem.
Units dependent on air in the room may only be set
up in rooms or buildings from which air is suctioned out by means of fans (such as ventilation or exhaust systems) if:
1. Safety mechanisms prevent the units and the air suctioning system(s) from operating simultane­ously.
2. The expulsion of exhaust is monitored by special safety devices.
3. The exhaust produced by the units is expelled by means of the air suctioning system(s).
4. The design or dimensions of the system ensure that no dangerous negative pressure can be pro­duced.
The units must be placed firmly on a suitable, non-
flammable surface outside of traffic zones, for exam­ple, away from cranes.
The units must be set up and operated in such a way
that people are not exposed to exhaust or radiant heat and fires cannot occur.
The units must be set up in such a way that they do
not cause any hazards or unreasonable annoyances, e.g. tremors, vibrations or noise.
The units must be set up and installed in such a way
that they are easily accessible for monitoring, repair and maintenance work.
Operating elements which can result in dangerous
operating conditions when used improperly must be protected from unauthorised operation if they are generally accessible.
When attaching mixed air flaps (accessories), they
must be connected against the flow of air and ensure a minimum cross-section for an adequate external air rate.
The units may not be set up or operated in rooms or
areas susceptible to fire or explosions.
Power Supply Prior to performing the electrical installation in line with
local requirements, check whether it is possible for even a temporary power overload to cause an impermissible undervoltage.
To connect the units, the line cross-sections are to be placed in such a way that they do not caused the burner voltage to lower to an impermissible level when the fan is started.
An adequate supply of air for combustion must be en­sured by meeting the relevant building requirements.
Excerpts from the German fire ordinance: (1) For furnaces with a total rated heat output of up to
35 kW that are dependent on the air in the room, evidence of an adequate air supply for combustion has been provided if the furnaces are set up in a room that has:
1. A minimum of one door to the outside or a win­dow that can be opened (rooms with a connec­tion to the outside) and a room capacity of at least 4 m3 per kW of total rated hear output or
2. An opening leading to the outside with a cross­section of at least 150 cm2 or two openings which are each 75 cm2 or lines to the outside with equivalent cross-sections for air flow.
(2) For furnaces with a total rated heat output of more
than 35 kW and less than 50 kW that are depend­ent on the air in the room, evidence of an adequate air supply for combustion has been provided if the furnaces are set up in rooms that meet the require­ments of Para. 1, No. 2.
(3) For furnaces with a total rated heat output of more
than 50 kW that are dependent on the air in the room, evidence of an adequate air supply for com­bustion has been provided if the furnaces are set up in rooms that have an opening or a line leading to the outside.
The cross-section of the opening must be at least 150 cm² plus and additional 2 cm² for each kW of rated heat output which is above 50 kW.
The lines’ cross-sections must have equivalent measurements for air flow.
The required cross-section may not divided among any more than 2 openings or lines.
(4) Combustion air openings and lines may not be
closed or blocked unless the safety mechanisms can ensure that the furnace can only be operated when the flap is closed.
The required cross-section may not be constricted by the flap or the grille.
(5) As an exception to Paras. 1 to 3, for furnaces de-
pendent on air in the room, evidence of an ade­quate air supply for combustion can be provided other ways.
For example by: A continuous line to the outside with a sufficient
cross-section that is attached to the burner or its lin­ing. This must be adjusted to the suction capacity of the burner and the line resistances (including the protective air suction grille) so that combustion is assured.
Page 7
Fuel Supply
Wall Assembly
Particularly for heating oil lines, make sure that the cross-section of the lines corresponds to the suction height, the total line resistance and increased viscosity at lower temperatures and, if necessary, it is possible to connect an oil transport device.
The lines must be placed in such a way that they are easily ventilated and are protected from corrosion and mechanical damage.
The measured pressure of the suction line should not exceed -0.3 bar. It may be a maximum of -0.4 bar.
G
Heating Rooms
The units only may be operated in closed rooms or warehouses if they have been equipped with a suitable room temperature control thermostat (room thermostat).
The wall where the unit is to be assembled may not be made of flammable materials. Its load-bearing capacity must be tested and, if necessary, reinforced.
Consoles must be anchored firmly to the wall and the units attached here. There must be adequate room to perform maintenance work on the heat-exchanger, burner, fan and exhaust system.
Assembling Suspended Units The units may only be attached to sturdy structures or
ceilings that are made of non-flammable materials and have adequate load-bearing capacity.
Sturdy mounts fixed on the unit are used to attach it. In addition, the requirements listed in the section “Wall As­sembly” must be observed.
Unit Setup
When setting up the units, the regional provisions and regulations must be observed.
The units may only be operated with accessories that have either been approved by the manufacturer or sup­plied with the units.
Proceed as follows to set up the units:
Setup and Assembly
Setup on the Ground The units must be placed firmly on non-flammable sur-
face outside of traffic zones, e.g. away from cranes. A safety zone of 1 m must be maintained around the
units to protect them from damage in commercial rooms, to ensure unhindered access for maintenance and repair work on the unit and burner and, if neces­sary, to prevent air intakes and outlets from blockage.
This safety zone is to be identified with a warning sign that says:
Maintain a Safety Zone of 1 m
We recommend clearly marking heavily trafficked ar­eas.
Outside Setup Units that are set up outside must be adequately pro-
tected from weather conditions so that they do not have any harmful effects or cause any unreasonable annoy­ances during operation.
The units may only be equipped with armatures and control devices that are suitable for outside use. If not, the control devices and switches must be protected ac­cordingly.
1. Remove the transport pallets or crates, protective
plastic or other packaging material before set up/ assembly.
2. Check the units for any damage.
3. Place the units firmly on a suitable surface.
4. If necessary, secure the units with suitable material.
5. Make sure an adequate distance is maintained to
flammable materials.
6. Make sure that air is supplied only via the air intake
openings intended for this purpose.
7. Make sure that there is a sufficient supply of air for
combustion.
8. If there are unfavourable pressure conditions in the
setup room or strong air impurities, install a burner­driven device that sucks in fresh air from the outside.
9. Make sure that air can flow freely into and out of the
units.
Heating Oil Connection
Make sure that there is an adequate supply of fuel. The suction line must be equipped with a valve at the
end of the hose in the tank.
Even when outside temperatures are low, a sufficient
amount of heating oil must be able to flow freely. Paraffin can accumulate at temperatures starting at approximately 5 °C depending on the quality of the heating oil.
Appropriate measures must be taken to prevent this from happening.
Page 8
L1L2L3L1L2L3L1L2L
3
Gas Connection
Depending on the capacity of the unit, the required quantity of gas must always be available and the neces­sary gas pressure present during unit operation.
Gas pressure regulators and shut-off valves are to be supplied by the manufacturer.
The line cross-section must correspond to the connec­tion values of the units, the total line resistance and the gas pressure.
Prior to initial operation, the gas supply line must be thoroughly cleaned and tested for impermeability!
G
Burner Installation
The forced-air burner supplied by the manufacturer is attached to the front of the unit with a clamp flange.
You must observe the following: Only forced-air burners with automatic burners that
have a 5 sec. safety period may be used.
It is not necessary to limit the capacity in single-
stage burner operation for the warm air generator.
The burner must be adjusted to the full heat load of
the unit.
The thermostat sensor may not be exposed directly to a particularly cold or warm air current.
The process is the same for installation of an automatic day/night temperature regulator (accessory).
Important Instructions for Unit Assembly
Make sure to observe the following general instructions as well.
Operating devices for the units and the fuel supply
must be able to be operated directly from the ground.
The operator must provide any support material nec-
essary for monitoring, maintenance and repair work.
Fan Motor Connection
The units are completely wired at the factory. In the event of changes or if the fan is replaced, make
sure to connect the motor and condenser to one an­other properly and ensure that the rotational direction of the motor is correct.
The combustion chamber may not be operated be-
low capacity.
The exhaust temperature may not fall below 160 de-
grees Kelvin above the room temperature.
Condensation accumulation.
Follow the operating instructions of the burner sup-
plied by the manufacturer.
If burners from other manufacturers are used, they
must be checked for compatibility with the unit.
Electrical Installation
The electrical connection of the units may only be per­formed by authorised personnel in accordance with the relevant regulations (including any local ones).
An easily accessible emergency switch must be at­tached in the setup room.
The emergency switch must be protected from unau­thorised use.
Thermostat Connection
The room thermostat (accessory) or day/night regulator (accessory) is connected via special connections. Please follow the appropriate wiring diagram for con­nection.
w2 u2 v2
u1 v1 w1u1 v1 w1
w2 u2 v2w2 u2 v2
u1 v1 w1
Motor 230 / 400 V
Power 3x 400 V Power 3x 400 V Power 3x 230 V
Y circuit
Y / circuit circuit
At the factory, the motors are initiated directly in Y up to
3.0 kW and by means of a Y / circuit for 4.0 kW and higher.
The room thermostat (accessory) must be placed in the most ideal location in the room for regulating tempera­ture.
Page 9
Exhaust Connection
Examples of Use
The unit is to be connected to suitable exhaust systems whose design has been approved.
Installation of an exhaust system always requires a permit.
G
Exhaust systems are structural systems located either in or on buildings whose sole purpose is to expel ex­haust from heating appliances safely above the roof.
When planning for the exhaust system, please observe the following:
The exhaust system must be installed and assem-
bled properly and in accordance with the relevant regulations.
The dimensions of the exhaust lines must be ad-
justed to the capacity of the unit and the construction height.
The dimensions of the exhaust systems must ensure
that the exhaust is expelled to the outside regardless of the operating conditions and guarantee that no positive pressure is produced in the rooms. These dimensions are based on the cross-section and height, and to the extent required, the heat penetra­bility resistance and internal surface.
Double-sided exhaust system / stainless-steel / outside assembly.
Upright unit assembly
AS-ME-D
AS-1000-D
AS-ÜGI-D AS-1000-E
AS-T90°-D
AS-RT-D AS-GI-D
AS-WK-D
The exhaust system openings must stick out at least
40 cm beyond the top of the roof or be at least 1 m away from the surface of the roof.
If impact pressures, e.g. from fall winds or neigh-
bouring buildings, are anticipated, the top of the chimney should be shaped accordingly.
The exhaust system must be attached securely and
properly according to the manufacturer’s specifica­tions.
In roof structures, the exhaust system must be led
through a pipe casing or a chute to allow the exhaust line to expand when heated.
The unit connection must be impermeable and se-
cured with rivets or screws from becoming acciden­tally loose.
It is preferable to have a horizontal exhaust line that
is as short as possible.
Incline 2 % = 2 cm/m.
You should plan to have a closable opening for per-
forming measurements at a distance of 2 x ex­haust pipe behind the unit connection.
Under certain circumstances, it is possible to meas­ure the exhaust opening.
Assembly of the unit on its side
AS-ME-D
AS-1000-D
AS-RB90-E AS-ÜGI-D
AS-500-E
AS-T90-D
AS-RT-D AS-GI-D
AS-WK-D
Wall
console
Make sure to maintain a safe distance to flamma­ble materials!
G
The double-walled, REMKO stainless steel exhaust sys­tems have been approved by the Institut für Bautechnik (German Institute for Construction Engineering) in ac­cordance with DIN 18160 Part 1.
Page 10
Prior to Initial Operation of the 400 V Series
Fan Motor Operation
Check the drive.
1. Check the rotational direction of the fan.
2. Check the initial tension of the drive belt.
3. Check that the tightening screws of the complete drive are secure.
Measuring the rated current and/or current consump­tion.
1. To prevent inaccurate measurements, open the grille in the air duct or the blow-out cover.
2. Attach all air suction grilles to the unit.
3. Check the available power supply.
4. Measure the current. Rated current for direct start.
The measured rated current may not exceed the value on the type plate of the motor. The thermal overcurrent relay must be adjusted to the rated current of the drive motor.
Rated current for Y / start.
The measured rated current may not exceed the value on the type plate of the motor. Multiply the rated current of the drive motor by a factor of 0.58 and adjust the thermal overcurrent relay to the calculated value.
Each phase should be measured separately to pre­vent inaccurate measurements.
G
Thermal Overcurrent Relay To check the function of the overcurrent relay or its set
value, remove a fuse. If the unit is functioning and set properly, the relay should activate after approximately 30 seconds.
Important Information about the Thermal Overcurrent Relay
The thermal overcurrent relay may only be operated when the relay is set to manual (H). The relay may not automatically switch on again after it has cooled. When the relay is set to automatic (A), the possibility that dam­age will occur cannot be ruled out. There is no guaran-
tee claim!
Before Starting
Initial operation of the unit and its forced-air burner must be performed by the manufacturer or one of its author­ised service representatives.
During this process, all regulating, control and safety mechanisms must be checked to ensure that they are functioning properly and set correctly.
Make sure that the fan’s screws and bolts and
burner attachments are secure.
Check the tension of the drive belts.
If applicable.
Open the blow-out grille if necessary and adjust it as
required.
Check the settings of the temperature monitor and
the temperature control thermostat.
Burner approx. 80 °C; fan approx. 40 °C. Factory setting at the VRS 20 INOX unit.
Switch the customer-supplied main switch or fuse
on.
Set the room thermostat to a higher value than the
current room temperature.
Open the fuel supply and set the operating switch to
“Heizen” (heating).
If the oil burner was supplied by the manufacturer, the burner start is delayed as a result of the standard oil preheating process (up to VRS 60).
Adjust the throughput for the heating oil or gas to
meet the heating capacity of the unit.
See the unit’s type plate.
Set the burner to the optimum values in accordance
with the manufacturer’s specifications.
Measure the chimney draught when cold and hot. The exhaust temperature difference (∆t) may not fall
below 200 Kelvin or below 160 Kelvin for the Inox series.
This prevents the temperature from falling below the dew point which causes corrosion in the heat­exchanger.
Keep a protocol of measurements and submit it to
the operator for safekeeping. Familiarise the opera­tor with the system.
Give the statement confirming the authorised com-
pany status and the company certificate of the re­spective installation company to the relevant authori­ties.
Current Consumption too High
If the motor is consuming too much current despite a proper electrical connection and adequate power sup­ply, the thermal overcurrent relay may not be set higher or bypassed under any circumstances.
To correct the problem, the air intakes and outlets (possible air compression) must be checked and appro­priate action taken.
10
Information on Gas-Fired Units.
For initial operation of gas-fired units, installation may only be performed by a contracted installation company (except in gas supply companies) or, for liquid gas, by a liquid gas supply company.
Page 11
Starting
Heating Mode
1. Turn the customer-supplied main switch or the fuse on.
2. Open the fuel supply.
3. Set the operating switch to “Heizen” (heating) or “I”.
4. Adjust the room thermostat to the room temperature you want.
When heat is necessary, the forced-air burner switches on automatically. The air supply fan only switches on once the target temperature has been reached. This prevents cold air from being blown out. The unit now functions fully-automatically to maintain the set room temperature.
Ventilation
Maintenance and Service
The operator must have the unit checked and serviced as necessary, at least once a year, by a representative of the manufacturing company or another authorised in­dividual in accordance with the operating conditions. The units must be checked for operational readiness, functional safety, efficiency and compliance with emis­sion limits.
The operator must be informed if defects are found. He must then have the unit serviced immediately or its components replaced.
The following applies:
Maintenance work on limiting devices, self­adjusting devices and flame monitoring devices as well as on other safety mechanisms may only be performed by the respective manufacturer or his representatives.
On the other hand, the individual contracted to service the unit may only replace components or assemblies with those provided by the manufac­turer or his representatives.
Adjustments or maintenance work on the unit or forced-air burner may only be performed by
G
authorised personnel!
1. Set the operating switch to “Lüften” (fan) or “II”.
2. Keep in mind that the unit’s fan runs continuously.
It is not possible to control it with a thermostat
Unit Shut Down
1. Set the operating switch to “0”.
2. Keep in mind that the air sup­ply fan continues running to cool down the heat-exchanger and can run several times before the unit is finally switched off.
Never interrupt (except in emergency situations) the power supply until the cool-down phase is completely finished.
G
Our guarantee does not cover damages caused to the unit by overheating.
3. If the unit is taken out of op­eration for a longer period of time, the customer-supplied main switch or the fuse should be switched off and the fuel supply closed off.
Regular Cleaning and Maintenance Dust and dirt must be cleaned from the unit including
from the heat-exchanger, combustion chamber and forced-air burner. Combustion residue in the combus­tion chamber and in the heat-exchanger must be re­moved.
Prior to doing any maintenance or repair work on the unit, unplug it from the power supply. It is not adequate to switch off the unit with the operating
G
switch!
The V-belt tension and the motor mount must be checked on a regular basis.
Parts that wear out, e.g. flue gas brakes, seals, oil filter inserts, oil nozzles, etc. must be checked, cleaned and replaced if necessary.
Important Information on Servicing the Unit
If the cleaning and burner adjustment intervals are
not observed, the guarantee becomes null and void.
It is therefore absolutely necessary to keep records
that work has been performed by authorised person­nel in addition to creating standard protocols.
We recommend entering into a maintenance con-
tract for the regularly scheduled maintenance and service work.
After maintenance work is complete, conduct an electrical safety test.
G
11
Page 12
Cleaning the Combustion Chamber and the Heat­Exchanger of VRS 20 INOX Type Units:
Cleaning the Combustion Chamber and the Heat­Exchanger of VRS B and VRS INOX Type Units:
Option 1: (in the unit or at the unit location).
1. Unplug the unit from the power supply.
2. Separate the exhaust connections from the unit and disassemble the lining plate on the back.
3. Disassemble the inspection cover 2.
4. Remove the flue gas brakes 3 from the flue gas chambers 4 and clean the flue gas brakes. Replace them if necessary.
5. Clean the dirt from all flue gas chambers 4 with a cleaning brush.
6. Disassemble the burner with burner flange.
7. Remove the combustion residue through the burner opening 7 by means of a cleaning brush and an in­dustrial vacuum cleaner.
A special boiler cleaning set for the REMKO industrial vacuum cleaner can be purchased as an accessory.
8. Proceed as described for Option 2 starting from step 5.
1 2 3 4
1. Unplug the unit from the power supply
2. Disassemble the following parts:
Lining plate(s) and burner (not shown)
Burner plate 6
Both front inspection covers 1
Lining plate, side (not shown)
Inspection cover, side 4
3. Remove the flue gas brakes 3 on both sides from the heat-exchanger lines and clean the flue gas brakes. Replace them if necessary.
4. Clean the combustion residue from the heat­exchanger lines with a suitable cleaning brush.
5. Remove the accumulated combustion residue with a vacuum cleaner from the front and back collection boxes.
A special boiler cleaning set for the REMKO indus­trial vacuum cleaner can be purchased as an acces­sory.
6. Reassemble all parts in the reverse order.
7. Make sure that all seals have been properly posi-
tioned.
Seals that have been damaged or malformed must be replaced.
5 6
Option 2: (outside the unit)
1. Perform the same work as described in Option 1, steps 1, 2 and 6.
2. Disassemble the front and side lining plates.
3. Disassemble the locking screw 5 and remove the en­tire combustion chamber from the front.
4. Perform the cleaning as described in steps 3 through 5 and step 7 in Option 1 in a suitable location.
5. Reassemble the unit and its parts in the reverse or­der.
Any parts that are damaged or malformed must be replaced.
6. Check the impermeability of the inspection cover 6 and the burner flange.
Replace them if necessary.
7. Service the burner in accordance with the separate operating instructions.
Check the burner and all regulating devices to en­sure that they are functioning properly and set
G
them to the optimum values.
6+7
3 2
8. Clean the combustion residue from the furnace through the burner opening.
Use a cleaning brush and an industrial vacuum cleaner.
9. Attach the burner with burner plate.
Replace seal 7 if necessary.
10. Service the burner in accordance with the separate operating instructions.
Check the burner and all regulating devices to en­sure that they are functioning properly and set
G
them to the optimum values.
shown. VRS 130
12
Page 13
Troubleshooting
The unit was subjected to repeating testing during pro­duction to ensure that it functions properly.
However, if you still experience functional problems, please refer to the list below.
For safety purposes, repair work on the electrical components and the burner may only be per-
G
formed by authorised personnel.
The unit does not start
1. Check the power supply
2. Check the fuses in the control box.
Only for units in the 400 V rotary current series.
3. Check the safety temperature limiter. If the safety temperature limiter (STB) has been acti-
vated, the reason the unit overheated must be deter­mined. The following are possible causes:
The unit could not cool down because the
power supply was interrupted. Even short inter­ruptions can activate the STB.
The temperature of the air being blown out is
too high because the grilles have not been prop­erly adjusted.
The fan was overloaded and the thermal over-
current relay of the 400 V series was activated or the thermal contacts in the fan motor of the 230 V series were activated.
The V-belt of the fan drive is loose or defective. Air intakes and outlets are blocked.
4. Check the operating and/or main switch.
5. Check the room thermostat setting.
The room thermostat must be set higher than the room temperature.
6. Set the operating switch to “Lüften” (fan) or “II”.
If the air supply fan starts now, look for the problem in the burner.
Check whether the burner malfunction control lamp
on the oil firing device is illuminated.
If so, release the relay by pressing the malfunction button. The malfunction light goes out and the burner tries to start. Keep in mind that some burners have a delayed start due to the oil preheating process for some units.
If, after the start phase, the burner switches off due to a malfunction, you may only re-release it after waiting 5 min. Additional releases are strictly pro-
G
hibited as there is a risk of explosion.
The air supply fan does not start
Set the operating switch to “Lüften” (fan) or “II”.
The air supply fan should now start.
Check that the fan and the fan drive are running
smoothly.
Check the V-belt on the fan drive. Check the electric cord on the fan motor for damage. Check whether the capacity of the fan was ex-
ceeded.
The thermal overcurrent relay (400 V series) or the thermal contacts (230 V series) in the fan motor have been activated.
Check the operating capacitor of the fan.
Only for the 230 V series.
Check that the temperature control thermostat (TR)
is working properly.
Please carry out an electrical safety test after hav­ing finished service on the unit.
G
Should the unit still not function properly after per­forming these checks, please contact an author-
G
ised service centre.
The burner does not start
Check whether the fuel filter is dirty. Check whether the shut-off valve of the fuel filter is
open.
Check that there is enough fuel in the fuel container. Check whether paraffin has accumulated in the heat-
ing oil. This can occur at temperatures below 5 °C.
Check oil lines for damage.
Leaks can cause air intake.
Use suitable means to ensure that the safety tem-
perature limiter (STB) and the temperature monitor (TW) are functioning properly.
Check the sensors and capillary pipes of the TW and
STB for damage and ensure that the sensor has been properly positioned.
Service and Guarantee
For the guarantee to be valid, the customer must com­pletely fill out the “guarantee certificate” enclosed with all heating units and send it back to REMKO GmbH & Co. KG in a timely manner after purchasing of the unit and putting it into operation.
The units have undergone several tests to ensure proper functioning at the factory. If there are still mal­functions that cannot be fixed by the operator using the troubleshooting instructions, please contact your dealer or contract partner.
An operation/use other than indicated in these in­structions is prohibited! In the case of non-compliance, we assume no li-
G
ability and our guarantee becomes null and void.
13
Page 14
Technical Data VRS INOX
REMKO VRS
Rated heat power kW 33 62 89 125 160 208 249
Rated heat output kW 29 57 83 116 149 193 232
Rated air output 1) m³/h 1.760 3.950 5.270 7.950 9.800 12.000 13.900
Rated pressure, external Pa 110 60 100 80 100 50 70
Fuel Heating oil EL or natural/liquid gas
Oil throughput (heating oil EL) kg/h 2,8 5,2 7,5 10,6 13,5 17,5 21,0
Gas throughput (natural gas H) m³/h 3,2 6,0 8,6 12,1 15,4 20,0 24,0
Gas throughput (natural gas L) m³/h 3,8 7,0 10,1 14,2 18,1 23,5 28,2
Gas throughput (liquid gas) m³/h 1,3 2,4 3,4 4,9 6,2 8,0 9,6
Exhaust mass current VAf 2) kg/h 50 95 138 190 245 320 385
Exhaust temperature approx. 3) °C 160–190 160–190 160–190 160–190 160–190 160–190 160–190
20
18
16,7
1.050
62
Heating oil EL
1,52
n/a
n/a
n/a
28,5
170–180
25 50 75 100 130 170 200
Required chimney draught Pa 0 0 0 0 0 0 0
Exhaust loss VA min./max. % 7 / 9 7 / 9 7 / 9 7 / 9 7 / 9 7 / 9 7 / 9
Furnace resistance Pa 6 8 18 20 25 31 38
Sound pressure level L
Electrical connection V 230/1~ 230/1~ 400/3N~ 400/3N~ 400/3N~ 400/3N~ 400/3N~
Frequency Hz 50 50 50 50 50 50 50
Rated current 5) A 2,2 2,6 2,8 3,7 3,7 3,7 5,2
Power consumption 5) kW 0,25 0,25 1,1 1,5 1,5 1,5 2,2
Power consumption 6) kW 0,46 0,46 1,55 1,95 1,95 1,84 2,54
Exhaust gas connection Ø mm 150 150 180 180 200 200 200
Weight 7) kg 150 240 310 360 550 730 820
4)
dB(A) 57 58 63 60 65 65 65
pA 1m
0
7 / 10
8
58
230/1~
50
1,1
0,17
0,28
150
90
Max. suction temperature 40 °C / max. outgoing temperature 100 °C
1) air current at t 40K / 1.2 kg/m³
2) approx. quantity for oil operation
3) measured temperature minus room temperature
4) noise measuring (without burner) DIN 45635-01-KL3
5) unit without burner
6) with manufacturer-supplied burner
7) for standard model, without burner and other accessories
Heating value Hi in its normal state
heating oil EL 11,86 kWh/kg natural gas H 10,38 kWh/m³ natural gas L 8,83 kWh/m³ liquid gas 25,89 kWh/m³ liquid gas 12,87 kWh/kg
14
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
Page 15
Technical Data VRS B
REMKO VRS
Rated heat power kW
Rated heat output kW
Rated air output 1) m³/h
Rated pressure, external 2) Pa
Fuel
Oil throughput (heating oil EL) kg/h
Gas throughput (natural gas H) m³/h
Gas throughput (natural gas L) m³/h
Gas throughput (liquid gas) m³/h
Exhaust mass current VAf 3) kg/h
Exhaust temperature approx. 4) °C
40 60 80 120 150 210 250 310 380 450
44 60 88 132 165 222 276 330 413 495
40 55 80 120 150 200 250 300 375 450
3.400 4.650 6.800 9.750 11.700 15.700 19.300 23.600 29.500 35.200
50 80 70 120 60 80 80 90 120 110
Heating oil EL or natural/liquid gas
3,7 5,1 7,4 11,1 13,9 18,7 23,3 27,8 34,8 41,6
4,2 5,8 8,5 12,7 15,9 21,4 26,6 31,8 39,8 47,7
5,0 6,8 9,9 14,9 18,7 25,1 31,2 37,4 46,8 56,0
1,7 2,3 3,4 5,1 6,4 8,6 10,6 12,7
68 93 134 200 250 332 415 500 622 748
195 200 195 195 200 205 205 200 200 200
Required chimney draught Pa
Exhaust loss VA max %
Furnace resistance Pa
Electrical connection 2) V
Frequency Hz
Rated current
Power consumption
Power consumption 6) W
Exhaust gas connection Ø mm
Weight 7) kg
2) 5)
A
2) 5)
kW
0 0 0 0 0 0 0 0 0 0
9 9 9 9 9 9 9 9 9 9
18 18 32 29 54 66 55 60 60 65
230/1~ 230/1~ 400/3N 400/3N 400/3N 400/3N 400/3N 400/3N 400/3N 400/3N
50 50 50 50 50 50 50 50 50 50
4,5 5,5 2,65 3,6 5,1 6,8 8,8 11,4 8,8/8,8 8,8/8,8
0,51 0,75 1,1 1,5 2,2 3,0 4,0 5,5 4,0/4,0 4,0/4,0
210 210 210 450 450 350 350 350 1900 1900
150 150 180 180 180 200 250 250 300 300
190 260 305 365 450 680 735 930 1055 1240
Max. suction temperature 40 °C / max. outgoing temperature 100 °C
1) air current at t 40 K / 1,2 kg/m³
2) for standard compression
3) approx. quantity for oil operation
4) measured temperature minus room temperature
5) unit without burner
6) for factory-installed burner
7) for standard model, without burner and other accessories
Heating value Hi in its normal state
heating oil EL 11,86 kWh/kg natural gas H 10,38 kWh/m³ natural gas L 8,83 kWh/m³ liquid gas 25,89 kWh/m³ liquid gas 12,87 kWh/kg
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
15
Page 16
Technical Data VRS B
REMKO
VRS
Typ
40
60
80
120
150
210
250
310
380
450
1) = Noise measuring (without burner) DIN 45635 -01 – KL3
Rated
pressure
∆p ext.
Pa V / Hz kW A
50 230 / 50 0,51 4,50 900 D 10/10 900 SPZ 1 —— —— 61 130 400Y / 50 0,55 1,42 1400 10/10 E 1050 SPZ 1 75 100 69 210 400Y / 50 0,75 1,86 1400 10/10 E 1190 SPZ 1 85 100 71 290 400Y / 50 1,10 2,65 1410 10/10 E 1326 SPZ 1 90 95 71 400 400Y / 50 1,10 2,65 1410 10/10 E 1494 SPZ 1 106 100 72
80 230 / 50 0,75 5,50 1380 10/10 E 1020 SPZ 1 75 106 65 190 400Y / 50 1,10 2,65 1410 10/10 E 1150 SPZ 1 85 106 67 290 400Y / 50 1,10 2,65 1410 10/10 E 1280 SPZ 1 100 112 68 350 400Y / 50 1,50 3,60 1410 10/10 E 1365 SPZ 1 106 112 69 480
70 400Y / 50 1,10 2,65 1410 10/8 Z 960 SPZ 1 85 125 63 190 400Y / 50 1,50 3,60 1410 10/8 Z 1135 SPZ 1 90 112 64 280 400Y / 50 1,50 3,60 1410 10/8 Z 1260 SPZ 1 100 112 65 430 500
120 400Y / 50 1,50 3,60 1410 10/10 Z 1150 SPZ 1 85 125 71 230 340 460
60 130 210 300 410
80 150 270 370 510
80 200 240 330 410
90 150 230 350 490
120 180 260 350 480
110 180 260 350 450
Electrical
connection
400 ∆ / 50
400 ∆ / 50 400 ∆ / 50
400 ∆ / 50 400 ∆ / 50 400 ∆ / 50
400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50
400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50
400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50
400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50
400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50
400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50 400 ∆ / 50
Electric motor(s) Ventilator(en) V-belt discs
Rated
power con-
sumption
2,20 5,10 1415 10/10 E 1530 SPZ 1 132 125 70
2,20 5,10 1415 10/8 Z 1445 SPZ 1 112 112 67 2,20 5,10 1415 10/8 Z 1530 SPZ 1 132 125 68
2,20 5,10 1415 10/10 Z 1290 SPZ 1 100 112 73 2,20 5,10 1415 10/10 Z 1445 SPZ 2 106 106 74 3,00 6,80 1430 10/10 Z 1634 SPZ 2 160 140 75
2,20 5,10 1415 12/12 Z 820 SPZ 2 80 140 68 2,20 5,10 1415 12/12 Z 920 SPZ 2 90 140 70 3,00 6,80 1430 12/12 Z 1030 SPZ 2 132 180 72 3,00 6,80 1430 12/12 Z 1145 SPZ 2 125 160 74 3,00 6,80 1430 12/12 Z 1275 SPZ 2 160 180 76
3,00 6,80 1430 15/11 Z 750 SPZ 2 118 224 69 4,00 8,80 1435 15/11 Z 835 SPZ 2 106 180 70 5,50 11,40 1450 15/11 Z 945 SPZ 2 132 200 72 5,50 11,40 1450 15/11 Z 1035 SPZ 2 160 224 73
2x 4,0 2x 8,8 1435 15/11 E 1160 SPZ 2 106 132 75
4,00 8,80 1435 15/15 Z 845 SPZ 2 106 180 72
5,50 11,40 1450 15/15 Z 955 SPZ 2 132 200 74 2x 3,0 2x 6,8 1430 15/15 E 1000 SPZ 2 140 200 76 2x 3,0 2x 6,8 1430 15/15 E 1085 SPZ 2 140 180 71 2x 4,0 2x 8,80 1435 15/15 E 1150 SPZ 2 106 132 80
5,50 11,40 1450 15/15 Z 855 SPZ 2 132 224 73
5,50 11,40 1450 15/15 Z 905 SPZ 2 140 224 75 2x 3,0 2x 6,8 1430 15/15 E 975 SPZ 2 125 180 76 2x 4,0 2x 8,8 1435 15/15 E 1085 SPZ 2 106 140 78 2x 5,5 2x 11,4 1450 15/15 E 1195 SPZ 2 132 160 81 2x 4,0 2x 8,8 1435 18/13 E 870 SPZ 2 112 180 79 2x 5,5 2x 11,4 1450 18/13 E 905 SPZ 2 140 224 80 2x 5,5 2x 11,4 1450 18/13 E 975 SPZ 2 132 200 81 2x 7,5 2x 15,4 1450 18/13 E 1015 SPZ 2 140 200 83 2x 7,5 2x 15,4 1450 18/13 E 1085 SPZ 2 150 200 84 2x 4,0 2x 8,8 1435 15/11 Z 895 SPZ 2 112 180 74 2x 4,0 2x 8,8 1435 15/11 Z 950 SPZ 2 106 160 75 2x 4,0 2x 8,8 1435 15/11 Z 1015 SPZ 2 106 150 77 2x 5,5 2x 11,4 1450 15/11 Z 1085 SPZ 2 150 200 78 2x 5,5 2x 11,4 1450 15/11 Z 1160 SPZ 2 160 200 79
Rated
current
Rated
engine
speed
min-1
Model
Rated
engine
speed
min-1
pressure
Model Motor Fan
ø mm ø mm dB(A)
Sound level
L
pA 1m
1)
16
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
Page 17
Wiring Diagram VRS 20 INOX
Fan motor: 230 V / 1~ Burner motor: 230 V / 1~
C Capacitor (fan) H1 Control lamp GREEN (operation) H2 Control lamp RED (burner malfunction) KL1 Terminal strip power input KL2 Terminal strip electrical wiring M Fan motor S Operating switch STB Safety temperature limiter TH External thermostat connection TR Temperature control thermostat TW Temperature monitor WS Wieland plug
(only for factory-installed burner)
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
An easily accessible emergency switch must be at­tached in the setup room, but not close to hazardous areas.
This switch must be protected from damage and un­authorised use!
The electrical connections should only be made by authorised personnel.
G
17
Page 18
Wiring Diagram 230 V
Fan motor: 230 V / 1~ Burner motor: 230 V / 1~
blue
black
black 1
black 2
black 4
black 3
C Capacitor KB REMKO Triple Combination Control KL Terminal strip in the control box M Fan motor RT Thermostat plug S Operating switch SK Control box STB Safety temperature limiter TR Temperature control thermostat TW Temperature monitor WS Wieland plug
(Only for factory-installed burner)
Wieland plug from
brown
blue
the control box
Wieland socket from the burner
An easily accessible emergency switch must be at­tached in the setup room, but not close to hazardous areas.
This switch must be protected from damage and un­authorised use!
The electrical connections should only be made by authorised personnel.
G
18
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
Page 19
Wiring Diagram 400 V Direct Start
Fan motor: 400 V / 3~ Burner motor: 230 V / 1~
Heat Fan
Burner plug
opt.
Running
red green green red
hour meter
Control voltage
Terminal strips in the control box
Night
Room thermostat
L1 for the burner relay
N for the burner relay
Thermostat strip
burner plug
numbered burner cable
Running hour meter
Malfunction lamp burner
F1 Control fuse F2 Fuse block (Fan) F3 Thermal overcurrent relay (fan motor) H1 Malfunction lamp (fan) H2 Operating lamp (fan) H3 Operating lamp (burner) H4 Malfunction lamp (burner) K1 Fan contactor KB REMKO triple combination control M Fan motor RT1 Room thermostat day (accessory) RT2 Room thermostat night (accessory) S1 Operating switch
Day
Supply line
Fan motor
STB Safety temperature limiter TR Temperature control thermostat TW Temperature monitor X1 Terminal strip 1 in the control box X2 Terminal strip 2 in the control box
An easily accessible emergency switch must be at­tached in the setup room, but not close to hazardous areas.
This switch must be protected from damage and un­authorised use!
The electrical connections should only be made by authorised personnel.
G
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
19
Page 20
Wiring Diagram 400 V / Y - Start
Fan motor: 400 V / 3~ Burner motor: 230 V / 1~
Heat
Fan
Off
opt.
Running
hour meter
Supply line
Burner plug
red
white
red
Terminal strips in the control box
Fan motor
white
red
numbered burner cable
*) During the thermostat connection: Remove bridge
20
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
Page 21
Wiring Diagram Fan Motor
Fan motor connection 400 V / 3~ Burner motor connection ( 3~ )
Control voltage
F1 Control fuse F2 Fuse block (fan motor) F3 Thermal overcurrent relay (fan motor) F4 Fuse block burner motor (optional) H2 Malfunction lamp (burner) H3 Operating lamp (burner) H4 Malfunction lamp (overheating) H5 Operating lamp (fan) H6 Malfunction lamp (fan) KB REMKO triple combination control K1M K2M Contactor for / Y switch
K3M
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
Burner 400 V
Connection to the
thermal overcurrent relay
on the burner motor
M Fan motor RT Room thermostat S1 Operating switchC STB Safety temperature limiter TR Temperature control thermostat TW Temperature monitor
An easily accessible emergency switch must be at­tached in the setup room, but not close to hazardous areas.
This switch must be protected from damage and un­authorised use!
The electrical connections should only be made by authorised personnel.
G
21
Page 22
Exploded View VRS 20 INOX
22
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
Page 23
Spare Part List VRS 20 INOX
No. Description Ref. No.
1 Blow-out cover, cpl. (without blow-out grille) 359169 2 Blow-out grille (front) 1095343 3 Lining plate, left/right 1103140 4 Insulation, left/right 1103141 5 Insulation, front 1103142 6 Lining plate, front 1103143 7 Air suction grille, left/right 1103144 8 Lining plate, top/bottom 1103145
9 Safety temperature limiter, STB 1101197 10 Temperature monitor, TW 1103146 11 Lining plate, operating field 1103147 12 Control lamp –RED- (burner malfunction) 1105513 13 Control lamp –GREEN- (operation display) 1105514 14 Operating switch 1101188 15 Unit frame, cpl. 1103148 16 Base plate 1103149 17 Air supply fan, cpl. 1108606 18 Air intake grille, back 1103150 19 Intermediate plate 1130151 20 Fan regulator, TR 1101683 21 Insulation, back 1103152 22 Lining plate, back 1103153 23 Rosette for exhaust gas connection 1103285 24 Blow-out grille (side) 1095344 29 Inspection cover with exhaust gas connection 1103155 30 Seal for inspection cover 1103156 31 Flue gas brake (set = 6 units) 1103157 32 Combustion chamber, cpl. 1103158
When ordering spare parts, always specify the unit no.!
23
Page 24
Exploded View VRS INOX
Fig. Fan with belt operation
Fig. VRS 50
Replacement for No. 6 for design size 130 and higher
24
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
Page 25
Spare Part List VRS INOX
No. Description
1 Unit frame, cpl. 2 Lining plate, insulated 3 Combustion chamber, cpl. 4 Screw cap 5 Seal, combustion chamber flange. 6 Lining plate, insulated 7 Seal 8 Burner plate 9
Triple combination control
10 Lining plate, front 11 Lining plate, side 12 Inspection cover, front 13 Slotted plate, suction 14 Seal, running metres 15 Flue gas brake 16 Fan, cpl. (230 V/1~)
25 Inox
Ref. No.
1103200 1103201 1103202 1103203 1103204 1103205 1103205 1103210 1103211 1103212 1103213 1103214 1103215 1103215 1103170 1103171 1103172 1103173 1103174 1103175 1103176 1103219 1103220 1103220 1103220 1103220 1103220 1103220 1102948 1102949 1102949 1102949 1102949 1102949 1102949 1103231 1103232 1103232 1103233 ----------- ----------- ----------­1102950 1102951 1102951 1102951 1102951 1102951 1102951 1103235 1103236 1103236 1103236 1103236 1103236 1103236 1108386 1108386 1108386 1108386 1108386 1108386 1108386 1103238 1103239 1103239 1103240 1103241 1103242 1103242 1103256 1103257 1103258 1103259 ----------- ----------- ----------­1103245 1103246 1103247 1103248 1103249 1103250 1103250 1103260 1103261 1103261 1103262 1103263 1103264 1103264 1103255 1103255 1103255 1103255 1103255 1103255 1103255 1102953 1102954 1102955 1102956 1102967 1102957 1102957 1108423 1108602 ----------- ----------- ----------- ----------- -----------
50 Inox
Ref. No.
75 Inox
Ref. No.
100 Inox Ref. No.
130 Inox
Ref. No.
170 Inox
Ref. No.
200 Inox
Ref. No.
17 Slotted plate, suction 18 Seal for inspection cover 19 Inspection cover, side 20 Seal for exhaust gas connection 21 Exhaust gas connection 22 Rosette for exhaust gas connection 23 Lining plate, insulated 24 Air guiding plate, side 25 Lining plate, insulated 26 Intermediate plate, insulated 30 Belt disc, fan 31 Fan motor 400V/3N~ 32 V-belt 33 Belt disc, motor 34 Fan
Not pictured
Control box, cpl. (230 V)
1103260 1103261 1103261 1103262 1103268 1103269 1103269 1103273 1103273 1103274 1103274 1103275 1103275 1103275 1103278 1103278 1103279 1103279 1103280 1103280 1103280 1102947 1102947 1102947 1102947 ----------- ----------- ----------­1103283 1103283 1103284 1103284 ----------- ----------- ----------­1103285 1103285 1103286 1103286 1103287 1103287 1103287 1103290 1103291 1103291 1103292 1103293 1103294 1103294 1103180 1103181 1103182 1103182 1103183 1103184 1103184
----------- ----------- ----------- ----------- 1103190 1103191 1103191
----------- ----------- ----------- ----------- 1103195 1103196 1103196
----------- ----------- 1102776 1102780 1102777 1102782 1102783
----------- ----------- 1102768 1102766 1102766 1102766 1102769
----------- ----------- 1102779 1102773 1102786 1102787 1102788
----------- ----------- 1102770 1102770 1102770 1102770 1102781
----------- ----------- 1108600 1108550 1108601 1108604 1108605
1108388 1108388 ----------- ----------- ----------- ----------- -----------
Control box, cpl. (400 V)
----------- ----------- 292306 292306 292306 292306 292306
When ordering spare parts, always specify the unit no.!
25
Page 26
56987121110151425a/b2
0261
3
1819242321221716234
Exploded View VRS B
35
34 33 32 31 30
29
1
27
28
Fig. VRS 80 upright model
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
26
Page 27
Spare Part List VRS B
No. Description
1 Lining plate, top 2 Unit frame, cpl. 3 Insulation for side lining 4 Verkleidungsblech, seitl. 5 Comb. chamber cpl. (Standard) 5 Comb. chamber cpl. (Inox) 6 Air guiding plate, right 7 Seal comb. chamber flange 8 Rosette 9 Screw cap
10
Triple combination control
11 Flue gas brake 12 Seal for inspection cover 13 Inspection cover, front 14 Insulation, front/top 15 Lining plate, front/top 16 Seal 17 Burner plate 18 Lining plate, front/middle 19 Insulation, front/middle 20 Blind plate 21 Belt disc, motor 22 Fan motor 400V / 3~/ N 23 V-belt
24 Belt disc, fan 25a Fan 25b Fan, cpl. (230 V / 1~ / N)
26 Slotted plate, side
27 Slotted plate, back
28 Assembly plate
29 Inspection cover, side
30 Seal for inspection cover
31 Lining plate, back
32 Insulation, back
33 Air guiding plate, left
34 Exhaust gas connection
35 Rosette, exhaust connection
Not pictured Seal for exhaust connection Control box, cpl. (230 V) Control box, cpl. (400 V)
Control box, cpl. ( Y∆ )
VRS 40 Ref. No.
1104201 1104202 1104202 1104203 1104204 1104205 1104205 1104206 1104207 1104208 1104209 1104210 1104211 1104212 1104213 1104214 1104214 1104215 1104216 1104217 1104218 1104219 1104220 1104221 1104222 1104223 1104223 ———— ———— ———— 1104227 1104228 1104229 1104230 1104231 1104232 1104232 1104233 1104234 1104235 1104237 1104238 1104239 1104240 1104241 1104242 1104243 1104244 1104245 1104246 1104248 1104249 1104250 1104251 1104252 1104253 1104254 1104255 1104256 1104257 1104258 1104259 1104260 1104261 1104262 1104263 1104263 1104264 1104265 1104266 1104267 1104267 1104267 1104267 1104267 1104268 1104268 1104375 1104375 1104375 1104269 1104269 1104269 1104269 1104269 1104269 1104269 1104269 1104269 1104269 1103219 1103219 1103219 1103219 1103219 1103219 1103219 1103219 1103219 1103219 1102572 1102572 1102572 1102572 1102572 1102572 1102572 1102572 1102572 1102572 1102953 1102954 1102955 1102955 1102955 1102957 1102957 1102958 1102958 1102959 1103255 1103255 1103255 1103255 1103255 1103255 1103255 1103255 1103255 1103255 1104271 1104272 1104272 1104273 1104273 1104274 1104274 1104275 1104276 1104277 1104279 1104280 1104280 1104281 1104281 1104282 1104282 ———— ———— ———— 1104286 1104287 1104287 1104288 1104288 1104289 1104289 1104290 1104291 1104291 1104292 1104292 1104292 1104292 1104292 1104293 1104293 1103234 1103234 1103234 1104294 1104294 1104294 1104294 1104294 1104295 1104295 1103237 1103237 1103237 1104297 1104298 1104298 1104299 1104299 1104300 1104300 1104301 1104302 1104302 1104304 1104305 1104305 1104306 1104306 1104307 1104307 ———— ———— ———— 1104311 1104312 1104312 1104313 1104314 1104315 1104315 1104316 1104317 1104317
dep. on compres. ----------- ----------- ----------- ----------- ----------- ----------- ----------- -----------
1104318 1104319 1104320 1104320 1104321 1104322 1104322 1104322 1104323 1104324 1104326 1104327 1104327 1104328 1104329 1104330 1104330 1104331 1104323 1104323
1104333 1104333 1104333 1104333 1104333 1104334 1104334 1104335 1104336 1104336 1103255 1103255 1103255 1103255 1103255 1103255 1103255 1103255 1103255 1103255 1104338 1104339 1104340 1104341 1104341 1104342 1104343 1104344 1104345 1104345 1104347 1104348 1104349 1104350 1104350 1104351 1104352 ———— ———— ———— 1104356 1104357 1104358 1104359 1104360 1104361 1104361 1104362 1104363 1104364 1104366 1104367 1104368 1104369 1104369 1104370 1104371 1104372 1104373 1104373 1103285 1103285 1103286 1103286 1103286 1103287 1103288 1103288 1103289 1103289
1103255 1103255 1103255 1103255 1103255 1103255 1103255 1103255 1103255 1103255
VRS 60 Ref. No.
VRS 80
Ref. No.
VRS 120
Ref. No.
dependent on the unit model and compression
dependent on the unit model and compression
dependent on the unit model and compression
VRS 150
Ref. No.
VRS 210
Ref. No.
VRS 250
Ref. No.
VRS 310
Ref. No.
VRS 380
Ref. No.
VRS 450
Ref. No.
The Spare Parts List VRS B applies only for standard model units.
G
When ordering spare parts, always specify the unit no.!
G
27
Page 28
Unit Dimensions VRS INOX
Standing Unit
ø R
C
D
E
Unit on its side
Unit type
(dimensions in mm)
A 565 850 1000 1250 1250 1530 1650 1650 B 455 600 800 800 900 1010 1200 1200 C 1285 1500 1700 1700 1800 2095 2260 2260
C1 1470 1570 1870 2070 2270
D 580 955 1052 1052 1100 1230 1330 1330 E 890 815 900 900 907 1075 1160 1160 F 35 35 35 35 35 35 35 35 G 262 335 435 435 485 540 635 635 R 150 150 150 180 180 200 200 200
B
A
B
G
C1
VRS 20 I VRS 25 I VRS 50 I VRS 75 I VRS 100 I VRS 130 I VRS 170 I VRS 200 I
F
A
28
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
Page 29
Unit Dimensions VRS B
Standing Unit
Unit on its side
Unit type
(dimensions in mm)
A 825 1055 1284 1284 1514 1667 1667 1860 1860 2318 B 595 825 825 978 978 1284 1284 1477 1630 1630 C 1208 1360 1360 1513 1743 1973 1973 2242 2472 2472 D 545 775 1005 928 1192 1234 1234 1377 1530 1912 E 545 775 775 928 928 1234 1234 1377 1530 1530 F 1073 1210 1210 1325 1583 1092 1092 1123 1257 1257 G 515 515 515 515 622 622 622 605 765 765
ø
P 120 130 130 145 142 190 190 215 240 240 R ø
S 982 976 976 1078 1308 1392 1392 1520 1736 1736 Weight kg 190 260 305 365 450 680 735 930 1055 1240
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.
VRS 40 VRS 60 VRS 80 VRS 120 VRS 150 VRS 210 VRS 250 VRS 310 VRS 380 VRS 450
dependent on the respective oil– or gas-forced-air burner
150 150 180 180 180 200 250 250 300 300
29
Page 30
Maintenance Log
Model: : ................................ Model No.: : ......................................
Burner : ................................ Burner No.: : ......................................
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Clean unit -surface­Clean unit -interior­Clean fan Clean combustion chamber Clean heat exchanger Clean/replace waste gas suppressor Replace seals -inspection cover­Replace seals –burner­Clean/replace filter -fuel­Check safety mechanisms Electric safety inspections Check protective mechanisms Check unit for damage Maintenance –burner Test run
Remarks: ......................................................................................................................................................................
......................................................................................................................................................................................
1. Date: ...................... 2. Date: ...................... 3. Date: ...................... 4. Date: ...................... 5. Date: ......................
.................................. ................................... ................................... ................................... ...................................
Signature Signature Signature Signature Signature
6. Date: ...................... 7. Date: ...................... 8. Date: ...................... 9. Date: ...................... 10. Date: ....................
.................................. ................................... ................................... ................................... ...................................
Signature Signature Signature Signature Signature
11. Date: .................... 12. Date: .................... 13. Date: .................... 14. Date: .................... 15. Date: ....................
.................................. ................................... ................................... ................................... ...................................
Signature Signature Signature Signature Signature
16. Date: .................... 17. Date: .................... 18. Date: .................... 19. Date: .................... 20. Date: ....................
.................................. ................................... ................................... ................................... ...................................
Signature Signature Signature Signature Signature
30
Maintenance work may only be performed by authorised personnel; settings must comply
with legal specifications. A corresponding test log must be kept.
Page 31
Page 32
REMKO GmbH & Co. KG
Klima- und Wärmetechnik D-32791 Lage Im Seelenkamp 12
D-32777 Lage PO Box 1827 Phone +49 (5232) 606 - 0 Fax +49 (5232) 606260
Loading...