Remko RXT 685 DC User guide

Page 1
Operating and installation instructions
REMKO RXT series
Wall and ceiling chests for cooling and heating
RXT 525 DC, RXT 685 DC, RXT 1055 DC, RXT 1405 DC
0217-2021-07 Edition 2, en_GB
Read the instructions prior to performing any task!
Page 2
Refrigerant
Read these operating instructions carefully before commis­sioning / using this device!
These instructions are an integral part of the system and must always be kept near or on the device.
Subject to modifications; No liability accepted for errors or mis­prints!
Translation of the original
Page 3

Table of contents

1 Safety and usage instructions............................................................................................................. 5
1.1 General safety notes....................................................................................................................... 5
1.2 Identification of notes...................................................................................................................... 5
1.3 Personnel qualifications.................................................................................................................. 5
1.4 Dangers of failure to observe the safety notes................................................................................ 5
1.5 Safety-conscious working............................................................................................................... 6
1.6 Safety instructions for the operator................................................................................................. 6
1.7 Safety notes for installation, maintenance and inspection ............................................................. 6
1.8 Unauthorised modification and changes......................................................................................... 7
1.9 Intended use................................................................................................................................... 7
1.10 Warranty........................................................................................................................................ 7
1.11 Transport and packaging............................................................................................................... 7
1.12 Environmental protection and recycling........................................................................................ 8
2 Technical data........................................................................................................................................ 9
2.1 Unit data.......................................................................................................................................... 9
2.2 Unit dimensions ............................................................................................................................ 12
3 Design and function............................................................................................................................ 13
3.1 Unit description............................................................................................................................. 13
4 Operation............................................................................................................................................. 14
4.1 General notes................................................................................................................................ 14
4.2 Display on indoor unit.................................................................................................................... 15
4.3 Keys on the remote control........................................................................................................... 16
5 Installation instructions for qualified personnel.............................................................................. 24
5.1 Important notes prior to installation............................................................................................... 24
5.2 Selection of installation location ................................................................................................... 24
5.3 Installation materials..................................................................................................................... 25
5.4 Wall openings................................................................................................................................ 26
5.5 Fastening options for the indoor unit............................................................................................. 27
5.6 Minimum clearances..................................................................................................................... 29
5.7 Connection variants...................................................................................................................... 29
5.8 Oil return measures....................................................................................................................... 29
6 Installation........................................................................................................................................... 30
6.1 Preparations for installation........................................................................................................... 30
6.2 Installation of the indoor unit......................................................................................................... 30
6.3 Connection of refrigerant piping.................................................................................................... 30
6.4 Additional notes on connecting the refrigerant piping................................................................... 32
6.5 Leak testing................................................................................................................................... 33
6.6 Adding refrigerant.......................................................................................................................... 33
7 Condensate drainage connection and safe drainage...................................................................... 34
8
Electrical wiring................................................................................................................................... 36
8.1 General notes................................................................................................................................ 36
8.2 Connecting the indoor unit............................................................................................................ 36
8.3 Outdoor unit connection................................................................................................................ 37
8.4 Electrical wiring diagram............................................................................................................... 37
8.5 Electrical drawings........................................................................................................................ 39
9 Before commissioning....................................................................................................................... 43
3
Page 4
REMKO RXT series
10 Commissioning................................................................................................................................... 43
1
1 Shut-down............................................................................................................................................ 44
12 Troubleshooting, customer service and fault analysis................................................................... 45
12.1 Troubleshooting and customer service....................................................................................... 45
12.2 Indoor unit fault analysis............................................................................................................. 48
12.3 Resistances of the temperature probes...................................................................................... 59
13 Care and maintenance........................................................................................................................ 62
14 Exploded view and spare parts lists................................................................................................. 64
14.1 Exploded view - Indoor unit RXT 525-685 DC ........................................................................... 64
14.2 Spare parts list - Indoor unit RXT 525-685 DC........................................................................... 65
14.3 Exploded view - Indoor unit RXT 1055-1405 DC ....................................................................... 66
14.4 Spare parts list - Indoor unit RXT 1055-1405 DC....................................................................... 67
14.5 Exploded view - Outdoor unit RXT 525 DC ................................................................................ 68
14.6 Spare parts list - Outdoor unit RXT 525 DC................................................................................ 69
14.7 Exploded view - Outdoor unit RXT 685 DC ................................................................................ 70
14.8 Spare parts list - Outdoor unit RXT 685 DC................................................................................ 71
14.9 Exploded view - Outdoor unit RXT 1055 DC .............................................................................. 72
14.10 Spare parts list - Outdoor unit RXT 1055 DC............................................................................ 73
14.11 Exploded view - Outdoor unit RXT 1405 DC ............................................................................ 74
14.12 Spare parts list - Outdoor unit RXT 1405 DC............................................................................ 75
15 Index..................................................................................................................................................... 76
4
Page 5
1 Safety and
usage instructions

1.1 General safety notes

Carefully read the operating manual before com­missioning the units or their components for the first time. It provides useful tips and notes such as hazard warnings to prevent injury and material damage. Failure to follow manual can endanger persons, the environment and the equipment itself or its components and will void any claims for liability.
Store this manual and the information required for the operation of this system (e.g. refrigerant data­sheet) in the vicinity of the unit.
The refrigerant used in the system is flammable. If applicable, observe the local safety conditions.
the directions in this
DANGER!
This combination of symbol and signal word warns of a situation in which there is immediate danger cause serious injury.
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury
, which if not avoided may be fatal or
WARNING!
.
Warning of inflammable substances!

Identification of notes

1.2
This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation.The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by sym­bols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.
CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or mate­rial and environmental damage.
NOTICE!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.
This symbol highlights useful tips and recom­mendations as well as information for efficient and fault-free operation.

1.3 Personnel qualifications

DANGER!
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.
Personnel responsible for commissioning, opera­tion, maintenance, inspection and installation must be able to demonstrate that they hold a qualifica­tion which proves their ability to undertake the work.
Dangers of failure to observe
1.4 the safety notes
Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.
5
Page 6
REMKO RXT series
In particular, failure to observe the safety notes may pose the following risks:
n The failure of important unit functions. n The failure of prescribed methods of mainte-
nance and repair
n Danger to people on account of electrical and
mechanical effects.
.

1.5 Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.
Safety instructions
1.6 for the operator
The operational safety of the units and compo­nents is only assured providing they are used as intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified per­sonnel.
n Protective covers (grills) over moving parts
must not be removed from units that are in operation.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with equipment parts or components
can lead to burns or injury
n The units and components must not be
exposed to any mechanical load, extreme levels of humidity or extreme temperatures.
n Rooms in which refrigerant may escape shall
be adequately aerated and ventilated. Other­wise, a risk of suffocation or fire exists.
n Do not leave children unsupervised when close
to the system.
n Commissioning must be performed by author-
ised specialists exclusively. Deficient commis­sioning may lead to water leaks, electric shocks or fire. Commissioning must take place as described in the user manual.
n Only instruct authorised specialist personnel to
perform maintenance or servicing.
n The system is filled with a flammable refrig-
erant. Never thaw any frozen unit components independently!
n Do not operate any further devices that pro-
duce high heat or naked flames in the same room.
.
n All housing parts and unit openings, e.g. air
inlets and outlets, must be kept clear
n The units must be inspected by a service tech-
nician to ensure that they are safe to use and fully functional at least once yearly. Visual inspections and cleaning may be performed by the operator when the units are disconnected from the mains.
.

1.7 Safety notes for installation, maintenance and inspection

n The refrigerant R32 used in the system is flam-
mable. If applicable, observe the local safety conditions.
n Keep the cooling circuit clear of other gases
and foreign substances. Only fill the cooling cir­cuit with the refrigerant R32.
n Only use the accessories, components and
appropriately marked parts provided. The use of non-standardised components may result in water leaks, electric shocks and fire.
n Only install and store the units in rooms larger
than 4 m2. With a failure to comply result in the room filling with a flammable mix­ture!
The minimum room size of 4 m2 required for installation and storage pertains to the basic fill quantity of the unit. This varies according to the installation type and total fill quantity of the system. The calculation must take place in accordance with valid DIN standards. Make sure that the installation site is suitable for safe unit operation.
n Only mount the unit components on structurally
suitable brickwork.
n The units must not be installed in rooms in
which further devices that produce heat are operated (heaters, open hearths).
n Make sure the installation room is sufficiently
ventilated.
n Interventions in the cooling circuit are only pos-
sible after completely draining the refrigerant. Never solder or grind unit components!
n Note that refrigerant may be odourless. n Never operate the air conditioning unit in a
humid room, such as a bathroom or laundry room. If the humidity is too high, this can cause short circuits on electrical parts.
n The product must be correctly earthed at all
times, otherwise it may induce electric shocks.
n Attach the condensate drain as described in
the operating manual. The inadequate drainage of condensate can lead to water damage in your apartment.
n All persons who intervene in the cooling circuit
must hold a valid certificate from the chamber of industry and commerce, which confirms their ability to work with refrigerant.
, leaks may
6
Page 7
n Appropriate hazard prevention measures must
be taken to prevent risks to people when per­forming installation, repair cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
n Regional regulations and laws as well as the
Water Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n Units may only be mounted at the points pro-
vided for this purpose at the factory. The units may only be secured or mounted on stable structures, walls or floors.
n The units and components should not be oper-
ated in areas where there is a heightened risk of damage. Observe the minimum clearances.
n The units and components must be kept at an
adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
n Safety devices may not be modified or
bypassed.
n The connection of the indoor unit must be
established as a permanent connection; a detachable, reusable connection is not permis­sible.
, maintenance or

1.8 Unauthorised modification and changes

1.10 Warranty

For warranty claims to be considered, it is essential that the ordering party or its representative com­plete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the "Gen­eral business and delivery conditions". Further­more, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.
1.1

1 Transport and packaging

The devices are supplied in a sturdy shipping con­tainer. Please check the equipment immediately upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to children!
Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufactured ensure safety use of other parts may invalidate liability for resulting consequences.
. The

1.9 Intended use

Depending on the model, the units and the addi­tional fittings with which they are equipped are only intended to be used as an air-conditioner for the purpose of cooling or heating the air in an enclosed space.
Any different or additional use is a non-intended use. The manufacturer/supplier assumes no lia­bility for damages arising from a non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
The threshold values specified in the technical data must not be exceeded.
7
Page 8
REMKO RXT series

1.12 Environmental protection and recycling

Disposal of packaging
All products are packed for transport in environ­mentally friendly materials. Make a valuable contri­bution to reducing waste and sustaining raw mate­rials. Only dispose of packaging at approved collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufac­ture of the devices and components. Help protect the environment by ensuring that the devices or components (for example batteries) are not dis­posed in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. using certified firms and recy­cling specialists or at collection points.
8
Page 9

2 Technical data

2.1 Unit data

Series RXT 525 DC RXT 685 DC RXT 1055 DC RXT 1405 DC
Operating mode
Nominal cooling output
1)
Energy efficiency ratio SEER
Power consumption, annual, QCE
3)
Energy efficiency ratio, cooling
Nominal heat capacity
2)
Energy efficiency ratio SCOP
Power consumption, annual, QHE
3)
Energy efficiency ratio, heating
Rated power consumption, electrical cooling
1)
kW
1)
kWh 305 413 574 ---
1)
kW
4)
kWh 1400 1925 2937 ---
2)
kW
Rated elec. curr. consump., cooling
1)
Inverter wall/ceiling-mounted room air conditioner combination
for cooling and heating
5,30
(2,70-5,90)
7,00
(2,70-7,70)
10,60
(2,70-1
1,80)
14,10
(3,50-15,20)
6,2 6,1 6,4 ---
A++ A++ A++ ---
5,60
(2,40-6,30)
7,60
(2,70-8,30)
11,70
(2,80-12,80)
16,10
(4,10-17,0)
4,0 4,0 4,0 ---
A+ A+ A+ ---
1.63 2.19 3.75 5.50
A 7.20 10.00 5.80 9.10
Rated power consumption, electrical heating
2)
Rated elec. curr. consump., heating
2)
kW 1.50 2.05 3.00 5.05
A 6.60 9.50 4.80 8.14
Max. power consumption kW 2.95 2.95 5.60 6.20
Max. current consumption A 13.50 13.50 10.00 11.20
EDP no. 1619550 1619560 1619570 1619580
1)
Air inlet temp. TK 27 °C/FK 19 °C, outside temperature TK 35 °C, FK 24 °C, max. air flow volume,
5 m pipe length
2)
Air inlet temp. TK 20 °C, outside temperature TK 7 °C, FK 6 °C, max. air flow volume, 5 m pipe length
3)
The specified value is based on results from standard testing.
The actual consumption depends on the use and location of the unit
4)
The specified value is based on the average heating period
9
Page 10
REMKO RXT series
Data specific to indoor unit
Power supply V/Ph/Hz 230/1~/50
Application area (room vol.) approx.
Adjustment range room temperature
Operating range
Air flow volume per stage
Sound pressure level per stage
Sound power (turbo mode) dB(A) 59 65 65 65
Enclosure class IP X0
Condensate drainage connection
Dimensions: H/W/D mm 675/1068/235 675/1650/235
5)
m
°C +17 to +30
°C/
RH %
m3/h
dB (A) 24/37/41/44 32/43/46/49 39/45/48/51 36/45/50/53
mm 25
RXT 525 DCITRXT 685 DCITRXT 1055 DCITRXT 1405 DC
3
160 230 320 470
+17 to +30 / 35 to 65
723/839/
958
853/1023/
1
192
1504/1728/
1955
IT
1600/1850/
2100
Weight kg 28.0 26.8 39.0 41.2
EDP no. 1619552 1619562 1619572 1619582
5)
At distance of 1 m in the open air; specified values are maximum values
10
Page 11
RXT 525 DC
RXT 685 DCATRXT 1055 DCATRXT 1405 DC
Data specific to outdoor unit
A
T
AT
Power supply V/Ph/Hz 230/1~/50 400/3~/50
Operating range, cooling °C
Operating range, heating °C
Air flow rate, max.
m3/h
+5 to +50
+5 to +24
2000 2700 4000 7500
7)
7)
Enclosure class IP 24
Sound pressure level
5)
dB (A) 55 62 64 66
Sound power level max. dB (A) 63 64 68 72
Refrigerant
6)
R32
Refrigerant, basic quantity kg 1.15 1.50 2.40 2.90
CO2 equivalent t 0.78 1.01 1.62 1.89
Operating pressure, max. kPa 4200/1500
Refrigerant, additional quantity >5 m
g/m 30 30 30 30
Refrigerant piping, max. length m 30 50 65 65
Refrigerant piping, max. height m 20 25 30 30
Refrigerant connection
Liquid line
Refrigerant connection
Suction pipe
Inches
(mm)
Inches
(mm)
1/4 (6.35) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
1/2 (12.70) 5/8 (15.90) 5/8 (15.90) 5/8 (15.90)
Dimensions: H/W/D mm 554/800/333 673/962/380 810/946/410 1333/952/410
Weight kg 33,5 43,9 80,5 103,7
EDP no. 1619551 1619561 1619571 1619581
5)
At distance of 1 m in the open air; specified values are maximum values
6)
Contains greenhouse gas per the Kyoto protocol, GWP 675 (for further information,
see chapter "Adding refrigerant")
7)
This can be extended to -15 °C with the appropriate accessory kit
11
Page 12
D
E
B
A
C
B
C
A
REMKO RXT series

2.2 Unit dimensions

Outdoor units
Fig. 1: Dimensions RXT 525-1405 DC AT (all measurements in mm)
Measurements (mm) A B C D E
RXT 525 DC AT 874 511 317 554 346
RXT 685 DC AT 962 663 348 673 380
RXT 1055 DC AT 946 810 410 673 403
RXT 1405 DC AT 952 1333 410 634 404
Indoor units
Fig. 2: Unit dimensions, indoor unit RXT 525-1405 DC IT
Measurements (mm) A B C
RXT 525 DC IT 675 1068 235
RXT 685 DC IT 675 1068 235
RXT 1055 DC IT 675 1650 235
RXT 1405 DC IT 675 1650 235
12
Page 13
B
A
4
3
5
6
1
2
3
7
8
9
1
EEV
RXT 1051 DC
M
M
PS H
T1
T2
T
3
TE
T5
P
S
L
T4
T3
T2
M3
M2
M1
PSL
PSH
T1
V1
M
M
TE
PS H
T1
T2
T
3
T5
P
S
L
M1
M3
T4
T3
T2
M2
PSL
PSH
T1
V1
EEV
2
A B
A B
FLT
FLT
FLT
FLT
OEL
T5
T5

3 Design and function

3.1 Unit description

The RXT room air conditioners have a REMKO RXT...DC AT outdoor unit as well as a RXT...DC IT indoor unit.
In cooling mode, the outdoor unit serves to output the heat extracted by the indoor unit from the room being cooled. In heating mode, the heat taken up by the outdoor unit can be discharged by the indoor unit into the room to be heated. In both operating modes, the output produced by the com­pressor precisely matches requirements, and thereby regulates the nominal temperature with minimal temperature deviations. This "inverter technology" results in energy savings over conven­tional split systems and also reduces noise emis­sions to a particularly low level. The outdoor unit can be installed in an outdoor area or, providing that certain requirements are met, an indoor area. The outdoor unit consists of a cooling cycle with compressor, fin condenser, condenser fan, reversing valve and electronic expansion valve. The outdoor unit is controlled by the regulation of the indoor unit.
The indoor unit is designed both for both wall and ceiling-mounted operation in indoor areas. It is operated by an infrared remote control. The indoor unit consists of a fin evaporator, evaporator fan, controller and condensate tray.
Floor consoles, wall consoles, refrigerant piping, wired remote controls and condensate pumps are available as accessories.
Refrigerant piping is used to connect the indoor unit to the outdoor unit.
Fig. 4: Cooling cycle schematic
A: Outdoor area B: Indoor area 1: RXT 525-685 DC 2: RXT 1055-1405 DC M1: Condenser fan M2: Compressor M3: Evaporator fan IT V1: Changeover valve C/H EEV: Electr. expansion valve FLT: Filter OEL: Oil return line PSH: High pressure switch AT PSL: Low pressure switch AT T1: Probe, evaporator IT T2: Probe, air inlet IT T3: Probe, condenser AT T4: Probe, air inlet AT T5: Probe, heat gas AT
Fig. 3: System layout RXT 525-1405 DC
A: Outdoor area / B: Indoor area 1: Indoor unit / 2: Outdoor unit 3: Condensate drainage line / 4: Condenser fan 5: Power supply / 6: Shut-off valve 7: Suction pipes / 8: Injection pipes 9: Control lines
13
Page 14
max. 6 m
REMKO RXT series

4 Operation

4.1 General notes

The indoor unit is easily operated using the standard infrared remote control. The indoor unit beeps to acknowledge the correct transmission of data. If it is not possible to program the indoor unit with the remote control, then it can also be man­ually operated.
Manual mode
The indoor unit can also be started manually. By pressing the "Manual" key (on the display board) multiple times, the unit can be activated with the following functions:
The following settings apply for manual operation:
Pressing once: Automatic mode 24°C, fan speed automatic
Pressing twice: Cooling mode, fan speed high
Pressing three times: Unit OFF
Fig. 5: Maximum distance
Infrared remote control
The infrared remote control sends the programmed settings a distance of up to 6 m to the receiver of the indoor unit. Data will only be received correctly if the remote control is pointed at the receiver and no objects are obstructing the transmission path.
wo AAA batteries must be inserted into the
T remote control in preparation. To do so, remove the flap from the battery compartment and insert the batteries the correct way around (see mark­ings).
NOTICE!
Immediately replace flat batteries with a new set, otherwise there is a risk of leakage. It is recommended that the batteries are removed if the equipment is shut down for longer periods.
14
Page 15
MANUAL TIMER
ALARM
OPERATION
DEF./FAN
1 2 3
5 6
4
7
Wired remote control
Connection of the optional wired remote control
1. The plug for connection of a wired remote control is located behind the panel at the dis­play board (
Fig. 6). The 5-core cable, coming from the display panel, is marked with the designations "A-E" (Fig. 7).
Fig. 6: Indoor unit panel
Fig. 7: Display circuit board

4.2 Display on indoor unit

Display on indoor unit
The LED indicators illuminate to indicate the set­tings:
Fig. 8: Display for setpoint/errors
1: Digital display 2: Manual operation 3: Operation display 4: Timer indicator 5: Unit for receiving signals from the remote con-
trol 6: Defrosting fan 7: Alarm indicator
Alarms are indicated by a code (see chapter
roubleshooting and customer service).
T
Help save on energy consumption in stand-by mode! If the device, system or component is not in use, we recommend disconnecting the power supply excluded from our recommendation!
. Components with a safety function is
15
Page 16
10
8
11 12
2
1
6
3
7
5
9
4
13
14
1
2
3
4
5
6
7
8
9
10
11
12
REMKO RXT series

4.3 Keys on the remote control

“Swing” key
Starts and stops the horizontal fin movement. Press and hold the key for 2 seconds to start the vertical fin movement (available depending on the unit model).
“Fan speed” key
Allows switching between the dif
ferent fan speeds
in the following order:
Automatic Low Medium High
Note: To activate the silence function (available depending on the appliance model) of the appli­ance, press and hold the key for 2 seconds.
urbo” key
“T
Activating the turbo function ensures that the set­point is reached as quickly as possible.
“Mode” key
This key allows switching between the dif
ferent
operating modes in the following order:
Fig. 9: Keys on the remote control
“On/Off” key
Press this key to switch the air conditioning unit on
f.
and of
“Arrow up” temperature key
Increases the setpoint in 1 °C steps up to a tem­perature of max. 30 °C.
“SET” key
Makes it possible to switch between dif ating functions as follows:
“Follow me” function (
- Network configuration ( )
- “Follow me” function ( )
The selected function flashes in the display firm with the “OK” key.
)
ferent oper-
, con-
Automatic Cooling Dehumidifying Heating Recirculation
“Sleep” key
Activates/deactivates the energy saving function of the unit (e.g. overnight).
“OK” key
Required to confirm various functions of the IR remote control.
imer” key
“T
Activates/deactivates the time-delayed start of the unit or the unit switch-off.
“Arrow down” temperature key
Decreases the setpoint in 1 °C steps down to a temperature of min. 17 °C.
“Fresh” key
Activates/deactivates the REMKO BioClean func­tion (ionisation).
16
Page 17
13
14
1 3
2
5
6
7
4
8
9
10
11
12
13
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
“Clean” key
Activates/deactivates the self-cleaning function of the unit (available depending on the unit model).
“LED” key
Enables switching on/of
f the unit lighting and the
signal tones (depending on the unit).
Indicators on the LCD
Time-delayed switch-on active.
Time-delayed switch-off active.
Silent mode active.
Fan speed
Displays the set fan speed as follows:
Low:
Medium:
High:
Automatic:
Mode selection
Shows the current operating mode.
Eco function
Lights up when the Eco function is active (available depending on the unit).
Key lock
Symbol appears when the key lock is activated.
emperature/Timer/Fan speed
T
Fig. 10: Indicators on the LCD
Shows the current temperature setpoint in the basic view. When using the additional function “Timer”, the corresponding time values are shown.
BioClean function active (available depending
on the unit type).
Sleep function active.
Follow-me function active.
Network configuration active.
Battery low (flashing).
Signal transmission
Lights up when a signal is sent from the IR remote control to the air conditioning unit.
17
Page 18
REMKO RXT series
Temperature setting
The temperature setting can be made within a range of 17-30 °C. The setpoint is adjusted in 1 °C steps.
Automatic mode
In automatic mode, the unit automatically selects the operating mode based on the set temperature setpoint.
1. Press the “Mode” key to activate the “Auto” function.
2. Set the desired temperature using the “Λ and “V” keys.
3. The unit can be switched on by pressing the “ON/OFF” key.
Cooling mode
1. Press the “Mode” key and activate the “Cool”
function.
2. Set the desired temperature using the “Λ
and “V” keys.
3. Press the “FAN” key to select the fan speed. The following are available: Automatic, Low, Medium and High
4. The unit can be switched on by pressing the “ON/OFF” key.
The fan speed cannot be set in automatic mode!
Fig. 11: Cooling mode
18
Page 19
2
1
3
2
1
3
Timer function
With the “Timer” function, the unit can switch on with a switch-on delay or switch of off delay.
Time-delayed switch-on
1. Press the “T
setting
2. Use the arrow keys to select the desired number of hours after which the air condi­tioning unit is to switch on
3. Point the remote control towards the air con­ditioning unit and wait 1 sec. The timer is now active (symbol in the display of the remote control)
imer” key to enter the “Time ON”
f with a switch-
Time-delayed switch-off
1. Press the “T
OFF” setting
2. Use the arrow keys to select the desired number of hours after which the air condi­tioning unit is to switch of
3. Point the remote control towards the air con­ditioning unit and wait 1 sec. The timer is now active (symbol in the display of the remote control)
imer” key to enter the “Time
f
Fig. 13: Time-delayed switch-off
Fig. 12: Time-delayed switch-on
19
Page 20
13.00
14.00 15.00 15.30 16.00 17.00 18.00
a
b c
2
1
3
1
2
REMKO RXT series
Combining time-delayed switching on and off
Fig. 14: Combining time-delayed switching on and off
1: Timer starts 2: Unit switches on 3: Unit switches off
Example: If both timers are activated at 13:00, the unit switches on 2.5 hours later (at 15:30) and switches off 5 hours later (at 18:00).
“Swing” function
Press the “Swing” key
1. The horizontal air guide fin starts to rise and fall automatically desired position
2. On units with 3D swing function, pressing the “Swing” key for 2 seconds activates the vertical fin move­ment
a: current (13:00) b: 2.5 hours later c: 5 hours later
. Pressing again stops the fin at the
Fig. 15: “Swing” function
20
Page 21
2
1
Deactivate lighting and signal tones
1. Press the “LED” key to switch the unit lighting
on and of
2. Press and hold the “LED” key for longer than 5 seconds, the ACTUAL temperature appears in the unit display (not available for all unit types)
Fig. 16: Deactivate lighting and signal tones
Activating Silent function
Depending on the unit type, the Silent function (low-noise unit operation) can be activated. T this, the “FAN” key must be pressed and held for 2 seconds. The unit now operates in a particularly quiet mode. It must be taken into account that the unit cannot call up the full cooling or heating capacity.
The silent mode can be deactivated again by pressing the “ON/OFF”, “Mode”, “Sleep”, “Turbo” or “Clean”.
f.
o do
Frost protection function
The air conditioning unit operates at high fan speed with a fixed setpoint of 8 °C (only available in heating mode).
o activate this function, heating mode must be
T activated and the setpoint must be set to 17°C.
Pressing the “Arrow down” key twice within one second activates the FP function.
The function can be deactivated again by pressing the “On/Off”, “Sleep”, “Mode”, “Fan” keys and the temperature setting.
Fig. 19: Frost protection function
Activating key lock
Hold the “Clean” and “T for 5 seconds to activate the key lock.
To deactivate the key lock, both keys must be pressed again for 2 seconds.
Fig. 20: Activating key lock
urbo” keys simultaneously
“Shortcut” key
Pressing this key (not available on all unit models) while the unit is in operation will reset all settings (including operating mode, setpoint, fan speed and
Fig. 17: Silent function
Eco function
Press the “Eco” key (not available on all models) to activate the energy-saving function of the unit.
Note: Function only available in cooling mode!
Fig. 18: COS Eco function
Function description:
Pressing this key in cooling mode automatically sets the temperature setpoint to 24 °C. When the room temperature is <24 °C, the fan goes into energy-saving mode. If the room temperature is >24 °C, the fan speed remains in the “Automatic” operating mode.
sleep function) to the last used settings.
Fig. 21: “Shortcut” key
21
Page 22
REMKO RXT series
Self-cleaning function
Press the “Clean” key (not available on all unit models).
Due to the formation of condensate on the heat exchanger and the residual moisture that remains, bacteria can multiply quickly operation, the heat exchanger is dried by the air volume flow. This drying process can also be started manually with the “Clean” function (for example, if the unit is not in regular use). In cooling or dehumidification mode, the self-cleaning func­tion can be activated. The unit switches off auto­matically after cleaning.
. In regular normal
“Turbo” function
If the “T unit operates with the highest possible cooling capacity and at the same time with the highest fan speed.
This allows the desired setpoint to be reached as quickly as possible.
Fig. 23: “Turbo” function
urbo” key is pressed in cooling mode, the
Fig. 22: Self-cleaning function
22
Page 23
“Set” key
Press the “Set” key to enter the settings menu. Press the “Set” key or the arrow keys again to select the desired function. The corresponding function flashes on the display of the remote control. Press the “OK” key to select it.
Fig. 24: “Set” key
The additional functions are shown in the following order:
BioClean function ( ) Sleep function ( ) Follow-Me function ( ) Network configuration ( )
If your remote control has the “Fresh” and “Sleep keys, these functions cannot be operated via the “SET”
.
key
“BioClean” function ( )
When the BioClean function is activated, negatively charged ions are released into the air stream to increase the air quality
Sleep function
The sleep function can be used to save energy during night operation. This function is not available in the “Recirculation” and “Humidification” operating modes. The “Sleep” key should be pressed before going to bed. In cooling mode, the unit will increase the setpoint by 1 °C after 1 operating hour ating hour, the temperature is increased by 1 °C again. In heating mode, the setpoint is lowered by the previ­ously mentioned parameters.
The sleep function deactivates automatically after an operating time of 8 hours.
AP mode (network configuration)
Not available for all unit types and can only be used in combination with the optional REMKO WifiStick. AP mode can be activated by pressing the “LED” key several times within 10 seconds. The unit is now in net­work configuration mode. For integration via WLAN, please observe the assembly and operating instructions of the REMKO Wifi-Stick.
.
. After another oper-
23
Page 24
REMKO RXT series

5 Installation instructions for qualified personnel

5.1 Important notes prior to installation

ransport the unit in its original packaging as
n T
close as possible to the installation location. You avoid transport damage by doing so.
n Check the contents of the packaging for com-
pleteness and check the unit for visible trans­port damage. Report any damage immediately to your contractual partner and the shipping company.
n Lift the unit on the corners and not on the
refrigerant or condensate drainage connec­tions.
n The refrigerant piping (injection and suction
pipe), valves and connections must be insu­lated against vapour density. If necessary also insulate the condensate drainage line.
n Select an installation location which allows air
to freely flow through the air inlet and outlet (see section "Minimum clearances").
n Do not install the unit in the immediate vicinity
of devices which generate intensive thermal radiation. Installation in the vicinity of thermal radiation reduces the unit output.
n Only open the shut-off valves on the refrigerant
piping after installation is complete.
n Seal off open refrigerant piping with suitable
caps or adhesive strips to prevent the infiltra­tion of moisture and never kink or compress the refrigerant piping.
n Avoid unnecessary bends. This minimises the
pressure loss in the refrigerant piping and ensures that the compressor oil can flow back without obstruction.
n Make special preparations regarding the oil
return if the outdoor unit is located above the indoor unit (see section "Oil return measures").
n Add refrigerant if the basic length of the refrig-
erant piping exceeds 5 metres. For the quantity of additional refrigerant, refer to chapter "Adding refrigerant".
n Perform all electrical wiring in accordance with
applicable DIN and VDE standards.
n Ensure the electrical cables are properly con-
nected to the terminals. Otherwise there is a risk of fire.
n Use suitable fastening materials for the instal-
lation location of the units.

5.2 Selection of installation location

Indoor unit
The indoor unit is designed for horizontal wall installation underneath windows. However also be used in the upper wall area (max. 1.25 m above the floor). The unit is also designed for hori­zontal ceiling installation. Observe the condensate drainage in particular here.
Fig. 25: Horizontal positioning
Outdoor unit
The outdoor unit is designed for horizontal installa­tion on a base in outdoor areas. The installation site must be level, flat and firm. The unit should also be secured to prevent it from tipping over outdoor unit can be set up outside as well as inside a building. For external installation, please observe the following notes to protect the unit from the influence of the weather.
Rain
For floor or roof set-up, the unit should be installed with at least 10cm ground clearance. A floor bracket is available as an optional accessory.
Sun
The condenser on the outdoor unit emits heat. Exposure to sunlight further increases the temper­ature of the fins and reduces the heat released by the finned heat exchanger. The outdoor unit should be installed on to the north side of the building whenever possible. If necessary, take measures to provide sufficient shade (responsibility of cus­tomer). One possible solution is to build a small roofed area over the unit. These measures should not affect the flow of warm outlet air.
, it can
. The
24
Page 25
Wind
1
20 cm
1
2
1
K
3
W
3
If the unit is being installed in windy areas, ensure that the warm outlet air is discharged in the pre­vailing wind direction. If this is not the possible, it may be necessary to install a windbreak (to be pro­vided by the customer). Ensure that the windbreak does not adversely af
Fig. 26: Windbreak
1: Wind
Snow
The unit should be wall-mounted in areas of heavy snowfall. Installation should be at least 20cm above the expected level of snow to prevent snow from entering the outdoor unit. An optional wall bracket is available as an accessory
fect the air intake to the unit.
.
Fig. 27: Minimum clearance to snow
1: Snow
Installation inside buildings
n Ensure that heat can dissipate adequately
when placing the outdoor unit in cellars, lofts, adjoining rooms or halls (
n Install an additional fan with a rated flow com-
parative to that of the outdoor unit being installed in the room and which can compen­sate any additional pressure loss in ventilation ducts (Fig. 28).
n Comply with any regulations and conditions
fecting the statics of the building. If neces-
af sary, fit acoustic installation.
Fig. 28).
Fig. 28: Installation inside buildings
K: Cold fresh air W: Warm air 1: Outdoor unit

5.3 Installation materials

The indoor unit is attached to the wall by a wall bracket and 4 screws (to be provided by the cus­tomer).
2: Additional fan 3: Air shaft
The outdoor unit is attached by 4 screws and a wall bracket to the wall or fixed by a floor bracket to the ground.
25
Page 26
21 5
3 4
REMKO RXT series

5.4 Wall openings

n A wall opening of at least 70 mm diameter and
10 mm incline from the inside to the outside must be created.
o prevent damage to the lines, the interior of
n T
the wall opening should be padded or, for example, lined with PVC pipe (see figure).
n After installation has been completed, use a
suitable sealing compound to close off the wall opening, taking account of fire protection regu­lations (provided by the customer). Do not use cement or lime containing substances!
Fig. 29: Wall opening
1: Injection pipe 2: Control line 3: Condensate drainage line 4: Suction pipe 5: PVC pipe
26
Page 27

5.5 Fastening options for the indoor unit

1
2
3
3
4
5
20 ~ 25 mm
1
1
1
1
If wall-mounted, the indoor units are mounted with fastening hooks and hanger bolts, and if ceiling-mounted then with fastening hooks and threaded rods.
Fig. 30: Unit fastening with threaded rod
1: Unit mount 2: Threaded rod M10 3: Nut M10
4: Washer 5: Vibration damper (optional)
Fig. 31: Unit fastening
1: Unit mount
27
Page 28
1
1
2
2
1
1
3
3
4
REMKO RXT series
Fig. 32: Unit fastening without housing
1: Unit mount 2: Hanger bolts or threaded rods
3: Side part 4: Air inlet grill
28
Page 29
2
1
A
B
C
D
E
>1000mm
> 35mm
>35mm
> 35mm
A
1
2
3
1
A
B
2

5.6 Minimum clearances

Observe the minimum clearances to allow access for maintenance and repair work and facilitate optimum air distribution.
Minimum clearances, outdoor units RXT 525-1405 DC A
Fig. 33: Minimum clearances, outdoor units
1: Air inlet / 2: Air outlet
Measure-
ments
(mm)
A 300
T
RXT 525-1405 DC AT

5.7 Connection variants

The following connection variants can be used for the refrigerant, condensate and control lines.
Fig. 35: Connection variants
A: Refrigerant piping 1: Outlet on the wall, right 2: Outlet through the wall, right 3: Outlet on the wall, down
B 2000
C 600
D 200
E 400
Minimum clearances, indoor units RXT 525-1405 DC IT
Fig. 34: Minimum clearances, indoor units (all measurements in mm)
A: Wall installation / B: Ceiling installation
29

5.8 Oil return measures

If the outdoor unit is installed at a higher level than the indoor unit, suitable oil return measures must be taken. Usually every 7 metres of height difference.
Fig. 36: Oil return measures
A: Outdoor unit B: Indoor unit 1: 1 x oil pump bend in suction pipe to outdoor
unit every 7 metres of height dif 50 mm
2: Max. 10 m
, an oil pump bend is installed for
ference, radius:
Page 30
REMKO RXT series

6 Installation

6.1 Preparations for installation

Removing the air inlet grill
NOTICE!
Installation should only be performed by author­ised specialists.
1. Fold the air inlet grill forwards.
2. Remove the middle retainer by releasing the
two bars from the fastening.
3. Undo the lateral fastening screws and remove the grill.
4. After installation, all parts that were removed must be fitted again.
6.2

Installation of the indoor unit

Wall installation
The unit is attached by means of a wall bracket, taking account of the air outlet side located towards the top of the unit.
1. Mark the mounting points on the structurally permissible building sections according to the dimensions of the wall bracket.
2. If necessary of the housing.
3. Hook the unit on to the previously attached bracket.
4. Connect the refrigerant piping, electrical cables and condensate drainage line to the indoor unit as described below
5. Hang the indoor unit onto the wall bracket by tilting it back slightly and by pressing the bottom part of the unit against the bracket.
6. Check again that the unit is level.
, remove the break out opening
.
Ceiling installation
The unit is attached by means of the integrated ceiling bracket, taking account of the air outlet side located on the front of the unit.
1. Mark the mounting points on the structurally permissible building sections according to the dimensions of the wall bracket.
2. If necessary of the housing.
3. Hook the unit onto the four previously installed screws/threaded rods.
4. Fit the unit such that it is attached 5 mm lower in the connection area (air inlet) than on the air outlet side!
5. Connect the refrigerant piping, electrical cables and condensate drainage line to the indoor unit as described below
, remove the break out opening
.
6.3 Connection of
refrigerant piping
The refrigerant piping is connected on the back side of the units.
It may be necessary to fit a reducer or flared adapter to the indoor unit. These fittings are included with the indoor unit as an accessory kit. Once installed, the connections should be insu­lated to make them vapour diffusion proof.
NOTICE!
Installation should only be performed by author­ised specialists.
NOTICE!
The unit is factory filled with dry nitrogen for leak testing purposes. The pressurised nitrogen is released when the union nuts are undone.
The wall bracket for the units must be attached with suitable screws and anchors.
NOTICE!
Use only tools which are approved for use in an HVAC environment. (z. B.: bending pliers, pipe/ tubing cutters, de-burrers and flaring tools). Do not cut refrigerant pipes with a saw.
NOTICE!
All work must be carried out in a way that pre­vents dirt, particles, water etc. from entering, refrigerant lines!
30
Page 31
The following instructions describe the installation
2
1
of the cooling cycle and the assembly of the indoor unit and the outdoor unit.
1. The required pipe diameters are given in the table "T
2. Install the indoor unit and connect the refrig­erant piping as described in the operating manual for the indoor unit.
3. Use the wall or floor brackets to fit the out­door unit against structural parts approved to support the static load (refer to the installa­tion instructions for the brackets).
4. Ensure that structure-borne sound is not transferred to parts of the building. Use vibra­tion dampers to reduce the ef ture-borne sound!
5. Lay the refrigerant piping from the indoor unit to the outdoor unit. Ensure that the fasten­ings are adequate and if necessary appropriate oil return measures!
6. Remove the factory-fitted protective caps and union nuts on the connections. These should be used later in the installation process.
7. Before flanging the refrigerant piping, ensure that the union nut is fitted on the pipe.
8. Prepare the laid refrigerant piping as shown below (
9. V (Fig. 39).
10. First connect and hand-tighten the refrigerant piping to ensure it is correctly seated.
11. Then tighten the fittings with 2 appropriately­sized open-ended spanners. Use one spanner to counter the force when tightening the fitting (Fig. 40).
12. Use insulation hoses which are designed for this temperature range and are dif proof.
13. Observe the permitted bending radius for the refrigerant piping during installation. Never bend a pipe twice in the same place. Brittle­ness and cracking can result.
14. Apply appropriate heat insulation to the installed refrigerant piping, including con­nector
15. T for all subsequent refrigerant piping.
echnical data".
fects of struc-
, take
Fig. 37 and Fig. 38).
erify that the shape of the flange is correct
fusion
.
ake the same action at the shut-off valves
Label the refrigerant piping (injection and suc­tion pipes) as well as the associated electrical control lines of each interior unit with a letter Only connect the lines to their associated con­nections.
NOTICE!
Always pay attention to the af electrical lines and refrigerant piping! The con­nections of the individual circuits must not be mixed up. Mixing up the assignment of control lines and refrigerant piping can have fatal con­sequences (compressor damage)!
Commissioning of the individual circuits must be carried out successively.
Fig. 37: Deburring the refrigerant piping
1: Refrigerant piping 2: Deburrer
filiation of the
.
31
Page 32
1
2
1
REMKO RXT series
Fig. 38: Flanging the refrigerant piping
1: Flanging tool
Fig. 39: Correct flange shape
Fig. 40: Tightening the fitting
1: Tighten with the first open-ended spanner 2: Counter with the second open-ended spanner
Pipe dimension in inches
1/4" 15-20
3/8" 33-40
1/2" 50-60
5/8" 65-75
3/4" 95-105
Tightening torque in Nm

6.4 Additional notes on connecting the refrigerant piping

n When combining the outdoor unit with some
indoor units, the procedure for connecting the refrigerant piping may dif vided reducer or expansion fittings to the indoor unit.
n If the basic length of the connecting line
exceeds 5m, add refrigerant when commis­sioning the system for the first time (see chapter "Adding refrigerant").
fer. Install the pro-
NOTICE!
A flare connection may only be established out­side the room. Detachable, reusable connec­tions are not permissible inside!
32
Page 33

6.5 Leak testing

Once all the connections have been made, the pressure gauge station is attached to the Schrader valve as follows (if fitted):
red = small valve = high pressure
blue = large valve = suction pressure
Once the connection has been made successfully the leak test is carried out with dry nitrogen.
Leak testing involves spraying a leak detection spray onto the connections. If bubbles are visible, the connections have not been made properly. In that case, tighten the connection or, if necessary, create a new flange.
After completing a successful leak test, the excess pressure in the refrigerant piping is removed and a vacuum pump with an absolute final partial pres­sure of min. 10 mbar is used to remove all of the air and empty the pipes. Any moisture present in the pipes will also be removed.
NOTICE!

6.6 Adding refrigerant

The units contain a basic quantity of refrigerant. In addition, an additional amount of refrigerant must be added for refrigerant piping lengths exceeding 5 metres per circuit. Refer to the following chart:
Up to and
,
RXT 525-1405
DC
CAUTION!
ear protective clothing when handling refrig-
W erant.
DANGER!
Only refrigerant in a liquid state may be used to fill the cooling cycle!
incl. 5m
0 g/m 30 g/m
From 5m to max. length
A vacuum of at least 20 mbar must be pro­duced!
The time required to generate the vacuum is dependent on the final pressure pipe volume of the indoor units and the length of the refrigerant piping. However minutes. Once any foreign gases and humidity have been completely extracted from the system, the valves on the pressure gauge station are closed and the valves on the outdoor unit are opened as described in the "Commissioning" sec­tion.
, the process will take at least 60
NOTICE!
Check the overheating to determine the refrig­erant fill quantity
NOTICE!
The escape of refrigerant contributes to climatic change. In the event of escape, refrigerant with a low greenhouse potential has a lesser impact on global warming than those with a high greenhouse potential. This unit contains refrigerant potential of 675. That means the escape of 1 kg of this refrigerant has an effect on global warming that is 675 times greater than 1 kg CO2, based on 100 years. Do not conduct any
work on the refrigerant circuit or dismantle the unit - always enlist the help of qualified experts.
.
with a greenhouse
33
Page 34
3
2
4
9
5 5
11
100
6
8
7
10 10
12 12
1
min. 2%
min. 2%
REMKO RXT series
7 Condensate drainage
connection and safe drainage
n The condensate drainage line should have an
incline of min. 2%. This is the responsibility of the customer proof insulation.
n When operating the unit at outside tempera-
tures below 4 °C, ensure the condensate drainage line is laid to protect it against frost. The lower part of the housing and condensate tray is also to be kept frost free in order to ensure permanent draining of the condensate. If necessary, fit a pipe heater.
n Following installation, check that the conden-
sate run off is unobstructed and ensure that the line is durably leak tight.
. If necessary, fit vapour-diffusion-
Fig. 41: Condensate drainage, seepage of conden­sate and strip foundation (cross-section)
1: Outdoor unit 2: Leg 3: Condensate collection tray 4: Floor bracket 5: Reinforced strip foundation
HxWxD = 300x200x800mm 6: Gravel layer for seepage 7: Condensate drainage heating 8: Drainage channel 9: Conduit for refrigerant piping and electrical
connecting line (temperature-resistant up to at
least 60°C) 10: Frost line 11: Drainage pipe 12: Soil
Condensate drainage connection
If the temperature falls below the dew point, con­densation will form on the finned condenser during
heating mode.
A condensate tray should be installed on the underside of the unit to drain any condensate.
Fig. 42: Condensate drainage connection IT on the wall
Fig. 43: Condensate drainage connection IT on the ceiling
34
Page 35
Safe drainage in the event of leakages
The REMKO oil separator OA 2.2 fulfils the fol­lowing list of requirements from regional regula­tions and laws.
NOTICE!
Local regulations or environmental laws, for example the German W (WHG), can require suitable precautions to pro­tect against uncontrolled draining in case of leakage to provide for safe disposal of escaping refrigerator oil or hazardous media.
NOTICE!
If condensate is removed via a duct in accord­ance with DIN EN 1717, ensure that any micro­biological contamination present on the waste­water side (bacteria, fungi, viruses) cannot enter the unit connected to it.
ater Resource Law
35
Page 36
2
1
2
1
REMKO RXT series

8 Electrical wiring

8.1 General notes

A mains cable must be installed as the power supply to the outdoor unit and a control line to the indoor unit, with appropriate protection.
DANGER!
All electrical installation work is to be performed by specialist companies. Disconnect the power supply when connecting the electrical terminals.
WARNING!
All electric lines are in accordance VDE regula­tions to dimension and to lay
NOTICE!
The electrical connection for the units must be made at a separate feedpoint with a residual current device in accordance with local regula­tions and should be laid out by an electrician.
.
Make the connection as follows:
1. The connection terminal block is located on the right inside the unit (
2. Connect the unit to the control line from the outdoor unit. See “Electrical wiring diagram”.
3. Re-assemble the unit.
Fig. 44).
e recommend using shielded wires for the
W control lines.
Check all plugged and clamped terminals to verify that they are seated correctly and make permanent contact. T
ighten as required.

8.2 Connecting the indoor unit

The unit requires a six-wired control line from the indoor unit to the outdoor unit.
e recommend installing a main / repair switch
n W
on the building close to the indoor unit. This is the responsibility of the customer.
n Power is supplied to the outdoor unit, the
indoor unit is supplied via the control line from the outdoor unit to the indoor unit.
n The terminal blocks for establishing the con-
nections are located inside the unit.
n If an optional condensate pump is used as an
accessory in conjunction with the unit, it may be necessary to install an additional relay with a higher contact rating after the switch-off con­tact on the pump to switch off the compressor.
Fig. 44: Connecting the indoor unit
1: Electrical connection (terminal box) 2: Connection of refrigerant lines
36
Page 37
A B
230V/1~/50 Hz
L N 1(L) 2(N) S L N PE
PE
S
PE
1
2

8.3 Outdoor unit connection

Proceed as follows to connect the line:
1. Remove the side-panel cover
2. Choose the cable cross-section in accord-
ance with the relevant specifications.
3. Connect the lines as shown on the electrical connection diagram.
.

8.4 Electrical wiring diagram

Connection RXT 525-685 DC
4. Fix the line in the strain relief and re-
assemble the unit.
Fig. 45: Outdoor unit connection
Fig. 46: Electrical wiring diagram
A: Outdoor unit RXT 525-685 DC AT B: Indoor unit RXT 525-685 DC IT
1: Mains cable 2: Communication lines
37
Page 38
A
B
400V/3~/50 Hz
L1 L2 L3 N
S 2(N) 1(L)
1(L) 2(N) S
1
2
REMKO RXT series
Connection RXT 1055-1405 DC
Fig. 47: Electrical wiring diagram
A: Outdoor unit RXT 1055-1405 DC AT B: Indoor unit RXT 1055-1405 DC IT
1 Power supply cable 2: Communication lines
38
Page 39

8.5 Electrical drawings

ALARM
CN33
T2
T1
CN6
4
CN5
CN9
X Y E
To CCM Comm.Bus
HB HA
CN45
WIRE
CONTROLLER
Y/G
CN18
J7
CN23
ON/OFF
CN43
Y/G
WHITE
WHITE (GRAY)
CN4
P1
P2
BLACK
BROWN
M
5
3
CN2 Cn1
CN3
Y/G
L
N S
REACTOR
CON2
RED
RED
DC MOTOR
DRIVER
MODLE
CON1
FAN1
3
3
M
4
CN1
CN15
CN34
DC FAN
3
Y/G
CN13
M
2
Y/G
MAGNETIC
RING
CN40
WIRE
CONTROLLER
4
MAGNETIC RING
DISPLAY
BOARD
WIRE
CONTROLLER
10
CN10
5
Y/G
12
13
3
4
5
8
7
A
6
14 15
1
B
Indoor units RXT 525-1405 DC IT
Fig. 48: Electrical drawings IT
A: Control board B: Display circuit board 1: AC fan motor 3: DC fan motor 4: Potential-free external contact on/off 5: Potential-free alarm contact 6: MCC-1 controller/SC-1 connection (optional)
7: Communication line to outdoor unit 8: Optional connection external fan motor 12: Connection of condensate pump 13: Wired remote control connection (optional) 14: Temperature probe, evaporator 15: Temperature probe, room temperature
39
Page 40
1(L) 2(N)
S L N
4/5
2/3/4/5
3 5/6
CN 3
CN 1
CN 2
CN 16
CN 60
CN 17
CN 15
CN 25
CN 1A
CN 9
CN 32
CN 30 CN 29 CN 28
CN 21
CN 7
CN 31
BURDBK
U W
V
A
2
1
5
6
7
8
9
10
11
1213
3
4
14
REMKO RXT series
Outdoor unit RXT 525 DC AT
Fig. 49: Electrical drawings
A: Control board 1: Compressor 2: Transformer 3: Connecting line to the indoor unit 4: Power supply 5: 4-way reversing valve 6: Crankcase heating 7: Condensate tray heating
8: Capacitor 9: AC fan 10: Electronic E-valve 11: DC fan motor 12: Air inlet temperature probe 13: Temperature probe for condenser outlet 14: Temperature probe for heat gas line
---: Optional
40
Page 41
Outdoor unit RXT 685 DC AT
A
1
4
5
6
7
8
9
10
1112
2
3
13
BURDBK
1(L) 2(N)
S L N
4/5
2/3/4/5
3 5/6
CN 6
CN 7
CN 8
CN 60
CN 16
CN 19
CN 5
CN 3
CN 17
CN 414
CN 18
U W
V
CN 2
CN 21
U V W
Fig. 50: Electrical drawings
A: Control board 1: Compressor 2: Connecting line to the indoor unit 3: Power supply 4: 4-way reversing valve 5: Crankcase heating 6: Condensate tray heating 7: Capacitor
8: AC fan 9: Electronic E-valve 10: DC fan motor 11: Air inlet temperature probe 12: Temperature probe for condenser outlet 13: Temperature probe for heat gas line
---: Optional
41
Page 42
BU RD
2
U
W
V
3
5
2
3
3 3
1
2(N) S
L1 L2
L3
N
2
MM
CN23 CN22
CN708A
CN707A
CN24 CN501
CN506 CN503 CN504 CN507 CN502
CN508
CN715
CN714
CN713
CN709
CN706
CN705
CN301
CN710CN777CN702CN703CN704
CN13
CN3
M
CN1 CON1
CON2
FAN1
FAN2
5
M
M M
RD
RD
BK
BK
WH
WH
WH
RD
YE
RD
BU
BU
RD
BK
RD
WH
BU
BU
WH
RD
BU
BU
A
4
5
6
7
8
9
10
11
12
3
13
1
2
44
14
15
16
17
18
19
20
21
REMKO RXT series
Outdoor unit RXT 1055-1405 DC AT
Fig. 51: Electrical drawings
A: Control board B: Inverter board 1: Klixon 2: Low pressure switch 3: High pressure switch 4: Air inlet temperature probe 5: Temperature probe for condenser outlet 6: Temperature probe for heat gas line 7: Condensate tray heating
8: Crankcase heating 9: 4-way reversing valve 10: Communication line to indoor unit 11: Power supply cable 12: Supply line to indoor unit 13: DC fan motor 14: Compressor 15: Transformer
---: Optional
42
Page 43

9 Before commissioning

After leak testing has been successfully com­pleted, connect the vacuum pump via the pressure gauge station to the valve connections on the out­door unit (see chapter "Leak testing") and create a vacuum.
Perform the following checks prior to putting the unit into operation for the first time and after any work on the cooling cycle. Record the results in the commissioning report:
n Check all refrigerant piping and valves for leak-
tightness using leak detection spray or soapy water
.
n Check the refrigerant piping and insulation for
damage.
n Check the electrical connection between the
indoor unit and the outdoor unit for correct polarity.
n Check that all fastenings, mountings, etc. are
firm and at the correct level.

10 Commissioning

NOTICE!
Commissioning should only be performed by specially trained personnel and documented after the certificate has been issued. Observe the operating manuals for the indoor unit and outdoor unit when commissioning the entire system.
Once all the components have been connected and tested, the system can be put into operation. A functional check should be performed to verify its correct function and identify any unusual operating behaviour prior to handing it over to the operator
NOTICE!
Check that the shut-of are tight after carrying out any work on the cooling cycle. Use appropriate sealant products as necessary.
f valves and valve caps
.
Functional checks and test run
Check the following points:
n Leak-tightness of the refrigerant piping. n Compressor and fan running smoothly. n In cooling mode, cold air output by the indoor
unit, and warm air output by the outdoor unit.
n Function test of the indoor unit and all program
sequences.
n Check of the surface temperature of the suc-
tion pipe and that the vaporiser is not over­heating. To measure the temperature, hold the thermometer to the suction pipe and subtract the boiling point temperature reading on the pressure gauge from the measured tempera­ture.
n Record the measured temperatures in the
commissioning report.
43
Page 44
REMKO RXT series
Function test of the cooling and heating modes
1. Remove the protective caps from the valves.
2. Start the commissioning procedure by briefly
opening the shut-of unit until the pressure gauge indicates a pressure of approx. 2 bar.
3. Check all connections for leaks with leak detection spray and suitable leak detectors.
4. If no leaks are found, fully open the shut-of valves by turning them anti-clockwise using a spanner. If leaks are found, remedy the faulty connection. It is imperative that the vacuum creation and drying steps are repeated.
5. Activate the main circuit breaker or fuse.
6. Use the remote control to switch on the unit
and select the cooling mode, maximum fan speed and lowest target temperature.
7. Check the overheating, outside, inside, outlet and vaporisation temperatures and record the measured values in the commissioning report. Check the correct function and set­tings of all regulation, control and safety devices.
8. Check the unit control system using the func­tions described in the chapter "Operation". T
imer, temperature setting, fan speeds and switching to ventilation or dehumidification mode.
9. Check the correct function of the condensate drainage line by pouring distilled water into the condensate tray recommended for pouring the water into the condensate tray.
10. Switch the indoor unit to heating mode.
11. During the test run, check the functionality of
all of the previously described safety devices.
12. Record the measured values into the com­missioning report and familiarise the operator with the system.
13. Remove the pressure gauge. Check that seals have been fitted in the sealing caps.
14. Re-install all disassembled parts.
f valves on the outdoor
f
. A bottle with a spout is

11 Shut-down

Temporary shut-down
1. Allow the indoor unit to run for 2 to 3 hours in
air circulation mode or in cooling mode at the maximum temperature setting in order to remove any residual moisture from the unit.
2. Shut down the system using the remote con­trol.
3. Switch of
4. Check the unit for visible signs of damage
and clean it as described in the chapter "Care and maintenance"
Permanent shut-down
Ensure that equipment and components are dis­posed of in accordance with the applicable regula­tions, e.g. through authorised disposal and recy­cling specialists or at collection points.
REMKO GmbH & Co. KGor your contractual partner will be pleased to provide a list of certified firms near you.
f the voltage supply to the unit.
44
Page 45

12 Troubleshooting, customer service and fault analysis

12.1 Troubleshooting and customer service

The unit and components are manufactured using state-of-the-art production methods and tested several times to verify their correct function. However detailed in the list below. For systems with an indoor unit and outdoor unit, refer to the chapter "Trouble­shooting and customer service" in both operating manuals. Please inform your dealer if the unit is still not working correctly after all function checks have been performed!
Operational malfunctions
Malfunction Possible causes Checks Remedial measures
, if malfunctions should occur, please check the functions as
The unit does not start or switches itself of
f
Power failure, under­voltage, defective mains fuse / main switch in OFF position
Damaged power supply Does all other elec.
Wait time after switching on is too short
Temperature outside operating range
Electrical surges caused by thunderstorms
Malfunction of the external condensate pump
High-pressure / low-pres­sure switches have trig­gered
Does all other electrical equipment function cor­rectly?
equipment function cor­rectly?
Have approx. 5 minutes elapsed since the restart?
Are the fans in the indoor unit and outdoor unit working correctly?
Have there been light­ning strikes in the area recently?
Has the pump shut down due to a malfunction?
Check refrigerant pres­sure and look for leaks if necessary
Check the voltage and if necessary come back on
Repair by specialist firm
Schedule longer wait times
Observe temperature ranges of indoor unit and outdoor unit
Switch off the mains breaker and switch it back on. Have it inspected by a specialist
Check and if necessary clean the pump
Rectify leakage and re­start
, wait for it to
Transmission distance too far / receiver af by interference
Defective remote control Is the unit running in
Receiver or transmitter unit exposed to exces-
The unit does not respond to the remote control
45
sive solar radiation
Electromagnetic fields are interfering with trans­mission
Key in remote control jammed / two buttons pressed at same time
Batteries in remote con­trol are flat
fected
Does the indoor unit beep when pressing a key?
manual mode?
Does it function correctly in the shade?
Does it function after removing potential sources of interference?
Does the “Transmitting” symbol appear on the display?
Have new batteries been inserted? Is the display incomplete?
Reduce the distance to less than 6 m or change position
Replace the remote con­trol
Place the receiver and/or transmitter unit in the shade
Signal is not transmitted when interference sources are operational
Release the key / only press one key
Insert new batteries
Page 46
REMKO RXT series
Malfunction Possible causes Checks Remedial measures
The unit is running but only provides reduced or no cooling or heating capacity
Filter is dirty / air inlet / outlet opening is blocked by debris
Windows and doors open. Heating / cooling load has increased
Neither cooling nor heating mode has been set
Fins on outdoor unit blocked by foreign objects
Leaking cooling cycle Are there signs of frost
Outdoor unit iced up Check outdoor unit. Has
Drainage pipe on collec­tion container clogged / damaged
Have the filters been cleaned?
Have structural / usage modifications been made?
Does the cooling symbol appear on the display?
Is the fan on the outdoor component running? Are the fins unobstructed?
on the exchanger fins of the indoor unit?
the cassette probe on the outdoor unit been correctly positioned?
Can the condensate drain of obstruction?
f without any
Clean the filters
Close windows and doors / install additional units
Correct the settings for the unit
Check the fan or winter fan speed control, reduce the air resistance
Repair by specialist
De-ice and fit the probe at the point where the most ice forms
Clean the drainage pipe and collection container
Condensate discharge on unit
NOTE
Faulty external conden­sate pump or float
Condensate has not drained away and has collected in the conden­sate drainage line
Condensate does not drain of
Float is stuck or jammed due to excessive dirt
f
Is the collection tray full of water and the pump not running?
Is there an incline on the condensate drainage line? Check there is no blockage in the pipe.
Are the condensate drainage lines unblocked and is there a steady incline? Are the conden­sate pump and liquid level switch functioning correctly?
Are the LEDs on the receiver unit of the indoor unit flashing?
Call out a specialist to replace the pump
Route the condensate drainage line with an incline and clean
Route the condensate drainage line with an incline and clean it. If the liquid level switch or the condensate pump is defective, have them replaced
Should be cleaned by specialist firm
If the outdoor unit makes noises at low outside temperatures, even although it is switched off, this is not a malfunction. This is the winding of the compressor being run briefly in order to heat up the oil within it and also to guarantee the viscosity at low ambient temperatures. If you do not use the unit in the winter then you can switch off the breaker will be required!
. Switch it back on again at least 12 hours before the next time that the unit
46
Page 47
Malfunction indicated by flashing code RXT 525-1405 DC
Number
Error description
EEPROM error, indoor unit 1 OFF E0
Communication error between indoor unit and outdoor unit 2 OFF E1
Evaporator fan motor speed control not OK 4 OFF E3
Room air temperature probe faulty 5 OFF E4
Evaporator temperature probe faulty 6 OFF E5
No cooling capacity after 30 minutes 7 OFF EC
Condensate pump liquid level switch triggered 8 OFF EE
Safety shut-down due to increased power consumption 1 ON F0
of flashes
per
second)
LED timer
Error code
Outdoor unit air inlet temperature probe faulty 2 ON F1
Condenser outlet temperature probe faulty 3 ON F2
Temperature probe for heat gas line faulty 4 ON F3
EEPROM error, outdoor unit 5 ON F4
Condenser fan speed control not OK 6 ON F5
Suction pipe temperature probe in AT faulty 7 ON F6
Inverter error 1 FLASHES P0
Over/undervoltage error 2 FLASHES P1
Safety shut-down compressor excess temperature 3 FLASHES P2
Safety shut-down due to low outside temperature 4 FLASHES P3
Compressor control faulty 5 FLASHES P4
Mode conflict 6 FLASHES P5
Low pressure alarm 7 FLASHES P6
47
Page 48
YES
REMKO RXT series
Probe resistance
Indoor unit probe, evaporator; indoor unit probe, ambient air
Temperature [°C] Resistance [kW]
0 35.20
5 26.88
10 20.72
15 16.12
20 12.64
25 10.00
30 7.97
35 6.40

12.2 Indoor unit fault analysis

Error code: E0 / F4
Reason: The control board of the outdoor unit or indoor unit cannot read the unit memory
(EEPROM)
Cause:
Switch off voltage, switch on again 2 minutes
later
Replace the circuit boards of the outdoor unit
and indoor unit in turn, in order to locate the
n Installation error n Control boards of outdoor unit or indoor unit defective
. Is the error still present?
defective EEPROM
48
Page 49
Error code: E1
YES
NO
YES YES
YES
NO
NO
YES
NO
Reason: The indoor unit does not receive a signal from the outdoor unit within 110 seconds.
Cause:
Switch off voltage, switch on again 2 minutes
later
Measure the voltage between the “S” and “N”
terminals of the outdoor unit. Is the measured
Check electrical connections in the outdoor
n Electrical connection not configured correctly n Control boards outdoor unit or indoor unit defective
. Is the error still present?
value positive?
unit. Are they OK?
Is the transformer OK?
Check electrical connections in the indoor unit.
Are they OK?
Replace the control boards of the indoor unit. Is
the fault remedied?
Replace the control boards of the outdoor unit
Replace the transformer
Replace the control boards of the outdoor unit.
Is the fault remedied?
Replace the control boards of the indoor unit
49
Page 50
NO
YES
NO
YES
NO
YES
NO
YES
NO
REMKO RXT series
Error code: E3 / F5
Reason: If the fan speed of the indoor unit/outdoor unit falls below 300 rpm, the unit switches off
and the display shows error code E3 or E5
Cause:
Switch off voltage, switch on again 2
minutes later
De-energise the unit and attempt to
turn the fan wheel by hand. Does it
Check the electrical connections.
Are these correctly implemented?
Measure the voltage at the corre-
sponding connector plug on the con-
trol board (see section
dure’ on page 51). Does the
measured voltage lie within the toler-
n Electrical connection faulty n Evaporator fan wheel defective n Evaporator fan motor defective n Control board faulty
. Is the error still
present?
rotate freely?
Ä
‘Proce-
ance range?
The unit operates normally.
Check the motor and the fan
wheel bearing, and replace the
defective parts.
Correctly establish the electrical
connection
Replace the control board.
Replace the fan motor. Is the fault
remedied?
50
Page 51
Procedure
1 3 4 5 6
DC fan motor of the indoor unit (control chip is installed in the motor):
Switch on the voltage to the unit. In standby mode, measure the unit between terminals 1-3 and 4-3 of the connector plug. Check the measured values against those listed in the table below problem with the control board and it must be replaced.
. If these differ, there is a
Fig. 52: Motor measurements
Terminal Colour Voltage
1 Red 280V~380 V
2 --- ---
3 Black 0 V
4 White 17-17.5V
5 Yellow 0~5.6V
6 Blue 17-17.5V
DC fan motor of the outdoor unit (control chip is installed in the motor):
Measure the resistance between terminals 1-3 and 4-3. This should be roughly identical. If the resistance deviates significantly, assume that the motor is defective and must be replaced.
51
Page 52
YES
JOO
NO YES
JOO
NO
REMKO RXT series
Error code: EC
Reason: The evaporator probe T2 measures the actual value with the compressor start and takes
this as the reference value T has not dropped by 2 °C for at least 4 seconds then the system assumes that the refrig-
erant is low error code "EC".
. The measurement is performed a total of 3 times before the display shows the
. If, 5 minutes after the compressor start, the value T
Start
Start
Cause:
Switch off voltage, switch on again 2 minutes
later. Is the error still present?
Check whether the indoor unit blows out cold
Check the cooling circuit for leaks. Leaks
Check the cooling circuit for any blockages. Are
the shut-of
n Refrigerant low or cooling circuit blocked n Evaporator probe T2 defective n Indoor unit control board defective
.
air
found?
f valves on the outdoor unit open?
Check the position and function of the evapo-
rator probe T2. Is it correctly seated and with
the correct resistance?
Exchange the control boards of the indoor unit.
Remedy leaks and put the unit back into opera-
tion.
52
Page 53
Error code: E4 / E5 / F1 / F2 / F3
NO
YES
NO
YES
Reason: If the test voltage of the probes is lower than 0.06 V or higher than 4.94 V then the display
shows the error code of the corresponding probe.
Cause:
Check the connecting cable between the con­trol board and the temperature probe. Is it OK
Check the probe for correct resistance,
depending on the temperature (see resistance
Replace the corresponding control board.
n Electrical connection faulty n T
emperature probe defective
n Control board defective
and correctly connected?
table)
Establish a proper connection.
Replace the probe.
Fig. 53: Check the probes
53
Page 54
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
REMKO RXT series
Error code: F0
Reason: Safety shutdown due to overly high current consumption of individual unit components
Cause:
Check the supply voltage. Is this correct?
Check the cooling circuit for any blockages. Is
Check the winding resistances of the com-
Check the electrical connections. Are these cor-
n Faulty power supply n Cooling circuit blocked n Faulty control board n Electrical connections faulty n Compressor defective
the cooling circuit OK?
pressor
. Are they OK?
rectly implemented?
Switch the unit off and ensure correct supply
voltage.
Remove the blockage (shut-off valve open?)
Replace the compressor.
Replace or correct the electrical connections.
Does the transformer operate fault-free?
Replace the outdoor unit.
Replace the transformer or control boards of
the outdoor unit.
54
Page 55
Error code: P0
JOO
NO
NO
YES
NO
YES
NO
YES
Reason: If the power supply to the compressor controller is faulty, the display shows the error code
“P0” and the unit switches of
f
Cause:
Check the connecting cables between the con-
trol board and compressor? Are they faulty?
Check the inverter controller (see section
Ä
‘Check the inverter controller’ on page 55).
Check the condenser fan motor. Is it working
Check the winding resistances of the com-
n Electrical connection faulty n Faulty control board n Condenser fan motor defective or blocked n Compressor defective
Fault eliminated?
correctly?
pressor
. Are they OK?
Establish a correct connection between the
control board and compressor
Replace the control board.
See troubleshooting fault F5
Replace the compressor.
.
Exchange the control boards of the outdoor
unit.
Check the inverter controller
Switch off the power supply to the unit. Wait until the capacitors are fully discharged and disconnect the com­pressor from the control board.
Check the resistances at the outputs of the control board with the aid of a digital voltmeter as follows:
Voltmeter Normal resistance
(+) Red (-) Black
U
V
N
W
(+) Red
¥
(multiple MW)
55
Page 56
NO
YES
NO
YES
NO
YES
NO
YES
REMKO RXT series
Error code: P1
Reason: Overvoltage or undervoltage protection has tripped
Cause:
Check the power supply. Is the supply voltage
Check the electrical connections. Are they OK?
Switch the power on and put the unit into
standby mode. Measure the voltage on the
board, at contacts "P" and "N". This should be
approx. 310 V
the unit. The voltage between "P" and "N"
should now be between 220-400V. Is the cor-
Check the transformer. Is a defect present?
n Faulty supply voltage n Refrigerant low or cooling circuit blocked n Faulty control board
correct?
, 340 V or 380 V DC. Now start
rect voltage applied?
Switch the unit off and have the power supply
checked/corrected.
Replace the electrical connections.
Replace the control board.
Replace the control board.
Replace the transformer.
56
Page 57
Error code: P2 (with units with a thermal contact)
JOO
NO
YES
NO
YES
NO
YES
YES
NO
JOO
Reason: If the test voltage of the thermal contact does not lie at 5 V, then the display shows the
error message “P2”
Cause:
Check the air flow
volumes of the
indoor unit and out-
door unit. Are they
blocked or dirty?
Switch off the power
supply to the unit
and switch it on
again after 10 mins.
Does the unit start
up?
Check the tempera-
ture of the com-
pressor
heated up?
n Faulty supply voltage n Refrigerant low or cooling circuit blocked n Faulty control board
. Has it
Clean the filter or heat exchanger and ensure a sufficient air flow volume.
Check the thermal contact. Is it correctly connected?
Measure the resistance of the thermal contact.
Is it 0?
Connect it correctly.
Check the cooling
circuit. Is it OK?
Replace the thermal
contact.
Replace the control board of the outdoor unit.
57
Page 58
JOO
NO
NO
YES
NO
YES
NO
YES
1
REMKO RXT series
Error code: P4
Reason: Safety shutdown of inverter controller. Internal system monitoring triggered (e.g. communi-
cation problem between board and compressor
, the compressor speed is not OK)
Cause:
Check the electrical connection between the
control board and compressor
Check the inverter controller. Is this functional?
Check the condenser fan motor. Is it OK?
Check the winding resistances of the com-
n Faulty electrical connections n Inverter regulation on board defective n Condenser fan motor defective n Compressor defective n Control board defective
. Are these cor-
rectly implemented?
pressor
. Are they OK?
Establish a proper connection.
Replace the control board.
Follow the instructions for troubleshooting fault
F5
Replace the compressor
Replace the control boards of the outdoor unit.
Check individual components
Check the temperature probes
Disconnect the temperature probe from the control board and measure the resistance on the plug's contacts.
1: Multimeter
Error code: dF
Reason: The unit is in heating mode and the outdoor unit is being defrosted. After the defrost phase,
the indoor unit automatically switches back to the last operating mode.
58
Page 59

12.3 Resistances of the temperature probes

Probe T1, T2, T3 and T4
Temp.
(°C)
-20 115.27 12 18.72
-19 108.15 13 17.80
-18 101.52 14 16.93
-17 96.34 15 16.12
-16 89.59 16 15.34
-15 84.22 17 14.62
-14 79.31 18 13.92
-13 74.54 19 13.26
-12 70.17 20 12.64
-11 66.09 21 12.06
-10 62.28 22 11.50
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Temp.
(°C)
44 4.39 79 1.21
45 4.21 80 1.17
46 4.05 81 1.14
47 3.89 82 1.10
48 3.73 83 1.06
49 3.59 84 1.03
50 3.45 85 1.00
51 3.32 86 0.97
52 3.19 87 0.94
53 3.07 88 0.91
54 2.96 89 0.88
55 2.84 90 0.85
56 2.74 91 0.83
57 2.64 92 0.80
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
-9 58.71 23 10.97
-8 56.37 24 10.47
-7 52.24 25 10.00
-6 49.32 26 9.55
-5 46.57 27 9.12
-4 44.00 28 8.72
-3 41.59 29 8.34
-2 39.82 30 7.97
-1 37.20 31 7.62
0 35.20 32 7.29
1 33.33 33 6.98
2 31.56 34 6.68
3 29.91 35 6.40
4 28.35 36 6.13
5 26.88 37 5.87
6 25.50 38 5.63
58 2.54 93 0.78
59 2.45 94 0.75
60 2.36 95 0.73
61 2.27 96 0.71
62 2.19 97 0.69
63 2.11 98 0.67
64 2.04 99 0.65
65 1.97 100 0.63
66 1.90 101 0.61
67 1.83 102 0.59
68 1.77 103 0.58
69 1.71 104 0.56
70 1.65 105 0.54
71 1.59 106 0.53
72 1.54 107 0.51
73 1.48 108 0.50
7 24.19 39 5.40
8 22.57 40 5.18
9 21.81 41 4.96
10 20.72 42 4.76
11 19.69 43 4.57
59
74 1.43 109 0.48
75 1.39 110 0.47
76 1.34 111 0.46
77 1.29 112 0.45
78 1.25 113 0.43
Page 60
REMKO RXT series
Temp.
(°C)
114 0.42 127 0.30
115 0.41 128 0.29
116 0.40 129 0.28
117 0.39 130 0.28
118 0.38 131 0.27
119 0.37 132 0.26
120 0.36 133 0.26
121 0.35 134 0.25
122 0.34 135 0.25
123 0.33 136 0.24
124 0.32 137 0.23
125 0.32 138 0.23
126 0.31 139 0.22
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Temp.
(°C)
16 82.54 51 18.96
17 78.79 52 18.26
18 75.24 53 17.58
19 71.86 54 16.94
20 68.66 55 16.32
21 65.62 56 15.73
22 62.73 57 15.16
23 59.98 58 14.62
24 57.37 59 14.09
25 54.89 60 13.59
26 52.53 61 13.11
27 50.28 62 12.65
28 48.14 63 12.21
29 46.11 64 11.79
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Probe T5
Temp.
(°C)
-20 542.7 -2 200.7
-19 511.9 -1 190.5
-18 483.0 0 180.9
-17 455.9 1 171.9
-16 430.5 2 163.3
-15 406.7 3 155.2
-14 384.3 4 147.6
-13 363.3 5 140.4
-12 343.6 6 133.5
-11 325.1 7 127.1
-10 307.7 8 121.0
-9 291.3 9 115.2
-8 275.9 10 109.8
-7 261.4 11 104.6
-6 247.8 12 99.69
-5 234.9 13 95.05
-4 222.8 14 90.66
-3 211.4 15 86.49
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
30 44.17 65 11.38
31 42.33 66 10.99
32 40.57 67 10.61
33 38.89 68 10.25
34 37.30 69 9.90
35 35.78 70 9.57
36 34.32 71 9.25
37 32.94 72 8.94
38 31.62 73 8.64
39 30.36 74 8.36
40 29.15 75 8.08
41 28.00 76 7.82
42 26.90 77 7.57
43 25.86 78 7.32
44 24.85 79 7.09
45 23.89 80 6.86
46 22.89 81 6.64
47 22.10 82 6.43
48 21.26 83 6.23
49 20.46 84 6.03
50 19.69 85 5.84
60
Page 61
Temp.
(°C)
86 5.66 109 2.86
87 5.49 110 2.78
88 5.32 111 2.70
89 5.16 112 2.63
90 5.00 113 2.56
91 4.85 114 2.49
92 4.70 115 2.42
93 4.56 116 2.36
94 4.43 117 2.29
95 4.29 118 2.23
96 4.17 119 2.17
97 4.05 120 2.12
98 3.93 121 2.06
99 3.81 122 2.01
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
100 3.70 123 1.96
101 3.60 124 1.91
102 3.49 125 1.86
103 3.39 126 1.81
104 3.30 127 1.76
105 3.20 128 1.72
106 3.11 129 1.67
107 3.03 130 1.63
108 2.94
61
Page 62
REMKO RXT series

13 Care and maintenance

Regular care and observation of some basic points will ensure trouble-free operation and a long service life.
This enables you to ensure the operational reli­ability of the plant at all times!
DANGER!
Prior to performing any work, ensure the equip­ment is disconnected from the voltage supply and secured to prevent accidental switch-on!
Care
n Ensure the unit is protected against dirt, mould
and other deposits.
n Only clean the unit using a damp cloth. Do not
use any caustic, abrasive or solvent-based cleaning products. Do not use a jet of water.
n Clean the fins on the unit prior to long shut-
down periods.
Maintenance
n It is recommended that you take out a mainte-
nance contract with an annual service from an appropriate specialist firm.
Type of task
Checks/maintenance/inspection
General
n For systems which operate year-round (e.g. in
server rooms), the maintenance intervals must be reduced accordingly
NOTICE!
Statutory regulations require an annual leak test for the cooling cycle dependant on the refrig­erant quantity. Inspection and documentation of the work performed is to be carried out by spe­cialist technicians.
Commis-
sioning Monthly
l
.
Half-
yearly Yearly
l
Check voltage and current
Check function of compressor/fans
Dirt on condenser/evaporator
Check the refrigerant volume
Check condensate drainage
Check insulation
Check moving parts
Sealing test for cooling cycle
1)
see note
Cleaning the housing
1. Disconnect the power supply to the unit.
2. Open the air inlet grill on the front side and
fold it forwards or backwards.
3. Clean the grill and cover with a soft, damp cloth.
4. Close the grill.
5. Switch the power supply back on.
l
l
l l
l
l
l
l
l
Air filter for indoor unit
Clean the air filter at intervals of no more than 2 weeks. Reduce this interval if the air is especially
.
dirty
l
l
l
l
l
l
1)
l
62
Page 63
Cleaning the filter
1. Disconnect the power supply to the unit.
2. Open the front side of the unit by folding the
grill down/forwards (
3. Pull the filter out in an upwards direction (Fig. 54).
4. Clean the filter with a commercially available vacuum cleaner so it is facing upwards (Fig. 55).
5. Dirt can also be removed by carefully cleaning with lukewarm water and mild cleaning agents ( should be face down.
6. If water is used, let the filter dry out properly in the air before fitting it back into the unit.
7. Carefully insert the filter locates correctly.
8. Close the front side as described above in reverse order
9. Switch the power supply back on.
10. Switch the unit back on.
.
Fig. 54).
. To do so, turn the dirty side
Fig. 56). The dirty side
. Ensure that it
Fig. 55: Cleaning with a vacuum cleaner
Cleaning the condensate pump (accessories)
The indoor unit may contain an optional integrated or separate condensate pump, which pumps out any accumulated condensate into higher posi­tioned drains.
Observe the care and maintenance instructions in the separate operating manual
Fig. 54: Fold the guard forwards
Fig. 56: Cleaning with lukewarm water
63
Page 64
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
30
25
26
27
28
29
REMKO RXT series

14 Exploded view and spare parts lists

14.1 Exploded view - Indoor unit RXT 525-685 DC

Fig. 57: Exploded view of the unit RXT 525-685 DC IT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
64
Page 65

14.2 Spare parts list - Indoor unit RXT 525-685 DC

IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)
No. Designation
1 Air inlet grill
2 Front panel
3 Evaporator
4 Temperature probe, evaporator
5 Side covering, left
6 Wall bracket, left
7 Fan wheel
8 Fastening protection
9 Display board
10 Air filter
11 Air outlet fins
12 Housing
TANT!
13 Wall bracket, right
14 Fan motor
15 Fin motor
16 Fin motor (vertical)
17 Condensate tray
18 Infrared remote control
19 Inverter module
20 Temperature probe, indoor air
21 Transformer
22 Control board
23 E-box cover
24 Side covering, right
25 Air outlet fin (vertical)
26 Fan casing (rear)
27 Fan casing (front)
28 Fan motor mount
29 Fan motor mounting plate
30 Cooling fin
65
Page 66
1
1
2
3
4
5
6
7
8
9
10
11
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
33
32
REMKO RXT series

14.3 Exploded view - Indoor unit RXT 1055-1405 DC

Fig. 58: Exploded view of the unit RXT 1055-1405 DC IT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
66
Page 67

14.4 Spare parts list - Indoor unit RXT 1055-1405 DC

No. Designation
1 Air inlet grill (large)
2 Air inlet grill (small)
3 Front panel
4 Evaporator
5 Temperature probe, evaporator
6 Side covering, left
7 Wall bracket, left
8 Fan wheel
9 Fastening protection
10 Display board
11 Air filter (large)
12 Air filter (small)
13 Air outlet fins
14 Housing
15 Wall bracket, right
16 Fan motor
17 Fin motor (vertical)
18 Condensate tray
19 Infrared remote control
20 Inverter module
21 Temperature probe, indoor air
22 Transformer
23 Control board
24 E-box cover
25 Side covering, right
26 Air outlet fin (vertical)
27 Fan casing (rear)
28 Fan casing (front)
29 Fan motor mount
30 Fan motor mounting plate
31 Cooling fin
32 Fin motor
33 Refrigerant connections cover
67
Page 68
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
REMKO RXT series

14.5 Exploded view - Outdoor unit RXT 525 DC

Fig. 59: Exploded view of the unit RXT 525 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
68
Page 69

14.6 Spare parts list - Outdoor unit RXT 525 DC

IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)
No. Designation
1 Cover panel
2 Protection grid, front wall
3 Front panel
4 Fan blade
5 Fan motor
6 Fan motor mounting plate
7 Corner panel, left
8 Condenser
9 Air inlet temperature probe
10 Electronic injection valve
11 Shut-off valve, injection pipe
12 4-way reversing valve
TANT!
13 Shut-off valve, suction pipe
14 Partitioning panel
15 Temperature probe for heat gas line
16 Compressor
17 Floor panel
18 Side panel, right
19 Refrigerant connections cover
20 Control board
21 Auxiliary circuit board
22 Temperature probe for condenser outlet
23 Condensate tray heating
24 Crankcase heating
69
Page 70
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
REMKO RXT series

14.7 Exploded view - Outdoor unit RXT 685 DC

Fig. 60: Exploded view of the unit RXT 685 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
70
Page 71

14.8 Spare parts list - Outdoor unit RXT 685 DC

No. Designation
1 Cover panel
2 Protection grid, front wall
3 Front panel
4 Fan blade
5 Fan motor
6 Fan motor mounting plate
7 Corner panel, left
8 Condenser
9 Air inlet temperature probe
10 Electronic injection valve
11 Shut-off valve, injection pipe
12 4-way reversing valve
13 Shut-off valve, suction pipe
14 Partitioning panel
15 Temperature probe for heat gas line
16 Compressor
17 Floor panel
18 Side section, right
19 Refrigerant connections cover
20 Terminal block cover
21 Control board
22 Inverter board
23 Cooling fins
24 Temperature probe for condenser outlet
25 Mounting plate for refrigerant connections
26 Transformer
27 Condensate tray heating
28 Crankcase heating
71
Page 72
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
REMKO RXT series

14.9 Exploded view - Outdoor unit RXT 1055 DC

Fig. 61: Exploded view of the unit RXT 1055 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
72
Page 73

14.10 Spare parts list - Outdoor unit RXT 1055 DC

No. Designation
1 Cover panel
2 Protection grid, front wall
3 Front panel
4 Fan blade
5 Fan motor
6 Fan motor mounting plate
7 Side panel, left
8 Recessed grip side panel, left
9 Temperature probe for condenser outlet
10 Temperature probe for condenser outlet
11 Temperature probe for heat gas line
12 Air inlet temperature probe
13 4-way reversing valve
14 Shut-off valve, suction pipe
15 Inverter board
16 Control board
17 Liquid separator
18 Transformer
19 Side panel, right
20 Terminal block cover
21 Shut-off valve cover
22 Recessed grip front panel, right
23 Front panel, right
24 Low pressure switch
25 Electronic injection valve
26 Shut-off valve, injection pipe
27 High pressure switch
28 Compressor
29 Partitioning panel
30 Floor panel
31 Shut-off valve mounting plate
32 Condensate tray heating
33 Crankcase heating
73
Page 74
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
REMKO RXT series

14.11 Exploded view - Outdoor unit RXT 1405 DC

Fig. 62: Exploded view of the unit RXT 1405 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
74
Page 75

14.12 Spare parts list - Outdoor unit RXT 1405 DC

No. Designation
1 Cover panel
2 Protection grid, front wall
3 Front panel
4 Fan blade
5 Fan motor
6 Fan motor mounting plate
7 Side panel, left
8 Condenser
9 4-way reversing valve
10 Shut-off valve, suction pipe
11 Partitioning panel
12 Shut-off valve, injection pipe
13 Air inlet temperature probe
14 Temperature probe for condenser outlet
15 Compressor
16 Control board
17 Floor panel
18 Shut-off valve mounting plate
19 Temperature probe for heat gas line
20 Auxiliary circuit board
21 High pressure switch
22 Inverter board
23 Transformer
24 Transformer
25 Front panel, right
26 Transformer
27 Low pressure switch
28 Liquid separator
29 Refrigerant connections cover
30 Condensate tray heating
31 Crankcase heating
32 Terminal block cover
33 Side panel, right
75
Page 76
REMKO RXT series

15 Index

A
Assembly
Strip foundation ...................... 34
C
Care and maintenance ................... 62
Cleaning
Air filter for indoor unit ................. 62
Condensate pump ....................63
Housing ............................ 62
Condensate drainage connection and safe
drainage .............................. 34
Customer service ....................... 45
D
Display on indoor unit .................... 15
Disposal of equipment .....................8
E
Electrical drawings ..............39, 40, 41, 42
Electrical wiring ......................... 36
Electrical wiring diagram ............... 37, 38
Environmental protection ...................8
Exploded view of the unit ... 64, 66, 68, 70, 72, 74
F
Flashing code, fault display ............... 47
Function test of the cooling and heating modes
Functional checks ....................... 43
44
I
Infrared remote control ................... 14
Installation location, selection .............. 24
Installation materials ..................... 25
Intended use ............................ 7
K
Keys on the remote control ................ 16
O
Oil return measures ......................29
Ordering spare parts ...... 65
, 67, 69, 71, 73, 75
P
Propellant in accordance with Kyoto Protocol ... 9
R
Remote control
Keys ...............................16
Resistances
Temperature probes ................... 59
S
Safe drainage in the event of leakages ....... 35
Safety
Dangers of failure to observe the safety
notes ............................... 5
General ............................. 5
Identification of notes ................... 5
Instructions for the operator .............. 6
Note for inspection work .................6
Note for installation work ................ 6
Note for maintenance work .............. 6
Personnel qualifications ................. 5
Safety-conscious working ................6
Unauthorised modification ...............7
Unauthorised replacement part manufacture . 7
Selection of installation location ............ 24
Shut-down
Permanent .......................... 44
Temporary .......................... 44
Spare parts list ...........65, 67, 69, 71, 73, 75
T
Temperature probes
Resistances ......................... 59
Test run ............................... 43
Troubleshooting and customer service ....... 45
M
Maintenance ........................... 62
Malfunction indicated by flashing code ....... 47
Malfunctions
Checks .............................45
Possible causes ...................... 45
Remedial measures ................... 45
Manual mode .......................... 14
Minimum clearances ..................... 29
U
Unit installation ......................... 30
W
Wall opening ........................... 26
Warranty ............................... 7
76
Page 77
77
Page 78
REMKO RXT series
78
Page 79
Page 80
REMKO QUALITY WITH SYSTEMS
Air-Conditioning | Heating | New Energies
Telephone +49 (0) 5232 606-0 Telefax +49 (0) 5232 606-260
E-mail info@remko.de URL www.remko.de
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 32791 Lage
Hotline within Germany
+49 (0) 5232 6 06-0
Hotline International
+49 (0) 5232 606-130
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
Loading...