2.1 Unit data.......................................................................................................................................... 9
2.2 Unit dimensions ............................................................................................................................ 12
3Design and function............................................................................................................................ 13
3.1 Unit description............................................................................................................................. 13
Carefully read the operating manual before commissioning the units or their components for the
first time. It provides useful tips and notes such as
hazard warnings to prevent injury and material
damage. Failure to follow
manual can endanger persons, the environment
and the equipment itself or its components and will
void any claims for liability.
Store this manual and the information required for
the operation of this system (e.g. refrigerant datasheet) in the vicinity of the unit.
The refrigerant used in the system is flammable. If
applicable, observe the local safety conditions.
the directions in this
DANGER!
This combination of symbol and signal word
warns of a situation in which there is immediate
danger
cause serious injury.
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may be fatal or cause
serious injury
, which if not avoided may be fatal or
WARNING!
.
Warning of inflammable substances!
Identification of notes
1.2
This section provides an overview of all important
safety aspects for proper protection of people and
safe and fault-free operation.The instructions and
safety notes contained within this manual must be
observed in order to prevent accidents, personal
injury and material damage.
Notes attached directly to the units must be
observed in their entirety and be kept in a fully
legible condition.
Safety notes in this manual are indicated by symbols. Safety notes are introduced with signal words
which help to highlight the magnitude of the danger
in question.
CAUTION!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause injury or material and environmental damage.
NOTICE!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause material and
environmental damage.
This symbol highlights useful tips and recommendations as well as information for efficient
and fault-free operation.
1.3 Personnel qualifications
DANGER!
Contact with live parts poses an immediate
danger of death due to electric shock. Damage
to the insulation or individual components may
pose a danger of death.
Personnel responsible for commissioning, operation, maintenance, inspection and installation must
be able to demonstrate that they hold a qualification which proves their ability to undertake the
work.
Dangers of failure to observe
1.4
the safety notes
Failure to observe the safety notes may pose a risk
to people, the environment and the units. Failure to
observe the safety notes may void any claims for
damages.
5
Page 6
REMKO RXT series
In particular, failure to observe the safety notes
may pose the following risks:
n The failure of important unit functions.
n The failure of prescribed methods of mainte-
nance and repair
n Danger to people on account of electrical and
mechanical effects.
.
1.5 Safety-conscious working
The safety notes contained in this manual, the
existing national regulations concerning accident
prevention as well as any internal company
working, operating and safety regulations must be
observed.
Safety instructions
1.6
for the operator
The operational safety of the units and components is only assured providing they are used as
intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified personnel.
n Protective covers (grills) over moving parts
must not be removed from units that are in
operation.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with equipment parts or components
can lead to burns or injury
n The units and components must not be
exposed to any mechanical load, extreme
levels of humidity or extreme temperatures.
n Rooms in which refrigerant may escape shall
be adequately aerated and ventilated. Otherwise, a risk of suffocation or fire exists.
n Do not leave children unsupervised when close
to the system.
n Commissioning must be performed by author-
ised specialists exclusively. Deficient commissioning may lead to water leaks, electric
shocks or fire. Commissioning must take place
as described in the user manual.
n Only instruct authorised specialist personnel to
perform maintenance or servicing.
n The system is filled with a flammable refrig-
erant. Never thaw any frozen unit components
independently!
n Do not operate any further devices that pro-
duce high heat or naked flames in the same
room.
.
n All housing parts and unit openings, e.g. air
inlets and outlets, must be kept clear
n The units must be inspected by a service tech-
nician to ensure that they are safe to use and
fully functional at least once yearly. Visual
inspections and cleaning may be performed by
the operator when the units are disconnected
from the mains.
.
1.7 Safety notes for installation,
maintenance and inspection
n The refrigerant R32 used in the system is flam-
mable. If applicable, observe the local safety
conditions.
n Keep the cooling circuit clear of other gases
and foreign substances. Only fill the cooling circuit with the refrigerant R32.
n Only use the accessories, components and
appropriately marked parts provided. The use
of non-standardised components may result in
water leaks, electric shocks and fire.
n Only install and store the units in rooms larger
than 4 m2. With a failure to comply
result in the room filling with a flammable mixture!
The minimum room size of 4 m2 required for
installation and storage pertains to the basic fill
quantity of the unit. This varies according to the
installation type and total fill quantity of the
system. The calculation must take place in
accordance with valid DIN standards. Make
sure that the installation site is suitable for safe
unit operation.
n Only mount the unit components on structurally
suitable brickwork.
n The units must not be installed in rooms in
which further devices that produce heat are
operated (heaters, open hearths).
n Make sure the installation room is sufficiently
ventilated.
n Interventions in the cooling circuit are only pos-
sible after completely draining the refrigerant.
Never solder or grind unit components!
n Note that refrigerant may be odourless.
n Never operate the air conditioning unit in a
humid room, such as a bathroom or laundry
room. If the humidity is too high, this can cause
short circuits on electrical parts.
n The product must be correctly earthed at all
times, otherwise it may induce electric shocks.
n Attach the condensate drain as described in
the operating manual. The inadequate
drainage of condensate can lead to water
damage in your apartment.
n All persons who intervene in the cooling circuit
must hold a valid certificate from the chamber
of industry and commerce, which confirms their
ability to work with refrigerant.
, leaks may
6
Page 7
n Appropriate hazard prevention measures must
be taken to prevent risks to people when performing installation, repair
cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken
in accordance with the usage and operating
conditions stipulated in this manual and comply
with all applicable regional regulations.
n Regional regulations and laws as well as the
Water Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n Units may only be mounted at the points pro-
vided for this purpose at the factory. The units
may only be secured or mounted on stable
structures, walls or floors.
n The units and components should not be oper-
ated in areas where there is a heightened risk
of damage. Observe the minimum clearances.
n The units and components must be kept at an
adequate distance from flammable, explosive,
combustible, abrasive and dirty areas or
atmospheres.
n Safety devices may not be modified or
bypassed.
n The connection of the indoor unit must be
established as a permanent connection; a
detachable, reusable connection is not permissible.
, maintenance or
1.8 Unauthorised modification
and changes
1.10 Warranty
For warranty claims to be considered, it is essential
that the ordering party or its representative complete and return the "certificate of warranty" to
REMKO GmbH & Co. KG at the time when the
units are purchased and commissioned.
The warranty conditions are detailed in the "General business and delivery conditions". Furthermore, only the parties to a contract can conclude
special agreements beyond these conditions. In
this case, contact your contractual partner in the
first instance.
1.1
1 Transport and packaging
The devices are supplied in a sturdy shipping container. Please check the equipment immediately
upon delivery and note any damage or missing
parts on the delivery and inform the shipper and
your contractual partner. For later complaints can
not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous
toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to
children!
Modifications or changes to units and components
are not permitted and may cause malfunctions.
Safety devices may not be modified or bypassed.
Original replacement parts and accessories
authorised by the manufactured ensure safety
use of other parts may invalidate liability for
resulting consequences.
. The
1.9 Intended use
Depending on the model, the units and the additional fittings with which they are equipped are only
intended to be used as an air-conditioner for the
purpose of cooling or heating the air in an
enclosed space.
Any different or additional use is a non-intended
use. The manufacturer/supplier assumes no liability for damages arising from a non-intended use.
The user bears the sole risk in such cases.
Intended use also includes working in accordance
with the operating and installation instructions and
complying with the maintenance requirements.
The threshold values specified in the technical
data must not be exceeded.
7
Page 8
REMKO RXT series
1.12 Environmental protection
and recycling
Disposal of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved
collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufacture of the devices and components. Help protect
the environment by ensuring that the devices or
components (for example batteries) are not disposed in household waste, but only in accordance
with local regulations and in an environmentally
safe manner, e.g. using certified firms and recycling specialists or at collection points.
8
Page 9
2 Technical data
2.1 Unit data
SeriesRXT 525 DCRXT 685 DCRXT 1055 DCRXT 1405 DC
Operating mode
Nominal cooling output
1)
Energy efficiency ratio SEER
Power consumption,
annual, QCE
3)
Energy efficiency ratio, cooling
Nominal heat capacity
2)
Energy efficiency ratio SCOP
Power consumption,
annual, QHE
3)
Energy efficiency ratio, heating
Rated power consumption,
electrical cooling
1)
kW
1)
kWh305413574---
1)
kW
4)
kWh140019252937---
2)
kW
Rated elec. curr. consump.,
cooling
1)
Inverter wall/ceiling-mounted room air conditioner combination
for cooling and heating
5,30
(2,70-5,90)
7,00
(2,70-7,70)
10,60
(2,70-1
1,80)
14,10
(3,50-15,20)
6,26,16,4---
A++A++A++---
5,60
(2,40-6,30)
7,60
(2,70-8,30)
11,70
(2,80-12,80)
16,10
(4,10-17,0)
4,04,04,0---
A+A+A+---
1.632.193.755.50
A7.2010.005.809.10
Rated power consumption,
electrical heating
2)
Rated elec. curr. consump.,
heating
2)
kW1.502.053.005.05
A6.609.504.808.14
Max. power consumptionkW2.952.955.606.20
Max. current consumptionA13.5013.5010.0011.20
EDP no.1619550161956016195701619580
1)
Air inlet temp. TK 27 °C/FK 19 °C, outside temperature TK 35 °C, FK 24 °C, max. air flow volume,
5 m pipe length
2)
Air inlet temp. TK 20 °C, outside temperature TK 7 °C, FK 6 °C, max. air flow volume, 5 m pipe length
3)
The specified value is based on results from standard testing.
The actual consumption depends on the use and location of the unit
4)
The specified value is based on the average heating period
9
Page 10
REMKO RXT series
Data specific to indoor unit
Power supplyV/Ph/Hz230/1~/50
Application area (room vol.)
approx.
Adjustment range
room temperature
Operating range
Air flow volume per stage
Sound pressure level
per stage
Sound power (turbo mode)dB(A)59656565
Enclosure classIPX0
Condensate drainage
connection
Dimensions: H/W/Dmm675/1068/235675/1650/235
5)
m
°C+17 to +30
°C/
RH %
m3/h
dB (A)24/37/41/4432/43/46/4939/45/48/5136/45/50/53
mm25
RXT 525 DCITRXT 685 DCITRXT 1055 DCITRXT 1405 DC
3
160230320470
+17 to +30 / 35 to 65
723/839/
958
853/1023/
1
192
1504/1728/
1955
IT
1600/1850/
2100
Weightkg28.026.839.041.2
EDP no.1619552161956216195721619582
5)
At distance of 1 m in the open air; specified values are maximum values
At distance of 1 m in the open air; specified values are maximum values
6)
Contains greenhouse gas per the Kyoto protocol, GWP 675 (for further information,
see chapter "Adding refrigerant")
7)
This can be extended to -15 °C with the appropriate accessory kit
11
Page 12
D
E
B
A
C
B
C
A
REMKO RXT series
2.2 Unit dimensions
Outdoor units
Fig. 1: Dimensions RXT 525-1405 DC AT (all measurements in mm)
Measurements (mm)ABCDE
RXT 525 DC AT874511317554346
RXT 685 DC AT962663348673380
RXT 1055 DC AT946810410673403
RXT 1405 DC AT9521333410634404
Indoor units
Fig. 2: Unit dimensions, indoor unit RXT 525-1405 DC IT
Measurements (mm)ABC
RXT 525 DC IT6751068235
RXT 685 DC IT6751068235
RXT 1055 DC IT6751650235
RXT 1405 DC IT6751650235
12
Page 13
B
A
4
3
5
6
1
2
3
7
8
9
1
EEV
RXT 1051 DC
M
M
PS H
T1
T2
T
3
TE
T5
P
S
L
T4
T3
T2
M3
M2
M1
PSL
PSH
T1
V1
M
M
TE
PSH
T1
T2
T
3
T5
P
S
L
M1
M3
T4
T3
T2
M2
PSL
PSH
T1
V1
EEV
2
AB
AB
FLT
FLT
FLT
FLT
OEL
T5
T5
3 Design and function
3.1 Unit description
The RXT room air conditioners have a REMKO
RXT...DC AT outdoor unit as well as a RXT...DC IT
indoor unit.
In cooling mode, the outdoor unit serves to output
the heat extracted by the indoor unit from the room
being cooled. In heating mode, the heat taken up
by the outdoor unit can be discharged by the
indoor unit into the room to be heated. In both
operating modes, the output produced by the compressor precisely matches requirements, and
thereby regulates the nominal temperature with
minimal temperature deviations. This "inverter
technology" results in energy savings over conventional split systems and also reduces noise emissions to a particularly low level. The outdoor unit
can be installed in an outdoor area or, providing
that certain requirements are met, an indoor area.
The outdoor unit consists of a cooling cycle with
compressor, fin condenser, condenser fan,
reversing valve and electronic expansion valve.
The outdoor unit is controlled by the regulation of
the indoor unit.
The indoor unit is designed both for both wall and
ceiling-mounted operation in indoor areas. It is
operated by an infrared remote control. The indoor
unit consists of a fin evaporator, evaporator fan,
controller and condensate tray.
Floor consoles, wall consoles, refrigerant piping,
wired remote controls and condensate pumps are
available as accessories.
Refrigerant piping is used to connect the indoor
unit to the outdoor unit.
Fig. 4: Cooling cycle schematic
A:Outdoor area
B:Indoor area
1:RXT 525-685 DC
2:RXT 1055-1405 DC
M1:Condenser fan
M2:Compressor
M3:Evaporator fan IT
V1:Changeover valve C/H
EEV: Electr. expansion valve
FLT: Filter
OEL: Oil return line
PSH: High pressure switch AT
PSL: Low pressure switch AT
T1:Probe, evaporator IT
T2:Probe, air inlet IT
T3:Probe, condenser AT
T4:Probe, air inlet AT
T5:Probe, heat gas AT
Fig. 3: System layout RXT 525-1405 DC
A: Outdoor area / B: Indoor area
1: Indoor unit / 2: Outdoor unit
3: Condensate drainage line / 4: Condenser fan
5: Power supply / 6: Shut-off valve
7: Suction pipes / 8: Injection pipes
9: Control lines
13
Page 14
max. 6 m
REMKO RXT series
4 Operation
4.1 General notes
The indoor unit is easily operated using the
standard infrared remote control. The indoor unit
beeps to acknowledge the correct transmission of
data. If it is not possible to program the indoor unit
with the remote control, then it can also be manually operated.
Manual mode
The indoor unit can also be started manually. By
pressing the "Manual" key (on the display board)
multiple times, the unit can be activated with the
following functions:
The following settings apply for manual operation:
Pressing once: Automatic mode 24°C, fan speed
automatic
Pressing twice: Cooling mode, fan speed high
Pressing three times: Unit OFF
Fig. 5: Maximum distance
Infrared remote control
The infrared remote control sends the programmed
settings a distance of up to 6 m to the receiver of
the indoor unit. Data will only be received correctly
if the remote control is pointed at the receiver and
no objects are obstructing the transmission path.
wo AAA batteries must be inserted into the
T
remote control in preparation. To do so, remove
the flap from the battery compartment and insert
the batteries the correct way around (see markings).
NOTICE!
Immediately replace flat batteries with a new
set, otherwise there is a risk of leakage. It is
recommended that the batteries are removed if
the equipment is shut down for longer periods.
14
Page 15
MANUAL TIMER
ALARM
OPERATION
DEF./FAN
123
56
4
7
Wired remote control
Connection of the optional wired remote control
1.The plug for connection of a wired remote
control is located behind the panel at the display board (
Fig. 6). The 5-core cable, coming
from the display panel, is marked with the
designations "A-E" (Fig. 7).
Fig. 6: Indoor unit panel
Fig. 7: Display circuit board
4.2 Display on indoor unit
Display on indoor unit
The LED indicators illuminate to indicate the settings:
Fig. 8: Display for setpoint/errors
1: Digital display
2: Manual operation
3: Operation display
4: Timer indicator
5: Unit for receiving signals from the remote con-
trol
6: Defrosting fan
7: Alarm indicator
Alarms are indicated by a code (see chapter
roubleshooting and customer service).
T
Help save on energy consumption in stand-by
mode! If the device, system or component is not
in use, we recommend disconnecting the power
supply
excluded from our recommendation!
. Components with a safety function is
15
Page 16
10
8
11
12
2
1
6
3
7
5
9
4
13
14
1
2
3
4
5
6
7
8
9
10
11
12
REMKO RXT series
4.3 Keys on the remote control
“Swing” key
Starts and stops the horizontal fin movement.
Press and hold the key for 2 seconds to start the
vertical fin movement (available depending on the
unit model).
“Fan speed” key
Allows switching between the dif
ferent fan speeds
in the following order:
Automatic Low Medium High
Note: To activate the silence function (available
depending on the appliance model) of the appliance, press and hold the key for 2 seconds.
urbo” key
“T
Activating the turbo function ensures that the setpoint is reached as quickly as possible.
“Mode” key
This key allows switching between the dif
ferent
operating modes in the following order:
Fig. 9: Keys on the remote control
“On/Off” key
Press this key to switch the air conditioning unit on
f.
and of
“Arrow up” temperature key
Increases the setpoint in 1 °C steps up to a temperature of max. 30 °C.
“SET” key
Makes it possible to switch between dif
ating functions as follows:
“Follow me” function (
- Network configuration ()
- “Follow me” function ( )
The selected function flashes in the display
firm with the “OK” key.
Activates/deactivates the energy saving function of
the unit (e.g. overnight).
“OK” key
Required to confirm various functions of the IR
remote control.
imer” key
“T
Activates/deactivates the time-delayed start of the
unit or the unit switch-off.
“Arrow down” temperature key
Decreases the setpoint in 1 °C steps down to a
temperature of min. 17 °C.
“Fresh” key
Activates/deactivates the REMKO BioClean function (ionisation).
16
Page 17
13
14
13
2
5
6
7
4
8
9
10
11
12
13
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
“Clean” key
Activates/deactivates the self-cleaning function of
the unit (available depending on the unit model).
“LED” key
Enables switching on/of
f the unit lighting and the
signal tones (depending on the unit).
Indicators on the LCD
Time-delayed switch-on active.
Time-delayed switch-off active.
Silent mode active.
Fan speed
Displays the set fan speed as follows:
Low:
Medium:
High:
Automatic:
Mode selection
Shows the current operating mode.
Eco function
Lights up when the Eco function is active (available
depending on the unit).
Key lock
Symbol appears when the key lock is activated.
emperature/Timer/Fan speed
T
Fig. 10: Indicators on the LCD
Shows the current temperature setpoint in the
basic view. When using the additional function
“Timer”, the corresponding time values are shown.
BioClean function active (available depending
on the unit type).
Sleep function active.
Follow-me function active.
Network configuration active.
Battery low (flashing).
Signal transmission
Lights up when a signal is sent from the IR remote
control to the air conditioning unit.
17
Page 18
REMKO RXT series
Temperature setting
The temperature setting can be made within a
range of 17-30 °C. The setpoint is adjusted in 1 °C
steps.
Automatic mode
In automatic mode, the unit automatically selects
the operating mode based on the set temperature
setpoint.
1.Press the “Mode” key to activate the “Auto”
function.
2.Set the desired temperature using the “Λ ”
and “V” keys.
3.The unit can be switched on by pressing the
“ON/OFF” key.
Cooling mode
1.Press the “Mode” key and activate the “Cool”
function.
2.Set the desired temperature using the “Λ ”
and “V” keys.
3.Press the “FAN” key to select the fan speed.
The following are available: Automatic, Low,
Medium and High
4.The unit can be switched on by pressing the
“ON/OFF” key.
The fan speed cannot be set in automatic
mode!
Fig. 11: Cooling mode
18
Page 19
2
1
3
2
1
3
Timer function
With the “Timer” function, the unit can switch on
with a switch-on delay or switch of
off delay.
Time-delayed switch-on
1.Press the “T
setting
2.Use the arrow keys to select the desired
number of hours after which the air conditioning unit is to switch on
3.Point the remote control towards the air conditioning unit and wait 1 sec. The timer is
now active (symbol in the display of the
remote control)
imer” key to enter the “Time ON”
f with a switch-
Time-delayed switch-off
1.Press the “T
OFF” setting
2.Use the arrow keys to select the desired
number of hours after which the air conditioning unit is to switch of
3.Point the remote control towards the air conditioning unit and wait 1 sec. The timer is
now active (symbol in the display of the
remote control)
imer” key to enter the “Time
f
Fig. 13: Time-delayed switch-off
Fig. 12: Time-delayed switch-on
19
Page 20
13.00
14.0015.0015.3016.0017.0018.00
a
b
c
2
1
3
1
2
REMKO RXT series
Combining time-delayed switching on and off
Fig. 14: Combining time-delayed switching on and off
1: Timer starts
2: Unit switches on
3: Unit switches off
Example: If both timers are activated at 13:00, the unit switches on 2.5 hours later (at 15:30) and switches off
5 hours later (at 18:00).
“Swing” function
Press the “Swing” key
1.The horizontal air guide fin starts to rise and fall automatically
desired position
2.On units with 3D swing function, pressing the “Swing” key for 2 seconds activates the vertical fin movement
a: current (13:00)
b: 2.5 hours later
c: 5 hours later
. Pressing again stops the fin at the
Fig. 15: “Swing” function
20
Page 21
2
1
Deactivate lighting and signal tones
1.Press the “LED” key to switch the unit lighting
on and of
2.Press and hold the “LED” key for longer than
5 seconds, the ACTUAL temperature
appears in the unit display (not available for
all unit types)
Fig. 16: Deactivate lighting and signal tones
Activating Silent function
Depending on the unit type, the Silent function
(low-noise unit operation) can be activated. T
this, the “FAN” key must be pressed and held for 2
seconds. The unit now operates in a particularly
quiet mode. It must be taken into account that the
unit cannot call up the full cooling or heating
capacity.
The silent mode can be deactivated again by
pressing the “ON/OFF”, “Mode”, “Sleep”, “Turbo” or
“Clean”.
f.
o do
Frost protection function
The air conditioning unit operates at high fan
speed with a fixed setpoint of 8 °C (only available
in heating mode).
o activate this function, heating mode must be
T
activated and the setpoint must be set to 17°C.
Pressing the “Arrow down” key twice within one
second activates the FP function.
The function can be deactivated again by pressing
the “On/Off”, “Sleep”, “Mode”, “Fan” keys and the
temperature setting.
Fig. 19: Frost protection function
Activating key lock
Hold the “Clean” and “T
for 5 seconds to activate the key lock.
To deactivate the key lock, both keys must be
pressed again for 2 seconds.
Fig. 20: Activating key lock
urbo” keys simultaneously
“Shortcut” key
Pressing this key (not available on all unit models)
while the unit is in operation will reset all settings
(including operating mode, setpoint, fan speed and
Fig. 17: Silent function
Eco function
Press the “Eco” key (not available on all models) to
activate the energy-saving function of the unit.
Note: Function only available in cooling mode!
Fig. 18: COS Eco function
Function description:
Pressing this key in cooling mode automatically
sets the temperature setpoint to 24 °C. When the
room temperature is <24 °C, the fan goes into
energy-saving mode. If the room temperature is
>24 °C, the fan speed remains in the “Automatic”
operating mode.
sleep function) to the last used settings.
Fig. 21: “Shortcut” key
21
Page 22
REMKO RXT series
Self-cleaning function
Press the “Clean” key (not available on all unit
models).
Due to the formation of condensate on the heat
exchanger and the residual moisture that remains,
bacteria can multiply quickly
operation, the heat exchanger is dried by the air
volume flow. This drying process can also be
started manually with the “Clean” function (for
example, if the unit is not in regular use). In cooling
or dehumidification mode, the self-cleaning function can be activated. The unit switches off automatically after cleaning.
. In regular normal
“Turbo” function
If the “T
unit operates with the highest possible cooling
capacity and at the same time with the highest fan
speed.
This allows the desired setpoint to be reached as
quickly as possible.
Fig. 23: “Turbo” function
urbo” key is pressed in cooling mode, the
Fig. 22: Self-cleaning function
22
Page 23
“Set” key
Press the “Set” key to enter the settings menu. Press the “Set” key or the arrow keys again to select the
desired function. The corresponding function flashes on the display of the remote control. Press the “OK” key
to select it.
Fig. 24: “Set” key
The additional functions are shown in the following order:
BioClean function ( ) Sleep function ( ) Follow-Me function ( ) Network configuration ()
If your remote control has the “Fresh” and “Sleep keys, these functions cannot be operated via the “SET”
.
key
“BioClean” function ( )
When the BioClean function is activated, negatively charged ions are released into the air stream to increase
the air quality
Sleep function
The sleep function can be used to save energy during night operation. This function is not available in the
“Recirculation” and “Humidification” operating modes. The “Sleep” key should be pressed before going to
bed. In cooling mode, the unit will increase the setpoint by 1 °C after 1 operating hour
ating hour, the temperature is increased by 1 °C again. In heating mode, the setpoint is lowered by the previously mentioned parameters.
The sleep function deactivates automatically after an operating time of 8 hours.
AP mode (network configuration)
Not available for all unit types and can only be used in combination with the optional REMKO WifiStick. AP
mode can be activated by pressing the “LED” key several times within 10 seconds. The unit is now in network configuration mode. For integration via WLAN, please observe the assembly and operating instructions
of the REMKO Wifi-Stick.
.
. After another oper-
23
Page 24
REMKO RXT series
5 Installation instructions for qualified personnel
5.1 Important notes
prior to installation
ransport the unit in its original packaging as
n T
close as possible to the installation location.
You avoid transport damage by doing so.
n Check the contents of the packaging for com-
pleteness and check the unit for visible transport damage. Report any damage immediately
to your contractual partner and the shipping
company.
n Lift the unit on the corners and not on the
refrigerant or condensate drainage connections.
n The refrigerant piping (injection and suction
pipe), valves and connections must be insulated against vapour density. If necessary also
insulate the condensate drainage line.
n Select an installation location which allows air
to freely flow through the air inlet and outlet
(see section "Minimum clearances").
n Do not install the unit in the immediate vicinity
of devices which generate intensive thermal
radiation. Installation in the vicinity of thermal
radiation reduces the unit output.
n Only open the shut-off valves on the refrigerant
piping after installation is complete.
n Seal off open refrigerant piping with suitable
caps or adhesive strips to prevent the infiltration of moisture and never kink or compress
the refrigerant piping.
n Avoid unnecessary bends. This minimises the
pressure loss in the refrigerant piping and
ensures that the compressor oil can flow back
without obstruction.
n Make special preparations regarding the oil
return if the outdoor unit is located above the
indoor unit (see section "Oil return measures").
n Add refrigerant if the basic length of the refrig-
erant piping exceeds 5 metres. For the quantity
of additional refrigerant, refer to chapter
"Adding refrigerant".
n Perform all electrical wiring in accordance with
applicable DIN and VDE standards.
n Ensure the electrical cables are properly con-
nected to the terminals. Otherwise there is a
risk of fire.
n Use suitable fastening materials for the instal-
lation location of the units.
5.2 Selection of installation
location
Indoor unit
The indoor unit is designed for horizontal wall
installation underneath windows. However
also be used in the upper wall area (max. 1.25 m
above the floor). The unit is also designed for horizontal ceiling installation. Observe the condensate
drainage in particular here.
Fig. 25: Horizontal positioning
Outdoor unit
The outdoor unit is designed for horizontal installation on a base in outdoor areas. The installation
site must be level, flat and firm. The unit should
also be secured to prevent it from tipping over
outdoor unit can be set up outside as well as inside
a building. For external installation, please observe
the following notes to protect the unit from the
influence of the weather.
Rain
For floor or roof set-up, the unit should be installed
with at least 10cm ground clearance. A floor
bracket is available as an optional accessory.
Sun
The condenser on the outdoor unit emits heat.
Exposure to sunlight further increases the temperature of the fins and reduces the heat released by
the finned heat exchanger. The outdoor unit should
be installed on to the north side of the building
whenever possible. If necessary, take measures to
provide sufficient shade (responsibility of customer). One possible solution is to build a small
roofed area over the unit. These measures should
not affect the flow of warm outlet air.
, it can
. The
24
Page 25
Wind
1
20 cm
1
2
1
K
3
W
3
If the unit is being installed in windy areas, ensure
that the warm outlet air is discharged in the prevailing wind direction. If this is not the possible, it
may be necessary to install a windbreak (to be provided by the customer). Ensure that the windbreak
does not adversely af
Fig. 26: Windbreak
1: Wind
Snow
The unit should be wall-mounted in areas of heavy
snowfall. Installation should be at least 20cm
above the expected level of snow to prevent snow
from entering the outdoor unit. An optional wall
bracket is available as an accessory
fect the air intake to the unit.
.
Fig. 27: Minimum clearance to snow
1: Snow
Installation inside buildings
n Ensure that heat can dissipate adequately
when placing the outdoor unit in cellars, lofts,
adjoining rooms or halls (
n Install an additional fan with a rated flow com-
parative to that of the outdoor unit being
installed in the room and which can compensate any additional pressure loss in ventilation
ducts (Fig. 28).
n Comply with any regulations and conditions
fecting the statics of the building. If neces-
af
sary, fit acoustic installation.
Fig. 28).
Fig. 28: Installation inside buildings
K: Cold fresh air
W: Warm air
1: Outdoor unit
5.3 Installation materials
The indoor unit is attached to the wall by a wall
bracket and 4 screws (to be provided by the customer).
2: Additional fan
3: Air shaft
The outdoor unit is attached by 4 screws and a
wall bracket to the wall or fixed by a floor bracket to
the ground.
25
Page 26
215
34
REMKO RXT series
5.4 Wall openings
n A wall opening of at least 70 mm diameter and
10 mm incline from the inside to the outside
must be created.
o prevent damage to the lines, the interior of
n T
the wall opening should be padded or, for
example, lined with PVC pipe (see figure).
n After installation has been completed, use a
suitable sealing compound to close off the wall
opening, taking account of fire protection regulations (provided by the customer). Do not use
cement or lime containing substances!
Fig. 29: Wall opening
1: Injection pipe
2: Control line
3: Condensate drainage line
4: Suction pipe
5: PVC pipe
26
Page 27
5.5 Fastening options for the indoor unit
1
2
3
3
4
5
20 ~ 25 mm
1
1
1
1
If wall-mounted, the indoor units are mounted with fastening hooks and hanger bolts, and if ceiling-mounted
then with fastening hooks and threaded rods.
Fig. 30: Unit fastening with threaded rod
1: Unit mount
2: Threaded rod M10
3: Nut M10
4: Washer
5: Vibration damper (optional)
Fig. 31: Unit fastening
1: Unit mount
27
Page 28
1
1
2
2
1
1
3
3
4
REMKO RXT series
Fig. 32: Unit fastening without housing
1: Unit mount
2: Hanger bolts or threaded rods
3: Side part
4: Air inlet grill
28
Page 29
2
1
A
B
C
D
E
>1000mm
> 35mm
>35mm
> 35mm
A
1
2
3
1
A
B
2
5.6 Minimum clearances
Observe the minimum clearances to allow access
for maintenance and repair work and facilitate
optimum air distribution.
Minimum clearances, outdoor units
RXT 525-1405 DC A
Fig. 33: Minimum clearances, outdoor units
1: Air inlet / 2: Air outlet
Measure-
ments
(mm)
A300
T
RXT 525-1405 DC AT
5.7 Connection variants
The following connection variants can be used for
the refrigerant, condensate and control lines.
Fig. 35: Connection variants
A: Refrigerant piping
1: Outlet on the wall, right
2: Outlet through the wall, right
3: Outlet on the wall, down
B2000
C600
D200
E400
Minimum clearances, indoor units
RXT 525-1405 DC IT
Fig. 34: Minimum clearances, indoor units (all
measurements in mm)
A: Wall installation / B: Ceiling installation
29
5.8 Oil return measures
If the outdoor unit is installed at a higher level than
the indoor unit, suitable oil return measures must
be taken. Usually
every 7 metres of height difference.
Fig. 36: Oil return measures
A: Outdoor unit
B: Indoor unit
1: 1 x oil pump bend in suction pipe to outdoor
unit every 7 metres of height dif
50 mm
2: Max. 10 m
, an oil pump bend is installed for
ference, radius:
Page 30
REMKO RXT series
6 Installation
6.1 Preparations for installation
Removing the air inlet grill
NOTICE!
Installation should only be performed by authorised specialists.
1.Fold the air inlet grill forwards.
2.Remove the middle retainer by releasing the
two bars from the fastening.
3.Undo the lateral fastening screws and
remove the grill.
4.After installation, all parts that were removed
must be fitted again.
6.2
Installation of the indoor unit
Wall installation
The unit is attached by means of a wall bracket,
taking account of the air outlet side located
towards the top of the unit.
1.Mark the mounting points on the structurally
permissible building sections according to the
dimensions of the wall bracket.
2.If necessary
of the housing.
3.Hook the unit on to the previously attached
bracket.
4.Connect the refrigerant piping, electrical
cables and condensate drainage line to the
indoor unit as described below
5.Hang the indoor unit onto the wall bracket by
tilting it back slightly and by pressing the
bottom part of the unit against the bracket.
6.Check again that the unit is level.
, remove the break out opening
.
Ceiling installation
The unit is attached by means of the integrated
ceiling bracket, taking account of the air outlet side
located on the front of the unit.
1.Mark the mounting points on the structurally
permissible building sections according to the
dimensions of the wall bracket.
2.If necessary
of the housing.
3.Hook the unit onto the four previously
installed screws/threaded rods.
4.Fit the unit such that it is attached 5 mm
lower in the connection area (air inlet) than
on the air outlet side!
5.Connect the refrigerant piping, electrical
cables and condensate drainage line to the
indoor unit as described below
, remove the break out opening
.
6.3 Connection of
refrigerant piping
The refrigerant piping is connected on the back
side of the units.
It may be necessary to fit a reducer or flared
adapter to the indoor unit. These fittings are
included with the indoor unit as an accessory kit.
Once installed, the connections should be insulated to make them vapour diffusion proof.
NOTICE!
Installation should only be performed by authorised specialists.
NOTICE!
The unit is factory filled with dry nitrogen for
leak testing purposes. The pressurised nitrogen
is released when the union nuts are undone.
The wall bracket for the units must be attached
with suitable screws and anchors.
NOTICE!
Use only tools which are approved for use in an
HVAC environment. (z. B.: bending pliers, pipe/
tubing cutters, de-burrers and flaring tools). Do
not cut refrigerant pipes with a saw.
NOTICE!
All work must be carried out in a way that prevents dirt, particles, water etc. from entering,
refrigerant lines!
30
Page 31
The following instructions describe the installation
2
1
of the cooling cycle and the assembly of the indoor
unit and the outdoor unit.
1.The required pipe diameters are given in the
table "T
2.Install the indoor unit and connect the refrigerant piping as described in the operating
manual for the indoor unit.
3.Use the wall or floor brackets to fit the outdoor unit against structural parts approved to
support the static load (refer to the installation instructions for the brackets).
4.Ensure that structure-borne sound is not
transferred to parts of the building. Use vibration dampers to reduce the ef
ture-borne sound!
5.Lay the refrigerant piping from the indoor unit
to the outdoor unit. Ensure that the fastenings are adequate and if necessary
appropriate oil return measures!
6.Remove the factory-fitted protective caps and
union nuts on the connections. These should
be used later in the installation process.
7.Before flanging the refrigerant piping, ensure
that the union nut is fitted on the pipe.
8.Prepare the laid refrigerant piping as shown
below (
9.V
(Fig. 39).
10.First connect and hand-tighten the refrigerant
piping to ensure it is correctly seated.
11.Then tighten the fittings with 2 appropriatelysized open-ended spanners. Use one
spanner to counter the force when tightening
the fitting (Fig. 40).
12.Use insulation hoses which are designed for
this temperature range and are dif
proof.
13.Observe the permitted bending radius for the
refrigerant piping during installation. Never
bend a pipe twice in the same place. Brittleness and cracking can result.
14.Apply appropriate heat insulation to the
installed refrigerant piping, including connector
15.T
for all subsequent refrigerant piping.
echnical data".
fects of struc-
, take
Fig. 37 and Fig. 38).
erify that the shape of the flange is correct
fusion
.
ake the same action at the shut-off valves
Label the refrigerant piping (injection and suction pipes) as well as the associated electrical
control lines of each interior unit with a letter
Only connect the lines to their associated connections.
NOTICE!
Always pay attention to the af
electrical lines and refrigerant piping! The connections of the individual circuits must not be
mixed up. Mixing up the assignment of control
lines and refrigerant piping can have fatal consequences (compressor damage)!
Commissioning of the individual circuits must
be carried out successively.
Fig. 37: Deburring the refrigerant piping
1: Refrigerant piping
2: Deburrer
filiation of the
.
31
Page 32
1
2
1
REMKO RXT series
Fig. 38: Flanging the refrigerant piping
1: Flanging tool
Fig. 39: Correct flange shape
Fig. 40: Tightening the fitting
1: Tighten with the first open-ended spanner
2: Counter with the second open-ended spanner
Pipe dimension in
inches
1/4"15-20
3/8"33-40
1/2"50-60
5/8"65-75
3/4"95-105
Tightening torque in Nm
6.4 Additional notes on connecting
the refrigerant piping
n When combining the outdoor unit with some
indoor units, the procedure for connecting the
refrigerant piping may dif
vided reducer or expansion fittings to the
indoor unit.
n If the basic length of the connecting line
exceeds 5m, add refrigerant when commissioning the system for the first time (see
chapter "Adding refrigerant").
fer. Install the pro-
NOTICE!
A flare connection may only be established outside the room. Detachable, reusable connections are not permissible inside!
32
Page 33
6.5 Leak testing
Once all the connections have been made, the
pressure gauge station is attached to the Schrader
valve as follows (if fitted):
red = small valve = high pressure
blue = large valve = suction pressure
Once the connection has been made successfully
the leak test is carried out with dry nitrogen.
Leak testing involves spraying a leak detection
spray onto the connections. If bubbles are visible,
the connections have not been made properly. In
that case, tighten the connection or, if necessary,
create a new flange.
After completing a successful leak test, the excess
pressure in the refrigerant piping is removed and a
vacuum pump with an absolute final partial pressure of min. 10 mbar is used to remove all of the
air and empty the pipes. Any moisture present in
the pipes will also be removed.
NOTICE!
6.6 Adding refrigerant
The units contain a basic quantity of refrigerant. In
addition, an additional amount of refrigerant must
be added for refrigerant piping lengths exceeding 5
metres per circuit. Refer to the following chart:
Up to and
,
RXT 525-1405
DC
CAUTION!
ear protective clothing when handling refrig-
W
erant.
DANGER!
Only refrigerant in a liquid state may be used to
fill the cooling cycle!
incl. 5m
0 g/m30 g/m
From 5m to
max. length
A vacuum of at least 20 mbar must be produced!
The time required to generate the vacuum is
dependent on the final pressure pipe volume of the
indoor units and the length of the refrigerant piping.
However
minutes. Once any foreign gases and humidity
have been completely extracted from the system,
the valves on the pressure gauge station are
closed and the valves on the outdoor unit are
opened as described in the "Commissioning" section.
, the process will take at least 60
NOTICE!
Check the overheating to determine the refrigerant fill quantity
NOTICE!
The escape of refrigerant contributes to climatic
change. In the event of escape, refrigerant with
a low greenhouse potential has a lesser impact
on global warming than those with a high
greenhouse potential.
This unit contains refrigerant
potential of 675. That means the escape of 1 kg
of this refrigerant has an effect on global
warming that is 675 times greater than 1 kg
CO2, based on 100 years. Do not conduct any
work on the refrigerant circuit or dismantle the
unit - always enlist the help of qualified experts.
.
with a greenhouse
33
Page 34
3
2
4
9
55
11
100
6
8
7
1010
1212
1
min. 2%
min. 2%
REMKO RXT series
7 Condensate drainage
connection and safe
drainage
n The condensate drainage line should have an
incline of min. 2%. This is the responsibility of
the customer
proof insulation.
n When operating the unit at outside tempera-
tures below 4 °C, ensure the condensate
drainage line is laid to protect it against frost.
The lower part of the housing and condensate
tray is also to be kept frost free in order to
ensure permanent draining of the condensate.
If necessary, fit a pipe heater.
n Following installation, check that the conden-
sate run off is unobstructed and ensure that the
line is durably leak tight.
. If necessary, fit vapour-diffusion-
Fig. 41: Condensate drainage, seepage of condensate and strip foundation (cross-section)
1:Outdoor unit
2:Leg
3:Condensate collection tray
4:Floor bracket
5:Reinforced strip foundation
HxWxD = 300x200x800mm
6:Gravel layer for seepage
7:Condensate drainage heating
8:Drainage channel
9:Conduit for refrigerant piping and electrical
connecting line (temperature-resistant up to at
least 60°C)
10: Frost line
11: Drainage pipe
12: Soil
Condensate drainage connection
If the temperature falls below the dew point, condensation will form on the finned condenser during
heating mode.
A condensate tray should be installed on the
underside of the unit to drain any condensate.
Fig. 42: Condensate drainage connection IT on the
wall
Fig. 43: Condensate drainage connection IT on the
ceiling
34
Page 35
Safe drainage in the event of leakages
The REMKO oil separator OA 2.2 fulfils the following list of requirements from regional regulations and laws.
NOTICE!
Local regulations or environmental laws, for
example the German W
(WHG), can require suitable precautions to protect against uncontrolled draining in case of
leakage to provide for safe disposal of escaping
refrigerator oil or hazardous media.
NOTICE!
If condensate is removed via a duct in accordance with DIN EN 1717, ensure that any microbiological contamination present on the wastewater side (bacteria, fungi, viruses) cannot
enter the unit connected to it.
ater Resource Law
35
Page 36
2
1
2
1
REMKO RXT series
8 Electrical wiring
8.1 General notes
A mains cable must be installed as the power
supply to the outdoor unit and a control line to the
indoor unit, with appropriate protection.
DANGER!
All electrical installation work is to be performed
by specialist companies. Disconnect the power
supply when connecting the electrical terminals.
WARNING!
All electric lines are in accordance VDE regulations to dimension and to lay
NOTICE!
The electrical connection for the units must be
made at a separate feedpoint with a residual
current device in accordance with local regulations and should be laid out by an electrician.
.
Make the connection as follows:
1.The connection terminal block is located on
the right inside the unit (
2.Connect the unit to the control line from the
outdoor unit. See “Electrical wiring diagram”.
3.Re-assemble the unit.
Fig. 44).
e recommend using shielded wires for the
W
control lines.
Check all plugged and clamped terminals to
verify that they are seated correctly and make
permanent contact. T
ighten as required.
8.2 Connecting the indoor unit
The unit requires a six-wired control line from the
indoor unit to the outdoor unit.
e recommend installing a main / repair switch
n W
on the building close to the indoor unit. This is
the responsibility of the customer.
n Power is supplied to the outdoor unit, the
indoor unit is supplied via the control line from
the outdoor unit to the indoor unit.
n The terminal blocks for establishing the con-
nections are located inside the unit.
n If an optional condensate pump is used as an
accessory in conjunction with the unit, it may
be necessary to install an additional relay with
a higher contact rating after the switch-off contact on the pump to switch off the compressor.
Fig. 44: Connecting the indoor unit
1: Electrical connection (terminal box)
2: Connection of refrigerant lines
36
Page 37
AB
230V/1~/50 Hz
L N 1(L) 2(N) S L N PE
PE
S
PE
1
2
8.3 Outdoor unit connection
Proceed as follows to connect the line:
1.Remove the side-panel cover
2.Choose the cable cross-section in accord-
ance with the relevant specifications.
3.Connect the lines as shown on the electrical
connection diagram.
.
8.4 Electrical wiring diagram
Connection RXT 525-685 DC
4.Fix the line in the strain relief and re-
assemble the unit.
Fig. 45: Outdoor unit connection
Fig. 46: Electrical wiring diagram
A: Outdoor unit RXT 525-685 DC AT
B: Indoor unit RXT 525-685 DC IT
1: Mains cable
2: Communication lines
37
Page 38
A
B
400V/3~/50 Hz
L1 L2 L3 N
S 2(N) 1(L)
1(L) 2(N) S
1
2
REMKO RXT series
Connection RXT 1055-1405 DC
Fig. 47: Electrical wiring diagram
A: Outdoor unit RXT 1055-1405 DC AT
B: Indoor unit RXT 1055-1405 DC IT
1Power supply cable
2: Communication lines
38
Page 39
8.5 Electrical drawings
ALARM
CN33
T2
T1
CN6
4
CN5
CN9
X Y E
To CCM
Comm.Bus
HB HA
CN45
WIRE
CONTROLLER
Y/G
CN18
J7
CN23
ON/OFF
CN43
Y/G
WHITE
WHITE
(GRAY)
CN4
P1
P2
BLACK
BROWN
M
5
3
CN2
Cn1
CN3
Y/G
L
NS
REACTOR
CON2
RED
RED
DC MOTOR
DRIVER
MODLE
CON1
FAN1
3
3
M
4
CN1
CN15
CN34
DC FAN
3
Y/G
CN13
M
2
Y/G
MAGNETIC
RING
CN40
WIRE
CONTROLLER
4
MAGNETIC RING
DISPLAY
BOARD
WIRE
CONTROLLER
10
CN10
5
Y/G
12
13
3
4
5
8
7
A
6
14
15
1
B
Indoor units RXT 525-1405 DC IT
Fig. 48: Electrical drawings IT
A: Control board
B: Display circuit board
1:AC fan motor
3:DC fan motor
4:Potential-free external contact on/off
5:Potential-free alarm contact
6:MCC-1 controller/SC-1 connection (optional)
7:Communication line to outdoor unit
8:Optional connection external fan motor
12: Connection of condensate pump
13: Wired remote control connection (optional)
14: Temperature probe, evaporator
15: Temperature probe, room temperature
39
Page 40
1(L) 2(N)
SLN
4/5
2/3/4/5
35/6
CN 3
CN 1
CN 2
CN 16
CN 60
CN 17
CN 15
CN 25
CN 1A
CN 9
CN 32
CN 30
CN 29
CN 28
CN 21
CN 7
CN 31
BURDBK
UW
V
A
2
1
5
6
7
8
9
10
11
1213
3
4
14
REMKO RXT series
Outdoor unit RXT 525 DC AT
Fig. 49: Electrical drawings
A: Control board
1:Compressor
2:Transformer
3:Connecting line to the indoor unit
4:Power supply
5:4-way reversing valve
6:Crankcase heating
7:Condensate tray heating
8:Capacitor
9:AC fan
10: Electronic E-valve
11: DC fan motor
12: Air inlet temperature probe
13: Temperature probe for condenser outlet
14: Temperature probe for heat gas line
---: Optional
40
Page 41
Outdoor unit RXT 685 DC AT
A
1
4
5
6
7
8
9
10
1112
2
3
13
BURDBK
1(L) 2(N)
SLN
4/5
2/3/4/5
35/6
CN 6
CN 7
CN 8
CN 60
CN 16
CN 19
CN 5
CN 3
CN 17
CN 414
CN 18
UW
V
CN 2
CN 21
U
V
W
Fig. 50: Electrical drawings
A: Control board
1:Compressor
2:Connecting line to the indoor unit
3:Power supply
4:4-way reversing valve
5:Crankcase heating
6:Condensate tray heating
7:Capacitor
8:AC fan
9:Electronic E-valve
10: DC fan motor
11: Air inlet temperature probe
12: Temperature probe for condenser outlet
13: Temperature probe for heat gas line
---: Optional
41
Page 42
BURD
2
U
W
V
3
5
2
3
33
1
2(N) S
L1 L2
L3
N
2
MM
CN23CN22
CN708A
CN707A
CN24CN501
CN506 CN503 CN504 CN507CN502
CN508
CN715
CN714
CN713
CN709
CN706
CN705
CN301
CN710CN777CN702CN703CN704
CN13
CN3
M
CN1 CON1
CON2
FAN1
FAN2
5
M
MM
RD
RD
BK
BK
WH
WH
WH
RD
YE
RD
BU
BU
RD
BK
RD
WH
BU
BU
WH
RD
BU
BU
A
4
5
6
7
8
9
10
11
12
3
13
1
2
44
14
15
16
17
18
19
20
21
REMKO RXT series
Outdoor unit RXT 1055-1405 DC AT
Fig. 51: Electrical drawings
A: Control board
B: Inverter board
1:Klixon
2:Low pressure switch
3:High pressure switch
4:Air inlet temperature probe
5:Temperature probe for condenser outlet
6:Temperature probe for heat gas line
7:Condensate tray heating
8:Crankcase heating
9:4-way reversing valve
10: Communication line to indoor unit
11: Power supply cable
12: Supply line to indoor unit
13: DC fan motor
14: Compressor
15: Transformer
---: Optional
42
Page 43
9 Before commissioning
After leak testing has been successfully completed, connect the vacuum pump via the pressure
gauge station to the valve connections on the outdoor unit (see chapter "Leak testing") and create a
vacuum.
Perform the following checks prior to putting the
unit into operation for the first time and after any
work on the cooling cycle. Record the results in the
commissioning report:
n Check all refrigerant piping and valves for leak-
tightness using leak detection spray or soapy
water
.
n Check the refrigerant piping and insulation for
damage.
n Check the electrical connection between the
indoor unit and the outdoor unit for correct
polarity.
n Check that all fastenings, mountings, etc. are
firm and at the correct level.
10 Commissioning
NOTICE!
Commissioning should only be performed by
specially trained personnel and documented
after the certificate has been issued. Observe
the operating manuals for the indoor unit and
outdoor unit when commissioning the entire
system.
Once all the components have been connected
and tested, the system can be put into operation. A
functional check should be performed to verify its
correct function and identify any unusual operating
behaviour prior to handing it over to the operator
NOTICE!
Check that the shut-of
are tight after carrying out any work on the
cooling cycle. Use appropriate sealant products
as necessary.
f valves and valve caps
.
Functional checks and test run
Check the following points:
n Leak-tightness of the refrigerant piping.
n Compressor and fan running smoothly.
n In cooling mode, cold air output by the indoor
unit, and warm air output by the outdoor unit.
n Function test of the indoor unit and all program
sequences.
n Check of the surface temperature of the suc-
tion pipe and that the vaporiser is not overheating. To measure the temperature, hold the
thermometer to the suction pipe and subtract
the boiling point temperature reading on the
pressure gauge from the measured temperature.
n Record the measured temperatures in the
commissioning report.
43
Page 44
REMKO RXT series
Function test of the cooling and heating modes
1.Remove the protective caps from the valves.
2.Start the commissioning procedure by briefly
opening the shut-of
unit until the pressure gauge indicates a
pressure of approx. 2 bar.
3.Check all connections for leaks with leak
detection spray and suitable leak detectors.
4.If no leaks are found, fully open the shut-of
valves by turning them anti-clockwise using a
spanner. If leaks are found, remedy the faulty
connection. It is imperative that the vacuum
creation and drying steps are repeated.
5.Activate the main circuit breaker or fuse.
6.Use the remote control to switch on the unit
and select the cooling mode, maximum fan
speed and lowest target temperature.
7.Check the overheating, outside, inside, outlet
and vaporisation temperatures and record
the measured values in the commissioning
report. Check the correct function and settings of all regulation, control and safety
devices.
8.Check the unit control system using the functions described in the chapter "Operation".
T
imer, temperature setting, fan speeds and
switching to ventilation or dehumidification
mode.
9.Check the correct function of the condensate
drainage line by pouring distilled water into
the condensate tray
recommended for pouring the water into the
condensate tray.
10.Switch the indoor unit to heating mode.
11.During the test run, check the functionality of
all of the previously described safety devices.
12.Record the measured values into the commissioning report and familiarise the operator
with the system.
13.Remove the pressure gauge. Check that
seals have been fitted in the sealing caps.
14.Re-install all disassembled parts.
f valves on the outdoor
f
. A bottle with a spout is
11 Shut-down
Temporary shut-down
1.Allow the indoor unit to run for 2 to 3 hours in
air circulation mode or in cooling mode at the
maximum temperature setting in order to
remove any residual moisture from the unit.
2.Shut down the system using the remote control.
3.Switch of
4.Check the unit for visible signs of damage
and clean it as described in the chapter
"Care and maintenance"
Permanent shut-down
Ensure that equipment and components are disposed of in accordance with the applicable regulations, e.g. through authorised disposal and recycling specialists or at collection points.
REMKO GmbH & Co. KGor your contractual
partner will be pleased to provide a list of certified
firms near you.
f the voltage supply to the unit.
44
Page 45
12 Troubleshooting, customer service and fault analysis
12.1 Troubleshooting and customer service
The unit and components are manufactured using state-of-the-art production methods and tested several
times to verify their correct function. However
detailed in the list below. For systems with an indoor unit and outdoor unit, refer to the chapter "Troubleshooting and customer service" in both operating manuals. Please inform your dealer if the unit is still not
working correctly after all function checks have been performed!
Operational malfunctions
MalfunctionPossible causesChecksRemedial measures
, if malfunctions should occur, please check the functions as
The unit does not start or
switches itself of
f
Power failure, undervoltage, defective mains
fuse / main switch in
OFF position
Damaged power supplyDoes all other elec.
Wait time after switching
on is too short
Temperature outside
operating range
Electrical surges caused
by thunderstorms
Malfunction of the
external condensate
pump
High-pressure / low-pressure switches have triggered
Does all other electrical
equipment function correctly?
equipment function correctly?
Have approx. 5 minutes
elapsed since the
restart?
Are the fans in the indoor
unit and outdoor unit
working correctly?
Have there been lightning strikes in the area
recently?
Has the pump shut down
due to a malfunction?
Check refrigerant pressure and look for leaks if
necessary
Check the voltage and if
necessary
come back on
Repair by specialist firm
Schedule longer wait
times
Observe temperature
ranges of indoor unit and
outdoor unit
Switch off the mains
breaker and switch it
back on. Have it
inspected by a specialist
Check and if necessary
clean the pump
Rectify leakage and restart
, wait for it to
Transmission distance
too far / receiver af
by interference
Defective remote controlIs the unit running in
Receiver or transmitter
unit exposed to exces-
The unit does not
respond to the remote
control
45
sive solar radiation
Electromagnetic fields
are interfering with transmission
Key in remote control
jammed / two buttons
pressed at same time
Batteries in remote control are flat
fected
Does the indoor unit
beep when pressing a
key?
manual mode?
Does it function correctly
in the shade?
Does it function after
removing potential
sources of interference?
Does the “Transmitting”
symbol appear on the
display?
Have new batteries been
inserted? Is the display
incomplete?
Reduce the distance to
less than 6 m or change
position
Replace the remote control
Place the receiver and/or
transmitter unit in the
shade
Signal is not transmitted
when interference
sources are operational
Release the key / only
press one key
Insert new batteries
Page 46
REMKO RXT series
MalfunctionPossible causesChecksRemedial measures
The unit is running but
only provides reduced or
no cooling or heating
capacity
Filter is dirty / air inlet /
outlet opening is blocked
by debris
Windows and doors
open. Heating / cooling
load has increased
Neither cooling nor
heating mode has been
set
Fins on outdoor unit
blocked by foreign
objects
Leaking cooling cycleAre there signs of frost
Outdoor unit iced upCheck outdoor unit. Has
Drainage pipe on collection container clogged /
damaged
Have the filters been
cleaned?
Have structural / usage
modifications been
made?
Does the cooling symbol
appear on the display?
Is the fan on the outdoor
component running? Are
the fins unobstructed?
on the exchanger fins of
the indoor unit?
the cassette probe on
the outdoor unit been
correctly positioned?
Can the condensate
drain of
obstruction?
f without any
Clean the filters
Close windows and
doors / install additional
units
Correct the settings for
the unit
Check the fan or winter
fan speed control,
reduce the air resistance
Repair by specialist
De-ice and fit the probe
at the point where the
most ice forms
Clean the drainage pipe
and collection container
Condensate discharge
on unit
NOTE
Faulty external condensate pump or float
Condensate has not
drained away and has
collected in the condensate drainage line
Condensate does not
drain of
Float is stuck or jammed
due to excessive dirt
f
Is the collection tray full
of water and the pump
not running?
Is there an incline on the
condensate drainage
line? Check there is no
blockage in the pipe.
Are the condensate
drainage lines unblocked
and is there a steady
incline? Are the condensate pump and liquid
level switch functioning
correctly?
Are the LEDs on the
receiver unit of the
indoor unit flashing?
Call out a specialist to
replace the pump
Route the condensate
drainage line with an
incline and clean
Route the condensate
drainage line with an
incline and clean it. If the
liquid level switch or the
condensate pump is
defective, have them
replaced
Should be cleaned by
specialist firm
If the outdoor unit makes noises at low outside temperatures, even although it is switched off, this is not a
malfunction. This is the winding of the compressor being run briefly in order to heat up the oil within it and
also to guarantee the viscosity at low ambient temperatures. If you do not use the unit in the winter then
you can switch off the breaker
will be required!
. Switch it back on again at least 12 hours before the next time that the unit
46
Page 47
Malfunction indicated by flashing code RXT 525-1405 DC
Number
Error description
EEPROM error, indoor unit1OFFE0
Communication error between indoor unit and outdoor unit2OFFE1
Safety shut-down due to low outside temperature4FLASHESP3
Compressor control faulty5FLASHESP4
Mode conflict6FLASHESP5
Low pressure alarm7FLASHESP6
47
Page 48
YES
REMKO RXT series
Probe resistance
Indoor unit probe, evaporator; indoor unit probe, ambient air
Temperature [°C]Resistance [kW]
035.20
526.88
1020.72
1516.12
2012.64
2510.00
307.97
356.40
12.2 Indoor unit fault analysis
Error code:E0 / F4
Reason:The control board of the outdoor unit or indoor unit cannot read the unit memory
(EEPROM)
Cause:
Switch off voltage, switch on again 2 minutes
later
Replace the circuit boards of the outdoor unit
and indoor unit in turn, in order to locate the
n Installation error
n Control boards of outdoor unit or indoor unit defective
. Is the error still present?
defective EEPROM
48
Page 49
Error code:E1
YES
NO
YES YES
YES
NO
NO
YES
NO
Reason:The indoor unit does not receive a signal from the outdoor unit within 110 seconds.
Cause:
Switch off voltage, switch on again 2 minutes
later
Measure the voltage between the “S” and “N”
terminals of the outdoor unit. Is the measured
Check electrical connections in the outdoor
n Electrical connection not configured correctly
n Control boards outdoor unit or indoor unit defective
. Is the error still present?
value positive?
unit. Are they OK?
Is the transformer OK?
Check electrical connections in the indoor unit.
Are they OK?
Replace the control boards of the indoor unit. Is
the fault remedied?
Replace the control boards of the outdoor unit
Replace the transformer
Replace the control boards of the outdoor unit.
Is the fault remedied?
Replace the control boards of the indoor unit
49
Page 50
NO
YES
NO
YES
NO
YES
NO
YES
NO
REMKO RXT series
Error code:E3 / F5
Reason:If the fan speed of the indoor unit/outdoor unit falls below 300 rpm, the unit switches off
and the display shows error code E3 or E5
Cause:
Switch off voltage, switch on again 2
minutes later
De-energise the unit and attempt to
turn the fan wheel by hand. Does it
Check the electrical connections.
Are these correctly implemented?
Measure the voltage at the corre-
sponding connector plug on the con-
trol board (see section
dure’ on page 51). Does the
measured voltage lie within the toler-
n Electrical connection faulty
n Evaporator fan wheel defective
n Evaporator fan motor defective
n Control board faulty
. Is the error still
present?
rotate freely?
Ä
‘Proce-
ance range?
The unit operates normally.
Check the motor and the fan
wheel bearing, and replace the
defective parts.
Correctly establish the electrical
connection
Replace the control board.
Replace the fan motor. Is the fault
remedied?
50
Page 51
Procedure
13 4 5 6
DC fan motor of the indoor unit (control chip is installed in the motor):
Switch on the voltage to the unit. In standby mode, measure the unit between terminals 1-3 and 4-3 of the
connector plug. Check the measured values against those listed in the table below
problem with the control board and it must be replaced.
. If these differ, there is a
Fig. 52: Motor measurements
TerminalColourVoltage
1Red280V~380 V
2------
3Black0 V
4White17-17.5V
5Yellow0~5.6V
6Blue17-17.5V
DC fan motor of the outdoor unit (control chip is installed in the motor):
Measure the resistance between terminals 1-3 and 4-3. This should be roughly identical. If the resistance
deviates significantly, assume that the motor is defective and must be replaced.
51
Page 52
YES
JOO
NO YES
JOO
NO
REMKO RXT series
Error code:EC
Reason:The evaporator probe T2 measures the actual value with the compressor start and takes
this as the reference value T
has not dropped by 2 °C for at least 4 seconds then the system assumes that the refrig-
erant is low
error code "EC".
. The measurement is performed a total of 3 times before the display shows the
. If, 5 minutes after the compressor start, the value T
Start
Start
Cause:
Switch off voltage, switch on again 2 minutes
later. Is the error still present?
Check whether the indoor unit blows out cold
Check the cooling circuit for leaks. Leaks
Check the cooling circuit for any blockages. Are
the shut-of
n Refrigerant low or cooling circuit blocked
n Evaporator probe T2 defective
n Indoor unit control board defective
.
air
found?
f valves on the outdoor unit open?
Check the position and function of the evapo-
rator probe T2. Is it correctly seated and with
the correct resistance?
Exchange the control boards of the indoor unit.
Remedy leaks and put the unit back into opera-
tion.
52
Page 53
Error code:E4 / E5 / F1 / F2 / F3
NO
YES
NO
YES
Reason:If the test voltage of the probes is lower than 0.06 V or higher than 4.94 V then the display
shows the error code of the corresponding probe.
Cause:
Check the connecting cable between the control board and the temperature probe. Is it OK
Check the probe for correct resistance,
depending on the temperature (see resistance
Replace the corresponding control board.
n Electrical connection faulty
n T
emperature probe defective
n Control board defective
and correctly connected?
table)
Establish a proper connection.
Replace the probe.
Fig. 53: Check the probes
53
Page 54
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
REMKO RXT series
Error code:F0
Reason:Safety shutdown due to overly high current consumption of individual unit components
Cause:
Check the supply voltage. Is this correct?
Check the cooling circuit for any blockages. Is
Check the winding resistances of the com-
Check the electrical connections. Are these cor-
n Faulty power supply
n Cooling circuit blocked
n Faulty control board
n Electrical connections faulty
n Compressor defective
the cooling circuit OK?
pressor
. Are they OK?
rectly implemented?
Switch the unit off and ensure correct supply
voltage.
Remove the blockage (shut-off valve open?)
Replace the compressor.
Replace or correct the electrical connections.
Does the transformer operate fault-free?
Replace the outdoor unit.
Replace the transformer or control boards of
the outdoor unit.
54
Page 55
Error code:P0
JOO
NO
NO
YES
NO
YES
NO
YES
Reason:If the power supply to the compressor controller is faulty, the display shows the error code
“P0” and the unit switches of
f
Cause:
Check the connecting cables between the con-
trol board and compressor? Are they faulty?
Check the inverter controller (see section
Ä
‘Check the inverter controller’ on page 55).
Check the condenser fan motor. Is it working
Check the winding resistances of the com-
n Electrical connection faulty
n Faulty control board
n Condenser fan motor defective or blocked
n Compressor defective
Fault eliminated?
correctly?
pressor
. Are they OK?
Establish a correct connection between the
control board and compressor
Replace the control board.
See troubleshooting fault F5
Replace the compressor.
.
Exchange the control boards of the outdoor
unit.
Check the inverter controller
Switch off the power supply to the unit. Wait until the capacitors are fully discharged and disconnect the compressor from the control board.
Check the resistances at the outputs of the control board with the aid of a digital voltmeter as follows:
VoltmeterNormal resistance
(+) Red(-) Black
U
V
N
W
(+) Red
¥
(multiple MW)
55
Page 56
NO
YES
NO
YES
NO
YES
NO
YES
REMKO RXT series
Error code:P1
Reason:Overvoltage or undervoltage protection has tripped
Cause:
Check the power supply. Is the supply voltage
Check the electrical connections. Are they OK?
Switch the power on and put the unit into
standby mode. Measure the voltage on the
board, at contacts "P" and "N". This should be
approx. 310 V
the unit. The voltage between "P" and "N"
should now be between 220-400V. Is the cor-
Check the transformer. Is a defect present?
n Faulty supply voltage
n Refrigerant low or cooling circuit blocked
n Faulty control board
correct?
, 340 V or 380 V DC. Now start
rect voltage applied?
Switch the unit off and have the power supply
checked/corrected.
Replace the electrical connections.
Replace the control board.
Replace the control board.
Replace the transformer.
56
Page 57
Error code:P2 (with units with a thermal contact)
JOO
NO
YES
NO
YES
NO
YES
YES
NO
JOO
Reason:If the test voltage of the thermal contact does not lie at 5 V, then the display shows the
error message “P2”
Cause:
Check the air flow
volumes of the
indoor unit and out-
door unit. Are they
blocked or dirty?
Switch off the power
supply to the unit
and switch it on
again after 10 mins.
Does the unit start
up?
Check the tempera-
ture of the com-
pressor
heated up?
n Faulty supply voltage
n Refrigerant low or cooling circuit blocked
n Faulty control board
. Has it
Clean the filter or heat exchanger and ensure a sufficient air flow volume.
Check the thermal contact. Is it correctly connected?
Measure the resistance of the thermal contact.
Is it 0?
Connect it correctly.
Check the cooling
circuit. Is it OK?
Replace the thermal
contact.
Replace the control board of the outdoor unit.
57
Page 58
JOO
NO
NO
YES
NO
YES
NO
YES
1
REMKO RXT series
Error code:P4
Reason:Safety shutdown of inverter controller. Internal system monitoring triggered (e.g. communi-
cation problem between board and compressor
, the compressor speed is not OK)
Cause:
Check the electrical connection between the
control board and compressor
Check the inverter controller. Is this functional?
Check the condenser fan motor. Is it OK?
Check the winding resistances of the com-
n Faulty electrical connections
n Inverter regulation on board defective
n Condenser fan motor defective
n Compressor defective
n Control board defective
. Are these cor-
rectly implemented?
pressor
. Are they OK?
Establish a proper connection.
Replace the control board.
Follow the instructions for troubleshooting fault
F5
Replace the compressor
Replace the control boards of the outdoor unit.
Check individual components
Check the temperature probes
Disconnect the temperature probe from the control board and measure the resistance on the plug's contacts.
1: Multimeter
Error code:dF
Reason:The unit is in heating mode and the outdoor unit is being defrosted. After the defrost phase,
the indoor unit automatically switches back to the last operating mode.
58
Page 59
12.3 Resistances of the
temperature probes
Probe T1, T2, T3 and T4
Temp.
(°C)
-20115.271218.72
-19108.151317.80
-18101.521416.93
-1796.341516.12
-1689.591615.34
-1584.221714.62
-1479.311813.92
-1374.541913.26
-1270.172012.64
-1166.092112.06
-1062.282211.50
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Temp.
(°C)
444.39791.21
454.21801.17
464.05811.14
473.89821.10
483.73831.06
493.59841.03
503.45851.00
513.32860.97
523.19870.94
533.07880.91
542.96890.88
552.84900.85
562.74910.83
572.64920.80
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
-958.712310.97
-856.372410.47
-752.242510.00
-649.32269.55
-546.57279.12
-444.00288.72
-341.59298.34
-239.82307.97
-137.20317.62
035.20327.29
133.33336.98
231.56346.68
329.91356.40
428.35366.13
526.88375.87
625.50385.63
582.54930.78
592.45940.75
602.36950.73
612.27960.71
622.19970.69
632.11980.67
642.04990.65
651.971000.63
661.901010.61
671.831020.59
681.771030.58
691.711040.56
701.651050.54
711.591060.53
721.541070.51
731.481080.50
724.19395.40
822.57405.18
921.81414.96
1020.72424.76
1119.69434.57
59
741.431090.48
751.391100.47
761.341110.46
771.291120.45
781.251130.43
Page 60
REMKO RXT series
Temp.
(°C)
1140.421270.30
1150.411280.29
1160.401290.28
1170.391300.28
1180.381310.27
1190.371320.26
1200.361330.26
1210.351340.25
1220.341350.25
1230.331360.24
1240.321370.23
1250.321380.23
1260.311390.22
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Temp.
(°C)
1682.545118.96
1778.795218.26
1875.245317.58
1971.865416.94
2068.665516.32
2165.625615.73
2262.735715.16
2359.985814.62
2457.375914.09
2554.896013.59
2652.536113.11
2750.286212.65
2848.146312.21
2946.116411.79
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Probe T5
Temp.
(°C)
-20542.7-2200.7
-19511.9-1190.5
-18483.00180.9
-17455.91171.9
-16430.52163.3
-15406.73155.2
-14384.34147.6
-13363.35140.4
-12343.66133.5
-11325.17127.1
-10307.78121.0
-9291.39115.2
-8275.910109.8
-7261.411104.6
-6247.81299.69
-5234.91395.05
-4222.81490.66
-3211.41586.49
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
3044.176511.38
3142.336610.99
3240.576710.61
3338.896810.25
3437.30699.90
3535.78709.57
3634.32719.25
3732.94728.94
3831.62738.64
3930.36748.36
4029.15758.08
4128.00767.82
4226.90777.57
4325.86787.32
4424.85797.09
4523.89806.86
4622.89816.64
4722.10826.43
4821.26836.23
4920.46846.03
5019.69855.84
60
Page 61
Temp.
(°C)
865.661092.86
875.491102.78
885.321112.70
895.161122.63
905.001132.56
914.851142.49
924.701152.42
934.561162.36
944.431172.29
954.291182.23
964.171192.17
974.051202.12
983.931212.06
993.811222.01
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
1003.701231.96
1013.601241.91
1023.491251.86
1033.391261.81
1043.301271.76
1053.201281.72
1063.111291.67
1073.031301.63
1082.94
61
Page 62
REMKO RXT series
13 Care and maintenance
Regular care and observation of some basic points
will ensure trouble-free operation and a long
service life.
This enables you to ensure the operational reliability of the plant at all times!
DANGER!
Prior to performing any work, ensure the equipment is disconnected from the voltage supply
and secured to prevent accidental switch-on!
Care
n Ensure the unit is protected against dirt, mould
and other deposits.
n Only clean the unit using a damp cloth. Do not
use any caustic, abrasive or solvent-based
cleaning products. Do not use a jet of water.
n Clean the fins on the unit prior to long shut-
down periods.
Maintenance
n It is recommended that you take out a mainte-
nance contract with an annual service from an
appropriate specialist firm.
Type of task
Checks/maintenance/inspection
General
n For systems which operate year-round (e.g. in
server rooms), the maintenance intervals must
be reduced accordingly
NOTICE!
Statutory regulations require an annual leak test
for the cooling cycle dependant on the refrigerant quantity. Inspection and documentation of
the work performed is to be carried out by specialist technicians.
Commis-
sioningMonthly
l
.
Half-
yearlyYearly
l
Check voltage and current
Check function of compressor/fans
Dirt on condenser/evaporator
Check the refrigerant volume
Check condensate drainage
Check insulation
Check moving parts
Sealing test for cooling cycle
1)
see note
Cleaning the housing
1.Disconnect the power supply to the unit.
2.Open the air inlet grill on the front side and
fold it forwards or backwards.
3.Clean the grill and cover with a soft, damp
cloth.
4.Close the grill.
5.Switch the power supply back on.
l
l
ll
l
l
l
l
l
Air filter for indoor unit
Clean the air filter at intervals of no more than 2
weeks. Reduce this interval if the air is especially
.
dirty
l
l
l
l
l
l
1)
l
62
Page 63
Cleaning the filter
1.Disconnect the power supply to the unit.
2.Open the front side of the unit by folding the
grill down/forwards (
3.Pull the filter out in an upwards direction
(Fig. 54).
4.Clean the filter with a commercially available
vacuum cleaner
so it is facing upwards (Fig. 55).
5.Dirt can also be removed by carefully
cleaning with lukewarm water and mild
cleaning agents (
should be face down.
6.If water is used, let the filter dry out properly
in the air before fitting it back into the unit.
7.Carefully insert the filter
locates correctly.
8.Close the front side as described above in
reverse order
9.Switch the power supply back on.
10.Switch the unit back on.
.
Fig. 54).
. To do so, turn the dirty side
Fig. 56). The dirty side
. Ensure that it
Fig. 55: Cleaning with a vacuum cleaner
Cleaning the condensate pump (accessories)
The indoor unit may contain an optional integrated
or separate condensate pump, which pumps out
any accumulated condensate into higher positioned drains.
Observe the care and maintenance instructions in
the separate operating manual
Fig. 54: Fold the guard forwards
Fig. 56: Cleaning with lukewarm water
63
Page 64
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
30
25
26
27
28
29
REMKO RXT series
14 Exploded view and spare parts lists
14.1 Exploded view - Indoor unit RXT 525-685 DC
Fig. 57: Exploded view of the unit RXT 525-685 DC IT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
64
Page 65
14.2 Spare parts list - Indoor unit RXT 525-685 DC
IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial
number (see type plate)
No. Designation
1Air inlet grill
2Front panel
3Evaporator
4Temperature probe, evaporator
5Side covering, left
6Wall bracket, left
7Fan wheel
8Fastening protection
9Display board
10Air filter
11Air outlet fins
12Housing
TANT!
13Wall bracket, right
14Fan motor
15Fin motor
16Fin motor (vertical)
17Condensate tray
18Infrared remote control
19Inverter module
20Temperature probe, indoor air
21Transformer
22Control board
23E-box cover
24Side covering, right
25Air outlet fin (vertical)
26Fan casing (rear)
27Fan casing (front)
28Fan motor mount
29Fan motor mounting plate
30Cooling fin
65
Page 66
1
1
2
3
4
5
6
7
8
9
10
11
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
33
32
REMKO RXT series
14.3 Exploded view - Indoor unit RXT 1055-1405 DC
Fig. 58: Exploded view of the unit RXT 1055-1405 DC IT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
66
Page 67
14.4 Spare parts list - Indoor unit RXT 1055-1405 DC
No. Designation
1Air inlet grill (large)
2Air inlet grill (small)
3Front panel
4Evaporator
5Temperature probe, evaporator
6Side covering, left
7Wall bracket, left
8Fan wheel
9Fastening protection
10Display board
11Air filter (large)
12Air filter (small)
13Air outlet fins
14Housing
15Wall bracket, right
16Fan motor
17Fin motor (vertical)
18Condensate tray
19Infrared remote control
20Inverter module
21Temperature probe, indoor air
22Transformer
23Control board
24E-box cover
25Side covering, right
26Air outlet fin (vertical)
27Fan casing (rear)
28Fan casing (front)
29Fan motor mount
30Fan motor mounting plate
31Cooling fin
32Fin motor
33Refrigerant connections cover
67
Page 68
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
REMKO RXT series
14.5 Exploded view - Outdoor unit RXT 525 DC
Fig. 59: Exploded view of the unit RXT 525 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
68
Page 69
14.6 Spare parts list - Outdoor unit RXT 525 DC
IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial
number (see type plate)
No. Designation
1Cover panel
2Protection grid, front wall
3Front panel
4Fan blade
5Fan motor
6Fan motor mounting plate
7Corner panel, left
8Condenser
9Air inlet temperature probe
10Electronic injection valve
11Shut-off valve, injection pipe
124-way reversing valve
TANT!
13Shut-off valve, suction pipe
14Partitioning panel
15Temperature probe for heat gas line
16Compressor
17Floor panel
18Side panel, right
19Refrigerant connections cover
20Control board
21Auxiliary circuit board
22Temperature probe for condenser outlet
23Condensate tray heating
24Crankcase heating
69
Page 70
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
REMKO RXT series
14.7 Exploded view - Outdoor unit RXT 685 DC
Fig. 60: Exploded view of the unit RXT 685 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
70
Page 71
14.8 Spare parts list - Outdoor unit RXT 685 DC
No. Designation
1Cover panel
2Protection grid, front wall
3Front panel
4Fan blade
5Fan motor
6Fan motor mounting plate
7Corner panel, left
8Condenser
9Air inlet temperature probe
10Electronic injection valve
11Shut-off valve, injection pipe
124-way reversing valve
13Shut-off valve, suction pipe
14Partitioning panel
15Temperature probe for heat gas line
16Compressor
17Floor panel
18Side section, right
19Refrigerant connections cover
20Terminal block cover
21Control board
22Inverter board
23Cooling fins
24Temperature probe for condenser outlet
25Mounting plate for refrigerant connections
26Transformer
27Condensate tray heating
28Crankcase heating
71
Page 72
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
REMKO RXT series
14.9 Exploded view - Outdoor unit RXT 1055 DC
Fig. 61: Exploded view of the unit RXT 1055 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
72
Page 73
14.10 Spare parts list - Outdoor unit RXT 1055 DC
No. Designation
1Cover panel
2Protection grid, front wall
3Front panel
4Fan blade
5Fan motor
6Fan motor mounting plate
7Side panel, left
8Recessed grip side panel, left
9Temperature probe for condenser outlet
10Temperature probe for condenser outlet
11Temperature probe for heat gas line
12Air inlet temperature probe
134-way reversing valve
14Shut-off valve, suction pipe
15Inverter board
16Control board
17Liquid separator
18Transformer
19Side panel, right
20Terminal block cover
21Shut-off valve cover
22Recessed grip front panel, right
23Front panel, right
24Low pressure switch
25Electronic injection valve
26Shut-off valve, injection pipe
27High pressure switch
28Compressor
29Partitioning panel
30Floor panel
31Shut-off valve mounting plate
32Condensate tray heating
33Crankcase heating
73
Page 74
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
REMKO RXT series
14.11 Exploded view - Outdoor unit RXT 1405 DC
Fig. 62: Exploded view of the unit RXT 1405 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
74
Page 75
14.12 Spare parts list - Outdoor unit RXT 1405 DC
No. Designation
1Cover panel
2Protection grid, front wall
3Front panel
4Fan blade
5Fan motor
6Fan motor mounting plate
7Side panel, left
8Condenser
94-way reversing valve
10Shut-off valve, suction pipe
11Partitioning panel
12Shut-off valve, injection pipe
13Air inlet temperature probe
14Temperature probe for condenser outlet
15Compressor
16Control board
17Floor panel
18Shut-off valve mounting plate
19Temperature probe for heat gas line
20Auxiliary circuit board
21High pressure switch
22Inverter board
23Transformer
24Transformer
25Front panel, right
26Transformer
27Low pressure switch
28Liquid separator
29Refrigerant connections cover
30Condensate tray heating
31Crankcase heating
32Terminal block cover
33Side panel, right
75
Page 76
REMKO RXT series
15 Index
A
Assembly
Strip foundation ...................... 34
C
Care and maintenance ................... 62
Cleaning
Air filter for indoor unit ................. 62
Condensate pump ....................63
Housing ............................ 62
Condensate drainage connection and safe
drainage .............................. 34
Customer service ....................... 45
D
Display on indoor unit .................... 15
Disposal of equipment .....................8
E
Electrical drawings ..............39, 40, 41, 42
Electrical wiring ......................... 36
Electrical wiring diagram ............... 37, 38
Environmental protection ...................8
Exploded view of the unit ... 64, 66, 68, 70, 72, 74