Remko RVT 681 DC user guide manual

REMKO RVD...DC
RVD 351DC, RVD 521DC, RVD 681DC, RVD 1051DC
Inverter ceiling-mounted air conditioner in split design
Operation · Technology · Spare parts
Edition GB – W09
Contents
Safety notes
Environmental protection and recycling
Warranty
Intended use
Transport and packaging
Description of the equipment
Operation
Shutdown
Care and maintenance
Installation instructions for qualified personnel
Installation
Tightness check
Condensate drain
4
4
4
4
5
5
6-12
13
13-14
15-18
18-19
20
20
Before commissioning
Electrical connection
Electrical connection diagram
Electrical circuit diagram
Add refrigerant
Commissioning
Troubleshooting and customer service
Resistances of the temperature- and hot gas sensors
Unit dimensions
Exploded view
Spare parts list
Technical data and performance charts for heating
EC-Declaration of Conformity
21
21
22
23-26
27
27-28
29-41
42-44
45
46-47
46-47
48-49
50
Made by REMKO
These operating instructions should be read carefully prior to commissioning / operation of the equipment!
Subject to modifications; No liability accepted for errors or misprints!
3
REMKO RVD...DC
Safety notes
Carefully read this manual before putting commissioning the equipment. It provides useful tips and information as well as hazard warnings to prevent injury or material damage . Failure to follow the directions in this manual can result in endangerment to persons, the environment and the equipment itself and will void any claims for liability.
Keep this manual and the
refrigerant datasheet near the unit.
The unit may only be set up and
installed by qualified personnel.
The setup, connection and
operation of the unit and its components must be in accordance with the operating conditions stipulated in this manual and comply with all applicable local regulations.
Mobile units must be set up
securely on suitable surfaces and in an upright position. Stationary units must be permanently installed for operation.
Modification of equipment
and components supplied by REMKO is not permitted and can cause malfunctions.
Equipment and components
may not be operated in areas where there is an increased risk of damage. Observe the minimum clearances.
The electrical voltage supply
is to be adapted to the requirements of the equipment.
The operational safety of
equipment and components is only assured if they are used as intended and fully assembled. Safety devices may not be modified or bypassed.
Do not operate equipment
or components with obvious defects or signs of damage.
All housing parts and openings,
e.g. air inlets and outlets, must be free of foreign objects, fluids or gases.
The equipment and components
must be kept an adequate distance from flammable, explosive, combustible, aggressive and dirty areas or atmospheres.
Touching equipment parts can
result in burns or injury.
Installation, repair and
maintenance work may only be carried out by authorised specialists. Visual inspections and cleaning can be performed by the operator as long as the equipment is not under voltage.
Take appropriate hazard
prevention measures when performing installation, repair or maintenance work or cleaning the equipment.
The equipment or components
are not to be exposed to any mechanical stresses, extreme levels of humidity or direct sunlight.
Warranty
Prerequisite for any warranty claims are that the purchaser or their customer has completely filled out the "warranty registration card" and commissioning report included with the unit at the time when the equipment was purchased and first put into operation and returned it to REMKO GmbH & Co. KG. The warranty conditions are listed in the "General Business and Delivery Conditions". Only the contractual parties can strike special agreements beyond these conditions. For this reason please first contact your direct contractual partner.
Environmental protection and recycling
Disposal of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufacture of the devices and components, Help protect the environment by ensuring that the devices or components (for example batteries) are not disposed in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. through authorised disposal and recycling specialists or at collection points.
Intended use
Depending on the model, the equipment and the additional fittings with which it is equipped is only intended to be used as an air-conditioner for the purpose of cooling or heating the air in an enclosed room. Different or additional use shall not be classed as intended use. The manufacturer/supplier assumes no liability for damages arising from an unintended use of the equipment. The user bears the sole risk in such cases. Using the equipment as intended also includes working in accord­ance with the operating manual and installation instructions and complying with the maintenance requirements.
4
M
M
RXT 351 DC
T2
T
3
T5
M
M
TE
PS H
T1
T2
T
3
T5
P
S
L
RXT 1051 DC
M
M
PS H
T1
T2
T
3
TE
T5
P
S
L
Transport and Packaging
The equipment is shipped in sturdy transport packaging. Immediately check the equipment on delivery and make a note of any damage or miss­ing parts on the delivery note. Inform the forwarding agent and contractual partner. Warranty claims at a later date will not be accepted.
Description of the equipment
The RVD 351-1051DC room air conditioning units have a REMKO RVD...AT outdoor component as well as an indoor unit RVD...IT.
The outdoor unit serves to output the heat extracted by the indoor unit from the room being cooled. In heating operation, the heat absorbed by the outdoor compo­nent can be discharged through the indoor unit into the room being heated.SFlbIn both operating modes, the performance of the compressor precisely adjusts itself to the de­mand, thereby regulating the target temperature with minimal tempera­ture variations. This "inverter-tech­nology" enables power saving over conventional split systems and also reduces noise emissions to a particu­larly low level. The outdoor component is mounted outdoors or under the observa­tion of certain requirements it may be installed indoors. The outdoor component consists of a refrigerant circuit with compressor, fin liquefier, liquefier fan, reverse flow valve and flow regulator. The outdoor unit is controlled via the regulation of the indoor unit.
The indoor unit is designed for indoor installation in suspended ceilings with Euroraster dimensions. The cassette is hidden behind the suspended ceiling, only its cover is visible. Operation is undertaken via an infrared remote control unit. The indoor unit consists of a fin vapor­iser, vaporiser fan, regulation system and condensation pan.
Floor consoles, wall consoles, re­frigerant pipes and a winter control program are available as accessories.
Schematic of refrigerant circuit series RVD 351-1051 DC
RVD 351 DC
RVD 521-681 DC
RVD 1051 DC
T2
M1
T2
M1
T2
M1
T3
M1 - Condenser fan M2 - Compressor M3 - Vaporiser fan IU V1 - Reversing valve C/H EEV - Elec. Expansion valve PSH - High pressure switch OU
V1
T1
M2
T3
Filter
PSL
V1
M2
T3
PSL
V1
M2
Oil return
EEV
EEV
Filter
PSH
T1
Filter
PSH
T1
FilterFilter
PSL - Low pressure switch OU T1 - Sensor hot gas OU T2 - Sensor air intake OU T3 - Sensor condenser OU T4 - Sensor air intake IU T5 - Sensor vaporiser IU
Indoor areaOutdoor area
M3
M3
M3
IU - Indoor unit OU - Outdoor unit
System layout
Indoor area
Indoor unit
Condensate drain
Outdoor area
Outdoor unit
Control line
Power output
Injection pipe
suction pipe
Condensate line
Shut-off valve
Condenser fan
The connection between the indoor unit and the outdoor component is made with refrigerant pipes.
T5
T4
T5
T4
T5
T4
5
REMKO RVD...DC
Operation
The indoor unit is easy to operate using an infrared remote control. This is supplied as standard. The indoor unit beeps to acknowledge the correct transmission of data. If it is not possible to program the indoor unit using the remote control, it can also be manually operated.
Manual operation
The indoor units can be started manually. Press the RESET button on the receiver unit of the cover to activate automatic mode. In manual operation, the following settings apply:
Cooling mode: 24 °C, Fan speed AUTO Heating mode: 26 °C, Fan speed AUTO
Pressing any button on the infra­red remote control interrupts manual operation
Display on indoor unit
The lit display LEDs indicate the settings.
LED “Operation” green = Operation screen LED “Timer” yellow = Timer mode LED “Pre/Def” red = Defroster mode LED “Alarm” red = Malfunction screen
Display RVD 351-521 DC
Display on indoor unit
Unit for receiving signals from the remote control
Operation-
screen
Timer­screen
Defrost
Display RVD 681-1051 DC
Display on indoor unit
Fan
Alarm display
infrared remote control
The infrared remote control sends the programmed settings over a distance of up to 6 m to the re­ceiver of the indoor unit. Data will only be received correctly if the remote control is pointed at the re­ceiver and no objects are obstruct­ing the transmission path.
First insert the supplied batteries (2 x type AAA) into the remote control. To do so, pull off the flap of the battery compartment and insert the batteries according to their polarization (see marks).
Operation-
screen
Maximum distance
max. 6 m
Timer­screen
Display
screen
Fan
Defrost
Alarm display
Infrared receiver
! CAUTION
Problems are shown in code (see chapter Troubleshooting and Customer service).
NOTE
Immediately replace flat batter­ies with a new set, otherwise there is a risk of leakage. It is recommended that the batteries are removed if the equipment is shut down for long periods.
6
Keys on the remote control
Keys on the remote control
"ON/OFF"key
Press this key to operate the unit.
"MODE" key
Press this key to select the operating mode. The indoor unit has 4 modes:
1. Automatic mode In this mode, the unit works in cooling or in heating mode.
2. Cooling mode In this mode, the warm air in the room is cooled down to the desired temperature.
3. Dehumidification mode In this mode the room is mainly dehumidified and the adjusted temperature is maintained.
4. Heating mode In this mode, the warm air in the room is warmed to the desired temperature.
5. Air circulation mode In this mode, the air in the room is circulated with no change in temperature.
"FAN SPEED" key
Press this key to set the
desired fan speed. 4 speeds are available: Automatic, high, medium and low fan speed.
Key "SLEEP"
Pressing this key
will automatically increase or decrease the target temperature by 1 °C every hour in cooling and heating mode respectively.
Key „SWING HORIZONTAL“
This key directly activates the
oscillating function of the fins for better air distribution in the room.
"TIMER ON" key
This key serves to program the
automatic shut-off time in 0.5 h intervals within the following 24 hours.
"TIMER OFF" key
This key serves to program the
automatic shut-off time in 0.5 h intervals within the following 24 hours.
"RESET" key
This key resets the remote
control to its factory default configuration.
"TURBO"key
The TURBO function activates
the maximum fan speed and the compressor.
"" key
With this key, the desired
temperature can be decreased to 17°C.
"" key
With this key, the desired
temperature can be increased up to 30°C.
"Follow me" function key
With this key, the sensing of the room temperature is moved from the interior unit to the remote control. The temperature measured on the remote control is then transmitted to the interior unit in certain intervals.
"Lock" key
This key can be used to lock
the keys on the remote control. This allows unintentional adjustment to be prevented.
7
REMKO RVD...DC
Remote control display
Indicator arrows will be displayed according to the settings.
Display on indoor unit
Automatic operation
Cooling mode
Dehumidifying mode
Heating mode
Fan speed
Temperature display
Key functions
A symbol is shown on the display to indicate that the settings are being transferred.
Remote control on/off
The remote control's on/off function is shown at the upper right of the remote control by a "wind symbol".
RESET key
The remote control can be reset by pressing the RESET key (recessed key).
ON/OFF key
8
Your air-conditioner is activated and deactivated by pressing the ON / OFF key. The programmed settings and adjustment values before the unit was turned off will appear in the display.
ON/OFF ON/OFF
▲/▼ Keys
Using the key, the target temperature can be adjusted up or down by 1°C. The temperature range lies between 17°C and 30°C
MODE key
Cooling mode
Automatic mode
Use the MODE key to select between individual operating modes. A total of 5 modes are available:
1. Automatic cooling or heating operation
2. Cooling primarily summer mode
3. Dehumidifying operating mode for summer or winter
4. Heating primarily winter mode
5. Circulation air circulation only
Automatic Cooling Dehumidifying Heating
MODEMODEMODE
Air circulation
AUTOMATIC MODE
In automatic mode, the controller autonomously selects between heating, circulation or cooling mode based on the room temperature Tr and the selected target value Ts. The target value can be adjusted between 17°C and 30°C by means of the ▲/▼ keys. The fan speed is selected automatically.
MODE
AUTOMATIC
Operational sequence: If Tr is less than 1K as Ts, then operating mode "Heating" is selected. If Tr is greater than 2K as Ts, then operating mode "Cooling" is selected. If Tr is between Ts -1K as Ts +2K, then operating mode "Circulation" is selected.
If after the compressor is shut down and not required for more than 15 mins. within an operating mode, then, in the event that the room temperature deviates, the corresponding mode heating, cooling or circulation will be selected again.
9
REMKO RVD...DC
Cooling MODE
Dehumidification MODE
In cooling mode, the air in the room is cooled down to the adjusted nominal temperature. The desired room temperature is set with the ▲/▼ keys in 1 °C increments. If the room temperature is 0.5 °C above the selected nominal temperature, then the interior unit starts to cool down the air in the room. If the temperature falls to approx. 1 °C below the set room temperature, the controller will switch off the cooling function. To protect the compressor, the controller only turns cooling on again after a waiting period of 3 minutes.
MODE
It is recommended that the target temperature be set to 24°C in dehumidifying mode. Due to the low temperature of the refrigerant, the dew point of the air at the condenser is undercut. The excess moisture in the air is condensed by the vaporiser, the room is dehumidified.
COOLING OPERATION
HEATING Mode
MODE
In the heating mode, you can heat the room in spring or fall. The selected room temperature is set using the ▲/▼ keys in 1 °C increments. If the room temperature is 1 °C below the selected target temperature, the indoor unit starts to heat the air in the room. If the set room temperature is exceeded by approx. 1 °C, the controller will switch off the heater function. To protect the compressor, the controller will wait 3 minutes before switching on the heating mode again.
MODE
DEHUMIDIFICATION MODE
HEATING OPERATION
10
FAN SPEED Key
The fan speed can be adjusted with this key. A selection can be made between low, medium, high and automatic fan speed.
SWING HORIZONTAL key
Automatic
FAN
Speed
High Medium
FAN
Speed
FAN
Speed
Low
FAN
Speed
The oscillating function of the air fins can be adjusted with this key. This makes it possible to switch directly between a preset position and the oscillating function. The air distribution in the room is improved with the swing function.
Pressing the button for longer than 2s causes the oscillating function to activate. To set your desired position, the button must be pressed for another 2s.
The “Swing Vertical” button has not been assigned a function.
11
REMKO RVD...DC
SLEEP key
TIMER Key
A programming function is activated using this key, which increases the target temperature in cooling mode by 1°C after one hour and by 2°C after 2 hours. In heating mode, the target temperature is decreased by 1 °C after one hour by 2 °C after 2 hours. The unit switches off automatically after 8 hours.
The activation and switch-off time can be programmed with this key. The timer is activated and the time display is switched off by pressing the Timer on or Timer off key. The timer display on the indoor unit illuminates. The desired activation or deactivation time is set by pressing the Timer On or Timer Off keys. When the programmed time has been reached, the device automatically switches on or off. If the indoor unit is automatically switched on, the mode, temperature and fan speed for the last setting are activated. Deleting the preset on and off time early is carried out by pressing the ON/OFF key. The timer display on the interior unit turns off.
TIMER ON Key
TIMER OFF Key
Timer On
Timer Off
Timer On
Timer Off
3 sec.
3 sec.
12
Shutdown
Care and maintenance
Temporary shutdown
1. Allow the indoor unit to run for 2 to 3 hours in air circulation mode or in cooling mode at the maximum temperature setting in order to remove any residual moisture from the unit.
2. Shut down the unit using the remote control.
3. Switch off the voltage supply to the unit.
4. Cover the unit as far as pos­sible with plastic foil in order to protect it from the influences of weather.
Permanent Shutdown
Ensure that equipment and com­ponents are disposed of in accord­ance with local regulations, e.g. through authorised disposal and recycling specialists or at col­lection points.
Regular care and maintenance serves to ensure trouble-free op­eration and long service life of the unit.
! CAUTION
Prior to performing any work, ensure the equipment is iso­lated from the voltage supply and secured to prevent acci­dental switch-on!
NOTE
The statutory regulations require an annual sealing test for the refrigerant circuit in relation to the refrigerant filling level. The inspection and documentation is to be carried out by corresponding specialist engineers.
Care
Ensure the indoor unit and out­door component are protected against dirt, mould and other deposits.
Clean the equipment using a damp cloth. Do not use any caustic, abrasive or solvent­based cleaning products. Do not use a jet of water.
Clean the fins on the indoor unit and outdoor component prior to long shutdown periods.
Maintenance
It is recommended that you take out a maintenance contract with an annual service from an appropriate specialist firm.
Systems which operate year­round (e.g. in server rooms), the maintenance intervals must be reduced accordingly.
TIP
This ensures the operational reliability of your equipment!
Contact REMKO GmbH & Co. KG or your contract partner for a list of specialist companies near you.
Type of task
Checks/Maintenance/Inspections
General
Measure voltage and current
Check compressor/fans are functioning cor­rectly
Check fan is functioning correctly
Dirt on liquefier/vaporiser
Check refrigerant fill quantity
Check condensation drain
Test insulation
Check moving parts
Sealing test for refrigerant circuit
1) see note
Commissioning
Monthly
Six-monthly
Yearly
1)
13
REMKO RVD...DC
Cleaning the cover of the indoor unit
1. Disconnect the supply voltage to the equipment.
2. Open and fold down the air inlet guard on the cover. The filter is held in place by the flaps screwed in at the side of the guard (Fig. 1).
3. Clean the guard using a soft, damp cloth.
4. Switch the supply voltage back on.
Air filter for indoor unit
Clean the air filter at intervals of no more than 2 weeks. Reduce this interval in case of heavily soiled air.
5. Any dirt can be cleaned off us­ing lukewarm water and mild cleaning agents. To do so, turn the dirty side downward (Fig. 3).
6. When using water, allow the filter dry out properly in air before replacing it in the unit.
7. Carefully insert the filter. Make sure it is seated correctly.
8. Close the cover as described above but in reverse order.
9. Switch the supply voltage back on.
10.
Switch the unit back on.
Cleaning the condensation pump
The indoor unit includes a built-in condensation pump, for pumping the condensation to a drain at a higher level.
1 Guard on cover
2 Clean with a vacuum cleaner
3
Cleaning with lukewarm water
Cleaning the filter
1. Disconnect the supply voltage to the equipment.
2. Open and fold down the air inlet guard on the cover. The filter is held in place by the flaps screwed in at the side of the guard (Fig. 1).
3. Tilt the filter and lift it out.
4. Clean the filter using a normal vacuum cleaner (Fig. 2). Turn the dirty side until it faces up.
The pump is more or less main­tenance free. The condensation pipes should be checked for dirt at regular intervals. Clean them as required.
If an external pump is also used, observe the maintenance and care instructions given in the separate operating manual.
14
Installation instructions for qualified personnel
Important points prior to in­stallation
Transport the unit in its original packaging as close as possible to the installation location to avoid transport damage.
Check the contents of the
packaging for completeness and check the unit for visible transport damage. Report any damage immediately to your contracting party and the ship­ping company.
Lift the unit at the corners and not by the refrigerant or con­densation connections.
The refrigerant pipes (injection and suction pipe), valves and connections must be insulated impervious to vapour diffusion. If necessary, also insu­late the condensation pipe.
Select an installation location which allows air to freely flow through the inlet and outlet. (See section "Minimum clear­ances").
Do not install the unit in the immediate vicinity of devices with intensive thermal radia­tion. Installation near sources of thermal radiation reduces the output of the unit.
Open the blocking valves of the refrigerant pipes only after the installation is complete.
Seal off open refrigerant pipes with suitable caps or adhesive strips to avoid infiltration of moisture and never kink or compress the refrigerant pipes.
Avoid unnecessary bends. This minimises the pres­sure loss in the refrigerant pipes
and ensures that the compres­sor oil can flow back without obstruction.
Use four supports and the as­sociated hooks to attach the ceiling cassette.
Use the insulated condensation hose in the scope of delivery as a junction piece to the continu­ing condensate drain. Secure the condensate drain with the supplied clamps.
4
Fixing materials for RVD 261-681 DC
Insulation
Suspension
Adapter piece
Clamps
15
REMKO RVD...DC
Wall openings
A wall opening of at least 70 mm diameter and 10 mm slope from the inside to the outside must be made for each indoor unit.
We recommend that the inside of the hole is padded or lined, e.g. using a PVC tube, to pre­vent the pipes being damaged.
After installation, the wall opening should be closed off on the building side with a suitable sealant. Do not use materials containing cement or lime!
Pipes and cables in wall breakthrough
Control line
PVC tube
Suction pipe
Condensation line
Injection pipe
Installation material
Selection of the installation location
Interior unit
The indoor unit is designed for horizontal wall installation above doors. However, it can also be used on the upper wall area (min. 1.75 m from upper edge of floor).
Exterior unit
The outdoor component is de­signed for horizontal base instal­lation in outdoor areas. It should be placed on level, flat and firm ground. The unit should also be secured to prevent toppling. The outdoor component can be set up outside as well as inside a building. For external installation, please observe the following notes to protect the unit from weather conditions.
Rain
The unit should be at least 10 cm off the ground when mounted on the roof or ground. A floor bracket is optionally available.
Wind
If the unit is being installed in windy areas, ensure that the warm outlet air discharges in the main wind direction. If this is not the case it may be necessary to install a windbreak (provided by the cus­tomer). Ensure that the windbreak does not adversely affect the air intake to the unit.
Windbreak
Wind
The indoor unit is fastened using a wall bracket and 4 threaded screws (provided by the customer).
The outdoor component is at­tached with 4 screws and a wall bracket to the wall or fixed by a floor bracket to the ground.
16
Sun
The liquefier on the outdoor unit radiates heat. Exposure to direct sunlight will further increase the temperature of the fins and reduce the heat out­put of the finned heat exchanger. The outdoor unit should therefore be installed as near as possible to the north side of the building. If necessary, take measures to pro­vide sufficient shade (responsibility of customer). One possible solu­tion is to build a small roof. These measures should not affect the flow of warm outlet air.
Snow
The unit should be wall-mounted in areas of heavy snowfall.
Installation should be at least 20 cm above the expected level of snow to prevent snow from enter­ing the outdoor component. An optional wall bracket is available as an accessory.
Minimum clearance to snow
Ensure a continuous and unob­structed air flow from outside, preferably using sufficiently large air intakes placed opposite each other (Figure 5).
5 Installation inside buildings
Warm air
Additional fan
Comply with any regulations and conditions affecting the statics of the building. If neces­sary, fit acoustic installation.
Cold Fresh air
Snow
20 cm
Installation inside buildings
Ensure there is adequate heat dissipation when placing the outdoor component in cellars, attics, adjoining rooms or halls (Fig 5).
Install an additional fan with a rated flow comparative to that of the outdoor unit being in­stalled in the room. This is used in conjunction with ventilation ducts to compensate any pres­sure losses
(Figure 5).
Light well
Warm air
Exterior unit
Light
well
Minimum clearances
Observe the minimum clearances to allow access for maintenance and repair work and facilitate optimum air distribution.
Minimum clearances
1000
1000
Air intake
1000
D
1000
A
500
E
Air outlet
B
All values in mm
C
RVD 351DC AT RVD 521DC AT RVD 681DC AT RVD 1051DC AT
A 150 mm
B 900 mm
C 500 mm
D 150 mm
E 500 mm
17
REMKO RVD...DC
Oil return measures
If the outdoor component is installed at a higher level than the indoor unit, suitable oil return measures must be taken. Usually an oil pump bend is installed for every 2.5 metres of height differ­ence.
Oil return measures
Exterior unit
Oil pump bend
in suction pipe to
outdoor unit
1 x every 5
metres of rising
pipe
Radius: 50 mm
max. 5/10 m
Interior unit
lection tray.
3. Fit the ceiling cassette approx. 2 cm higher than the surface of the ceiling. (see Figure 8)
4. Make sure that clearance A, (Fig. 8) as specified in the table below, is provided between the underside of the suspended unit and the underside of the fastening surface.
5. Connect the refrigerant pipes, electrical cables and condensa­tion line to the indoor unit as described below.
6. Check that the unit is level.
7. The final task is to tighten the counternuts and attach the cover.
6 Mounting the unit
400
All dimensions in mm
Dimensions in mm
RVD 351-
521DC
Distance A 35 mm
Distance B 25 mm
Mounting the unit
Dimensions in mm
620 x 400 mm
RVD 681-
1051DC
Distance A 35 mm
610
Installation
NOTE
Installation should only be performed by authorised spe­cialists.
Unit installation
The indoor unit is mounted face down on four threaded rods. Take into account the ceiling grid and any other installations.
1. Use the dimensions of the ceil­ing cassette (Fig. 6) to mark the fixing points for the threaded rods on structural parts ap­proved to support the static load above the suspended ceil­ing.
7 Hooking in the unit
8 Fastening the unit
Structural component
A
B
Distance B 25 mm
Mounting the unit
Structural component
620 x 400 mm
Structural component
2. Fit the indoor unit onto the threaded rods and use the lower nuts to level the unit (Fig. 7).This ensures that the condensate drains into the col-
18
abaut 2 cm
Connection of refrigerant pipes
The on-site connection of the refrigerant pipes is made at the rear of the unit.
It may be necessary to fit a reducer or flared adapter to the indoor unit. These fittings are included as standard with the indoor unit. Once installed, the connections should be made tight against va­pour diffusion.
CAUTION
!
The units are factory filled with dry nitrogen to check for leaks. The pressurised nitrogen is released when loosening the union nuts.
The following instructions describe the installation of the refriger­ant circuit and the assembly of the indoor unit and the outdoor component.
5. Verify that the shape of the flange is correct(Figure 11).
6. First connect and hand-tighten the refrigerant connections to ensure they are correctly seated.
7. Now fully tighten the fittings using 2 suitably sized open­ended spanners. Use one span­ner to counter the force when tightening the fitting (Figure
12).
8. Use insulation hoses which are designed for this temperature range and diffusion tight.
9. Lay the refrigerant pipes from the indoor unit to the outdoor component. In doing so, ensure
9 Deburring the refrigerant pipe
Refrigerant pipe
that they are sufficiently at-
tached and take measures for the oil return, if necessary!
10.
Observe the permitted bend­ing radius for the refrigerant pipes during installation. Never bend a pipe twice in the same place. Brittle pipes and potential cracking are the consequences.
NOTE
Only employ tools and com­ponents suitable for refrigera­tion applications.
11.
Use the wall or floor brackets to fit the outdoor component against structural parts ap­proved to support the static load (refer to the installation instructions for the brackets).
10 Flanging the refrigerant pipe
Flanging tool
1.
The required pipe diameters are
given in the table "Technical data".
2. Remove the factory-fitted pro­tective caps and union nuts on the connections. These should be used during installation.
3. Before flanging the refrigerant pipes, ensure that the union nut is fitted on the pipe.
4. Prepare the laid refrigerant pipes as shown below
(Fig. 9+10).
Deburrer
11 Correct flange shape
12 Tighten the fitting
Tighten 1. spanner
Counter
2. spanner
Tightening torque:
15-20 Nm
33-40 Nm
50-60 Nm
65-75 Nm
95-105 Nm
19
REMKO RVD...DC
Tightness check
Once all the connections have been established, the pressure gauge station is attached as fol­lows to the Schrader valve (if fitted): red = small valve = injection pressure blue = large valve = suction pressure
Once connected, perform a tight­ness test using dried nitrogen.
The tightness test involves spray­ing a leak detection spray onto the connections. If bubbles are visible, the connections have not been properly made. Re-tighten the connection or prepare a new flange.
If the tightness test is success­fully completed, depressurise the refrigerant pipes and start a vacuum pump with an absolute final partial pressure of min. 10 mbar to remove the air in the pipe. Any humidity present in the pipes is also removed.
!
CAUTION
A vacuum of min. 20 mbar must be created!
Condensate drain
If the temperature falls below the dew point, condensation will form on the cooling fins during cooling mode. A collection tray together with a condensation pump and float switch are fitted as standard below the cooling fins. Should the float switch trip a protective shutdown due to inadequate removal of the condensation, the pump will switch on immediately and run on for approx. three minutes.
The condensation pipe should have a fall of min. 2 %. This is the responsibility of the cus­tomer. If necessary, fit vapour diffusion proof insulation.
If the level of the condensation pipe on the unit is above that of the outlet, route the pipe verti­cally upwards and then with a fall to the drain.
The delivery rate varies accord-
ing to device type (see right)
The condensation line from the unit should run freely into the drainage pipe. If the condensa­tion runs directly into a sewer pipe, fit a trap to prevent any unpleasant odours.
Condensation connection - Wrong!
Riser pipe too far away
No fall
Condensation pipe too large/small
Cannot freely drain away
Condensation connection - Correct!
min. 2% fall
12-20 mm
500 mm 750 mm
The time required to generate the vacuum is dependent on the pipe­work volume of the indoor unit and the length of the refrigerant pipes. This always takes at least 60 minutes. Once any foreign gases and humidity have been completely extracted from the system, the valves on the pressure gauge sta­tion are closed and the valves on the outdoor unit are opened as described in the chapter on "Com­missioning".
20
When operating the unit at outdoor temperatures below 4°C, ensure the condensation pipe is laid to protect it against frost. If necessary, fit supple­mentary pipe heating.
Once the pipe has been laid, check the condensation drains off and permanently seal it.
Local regulations or laws of environmental protection, eg Water Resources Act (WHG) are observed.
max. 100 mm
! CAUTION
The maximum flow rate of the condensate pump is 500/750 mm head. External influences, such as for example can air-side pressure, pollution, or wear it come to power reduction. To ensure a safe functional opera­tion, we recommend a maxi­mum lifting height of 500 mm, not to exceed!
Before Commissioning
After the tightness check has been successfully completed, connect the vacuum pump via the pressure gauge station to the valve connections on the outdoor unit (see chapter "Tightness check") and create a vacuum.
Perform the following checks prior to commissioning the unit for the first time and after any interven­tions affecting the refrigerant circuit. Record the results in the commissioning report:
Check of all refrigerant pipes and valves with leak detection spray or soapy water for leaks and for inad­vertent mix up of suction and injection pipe, with the unit at a standstill.
Check of all refrigerant pipes and insulation for dam­age.
Check of all electrical connections between indoor unit and outdoor unit for correct polarity.
Check that all fastenings, mountings etc. are firm and at the correct level.
! CAUTION
All electrical installation work should be performed by spe­cialist contractors. Isolate the voltage supply when connect­ing the electrical terminals.
We recommend that custom­ers install a main/repair switch in the vicinity of the outdoor component.
The terminal blocks for making the connections are located at the rear of the unit. When the unit is installed, measurements can be made from the front by removing the cover.
If an optional condensation pump is used in conjunction with the unit, it may be neces­sary to install an additional relay with a higher contact rating after the switch-off contact on the pump to switch off the compressor.
Control cables should be screened if laid in areas exposed to strong magnetic fields.
Details concerning the electrical protection of the system are given in the section on technical data.
nent. See electrical connection diagram.
4. Re-assemble the unit.
13
Connecting the indoor unit
Cover
Terminal block Control line
Connecting the outdoor unit
Proceed as follows to connect the cable:
1. Remove the cover from the unit.
2. Remove the side panel next to the terminals.
Electrical connection
A protected mains supply cable and control cable should be con­nected to the outdoor component RVD 351-1051DC and indoor unit respectively.
NOTE
We recommend realising the control lines with shielded cable.
Connecting the indoor unit
Make the connection as follows:
1. Open the air intake grill.
2. Unfasten the cover on the right side (RVD 351-521DC) or below the panel (RVD 681­1051DC (Fig. 13).
3. Connect the unit to the control cable on the outdoor compo-
3. Select the cable cross-section according to the relevant stand­ards.
4. Feed both cables through the edge protection rings on the fixed connection panel.
5. Terminate the cables as shown on the electrical connection diagram.
6. Support the cable in the strain relief and re-assemble the unit.
21
REMKO RVD...DC
Electrical connection diagrams
RVD 351 DC
Indoor unit
L1
Phase cond.
N
Neutral cond.
S
Data cond.
Earth conductor
Outdoor unit
L1
N
S
Power output
Phase cond.
Neutral cond.
Earth conductor
230 V~, 50 Hz, L1 / N / PE
Note: The A-E plug to connect a cable remote control! Terminals X, Y, E at RVT 521 DC are not used! The attached fixed resistor is not needed
RVD 521DC
Indoor unit
L
Phase conductor
N
Neutral conductor
P
Control conductor
Q
Control conductor
E
Control conductor
PE PE
Earth conductor
Outdoor unit
L
Phase conductor
Neutral conductor
N
P
Q
E
Earth conductor
Note: The A-E plug to connect a cable remote control! Terminals X, Y, E at RVT 521-1051DC are not used! The attached fixed resistor is not needed
Power output
L
N
PE
230 V~, 50 Hz, L / N / PE
Note: For the correct address selection, all 4 DIP switches (red) to ON
DIP-Switch
Note: For the correct address selection, all 4 DIP switches (red) to OFF
RVD 681DC
Indoor unit
L
Phase conductor
N
Neutral conductor
Control conductor
P
Q
Control conductor
E
Control conductor
PE PE
Outdoor unit
Earth conductor
L
Neutral conductor
N
P
Q
E
Note: The A-E plug to connect a cable remote control! Terminals X, Y, E at RVT 1051DC are not used! The attached fixed resistor is not needed
Power output
Phase conductor
Earth conductor
PE
RVD 1051DC
Indoor unit
Neutral cond.
Earth conductor
P
Control cond.
Q
Control cond.
E
Control cond.
Outdoor unit
L1L1 L1
NN N
Pe PePe
P
Q
E
Power output
Phase cond.
Phase cond.
Phase cond.
Neutral cond.
Earth conductor
L2L2
L3L3
L
N
400 V/3~, 50 Hz, L / N / PE
230 V/1~, 50 Hz, L / N / PE
DIP-Switch
Note: For the correct address selection, all 4 DIP switches (red) to OFF
DIP-Switch
Note: The A-E plug to connect a cable remote control! Terminals X, Y, E at RVT 521-1051DC are not used! The attached fixed resistor is not needed
22
Note: For the correct address selection, all 2 DIP switches (red) to OFF
A
U
V
W
Y/G
U
V
W
RY3
4
CN6
CN7
CN5
CN4
CN2 8
CN26
C
N
1
0
N
-
B
B
C
N
3
C
N
2
C
N
1
CN15
CN14
CN16
N-A
Zum Innengerät
Y/G
WHITE
REACTOR2 R6025C REACTOR1 R1310K
Kurbelwannenheizung
Heizung
5
CN31
CN33
CN34
CN32
B
L
A
C
K
Y/G
T3
Sensor Umgebung
T5
Sensor Verflüssiger Sensor Heißgas
Sensor Öl
Kompressor
Ventilatormotor
Umkehrventil
Blau
Schwarz
Rot
Schwarz
Rot
Rot
Hauptplatine
Grau
Optional
Orange
Gelb
Rot
Orange
Gelb
Gelb
Orange
Rot
Blau
Stromüberwachung
Gelb
Blau
Braun
Electrical circuit diagram
RVD 351 DC Indoor unit
M
RVD 351 DC Outdoor unit
blue
red
black
Compressor
Probe condenser
Sensor environment
Main board
blue
Power management
yellow
yellow
red
red
Hot gas sensor
Sensor oil
black
yellow
yellow
blue
brown
red
Fan motor
Heating
Crankcase heating
To indoor unit
red
gray
Reversing valve
23
Blau
Blau
Blau
Blau
Blau
Blau
Blau
Kompressor
Rot
Schwarz
Gelb
Gelb
Schwarz
Rot
Weiß
Rot
RotRot
Schwarz
Gelb
Grau
Filter
Schwarz
Rot
Rot
Schwarz
Schwarz
Yellow/Green
Yellow/Green
Yellow/Green
Schwarz
Rot
Schwarz
Braun
Braun
Weiß
Weiß Weiß
Weiß
Rot
Rot
Rot
Rot
Rot
Orange
Rot
Schwarz
UWV
U
V
W
P
N
IPM
10PIN
W V
U
L202
IPM
EEW
T5
CN4
CN12
CN5CN5
CN16
CN11
CN1
CN2
Trans. Trans.
CN20
CN27
CN28
CN9
Hochdruckschalter
Niedrigdruckschalter
R2503
P-3
P-4
P-5
P-6
P-2
3
CN3
R1815B
R1325C
CN14
CN15
CN13
CN12
CN7
CN5
CN6
CN4
CN8
CN10
CN9
Blau
Ventilator
CN1 CN2
L
N
L
N
P-1
L
H
Sensor Heißgas
Sensor Außentemperatur
Sensor Austritt Verflüssiger
Elektronisches Expansionsventil
Leistungsplatine
zum Innengerät
Steuerleiter
Hauptplatine
Steckverbinder
Steckverbinder
GM
P1
Lila
Weiß
Netzzuleitung Innenteil
Rot
Weiß
CN4
CN11 CN5 CN7 CN9
Weiß
C5
Weiß Schwarz
Rot
CN3
CN2
T1 T2
T2 T1
CN14 CN10 CN15
(E)
Y
X
Schwarz
Grau
Gelb
Schwarz
Blau
Weiß
(E)
P
C
YEX
E
F M
CN12
CN1
zum Außengerät Steuerleiter
zum CCN Steuerleiter
DM
Display
Y/G
c
Blau
Y/G
CN5
REMKO RVD...DC
RVD 521 DC Indoor unit
white
purple
Power output indoor unit
RVD 521 DC Outdoor unit
red
black
24
red
blue
Compressor
blue red black
red
white
white
red
Connector
blue
red
blue
orange
red
white
red
Electronic expansion valve
red
blue white white
Main board
white
Probe outlet condenser
black
Power board
brown
brown
white
To CCN
Control
conductor
blue
black
blue
black
To outdoor unit
black
white
yellow
Red
blue
Fan
black
yellow
gray
Control
conductor
High pressure switch
Low pressure switch
yellow
Red
yellow
To the indoor unit
Control conductor
black
red
blue
blue
black
red
white
Hot gas sensor
Sensor outside temperature
black
gray
black
red
Connector
RVD 681 DC Indoor unit
GM
P1
Lila
Weiß
Netzzuleitung Innenteil
Rot
Weiß
CN4
CN11 CN5 CN7 CN9
Weiß
C5
Weiß Schwarz
Rot
CN3
CN2
T1 T2
T2 T1
CN14 CN10 CN15
(E)
Y
X
Schwarz
Grau
Gelb
Schwarz
Blau
Weiß
(E)
P
Q
YEX
E
F M
CN12
CN1
DM
Display
Y/G
c
Blau
Y/G
CN5
Blau
Blau
Blau
Blau
Blau
Blau
Blau
Kompressor
Rot
Schwarz
Gelb
Gelb
Schwarz
Rot
Weiß
Rot
RotRot
Schwarz
Gelb
Grau
Filter
Schwarz
Rot
Rot
Schwarz
Schwarz
Yellow/Green
Yellow/Green
Yellow/Green
Schwarz
Rot
Schwarz
Braun
Braun
Weiß
Weiß Weiß
Weiß
Rot
Rot
Rot
Rot
Rot
Orange
Rot
Schwarz
UWV
U
V
W
P
N
IPM
10PIN
W V
U
L202
IPM
EEW
T5
CN4
CN12
CN5CN5
CN16
CN11
CN1
CN2
Trans. Trans.
CN20
CN27
CN28
CN9
Hochdruckschalter
Niedrigdruckschalter
R2503
P-3
P-4
P-5
P-6
P-2
3
CN3
R1815B
R1325C
CN14
CN15
CN13
CN12
CN7
CN5
CN6
CN4
CN8
CN10
CN9
Blau
Ventilator
CN1 CN2
L
N
L
N
P-1
L
H
Sensor Heißgas
Sensor Außentemperatur
Sensor Austritt Verflüssiger
Elektronisches Expansionsventil
Leistungsplatine
zum Innengerät
Steuerleiter
Hauptplatine
Steckverbinder
Steckverbinder
white
purple
red blue
Power output indoor unit
RVD 681 DC Outdoor unit
Compressor
blue red black
red
Connector
red
black
red
blue
red
white
white
Electronic expansion valve
blue
red
orange
red
white
red
blue white white
Probe outlet condenser
Main board
Power board
brown
brown
white
black
blue
blue
black
white
To CCN
Control
conductor
black
white
yellow
High pressure switch
Red
Low pressure switch
yellow
Red
yellow
To the indoor unit
Control conductor
black
red
blue
blue
black
red
Fan
white
blue
black
yellow
To outdoor unit
Control
conductor
Hot gas sensor
Sensor outside temperature
black
gray
black
red
black
gray
Connector
25
POWER_RY
HEAT
4-WAY
FAN_H
FAN_L
TRANS IN
T4
N
TRANS IN
CT1
L1
L2
L3
L1
L2
L3
CN16
T5T3
1
5
3
4
2
RED
CN42
CN48
CN46 CN47
CN44 CN45
CN43
CN20-CN22
GND
A1
A2
2T1
4T2
6T3
1L1
3L2
5L3
21
22
2
REMKO RVD...DC
RVD 1051 DC Indoor unit
DM
Weiß
white
Lila
purple
red blue
Rot
Y/G
Netzzuleitung Innenteil
Power output indoor unit
Blau
CN1
CN3
CN2
CN12
c
P1
Weiß
white
GM
Display
CN14 CN10 CN15
CN4
CN11 CN5 CN7 CN9
red
Rot
C5
Y/G
F M
Weiß
white
CN5
T2 T1
black
white
Weiß Schwarz
T1 T2
YEX
E
Weiß
Blau
white
blue
X
Y
To CCN
Control
conductor
Schwarz
black
(E)
To outdoor unit
Gelb
yellow
P
Q
Control
conductor
Grau
gray
(E)
Schwarz
black
RVD 1051 DC Outdoor unit
26
Add refrigerant
The equipment contains a basic quantity of refrigerant. Beyond these conditions, for refrigerant pipe lengths of more than 5 meters per circuit, an additional amount of refrigerant must be added, accord­ing to the following chart:
! CAUTION
Note that the employed refrig­erant is always filled in liquid form!
NOTE
Check the overheating to determine the refrigerant fill quantity
CAUTION
!
Wear protective clothing when handling refrigerant.
RVD
RVD
RVD
681
DC
30
g/m
RVD
1051
DC
30
g/m
Up to and incl. 5m
From 5m to max. Length
351
DC
25
g/m
521
DC
0 g/m
25
g/m
Commissioning
NOTE
Commissioning should only be performed and documented by specially trained personnel.
The system can be commissioned once all the components have been connected and tested. A functional check should be per­formed to verify its correct func­tion and identify any unusual operational behaviour prior to handing it over to the operator.
NOTE
Check that the stop valves and valve caps are tight after carrying out any work on the refrigerant circuit. If necessary, use appropri­ate sealant products.
Function test and test run
Check the following points:
Leak tightness of refrigerant pipes.
Compressor and fan running smoothly.
In cooling mode, cold air should be output by the indoor unit, and warm air should be output by the outdoor component.
Functional test of the indoor unit and all program sequences.
Check of the surface tempera­ture of the suction pipe and determination of vaporiser overheating. To measure the temperature, hold the ther­mometer to the suction pipe and subtract the boiling point temperature reading on the pressure gauge from the meas­ured temperature.
Record the measured tem­peratures in the commissioning report.
Functional test for cooling and heating modes
1. Remove the caps from the valves.
2. Begin the commissioning process by briefly opening the blocking valves of the external section until the manometer
displays a pressure of approx. 2 bar.
3. Use leak detection spray or suit­able devices to check that all the connections are tight.
4. If no leaks are found, fully open the stop valves by turning them anti-clockwise using a spanner. If leaks are found, repair the faulty connection. It is impera­tive that the vacuum creation and drying steps are repeated.
5. Switch off the main circuit breaker or remove the fuse (provided by the customer).
6 Press the test knob on the
outdoor unit and wait until a frequency of min. 50 Hz is established.
7. Use the remote control to switch on the unit and select the cooling mode, maximum fan speed and lowest target temperature.
8. Check the overheating, out­door, indoor, outlet and vapori­sation temperatures and record the measured values in the commissioning report. Check the correct function and set­tings of all regulation, control and safety devices.
9. Check the indoor unit control system using the functions described in the chapter "Oper­ation". Timer, temperature set­ting, fan speeds and switching to ventilation or dehumidifying mode.
10.Check the correct function of the condensation pipe by pouring distilled water into the condensation tray. A bottle with a spout is recom­mended for pouring the water into the condensation tray.
11.
Switch the indoor unit to heat­ing mode.
27
REMKO RVD...DC
12.
Check all the previously described safety devices and functions during the test run.
13.
Enter the measured data in the commissioning report. in the commissioning report and familiarize the operator with the system.
14.
Remove the pressure gauge. Check that seals have been fitted in the sealing caps.
NOTE
Press the TEST knob on the outdoor unit board. This serves to set the inverter to max. refrigerating capacity.
15. Reinstall all parts which were removed.
Functional test and test run
During operation of the plant operating parameters can be called up on the outdoor unit display. (only RVD 521-1051DC) The following parameters are dis­played successively:
RVD 521-1051 DC
- Frequency of the compressor
- Operating mode
- Level fan
- Current cooling/heating perforance
- Temperature sensor liquefier
- Temperature sensor hot gas
- Temperature sensor air inlet
- Power consumption outdoor unit
- Degree of opening for electronic Expansion valve only RVD 521 DC
- error code
Proceed as follows to call up the operating parameters:
1. Remove the cover from the outdoor unit.
2. Switch all indoor units on and select cooling mode and the highest fan speed.
Display
The display on the outdoor unit PCB can call up the operating pa­rameters of the plant in the above order. In order to do so, press the check button located next to the display on the outdoor unit board.
Check button
Frequency gauge
Display Frequency (Hz)
30 30
-- Stand by
60 60
Operating mode
Display
0 Off 2 Cooling mode 3 Heating mode 4 Forced cooling
Mode Outdoor unit
Operating mode fan
Display Mode fan
0 Off 1 Low rotational speed 2 High rotational speed
Cooling output - heating output Outdoor unit / Indoor unit
Display Cooling output
1 2.0-2.5 kW 2 2.5-3.0 kW 3 3.0-3.8 kW 4 3.8-5.0 kW 5 5.0-5.5 kW 6 5.5-6.1 kW
Temperature sensor liquefier
Display Temperature
10 35-40 °C 11 40-45 °C 12 45-50 °C 13 50-55 °C 14 55-60 °C 15 60-65 °C 16 65-70 °C
Temperature sensor hot gas
Display Temperature
10 35-40 °C 11 40-45 °C 12 45-50 °C 13 50-55 °C 14 55-60 °C 15 60-65 °C 16 65-70 °C
Temperature sensor air inlet
Display Temperature
15 -7.5 °C 20 -5.0 °C 25 -2.5 °C 30 0° C 35 2.5 °C 40 5.0 °C 45 7.5 °C 50 10.0 °C 55 12.5 °C 60 15.0 °C 65 17.5 °C 70 20.0 °C 75 22.5 °C 80 25.0 °C 85 27.5 °C 90 30.0 °C 95 32.5 °C 99 34.5 °C
Power consumption outdoor unit
Display
44 6.0 A 46 6.2 A 54 7.4 A 55 7.6 A 58 7.8 A 62 8.0 A 66 8.6 A 67 8.8 A 68 9.0 A 70 9.2 A 72 9.5 A 76 10.0 A 78 10.2 A 80 10.4 A 82 10.6 A 84 11.0 A 88 11.6 A 92 12.0 A 94 12.2 A
Power consump-
tion
28
Troubleshooting and customer service
The equipment and components are manufactured using state-of-the-art production methods and tested several times to verify their correct function. If malfunctions should occur, please check the functions as detailed in the list below. Please inform your dealer if the unit is still not working correctly after all the functional checks have been performed!
Malfunction
Fault Possible cause Checks Remedial measures
The unit does not start or switches itself off
The unit does not respond to the remote control
The unit is running with reduced or without reduced cooling / heating performance
Condensation discharge on unit
Power outage, undervoltage, defective mains fuse / main circuit breaker switched off
Damaged mains cable
Waiting time after switch-on too short
Temperature outside operating range.
Overvoltages caused by thunder storms
Fault in external condensation pump
High-pressure / low-pressure monitors have triggered
Transmission distance too far / receiver affected by interference
Defective remote control
Receiver or transmitter unit ex­posed to excessive solar radiation
Electromagnetic fields are interfer­ing with transmission
Button in remote control jammed / two buttons pressed at same time
Batteries in remote control are flat
Filter is unclean / air inlet / outlet blocked by foreign items
Windows and doors open. Heat­ing/cooling output increases
Neither cooling nor heating mode has been set
Fins on outdoor component blocked by foreign items
Leaking refrigerant circuit
Outdoor component iced up
Drainage pipe on collection con­tainer clogged / damaged
Faulty external condensation pump or float
Condensation has not drained away and has collected in the condensation line
Condensation does not drain off
Float is stuck or jammed due to excessive dirt.
Are all other electrical installations functioning correctly?
Are all other electrical installations functioning correctly?
Have approx. 5 minutes elapsed since the restart?
Are the fans in the indoor unit and outdoor component working correctly?
Has there recently been lightning?
Did the pump shut down due to a fault?
Check refrigerant pressure and look for leaks if necessary
Does the indoor unit beep when pressing a button?
Is the unit running in manual mode?
Does it function correctly in the shade?
Does it function when switching off possible sources of interference?
Does the “Send” symbol appear on the display?
Have new batteries been inserted? Is the display incomplete?
Have the filters been cleaned? Clean the filters
Have there been any construc­tional / application-related changes?
Does the cooling symbol appear on the display?
Is the fan on the outdoor com­ponent running? Are the fins unobstructed?
Are there signs of frost on the fins of the indoor unit?
Check outdoor component. Has the cassette sensor on the outdoor component been correctly posi­tioned?
Can the condensation drain off without any obstruction?
Is the collection tray full of water and the pump not running?
Is there a steady fall on the con­densation pipe? Check there is no blockage in the pipe.
Are the condensation lines un­blocked and is there a steady fall? Are the condensation pump and float switch functioning correctly?
Are the LEDs on the receiver unit of the indoor unit flashing?
Check voltage possible wait until turned on again.
Repair by a specialist
Schedule longer waiting periods
Take into account the tempera­ture range for the indoor unit and outdoor component
Switch off the mains breaker and switch it back on. Have it checked by a specialist
Check and if necessary clean the pump
Rectify leakage and re-start
Reduce the distance to less than 6 m or change position
Replace the remote control
Place the receiver&transmitter unit in the shade
Signal is not transmitted when in­terference sources are operational
Release the button / only press one button
Insert new batteries
Close windows and doors / install additional units
Correct the settings for the unit
Check the fan or winter controller, reduce the air resistance
Repair by specialist
De-ice and fit the sensor at the point where the most ice forms
Clean the drainage pipe and col­lection container
Call out a specialist to replace the pump
Ensure there is a fall when laying the condensation pipe and clean the pipe.
The condensation line must have a fall. If necessary, clean the pipe. A faulty condensation pump and float switch should be replaced.
Should be cleaned by specialist firm
29
REMKO RVD...DC
Problem display by blinker code
LED
Operation
flashes rapidly
flashes
slowly
LED
Timer
flashes rapidly
flashes
slowly
LED
Defrost
flashes rapidly
flashes
slowly
LED
Alarm
flashes
slowly
flashes rapidly
Display
outdoor
unit
E0 EEPROM error Check EEPROM
E2
E3
E4
E5 Overvoltage compressor Check compressor voltage
P0 Excessive temperature compressor Allow compressor to cool
P1 High pressure sensor has triggered Check refrigerant pressure
P2 Low pressure sensor has responded Check refrigerant pressure
P3
P4 Compressor discharge gas over 105°C
P5 Liquefier temperature over 65°C
P6
Communication error between PCBs outdoor unit & indoor unit Communication error between out­door unit main board & outdoor unit inverter board Outdoor temp sensor on outdoor com­ponent tripped
Compressor power consumption too high
Voltage protection main board outdoor unit Sensor air circulation / sensor liquefier tripped Communication error between outdoor unit & indoor unit
Mode malfunction
Sensor liquefier / outdoor temp faulty or not correctly connected
Condensate pump float switch faulty
Cause Required action
Check electrical connection leads
Check wiring
Check resistance and tem­perature on sensor
Check compressor power consumption Clean liquefier, check refrig­erant circuit Clean liquefier, check refrig­erant circuit
Check voltage
Check resistance
Check electrical connection leads
Switch system off
Read off error code on outdoor unit Check sensors Check condensate pump and float switch
30
Fault analysis
1. Operation light flashes at 5 Hz: fault on the room temperature sensor
Is the resistance of the vaporise sensor OK? (white cable) (Table 1 P92-94)?
Yes
Is the resistance of the room sensor OK? (Table 1 P92-94)?
Yes
Replace indoor unit main board
No
No
Replace temperature sensor
Replace temperature sensor
Note:
The room temperature sensor and vaporiser sensor are brought together in a single connector, CN9
3. Timer light flashes at 5 Hz: communication error between indoor unit and outdoor component
2. Defrost light flashes at 5 Hz: fault on the vaporiser sensor
Is the resistance of the temperature sensor OK? (black cable) (Table 1 P92-94)?
Yes
Replace indoor unit main board
No
Replace temperature sensor
4. Alarm light flashes at 5 Hz: float switch / condensation pump
Set the cooling mode on the indoor unit and run the system so a few minutes. If the error still exist?
Is there voltage in the indoor unit?
Yes
Is the connecting cable shielded, and is it earthed?
Yes
Is the cable connecting the indoor unit and outdoor component properly connected?
Yes
Is the cable connecting the indoor unit and outdoor component damaged?
No
No
No
No
Yes
Establish the power supply.
Use a shielded, earthed cable
Connect the cable properly.
Replace the cable.
Yes
Is the float switch working properly?
Yes
Does the condensate pump properly appropriate?
Yes
Check the condensate drain, whether it is bent if necessary. If the condensate drain okay?
Yes
Replace the main board for the indoor unit
No
No
No
Replace float switch. Error still exists?
Condensate pump exchange. Error still exists?
Condensate drain renew or repair
Replace the main board for the indoor unit or outdoor component
31
REMKO RVD...DC
5. Operation and Timer lights flash at 5 Hz: EEPROM error
Is the EEPROM fitted properly?
No
Fit EEPROM properly
Yes
Replace outdoor component main board
6. Operation light flashes at 5 HZ and Alarm light is on: IPM safety shutdown
Check the power supply to the circuit board. Is it working OK?
No
Yes
Are the connections from the circuit board to the compressor OK?
Yes
Check the windings of the compressor
Correct connections
No
Check the power supply for the outdoor component. Is a voltage of 230 V present at the unit power supply?
Yes
Check the unit's electrical supply. Is it properly connected?
No
No
No
Correct the power supply to the unit. Is the unit working properly again?
Connect the electrical supply properly
Are the windings of the compressors OK?
Yes
Replace circuit board
No
No
Replace circuit board
Replace compressor
Does the unit run after replacing the compressor?
Are all the circuit board's electrical cables properly connected?
Check the chokes on the circuit board
Chokes have resistance?
Check the fuses on the circuit board
Circuit board fuses
Yes
OK?
Yes
Yes
No
No
No
Yes
Connect all electrical cables properly
Replace circuit board
Replace fuse or circuit board
32
7. RVD 351 DC Operation light flashes at 5 Hz and Timer light is on: condenser temperature sensor
outdoor component overcurrent protection
9. Operation, Timer and Alarm lights flash at 5Hz:
RVD 521 DC Alarm light flashes at 1 Hz: Fault Temperature sensor condenser or outdoor unit is not working properly (look at E4, P1 and P2)
Connection of sensor line OK?
Yes
Resistance of the sensor OK (Table 1, P92-94)?
No
Replace temperature sensor
No
Yes
Correct sensor line
Replace outdoor component main board
8. Operation light flashes at 5 Hz, Timer and Alarm lights are on: outdoor component overvoltage protection
Is the input current greater than 16A?
Yes
Check refrigerant pipes
Is the outdoor temperature too high?
No
Is the function of the fan on the outdoor component OK?
Yes
Is the register of the outdoor component dirty?
No
Yes
Switch off unit
Ensure fan functions properly
Clean the register
Yes
of the outdoor component
Connection of sensor line OK?
Yes
Is the voltage between L and N of the outdoor component 198 – 254V?
Yes
Replace main board
No
No
Connect the sensor properly
Establish correct power supply
No
Are the refrigerant pipes blocked or bent?
No
Replace outdoor component main board
Siphon off refrigerant, replace pipe / remove
Yes
blocked, perform pressure test, drawn vacuum and refill
33
REMKO RVD...DC
10. Operation light flashes at 5 Hz and Defrost light is on: Hot gas temperature too high
Is the temperature of the Klixon over 115°C?
No
Is the connection between the Klixon and circuit board OK?
Yes
Is the resistance value for the Klixon correct (Table 2, P95)?
Yes
Replace outdoor component main board
Yes
No
No
Is there a refrigerant leak?
Establish a proper connection
Replace Klixon
Yes
Fix the leak and top up
34
RVD 521-1051DC outdoor unit fault analysis
Fault displays shown on the outdoor component
Fault code DISPLAY
Fault description Required action
E0 EEPROM error see page 85 / point 1
E2 Communication error between indoor unit and outdoor component see page 85 / point 2
E3 Communication error on outdoor component main board see page 86 / point 3
E4 Fault on the outdoor temperature sensor see page 86 / point 4
E5 Compressor overvoltage protection see page 86 / point 5
P0 Compressor overload protection (Klixon) tripped
P1 High pressure fault (from RVD 521 and up) see page 87 / point 6
P2 Low pressure fault (from RVD 521 and up) see page 88 / point 7
P3 Compressor overcurrent protection tripped see page 89 / point 8
P4 Compressor overload protection (Klixon) see page 90 / point 9
P5 Condenser outlet sensor triggered see page 90 / point 10
P6 IPM power board safety shutdown see page 91 / point 11
2.
1. Fault code E0: EEPROM error
Fault code E2: communication error between indoor
unit and outdoor component
No
Establish the power supply.
fitted properly?
No
Fit EEPROM properlyIs the EEPROM
Is there voltage in the indoor unit?
Yes
Replace outdoor component main board
Yes
Are the DIP switches on the main board set correctly?. See cover.
Yes
Is the cable connecting the indoor unit and outdoor component properly connected?
Yes
Is the cable connecting the indoor unit and outdoor component damaged?
No
Replace the main board for the indoor unit or outdoor component
No
No
Yes
Reset the DIP switch and switch for 5 min without current.
Connect the cable properly.
Replace the cable.
35
REMKO RVD...DC
3. Fault code E3: communication error on main board of the outdoor component
Does LED1 flash on the outdoor component main board?
No
Is the electrical connection between the power board and CN4 on the main board OK?
Yes
Disconnect the electrical connection between the power board and CN4 on the main board. Is there a measurement of 5V on power board CN1 between the 3th and 4th pins?
No
Is the connection between the IPM module (positive terminal) and CN12 on the power board OK?
Yes
No
Yes
No
Replace main board
Establish a proper connection
Replace main board
Establish a proper connection
4. Fault code E4: fault on outside temperature sensor T4 or condenser sensor T3
Is the condenser sensor properly connected?
Yes
Measure the resistance of the sensor. (Table 1, P92-94) Resistance OK?
Yes
Is the outside temperature sensor properly connected?
Yes
Measure the resistance of the sensor. (Table 1, P92-94) Resistance OK?
Yes
Replace main board
No
No
No
No
Connect condenser sensor properly
Replace sensor
Connect the outside temperature sensor properly
Replace sensor
Yes
Is the connection between the IPM module (negative terminal) and CN13 on the power board OK?
Yes
Is there a measurement of 277-345V between CN12 and CN13 on the power board?
No
No
Yes
Establish a proper connection
Replace power board
Replace IPM module
5. Fault code E5: compressor overvoltage protection
Is the supply line properly connected and are there 172-265 V between L1 and N?
Yes
Replace power board Does the unit work after the replacement?
No
No
Replace supply line
Replace main board
36
6. Fault code P1: high pressure fault
Is the connecting cable from the high pressure switch to the main board OK?
Yes
High pressure switch may be defective
Bypass the high pressure switch on the circuit board. Does the unit work now?
No
Check refrigerant pipes
No
Yes
Correct connection
Replace the high pressure switch
Is the outdoor temperature too high?
No
Yes
Switch off unit
Replace outdoor component main board
Is the function of the fan on the outdoor component OK?
Yes
Is the register of the outdoor component dirty?
No
Are the refrigerant pipes blocked or bent?
No
Yes
Yes
Ensure fan functions properly
Clean the register of the outdoor component
Siphon off refrigerant, replace pipe / remove blocked, perform pressure test, drawn vacuum and refill
37
REMKO RVD...DC
7. Fault code P2: low pressure fault
Is the connecting cable from the lower pressure switch to the main board OK?
Yes
Low pressure switch may be defective
Bypass the low pressure switch on the circuit board. Does the unit work now?
No
Check refrigerant pipes
No
Yes
Correct connection
Replace the high pressure switch
Is the outdoor temperature too low?
No
Yes
Switch off unit
Siphon off refrigerant, replace pipe / remove blocked, perform pressure test, drawn vacuum and refill
No
Replace outdoor com­ponent main board
The refrigerant pipes may be leaking
Check the refrigerant pressure with a manometer. Is the refrigerant pressure less than 1.4 bar?
No
Refrigerant pipe may be blocked
Yes
Check the refrigerant pipes with leak detection spray or an electronic leak detector
38
8. Fault code P3: compressor overcurrent protection has tripped
Is the input current greater than 20A?
No
Check refrigerant pipes
Yes
Is the outdoor temperature too high?
No
Is the function of the fan on the outdoor component OK?
Yes
Is the register of the outdoor component dirty?
No
Are the refrigerant pipes blocked or bent?
No
Replace outdoor component main board
No
Yes
Yes
Yes
Switch off unit
Ensure fan functions properly
Clean the register of the outdoor component
Siphon off refrigerant, replace pipe / remove blocked, perform pressure test, drawn vacuum and refill
39
REMKO RVD...DC
9. Fault code P4: hot gas temperature too high
Is the hot gas temperature over 115°C?
No
Is the connection between the sensor and circuit board OK?
No
Is the resistance value for the sensor correct (Table 2, P95)?
Yes
Replace outdoor component main board
Yes
No
No
Is there a refrigerant leak?
Establish a proper connection
Replace hot gas sensor
10. Fault code P5: condenser outlet sensor triggered
Yes
Fix the leak and top up
Is the condenser outlet temp. greater than 65°C?
No
Check the resistance of the sensor. (Table 1, P92-94) Is the resistance OK?
Yes
Replace outdoor component main board
No
Yes
Switch off unit
Replace sensor
Clean condenser register
Siphon off refrigerant, replace pipe / remove blocked, perform pressure test, drawn vacuum and refill
Yes
Yes
Yes
Is the outdoor temperature too high?
No
Is the condenser register dirty?
No
Are the refrigerant pipes blocked or bent?
No
40
Replace outdoor component main board
11. Fault code P6: IPM power board safety shutdown
Is the voltage range between P and N of the IPM module OK?
Yes
Is the connection between the main board and IPM module OK?
Yes
Is the connection to the compressor OK?
Yes
Replace IPM module. Is fault still present?
No
No
No
Is the input voltage between P and N of the IPM module 230V / the frequency 50 Hz?
Connect cables properly Is fault still present?
Establish a proper connection
Establish a proper connection
Replace single-phase bridge circuit
No
No
Ensure the correct supply voltage
Yes
Are all the electrical cables properly connected?
Yes
Yes
Is the single-phase bridge OK? Take a measurement with a multimeter between “+” and the two AC contacts and between “-” and the two AC contacts. Is the resistance for the two measurements 0Ω?
Yes
No
Yes
Replace main board. Is fault still present?
Yes
Replace compressor. Is fault still present?
4-way valve
Temperature Resistance Measuring point
20 °C 1.5 kΩ Blue - Blue
Replace connecting cables
Replace the defective fuse
Note:
Heating mode 0V AC Cooling mode 230V AC
No
Yes
Are the connecting cables to the chokes OK? Is the resistance of the connecting cables ?
No
Check the fuses on the power board. Are they working OK?
Yes
Replace the power board
41
REMKO RVD...DC
Resistances of the temperature sensors (Table 1)
Temp. Resistance kΩ
(°C) Rmax
-20 116.539 106.732 96.920
-19 110.231 100.552 91.451
-18 103.743 94.769 86.328
-17 97.673 89.353 81.525
-16 91.990 84.278 77.017
-15 86.669 79.521 72.788
-14 81.684 75.059 68.815
-13 77.013 70.873 65.083
-12 72.632 66.943 61.574
-11 68.523 63.252 58.274
-10 64.668 59.784 55.169
-9 61.048 56.524 52.246
-8 57.649 53.458 49.492
-7 54.456 50.575 46.899
-6 51.456 47.862 44.455
-5 48.636 45.308 42.150
-4 45.984 42.903 39.977
-3 43.490 40.638 37.927
-2 41.144 38.504 35.992
-1 38.935 36.492 34.165
0 36.857 34.596 32.440
1 34.898 32.807 30.810
2 33.055 31.120 29.271
3 31.317 29.528 27.815
4 29.681 28.026 26.440
5 28.138 26.608 25.140
6 26.682 25.268 23.909
7 25.310 24.003 22.745
8 24.016 22.808 21.644
9 22.794 21.678 20.601
10 21.641 20.610 19.614
11 20.553 19.601 18.680
12 19.525 18.646 17.794
13 18.554 17.743 16.955
14 17.636 16.888 16.160
15 16.769 16.079 15.406
16 15.949 15.313 14.691
17 15.174 14.588 14.014
18 14.442 13.902 13.372
19 13.748 13.251 12.762
20 13.093 12.635 12.183
21 12.471 12.050 11.634
R(t) Normal
Rmin
Temp. Resistance kΩ
(°C) Rmax
22 11.883 11.496 11.112
23 11.327 10.971 10.617
24 10.800 10.473 10.147
25 10.300 10.000 9.700
26 9.848 9.551 9.255
27 9.418 9.125 8.834
28 9.010 8.721 8.434
29 8.621 8.337 8.055
30 8.252 7.972 7.695
31 7.900 7.625 7.353
32 7.566 7.296 7.029
33 7.247 6.982 6.721
34 6.944 6.684 6.428
35 6.656 6.401 6.150
36 6.381 6.131 5.886
37 6.119 5.874 5.634
38 5.870 5.630 5.395
39 5.631 5.397 5.167
40 5.404 5.175 4.951
41 5.188 4.964 4.745
42 4.982 4.763 4.549
43 4.785 4.571 4.362
44 4.596 4.387 4.183
45 4.417 4.213 4.014
46 4.246 4.046 3.851
47 4.082 3.887 3.697
48 3.925 3.735 3.550
49 3.776 3.590 3.409
50 3.632 3.451 3.274
51 3.495 3.318 3.146
52 3.363 3.191 3.023
53 3.237 3.069 2.905
54 3.116 2.952 2.793
55 3.001 2.841 2.685
56 2.890 2.734 2.582
57 2.784 2.632 2.484
58 2.682 2.534 2.390
59 2.585 2.440 2.299
60 2.491 2.350 2.213
61 2.401 2.264 2.130
62 2.315 2.181 2.051
63 2.233 2.102 1.975
R(t) Normal
Rmin
42
Temp. Resistance kΩ
(°C) Rmax
64 2.154 2.026 1.903
65 2.077 1.953 1.833
66 2.004 1.883 1.766
67 1.934 1.816 1.702
68 1.867 1.752 1.641
69 1.802 1.690 1.582
70 1.740 1.631 1.525
71 1.680 1.574 1.471
72 1.622 1.519 1.419
73 1.567 1.466 1.369
74 1.514 1.416 1.321
75 1.463 1.367 1.275
76 1.414 1.321 1.230
77 1.367 1.276 1.188
78 1.321 1.233 1.147
79 1.277 1.191 1.108
80 1.235 1.151 1.070
81 1.195 1.113 1.034
82 1.156 1.076 0.999
83 1.118 1.041 0.966
84 1.082 1.007 0.934
85 1.047 0.974 0.903
86 1.014 0.942 0.874
87 0.982 0.912 0.845
88 0.951 0.883 0.818
89 0.921 0.855 0.791
90 0.892 0.828 0.766
91 0.864 0.802 0.742
92 0.838 0.777 0.719
93 0.812 0.753 0.696
94 0.787 0.730 0.675
95 0.763 0.708 0.654
96 0.740 0.686 0.634
97 0.718 0.666 0.615
98 0.697 0.646 0.597
99 0.677 0.627 0.579
100 0.657 0.609 0.562
101 0.638 0.591 0.546
102 0.620 0.574 0.530
103 0.602 0.558 0.515
104 0.585 0.542 0.501
105 0.569 0.527 0.485
R(t) Normal
Rmin
43
REMKO RVD...DC
Resistances of the hot gas sensors (Table 2)
°C kΩ °C kΩ °C kΩ °C kΩ
-20 542.7 22 62.73 64 11.79 106 3.113
-19 511.9 23 59.98 65 11.38 107 3.025
-18 483 24 57.37 66 10.99 108 2.941
-17 455.9 25 54.89 67 10.61 109 2.86
-16 430.5 26 52.53 68 10.25 110 2.781
-15 406.7 27 50.28 69 9.902 111 2.704
-14 384.3 28 48.14 70 9.569 112 2.63
-13 363.3 29 46.11 71 9.248 113 2.559
-12 343.6 30 44.17 72 8.94 114 2.489
-11 325.1 31 42.33 73 8.643 115 2.422
-10 307.7 32 40.57 74 8.358 116 2.357
-9 291.3 33 38.89 75 8.084 117 2.294
-8 275.9 34 37.3 76 7.82 118 2.233
-7 261.4 35 35.78 77 7.566 119 2.174
-6 247.8 36 34.32 78 7.321 120 2.117
-5 234.9 37 32.94 79 7.086 121 2.061
-4 222.8 38 31.62 80 6.859 122 2.007
-3 211.4 39 30.36 81 6.641 123 1.955
-2 200.7 40 29.15 82 6.43 124 1.905
-1 190.5 41 28 83 6.228 125 1.856
0 180.9 42 26.9 84 6.033 126 1.808
1 171.9 43 25.86 85 5.844 127 1.762
2 163.3 44 24.85 86 5.663 128 1.717
3 155.2 45 23.89 87 5.488 129 1.674
4 147.6 46 22.89 88 5.32 130 1.632
5 140.4 47 22.1 89 5.157
6 133.5 48 21.26 90 5
7 127.1 49 20.46 91 4.849
8 121 50 19.69 92 4.703
9 115.2 51 18.96 93 4.562
10 109.8 52 18.26 94 4.426
11 104.6 53 17.58 95 4.294 B(25/50)=3950K
12 99.69 54 16.94 96 4.167
13 95.05 55 16.32 97 4.045 R(90°C)=5KΩ±3%
14 90.66 56 15.73 98 3.927
15 86.49 57 15.16 99 3.812
16 82.54 58 14.62 100 3.702
17 78.79 59 14.09 101 3.595
18 75.24 60 13.59 102 3.492
19 71.86 61 13.11 103 3.392
20 68.66 62 12.65 104 3.296
21 65.62 63 12.21 105 3.203
44
Unit dimensions
RVD 351-521 DC Indoor unit
650
RVD 681-1051 DC Indoor unit
950
650
950
580
840
400
580
610880
28
580
600
840
300 254
28
840
RVD 351-1051 DC Outdoor unit
A
RVD 351 DC RVD 521 DC RVD 681 DC RVD 1051 DC
A 760 840 895 990 B 270 310 313 354 C 590 700 862 966
D 530 560 860 600
E 290 335 315 375
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
B
E
C
D
All values in mm
45
REMKO RVD...DC
Exploded view RVD 351DC IT to RVD 1051DC IT
5
1
2
14
6
3
9
8
10
7
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
11
12
13
Spare parts list
No. Designation RVD 351 DC IT RVD 521 DC IT RVD 681 DC IT RVD 1051 DC IT
1 Air inlet guard 1110950 1110950 1111550 1111550 2 Air filter 1110951 1110951 1111551 1111551 3 Cover 1110952 1110952 1111552 1111552 4 Fin motor 1110953 1110953 1111553 1111553 5 Air inlet, condensate pan module 1110954 1110954 1111554 1111554 6 Outlet fins, set of 4 1110955 1110956 1111555 1111555 7 Vaporiser 1110957 1110958 1111556 1111557 8 Condensation pump cpl. 1110959 1110959 1110959 1110959
9 Fan wheel 1110960 1110961 1111558 1111559 10 Vaporiser fan motor 1110962 1110963 1111560 1111561 11 Control PCB 1110964 1110965 1111562 1111563 12 Transformer 1110966 1110966 1111564 1111564 13 Condenser, vaporiser fan 1110967 1110968 1111565 1111565 14 IR remote control 1111566 1111566 1111566 1111566
Spare parts (not illustrated)
Condensation float switch 1110970 1110970 1110970 1110970 Display board 1110971 1110971 1111567 1111567 Air circulation sensor 1110972 1110972 1110972 1110972 Vaporiser sensor 1110973 1110973 1110973 1110973
When ordering spare parts, please state the computerised part no., unit number and type (see identification plate)!
46
Exploded view RVD 351-1051 DC AT
5
6
4
11
8
9
3
2
12
10
1
7
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
Spare parts list
No. Designation RVD 351 DC AT RVD 521 DC AT RVD 681 DC AT RVD 1051 DC AT
1 Front panel
2 Fan blade, liquefier
3 Fan motor, liquefier
4 Liquefier
5 Cover panel
6 Side part
7 Compressor, cpl.
8 Stop valve, suction pipe
9 Stop valve, injection pipe
10 Reverse flow valve
11 Control PCB
12 Condenser, compressor
Spare parts (not illustrated)
E-Box, complete
Electronic expansion valve
PCB with display
Temperature sensors, set
When ordering spare parts, please state the computerised part no. and unit number (see identification plate) !
1110990 1110991 1111580 1111581
1110992 1110993 1111582 1111583
1110994 1110995 1111584 1111585
1110996 1111021 1111586 1111587
1110998 1110999 1111588 1111589
1111000 1111001 1111590 1111591
1111002 1111022 1111592 1111593
1111004 1111005 1111594 1111595
1111006 1111007 1111596 1111597
1111008 1111009 1111598 1111599
1111010 1111011 1111600 1111601
1111012 1111013 1111602 1111603
1111014 1111015 1111604 1111605
--- 1111016 1111606 1111607
--- 1111018 1111608 1111609
1111019 1111020 1111020 1111020
47
REMKO RVD...DC
Technical data
Range RVD 351DC RVD 521DC RVD 681DC RVD 1051DC
Operational mode Cooling / heating Nominal cooling output
Nominal heating output Energy efficiency class, cooling Energy efficiency ratio EER Energy efficiency class, heating Coefficient of performance COP Power consumption, annual, (500h) C/H 530 / 595 1090 / 1060 1190 / 1060 1625 / 1600 Operating range (room volume), approx. 110 160 230 320 Coolant 410A Power supply V/Hz 230/1~/50 Hz 400 / 3~ / 50 Nom. elect. power consumption,cooling 1)kW Nom. elect. power consumption,heating 2)kW Electr. rated power consumption kW Electr. nominal power consumpt. cooling 1)A Electr. nominal power consumpt. heating 2)A Electr. starting current, max. A 12,0 12,0 15,5 25,0
Coolant connection - injection line
Coolant connection - suction line
Max. operating pressure kPa
Corresponding indoor unit
Adjustment range, room temperature °C +17-+30 Operating range °C +17-+31 Air flow volume per speed setting m³/h 510/530/680 560/710/800 820/1010/1220 1100/1300/1530 Sound pressure level per speed setting 3)dB(A) 33/37/40 37/40/42 39/41/43 41/42/44 Protection degree IP X0 Condensate drain mm 25 32 Condensate pump, flow rate, max. mmWS 500 750 Dimensions - Height mm 255 250 300
Width mm 580 840
Depth mm 580 840 Dimensions Cover length / width mm 650 / 650 950 / 950 Weight kg
Corresponding outdoor unit
Operating range - cooling °C +5 - +43 Operating range - heating °C -5 - +24 Air flow rate, max. m³/h 1600/2500 2300/2570 3000 /3250 5800 /6000 Protection degree IP 24 Noise output max. Refrigerant, basic quantity kg 1,40 1,70 2,30 4,10 Refrigerant, additional quantity > 5 m g/m 30 30 30 30 Refrigerant pipe, max. length m 15 25 25 30 Refrigerant pipe, height indoor unit and
outdoor unit max. Dimensions - Height mm 590 700 860 990
Width mm 760 845 895 940
Depth mm 280 310 335 360 Weight kg 39,0 59,0 73,0 87,0 Serial number 548... 549... 713... 714... EDP no. 1623160 1623170 1623180 1623190
1) Air intake temp. TK 27°C / FK 19°C, outdoor temp. TK 35°C / FK 24°C, max. air volume, 5m pipe length in combination with MVT 900 / 950 DC
2) Air intake temperature TK 20°C outdoor temperature TK 7°C, FK 6°C, max. air volume, 5m pipe length in combination with MVT 900 / 950 DC
3) Gap 1 m free space 4) Contains greenhouse gas according to Kyoto protocol
48
1)
2)
1)
1)
2)
2)
kW kW
3,52 (1,41 to 4,11) 5,27 (1,59 to 5,65) 7,03 (1,63 to 7,92) 10,55 (3,01 to 13,22) 4,29 (1,43 to 4,83) 5,86 (1,45 to 6,15) 7,76 (1,75 to 8,61) 11,72 (3,75 to 14,02)
A A A A
3,32 3,25 3,22 3,25
A A B A
3,61 3,80 3,42 3,64
4)
1,06 (0,41-1,45) 1,62(0,56-2,63) 2,18 (0,84-2,35) 3,25 (2,31-5,50) 1,19 (0,38-1,88) 1,54 (0,72-2,65) 2,12 (0,72-2,72) 3,20 (2,00-5,22)
1,90 2,60 3,25 5,50
4,34 (2,02-12,24) 7,08 (2,43-12,35) 10,30 (3,65-11,52) 14,62 (10,09-25,01)
6,64(2,06-12,03) 6,82 (3,13-12,32) 10,05 (3,22-12,81) 14,35 (8,69-23,64)
Inches
(mm)
Inches
(mm)
1/4 (6,35) 1/4 (6,35) 3/8 (9,52) 3/8 (9,52)
1/2 (12,70) 1/2 (12,70) 5/8 (15,90) 5/8 (15,90)
4200 / 2500
RVD 351DC IT RVD 521DC IT RVD 681DC IT RVD 1051DC IT
18,0 21,0 29,0 30,0
RVD 351DC AT RVD 521DC AT RVD 681DC AT RVD 1051DC AT
3)
dB(A) 48 52 53 55
m 10 10 10 20
3, 0
2, 5
1, 5
2, 0
3, 5
4, 0
4, 5
1, 0
0 3 6 9 12 -15 -12 -9 -6
-3
0, 80
1, 00
1, 20
1, 40
0, 30
0, 50
0, 70
7. 00
7, 00
6. 50
5. 50
6. 00
7. 50
8. 00
8. 50
5. 00
1. 50
2. 00
2. 50
3. 00
0. 90
0. 95
1. 00
4. 50
0
3 6 9 12 -15 - 11
-9
-6
-3
15
18
14, 00
2. 50
3. 00
3. 50
4. 00
0. 90
1. 00
2. 00
13, 00
12, 00
11, 00
10, 00
9, 00
8, 00
7, 00
6, 00
0
3 6 9 12 -15 - 11
-9
-6
-3
15
18
Performance charts for heating
RVD 351 DC
1
Heating output
Elec. power consumption
Outdoor temperature
RVD 521 DC
6. 50
6. 00
5. 50
1
5, 00
4. 50
4. 00
3. 50
Heating output
3. 00
1. 70
1. 60
1. 50
1. 40
1. 30
1. 20
1. 10
Elec. power consumption
-9
-3
-6
Outdoor temperature
3 6 9 12 -15 - 11
0
15
18
RVD 681 DC
1
RVD 1051 DC
1
Heating output
Heating output
Elec. power consumption
Elec. power consumption
Outdoor temperature
1) Air intake temperature TK 20°C, outdoor temperature TK 7°C, FK 6°C, max. air flow volume, 5m pipe length
Outdoor temperature
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
49
REMKO RVD...DC
EC – Declaration of Conformity
in accordance with the Machinery Directive, Annex II 1A
Original Declaration of Conformity
We hereby declate that the devices described in the following section conform to the require­ments of the specified applicable EC directives due to their design and type in the version as marketed by us.
Name of Manufacturer: REMKO GmbH & Co. KG Klima- und Wärmetechnik Im Seelenkamp 12 D - 32791 Lage
Name of Authorised Agent: REMKO GmbH & Co. KG Klima- und Wärmetechnik Im Seelenkamp 12 D - 32791 Lage
Equipment (machinery) - Implementation: Inverter ceiling-mounted air conditioner in split design
Series / Model: RVD 681 DC, RVD 1051 DC Series / Class Number: 548..., 549..., 713..., 714...
Applicable regulations: MA DIR. 2006/42/EC Machinery Directive LV DIR. 2006/95/EC Low-Voltage Directive EMC DIR. 2004/108 EEC Electromagnetic Compatibility Directive EnCLB DIR. 92/75/EEC Energy Consumption Labelling Directive EC 97/23/EC Pressure Equipment Directive
Applicable Standards: DIN EN ISO 12100-1-2 : 2004-04; DIN EN ISO 13857, EN 14511 T1-4; DIN 45635 - 1; EN 378 – 1-4; EN 55014 - 1; EN 55014 - 2; EN 55104 EN 60204 - 1; EN 60335 - 1; EN 60335 - 2 - 40; EN 61000 - 3 - 2; EN 61000 - 3 - 3;
REMKO RVD 351DC, RVD 521 DC,
Lage, 22nd January 2010 REMKO GmbH & Co. KG
..............................................
Signature, Product Manager
50
REMKO INTERNATIONAL
… and also right in your neighbourhood! Make use of our experience and advice
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telefon +49 5232 606-0 Telefax +49 52 32 6 06-2 60 E-mail info@remko.de Internet www.remko.de
Hotline
Klima- und Wärmetechnik
+49 5232 606-0
Export
+49 5232 606-130
Advice
We keep the specialist knowl-
edge of our advisers continu-
ously up-to-date with intensive
training. This has earned us a
reputation as more than just a
good, reliable supplier:
REMKO, a partner
who is here to help solve prob-
lems.
Distribution
REMKO provides not only a
well-developed distribution
network in Germany and abroad,
but also unusually highly skilled
professionals in distribution.
REMKO staff in the field are
more than mere salespeople:
they must primarily act as
advisers in air conditioning and
heating technology for our
customers.
Customer Service
Our units work precisely and
dependably. Should a failure
occur, however, REMKO cus-
tomer service will rapidly be at
your side. Our comprehensive
network of experienced dealers
guarantees quick and
reliable service.
Subject to technical modifications, no responsibility taken for the correctness of information!
Loading...