Inverter ceiling-mounted air conditioner in split design
Operation · Technology · Spare parts
Edition GB – W09
Contents
Safety notes
Environmental protection and recycling
Warranty
Intended use
Transport and packaging
Description of the equipment
Operation
Shutdown
Care and maintenance
Installation instructions for qualified personnel
Installation
Tightness check
Condensate drain
4
4
4
4
5
5
6-12
13
13-14
15-18
18-19
20
20
Before commissioning
Electrical connection
Electrical connection diagram
Electrical circuit diagram
Add refrigerant
Commissioning
Troubleshooting and customer service
Resistances of the temperature- and hot gas sensors
Unit dimensions
Exploded view
Spare parts list
Technical data and performance charts for heating
EC-Declaration of Conformity
21
21
22
23-26
27
27-28
29-41
42-44
45
46-47
46-47
48-49
50
Made by REMKO
These operating instructions should be read carefully
prior to commissioning / operation of the equipment!
These instructions are part of the equipment and must always
be kept in the vicinity of the installation or on the equipment.
This operating manual is a translation of the German original.
Subject to modifications; No liability accepted for errors or misprints!
3
REMKO RVD...DC
Safety notes
Carefully read this manual before
putting commissioning the
equipment. It provides useful
tips and information as well as
hazard warnings to prevent injury
or material damage . Failure to
follow the directions in this manual
can result in endangerment to
persons, the environment and the
equipment itself and will void any
claims for liability.
■ Keep this manual and the
refrigerant datasheet near the
unit.
■ The unit may only be set up and
installed by qualified personnel.
■ The setup, connection and
operation of the unit and
its components must be in
accordance with the operating
conditions stipulated in this
manual and comply with all
applicable local regulations.
■ Mobile units must be set up
securely on suitable surfaces and
in an upright position. Stationary
units must be permanently
installed for operation.
■ Modification of equipment
and components supplied by
REMKO is not permitted and
can cause malfunctions.
■ Equipment and components
may not be operated in areas
where there is an increased
risk of damage. Observe the
minimum clearances.
■ The electrical voltage supply
is to be adapted to the
requirements of the equipment.
■ The operational safety of
equipment and components is
only assured if they are used as
intended and fully assembled.
Safety devices may not be
modified or bypassed.
■ Do not operate equipment
or components with obvious
defects or signs of damage.
■ All housing parts and openings,
e.g. air inlets and outlets, must
be free of foreign objects, fluids
or gases.
■ The equipment and components
must be kept an adequate
distance from flammable,
explosive, combustible,
aggressive and dirty areas or
atmospheres.
■ Touching equipment parts can
result in burns or injury.
■ Installation, repair and
maintenance work may only
be carried out by authorised
specialists. Visual inspections
and cleaning can be performed
by the operator as long as the
equipment is not under voltage.
■ Take appropriate hazard
prevention measures when
performing installation, repair or
maintenance work or cleaning
the equipment.
■ The equipment or components
are not to be exposed to any
mechanical stresses, extreme
levels of humidity or direct
sunlight.
Warranty
Prerequisite for any warranty claims
are that the purchaser or their
customer has completely filled out
the "warranty registration card"
and commissioning report included
with the unit at the time when the
equipment was purchased and first
put into operation and returned it
to REMKO GmbH & Co. KG.
The warranty conditions are
listed in the "General Business
and Delivery Conditions". Only
the contractual parties can strike
special agreements beyond these
conditions. For this reason please
first contact your direct contractual
partner.
Environmental
protection
and recycling
Disposal of packaging
All products are packed for
transport in environmentally
friendly materials. Make a valuable
contribution to reducing waste
and sustaining raw materials.
Only dispose of packaging at
approved collection points.
Disposal of equipment
and components
Only recyclable materials are used
in the manufacture of the devices
and components,
Help protect the environment
by ensuring that the devices
or components (for example
batteries) are not disposed in
household waste, but only in
accordance with local regulations
and in an environmentally safe
manner, e.g. through authorised
disposal and recycling specialists or
at collection points.
Intended use
Depending on the model, the
equipment and the additional
fittings with which it is equipped
is only intended to be used as an
air-conditioner for the purpose of
cooling or heating the air in an
enclosed room.
Different or additional use shall not
be classed as intended use. The
manufacturer/supplier assumes no
liability for damages arising from an
unintended use of the equipment.
The user bears the sole risk in such
cases.
Using the equipment as intended
also includes working in accordance with the operating manual
and installation instructions and
complying with the maintenance
requirements.
4
M
M
RXT351DC
T2
T
3
T5
M
M
TE
PSH
T1
T2
T
3
T5
P
S
L
RXT1051 DC
M
M
PS H
T1
T2
T
3
TE
T5
P
S
L
Transport and
Packaging
The equipment is shipped in sturdy
transport packaging. Immediately
check the equipment on delivery and
make a note of any damage or missing parts on the delivery note. Inform
the forwarding agent and contractual
partner. Warranty claims at a later
date will not be accepted.
Description of the
equipment
The RVD 351-1051DC room air
conditioning units have a REMKO
RVD...AT outdoor component as
well as an indoor unit RVD...IT.
The outdoor unit serves to output
the heat extracted by the indoor
unit from the room being cooled.
In heating operation, the heat
absorbed by the outdoor component can be discharged through
the indoor unit into the room being
heated.SFlbIn both operating modes,
the performance of the compressor
precisely adjusts itself to the demand, thereby regulating the target
temperature with minimal temperature variations. This "inverter-technology" enables power saving over
conventional split systems and also
reduces noise emissions to a particularly low level.
The outdoor component is mounted
outdoors or under the observation of certain requirements it may
be installed indoors. The outdoor
component consists of a refrigerant
circuit with compressor, fin liquefier,
liquefier fan, reverse flow valve and
flow regulator. The outdoor unit is
controlled via the regulation of the
indoor unit.
The indoor unit is designed for
indoor installation in suspended
ceilings with Euroraster dimensions.
The cassette is hidden behind the
suspended ceiling, only its cover is
visible. Operation is undertaken via
an infrared remote control unit. The
indoor unit consists of a fin vaporiser, vaporiser fan, regulation system
and condensation pan.
Floor consoles, wall consoles, refrigerant pipes and a winter control
program are available as accessories.
Schematic of refrigerant circuit series RVD 351-1051 DC
RVD 351 DC
RVD 521-681 DC
RVD 1051 DC
T2
M1
T2
M1
T2
M1
T3
M1 - Condenser fan
M2 - Compressor
M3 - Vaporiser fan IU
V1 - Reversing valve C/H
EEV - Elec. Expansion valve
PSH - High pressure switch OU
V1
T1
M2
T3
Filter
PSL
V1
M2
T3
PSL
V1
M2
Oil return
EEV
EEV
Filter
PSH
T1
Filter
PSH
T1
FilterFilter
PSL - Low pressure switch OU
T1 - Sensor hot gas OU
T2 - Sensor air intake OU
T3 - Sensor condenser OU
T4 - Sensor air intake IU
T5 - Sensor vaporiser IU
Indoor areaOutdoor area
M3
M3
M3
IU - Indoor unit
OU - Outdoor unit
System layout
Indoor area
Indoor unit
Condensate drain
Outdoor area
Outdoor unit
Control line
Power output
Injection pipe
suction pipe
Condensate line
Shut-off valve
Condenser fan
The connection between the indoor unit and the outdoor component is
made with refrigerant pipes.
T5
T4
T5
T4
T5
T4
5
REMKO RVD...DC
Operation
The indoor unit is easy to operate using an infrared remote control. This is supplied as standard. The indoor unit
beeps to acknowledge the correct transmission of data. If it is not possible to program
the indoor unit using the remote control, it can also be manually operated.
Manual operation
The indoor units can be started
manually. Press the RESET button
on the receiver unit of the cover to
activate automatic mode. In manual
operation, the following settings
apply:
Cooling mode: 24 °C,
Fan speed AUTO
Heating mode: 26 °C,
Fan speed AUTO
Pressing any button on the infrared remote control interrupts
manual operation
Display on indoor unit
The lit display LEDs indicate the settings.
LED “Operation” green = Operation screen
LED “Timer” yellow = Timer mode
LED “Pre/Def” red = Defroster mode
LED “Alarm” red = Malfunction screen
Display RVD 351-521 DC
Display on indoor unit
Unit for receiving signals
from the remote control
Operation-
screen
Timerscreen
Defrost
Display RVD 681-1051 DC
Display on indoor unit
Fan
Alarm display
infrared remote control
The infrared remote control sends
the programmed settings over a
distance of up to 6 m to the receiver of the indoor unit. Data will
only be received correctly if the
remote control is pointed at the receiver and no objects are obstructing the transmission path.
First insert the supplied batteries
(2 x type AAA) into the remote
control. To do so, pull off the flap
of the battery compartment and
insert the batteries according to
their polarization (see marks).
Operation-
screen
Maximum distance
max. 6 m
Timerscreen
Display
screen
Fan
Defrost
Alarm display
Infrared
receiver
! CAUTION
Problems are
shown in code
(see chapter Troubleshooting
and Customer service).
NOTE
Immediately replace flat batteries with a new set, otherwise
there is a risk of leakage. It is
recommended that the batteries
are removed if the equipment is
shut down for long periods.
6
Keys on the remote control
Keys on the remote control
"ON/OFF"key
Press this key to operate the
unit.
"MODE" key
Press this key to select the
operating mode.
The indoor unit has 4 modes:
1. Automatic mode
In this mode, the unit works in
cooling or in heating mode.
2. Cooling mode
In this mode, the warm air in
the room is cooled down to the
desired temperature.
3. Dehumidification mode
In this mode the room is mainly
dehumidified and the adjusted
temperature is maintained.
4. Heating mode
In this mode, the warm air in
the room is warmed to the
desired temperature.
5. Air circulation mode
In this mode, the air in the
room is circulated with no
change in temperature.
"FAN SPEED" key
Press this key to set the
desired fan speed. 4 speeds
are available: Automatic, high,
medium and low fan speed.
Key "SLEEP"
Pressing this key
will automatically increase or
decrease the target temperature
by 1 °C every hour in cooling
and heating mode respectively.
Key „SWING HORIZONTAL“
This key directly activates the
oscillating function of the fins
for better air distribution in the
room.
"TIMER ON" key
This key serves to program the
automatic shut-off time in 0.5
h intervals within the following
24 hours.
"TIMER OFF" key
This key serves to program the
automatic shut-off time in 0.5
h intervals within the following
24 hours.
"RESET" key
This key resets the remote
control to its factory default
configuration.
"TURBO"key
The TURBO function activates
the maximum fan speed and
the compressor.
"▼ " key
With this key, the desired
temperature can be decreased
to 17°C.
"▲ " key
With this key, the desired
temperature
can be increased up to 30°C.
"Follow me" function key
With this key, the sensing of
the room temperature is moved
from the interior unit to the
remote control.
The temperature measured
on the remote control is then
transmitted to the interior unit
in certain intervals.
"Lock" key
This key can be used to lock
the keys on the remote control.
This allows unintentional
adjustment to be prevented.
7
REMKO RVD...DC
Remote control display
Indicator arrows will be displayed according to the settings.
Display on indoor unit
Automatic operation
Cooling mode
Dehumidifying mode
Heating mode
Fan speed
Temperature display
Key functions
A symbol is shown on the display to indicate that the settings are being transferred.
Remote control on/off
The remote control's on/off function is shown at the upper right of the
remote control by a "wind symbol".
RESET key
The remote control can be reset by pressing the RESET key (recessed key).
ON/OFF key
8
Your air-conditioner is activated and deactivated by pressing the ON /
OFF key. The programmed settings and adjustment values before the
unit was turned off will appear in the display.
ON/OFFON/OFF
▲/▼ Keys
Using the key, the target temperature can be adjusted up or down by
1°C. The temperature range lies between 17°C and 30°C
MODE key
Cooling mode
▼
▼
Automatic mode
▲
▲
Use the MODE key to select between individual operating modes. A total
of 5 modes are available:
1. Automatic cooling or heating operation
2. Cooling primarily summer mode
3. Dehumidifying operating mode for summer or winter
4. Heating primarily winter mode
5. Circulation air circulation only
AutomaticCoolingDehumidifyingHeating
MODEMODEMODE
Air circulation
AUTOMATIC MODE
In automatic mode, the controller autonomously selects between heating,
circulation or cooling mode based on the room temperature Tr and
the selected target value Ts. The target value can be adjusted between
17°C and 30°C by means of the ▲/▼ keys. The fan speed is selected
automatically.
MODE
AUTOMATIC
Operational sequence:
If Tr is less than 1K as Ts, then operating mode "Heating" is selected.
If Tr is greater than 2K as Ts, then operating mode "Cooling" is selected.
If Tr is between Ts -1K as Ts +2K, then operating mode "Circulation" is selected.
If after the compressor is shut down and not required for more than 15 mins. within an operating mode, then,
in the event that the room temperature deviates, the corresponding mode heating, cooling or circulation
will be selected again.
9
REMKO RVD...DC
Cooling MODE
Dehumidification MODE
In cooling mode, the air in the room is cooled down to the adjusted
nominal temperature. The desired room temperature is set with the ▲/▼
keys in 1 °C increments. If the room temperature is 0.5 °C above the
selected nominal temperature, then the interior unit starts to cool down
the air in the room. If the temperature falls to approx. 1 °C below the set
room temperature, the controller will switch off the cooling function. To
protect the compressor, the controller only turns cooling on again after a
waiting period of 3 minutes.
MODE
It is recommended that the target temperature be set to 24°C in
dehumidifying mode. Due to the low temperature of the refrigerant, the
dew point of the air at the condenser is undercut. The excess moisture in
the air is condensed by the vaporiser, the room is dehumidified.
COOLING
OPERATION
HEATING Mode
MODE
In the heating mode, you can heat the room in spring or fall. The selected
room temperature is set using the ▲/▼ keys in 1 °C increments. If the
room temperature is 1 °C below the selected target temperature, the
indoor unit starts to heat the air in the room. If the set room temperature
is exceeded by approx. 1 °C, the controller will switch off the heater
function. To protect the compressor, the controller will wait 3 minutes
before switching on the heating mode again.
MODE
DEHUMIDIFICATION
MODE
HEATING
OPERATION
10
FAN SPEED Key
The fan speed can be adjusted with this key. A selection can be made
between low, medium, high and automatic fan speed.
SWING HORIZONTAL key
Automatic
FAN
Speed
HighMedium
FAN
Speed
FAN
Speed
Low
FAN
Speed
The oscillating function of the air fins can be adjusted with this key. This
makes it possible to switch directly between a preset position and the
oscillating function. The air distribution in the room is improved with the
swing function.
Pressing the button for longer than 2s causes the oscillating function to
activate. To set your desired position, the button must be pressed for
another 2s.
The “Swing Vertical” button has not been assigned a function.
11
REMKO RVD...DC
SLEEP key
TIMER Key
A programming function is activated using this key, which increases the
target temperature in cooling mode by 1°C after one hour and by 2°C
after 2 hours. In heating mode, the target temperature is decreased
by 1 °C after one hour by 2 °C after 2 hours. The unit switches off
automatically after 8 hours.
The activation and switch-off time can be programmed with this key.
The timer is activated and the time display is switched off by pressing
the Timer on or Timer off key. The timer display on the indoor unit
illuminates. The desired activation or deactivation time is set by pressing
the Timer On or Timer Off keys. When the programmed time has been
reached, the device automatically switches on or off. If the indoor unit
is automatically switched on, the mode, temperature and fan speed for
the last setting are activated. Deleting the preset on and off time early is
carried out by pressing the ON/OFF key. The timer display on the interior
unit turns off.
TIMER ON Key
TIMER OFF Key
Timer On
Timer Off
Timer On
Timer Off
3 sec.
3 sec.
12
Shutdown
Care and maintenance
Temporary shutdown
1. Allow the indoor unit to run for
2 to 3 hours in air circulation
mode or in cooling mode at the
maximum temperature setting
in order to remove any residual
moisture from the unit.
2. Shut down the unit using the
remote control.
3. Switch off the voltage supply to
the unit.
4. Cover the unit as far as possible with plastic foil in order to
protect it from the influences of
weather.
Permanent
Shutdown
Ensure that equipment and components are disposed of in accordance with local regulations, e.g.
through authorised disposal
and recycling specialists or at collection points.
Regular care and maintenance
serves to ensure trouble-free operation and long service life of the
unit.
! CAUTION
Prior to performing any work,
ensure the equipment is isolated from the voltage supply
and secured to prevent accidental switch-on!
NOTE
The statutory regulations
require an annual sealing test
for the refrigerant circuit in
relation to the refrigerant
filling level. The inspection
and documentation is to be
carried out by corresponding
specialist engineers.
Care
■
Ensure the indoor unit and outdoor component are protected
against dirt, mould and other
deposits.
■
Clean the equipment using a
damp cloth. Do not use any
caustic, abrasive or solventbased cleaning products. Do
not use a jet of water.
■
Clean the fins on the indoor
unit and outdoor component
prior to long shutdown periods.
Maintenance
■
It is recommended that
you take out a maintenance
contract with an annual service
from an appropriate specialist
firm.
■
Systems which operate yearround (e.g. in server rooms),
the maintenance intervals must
be reduced accordingly.
TIP
This ensures the operational
reliability of your
equipment!
Contact REMKO GmbH & Co. KG
or your contract partner for a list
of specialist companies near you.
Type of task
Checks/Maintenance/Inspections
General
Measure voltage and current
Check compressor/fans are functioning correctly
Check fan is functioning correctly
Dirt on liquefier/vaporiser
Check refrigerant fill quantity
Check condensation drain
Test insulation
Check moving parts
Sealing test for refrigerant circuit
1) see note
Commissioning
Monthly
Six-monthly
••
••
••
••
••
••
••
••
••
• •
Yearly
1)
13
REMKO RVD...DC
Cleaning the cover
of the indoor unit
1. Disconnect the supply voltage
to the equipment.
2. Open and fold down the air
inlet guard on the cover. The
filter is held in place by the flaps
screwed in at the side of the
guard (Fig. 1).
3. Clean the guard using a soft,
damp cloth.
4. Switch the supply voltage back
on.
Air filter for indoor unit
Clean the air filter at intervals of
no more than 2 weeks.
Reduce this interval in case of
heavily soiled air.
5. Any dirt can be cleaned off using lukewarm water and mild
cleaning agents.
To do so, turn the dirty side
downward (Fig. 3).
6. When using water, allow
the filter dry out properly in air
before replacing it in the unit.
7. Carefully insert the filter. Make
sure it is seated correctly.
8. Close the cover as described
above but in reverse order.
9. Switch the supply voltage back
on.
10.
Switch the unit back on.
Cleaning the
condensation pump
The indoor unit includes a built-in
condensation pump,
for pumping the condensation to a
drain at a higher level.
1 Guard on cover
2 Clean with a vacuum cleaner
3
Cleaning with lukewarm water
Cleaning the filter
1. Disconnect the supply voltage
to the equipment.
2. Open and fold down the air
inlet guard on the cover. The
filter is held in place by the flaps
screwed in at the side of the
guard (Fig. 1).
3. Tilt the filter and lift it out.
4. Clean the filter using a normal
vacuum cleaner (Fig. 2).
Turn the dirty side until it faces
up.
The pump is more or less maintenance free. The condensation
pipes should be checked for dirt
at regular intervals. Clean them as
required.
If an external pump is also used,
observe the maintenance and care
instructions given in the separate
operating manual.
14
Installation instructions for qualified personnel
Important points prior to installation
■
Transport the unit in its original
packaging as close as possible
to the installation location to
avoid transport damage.
■
Check the contents of the
packaging for completeness
and check the unit for visible
transport damage. Report any
damage immediately to your
contracting party and the shipping company.
■
Lift the unit at the corners and
not by the refrigerant or condensation connections.
■
The refrigerant pipes
(injection and suction pipe),
valves and connections must be
insulated impervious to vapour
diffusion. If necessary, also insulate the condensation pipe.
■
Select an installation location
which allows air to freely flow
through the inlet and outlet.
(See section "Minimum clearances").
■
Do not install the unit in the
immediate vicinity of devices
with intensive thermal radiation. Installation near sources of
thermal radiation reduces the
output of the unit.
■
Open the blocking valves of the
refrigerant pipes only after the
installation is complete.
■
Seal off open refrigerant pipes
with suitable caps or adhesive
strips to avoid infiltration of
moisture
and never kink or compress the
refrigerant pipes.
■
Avoid unnecessary
bends. This minimises the pressure loss in the refrigerant pipes
and ensures that the compressor oil can flow back without
obstruction.
■
Use four supports and the associated hooks to attach the
ceiling cassette.
■
Use the insulated condensation
hose in the scope of delivery as
a junction piece to the continuing condensate drain. Secure
the condensate drain with the
supplied clamps.
4
Fixing materials for RVD 261-681 DC
Insulation
Suspension
Adapter piece
Clamps
15
REMKO RVD...DC
Wall openings
■
A wall opening of at least 70
mm diameter and 10 mm slope
from the inside to the outside
must be made for each indoor
unit.
■
We recommend that the inside
of the hole is padded or lined,
e.g. using a PVC tube, to prevent the pipes being damaged.
■
After installation, the wall
opening should be closed off on
the building side with a suitable
sealant. Do not use materials
containing cement or lime!
Pipes and cables in wall breakthrough
Control line
PVC tube
Suction pipe
Condensation line
Injection pipe
Installation material
Selection of the installation
location
Interior unit
The indoor unit is designed for
horizontal wall installation above
doors. However, it can also be
used on the upper wall area
(min. 1.75 m from upper edge of
floor).
Exterior unit
The outdoor component is designed for horizontal base installation in outdoor areas. It should
be placed on level, flat and firm
ground. The unit should also
be secured to prevent toppling.
The outdoor component can be
set up outside as well as inside a
building. For external installation,
please observe the following notes
to protect the unit from weather
conditions.
Rain
The unit should be at least 10 cm
off the ground when mounted on
the roof or ground. A floor bracket
is optionally available.
Wind
If the unit is being installed in
windy areas, ensure that the warm
outlet air discharges in the main
wind direction. If this is not the
case it may be necessary to install
a windbreak (provided by the customer). Ensure that the windbreak
does not adversely affect the air
intake to the unit.
Windbreak
Wind
The indoor unit is fastened
using a wall bracket and 4 threaded
screws (provided by the customer).
The outdoor component is attached with 4 screws and a wall
bracket to the wall or fixed by a
floor bracket to the ground.
16
Sun
The liquefier on the outdoor unit
radiates heat.
Exposure to direct sunlight will
further increase the temperature of
the fins and reduce the heat output of the finned heat exchanger.
The outdoor unit should therefore
be installed as near as possible to
the north side of the building. If
necessary, take measures to provide sufficient shade (responsibility
of customer). One possible solution is to build a small roof. These
measures should not affect the
flow of warm outlet air.
Snow
The unit should be wall-mounted
in areas of heavy snowfall.
Installation should be at least 20
cm above the expected level of
snow to prevent snow from entering the outdoor component. An
optional wall bracket is available as
an accessory.
Minimum clearance to snow
■
Ensure a continuous and unobstructed air flow from outside,
preferably using sufficiently
large air intakes placed opposite
each other
(Figure 5).
5 Installation inside buildings
Warm air
Additional
fan
■
Comply with any regulations
and conditions affecting the
statics of the building. If necessary, fit acoustic installation.
Cold
Fresh air
Snow
20 cm
Installation inside buildings
■
Ensure there is adequate heat
dissipation when placing the
outdoor component in cellars,
attics, adjoining rooms or halls
(Fig 5).
■
Install an additional fan with a
rated flow comparative to that
of the outdoor unit being installed in the room. This is used
in conjunction with ventilation
ducts to compensate any pressure losses
(Figure 5).
Light
well
Warm air
Exterior unit
Light
well
Minimum clearances
Observe the minimum clearances to allow access for maintenance and
repair work and facilitate optimum air distribution.
Minimum clearances
1000
1000
Air intake
1000
D
1000
A
500
E
Air outlet
B
All values in mm
C
RVD 351DC AT RVD 521DC AT RVD 681DC AT RVD 1051DC AT
A150 mm
B900 mm
C500 mm
D150 mm
E500 mm
17
REMKO RVD...DC
Oil return measures
If the outdoor component is
installed at a higher level than
the indoor unit, suitable oil return
measures must be taken. Usually
an oil pump bend is installed for
every 2.5 metres of height difference.
Oil return measures
Exterior unit
Oil pump bend
in suction pipe to
outdoor unit
1 x every 5
metres of rising
pipe
Radius:
50 mm
max. 5/10 m
Interior unit
lection tray.
3. Fit the ceiling cassette approx.
2 cm higher than the surface of
the ceiling. (see Figure 8)
4. Make sure that clearance A,
(Fig. 8) as specified in the table
below, is provided between the
underside of the suspended
unit and the underside of the
fastening surface.
5. Connect the refrigerant pipes,
electrical cables and condensation line to the indoor unit as
described below.
6. Check that the unit is level.
7. The final task is to tighten the
counternuts and attach the
cover.
6 Mounting the unit
400
All dimensions in mm
Dimensions in
mm
RVD 351-
521DC
Distance A35 mm
Distance B25 mm
Mounting
the unit
Dimensions in
mm
620 x 400 mm
RVD 681-
1051DC
Distance A35 mm
610
Installation
NOTE
Installation should only be
performed by authorised specialists.
Unit installation
The indoor unit is mounted face
down on four threaded rods. Take
into account the ceiling grid and
any other installations.
1. Use the dimensions of the ceiling cassette (Fig. 6) to mark the
fixing points for the threaded
rods on structural parts approved to support the static
load above the suspended ceiling.
7 Hooking in the unit
8 Fastening the unit
Structural component
A
B
Distance B25 mm
Mounting
the unit
Structural component
620 x 400 mm
Structural component
2. Fit the indoor unit onto the
threaded rods and use the
lower nuts to level the unit
(Fig. 7).This ensures that the
condensate drains into the col-
18
abaut 2 cm
Connection of
refrigerant pipes
The on-site connection of the
refrigerant pipes is made at the
rear of the unit.
It may be necessary to fit a reducer
or flared adapter to the indoor
unit. These fittings are included
as standard with the indoor unit.
Once installed, the connections
should be made tight against vapour diffusion.
CAUTION
!
The units are factory filled with
dry nitrogen to check for leaks.
The pressurised nitrogen is
released when loosening the
union nuts.
The following instructions describe
the installation of the refrigerant circuit and the assembly of
the indoor unit and the outdoor
component.
5. Verify that the shape of the
flange is correct(Figure 11).
6. First connect and hand-tighten
the refrigerant connections
to ensure they are correctly
seated.
7. Now fully tighten the fittings
using 2 suitably sized openended spanners. Use one spanner to counter the force when
tightening the fitting (Figure
12).
8. Use insulation hoses which are
designed for this temperature
range and diffusion tight.
9. Lay the refrigerant pipes from
the indoor unit to the outdoor
component. In doing so, ensure
9 Deburring the refrigerant pipe
Refrigerant pipe
that they are sufficiently at-
tached and take measures for
the oil return, if necessary!
10.
Observe the permitted bending radius for the refrigerant
pipes during installation. Never
bend a pipe twice in the same
place. Brittle pipes and potential
cracking are the consequences.
NOTE
Only employ tools and components suitable for refrigeration applications.
11.
Use the wall or floor brackets
to fit the outdoor component
against structural parts approved to support the static
load (refer to the installation
instructions for the brackets).
10 Flanging the refrigerant pipe
Flanging tool
1.
The required pipe diameters are
given in the table "Technical
data".
2. Remove the factory-fitted protective caps and union nuts on
the connections. These should
be used during installation.
3. Before flanging the refrigerant
pipes, ensure that the union nut
is fitted on the pipe.
4. Prepare the laid refrigerant
pipes as shown below
(Fig. 9+10).
Deburrer
11 Correct flange shape
12 Tighten the fitting
Tighten 1. spanner
Counter
2. spanner
Tightening
torque:
“
15-20 Nm
“
33-40 Nm
“
50-60 Nm
“
65-75 Nm
“
95-105 Nm
19
REMKO RVD...DC
Tightness check
Once all the connections have
been established, the pressure
gauge station is attached as follows to the Schrader valve (if
fitted):
red = small valve
= injection pressure
blue = large valve
= suction pressure
Once connected, perform a tightness test using dried nitrogen.
The tightness test involves spraying a leak detection spray onto
the connections. If bubbles are
visible, the connections have not
been properly made. Re-tighten
the connection or prepare a new
flange.
If the tightness test is successfully completed, depressurise
the refrigerant pipes and start a
vacuum pump with an absolute
final partial pressure of min. 10
mbar to remove the air in the pipe.
Any humidity present in the pipes
is also removed.
!
CAUTION
A vacuum of min. 20 mbar
must be created!
Condensate drain
If the temperature falls below the
dew point, condensation will form
on the cooling fins during cooling
mode.
A collection tray together with
a condensation pump and float
switch are fitted as standard below
the cooling fins. Should the float
switch trip a protective shutdown
due to inadequate removal of
the condensation, the pump will
switch on immediately and run on
for approx. three minutes.
■
The condensation pipe should
have a fall of min. 2 %. This is
the responsibility of the customer. If necessary, fit vapour
diffusion proof insulation.
■
If the level of the condensation
pipe on the unit is above that of
the outlet, route the pipe vertically upwards and then with a
fall to the drain.
■ The delivery rate varies accord-
ing to device type (see right)
■
The condensation line from the
unit should run freely into the
drainage pipe. If the condensation runs directly into a sewer
pipe, fit a trap to prevent any
unpleasant odours.
Condensation connection - Wrong!
Riser pipe too far away
No fall
Condensation pipe too large/small
Cannot freely drain away
Condensation connection - Correct!
min. 2% fall
12-20 mm
500 mm
750 mm
The time required to generate the
vacuum is dependent on the pipework volume of the indoor unit
and the length of the refrigerant
pipes. This always takes at least
60 minutes.
Once any foreign gases and
humidity have been completely
extracted from the system, the
valves on the pressure gauge station are closed and the valves on
the outdoor unit are opened as
described in the chapter on "Commissioning".
20
■
When operating the unit at
outdoor temperatures below
4°C, ensure the condensation
pipe is laid to protect it against
frost. If necessary, fit supplementary pipe heating.
■
Once the pipe has been laid,
check the condensation drains
off and permanently seal it.
■
Local regulations or laws of
environmental protection, eg
Water Resources Act (WHG)
are observed.
max. 100 mm
! CAUTION
The maximum flow rate of the
condensate pump is 500/750
mm head. External influences,
such as for example can air-side
pressure, pollution, or wear it
come to power reduction. To
ensure a safe functional operation, we recommend a maximum lifting height of 500 mm,
not to exceed!
Before
Commissioning
After the tightness check has been
successfully completed,
connect the vacuum pump via the
pressure gauge station to the valve
connections on the outdoor unit
(see chapter "Tightness check")
and create a vacuum.
Perform the following checks prior
to commissioning the unit for the
first time and after any interventions affecting the refrigerant
circuit. Record the results in the
commissioning report:
■
Check of all refrigerant
pipes and valves with
leak detection spray or soapy
water for leaks and for inadvertent mix up of suction and
injection pipe, with the unit at a
standstill.
■
Check of all refrigerant
pipes and insulation for damage.
■
Check of all electrical
connections between
indoor unit and outdoor unit
for correct polarity.
■
Check that all fastenings,
mountings etc.
are firm and at the correct level.
! CAUTION
All electrical installation work
should be performed by specialist contractors. Isolate the
voltage supply when connecting the electrical terminals.
■
We recommend that customers install a main/repair switch
in the vicinity of the outdoor
component.
■
The terminal blocks for making
the connections are located at
the rear of the unit. When the
unit is installed, measurements
can be made from the front by
removing the cover.
■
If an optional condensation
pump is used in conjunction
with the unit, it may be necessary to install an additional relay
with a higher contact rating
after the switch-off contact
on the pump to switch off the
compressor.
■
Control cables should be
screened if laid in areas exposed
to strong magnetic fields.
■
Details concerning the electrical
protection
of the system are given in the
section on technical data.
nent. See electrical connection
diagram.
4. Re-assemble the unit.
13
Connecting the indoor unit
Cover
Terminal
block
Control line
Connecting the outdoor unit
Proceed as follows to connect the
cable:
1. Remove the cover from the
unit.
2. Remove the side panel next to
the terminals.
Electrical connection
A protected mains supply cable
and control cable should be connected to the outdoor component
RVD 351-1051DC and indoor unit
respectively.
NOTE
We recommend realising the
control lines with shielded
cable.
Connecting the indoor unit
Make the connection as follows:
1. Open the air intake grill.
2. Unfasten the cover on the
right side (RVD 351-521DC) or
below the panel (RVD 6811051DC (Fig. 13).
3. Connect the unit to the control
cable on the outdoor compo-
3. Select the cable cross-section
according to the relevant standards.
4. Feed both cables through the
edge protection rings on the
fixed connection panel.
5. Terminate the cables as shown
on the electrical connection
diagram.
6. Support the cable in the strain
relief and re-assemble the unit.
21
REMKO RVD...DC
Electrical connection diagrams
RVD 351 DC
Indoor unit
L1
Phase cond.
N
Neutral cond.
S
Data cond.
Earth conductor
Outdoor unit
L1
N
S
Power output
Phase cond.
Neutral cond.
Earth conductor
230 V~,
50 Hz,
L1 / N / PE
Note:
The A-E plug to connect a cable remote control!
Terminals X, Y, E at RVT 521 DC are not used!
The attached fixed resistor is not needed
RVD 521DC
Indoor unit
L
Phase conductor
N
Neutral conductor
P
Control conductor
Q
Control conductor
E
Control conductor
PEPE
Earth conductor
Outdoor unit
L
Phase conductor
Neutral conductor
N
P
Q
E
Earth conductor
Note:
The A-E plug to connect a cable remote control!
Terminals X, Y, E at RVT 521-1051DC are not used!
The attached fixed resistor is not needed
Power output
L
N
PE
230 V~,
50 Hz,
L / N / PE
Note:
For the correct address selection, all 4 DIP switches (red) to ON
DIP-Switch
Note:
For the correct address selection, all 4 DIP switches (red) to
OFF
RVD 681DC
Indoor unit
L
Phase conductor
N
Neutral conductor
Control conductor
P
Q
Control conductor
E
Control conductor
PEPE
Outdoor unit
Earth conductor
L
Neutral conductor
N
P
Q
E
Note:
The A-E plug to connect a cable remote control!
Terminals X, Y, E at RVT 1051DC are not used!
The attached fixed resistor is not needed
Power output
Phase conductor
Earth conductor
PE
RVD 1051DC
Indoor unit
Neutral cond.
Earth conductor
P
Control cond.
Q
Control cond.
E
Control cond.
Outdoor unit
L1L1L1
NNN
PePePe
P
Q
E
Power output
Phase cond.
Phase cond.
Phase cond.
Neutral cond.
Earth conductor
L2L2
L3L3
L
N
400 V/3~,
50 Hz,
L / N / PE
230 V/1~,
50 Hz,
L / N / PE
DIP-Switch
Note:
For the correct address selection, all 4 DIP switches (red) to
OFF
DIP-Switch
Note:
The A-E plug to connect a cable remote control!
Terminals X, Y, E at RVT 521-1051DC are not used!
The attached fixed resistor is not needed
22
Note:
For the correct address selection, all 2 DIP switches (red) to
OFF
A
U
V
W
Y/G
U
V
W
RY3
4
CN6
CN7
CN5
CN4
CN2 8
CN26
C
N
1
0
N
-
B
B
C
N
3
C
N
2
C
N
1
CN15
CN14
CN16
N-A
Zum Innengerät
Y/G
WHITE
REACTOR2 R6025C
REACTOR1 R1310K
Kurbelwannenheizung
Heizung
5
CN31
CN33
CN34
CN32
B
L
A
C
K
Y/G
T3
Sensor Umgebung
T5
Sensor VerflüssigerSensor Heißgas
Sensor Öl
Kompressor
Ventilatormotor
Umkehrventil
Blau
Schwarz
Rot
Schwarz
Rot
Rot
Hauptplatine
Grau
Optional
Orange
Gelb
Rot
Orange
Gelb
Gelb
Orange
Rot
Blau
Stromüberwachung
Gelb
Blau
Braun
Electrical circuit diagram
RVD 351 DC Indoor unit
M
RVD 351 DC Outdoor unit
blue
red
black
Compressor
Probe condenser
Sensor environment
Main board
blue
Power management
yellow
yellow
red
red
Hot gas sensor
Sensor oil
black
yellow
yellow
blue
brown
red
Fan motor
Heating
Crankcase heating
To indoor unit
red
gray
Reversing valve
23
Blau
Blau
Blau
Blau
Blau
Blau
Blau
Kompressor
Rot
Schwarz
Gelb
Gelb
Schwarz
Rot
Weiß
Rot
RotRot
Schwarz
Gelb
Grau
Filter
Schwarz
Rot
Rot
Schwarz
Schwarz
Yellow/Green
Yellow/Green
Yellow/Green
Schwarz
Rot
Schwarz
Braun
Braun
Weiß
WeißWeiß
Weiß
Rot
Rot
Rot
Rot
Rot
Orange
Rot
Schwarz
UWV
U
V
W
P
N
IPM
10PIN
W V
U
L202
IPM
EEW
T5
CN4
CN12
CN5CN5
CN16
CN11
CN1
CN2
Trans.Trans.
CN20
CN27
CN28
CN9
Hochdruckschalter
Niedrigdruckschalter
R2503
P-3
P-4
P-5
P-6
P-2
3
CN3
R1815B
R1325C
CN14
CN15
CN13
CN12
CN7
CN5
CN6
CN4
CN8
CN10
CN9
Blau
Ventilator
CN1 CN2
L
N
L
N
P-1
L
H
Sensor Heißgas
Sensor Außentemperatur
Sensor Austritt Verflüssiger
Elektronisches
Expansionsventil
Leistungsplatine
zum Innengerät
Steuerleiter
Hauptplatine
Steckverbinder
Steckverbinder
GM
P1
Lila
Weiß
Netzzuleitung Innenteil
Rot
Weiß
CN4
CN11CN5CN7CN9
Weiß
C5
WeißSchwarz
Rot
CN3
CN2
T1T2
T2T1
CN14CN10CN15
(E)
Y
X
Schwarz
Grau
Gelb
Schwarz
Blau
Weiß
(E)
P
C
YEX
E
F M
CN12
CN1
zum AußengerätSteuerleiter
zum CCN
Steuerleiter
DM
Display
Y/G
c
Blau
Y/G
CN5
REMKO RVD...DC
RVD 521 DC Indoor unit
white
purple
Power output indoor unit
RVD 521 DC Outdoor unit
red
black
24
red
blue
Compressor
blue redblack
red
white
white
red
Connector
blue
red
blue
orange
red
white
red
Electronic
expansion valve
red
blue
white
white
Main board
white
Probe outlet
condenser
black
Power board
brown
brown
white
To CCN
Control
conductor
blue
black
blue
black
To outdoor unit
black
white
yellow
Red
blue
Fan
black
yellow
gray
Control
conductor
High pressure switch
Low pressure switch
yellow
Red
yellow
To the indoor unit
Control conductor
black
red
blue
blue
black
red
white
Hot gas sensor
Sensor outside
temperature
black
gray
black
red
Connector
RVD 681 DC Indoor unit
GM
P1
Lila
Weiß
Netzzuleitung Innenteil
Rot
Weiß
CN4
CN11CN5CN7CN9
Weiß
C5
WeißSchwarz
Rot
CN3
CN2
T1T2
T2T1
CN14CN10CN15
(E)
Y
X
Schwarz
Grau
Gelb
Schwarz
Blau
Weiß
(E)
P
Q
YEX
E
F M
CN12
CN1
DM
Display
Y/G
c
Blau
Y/G
CN5
Blau
Blau
Blau
Blau
Blau
Blau
Blau
Kompressor
Rot
Schwarz
Gelb
Gelb
Schwarz
Rot
Weiß
Rot
RotRot
Schwarz
Gelb
Grau
Filter
Schwarz
Rot
Rot
Schwarz
Schwarz
Yellow/Green
Yellow/Green
Yellow/Green
Schwarz
Rot
Schwarz
Braun
Braun
Weiß
WeißWeiß
Weiß
Rot
Rot
Rot
Rot
Rot
Orange
Rot
Schwarz
UWV
U
V
W
P
N
IPM
10PIN
W V
U
L202
IPM
EEW
T5
CN4
CN12
CN5CN5
CN16
CN11
CN1
CN2
Trans.Trans.
CN20
CN27
CN28
CN9
Hochdruckschalter
Niedrigdruckschalter
R2503
P-3
P-4
P-5
P-6
P-2
3
CN3
R1815B
R1325C
CN14
CN15
CN13
CN12
CN7
CN5
CN6
CN4
CN8
CN10
CN9
Blau
Ventilator
CN1 CN2
L
N
L
N
P-1
L
H
Sensor Heißgas
Sensor Außentemperatur
Sensor Austritt Verflüssiger
Elektronisches
Expansionsventil
Leistungsplatine
zum Innengerät
Steuerleiter
Hauptplatine
Steckverbinder
Steckverbinder
white
purple
redblue
Power output indoor unit
RVD 681 DC Outdoor unit
Compressor
blue redblack
red
Connector
red
black
red
blue
red
white
white
Electronic
expansion valve
blue
red
orange
red
white
red
blue
white
white
Probe outlet
condenser
Main board
Power board
brown
brown
white
black
blue
blue
black
white
To CCN
Control
conductor
black
white
yellow
High pressure switch
Red
Low pressure switch
yellow
Red
yellow
To the indoor unit
Control conductor
black
red
blue
blue
black
red
Fan
white
blue
black
yellow
To outdoor unit
Control
conductor
Hot gas sensor
Sensor outside
temperature
black
gray
black
red
black
gray
Connector
25
POWER_RY
HEAT
4-WAY
FAN_H
FAN_L
TRANS IN
T4
N
TRANS IN
CT1
L1
L2
L3
L1
L2
L3
CN16
T5T3
1
5
3
4
2
RED
CN42
CN48
CN46
CN47
CN44
CN45
CN43
CN20-CN22
GND
A1
A2
2T1
4T2
6T3
1L1
3L2
5L3
21
22
2
REMKO RVD...DC
RVD 1051 DC Indoor unit
DM
Weiß
white
Lila
purple
redblue
Rot
Y/G
Netzzuleitung Innenteil
Power output indoor unit
Blau
CN1
CN3
CN2
CN12
c
P1
Weiß
white
GM
Display
CN14CN10CN15
CN4
CN11CN5CN7CN9
red
Rot
C5
Y/G
F M
Weiß
white
CN5
T2T1
black
white
WeißSchwarz
T1T2
YEX
E
Weiß
Blau
white
blue
X
Y
To CCN
Control
conductor
Schwarz
black
(E)
To outdoor unit
Gelb
yellow
P
Q
Control
conductor
Grau
gray
(E)
Schwarz
black
RVD 1051 DC Outdoor unit
26
Add refrigerant
The equipment contains a basic
quantity of refrigerant. Beyond
these conditions, for refrigerant
pipe lengths of more than 5 meters
per circuit, an additional amount of
refrigerant must be added, according to the following chart:
! CAUTION
Note that the employed refrigerant is always filled in liquid
form!
NOTE
Check the overheating to
determine the refrigerant fill
quantity
CAUTION
!
Wear protective clothing when
handling refrigerant.
RVD
RVD
RVD
681
DC
30
g/m
RVD
1051
DC
30
g/m
Up to and
incl. 5m
From 5m to
max.
Length
351
DC
25
g/m
521
DC
0 g/m
25
g/m
Commissioning
NOTE
Commissioning should only be
performed and documented by
specially trained personnel.
The system can be commissioned
once all the components have
been connected and tested. A
functional check should be performed to verify its correct function and identify any unusual
operational behaviour prior to
handing it over to the operator.
NOTE
Check that the stop valves and
valve caps are tight after carrying
out any work on the refrigerant
circuit. If necessary, use appropriate sealant products.
Function test and
test run
Check the following points:
■
Leak tightness of refrigerant
pipes.
■
Compressor and fan running
smoothly.
■
In cooling mode, cold air should
be output by the indoor unit,
and warm air should be output
by the outdoor component.
■
Functional test of the indoor
unit and all program
sequences.
■
Check of the surface temperature of the suction pipe and
determination of vaporiser
overheating. To measure the
temperature, hold the thermometer to the suction pipe
and subtract the boiling point
temperature reading on the
pressure gauge from the measured temperature.
■
Record the measured temperatures in the commissioning
report.
Functional test for cooling
and heating modes
1. Remove the caps
from the valves.
2. Begin the commissioning
process by briefly opening the
blocking valves of the external
section until the manometer
displays a pressure of approx. 2
bar.
3. Use leak detection spray or suitable devices to check that all
the connections are tight.
4. If no leaks are found, fully open
the stop valves by turning them
anti-clockwise using a spanner.
If leaks are found, repair the
faulty connection. It is imperative that the vacuum creation
and drying steps are repeated.
5. Switch off the main circuit
breaker or remove the fuse
(provided by the customer).
6 Press the test knob on the
outdoor unit and wait until
a frequency of min. 50 Hz is
established.
7. Use the remote control to
switch on the unit and select
the cooling mode, maximum
fan speed and lowest target
temperature.
8. Check the overheating, outdoor, indoor, outlet and vaporisation temperatures and record
the measured values in the
commissioning report. Check
the correct function and settings of all regulation, control
and safety devices.
9. Check the indoor unit control
system using the functions
described in the chapter "Operation". Timer, temperature setting, fan speeds and switching
to ventilation or dehumidifying
mode.
10.Check the correct function
of the condensation pipe by
pouring distilled water into the
condensation tray.
A bottle with a spout is recommended for pouring the water
into the condensation tray.
11.
Switch the indoor unit to heating mode.
27
REMKO RVD...DC
12.
Check all the previously
described safety devices and
functions during the test run.
13.
Enter the measured data in
the commissioning report.
in the commissioning report
and familiarize the operator
with the system.
14.
Remove the pressure gauge.
Check that seals have been
fitted in the sealing caps.
NOTE
Press the TEST knob on the
outdoor unit board. This
serves to set the inverter to
max. refrigerating capacity.
15. Reinstall all parts which were
removed.
Functional test and test run
During operation of the plant
operating parameters can be called
up on the outdoor unit display.
(only RVD 521-1051DC)
The following parameters are displayed successively:
RVD 521-1051 DC
- Frequency of the compressor
- Operating mode
- Level fan
- Current cooling/heating perforance
- Temperature sensor liquefier
- Temperature sensor hot gas
- Temperature sensor air inlet
- Power consumption outdoor unit
- Degree of opening for electronic
Expansion valve only RVD 521 DC
- error code
Proceed as follows to call up the
operating parameters:
1. Remove the cover from the
outdoor unit.
2. Switch all indoor units on and
select cooling mode and the
highest fan speed.
Display
The display on the outdoor unit
PCB can call up the operating parameters of the plant in the above
order. In order to do so, press the
check button located next to the
display on the outdoor unit board.
Check button
Frequency gauge
DisplayFrequency (Hz)
3030
--Stand by
6060
Operating mode
Display
0Off
2Cooling mode
3Heating mode
4Forced cooling
Mode Outdoor unit
Operating mode fan
DisplayMode fan
0Off
1Low rotational speed
2High rotational speed
Cooling output - heating output
Outdoor unit / Indoor unit
1035-40 °C
1140-45 °C
1245-50 °C
1350-55 °C
1455-60 °C
1560-65 °C
1665-70 °C
Temperature sensor hot gas
DisplayTemperature
1035-40 °C
1140-45 °C
1245-50 °C
1350-55 °C
1455-60 °C
1560-65 °C
1665-70 °C
Temperature sensor air inlet
DisplayTemperature
15-7.5 °C
20-5.0 °C
25-2.5 °C
300° C
352.5 °C
405.0 °C
457.5 °C
5010.0 °C
5512.5 °C
6015.0 °C
6517.5 °C
7020.0 °C
7522.5 °C
8025.0 °C
8527.5 °C
9030.0 °C
9532.5 °C
9934.5 °C
Power consumption outdoor unit
Display
446.0 A
466.2 A
547.4 A
557.6 A
587.8 A
628.0 A
668.6 A
678.8 A
689.0 A
709.2 A
729.5 A
7610.0 A
7810.2 A
8010.4 A
8210.6 A
8411.0 A
8811.6 A
9212.0 A
9412.2 A
Power consump-
tion
28
Troubleshooting and customer service
The equipment and components are manufactured using state-of-the-art production methods and tested several times
to verify their correct function. If malfunctions should occur, please check the functions as detailed in the list below.
Please inform your dealer if the unit is still not working correctly after all the functional checks have been performed!
Malfunction
FaultPossible causeChecksRemedial measures
The unit does not start
or switches itself off
The unit does not respond
to the remote control
The unit is running with
reduced or without
reduced cooling / heating
performance
Condensation discharge
on unit
Power outage, undervoltage,
defective mains fuse / main circuit
breaker switched off
Damaged mains cable
Waiting time after switch-on too
short
Temperature outside operating
range.
Overvoltages caused by thunder
storms
Fault in external condensation
pump
High-pressure / low-pressure
monitors have triggered
Transmission distance too far /
receiver affected by interference
Defective remote control
Receiver or transmitter unit exposed to excessive solar radiation
Electromagnetic fields are interfering with transmission
Button in remote control jammed
/ two buttons pressed at same
time
Batteries in remote control are flat
Filter is unclean / air inlet / outlet
blocked by foreign items
Windows and doors open. Heating/cooling output increases
Neither cooling nor heating mode
has been set
Fins on outdoor component
blocked by foreign items
Leaking refrigerant circuit
Outdoor component iced up
Drainage pipe on collection container clogged / damaged
Faulty external condensation
pump or float
Condensation has not drained
away and has collected in the
condensation line
Condensation does not drain off
Float is stuck or jammed due to
excessive dirt.
Are all other
electrical installations functioning
correctly?
Are all other
electrical installations functioning
correctly?
Have approx. 5 minutes
elapsed since the restart?
Are the fans in the indoor unit
and outdoor component working
correctly?
Has there recently been lightning?
Did the pump shut down due to
a fault?
Check refrigerant pressure and
look for leaks if necessary
Does the indoor unit beep when
pressing a button?
Is the unit running in manual
mode?
Does it function correctly in the
shade?
Does it function when switching off
possible sources of interference?
Does the “Send”
symbol appear on the display?
Have new batteries been inserted?
Is the display incomplete?
Have the filters been cleaned?Clean the filters
Have there been any constructional /
application-related
changes?
Does the cooling symbol appear
on the display?
Is the fan on the outdoor component running? Are the fins
unobstructed?
Are there signs of frost on the fins
of the indoor unit?
Check outdoor component. Has
the cassette sensor on the outdoor
component been correctly positioned?
Can the condensation drain off
without any obstruction?
Is the collection tray full of water
and the pump not running?
Is there a steady fall on the condensation pipe? Check there is no
blockage in the pipe.
Are the condensation lines unblocked and is there a steady fall?
Are the condensation pump and
float switch functioning correctly?
Are the LEDs on the receiver unit
of the indoor unit flashing?
Check voltage
possible wait until turned on
again.
Repair by
a specialist
Schedule longer waiting
periods
Take into account the temperature range for the indoor unit and
outdoor component
Switch off the mains breaker and
switch it back on. Have it checked
by a specialist
Check and if necessary clean the
pump
Rectify leakage and re-start
Reduce the distance to less than 6
m or change position
Replace the remote control
Place the receiver&transmitter unit
in the shade
Signal is not transmitted when interference sources are operational
Release the button / only press
one button
Insert new batteries
Close windows and doors / install
additional units
Correct the settings for the unit
Check the fan or winter controller,
reduce the air resistance
Repair by specialist
De-ice and fit the sensor at the
point where the most ice forms
Clean the drainage pipe and collection container
Call out a specialist to replace the
pump
Ensure there is a fall when laying
the condensation pipe and clean
the pipe.
The condensation line must have
a fall. If necessary, clean the pipe.
A faulty condensation pump and
float switch should be replaced.
Should be cleaned by specialist firm
29
REMKO RVD...DC
Problem display by blinker code
LED
Operation
flashes
rapidly
flashes
slowly
LED
Timer
flashes
rapidly
flashes
slowly
LED
Defrost
flashes
rapidly
flashes
slowly
LED
Alarm
flashes
slowly
flashes
rapidly
Display
outdoor
unit
E0EEPROM errorCheck EEPROM
E2
E3
E4
E5Overvoltage compressorCheck compressor voltage
P0Excessive temperature compressorAllow compressor to cool
P1High pressure sensor has triggeredCheck refrigerant pressure
P2Low pressure sensor has respondedCheck refrigerant pressure
P3
P4Compressor discharge gas over 105°C
P5Liquefier temperature over 65°C
P6
Communication error between PCBs
outdoor unit & indoor unit
Communication error between outdoor unit main board & outdoor unit
inverter board
Outdoor temp sensor on outdoor component tripped
Compressor power consumption too
high
Voltage protection main board outdoor
unit
Sensor air circulation / sensor liquefier
tripped
Communication error between outdoor
unit & indoor unit
Mode malfunction
Sensor liquefier / outdoor temp faulty
or not correctly connected
Set the cooling mode
on the indoor unit and
run the system so a
few minutes.
If the error still exist?
Is there voltage in the
indoor unit?
Yes
Is the connecting cable
shielded, and is it
earthed?
Yes
Is the cable connecting
the indoor unit and
outdoor component
properly connected?
Yes
Is the cable connecting
the indoor unit and
outdoor component
damaged?
No
No
No
No
Yes
Establish the power
supply.
Use a shielded,
earthed cable
Connect the cable
properly.
Replace the cable.
Yes
Is the float switch
working properly?
Yes
Does the condensate
pump properly
appropriate?
Yes
Check the condensate
drain, whether it is
bent if necessary.
If the condensate drain
okay?
Yes
Replace the main board
for the indoor unit
No
No
No
Replace float switch.
Error still exists?
Condensate pump
exchange. Error still
exists?
Condensate drain
renew or repair
Replace the main board
for the indoor unit or
outdoor component
31
REMKO RVD...DC
5. Operation and Timer lights flash at 5 Hz:
EEPROM error
Is the EEPROM
fitted properly?
No
Fit EEPROM properly
Yes
Replace outdoor
component main board
6. Operation light flashes at 5 HZ and Alarm light is on: IPM safety shutdown
Check the power
supply to the circuit
board. Is it working
OK?
No
Yes
Are the connections from the circuit board to
the compressor OK?
Yes
Check the
windings of the
compressor
Correct
connections
No
Check the power
supply for the
outdoor component.
Is a voltage of 230
V present at the unit
power supply?
Yes
Check the unit's
electrical supply.
Is it properly
connected?
No
No
No
Correct the power
supply to the unit.
Is the unit working
properly again?
Connect the electrical
supply properly
Are the
windings of the
compressors
OK?
Yes
Replace
circuit board
No
No
Replace circuit board
Replace
compressor
Does the
unit run after
replacing the
compressor?
Are all the circuit
board's electrical
cables properly
connected?
Check the chokes on
the circuit board
Chokes have ∞
resistance?
Check the fuses on
the circuit board
Circuit board fuses
Yes
OK?
Yes
Yes
No
No
No
Yes
Connect all electrical
cables properly
Replace circuit board
Replace fuse or circuit
board
32
7. RVD 351 DC
Operation light flashes at 5 Hz and Timer light is on:
condenser temperature sensor
outdoor component overcurrent protection
9. Operation, Timer and Alarm lights flash at 5Hz:
RVD 521 DC
Alarm light flashes at 1 Hz: Fault Temperature sensor
condenser or outdoor unit is not working properly
(look at E4, P1 and P2)
Connection of sensor
line OK?
Yes
Resistance of the
sensor OK
(Table 1, P92-94)?
No
Replace temperature
sensor
No
Yes
Correct
sensor line
Replace outdoor
component main
board
8. Operation light flashes at 5 Hz, Timer and
Alarm lights are on: outdoor component
overvoltage protection
Is the input current
greater than 16A?
Yes
Check refrigerant pipes
Is the outdoor
temperature too high?
No
Is the function of the
fan on the outdoor
component OK?
Yes
Is the register of the
outdoor component
dirty?
No
Yes
Switch off unit
Ensure fan functions
properly
Clean the register
Yes
of the outdoor
component
Connection of sensor
line OK?
Yes
Is the voltage between
L and N of the outdoor
component 198 –
254V?
Yes
Replace main board
No
No
Connect the sensor
properly
Establish correct
power supply
No
Are the refrigerant
pipes blocked or bent?
No
Replace outdoor
component main board
Siphon off refrigerant,
replace pipe / remove
Yes
blocked, perform
pressure test, drawn
vacuum and refill
33
REMKO RVD...DC
10. Operation light flashes at 5 Hz and Defrost light is on: Hot gas temperature too high
Is the temperature of
the Klixon over 115°C?
No
Is the connection
between the Klixon and
circuit board OK?
Yes
Is the resistance value
for the Klixon correct
(Table 2, P95)?
Yes
Replace outdoor
component main board
Yes
No
No
Is there a
refrigerant leak?
Establish a proper
connection
Replace Klixon
Yes
Fix the leak and top up
34
RVD 521-1051DC outdoor unit fault analysis
Fault displays shown on the outdoor component
Fault code
DISPLAY
Fault descriptionRequired action
E0EEPROM errorsee page 85 / point 1
E2Communication error between indoor unit and outdoor componentsee page 85 / point 2
E3Communication error on outdoor component main boardsee page 86 / point 3
E4Fault on the outdoor temperature sensorsee page 86 / point 4
E5Compressor overvoltage protectionsee page 86 / point 5
P0Compressor overload protection (Klixon) tripped
P1High pressure fault (from RVD 521 and up)see page 87 / point 6
P2Low pressure fault (from RVD 521 and up)see page 88 / point 7
P3Compressor overcurrent protection trippedsee page 89 / point 8
P4Compressor overload protection (Klixon)see page 90 / point 9
P5Condenser outlet sensor triggeredsee page 90 / point 10
P6IPM power board safety shutdownsee page 91 / point 11
2.
1. Fault code E0: EEPROM error
Fault code E2: communication error between indoor
unit and outdoor component
No
Establish the power
supply.
fitted properly?
No
Fit EEPROM properlyIs the EEPROM
Is there voltage in the
indoor unit?
Yes
Replace outdoor
component main board
Yes
Are the DIP switches
on the main board set
correctly?. See cover.
Yes
Is the cable connecting
the indoor unit and
outdoor component
properly connected?
Yes
Is the cable connecting
the indoor unit and
outdoor component
damaged?
No
Replace the main board
for the indoor unit or
outdoor component
No
No
Yes
Reset the DIP switch
and switch for 5 min
without current.
Connect the cable
properly.
Replace the cable.
35
REMKO RVD...DC
3. Fault code E3: communication error on main board
of the outdoor component
Does LED1 flash on the
outdoor component
main board?
No
Is the electrical
connection between
the power board and
CN4 on the main board
OK?
Yes
Disconnect the
electrical connection
between the power
board and CN4 on the
main board.
Is there a measurement
of 5V on power board
CN1 between the 3th
and 4th pins?
No
Is the connection between
the IPM module (positive
terminal) and CN12 on
the power board OK?
Yes
No
Yes
No
Replace
main board
Establish a proper
connection
Replace
main board
Establish a proper
connection
4. Fault code E4: fault on outside temperature
sensor T4 or condenser sensor T3
Is the condenser
sensor properly
connected?
Yes
Measure the resistance
of the sensor. (Table 1,
P92-94)
Resistance OK?
Yes
Is the outside
temperature sensor
properly connected?
Yes
Measure the resistance
of the sensor. (Table 1,
P92-94)
Resistance OK?
Yes
Replace
main board
No
No
No
No
Connect condenser
sensor properly
Replace
sensor
Connect the outside
temperature sensor
properly
Replace sensor
Yes
Is the connection between
the IPM module (negative
terminal) and CN13 on
the power board OK?
Yes
Is there a measurement
of 277-345V between
CN12 and CN13 on
the power board?
Check the resistance
of the sensor. (Table 1,
P92-94)
Is the resistance OK?
Yes
Replace outdoor
component main board
No
Yes
Switch off unit
Replace
sensor
Clean condenser
register
Siphon off refrigerant,
replace pipe / remove
blocked, perform
pressure test, drawn
vacuum and refill
Yes
Yes
Yes
Is the outdoor
temperature too high?
No
Is the condenser
register dirty?
No
Are the refrigerant
pipes blocked or bent?
No
40
Replace outdoor
component main board
11. Fault code P6: IPM power board safety shutdown
Is the voltage range
between P and N of
the IPM module OK?
Yes
Is the connection
between the main board
and IPM module OK?
Yes
Is the connection to the
compressor OK?
Yes
Replace IPM module.
Is fault still present?
No
No
No
Is the input voltage
between P and N of
the IPM module 230V
/ the frequency 50 Hz?
Connect cables
properly
Is fault still present?
Establish a proper
connection
Establish a proper
connection
Replace single-phase
bridge circuit
No
No
Ensure the correct
supply voltage
Yes
Are all the electrical
cables properly
connected?
Yes
Yes
Is the single-phase
bridge OK?
Take a measurement
with a multimeter
between “+” and the
two AC contacts and
between “-” and the
two AC contacts. Is the
resistance for the two
measurements 0Ω?
Yes
No
Yes
Replace main board.
Is fault still present?
Yes
Replace compressor.
Is fault still present?
4-way valve
TemperatureResistanceMeasuring point
20 °C1.5 kΩBlue - Blue
Replace connecting
cables
Replace the defective
fuse
Note:
Heating mode 0V AC
Cooling mode 230V AC
No
Yes
Are the connecting
cables to the chokes
OK? Is the resistance of
the connecting cables
∞?
No
Check the fuses on the
power board. Are they
working OK?
Yes
Replace the
power board
41
REMKO RVD...DC
Resistances of the temperature sensors (Table 1)
Temp.Resistance kΩ
(°C)Rmax
-20116.539106.73296.920
-19110.231100.55291.451
-18103.74394.76986.328
-1797.67389.35381.525
-1691.99084.27877.017
-1586.66979.52172.788
-1481.68475.05968.815
-1377.01370.87365.083
-1272.63266.94361.574
-1168.52363.25258.274
-1064.66859.78455.169
-961.04856.52452.246
-857.64953.45849.492
-754.45650.57546.899
-651.45647.86244.455
-548.63645.30842.150
-445.98442.90339.977
-343.49040.63837.927
-241.14438.50435.992
-138.93536.49234.165
036.85734.59632.440
134.89832.80730.810
233.05531.12029.271
331.31729.52827.815
429.68128.02626.440
528.13826.60825.140
626.68225.26823.909
725.31024.00322.745
824.01622.80821.644
922.79421.67820.601
1021.64120.61019.614
1120.55319.60118.680
1219.52518.64617.794
1318.55417.74316.955
1417.63616.88816.160
1516.76916.07915.406
1615.94915.31314.691
1715.17414.58814.014
1814.44213.90213.372
1913.74813.25112.762
2013.09312.63512.183
2112.47112.05011.634
R(t) Normal
Rmin
Temp.Resistance kΩ
(°C)Rmax
2211.88311.49611.112
2311.32710.97110.617
2410.80010.47310.147
2510.30010.0009.700
269.8489.5519.255
279.4189.1258.834
289.0108.7218.434
298.6218.3378.055
308.2527.9727.695
317.9007.6257.353
327.5667.2967.029
337.2476.9826.721
346.9446.6846.428
356.6566.4016.150
366.3816.1315.886
376.1195.8745.634
385.8705.6305.395
395.6315.3975.167
405.4045.1754.951
415.1884.9644.745
424.9824.7634.549
434.7854.5714.362
444.5964.3874.183
454.4174.2134.014
464.2464.0463.851
474.0823.8873.697
483.9253.7353.550
493.7763.5903.409
503.6323.4513.274
513.4953.3183.146
523.3633.1913.023
533.2373.0692.905
543.1162.9522.793
553.0012.8412.685
562.8902.7342.582
572.7842.6322.484
582.6822.5342.390
592.5852.4402.299
602.4912.3502.213
612.4012.2642.130
622.3152.1812.051
632.2332.1021.975
R(t) Normal
Rmin
42
Temp.Resistance kΩ
(°C)Rmax
642.1542.0261.903
652.0771.9531.833
662.0041.8831.766
671.9341.8161.702
681.8671.7521.641
691.8021.6901.582
701.7401.6311.525
711.6801.5741.471
721.6221.5191.419
731.5671.4661.369
741.5141.4161.321
751.4631.3671.275
761.4141.3211.230
771.3671.2761.188
781.3211.2331.147
791.2771.1911.108
801.2351.1511.070
811.1951.1131.034
821.1561.0760.999
831.1181.0410.966
841.0821.0070.934
851.0470.9740.903
861.0140.9420.874
870.9820.9120.845
880.9510.8830.818
890.9210.8550.791
900.8920.8280.766
910.8640.8020.742
920.8380.7770.719
930.8120.7530.696
940.7870.7300.675
950.7630.7080.654
960.7400.6860.634
970.7180.6660.615
980.6970.6460.597
990.6770.6270.579
1000.6570.6090.562
1010.6380.5910.546
1020.6200.5740.530
1030.6020.5580.515
1040.5850.5420.501
1050.5690.5270.485
R(t) Normal
Rmin
43
REMKO RVD...DC
Resistances of the hot gas sensors (Table 2)
°CkΩ°CkΩ°CkΩ°CkΩ
-20542.72262.736411.791063.113
-19511.92359.986511.381073.025
-184832457.376610.991082.941
-17455.92554.896710.611092.86
-16430.52652.536810.251102.781
-15406.72750.28699.9021112.704
-14384.32848.14709.5691122.63
-13363.32946.11719.2481132.559
-12343.63044.17728.941142.489
-11325.13142.33738.6431152.422
-10307.73240.57748.3581162.357
-9291.33338.89758.0841172.294
-8275.93437.3767.821182.233
-7261.43535.78777.5661192.174
-6247.83634.32787.3211202.117
-5234.93732.94797.0861212.061
-4222.83831.62806.8591222.007
-3211.43930.36816.6411231.955
-2200.74029.15826.431241.905
-1190.54128836.2281251.856
0180.94226.9846.0331261.808
1171.94325.86855.8441271.762
2163.34424.85865.6631281.717
3155.24523.89875.4881291.674
4147.64622.89885.321301.632
5140.44722.1895.157
6133.54821.26905
7127.14920.46914.849
81215019.69924.703
9115.25118.96934.562
10109.85218.26944.426
11104.65317.58954.294B(25/50)=3950K
1299.695416.94964.167
1395.055516.32974.045R(90°C)=5KΩ±3%
1490.665615.73983.927
1586.495715.16993.812
1682.545814.621003.702
1778.795914.091013.595
1875.246013.591023.492
1971.866113.111033.392
2068.666212.651043.296
2165.626312.211053.203
44
Unit dimensions
RVD 351-521 DC Indoor unit
650
RVD 681-1051 DC Indoor unit
950
650
950
580
840
400
580
610880
28
580
600
840
300254
28
840
RVD 351-1051 DC Outdoor unit
A
RVD 351 DCRVD 521 DCRVD 681 DCRVD 1051 DC
A760840895990
B270310313354
C590700862966
D530560860600
E290335315375
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
B
E
C
D
All values in mm
45
REMKO RVD...DC
Exploded view RVD 351DC IT to RVD 1051DC IT
5
1
2
14
6
3
9
8
10
7
We reserve the right to modify the dimensions and constructional
design as part of the ongoing technical development process.
11
12
13
Spare parts list
No.Designation RVD 351 DC IT RVD 521 DC IT RVD 681 DC IT RVD 1051 DC IT
1Air inlet guard1110950111095011115501111550
2Air filter1110951111095111115511111551
3Cover1110952111095211115521111552
4Fin motor1110953111095311115531111553
5Air inlet, condensate pan module1110954111095411115541111554
6Outlet fins, set of 41110955111095611115551111555
7Vaporiser1110957111095811115561111557
8Condensation pump cpl. 1110959111095911109591110959
Operating range - cooling°C+5 - +43
Operating range - heating°C-5 - +24
Air flow rate, max.m³/h1600/25002300/25703000 /32505800 /6000
Protection degreeIP24
Noise output max.
Refrigerant, basic quantitykg1,401,702,304,10
Refrigerant, additional quantity > 5 mg/m30303030
Refrigerant pipe, max. lengthm15252530
Refrigerant pipe, height indoor unit and
outdoor unit max.
Dimensions - Heightmm590700860990
Widthmm760845895940
Depthmm280310335360
Weightkg39,059,073,087,0
Serial number548...549...713...714...
EDP no.1623160162317016231801623190
1) Air intake temp. TK 27°C / FK 19°C, outdoor temp. TK 35°C / FK 24°C, max. air volume, 5m pipe length in combination with MVT 900 / 950 DC
2) Air intake temperature TK 20°C outdoor temperature TK 7°C, FK 6°C, max. air volume, 5m pipe length in combination with MVT 900 / 950 DC
3) Gap 1 m free space 4) Contains greenhouse gas according to Kyoto protocol
48
1)
2)
1)
1)
2)
2)
kW
kW
3,52 (1,41 to 4,11)5,27 (1,59 to 5,65)7,03 (1,63 to 7,92) 10,55 (3,01 to 13,22)
4,29 (1,43 to 4,83)5,86 (1,45 to 6,15)7,76 (1,75 to 8,61) 11,72 (3,75 to 14,02)
RVD 351DC IT RVD 521DC IT RVD 681DC IT RVD 1051DC IT
18,021,029,030,0
RVD 351DC AT RVD 521DC AT RVD 681DC AT RVD 1051DC AT
3)
dB(A)48525355
m10101020
3, 0
2, 5
1, 5
2, 0
3, 5
4, 0
4, 5
1, 0
0 3 6 9 12 -15 -12 -9 -6
-3
0, 80
1, 00
1, 20
1, 40
0, 30
0, 50
0, 70
7. 00
7, 00
6. 50
5. 50
6. 00
7. 50
8. 00
8. 50
5. 00
1. 50
2. 00
2. 50
3. 00
0. 90
0. 95
1. 00
4. 50
0
3 6 9 12 -15 - 11
-9
-6
-3
15
18
14, 00
2. 50
3. 00
3. 50
4. 00
0. 90
1. 00
2. 00
13, 00
12, 00
11, 00
10, 00
9, 00
8, 00
7, 00
6, 00
0
3 6 9 12 -15 - 11
-9
-6
-3
15
18
Performance charts for heating
RVD 351 DC
1
Heating output
Elec. power consumption
Outdoor temperature
RVD 521 DC
6. 50
6. 00
5. 50
1
5, 00
4. 50
4. 00
3. 50
Heating output
3. 00
1. 70
1. 60
1. 50
1. 40
1. 30
1. 20
1. 10
Elec. power consumption
-9
-3
-6
Outdoor temperature
3 6 9 12 -15 - 11
0
15
18
RVD 681 DC
1
RVD 1051 DC
1
Heating output
Heating output
Elec. power consumption
Elec. power consumption
Outdoor temperature
1) Air intake temperature TK 20°C, outdoor temperature TK 7°C, FK 6°C, max. air flow volume, 5m pipe length
Outdoor temperature
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
49
REMKO RVD...DC
EC – Declaration of Conformity
in accordance with the Machinery Directive, Annex II 1A
Original Declaration of Conformity
We hereby declate that the devices described in the following section conform to the requirements of the specified applicable EC directives due to their design and type in the version as
marketed by us.
Name of Manufacturer: REMKO GmbH & Co. KG
Klima- und Wärmetechnik
Im Seelenkamp 12
D - 32791 Lage
Name of Authorised Agent: REMKO GmbH & Co. KG
Klima- und Wärmetechnik
Im Seelenkamp 12
D - 32791 Lage
Equipment (machinery) - Implementation: Inverter ceiling-mounted air conditioner in
split design
Series / Model:
RVD 681 DC, RVD 1051 DC
Series / Class Number: 548..., 549..., 713..., 714...
Applicable regulations:
MA DIR. 2006/42/EC Machinery Directive
LV DIR. 2006/95/EC Low-Voltage Directive
EMC DIR. 2004/108 EEC Electromagnetic Compatibility Directive
EnCLB DIR. 92/75/EEC Energy Consumption Labelling Directive
EC 97/23/EC Pressure Equipment Directive
Applicable Standards:
DIN EN ISO 12100-1-2 : 2004-04; DIN EN ISO 13857,
EN 14511 T1-4;
DIN 45635 - 1;
EN 378 – 1-4;
EN 55014 - 1; EN 55014 - 2; EN 55104
EN 60204 - 1; EN 60335 - 1; EN 60335 - 2 - 40;
EN 61000 - 3 - 2; EN 61000 - 3 - 3;
REMKO RVD 351DC, RVD 521 DC,
Lage, 22nd January 2010 REMKO GmbH & Co. KG
..............................................
Signature, Product Manager
50
REMKO INTERNATIONAL
… and also right in your neighbourhood!
Make use of our experience and advice
REMKO GmbH & Co. KG
Klima- und Wärmetechnik
Im Seelenkamp 12 D-32791 Lage
Postfach 1827 D-32777 Lage
Telefon +49 5232 606-0
Telefax +49 52 32 6 06-2 60
E-mail info@remko.de
Internet www.remko.de
Hotline
Klima- und Wärmetechnik
+49 5232 606-0
Export
+49 5232 606-130
Advice
We keep the specialist knowl-
edge of our advisers continu-
ously up-to-date with intensive
training. This has earned us a
reputation as more than just a
good, reliable supplier:
REMKO, a partner
who is here to help solve prob-
lems.
Distribution
REMKO provides not only a
well-developed distribution
network in Germany and abroad,
but also unusually highly skilled
professionals in distribution.
REMKO staff in the field are
more than mere salespeople:
they must primarily act as
advisers in air conditioning and
heating technology for our
customers.
Customer Service
Our units work precisely and
dependably. Should a failure
occur, however, REMKO cus-
tomer service will rapidly be at
your side. Our comprehensive
network of experienced dealers
guarantees quick and
reliable service.
Subject to technical modifications, no responsibility taken for the correctness of information!
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.