
Electrical Wiring Diagram
Installation Instructions for the Wall Bushing

jected to numerous material, function,
The device is not suited for out-
The device may not be set up and
sion and in atmospheres containing
security distance to infl ammable
surface. Never place it on its side
the connected load of the device,
the line length, and the intended
Work on the cooling system and
the electrical equipment may be
Transport the device only in an
After every transport of the
scribed in these instructions is
prohibited. Nonobservance leads
to the extinguishment of any li-
ability and warranty claims.
Batteries (type AAA/1.5 V)
Air outlet hose with connection

All devices are carefully packed
warranty can be assumed for later
free; observe the minimum
sensitive objects such as plants
side of the remote control
the compartment (Fig. 6).
There is otherwise a danger of
so that the cooling effect can be
short as possible (max. length
Always lay the air outlet
The air outlet hose may not be
the window jet and the de-
fl at nozzle between the win
the wings, close the window
the wings with a holding strap
through the wall bushing (Fig.
not included in supply schedule)
hose with a constant upward

“Timer/Temp. Adjust“: 5 higher, 6 lower
Red fault LED: Reservoir full (s. p. 7 Trouble Shooting)
An acoustic and an optical signal indicate that the fl oat switch of the internal
reservoir has shut down the operation of the device. The acoustic signal dies
down after a short period of time, but the LED remains active.
14 “°C/°F“ toggle button (only on the remote control)
The device is operated comfortably using
the control panel on the device or the in-
frared remote control. Keys with the same
symbols have the same function.
The device is used to cool the room. It fi lters
The device circulates the air, fi lters it, and
without interference, there should be
The proper reception of the signal is

Attach the air outlet hose to the wall
Activate the device using the “Power“
Press the “Mode“ button (2) until the
Activate the device using the “Power“
The room temperature is not infl uenced
the temperature and time setting
Attach the air outlet hose to the wall
Activate the device using the “Power“
f the “Room Temp.“ LED (12) lights up,
the current room temperature is shown
As soon as the (4/5/6) button is
ture (LED 13 lights up) and shows the
the “Timer/Temp. Adjust“ button (5/6).
The up arrow (5) increases the set value
shown in the display (7), while the
You can turn the device on and off
Activate the device using the
Select the mode and make all set-
tings for the desired mode.
Temp. Adjust“ button (5/6).
The device activates automatically
The device is running in the previ-
the “Timer/Temp. Adjust“ button
The device deactivates automati-
room climate by selecting
a set temperature that is a
maximum of 4 to 7°C below

With low cleaning effort, you
friendly cleaning agents.
vacuum cleaner or, in case
Always turn off the device
The condensate evaporates
the device collects conden-
sate in a reservoir. If the
the red fault LED lights up
Functional principle of the cooling process
Air inlet (circulation air)

contractual partner if the
the cooling circuit or the
The device is not function
· the mains plug is properly inserted;
· the mains voltage is present (fuse)
The device is not functioning and
The room temperature lies outside the
working range (reduce the incident of
sunlight and close windows and doors,
The device deactivates automatically.
The fault LED fl ashes and a signal sounds
To drain the reservoir, proceed as follows:
After the condensate has drained,
The device is not cooling properly.
the curtains and blinds. In addition,
· no foreign bodies impair the ex-
haust or intake air supply (observe
· the air directing plate fi ns are free of
soiling or foreign objects
· the set temperature is not too high
(operating limits of the device: 16
· the batteries are functioning;
change them if necessary;
· the batteries are inserted with the
correct polarity (cf. the marking);
remote control and the device
· the device is on a horizontal
· the plug is fi rmly inserted in the

The function of the device was precisely
the “Trouble Shooting“ chapter (s. p.
warranty, the “Warranty Certifi cate“
fi lled out and sent to REMKO GmbH &
able for damage that occurs
manufacturer instructions or
the legal requirements or due
to unauthorised changes to
To take the device out of service,
storage during the winter, observe the
face of the evaporator plate fi ns. In this
way, the residual moisture is removed
from the device and you can prevent

Protective
grille
Sealing cap
Telescopic
pipe
min. 430 mm
Trap
max.
480 mm
The refrigerant used belongs to the
to the cooling circuit, injury to the respi-
Take the minimum distance of 430 mm
the device) and the centre of the wall
To prevent cold bridges, insulate the
telescopic pipe with suitable insulating
Wall the telescopic pipe into the core
side of the wall (make sure it is protect-
The “top“ label on the trap must be
When taking the device out of service,
for example, at the beginning of winter,
sealing cap to prevent air circulation.

Device diagram of the MKT 240

3 Condensate motor with rotor
5 Float regulator (reservoir)
7 Microswitch (reservoir)
9 Condenser 2.5 µF (compressor)
11 Fan housing (exhaust air)
12 Fan wheel (exhaust air)
13 Fan motor (exhaust air)
15 Exhaust air pipe adapter
18 Fan housing, 3-pc. (circulation air)
19 Fan wheel, left (circulation air)
20 Fan wheel, right (circulation air)
21 Fan motor (circulation air)
24 Mains supply line with plug
Air outlet hose, cpl. (Nos. 33, 34, 35)
34 Connection pipe adapter
Not shown Condensate drain spout with plug
Not shown Sensor (circulation air)
en ordering spare parts, enter
rating plate in addition to the

Air-conditioning and heating technology
Application range (room air volume) Approx. m
Temperature setting range °C 16 bis 32
Temperature operating limits °C 16 bis 35
Voltage supply V/Ph/Hz 230/1~/50
Air outlet hose, length mm 1400
Air outlet hose, diameter mm 125
Air-conditioning • Heating • Dehumidifi cation