REMKO LTE 50, LTE 60, LTE 80 Assembly And Operating Instructions Manual

Assembly and operating instructions
REMKO LTE 50, 60, 80
Dehumidifier
0153-2017-07 Edition 1, en_GB
Read the instructions prior to performing any task!
Read these operating instructions carefully before commis­sioning / using this device!
These instructions are an integral part of the system and must always be kept near or on the device.
Subject to modifications; No liability accepted for errors or mis­prints!
Installation and operating instructions (translation of the orig­inal)

Table of contents

1 Safety and usage instructions............................................................................................................. 4
1.1 General safety notes....................................................................................................................... 4
1.2 Identification of notes...................................................................................................................... 4
1.3 Personnel qualifications.................................................................................................................. 4
1.4 Dangers of failure to observe the safety notes................................................................................ 4
1.5 Safety-conscious working............................................................................................................... 4
1.6 Safety instructions for the operator................................................................................................. 5
1.7 Safety notes for installation, maintenance and inspection work...................................................... 5
1.8 Unauthorised modification and changes......................................................................................... 6
1.9 Intended use................................................................................................................................... 6
1.10 Warranty........................................................................................................................................ 6
1.11 Transport and packaging............................................................................................................... 6
1.12 Environmental protection and recycling........................................................................................ 6
2 Technical data........................................................................................................................................ 7
2.1 Unit data.......................................................................................................................................... 7
3 Design and function.............................................................................................................................. 9
3.1 Air dehumidification - general note.................................................................................................. 9
3.2 Unit description............................................................................................................................. 12
4 Assembly............................................................................................................................................. 14
4.1 Setting up the unit......................................................................................................................... 14
4.2 Unit transport................................................................................................................................. 14
5 Electrical wiring................................................................................................................................... 15
5.1 General notes................................................................................................................................ 15
5.2 Electrical wiring diagram............................................................................................................... 15
6 Commissioning................................................................................................................................... 16
7
Condensate removal........................................................................................................................... 21
8 Troubleshooting and customer service............................................................................................ 24
9 Shutdown............................................................................................................................................. 25
10 Care and maintenance........................................................................................................................ 26
10.1 Care and maintenance................................................................................................................ 26
10.2 Maintenance protocol.................................................................................................................. 28
11 Exploded view of unit and spare parts............................................................................................. 29
11.1 Exploded view of the unit LTE 50/60/80...................................................................................... 29
11.2 Spare parts list LTE 50/60/80...................................................................................................... 30
12 Index..................................................................................................................................................... 32
3
REMKO LTE
1 Safety and
usage instructions

1.1 General safety notes

Carefully read the operating manual before com­missioning the units for the first time. It contains useful tips and notes such as hazard warnings to prevent personal injury and material damage. Failure to follow the directions in this manual not only presents a danger to people, the environment and the system itself, but will void any claims for
.
liability
Keep this operating manual and the refrigerant data sheet near to the units.

1.2 Identification of notes

This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation.The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by sym­bols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.
DANGER!
CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or mate­rial and environmental damage.
NOTICE!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.
This symbol highlights useful tips and recom­mendations as well as information for efficient and fault-free operation.

1.3 Personnel qualifications

Personnel responsible for commissioning, opera­tion, maintenance, inspection and installation must be able to demonstrate that they hold a qualifica­tion which proves their ability to undertake the work.
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.
DANGER!
This combination of symbol and signal word warns of a situation in which there is immediate danger cause serious injury.
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury
, which if not avoided may be fatal or
WARNING!
.
1.4

Dangers of failure to observe the safety notes

Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.
In particular, failure to observe the safety notes may pose the following risks:
n The failure of important unit functions. n The failure of prescribed methods of mainte-
nance and repair
n Danger to people on account of electrical and
mechanical effects.
.

1.5 Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.
4

1.6 Safety instructions for the operator

The operational safety of the units and compo­nents is only assured providing they are used as intended and in a fully assembled state.
This unit can be used by children above the age of 8, as well as by people with impaired physical, sensory or mental capabilities or a lack of experi­ence and knowledge if they are supervised or have received instruction in the safe operation of the unit, and if they understand the associated poten­tial hazards. Children must never play with the device. Cleaning and user maintenance must not be carried out by unsupervised children.
n The units and components may only be set up,
installed and maintained by qualified per­sonnel.
n If the mains power supply line of this unit is
damaged, this must be replaced by the manu­facturer or their customer services department or a similarly qualified person in order to avoid any hazard.
n Do not operate units or components with
obvious defects or signs of damage.
n The units may not be installed or operated in
explosive environments.
n The units must not be installed or operated in
atmospheres containing oil, sulphur salt.
n The units must be installed upright and in a
stable position.
n The units and components must not be
exposed to any mechanical load, extreme levels of humidity or extreme temperatures.
n All housing parts and device openings, e.g. air
inlets and outlets, must be free from foreign objects. An unobstructed air inlet and air outlet must be guaranteed at all times.
n The units must not be covered during opera-
tion.
n Never stick foreign objects into the units. n The units must not be transported while they
are running.
n The units must only be transported when the
condensate container is empty and the evapo­rator is dry.
n All electrical cables on the outside of the units
must be protected against damage (e.g. by ani­mals etc.).
n Before each change of location, the conden-
sate container must be emptied.
n The units must be inspected by a service tech-
nician to ensure that they are safe to use and fully functional at least once yearly. Visual inspections and cleaning may be performed by the operator when the units are disconnected from the mains.
, chlorine or
NOTICE!
Extensions to the connection cable must only be conducted by authorised specialist electri­cians, taking into consideration the unit power consumption, cable length and local use.
NOTICE!
W
ork on the refrigerant system and on the elec­trical equipment must only be conducted by a specially-authorised specialist!

1.7 Safety notes for installation, maintenance and inspection work

n Appropriate hazard prevention measures must
be taken to prevent risks to people when per­forming installation, repair cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
n If the mains power supply line of this unit is
damaged, this must be replaced by the manu­facturer or their customer services department or a similarly qualified person in order to avoid any hazard.
n The units must be installed upright and in a
stable position.
n The units must not be exposed to direct jets of
water, e.g. pressure washers etc.
n Safety devices may not be modified or
bypassed.
n The units and components may only be set up,
installed and maintained by qualified per­sonnel.
n Do not operate units or components with
obvious defects or signs of damage.
n The units may not be installed or operated in
explosive environments.
n The units must not be installed or operated in
atmospheres containing oil, sulphur, chlorine or salt.
n The units and components must not be
exposed to any mechanical load, extreme levels of humidity or extreme temperatures.
n All housing parts and device openings, e.g. air
inlets and outlets, must be free from foreign objects. An unobstructed air inlet and air outlet must be guaranteed at all times.
, maintenance or
5
REMKO LTE
n All electrical cables on the outside of the units
must be protected against damage (e.g. by ani­mals etc.).
n The units must be inspected by a service tech-
nician to ensure that they are safe to use and fully functional at least once yearly inspections and cleaning may be performed by the operator when the units are disconnected from the mains.
. Visual

1.8 Unauthorised modification and changes

Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufactured ensure safety use of other parts may invalidate liability for resulting consequences.
. The

1.9 Intended use

The units are designed exclusively for drying and dehumidification purposes in industrial or commer­cial situations on the basis of their structural design and equipment. The units must only be operated by appropriately instructed personnel.
Any different or additional use is a non-intended use. The manufacturer/supplier assumes no lia­bility for damages arising from non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
The threshold values specified in the technical data must not be exceeded.

1.10 Warranty

For warranty claims to be considered, it is essential that the ordering party or its representative com­plete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the "Gen­eral business and delivery conditions". Further­more, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.

1.11 Transport and packaging

The devices are supplied in a sturdy shipping con-
. Please check the equipment immediately
tainer upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to children!

1.12 Environmental protection and recycling

Disposal of packaging
All products are packed for transport in environ­mentally friendly materials. Make a valuable contri­bution to reducing waste and sustaining raw mate­rials. Only dispose of packaging at approved collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufac­ture of the devices and components. Help protect the environment by ensuring that the devices or components (for example batteries) are not dis­posed in household waste, but only in accordance with local regulations and in an environmentally safe manner cling specialists or at collection points.
, e.g. using certified firms and recy-
6

2 Technical data

2.1 Unit data

Unit type LTE 50 LTE 60 LTE 80
Operating range, temperature °C 3 to 32
Operating range, humidity % RH 40 to 100
Dehumidification capacity max. l/day 51 62 80
at 30 °C / 80% RH
(DER)
1)
45.2 54.0 70.1
l/day
l/day
at 20 °C / 70% RH
(DER)
1)
25.6 31.9 40.7
l/day
at 10 °C / 60% RH
Max. airflow volume
(DER)
m3/h
1)
8.0 10.1 12.3
380 465 490
Condensate container capacity l 10.0
Compressor / condenser - design Rotary piston
Refrigerant
2)
R410A
Refrigerant quantity g 420 540 750
Power supply V/Hz 230/1~/50
Max. rated current consumption A 2.86 3.61 4.01
Max. power consumption kW 0.63 0.76 0.91
At 20 °C / 70% RH kW 0.48 0.60 0.68
Customer-provided electrical protection A 16
Type of connection Y
Enclosure class IP20
Sound pressure level LpA 1m
3)
dB(A) 49 53 52
Electronic start safeguard Series
Operating hours counter Series
Power meters Series
Hot gas defrosting Series
Hygrostat Series
Room temperature sensor Series
Condensate pump, built-in Option
Hose length (condensate pump) m
5 (10 4))
Delivery height (condensate pump) m 5
For more, see the next page.
7
REMKO LTE
Unit type LTE 50 LTE 60 LTE 80
Dimensions
Depth mm 512
Width mm 540
Height mm 795
Height incl. transportation bracket mm 945
Weight kg 38.5 40.0 45.0
EDP no. 618500 618600 618800
EDP no. Unit with condensate pump 618505 618605 618805
1)
(DER) = Dehumidification output figure in accordance with DIN EN 810
2)
Contains greenhouse gas according to Kyoto protocol.
3)
Noise level measurement DIN 3744 - KL 2
4)
Max. permissible hose length
W
e reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
8
A
B

3 Design and function

3.1 Air dehumidification ­general note
The correlations occurring when air is dehumidified are based on physical laws. These are depicted here in graphical form in order to provide you with a brief overview of the principles of air dehumidifi­cation
The use of REMKO air dehumidifiers
n Even if windows and doors are well insulated,
water and moisture are still capable of pene­trating thick concrete walls.
n The water required for setting in the production
of concrete, mortar and plaster etc. may only
fused after 1-2 months.
be dif
n Even moisture trapped in the masonry after
high-water or a flood is released very slowly.
n The same is also true of moisture contained in
stored materials for example.
The moisture (water vapour) released from parts of a building or materials is absorbed by the sur­rounding air increases, which ultimately gives rise to corrosion, mould, rot, peeling of paint and other unwanted damage. By way of example, the diagram below shows the corrosion rate of metal in different levels of humidity.
. As a result, the moisture content
1. By heating and air exchange: The air in the room is heated in order for moisture to be removed and then this air is fed outside. All of the energy that is involved is lost together with the moist air that is released.
2. By air dehumidification: The moist air that is present within an enclosed space is continu­ously dehumidified in accordance with the condensation principle.
With regard to energy consumption, air dehumidifi­cation has one distinct advantage:
Energy expenditure is limited exclusively to the air volumes present. The mechanical heat that is released by the dehumidification process is fed back into the room.
NOTICE!
Under normal use, the air dehumidifier uses approximately 25% of the energy that is required for the "heating and ventilating" prin­ciple.
Fig. 1: Corrosion rate in relation to relative humidity
A: Corrosion rate B: Relative humidity [%]
It is evident that the corrosion rate below 50% rela­tive humidity (RH) is low gible.
The corrosion rate increases significantly above 60% RH. This threshold for damage as the result of humidity also applies to other materials, such as powdery substances, packaging, wood and elec­tronic units.
Buildings may be dried in a variety of ways:
9
, and below 40% is negli-
REMKO LTE
Relative air humidity
Our ambient air is a gaseous mixture which always contains a certain volume of water in the form of water vapour per kg of dry air (absolute moisture content).
1m3 of air weighs approx. 1.2 kg at 20 °C
Depending on the temperature, each kg of air is only capable of absorbing a certain volume of water vapour. Once this capacity has been reached, the air is referred to as "saturated" and has a relative humidity (RH) of 100%.
Relative humidity is understood to mean the ratio between the current quantity of water vapour in the air and the maximum possible quantity of water vapour at the same temperature. The ability of the air to absorb water vapour increases as the tem­perature rises. I.e. the maximum possible (abso­lute) water content becomes greater as the tem­perature rises.
Temp.
°C 40% 60%
. This volume of water is specified in g
Water vapour content in g/m at humidity of
3
Drying materials
Building materials and structures are capable of absorbing considerable volumes of water brick 90-190 l/m³, heavy concrete 140-190 l/m³ and limestone 180-270 l/m³. The drying of moist mate­rials such as masonry is effected as follows:
The moisture moves from the inside of the material to its surface.
, such as
-5 1.3 1.9
+10 3.8 5.6
+15 5.1 7.7
+20 6.9 10.4
+25 9.2 13.8
+30 12.9 18.2
°C 80% 100%
-5 2.6 3.3
+10 7.5 9.4
+15 10.2 12.8
+20 13.8 17.3
+25 18.4 23.0
+30 24.3 30.3
n Evaporation occurs on the surface = T
of water vapour to the ambient air
n The air containing water vapour is constantly
circulated through the REMKO air dehumidifier. The air is dehumidified and, slightly heated, leaves the unit in order to re-absorb water vapour
n In this way, the moisture contained in the mate-
rial is reduced gradually
The material is dried!
The accumulated condensate is collected in the unit and drained of
f from there.
ransfer
Fig. 3: Extracting and collecting condensate
10
Functional principle of the air dehumidifier
2
1
A
B
C
a
As it flows through or over the evaporator, the air stream is cooled to dew point. The water vapour con­denses, and is collected in a condensate trap from where it is drained of
f.
Fig. 4: Functional principle of the air dehumidifier
1: Evaporator 2: Condenser A: Air temperature
The condensation of water vapour
Because the capacity for the maximum possible volume of water vapour increases as the air is heated, the volume of water vapour contained remains constant and so relative humidity falls.
In contrast, because the capacity for the maximum possible volume of water vapour decreases as the air is cooled, the volume of water vapour contained remains constant and so relative humidity increases. If the temperature continues to fall, the capacity for the maximum possible volume of water vapour is reduced so much so that it is ultimately equal to the volume of water vapour contained in
.
the air
This temperature is referred to as the dew point. If the air is cooled to below dew point, the volume of water vapour in the air will become greater than the maximum possible volume of water vapour. At this point, the water vapour begins to precipitate. It then condenses to water. Humidity is then removed from the air.
B: Air direction C: Humidity a: Progression
Examples of condensation include steamed-up window panes in winter, or the moisture on the out­side of a cold drinks bottle.
As the relative humidity of the air increases, so too does the dew point, making it easier for the tem­perature to fall below it.
Condensation heat
The energy transferred to the air from the con­denser consists of:
1. the amount of heat derived beforehand in the evaporator
2. the electrical drive energy
3. the condensation heat released by the lique-
fying of the water vapour
.
11
REMKO LTE
Energy must be supplied when liquid is converted into a gas. This energy is designated as evapora­tion heat. It does not cause any increase in tem­perature, but is required to convert a liquid into a gas. Conversely liquefied, this is designated as condensation heat.
The amount of energy from evaporation heat and condensation heat is the same.
For water, this is: 2250 kJ/kg (4.18 kJ = 1kcal)
From this it is evident that the condensation of water vapour causes a large quantity of energy to be released. With drying operations, a heat cycle is created, whereby heat is consumed for evapora­tion and released for condensation.
Generally speaking, the time required for the drying process is not only dependent on the output of the unit, but is determined to a greater extent by the speed at which the material or building section loses its moisture.
, energy is released when gas is

3.2 Unit description

The units have been designed for universal and straightforward air dehumidification.
Their compact dimensions allow the unit to be transported and set up with ease.
The units operate in accordance with the conden­sation principle and are equipped with a hermeti­cally sealed refrigerant system, low-noise and low­maintenance fan, operating hours and energy counter as well as a connection cable with plug. Fully-automatic electronic controller container with integrated overflow protection in addition to connection ports for direct condensate drainage help to ensure continuous fault-free oper­ation.
The units conform to the fundamental health and safety requirements of the appropriate EU stipula­tions. The units are dependable and offer ease of operation.
Locations at which units are used
The units are used in all locations, where dry air is a must and where economic consequential damage (such as that caused by mould) must be prevented.
, a condensate
The units may be used for the drying and dehumid­ification of areas such as:
n New buildings, industrial buildings n Basements, storage rooms n Archives, laboratories
eekend homes, caravans
n W n Bathrooms, wash rooms and changing rooms
etc.
Operating sequence
Switching on the unit puts the electrical control into operation. The green "COMP on the control panel illuminates. Due to an auto­matic pressure equalisation, the units start with a time delay of around 10 seconds.
The fan extracts the moist room air through the dust filter, evaporator and the condenser behind.
Heat is removed from the room air on the cold evaporator. The air is then cooled to below dew point. The water vapour contained in the room air is then deposited as condensate or rime on the evaporator fins.
If the temperature sensor here measures a pre-set minimum, it activates a timer with a 30 minute delay. If the evaporator temperature stops increasing during this period, the cooling cycle switches to hot gas defrosting after the timer cycle.
The fan remains out of operation during the defrosting phase.
As soon as the rime (ice) has been defrosted and the temperature at the probe has increased, the unit switches back to normal dehumidification mode.
If the room temperature is sufficiently high, the sur­face of the fins will not be cold enough for rime for­mation to occur, rendering defrosting unnecessary. Therefore, the air dehumidifiers work economically.
The cooled and dehumidified air is re-heated by the condenser (heat exchanger), and blown back into the room through the outlet grille. The pro­cessed, dry, heated air then re-mixes with the room air.
Continuous circulation of the room air through the unit gradually reduces the relative humidity (% RH) in the room to the desired humidity level. Depending on the room temperature and the humidity, only 30-40% electrical energy is required, in accordance with the output of the unit.
. ON" indicator light
12
21
4
3
5
A
B
Fig. 5: Air dehumidification operating principle
A: Dehumidified room air B: Moist room air 1: Fan 2: Condenser
3: Evaporator 4: Compressor 5: Condensate container
13
0,5 m
0,5 m
REMKO LTE

4 Assembly

4.1 Setting up the unit

For the best economic and safe use of the units, the following notes must be followed in full:
n The units must be set up in an upright and
level position, to ensure that the condensate can drain freely
o ensure optimum air circulation, the units
n T
should be set up in the centre of the room, where possible
n It must be ensured that the air can be sucked
in on the front of the unit and blown out of the rear of the unit without obstruction
n Observe a minimum clearance of 50 cm from
walls at all times
n Units must never be set up in the immediate
vicinity of heaters or other sources of heat
n The room being dried or dehumidified must be
closed to the surrounding atmosphere
n Air circulation is improved if the unit is set up
approx. 1 m above the ground
n Avoid having opened windows and doors etc.,
and avoid frequent entry to or exit from the room as much as possible
n If the units are to be used in dusty environ-
ments, appropriate care and maintenance measures should be taken in accordance with the relevant conditions
n The output of the unit is entirely dependent on
the conditions inside the room, room tempera­ture, relative humidity and observance of the set-up instructions
n The units may not be used in environments
containing a great deal of dust or chlorine, or in places with atmospheres containing ammonia
NOTES:
Keep windows and doors closed! Keep at least 0.5 m away from walls. Maintain adequate clearance from heaters
or other sources of heat.

4.2 Unit transport

For easy transportation, the units are equipped with 2 large wheels and an ergonomic transporta­tion handle and protective frame. This can also be dismantled easily if required.
When transporting the units, observe the following:
1. Before each change of location, switch of the unit and remove the power plug from the mains socket.
2. Drain the condensate container
3. Only transport the units in an upright position
where possible.
4. If the unit was transported on its side, you must wait 1 hour with the unit in an upright position before switching on.
.
f
Fig. 6: Setting up the unit
NOTICE!
Beware of dripping condensate. After switching of
f the units, the evaporator may continue to defrost under the influence of the ambient tem­perature.
WARNING!
The mains cable must never be used as a pull cord or fixing device.
14

5 Electrical wiring

~
A
B
21 4
3
5 6 7 8 9
1 2 3 4 5 6 7 8
PE
PE
PE
10
C
PE L N
11
12
PE

5.1 General notes

n The units are operated with 230 V / 50 Hz
alternating current
n The electrical connection is made using a built-
in mains cable with earthed safety plug
WARNING!
The electrical connection to the units must be made at feed-points with residual current devices in accordance with VDE 0100, Section
704. When installing the units in extremely damp environments such as laundry rooms, showers etc., the unit must secured with a residual current device provided by the cus­tomer in accordance with the regulations.

5.2 Electrical wiring diagram

n Extensions to the connection cable may only
be carried out by authorised electricians, sub­ject to the length of the cable, connected load of the unit and taking into consideration how the unit is used at its location
CAUTION!
All cable extensions must only be used in fully un-reeled or reeled of
f condition.
Fig. 7: Electrical wiring diagram
A: Control board B: Display circuit board C: Optional 1: Power supply 2: Compressor 3: Solenoid valve 4: Fan motor 5: Evaporator probe
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
15
6: Condenser probe 7: Water stop probe 8: RESET button 9: Humidity probe 10: Fuse 3.15A 250V 11: Mains adapter 12: Condensate pump
REMKO LTE

6 Commissioning

Before commissioning the unit or if local require­ments dictate, the air-inlet grille and air-outlet grille must be checked for contamination.
NOTICE!
A contaminated grille or filter must be cleaned or replaced immediately
Important notes prior to commissioning
n All extensions to the electrical connection must
be of a suf used fully rolled out or unrolled.
n Never use the power supply connection cable
as a pull cord.
n After being switched on, the units operate fully-
automatically until switched off by the float when the condensate container is full.
n The condensate container must be inserted
properly.
n In order to prevent damage to the condenser,
the units are equipped with a mechanism that prevents the compressor from being immedi­ately switched back on after it is switched off
The compressor does not switch back on until after a waiting time of ca. 1 minute!
ficient cable size and must only be
.
Starting the unit
Start the unit as follows:
1. Plug the unit's power plug into a properly installed and fused mains socket (230V/50 Hz).
If you connect the dehumidifier to the mains, the unit should be switched of ating). The segment display and LED indica­tors illuminate for 3 seconds (the humidity display shows "88" and the hour counter dis­play shows "88888.8"). After that the seg­ment display for the humidity [3] shows the environmental humidity and the display for the operating hours counter and the energy counter [6] shows the operating hours counted for the compressor.
2. Actuate the "ON/OFF" key
The green "COMP. ON" indicator light illumi­nates. The unit switches on with a time delay of around 10 seconds and then runs in con­tinuous operating mode.
The unit will now operates fully-automatically until the desired relative humidity (% RH) has been reached or until the unit is switched off by the float when the condensate container is full. In this case, the red "FULL TANK" indi­cator light illuminates.
f (not oper-
.
NOTICE!
In room temperatures below 10 °C and relative humidity below 40%, economical use of the unit can no longer be guaranteed.
Automatic restart after power failure:
If the electrical power fails or if the power plug is pulled out during operation, the unit switches off. When the unit is switched back on again or if the power plug is put back in again the unit starts up again automatically after a safety delay time of 70 seconds.
16
Control and display panel:
2 14
3
56
789101112
1
2
3
Fig. 8: Control panel
ON / OFF key:
After actuating the ON / OFF key whilst switched of
f, the unit starts as soon as the humidity in the room (RH) is 4% higher than the target value set for the humidity in the room. The start sequence is: Fan motor ON → solenoid valve ON 10 seconds and then OFF → compressor ON. If the room humidity is lower than the target value set for the humidity in the room, then the "COMP. ON" indi­cator flashes and the unit is in standby mode (not operating).
If the ON / OFF key is actuated during operation, the unit and the COMP ON" display switch off. The ON / OFF delay time of the compressor is 1 minute.
SET HUMIDITY - Desired humidity setting:
After the unit is switched on, the target room humidity can be adjusted up or down by pressing the arrow keys. As soon as the room humidity rea­ches the target humidity set, the compressor and the fan motor stop. The target room humidity set is displayed for 3 seconds during the adjustment and then reverts to the current measured room humidity
.
NOTE:
If the humidity lies below the target humidity set (i.e.: rRH <-3%), the compressor and the fan motor stop. If the humidity is higher than the target humidity set (i.e.: rRH >+4%), the unit restarts with a 3 minute delay
.
Example: If the target humidity = 50% RH, but the room humidity is 47% RH, then the compressor and fan motor stop and the "COMP. ON" indicator flashes (standby display!). While the room humidity rises to 54% RH, the unit restarts with a 3 minute delay time in accordance with the start function sequence.
The target room humidity value must be set within 3 seconds by pressing the up arrow or down arrow keys. Then the current room humidity is displayed again.
Segment display for humidity
, room temper-
ature and malfunction code:
The standard display is the current measured room humidity. The humidity value to be changed is dis­played for 3 seconds by pressing one of the arrow keys [2] to set the target room humidity. If the ROOM TEMP key is pressed, the current meas­ured room temperature is shown in the display for 5 seconds and then the display automatically switches back to the current measured room humidity.
n If the unit is restarted it reverts to the pre-
vious setting
n The adjustment steps for the target humidity
are 5% ( RH) per key press. The adjustment range for the target humidity should lie between 30% and 70% ( RH)
17
4
5
6
7
8
9
REMKO LTE
Function or situation Segment display
Power plug is plugged in, the unit is switched of
f
Current measured room humidity is displayed
The unit starts Current measured room humidity is displayed
During the adjustment of the target room
The target room humidity set is displayed
humidity
Upon actuation of the ROOM TEMP. Key
The current measured room temperature is displayed for 5 secs
Is a malfunction is present Error code is displayed
Room temperature key (RT) - T
o display the
room temperature:
By actuating the "ROOM TEMP." key, the red RT °C indicator illuminates and the current room tem­perature is displayed for 5 seconds in the segment display [3]. Then the current measured room humidity appears again automatically.
COMP
. ON INDICATOR:
If the compressor is running, this indicator is illumi­nated. If the compressor is stops, the indicator flashes.
The unit has a 3 minute restart delay for the com­pressor as a safety function. This means that the compressor requires 3 minutes to restart after it has stopped due to having reached the target
COUNTED key - to display the electrical
power consumed or the compressor run-time
room humidity set. The "COMP. ON" indicator flashes during the 3-minute protection period
counted:
By actuating the "COUNTED" key
, the "kWh" indi­cator illuminates and the electrical power (kW) con­sumed by the unit is displayed in the segment dis­play [6].
Actuating the "COUNTED" key again switches off the "kWh" indicator and the operating hours (h) of the compressor are displayed in the segment dis­play [6].
DEFROST INDICA
If the temperature of the evaporator (Te) is <= 1 °C and the compressor runs for more than 5 minutes, the DEFROST indicator flashes and the 30-minute delay timer for the defrost function starts.
Defrost function: Compressor still ON, fan motor OFF, solenoid valve ON, DEFROST indicator illu­minates. If the temperature of the evaporator (Te)
TOR:
is >= 3 °C then the defrost function stops and the
Segment display - display of the electrical
power consumed or the compressor run-time counted:
In standby mode, the current compressor run-time (h) is displayed in the segment display [6] or
, by actuating the "COUNTED" key, the electrical power consumed (kWh).
The segment display [6] shows the operating hours of the compressor or the electrical power con­sumed by the unit. The display shows values from "0.0" to "99999.9"
DEFROST indicator extinguishes.
Function of the unit after defrost: Compressor ON, fan motor ON, solenoid valve OFF, DEFROST indi­cator off
"CHECK" indicator:
If there is an abnormal situation (malfunction), the CHECK indicator [9] illuminates or flashes. If the temperature probe (T
e or Tc) or the humidity probe is defective, the unit switches off and the indicator light [9] illuminates. Then the error code (E1, E2, E4 or E5) is displayed in the segment display [3]. If the water tank is full (FULL TANK), the indicator light (CHECK) flashes.
If the temperature of the condenser (Tc) is over 50 °C while the unit is running, the indicator light (CHECK) flashes.
There are two types of protective function for the Tc over-temperature (50 °C):
18
10
11
12
If Tc is >50 °C and the compressor runs within 5 minutes, the unit switches of
f and the error code "E3" is shown in the segment display [3] and the CHECK indicator [9] flashes. In this case, the fault cannot be reset with a key press. The unit power plug must be removed from the socket so that the unit is completely de-energised. Then, the dehu­midifier can be restarted after a restart delay of 70 seconds.
If Tc is > 50 °C and the compressor runs over 5 minutes, the compressor stops but the fan motor continues to run for a further 30 minutes. The seg­ment display flashes with fault code E3 during this time. After 30 minutes the unit is restarted for normal function with the previous setting.
NOTE:
n Within this 30 minute protective period, the
"ON / OFF" key can be pressed in order to switch the unit of
f. If the "ON / OFF" key is then pressed, the unit restarts after a delay time of 1 minute.
RT °C INDICATOR:
If the "ROOM TEMP" key is pressed, the RT indi­cator [10] illuminates for 5 seconds.
"FULL T
ANK" DISPLAY:
If the water tank is full the "FULL TANK" and "CHECK" indicators illuminate. The compressor and the fan motor are automatically switched off at this time.
In order to reset the messages described, the con­densate water must be removed from the water tank. Then the water tank must be properly inserted back into the unit. After that the unit will start again after a 3 minute delay time.
If the unit is switched off while the "FULL TANK" and "CHECK" indicators are illuminated, both indi­cators switch off.
If the unit is switched on, but is in standby mode (i.e.: room humidity is lower than the target room humidity set), the compressor and the fan motor are switched off and the "COMP. ON" indicator illu­minates. If the water tank is full at this time, the "FULL TANK" and "CHECK" indicators flash.
kWh INDICA
TOR:
By actuating the "COUNTED" key, the "kWh" indi­cator illuminates and the electrical power in kW consumed by the unit is displayed in the segment display [6].
19
REMKO LTE
Function table:
Functions
A Comp. ON LED OFF Flashes ON ON ON OFF
B Check LED OFF OFF OFF OFF OFF Flashes
C Defrost LED OFF OFF OFF Flashes
D Full Tank LED OFF OFF OFF OFF OFF Flashes
E Solenoid valve OFF OFF
F Fan motor OFF OFF
Power plug
inserted
OFF
(no opera-
tion)
Operating status: Unit
operating or in standby
Standby
(no opera-
tion)
r RH <-3%
The unit
starts
r
RH >+4%
ON
for 10 sec.
then OFF
ON
after
10 sec.
Defrost function
30 min. timer
expires if
e<=1 °C
T
OFF
ON
After the 30 mins.
defrost timer
function has
passed
ON
If
T
e >=3 °C,
then OFF
ON
If
T
e >=3 °C,
then OFF
OFF
If
T
e >=3 °C,
then ON
Full tank
function
OFF
OFF
OFF
G Compressor OFF OFF
Humidity seg-
H
ment display [3]
Operating hours / power
I
consumption segment dis­play [6]
Operating hours or power consumption are displayed
(changeover by actuating the "h/kWh" key)
ON
after
10+0.5 sec
Current room humidity is displayed
ON ON OFF
20

7 Condensate removal

A
B
Depending on the air temperature and the relative humidity densate container either continuously or only during the defrosting phases.
A float is located inside the condensate container. In the event that the container is full, the float will activate a water stop switch which will switch off dehumidification mode.
To guard against accidental stops caused by water sloshing around etc., this switch does not activate until after a time delay of 10 seconds. The unit will switch off and the red "TANK FULL" indicator light on the control panel will flash.
In order to empty the condensate tank, proceed as follows:
1. Actuate the "ON/OFF" switch.
2. Remove the filled condensate tank. T
, condensed water will drip into the con-
o do this, lift the container slightly using the embedded recessed grip and then pull it carefully forwards and out.
NOTICE!
5. Close the pouring opening [B] and carefully
insert the condensate container back into the unit.
6.
NOTICE!
After being emptied, the condensate con­tainer incl. float must be checked for damage, contamination etc.
Switch the unit on again with the "ON/OFF" key .
Beware of dripping condensate. After switching of
f the units, the evaporator may continue to defrost under the influence of the ambient tem­perature.
3.
Place the container carefully outside the unit and pull of the sealing cover [A] of the pouring opening [B].
4. Pour the water into a drain.
NOTICE!
The units are only fully functional if the conden­sate container is inserted properly
Unit operation with hose connection
The hose connection is implemented directly on the 12 mm Ø screw-in hose nozzle that is placed on the top edge of the condensate tank when shipped.
Connect the hose as follows:
1. Remove the condensate tank.
2. Remove the screw-in hose nozzle from the
place-holder [D] and swap this for the sealing screw in the 3/8" inside thread [C]. Then tighten the screw-in hose nozzle hand-tight.
Ensure that the connection is sealed!
3. Plug hose with inside diameter 12 mm onto the screw-in hose nozzle and secure this with a hose clamp to prevent it slipping off.
4. Then fit the condensate tank back into place.
Ensure that there are no kinks in the hose!
.
21
C
D
E
F
REMKO LTE
Unit operation with condensate pump (optional)
The condensate tank with integrated pump has two magnetic contacts [E] on the rear to establish the electrical connection with the unit. If the unit is sup­plied with power at the contacts on the unit side. This provides the power supply for the condensate pump.
, 12 V DC is continuously present
Fig. 9: Detailed view
Fig. 10: Placeholder
Fig. 11: Sealing screw
Fig. 13: Condensate tank at the rear
The following steps should be carried out for unit operation with condensate pump:
1. Remove the condensate tank.
2. Plug the hose supplied onto the pass-though
hose nozzle [F] fitted previously and secure this with a hose clamp to prevent it slipping of
f.
3. Ensure that the connection is sealed.
4. Fit the condensate tank back into place. The
pump is immediately ready for use. If the water level in the condensate tank is suf ciently high, this starts to pump out the water.
Ensure that there are no kinks in the hose!
fi-
Fig. 12: Screw-in hose nozzle
In unattended permanent operating mode, the con­densate should preferably be drained into a lower­level drain. If using a collection container (pan, bucket, etc.), the unit must be placed at a correct height.
Fig. 14: Condensate tank and hose
NOTICE!
Unit operation with condensate pump is only possible with units that were shipped with the pump installed.
22
NOTICE!
If the condensate pump runs for an extended period of time, the condensate tank must be checked for contamination at regular intervals.
Unit operation with a condensate tank without pump is possible at any time.
23
REMKO LTE

8 Troubleshooting and customer service

The unit and components are manufactured using state-of-the-art production methods and tested several times to verify that they function correctly detailed in the list below. Please inform your dealer if the unit is still not working correctly after all function checks have been performed!
Operational malfunctions
Malfunction Remedial measures
Check the setting of the "ON/OFF" switch. The green "COMP. "ON" indi­cator must illuminate
Check the power supply and the power fuse provided by the customer 230V/1~/50 Hz
The unit does not start
Check the power plug and the cable for damage
. However, if alarms should occur, please check the functions as
The red CHECK (malfunction) indicator light illuminates
The unit runs but does not form any condensate
Check the level and correct seating of the condensate tank
Check the setting of the desired humidity. The pre-set value must be lower than the relative humidity in the room
The cooling cycle is overloaded or overheated (see "CHECK" indicator
Ä
on page 18)
Before starting the unit again, first identify the cause of the malfunction. (see "CHECK" indicator
Check the room temperature. The operating range of the unit is between 3 °C and 32 °C
Check humidity of the air, min. 40% RH required
Check the dust filter for contamination and clean or replace if necessary
Check the evaporator and condenser fins for contamination and clean if necessary
Check the evaporator for ice or rime formation. If ice has formed, check the functionality of the automatic defrost and the temperature sensor
If the unit fails to function correctly after the checks have been carried out, contact an authorised specialist
Ä
on page 18)
WARNING!
ork on the refrigerant system and on the electrical equipment must only be conducted by a specially-
W authorised specialist!
24
Display of error codes
1
Error codes are displayed in the segment display [1].
Fig. 15: Segment display
Error code description:
Error code Error description
E1 Evaporator temperature probe (Te) defective
E2 Condensate temperature probe (Tc) defective
E3 Compressor runs within 5 minutes and the condenser temperature (Tc) > 50 °C
E3 flashes Compressor runs over 5 minutes and the condenser temperature (Tc) > 50 °C
E4 Humidity/temperature probe (hygrostat) defective (room humidity measured > 100% RH)
E5 Humidity/temperature probe (room temperature Rt)

9 Shutdown

Actuate the "ON/OFF" key, the "COMP. ON" indi­cator must extinguish.
If the units are inactive for longer periods, discon­nect them from the mains power supply
Empty the condensate container and dry with a clean cloth.
Beware of dripping condensate!
When storing the unit, cover with a plastic sheet/ foil if necessary and store in an upright position in a sheltered and dry location.
To save space when storing, the units can be stacked on top of one another (max. two units stacked on top of each another). For this purpose, they are equipped with rubber pads on the base plate.
.
Fig. 16: Stacking with max. 2 units
NOTICE!
The units must be protected against falling down and unauthorised access after stacking.
25
REMKO LTE

10 Care and maintenance

10.1 Care and maintenance

General notes
Regular care and maintenance is fundamental to a long service life and fault-free operation of the unit.
All moving parts have a low-maintenance perma­nent coat of lubricant. The refrigerant system is designed as a hermetically sealed system and may only be repaired by a specialist.
DANGER!
Before undertaking any work on the units, the mains plug must be removed from the mains socket.
n Observe the regular care and maintenance
intervals
Cleaning the dust filter
NOTICE!
Check the inlet and outlet grille and the dust filter for contamination on a regular basis.
Pull the protection grid forwards and then remove upwards.
Then remove the dust filter which has now been released. Light contamination of the dust filter may be remedied with careful blowing or suction.
Heavier contamination may be remedied by rinsing the filter in a lukewarm (max. 40 °C) soap solution. Finally
, always rinse the filter carefully with clear
water and allow to dry!
Before refitting the dust filter, ensure that its fully dry and that no damage has been sustained.
NOTICE!
Heavily contaminated dust filters must be replaced with new parts. Only original replace­ment parts may be used.
NOTICE!
Check the inlet and outlet grille for contamina­tion on a regular basis.
n In accordance with the operating conditions,
the units must be checked as and when required, but at least once per year cialist to ensure that they are in a condition that is safe to use
n Keep the units free of dust and other debris n Only clean the units with a dry or moistened
cloth
n Never subject to direct jets of water
(e.g. pressure washers etc.)
n Never use abrasive or solvent-based cleaners n Even with heavy contamination, use only suit-
able cleaners
, by a spe-
The units may only be operated with the dust filter in place.
26
C
Cleaning the units
The unit housing must be opened to allow the inside of the unit to be cleaned and to provide access to electrical components.
NOTICE!
Adjustment and maintenance work may only be carried out by authorised qualified technicians.
1. Loosen the two fastening screws [C].
2. Lift up the service flap and unhook the top
lugs.
4. Clean the evaporator fins, for example with a lukewarm soap solution (or similar).
NOTICE!
When cleaning the exchanger must be taken because the fine aluminium fins bend very easily.
5. Never subject to direct jets of water
6. Rinse with clean water to remove any
remaining soap.
7. Clean the internal surfaces of the unit and the fan blade.
8. Clean the condensate trap and the connec­tion nozzle.
9. Once cleaning has been completed, the unit should be dried. T
electrical components!
10. Re-install all dismantled components in
reverse order
11. Carry out a unit function check and electrical safety check.
ake particular care with
.
, particular care
.
3. Clean the condenser fins by blowing, with suction or using a smooth brush.
WARNING!
An electrical safety check must be carried out in accordance with VDE 0701 after any work on the units.
27
REMKO LTE

10.2 Maintenance protocol

Unit type:
--------------------------------
010203040506070809101112131415161718192
Unit cleaned - outside -
Unit cleaned - inside -
Fan blade cleaned
Fan housing cleaned
Condenser cleaned
Evaporator cleaned
Fan function checked
Air-inlet grid with filter cleaned
Unit checked for damage
Safety devices checked
All fastening screws checked
Electrical safety check
Unit number:
---------------------------------------
0
Test run
Comments: ...................................................................................................................................................
.............................................................................................................................................................................
01. Date: .............
...............................
Signature
06. Date: ............
...............................
Signature
11. Date: ............
...............................
Signature
16. Date: ............
...............................
Signature
02. Date: .............
...............................
Signature
07. Date: .............
...............................
Signature
12. Date: .............
...............................
Signature
17. Date: .............
...............................
Signature
03. Date: .............
...............................
Signature
08. Date: .............
...............................
Signature
13. Date: .............
...............................
Signature
18. Date: .............
...............................
Signature
04. Date: .............
...............................
Signature
09. Date: .............
...............................
Signature
14. Date: .............
...............................
Signature
19. Date: .............
...............................
Signature
05. Date: .............
...............................
Signature
10. Date: .............
...............................
Signature
15. Date: .............
...............................
Signature
20. Date: .............
...............................
Signature
Unit to be maintained only by authorised specialists in accordance with the statutory regulations.
28

11 Exploded view of unit and spare parts

5
6
4
3
2
1
7
8
9
10
11
12
13
14
15
16
17
19
18
20
21
22
23
24
25
26
27
28
29
30
31
25
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
50
51
52
53
54
49

11.1 Exploded view of the unit LTE 50/60/80

We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
29
REMKO LTE

11.2 Spare parts list LTE 50/60/80

No. Designation LTE 50 LTE 60 LTE 80
1 Lock for sealing flap
2 Air-inlet grille
3 Dust filter
4 Unit housing
5 Control panel
6 Filter grill, interior
7 Evaporator fin package cpl.
8 Top separating panel
9 Transportation bracket
10 Side covering, right
11 Support frame
12 Fan blade
13 Engine mounting cpl.
14 Drive clutch
15 Fan motor
16 Hose clamp 3/8" x 12 mm with O-ring
17 Condensate container cpl.
18 Taper plug
19 Magnetic float compl.
20 Dry filter
21 Humidity / temp. probe cover
22 Humidity / temp. probe
23 Humidity / temp. probe holder
24 NTC evaporator probe
25 NTC condenser probe
26 Condensate tank slide rail (left, right)
On request by providing the
serial number
27 Condensate guide panel (left, right)
28 Magnetic contact retaining plate
29 Pump mains power unit with magnetic contact and cable
30 Fastening plate for water stop switch
31 Water stop switch (reed contact)
32 Side covering, left
33 Hub cover cap
34 Wheel screw
30
No. Designation LTE 50 LTE 60 LTE 80
35 Wheel
36 Wheel
37 Triangular bracket
38 Condensate tank fastening plate
39 Base plate
40 Compressor, cpl.
41 Solenoid valve
42 Coil for solenoid valve
43 Housing cover
44 Operating condenser
45 Control board
46 Switch cabinet housing
47 Rear wall, housing parts
48 Stand
49 Rubber stopper, stand (2 pieces / set)
50 Strain relief
51 Axle
52 Axle fastening plate
53 Rubber stopper, base plate (4 pieces / set)
54 Mains cable with plug
Spare parts not illustrated
Sealing screw with O-ring
Magnetic float brake
O-ring
Condensate tank with pump cpl.
Tank pass-through
On request by providing the
serial number
On request by providing the
serial number
Check valve
Hose 1m
To assure the correct delivery of spare parts, please always provide the unit type with its corresponding serial number (see name plate).
31
REMKO LTE

12 Index

A
Air dehumidification, description ............. 9
Automatic restart after power failure ......... 16
C
Care ................................. 26
Care and maintenance ................... 26
Clean dust filter ......................... 26
Clean units ............................ 27
Cleaning the dust filter ................... 26
Cleaning the units ....................... 27
Commissioning ......................... 16
Condensate removal ..................... 21
Condensate trap, function ................. 1
Condensation heat ...................... 11
Condensation of water vapour ..............11
Control and display panel: .................17
Customer service ....................... 24
1
D
Display of error codes .................... 25
Disposal of equipment .....................6
Drying materials ........................ 10
E
Electrical wiring ......................... 15
Electrical wiring diagram .................. 15
Environmental protection ...................6
Error codes, display and description ......... 25
Exploded view drawing ................... 29
Exploded view of the unit ................. 29
L
Locations for use ........................12
M
Maintenance ........................... 26
Malfunction ............................ 24
O
Operating sequence ..................... 12
Operational malfunctions ..................24
Ordering spare parts ..................... 30
R
Relative air humidity ..................... 10
S
Safety
Dangers of failure to observe the safety
notes ............................... 4
General ............................. 4
Identification of notes ................... 4
Instructions for the operator .............. 5
Note for inspection work .................5
Note for installation work ................ 5
Note for maintenance work .............. 5
Personnel qualifications ................. 4
Safety-conscious working ................4
Unauthorised modification ...............6
Unauthorised replacement part manufacture . 6
Setting up the unit ....................... 14
Shutdown ............................. 25
Spare parts list ......................... 30
Starting the unit .........................16
T
Transporting the unit ..................... 14
Troubleshooting and customer service ....... 24
U
Unit transport .......................... 14
W
Warranty ............................... 6
Water vapour content .................... 10
Water vapour, condensation ............... 11
32
33
REMKO LTE
34
Consulting
Thanks to intensive training, our consultants are always completely up-to-date in terms of technical knowledge. This has given us the reputation of being more than just an excellent, reliable supplier: REMKO, a partner helping you find solutions to your problems.
Distribution
REMKO offers not just a well established sales network both nationally and internationally, but also has exceptionally highly­qualified sales specialists. REMKO field staff are more than just sales representatives: above all, they must act as advisers to our customers in air conditioning and heating technology.
SFlbCustomer Service
Our equipment operates precisely and reliably. However, in the event of a fault, REMKO customer service is quickly at the scene. Our comprehensive network of experienced dealers always guarantees quick and reliable service.
REMKO INTERNATIONAL
… and also right in your neighbourhood! Make use of our experience and advice
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
REMKO GmbH & Co. KG Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 606-0 Telefax +49 5232 606-2 60 E-mail info@remko.de Website www.remko.de
Loading...