Carefully read the operating manual before commissioning the units for the first time. It contains
useful tips and notes such as hazard warnings to
prevent personal injury and material damage.
Failure to follow the directions in this manual not
only presents a danger to people, the environment
and the system itself, but will void any claims for
.
liability
Keep this operating manual and the refrigerant
data sheet near to the units.
1.2 Identification of notes
This section provides an overview of all important
safety aspects for proper protection of people and
safe and fault-free operation.The instructions and
safety notes contained within this manual must be
observed in order to prevent accidents, personal
injury and material damage.
Notes attached directly to the units must be
observed in their entirety and be kept in a fully
legible condition.
Safety notes in this manual are indicated by symbols. Safety notes are introduced with signal words
which help to highlight the magnitude of the danger
in question.
DANGER!
CAUTION!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause injury or material and environmental damage.
NOTICE!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause material and
environmental damage.
This symbol highlights useful tips and recommendations as well as information for efficient
and fault-free operation.
1.3 Personnel qualifications
Personnel responsible for commissioning, operation, maintenance, inspection and installation must
be able to demonstrate that they hold a qualification which proves their ability to undertake the
work.
Contact with live parts poses an immediate
danger of death due to electric shock. Damage
to the insulation or individual components may
pose a danger of death.
DANGER!
This combination of symbol and signal word
warns of a situation in which there is immediate
danger
cause serious injury.
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may be fatal or cause
serious injury
, which if not avoided may be fatal or
WARNING!
.
1.4
Dangers of failure to observe
the safety notes
Failure to observe the safety notes may pose a risk
to people, the environment and the units. Failure to
observe the safety notes may void any claims for
damages.
In particular, failure to observe the safety notes
may pose the following risks:
n The failure of important unit functions.
n The failure of prescribed methods of mainte-
nance and repair
n Danger to people on account of electrical and
mechanical effects.
.
1.5 Safety-conscious working
The safety notes contained in this manual, the
existing national regulations concerning accident
prevention as well as any internal company
working, operating and safety regulations must be
observed.
4
1.6 Safety notes for the operator
The operational safety of the units and components is only assured providing they are used as
intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified personnel.
n Protective covers (grille) over moving parts
must not be removed from units that are in
operation.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with certain unit parts or components
may lead to burns or injury
n The units and components must not be
exposed to any mechanical load, extreme
levels of humidity or extreme temperature.
n Spaces in which refrigerant can leak sufficient
to load and vent. Otherwise there is danger of
suffocation.
n All housing parts and device openings, e.g. air
inlets and outlets, must be free from foreign
objects, fluids or gases.
n The units must be inspected by a service tech-
nician at least once annually. Visual inspections and cleaning may be performed by the
operator when the units are disconnected from
the mains.
.
1.7 Safety notes for installation,
maintenance and inspection
n The units and components must be kept at an
adequate distance from flammable, explosive,
combustible, abrasive and dirty areas or
atmospheres.
n Safety devices must not be altered or
bypassed.
Unauthorised modification
1.8
and changes
Modifications or changes to units and components
are not permitted and may cause malfunctions.
Safety devices may not be modified or bypassed.
Original replacement parts and accessories
authorised by the manufactured ensure safety
use of other parts may invalidate liability for
resulting consequences.
. The
1.9 Intended use
Depending on the model, the equipment and the
additional fittings with which it is equipped is only
intended to be used as an air-conditioner for the
purpose of cooling or heating the air in an
enclosed room.
Any different or additional use shall be classed as
non-intended use. The manufacturer/supplier
assumes no liability for damages arising from such
use. The user bears the sole risk in such cases.
Intended use also includes working in accordance
with the operating and installation instructions and
complying with the maintenance requirements.
n Appropriate hazard prevention measures must
be taken to prevent risks to people when performing installation, repair
cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken
in accordance with the usage and operating
conditions stipulated in this manual and comply
with all applicable regional regulations.
n Local regulations and laws such as Water
Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n Units may only be mounted at the points pro-
vided for this purpose at the factory. The units
may only be secured or mounted on stable
structures, walls or floors.
n Mobile units must be set up securely on suit-
able surfaces and in an upright position. Stationary units must be permanently installed for
operation.
n The units and components should not be oper-
ated in areas where there is a heightened risk
of damage. Observe the minimum clearances.
, maintenance or
Under no circumstances should the threshold
values specified in the technical data be exceeded.
1.10 Warranty
For warranty claims to be considered, it is essential
that the ordering party or its representative complete and return the "certificate of warranty" to
REMKO GmbH & Co. KG at the time when the
units are purchased and commissioned.
The warranty conditions are detailed in the "General business and delivery conditions". Furthermore, only the parties to a contract can conclude
special agreements beyond these conditions. In
this case, contact your contractual partner in the
first instance.
5
REMKO HTS series
1.11 Transport and packaging
The devices are supplied in a sturdy shipping con-
. Please check the equipment immediately
tainer
upon delivery and note any damage or missing
parts on the delivery and inform the shipper and
your contractual partner. For later complaints can
not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous
toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to
children!
1.12 Environmental protection
and recycling
Disposal of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved
collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufacture of the devices and components. Help protect
the environment by ensuring that the devices or
components (for example batteries) are not disposed in household waste, but only in accordance
with local regulations and in an environmentally
safe manner
cling specialists or at collection points.
, e.g. using certified firms and recy-
6
2 Electrical wiring - General
A
B
D
C
1
2
3
4
5
6
8
7
2.1 System layout
Fig. 1: System layout HTS 80/90/110/130
A: Outdoor area
B: Indoor area
C: Outdoor unit
D: Indoor unit
1: Fan / air outlet
2: Condensate drainage, outdoor unit
(must be designed to be frost proof!)
3: Lines between indoor and outdoor modules:
Control line outdoor module 0-10V (sheathed) /
sensor cable (sheathed), e.g. 5 x 1,0 mm
Power supply coming from the outdoor unit /
Condensate drainage heating 5x1.5 mm2,
4:
Refrigerant lines 3/8" and 5/8“
2
5: Inlet
6: Return flow
7: Power supply line to indoor module:
A:Outdoor area
B:Indoor area
C1: Outdoor unit 1
C2: Outdoor unit 2
D:Indoor unit
1:Fan
2:Condensate drain, external module
(must contain anti-freeze!)
3:Lines between indoor and outdoor modules:
Control line outdoor module (sheathed) / sensor
cable (sheathed), e.g. 5 x 1,0 mm
Power supply from the outdoor unit /
condensate drainage heating 5 x 1.5 mm
The indoor and outdoor modules have to be connected with refrigerant lines of dimensions (outer
diameter) 3/8"(=9.52 mm) and 5/8"(=15.88 mm).
2
2
4:
Refrigerant lines 3/8" and 5/8“
5:Inlet
6:Return flow
7:Power supply, indoor unit =
400V / 3~ / 50Hz,16A (e.g. 5 x 2.5 mm2)
Control voltage regulation =
230V / 1~ / 50Hz, 16A (e.g. 3 x 1.5 mm2)
All electric lines are in accordance VDE regulations to dimension and to lay
.
8
2.2 General notes
n It is necessary to lay multiple power supply
lines from the distribution system to the indoor
unit, depending on the version. See "Electrical
wiring" chapter
n The electrical connection between outdoor and
indoor units is made using a sheathed control
line (see "Overview of electrical connecting
lines" chapter).
n A connection schematic along with corre-
sponding circuit diagrams can be found in the
"Connection diagram" chapter of this manual.
n If an auxiliary heater is required in the indoor
unit, another three-phase 400 V / 3~/50 Hz
power supply shall be provided to the indoor
unit for an auxiliary heater.
n Power to the smart control may not be discon-
nected by the power company when fitted with
an off-period circuit (anti-freeze protection).
n The Smart-Control needs to know whether a
power-company release or off-period is in
effect (contact S16). A potential-free switch
must be installed by the customer for this purpose. (contact closed signifies release, while
contact open signifies an off-period).
n Special rates for heat pumps may be offered
by the power-company (utility).
n Ask your local power company about the
details of any rates that might be available.
.
WARNING!
All cable sizes are to be selected according to
VDE 0100. Special attention should be given to
cable lengths, cable type and the kind of installation. The information in the connection diagram and in the system overview are to be
seen as an acceptable installation possibility
only in a standard case!
NOTICE!
The electrical connection for the units must be
made at a separate feedpoint with a residual
current device in accordance with local regulations and should be laid out by an electrician.
Check all plugged and clamped terminals to
verify that they are seated correctly and make
permanent contact. Tighten as required.
DANGER!
All electrical installation work must be done by
an electrician.
WARNING!
Always note the currently applicable VDE
guidelines and the notes in TAB 2007. The size
and type of the fuse are to be taken from the
technical data.
9
REMKO HTS series
2.3 Electrical connection - indoor
module
The following instructions describe the electrical
connection of the inner module.
1.Remove the cover from the indoor module by
pressing it upwards and pulling it forwards
out of the rear groove.
2.Guide the supply cable to the indoor module
through the cable openings, and also route
the control cable between indoor and outdoor
modules and the cables for external devices
and sensors into the indoor module. Note
that the cable openings are located at the
top.
3.Connect the mains power supply line and the
control line of the indoor module to the terminals (see chapter "Electrical wiring").
4.Connect all secondary consumers
(HGM,HGU, changeover valves etc.) to the
I/O module.
NOTICE!
It is necessary to provide a separate RCD 100
mA, type B (universal current-sensitive) with a
contact load of 40 A for the heat pump.
NOTICE!
Attach cables in accordance with the connection schematic and/or the circuit diagram in the
control box.
NOTICE!
Ensure correct polarity when connecting the
electrical leads, especially the control cable.
The number of lines and the sensors is
dependent on the configuration of the heating
system and the components.
At the site, avoid adding cable inlets.
10
2
1
2
2.4 Electrical connection - outdoor
module
o connect up the electrics, remove the whole
n T
basket.
Fig. 3: Remove the basket
Contact sensor
Contact sensors can be mounted on the pipes, to
measure the heating-circuit temperatures, for
example.
n The contact sensors are fastened to a pipe
with the accessories provided.
n Clean the appropriate point. Subsequently a
thermal compound (A) is applied and the
sensor is fixed in position.
n Electrical protection for the system is imple-
mented in accordance with the information in
the T
echnical Data. Observe the required con-
ductor cross-sections!
n All cables must be connected with the correct
polarity and strain relief.
n Follow the connection schematic and the circuit
Ä
diagrams (
on page 14).
n When connecting the control cable, make sure
that polarity is correct.
n If the outdoor module is installed on a roof, it
and the supporting structure must be earthed
separately (connection to lightning conductors
or foundation earth/ground feature).
Temperature sensors
n The number of sensors required can vary with
the type of system.
n Observe the pertinent notes for the sensor
position found in the hydraulic schematic.
n The standard scope of delivery includes the
outdoor sensors (S10), an immersion sensor
(provided for use as a domestic hot water
sensor - (S08).
n When connecting up a solar system, use a
-1000 sensor (S01) as a collector sensor
PT
and a PT-1000 sensor (S02) as the lower
storage tank sensor.
n All sensors are to be connected to the indoor
module switch cabinet in accordance with the
terminal assignment diagram.
Chapter 2.6 ‘Terminal block / key’
Fig. 4: Securing the inductive sensor (figure similar)
If the sensor cables are too short, they can be
extended up to a maximum of 100m with wire
having a cross-section of 1.5 mm².
11
REMKO HTS series
Outdoor sensor
The connection of an outdoor sensor is always
required for Smart Control.
n Mount the outdoor sensor pointing skyward, in
a north-easterly direction, about 2.5 metres
above the ground. It may not be subjected to
direct sunlight and is to be protected against
excessive wind. Installation above windows or
air ducts is to be avoided.
n In order to carry out the installation, remove the
cover and secure the sensor with the screw
provided.
n A cable with wire cross-sections of min. 0.5
mm2 is recommended for connecting the
.
sensor
Fig. 5: Outdoor sensor (figure similar)
12
2.5 Electrical configuration - I/O module
4
5
5
4
8
3L
N
1
01
10
96
7
8
3L
3L
1L
1L
2L
2L
N
N
EP
EP
2
3
3
2
7
10
01
7
10
6
9
6
9
1X kcolb lanimreT
Power supply
Internal module
5x2.5mm²
Depending on device type 3 phase or 1 phase
Control line (0-10V)
external module
Power supply internal
to external module A
e.g.3 x 1.5 mm2
EP-1
L-2
N-3
Sensor wire,
exterior module
Switch output
exterior module A
(electrical heating)
EP
N-4
L-5
9
01
V01-0-6
DNG-7
ybdnats-8 ria .
assigned
41
51
51
41
81
3L
N
11
01
10
96
7
81
21
31
31
21
71
02
01
71
20
6
1
91
61
91
Control wire (0-10V)
external module B
3x1.0 mm2
Power supply internal
to external module B
e.g.3x1.5 mm2
1 EP-1
N-21
L-31
Sensor wire
exterior module B
2x1.0 mm2
EP
N-41
L-51
91
02
V01-0-61
DNG-71
ybdnats-81 ria .
Switch output
exterior module B
(electrical heating) 3 x 1.5 mm2
L N EP
`L N EP
`L N EP
N EP`L 01A
N
EP1A `L 1
N EP
`L 21A
N EP
`L 31A
N EP`L 41A
N EP10A
N EP
20A
N EP30A
N EP40A
N EP 02A12A
N EP 22A32A
N EP 42A52A
Power
Actuator Outputs
Actuator Supply
Actuator Outputs
Actuator Outputs
S
ensor Inputs
DNG V5+ 52S
DNG V5+ 62S
DNG V5+ 72S
DNG V5+ 82S
DNG V5+ 92S
Actuator S
ignal
DNG04A
DNG14A
DNG24A
DNG34A
DNG44A
DNG54A
DNG64A
DNG SSn
KLC OM IM
KNX - TP
1T0 1T0
2T02T0
CR
2B 2A
2B 3A
1B V21+DNG 1A
DNG R
14S 04S DNG V5+ 02S
34S 24S DNG V5+ 12S
54S 44S DNG V5+ 22S
74S 64S DNG V5+ 32S
94S 84S DNG V5+ 42S
DNG 10S
DNG 20S
DNG 30S
DNG 40S
DNG 50S
DNG 60S
DNG 70S
DNG 80S
stupnI rosneS
stupnI rosneS
stupnI rosneS
stupnI rosneS
DNG 90S
DNG 01S
1SDNG 1
DNG 21S
DNG 31S
DNG 41S
DNG 51S
DNG 61S
stuptuO
eerFlaitneto
P
03A 03A
13A
23A
33A
43A
SD
Fuse
RJ 45
Power supply,
primary pump - IM
Energy supplier contact
closed = release
Power supply
I/O module
Potential-free
S0 PV power supply
(min. 500 impulses/kWh)
S0 PV yield
(min. 500 imp./kWh)
S0 household
counter
(min. 500 imp./kWh)
S0 WP current
counter
(min. 500 imp./kWh)
S29
S28
S26
S25
External probe
S10
S16
Changeover valve,
drinking water
M
01A
Pump HK approx.
230V optional
A03
Pump circulation
230 V
A04
M
Closed
Open
Mixer HGM 1
(HK 1 floor)
A20/21
NOTE: without EVU connection,
a bridge must be installed
A: Outdoor unit
B: Indoor unit
C: Customer-provided sub-distribution
D: External probe
1: Power supply, indoor unit, 400V / 3~ / 50Hz,
16A, e.g. 5 x 1.5 mm
2: Power supply, auxiliary heating, 400V /3~/ 50Hz,
16A, e.g. 5 x 2.5 mm
3: Power supply from indoor to outdoor unit / con-
densate drainage heating, 230V / 1~ / 50Hz,
10A, e.g. 5 x 1.5 mm
WARNING!
2
2
2
The configuration of the core cross sections can
be defined by an installation specialist!
only
All cable insertions to the indoor module are
made from above!
All cable insertions to the outdoor module are
made from below!
4: Control line, outdoor unit 0-10V (sheathed) /
sensor line (sheathed), e.g. 5 x 1.0 mm
5:
Sensor cable on external probe, e.g. 2 x 1.0 mm
6: Power supply, controller (Smart-Control)
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
7: Potential-free electrical power supply company
signal for Smart-Control S16,
NOTICE!
For an existing block the heat pump by the
utility (utility switching) must be used the control
contact S 16 of the Smart-Control.
e.g. 2 x 1.0 mm
2
2
2
2
16
3.2 Overview of terminal assignment
B
C
A
E
D
2
34
1
5
Fig. 7: Terminal configuration HTS 80
A: Outdoor unit
B: Indoor unit
C: Customer-provided sub-distribution
D: External probe
E: Electrical heating coil
1: Power supply, indoor unit,
400V / 3~ / 50Hz, 16A, e.g. 3 x 2.5 mm
Electrical connections between indoor and outdoor unit
Indoor unitOutdoor unit
TerminalDescriptionTerminal
1Power supply PE1
2Power supply L2
3Power supply N3
4Power supply, auxiliary heating L4
5Power supply, auxiliary heating N5
6Signal cable 0-10V6
7GND7
2
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 1.5 mm
3: Terminals in indoor unit
4: Terminals on electrical heating coil
5: Power supply, Smart-Control controller (I/O
module)
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
2
2
8Response signal8
9Temperature sensor9
10GND10
17
REMKO HTS series
Electrical connections between distribution and indoor unit
DistributionIndoor unit
TerminalDescriptionTerminal
L1
L2L2
L3L3
NN
PePe
L
NN
PePe
L1
L2L2
L3L3
NN
PePe
Power supply, indoor unit 400V/ 3~/ 50Hz
Power supply, Smart-Control 230V/1~/ 50Hz
Power supply, Smart-Serv 400V/3~/ 50Hz 9kW
L1
L
L1
18
4 Electrical wiring HTS 90
B
C
4
6
A
2
D
5
3
7
1
4.1 Overview of electrical connection cables
Fig. 8: Overview of electrical connection HTS 90
A: Outdoor unit
B: Indoor unit
C: Customer-provided sub-distribution
D: External probe
1: Power supply, indoor unit, 230V / 1~ / 50Hz,
16A, e.g. 3 x 2.5 mm
2: Power supply, auxiliary heating, 400V /3~/ 50Hz,
16A, e.g. 5 x 2.5 mm
3: Power supply from indoor to outdoor unit / con-
densate drainage heating, 230V / 1~ / 50Hz,
10A, e.g. 5 x 1.5 mm
2
2
2
WARNING!
The configuration of the core cross sections can
be defined by an installation specialist!
only
All cable insertions to the indoor module are
made from above!
All cable insertions to the outdoor module are
made from below!
4: Control line, outdoor unit 0-10V (sheathed) /
sensor line (sheathed), e.g. 5 x 1.0 mm
5:
Sensor cable on external probe, e.g. 2 x 1.0 mm
6: Power supply, Smart-Control controller (I/O
module)
7: Potential-free electrical power supply company
signal for Smart-Control S16,
For an existing block the heat pump by the
utility (utility switching) must be used the control
contact S 16 of the Smart-Control.
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
e.g. 2 x 1.0 mm
NOTICE!
2
2
2
2
19
B
C
A
E
D
2
34
1
5
REMKO HTS series
4.2 Overview of terminal assignment
Fig. 9: Terminal configuration HTS 90
A: Outdoor unit
B: Indoor unit
C: Customer-provided sub-distribution
D: External probe
E: Electrical heating coil
1: Power supply, indoor unit,
230V / 1~ / 50Hz, 16A, e.g. 3 x 2.5 mm
Electrical connections between indoor and outdoor unit
Indoor unitOutdoor unit
TerminalDescriptionTerminal
1Power supply PE1
2Power supply L2
3Power supply N3
4Power supply, auxiliary heating L4
5Power supply, auxiliary heating N5
6Signal cable 0-10V6
7GND7
2
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
3: Terminals in indoor unit
4: Terminals on electrical heating coil
5: Power supply, controller (I/O module)
230V / 1~ / 50Hz, e.g. 3 x 1.5 mm
2
2
8Response signal8
9Temperature sensor9
10GND10
20
Electrical connections between distribution and indoor unit
DistributionIndoor unit
TerminalDescriptionTerminal
L1
NN
PePe
L
NN
PePe
L1
L2L2
L3L3
NN
PePe
Power supply, indoor unit 230V/ 1~/ 50Hz
Power supply, Smart-Control 230V/1~/ 50Hz
Power supply, Smart-Serv 400V/3~/ 50Hz 9kW
L1
L
L1
21
B
C
4
6
A
2
D
5
3
7
1
REMKO HTS series
5 Electrical wiring HTS 110
5.1 Overview of electrical connection cables
Fig. 10: Overview of electrical connection HTS 110
A: Outdoor unit
B: Indoor unit
C: Customer-provided sub-distribution
D: External probe
1: Power supply, indoor unit, 400V / 3~ / 50Hz,
16A, e.g. 5 x 2.5 mm
2: Power supply, auxiliary heating, 400V /3~/ 50Hz,
16A, e.g. 5 x 2.5 mm
3: Power supply from indoor to outdoor unit / con-
densate drainage heating, 230V / 1~ / 50Hz,
10A, e.g. 5 x 1.5 mm
WARNING!
2
2
2
The configuration of the core cross sections can
be defined by an installation specialist!
only
All cable insertions to the indoor module are
made from above!
All cable insertions to the outdoor module are
made from below!
4: Control line, outdoor unit 0-10V (sheathed) /
sensor line (sheathed), e.g. 5 x 1.0 mm
5:
Sensor cable on external probe, e.g. 2 x 1.0 mm
6: Power supply, Smart-Control controller (I/O
module)
7: Potential-free electrical power supply company
signal for Smart-Control S16,
For an existing block the heat pump by the
utility (utility switching) must be used the control
contact S 16 of the Smart-Control.
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
e.g. 2 x 1.0 mm
NOTICE!
2
2
2
2
22
5.2 Overview of terminal assignment
B
C
A
E
D
2
34
1
5
Fig. 11: Terminal configuration HTS 110
A: Outdoor unit
B: Indoor unit
C: Customer-provided sub-distribution
D: External probe
E: Electrical heating coil
1: Power supply, indoor unit,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
Electrical connections between indoor and outdoor unit
Indoor unitOutdoor unit
TerminalDescriptionTerminal
1Power supply PE1
2Power supply L2
3Power supply N3
4Power supply, auxiliary heating L4
5Power supply, auxiliary heating N5
6Signal cable 0-10V6
7GND7
2
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
3: Terminals in indoor unit
4: Terminals on electrical heating coil
5: Power supply, control unit (I/O module)
400V / 3~ / 50Hz, e.g. 3 x 1.5 mm
2
2
8Response signal8
9Temperature sensor9
10GND10
23
REMKO HTS series
Electrical connections between distribution and indoor unit
DistributionIndoor unit
TerminalDescriptionTerminal
L1
L2L2
L3L3
NN
PePe
L
NN
PePe
L1
L2L2
L3L3
NN
PePe
Power supply, indoor unit 400V/ 3~/ 50Hz
Power supply, Smart-Control 230V/1~/ 50Hz
Power supply, Smart-Serv 400V/3~/ 50Hz 9kW
L1
L
L1
24
6 Electrical wiring HTS 130
B
C
4
6
A
2
D
5
3
7
1
6.1 Overview of electrical connection cables
Fig. 12: Overview of electrical connection HTS 130
A: Outdoor unit
B: Indoor unit
C: Customer-provided sub-distribution
D: External probe
1: Power supply, indoor unit, 400V / 3~ / 50Hz,
16A, e.g. 5 x 2.5 mm
2: Power supply, auxiliary heating, 400V /3~/ 50Hz,
16A, e.g. 5 x 2.5 mm
3: Power supply from indoor to outdoor unit / con-
densate drainage heating, 230V / 1~ / 50Hz,
10A, e.g. 5 x 1.5 mm
2
2
2
WARNING!
The configuration of the core cross sections can
be defined by an installation specialist!
only
All cable insertions to the indoor module are
made from above!
All cable insertions to the outdoor module are
made from below!
4: Control line, outdoor unit 0-10V (sheathed) /
sensor line (sheathed), e.g. 5 x 1.0 mm
5:
Sensor cable on external probe, e.g. 2 x 1.0 mm
6: Power supply, controller (I/O module)
230V / 1~ / 50Hz, e.g. 3 x 1.5 mm
7: Electrical power supply company signal for
Smart-Control S16, e.g. 2 x 1.0 mm
NOTICE!
For an existing block the heat pump by the
utility (utility switching) must be used the control
contact S 16 of the Smart-Control.
2
2
2
2
25
B
C
A
E
D
2
34
1
5
REMKO HTS series
6.2 Overview of terminal assignment
Fig. 13: Terminal configuration HTS 130
A: Outdoor unit
B: Indoor unit
C: Customer-provided sub-distribution
D: External probe
E: Electrical heating coil
1: Power supply, indoor unit,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
Electrical connections between indoor and outdoor unit
Indoor unitOutdoor unit
TerminalDescriptionTerminal
1Power supply PE1
2Power supply L2
3Power supply N3
4Power supply, auxiliary heating L4
5Power supply, auxiliary heating N5
6Signal cable 0-10V6
7GND7
2
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
3: Terminals in indoor unit
4: Terminals on electrical heating coil
5: Power supply, control unit (I/O module)
230V / 1~ / 50Hz, e.g. 3 x 1.5 mm
2
2
8Response signal8
9Temperature sensor9
10GND10
26
Electrical connections between distribution and indoor unit
DistributionIndoor unit
TerminalDescriptionTerminal
L1
L2L2
L3L3
NN
PePe
L
NN
PePe
L1
L2L2
L3L3
NN
PePe
Power supply, indoor unit 400V/ 3~/ 50Hz
Power supply, Smart-Control 230V/1~/ 50Hz
Power supply, Smart-Serv 400V/3~/ 50Hz 9kW
L1
L
L1
27
D
B
C
3
4
5
A
1
A
2
2
1
7
6
8
9
REMKO HTS series
7 Electrical wiring HTS 200
7.1 Overview of electrical connection cables
Fig. 14: Connection cables HTS 200
A1: Outdoor unit 1
A2: Outdoor unit 2
B:Indoor unit
C:Customer-provided sub-distribution
D:External probe
1:Power supply, indoor unit,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
2:Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
3:Power supply from IM to AM 1 /
condensate drain heating,
230V /1~/ 50Hz, 10A, e.g. 5 x 1.5 mm
2
4:Power supply from IM to AM 2 /
condensate drain heating,
WARNING!
The configuration of the core cross sections can
only be defined by an installation specialist!
230V /1~/ 50Hz, 10A, e.g. 5 x 1.5 mm
2
5:Control line, outdoor unit 1 (sheathed) / sensor
line (sheathed), e.g. 5 x 1.0 mm
2
6:Control line, outdoor unit 2, (sheathed),
e.g. 3 x 1.0 mm
2
2
7:Sensor cable on external probe, e.g. 2 x 1.0
2
mm
8:Power supply, Smart-Control controller (I/O
module)
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
2
2
9:Potential-free electrical power supply company
signal for Smart-Control S16, e.g. 2 x 1.0 mm
2
All cable insertions to the indoor module are
made from above!
All cable insertions to the outdoor module are
made from below!
NOTICE!
For an existing block the heat pump by the
utility (utility switching) must be used the control
contact S 16 of the Smart-Control.
28
7.2 Overview of terminal assignment
E
D
34
A1
A2
B
C
1
2
5
Fig. 15: Terminal configuration HTS 200
A1: Outdoor unit 1
A2: Outdoor unit 2
B:Indoor unit
C:Customer-provided sub-distribution
D:External probe
E:Electrical heating coil
1:Power supply, indoor unit,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
2:Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
3:Terminals in indoor unit
4:Terminals on electrical heating coil
5:Power supply, Smart-Control controller (I/O
module)
2
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
2
2
29
REMKO HTS series
Electrical connections between indoor and outdoor unit 1
Indoor unitOutdoor unit 1
TerminalDescriptionTerminal
1Power supply PE1
2Power supply L2
3Power supply N3
4Power supply, auxiliary heating L4
5Power supply, auxiliary heating N5
6Signal cable 0-10V6
7GND7
8Response signal8
9Temperature sensor9
10GND10
Electrical connections between indoor module and outdoor unit 2
Indoor unitOutdoor unit 2
TerminalDescriptionTerminal
11Power supply PE1
12Power supply L2
13Power supply N3
14Power supply, auxiliary heating L4
15Power supply, auxiliary heating N5
16Signal cable 0-10V6
17GND7
18Response signal8
19Not connected9
20Not connected10
30
Electrical connections between distribution and indoor unit
DistributionIndoor unit
TerminalDescriptionTerminal
L1
L2L2
L3L3
NN
PePe
L
NN
PePe
L1
L2L2
L3L3
NN
PePe
Power supply, indoor unit 400V/ 3~/ 50Hz
Power supply, Smart-Control 230V/1~/ 50Hz
Power supply, Smart-Serv 400V/3~/ 50Hz 9kW
L1
L
L1
31
D
B
C
3
4
5
A
1
A
2
2
1
7
6
8
9
REMKO HTS series
8 Electrical wiring HTS 260
8.1 Overview of electrical connection cables
Fig. 16: Connection cables HTS 260
A1: Outdoor unit 1
A2: Outdoor unit 2
B:Indoor unit
C:Customer-provided sub-distribution
D:External probe
1:Power supply, indoor unit,
400V/3~/50Hz, 20A, e.g. 5 x 2.5 mm
2
2:Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
3:Power supply from IM to AM 1 /
condensate drain heating,
230V /1~/ 50Hz, 10A, e.g. 5 x 1.5 mm
2
4:Power supply from IM to AM 2 /
condensate drain heating,
WARNING!
The configuration of the core cross sections can
only be defined by an installation specialist!
230V /1~/ 50Hz, 10A, e.g. 5 x 1.5 mm
2
5:Control line, outdoor unit 1 (sheathed) / sensor
line (sheathed), e.g. 5 x 1.0 mm
2
6:Control line, outdoor unit 2, (sheathed),
e.g. 3 x 1.0 mm
2
7:Sensor cable on external probe, e.g. 2 x 1.0
2
mm
2
8:Power supply, Smart-Control controller (I/O
module) 230V /1~/ 50Hz, e.g. 3 x 1.5 mm
2
9:Potential-free electrical power supply company
signal for Smart-Control S16,
e.g. 2 x 1.0 mm
2
All cable insertions to the indoor module are
made from above!
All cable insertions to the outdoor module are
made from below!
NOTICE!
For an existing block the heat pump by the
utility (utility switching) must be used the control
contact S 16 of the Smart-Control.
32
8.2 Overview of terminal assignment
E
D
34
A1
A2
B
C
1
2
5
Fig. 17: Terminal configuration HTS 260
A1: Outdoor unit 1
A2: Outdoor unit 2
B:Indoor unit
C:Customer-provided sub-distribution
D:External probe
E:Electrical heating coil
1:Power supply, indoor unit,
400V / 3~ / 50Hz, 20A, e.g. 5 x 2.5 mm
2:Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
3:Terminals in indoor unit
4:Terminals on electrical heating coil
5:Power supply, Smart-Control controller (I/O
module)
2
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
2
2
33
REMKO HTS series
Electrical connections between indoor and outdoor unit 1
Indoor unitOutdoor unit 1
TerminalDescriptionTerminal
1Power supply PE1
2Power supply L2
3Power supply N3
4Power supply, auxiliary heating L4
5Power supply, auxiliary heating N5
6Signal cable 0-10V6
7GND7
8Response signal8
9Temperature sensor9
10GND10
Electrical connections between indoor module and outdoor unit 2
Indoor unitOutdoor unit 2
TerminalDescriptionTerminal
11Power supply PE1
12Power supply L2
13Power supply N3
14Power supply, auxiliary heating L4
15Power supply, auxiliary heating N5
16Signal cable 0-10V6
17GND7
18Response signal8
19Not connected9
20Not connected10
34
Electrical connections between distribution and indoor unit