REMKO HTS Series, HTS 110, HTS 130, HTS 80, HTS 200 Instruction

...
Electrical wiring
REMKO HTS series
ArtStyle heat pumps Air/water system for heating and cooling
HTS 80, HTS 90, HTS 110, HTS 130, HTS 200, HTS 260
Instructions for the Technician
0160-2019-01 Edition 2, en_GB
Read the instructions prior to performing any task!
Read these operating instructions carefully before commis­sioning / using this device!
These instructions are an integral part of the system and must always be kept near or on the device.
Subject to modifications; No liability accepted for errors or mis­prints!

Table of contents

1 Safety and usage instructions............................................................................................................. 4
1.1 General safety notes....................................................................................................................... 4
1.2 Identification of notes...................................................................................................................... 4
1.3 Personnel qualifications.................................................................................................................. 4
1.4 Dangers of failure to observe the safety notes................................................................................ 4
1.5 Safety-conscious working............................................................................................................... 4
1.6 Safety notes for the operator........................................................................................................... 5
1.7 Safety notes for installation, maintenance and inspection.............................................................. 5
1.8 Unauthorised modification and changes......................................................................................... 5
1.9 Intended use................................................................................................................................... 5
1.10 Warranty........................................................................................................................................ 5
1.11 Transport and packaging............................................................................................................... 6
1.12 Environmental protection and recycling........................................................................................ 6
2 Electrical wiring - General.................................................................................................................... 7
2.1 System layout.................................................................................................................................. 7
2.2 General notes.................................................................................................................................. 9
2.3 Electrical connection - indoor module........................................................................................... 10
2.4 Electrical connection - outdoor module ........................................................................................ 11
2.5 Electrical configuration - I/O module............................................................................................. 13
2.6 Terminal block / key....................................................................................................................... 14
3 Electrical wiring HTS 80..................................................................................................................... 16
3.1 Overview of electrical connection cables...................................................................................... 16
3.2 Overview of terminal assignment.................................................................................................. 17
4 Electrical wiring HTS 90..................................................................................................................... 19
4.1 Overview of electrical connection cables...................................................................................... 19
4.2 Overview of terminal assignment.................................................................................................. 20
5 Electrical wiring HTS 110.................................................................................................................... 22
5.1 Overview of electrical connection cables...................................................................................... 22
5.2 Overview of terminal assignment.................................................................................................. 23
6 Electrical wiring HTS 130................................................................................................................... 25
6.1 Overview of electrical connection cables...................................................................................... 25
6.2 Overview of terminal assignment.................................................................................................. 26
7 Electrical wiring HTS 200................................................................................................................... 28
7.1 Overview of electrical connection cables...................................................................................... 28
7.2 Overview of terminal assignment.................................................................................................. 29
8 Electrical wiring HTS 260................................................................................................................... 32
8.1 Overview of electrical connection cables...................................................................................... 32
8.2 Overview of terminal assignment.................................................................................................. 33
9 Circuit diagrams.................................................................................................................................. 36
10
Index..................................................................................................................................................... 51
3
REMKO HTS series
1 Safety and
usage instructions

1.1 General safety notes

Carefully read the operating manual before com­missioning the units for the first time. It contains useful tips and notes such as hazard warnings to prevent personal injury and material damage. Failure to follow the directions in this manual not only presents a danger to people, the environment and the system itself, but will void any claims for
.
liability
Keep this operating manual and the refrigerant data sheet near to the units.

1.2 Identification of notes

This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation.The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by sym­bols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.
DANGER!
CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or mate­rial and environmental damage.
NOTICE!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.
This symbol highlights useful tips and recom­mendations as well as information for efficient and fault-free operation.

1.3 Personnel qualifications

Personnel responsible for commissioning, opera­tion, maintenance, inspection and installation must be able to demonstrate that they hold a qualifica­tion which proves their ability to undertake the work.
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.
DANGER!
This combination of symbol and signal word warns of a situation in which there is immediate danger cause serious injury.
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury
, which if not avoided may be fatal or
WARNING!
.
1.4

Dangers of failure to observe the safety notes

Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.
In particular, failure to observe the safety notes may pose the following risks:
n The failure of important unit functions. n The failure of prescribed methods of mainte-
nance and repair
n Danger to people on account of electrical and
mechanical effects.
.

1.5 Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.
4

1.6 Safety notes for the operator

The operational safety of the units and compo­nents is only assured providing they are used as intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified per­sonnel.
n Protective covers (grille) over moving parts
must not be removed from units that are in operation.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with certain unit parts or components
may lead to burns or injury
n The units and components must not be
exposed to any mechanical load, extreme levels of humidity or extreme temperature.
n Spaces in which refrigerant can leak sufficient
to load and vent. Otherwise there is danger of suffocation.
n All housing parts and device openings, e.g. air
inlets and outlets, must be free from foreign objects, fluids or gases.
n The units must be inspected by a service tech-
nician at least once annually. Visual inspec­tions and cleaning may be performed by the operator when the units are disconnected from the mains.
.

1.7 Safety notes for installation, maintenance and inspection

n The units and components must be kept at an
adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
n Safety devices must not be altered or
bypassed.
Unauthorised modification
1.8 and changes
Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufactured ensure safety use of other parts may invalidate liability for resulting consequences.
. The

1.9 Intended use

Depending on the model, the equipment and the additional fittings with which it is equipped is only intended to be used as an air-conditioner for the purpose of cooling or heating the air in an enclosed room.
Any different or additional use shall be classed as non-intended use. The manufacturer/supplier assumes no liability for damages arising from such use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
n Appropriate hazard prevention measures must
be taken to prevent risks to people when per­forming installation, repair cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
n Local regulations and laws such as Water
Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n Units may only be mounted at the points pro-
vided for this purpose at the factory. The units may only be secured or mounted on stable structures, walls or floors.
n Mobile units must be set up securely on suit-
able surfaces and in an upright position. Sta­tionary units must be permanently installed for operation.
n The units and components should not be oper-
ated in areas where there is a heightened risk of damage. Observe the minimum clearances.
, maintenance or
Under no circumstances should the threshold values specified in the technical data be exceeded.

1.10 Warranty

For warranty claims to be considered, it is essential that the ordering party or its representative com­plete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the "Gen­eral business and delivery conditions". Further­more, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.
5
REMKO HTS series

1.11 Transport and packaging

The devices are supplied in a sturdy shipping con-
. Please check the equipment immediately
tainer upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to children!

1.12 Environmental protection and recycling

Disposal of packaging
All products are packed for transport in environ­mentally friendly materials. Make a valuable contri­bution to reducing waste and sustaining raw mate­rials. Only dispose of packaging at approved collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufac­ture of the devices and components. Help protect the environment by ensuring that the devices or components (for example batteries) are not dis­posed in household waste, but only in accordance with local regulations and in an environmentally safe manner cling specialists or at collection points.
, e.g. using certified firms and recy-
6

2 Electrical wiring - General

A
B
D
C
1
2
3
4
5
6
8
7

2.1 System layout

Fig. 1: System layout HTS 80/90/110/130
A: Outdoor area B: Indoor area C: Outdoor unit D: Indoor unit 1: Fan / air outlet 2: Condensate drainage, outdoor unit
(must be designed to be frost proof!)
3: Lines between indoor and outdoor modules:
Control line outdoor module 0-10V (sheathed) / sensor cable (sheathed), e.g. 5 x 1,0 mm Power supply coming from the outdoor unit / Condensate drainage heating 5x1.5 mm2,
4:
Refrigerant lines 3/8" and 5/8“
2
5: Inlet 6: Return flow 7: Power supply line to indoor module:
HTS 90=230V/1~/ 50Hz,16A (e.g. 3x2.5 mm2) HTS 80/110/130=400V/3~/ 50Hz, 3x16A (e.g. 5x2.5 mm2) Control voltage regulation = 230V/1~/50Hz, 16A (e.g. 3x1.5 mm2)
8: Mains supply line, electrical auxiliary heater =
400V / 3~ / 50Hz, 16A (e.g. 5x2.5 mm2)
7
A
B
D
1
2
3
5
6
8
7
C
1
C
2
1
2
4 4
3
9
REMKO HTS series
Fig. 2: System layout HTS 200/260
A: Outdoor area B: Indoor area C1: Outdoor unit 1 C2: Outdoor unit 2 D: Indoor unit 1: Fan 2: Condensate drain, external module
(must contain anti-freeze!)
3: Lines between indoor and outdoor modules:
Control line outdoor module (sheathed) / sensor cable (sheathed), e.g. 5 x 1,0 mm Power supply from the outdoor unit / condensate drainage heating 5 x 1.5 mm
The indoor and outdoor modules have to be con­nected with refrigerant lines of dimensions (outer diameter) 3/8"(=9.52 mm) and 5/8"(=15.88 mm).
2
2
4:
Refrigerant lines 3/8" and 5/8“
5: Inlet 6: Return flow 7: Power supply, indoor unit =
400V / 3~ / 50Hz,16A (e.g. 5 x 2.5 mm2) Control voltage regulation = 230V / 1~ / 50Hz, 16A (e.g. 3 x 1.5 mm2)
8: Mains supply line, electrical auxiliary heater =
400V / 3~ / 50Hz, 16A (e.g. 5 x 2.5 mm2)
9: Refrigerant line 1/2" and 3/4"
WARNING!
All electric lines are in accordance VDE regula­tions to dimension and to lay
.
8

2.2 General notes

n It is necessary to lay multiple power supply
lines from the distribution system to the indoor unit, depending on the version. See "Electrical wiring" chapter
n The electrical connection between outdoor and
indoor units is made using a sheathed control line (see "Overview of electrical connecting lines" chapter).
n A connection schematic along with corre-
sponding circuit diagrams can be found in the "Connection diagram" chapter of this manual.
n If an auxiliary heater is required in the indoor
unit, another three-phase 400 V / 3~/50 Hz power supply shall be provided to the indoor unit for an auxiliary heater.
n Power to the smart control may not be discon-
nected by the power company when fitted with an off-period circuit (anti-freeze protection).
n The Smart-Control needs to know whether a
power-company release or off-period is in effect (contact S16). A potential-free switch must be installed by the customer for this pur­pose. (contact closed signifies release, while contact open signifies an off-period).
n Special rates for heat pumps may be offered
by the power-company (utility).
n Ask your local power company about the
details of any rates that might be available.
.
WARNING!
All cable sizes are to be selected according to VDE 0100. Special attention should be given to cable lengths, cable type and the kind of instal­lation. The information in the connection dia­gram and in the system overview are to be seen as an acceptable installation possibility only in a standard case!
NOTICE!
The electrical connection for the units must be made at a separate feedpoint with a residual current device in accordance with local regula­tions and should be laid out by an electrician.
Check all plugged and clamped terminals to verify that they are seated correctly and make permanent contact. Tighten as required.
DANGER!
All electrical installation work must be done by an electrician.
WARNING!
Always note the currently applicable VDE guidelines and the notes in TAB 2007. The size and type of the fuse are to be taken from the technical data.
9
REMKO HTS series
2.3 Electrical connection - indoor
module
The following instructions describe the electrical connection of the inner module.
1. Remove the cover from the indoor module by
pressing it upwards and pulling it forwards out of the rear groove.
2. Guide the supply cable to the indoor module
through the cable openings, and also route the control cable between indoor and outdoor modules and the cables for external devices and sensors into the indoor module. Note that the cable openings are located at the top.
3. Connect the mains power supply line and the
control line of the indoor module to the termi­nals (see chapter "Electrical wiring").
4. Connect all secondary consumers
(HGM,HGU, changeover valves etc.) to the I/O module.
NOTICE!
It is necessary to provide a separate RCD 100 mA, type B (universal current-sensitive) with a contact load of 40 A for the heat pump.
NOTICE!
Attach cables in accordance with the connec­tion schematic and/or the circuit diagram in the control box.
NOTICE!
Ensure correct polarity when connecting the electrical leads, especially the control cable.
The number of lines and the sensors is dependent on the configuration of the heating system and the components.
At the site, avoid adding cable inlets.
10
2
1
2

2.4 Electrical connection - outdoor module

o connect up the electrics, remove the whole
n T
basket.
Fig. 3: Remove the basket
Contact sensor
Contact sensors can be mounted on the pipes, to measure the heating-circuit temperatures, for example.
n The contact sensors are fastened to a pipe
with the accessories provided.
n Clean the appropriate point. Subsequently a
thermal compound (A) is applied and the sensor is fixed in position.
n Electrical protection for the system is imple-
mented in accordance with the information in the T
echnical Data. Observe the required con-
ductor cross-sections!
n All cables must be connected with the correct
polarity and strain relief.
n Follow the connection schematic and the circuit
Ä
diagrams ( on page 14).
n When connecting the control cable, make sure
that polarity is correct.
n If the outdoor module is installed on a roof, it
and the supporting structure must be earthed separately (connection to lightning conductors or foundation earth/ground feature).
Temperature sensors
n The number of sensors required can vary with
the type of system.
n Observe the pertinent notes for the sensor
position found in the hydraulic schematic.
n The standard scope of delivery includes the
outdoor sensors (S10), an immersion sensor (provided for use as a domestic hot water sensor - (S08).
n When connecting up a solar system, use a
-1000 sensor (S01) as a collector sensor
PT and a PT-1000 sensor (S02) as the lower storage tank sensor.
n All sensors are to be connected to the indoor
module switch cabinet in accordance with the terminal assignment diagram.
Chapter 2.6 ‘Terminal block / key’
Fig. 4: Securing the inductive sensor (figure sim­ilar)
If the sensor cables are too short, they can be extended up to a maximum of 100m with wire having a cross-section of 1.5 mm².
11
REMKO HTS series
Outdoor sensor
The connection of an outdoor sensor is always required for Smart Control.
n Mount the outdoor sensor pointing skyward, in
a north-easterly direction, about 2.5 metres above the ground. It may not be subjected to direct sunlight and is to be protected against excessive wind. Installation above windows or air ducts is to be avoided.
n In order to carry out the installation, remove the
cover and secure the sensor with the screw provided.
n A cable with wire cross-sections of min. 0.5
mm2 is recommended for connecting the
.
sensor
Fig. 5: Outdoor sensor (figure similar)
12

2.5 Electrical configuration - I/O module

4
5
5
4
8
3L
N
1
01
10
9 6
7
8
3L
3L
1L
1L
2L
2L
N
N
EP
EP
2
3
3
2
7
10
01
7
10
6
9
6
9
1X kcolb lanimreT
Power supply Internal module
5x2.5mm² Depending on device type 3 phase or 1 phase
Control line (0-10V) external module
Power supply internal to external module A e.g.3 x 1.5 mm2
EP-1
L-2
N-3
Sensor wire, exterior module
Switch output exterior module A (electrical heating)
EP
N-4
L-5
9
01
V01-0-6
DNG-7
ybdnats-8 ria .
assigned
41
51
51
41
81
3L
N
11
01
10
9 6
7
81
21
31
31
21
71
02
01
71
20
6
1
91
61
91
Control wire (0-10V) external module B 3x1.0 mm2
Power supply internal to external module B e.g.3x1.5 mm2
1 EP-1
N-21
L-31
Sensor wire exterior module B 2x1.0 mm2
EP
N-41
L-51
91
02
V01-0-61
DNG-71
ybdnats-81 ria .
Switch output exterior module B (electrical heating) 3 x 1.5 mm2
L N EP
`L N EP
`L N EP
N EP `L 01A
N
EP 1A `L 1
N EP
`L 21A
N EP
`L 31A
N EP `L 41A
N EP 10A
N EP 20A
N EP 30A
N EP 40A
N EP 02A 12A
N EP 22A 32A
N EP 42A 52A
Power
Actuator Outputs
Actuator Supply
Actuator Outputs
Actuator Outputs
S ensor Inputs
DNG V5+ 52S
DNG V5+ 62S
DNG V5+ 72S
DNG V5+ 82S
DNG V5+ 92S
Actuator S
ignal
DNG 04A
DNG 14A
DNG 24A
DNG 34A
DNG 44A
DNG 54A
DNG 64A
DNG SSn
KLC OM IM
KNX - TP
1T0 1T0
2T0 2T0
CR
2B 2A
2B 3A
1B V21+ DNG 1A
DNG R
14S 04S DNG V5+ 02S
34S 24S DNG V5+ 12S
54S 44S DNG V5+ 22S
74S 64S DNG V5+ 32S
94S 84S DNG V5+ 42S
DNG 10S
DNG 20S
DNG 30S
DNG 40S
DNG 50S
DNG 60S
DNG 70S
DNG 80S
stupnI rosneS
stupnI rosneS
stupnI rosneS
stupnI rosneS
DNG 90S
DNG 01S 1S DNG 1
DNG 21S
DNG 31S
DNG 41S
DNG 51S
DNG 61S
stuptuO
eerF laitneto
P
03A 03A
13A
23A
33A
43A
SD
Fuse
RJ 45
Power supply, primary pump - IM
Energy supplier contact
closed = release
Power supply I/O module
Potential-free
S0 PV power supply (min. 500 impulses/kWh)
S0 PV yield (min. 500 imp./kWh)
S0 household counter (min. 500 imp./kWh)
S0 WP current counter (min. 500 imp./kWh)
S29
S28
S26
S25
External probe
S10
S16
Changeover valve, drinking water
M
01A
Pump HK approx. 230V optional
A03
Pump circulation 230 V
A04
M
Closed
Open
Mixer HGM 1 (HK 1 floor)
A20/21
NOTE: without EVU connection, a bridge must be installed
Hot water tank
S08
Optional
egatlov sniaM
EP/N/~3/V004
Wk9 lioc gnitaeh cirtcelE
morf remotsuc eht yb dedivorp noitcennoc egatlov sniaM
!noitubirtsid-bus
1L
2L 3L N
eP
1 2 3 4 Pe
lioc gnitaeh eht no gulP
e.g. 5x 2.5 mm²
2.mix. Heating circuit RF
S14
S12
1.mix. Heating circuit inlet
S11
1. mix. Heating circuit RF
Storage tank, centre
S09
Acquisition of the stored energy
0-10V pump
HGM 2
A46
S06
2. mix. Heating
circuit inlet
S05
Drinking water circulation
S04
RL Solar WMZ
VL Solar WMZ
S03
S02
Storage tank, bottom
S01
Solar/solar collector
M
Changeover valve 2nd heat generator
Mixer HGM 2 (HK 2 floor)
M
Closed
Open
52/42A
0-10V pump A40 solar 0-10V pump A41 HGM 1 0-10V pump
A42 HGU
Pump 1 acc. to 230V optional
A02
Pump 2 acc. to 230V optional
A13
Pump Solar approx. 230V optional
A01
S
2
3
internally assigned
S15
internally assigned
S13
internally assigned
internally assigned
internally assigned
RC
internally assigned
BUS2
BM internally assigned
A32 release 2 WE
M
Closed
Open
M
Closed
Open
Changeover valve, cooling
A14
Cooling pump
A11
S27
Air volume flow warm water (pulse)
General alarm signal
A34
Use wire gauge corresponding with the connection cable supplied! Lay load lines separately to measuring lines!
13
REMKO HTS series

2.6 Terminal block / key

Terminal configuration
Designation Input Output Signal Description
PW X Power supply I/O 230V
PP X Power supply primary pump IM
S01 X Solar probe collector
S02 X Solar probe storage tank, bottom
S03 X Solar probe inlet HM solar
S04 X Solar probe RF HM solar
S05 X Circulation RF temp./impulse
S06 X 2nd mixed heating cycle inlet sensor
S07 X Not connected
S08 X Drinking water storage tank at top
S09 X Buffer storage tank, centre
S10 X External probe
S11 X 1st mixed heating circuit RF
S12 X 1st mixed heating circuit INL
S13 X Heat pump inlet
S14 X 2nd mixed heating circuit RF
S15 X Heat pump RF
S16 X
S20 X Not connected
S21 X Not connected
S22 X Not connected
S23 X Ultrasonic flow rate meter solar, impulse rate
S24 X Ultrasonic flow rate meter HP, impulse rate
S25 X HP electricity meter S0
EVU contact (NC) / dewpoint monitoring external (open = locked, closed = release)
S26 X Household electricity S0
S27 X Probe flow volume
S28 X PV yield electricity meter S0
S29 X PV in-feed electricity meter S0
A01 X Solar pump unregulated (230 V)
A02 X 1st mixed heating cycle pump (230 V) switched
A03 X Pump unmixed Heating circuit HK (230 V) switched
A04 X Circulation pump (230V) switched
A10 X Changeover valve, drinking water
14
Designation Input Output Signal Description
A11 X Changeover valve 2WE
A12 X Not connected
A13 X Pump 2nd mixed heating circuit (230 V) switched
A14 X Changeover valve / pump cooling (230 V) switched
A20 X 1st mixed heating circuit 'Open'
A21 X 1st mixed heating circuit 'Closed'
A22 X Bypass mixer 'Open'
A23 X Bypass mixer 'Closed'
A24 X 2nd mixed heating circuit 'Open'
A25 X 2nd mixed heating circuit 'Closed'
A30 X Not connected
A31 X Not connected
A32 X Enable 2nd WE booster heating or boiler
A33 X Not connected
A34 X General fault, external
A40 X Speed setting solar pump PWM
A41 X Speed specification, 1st mixed heating circ. (0-10V)
A42 X Speed specification unmixed heating circuit (0-10V)
A43 X PWM
A44 X Not connected
A45 X Not connected
A46 X Speed specification 2nd mixed heating circ. (0-10V)
MI
MO
CLK
nSS
GND
Not connected
OT 1 (2x) Not connected
OT 2 (2x) Not connected
B1, A1
+12 V
olt,
GND
B2 / A2 Bus 2 communication
B3 / A2 Not connected
R RC code resistance HTS 90/130/200/260
15
Operating module 1 - Bus 1 communication
B
C
4
6
A
2
D
5
3
7
1
REMKO HTS series

3 Electrical wiring HTS 80

3.1 Overview of electrical connection cables

Fig. 6: Overview of electrical connection HTS 80
A: Outdoor unit B: Indoor unit C: Customer-provided sub-distribution D: External probe 1: Power supply, indoor unit, 400V / 3~ / 50Hz,
16A, e.g. 5 x 1.5 mm
2: Power supply, auxiliary heating, 400V /3~/ 50Hz,
16A, e.g. 5 x 2.5 mm
3: Power supply from indoor to outdoor unit / con-
densate drainage heating, 230V / 1~ / 50Hz, 10A, e.g. 5 x 1.5 mm
WARNING!
2
2
2
The configuration of the core cross sections can
be defined by an installation specialist!
only
All cable insertions to the indoor module are made from above!
All cable insertions to the outdoor module are made from below!
4: Control line, outdoor unit 0-10V (sheathed) /
sensor line (sheathed), e.g. 5 x 1.0 mm
5:
Sensor cable on external probe, e.g. 2 x 1.0 mm
6: Power supply, controller (Smart-Control)
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
7: Potential-free electrical power supply company
signal for Smart-Control S16,
NOTICE!
For an existing block the heat pump by the utility (utility switching) must be used the control contact S 16 of the Smart-Control.
e.g. 2 x 1.0 mm
2
2
2
2
16

3.2 Overview of terminal assignment

B
C
A
E
D
2
3 4
1
5
Fig. 7: Terminal configuration HTS 80
A: Outdoor unit B: Indoor unit C: Customer-provided sub-distribution D: External probe E: Electrical heating coil 1: Power supply, indoor unit,
400V / 3~ / 50Hz, 16A, e.g. 3 x 2.5 mm
Electrical connections between indoor and outdoor unit
Indoor unit Outdoor unit
Terminal Description Terminal
1 Power supply PE 1
2 Power supply L 2
3 Power supply N 3
4 Power supply, auxiliary heating L 4
5 Power supply, auxiliary heating N 5
6 Signal cable 0-10V 6
7 GND 7
2
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 1.5 mm 3: Terminals in indoor unit 4: Terminals on electrical heating coil 5: Power supply, Smart-Control controller (I/O
module)
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
2
2
8 Response signal 8
9 Temperature sensor 9
10 GND 10
17
REMKO HTS series
Electrical connections between distribution and indoor unit
Distribution Indoor unit
Terminal Description Terminal
L1
L2 L2
L3 L3
N N
Pe Pe
L
N N
Pe Pe
L1
L2 L2
L3 L3
N N
Pe Pe
Power supply, indoor unit 400V/ 3~/ 50Hz
Power supply, Smart-Control 230V/1~/ 50Hz
Power supply, Smart-Serv 400V/3~/ 50Hz 9kW
L1
L
L1
18

4 Electrical wiring HTS 90

B
C
4
6
A
2
D
5
3
7
1

4.1 Overview of electrical connection cables

Fig. 8: Overview of electrical connection HTS 90
A: Outdoor unit B: Indoor unit C: Customer-provided sub-distribution D: External probe 1: Power supply, indoor unit, 230V / 1~ / 50Hz,
16A, e.g. 3 x 2.5 mm
2: Power supply, auxiliary heating, 400V /3~/ 50Hz,
16A, e.g. 5 x 2.5 mm
3: Power supply from indoor to outdoor unit / con-
densate drainage heating, 230V / 1~ / 50Hz, 10A, e.g. 5 x 1.5 mm
2
2
2
WARNING!
The configuration of the core cross sections can
be defined by an installation specialist!
only
All cable insertions to the indoor module are made from above!
All cable insertions to the outdoor module are made from below!
4: Control line, outdoor unit 0-10V (sheathed) /
sensor line (sheathed), e.g. 5 x 1.0 mm 5:
Sensor cable on external probe, e.g. 2 x 1.0 mm 6: Power supply, Smart-Control controller (I/O
module) 7: Potential-free electrical power supply company
signal for Smart-Control S16,
For an existing block the heat pump by the utility (utility switching) must be used the control contact S 16 of the Smart-Control.
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
e.g. 2 x 1.0 mm
NOTICE!
2
2
2
2
19
B
C
A
E
D
2
3 4
1
5
REMKO HTS series

4.2 Overview of terminal assignment

Fig. 9: Terminal configuration HTS 90
A: Outdoor unit B: Indoor unit C: Customer-provided sub-distribution D: External probe E: Electrical heating coil 1: Power supply, indoor unit,
230V / 1~ / 50Hz, 16A, e.g. 3 x 2.5 mm
Electrical connections between indoor and outdoor unit
Indoor unit Outdoor unit
Terminal Description Terminal
1 Power supply PE 1
2 Power supply L 2
3 Power supply N 3
4 Power supply, auxiliary heating L 4
5 Power supply, auxiliary heating N 5
6 Signal cable 0-10V 6
7 GND 7
2
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm 3: Terminals in indoor unit 4: Terminals on electrical heating coil 5: Power supply, controller (I/O module)
230V / 1~ / 50Hz, e.g. 3 x 1.5 mm
2
2
8 Response signal 8
9 Temperature sensor 9
10 GND 10
20
Electrical connections between distribution and indoor unit
Distribution Indoor unit
Terminal Description Terminal
L1
N N
Pe Pe
L
N N
Pe Pe
L1
L2 L2
L3 L3
N N
Pe Pe
Power supply, indoor unit 230V/ 1~/ 50Hz
Power supply, Smart-Control 230V/1~/ 50Hz
Power supply, Smart-Serv 400V/3~/ 50Hz 9kW
L1
L
L1
21
B
C
4
6
A
2
D
5
3
7
1
REMKO HTS series

5 Electrical wiring HTS 110

5.1 Overview of electrical connection cables

Fig. 10: Overview of electrical connection HTS 110
A: Outdoor unit B: Indoor unit C: Customer-provided sub-distribution D: External probe 1: Power supply, indoor unit, 400V / 3~ / 50Hz,
16A, e.g. 5 x 2.5 mm
2: Power supply, auxiliary heating, 400V /3~/ 50Hz,
16A, e.g. 5 x 2.5 mm
3: Power supply from indoor to outdoor unit / con-
densate drainage heating, 230V / 1~ / 50Hz, 10A, e.g. 5 x 1.5 mm
WARNING!
2
2
2
The configuration of the core cross sections can
be defined by an installation specialist!
only
All cable insertions to the indoor module are made from above!
All cable insertions to the outdoor module are made from below!
4: Control line, outdoor unit 0-10V (sheathed) /
sensor line (sheathed), e.g. 5 x 1.0 mm 5:
Sensor cable on external probe, e.g. 2 x 1.0 mm 6: Power supply, Smart-Control controller (I/O
module) 7: Potential-free electrical power supply company
signal for Smart-Control S16,
For an existing block the heat pump by the utility (utility switching) must be used the control contact S 16 of the Smart-Control.
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
e.g. 2 x 1.0 mm
NOTICE!
2
2
2
2
22

5.2 Overview of terminal assignment

B
C
A
E
D
2
3 4
1
5
Fig. 11: Terminal configuration HTS 110
A: Outdoor unit B: Indoor unit C: Customer-provided sub-distribution D: External probe E: Electrical heating coil 1: Power supply, indoor unit,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
Electrical connections between indoor and outdoor unit
Indoor unit Outdoor unit
Terminal Description Terminal
1 Power supply PE 1
2 Power supply L 2
3 Power supply N 3
4 Power supply, auxiliary heating L 4
5 Power supply, auxiliary heating N 5
6 Signal cable 0-10V 6
7 GND 7
2
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm 3: Terminals in indoor unit 4: Terminals on electrical heating coil 5: Power supply, control unit (I/O module)
400V / 3~ / 50Hz, e.g. 3 x 1.5 mm
2
2
8 Response signal 8
9 Temperature sensor 9
10 GND 10
23
REMKO HTS series
Electrical connections between distribution and indoor unit
Distribution Indoor unit
Terminal Description Terminal
L1
L2 L2
L3 L3
N N
Pe Pe
L
N N
Pe Pe
L1
L2 L2
L3 L3
N N
Pe Pe
Power supply, indoor unit 400V/ 3~/ 50Hz
Power supply, Smart-Control 230V/1~/ 50Hz
Power supply, Smart-Serv 400V/3~/ 50Hz 9kW
L1
L
L1
24

6 Electrical wiring HTS 130

B
C
4
6
A
2
D
5
3
7
1

6.1 Overview of electrical connection cables

Fig. 12: Overview of electrical connection HTS 130
A: Outdoor unit B: Indoor unit C: Customer-provided sub-distribution D: External probe 1: Power supply, indoor unit, 400V / 3~ / 50Hz,
16A, e.g. 5 x 2.5 mm
2: Power supply, auxiliary heating, 400V /3~/ 50Hz,
16A, e.g. 5 x 2.5 mm
3: Power supply from indoor to outdoor unit / con-
densate drainage heating, 230V / 1~ / 50Hz, 10A, e.g. 5 x 1.5 mm
2
2
2
WARNING!
The configuration of the core cross sections can
be defined by an installation specialist!
only
All cable insertions to the indoor module are made from above!
All cable insertions to the outdoor module are made from below!
4: Control line, outdoor unit 0-10V (sheathed) /
sensor line (sheathed), e.g. 5 x 1.0 mm 5:
Sensor cable on external probe, e.g. 2 x 1.0 mm 6: Power supply, controller (I/O module)
230V / 1~ / 50Hz, e.g. 3 x 1.5 mm 7: Electrical power supply company signal for
Smart-Control S16, e.g. 2 x 1.0 mm
NOTICE!
For an existing block the heat pump by the utility (utility switching) must be used the control contact S 16 of the Smart-Control.
2
2
2
2
25
B
C
A
E
D
2
3 4
1
5
REMKO HTS series

6.2 Overview of terminal assignment

Fig. 13: Terminal configuration HTS 130
A: Outdoor unit B: Indoor unit C: Customer-provided sub-distribution D: External probe E: Electrical heating coil 1: Power supply, indoor unit,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
Electrical connections between indoor and outdoor unit
Indoor unit Outdoor unit
Terminal Description Terminal
1 Power supply PE 1
2 Power supply L 2
3 Power supply N 3
4 Power supply, auxiliary heating L 4
5 Power supply, auxiliary heating N 5
6 Signal cable 0-10V 6
7 GND 7
2
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm 3: Terminals in indoor unit 4: Terminals on electrical heating coil 5: Power supply, control unit (I/O module)
230V / 1~ / 50Hz, e.g. 3 x 1.5 mm
2
2
8 Response signal 8
9 Temperature sensor 9
10 GND 10
26
Electrical connections between distribution and indoor unit
Distribution Indoor unit
Terminal Description Terminal
L1
L2 L2
L3 L3
N N
Pe Pe
L
N N
Pe Pe
L1
L2 L2
L3 L3
N N
Pe Pe
Power supply, indoor unit 400V/ 3~/ 50Hz
Power supply, Smart-Control 230V/1~/ 50Hz
Power supply, Smart-Serv 400V/3~/ 50Hz 9kW
L1
L
L1
27
D
B
C
3
4
5
A
1
A
2
2
1
7
6
8
9
REMKO HTS series

7 Electrical wiring HTS 200

7.1 Overview of electrical connection cables

Fig. 14: Connection cables HTS 200
A1: Outdoor unit 1 A2: Outdoor unit 2 B: Indoor unit C: Customer-provided sub-distribution D: External probe 1: Power supply, indoor unit,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
3: Power supply from IM to AM 1 /
condensate drain heating, 230V /1~/ 50Hz, 10A, e.g. 5 x 1.5 mm
2
4: Power supply from IM to AM 2 /
condensate drain heating,
WARNING!
The configuration of the core cross sections can only be defined by an installation specialist!
230V /1~/ 50Hz, 10A, e.g. 5 x 1.5 mm
2
5: Control line, outdoor unit 1 (sheathed) / sensor
line (sheathed), e.g. 5 x 1.0 mm
2
6: Control line, outdoor unit 2, (sheathed),
e.g. 3 x 1.0 mm
2
2
7: Sensor cable on external probe, e.g. 2 x 1.0
2
mm
8: Power supply, Smart-Control controller (I/O
module)
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
2
2
9: Potential-free electrical power supply company
signal for Smart-Control S16, e.g. 2 x 1.0 mm
2
All cable insertions to the indoor module are made from above!
All cable insertions to the outdoor module are made from below!
NOTICE!
For an existing block the heat pump by the utility (utility switching) must be used the control contact S 16 of the Smart-Control.
28

7.2 Overview of terminal assignment

E
D
3 4
A1
A2
B
C
1
2
5
Fig. 15: Terminal configuration HTS 200
A1: Outdoor unit 1 A2: Outdoor unit 2 B: Indoor unit C: Customer-provided sub-distribution D: External probe E: Electrical heating coil 1: Power supply, indoor unit,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm 3: Terminals in indoor unit 4: Terminals on electrical heating coil 5: Power supply, Smart-Control controller (I/O
module)
2
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
2
2
29
REMKO HTS series
Electrical connections between indoor and outdoor unit 1
Indoor unit Outdoor unit 1
Terminal Description Terminal
1 Power supply PE 1
2 Power supply L 2
3 Power supply N 3
4 Power supply, auxiliary heating L 4
5 Power supply, auxiliary heating N 5
6 Signal cable 0-10V 6
7 GND 7
8 Response signal 8
9 Temperature sensor 9
10 GND 10
Electrical connections between indoor module and outdoor unit 2
Indoor unit Outdoor unit 2
Terminal Description Terminal
11 Power supply PE 1
12 Power supply L 2
13 Power supply N 3
14 Power supply, auxiliary heating L 4
15 Power supply, auxiliary heating N 5
16 Signal cable 0-10V 6
17 GND 7
18 Response signal 8
19 Not connected 9
20 Not connected 10
30
Electrical connections between distribution and indoor unit
Distribution Indoor unit
Terminal Description Terminal
L1
L2 L2
L3 L3
N N
Pe Pe
L
N N
Pe Pe
L1
L2 L2
L3 L3
N N
Pe Pe
Power supply, indoor unit 400V/ 3~/ 50Hz
Power supply, Smart-Control 230V/1~/ 50Hz
Power supply, Smart-Serv 400V/3~/ 50Hz 9kW
L1
L
L1
31
D
B
C
3
4
5
A
1
A
2
2
1
7
6
8
9
REMKO HTS series

8 Electrical wiring HTS 260

8.1 Overview of electrical connection cables

Fig. 16: Connection cables HTS 260
A1: Outdoor unit 1 A2: Outdoor unit 2 B: Indoor unit C: Customer-provided sub-distribution D: External probe 1: Power supply, indoor unit,
400V/3~/50Hz, 20A, e.g. 5 x 2.5 mm
2
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
3: Power supply from IM to AM 1 /
condensate drain heating, 230V /1~/ 50Hz, 10A, e.g. 5 x 1.5 mm
2
4: Power supply from IM to AM 2 /
condensate drain heating,
WARNING!
The configuration of the core cross sections can only be defined by an installation specialist!
230V /1~/ 50Hz, 10A, e.g. 5 x 1.5 mm
2
5: Control line, outdoor unit 1 (sheathed) / sensor
line (sheathed), e.g. 5 x 1.0 mm
2
6: Control line, outdoor unit 2, (sheathed),
e.g. 3 x 1.0 mm
2
7: Sensor cable on external probe, e.g. 2 x 1.0
2
mm
2
8: Power supply, Smart-Control controller (I/O
module) 230V /1~/ 50Hz, e.g. 3 x 1.5 mm
2
9: Potential-free electrical power supply company
signal for Smart-Control S16,
e.g. 2 x 1.0 mm
2
All cable insertions to the indoor module are made from above!
All cable insertions to the outdoor module are made from below!
NOTICE!
For an existing block the heat pump by the utility (utility switching) must be used the control contact S 16 of the Smart-Control.
32

8.2 Overview of terminal assignment

E
D
3 4
A1
A2
B
C
1
2
5
Fig. 17: Terminal configuration HTS 260
A1: Outdoor unit 1 A2: Outdoor unit 2 B: Indoor unit C: Customer-provided sub-distribution D: External probe E: Electrical heating coil 1: Power supply, indoor unit,
400V / 3~ / 50Hz, 20A, e.g. 5 x 2.5 mm
2: Power supply, auxiliary heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm 3: Terminals in indoor unit 4: Terminals on electrical heating coil 5: Power supply, Smart-Control controller (I/O
module)
2
230V /1~/ 50Hz, e.g. 3 x 1.5 mm
2
2
33
REMKO HTS series
Electrical connections between indoor and outdoor unit 1
Indoor unit Outdoor unit 1
Terminal Description Terminal
1 Power supply PE 1
2 Power supply L 2
3 Power supply N 3
4 Power supply, auxiliary heating L 4
5 Power supply, auxiliary heating N 5
6 Signal cable 0-10V 6
7 GND 7
8 Response signal 8
9 Temperature sensor 9
10 GND 10
Electrical connections between indoor module and outdoor unit 2
Indoor unit Outdoor unit 2
Terminal Description Terminal
11 Power supply PE 1
12 Power supply L 2
13 Power supply N 3
14 Power supply, auxiliary heating L 4
15 Power supply, auxiliary heating N 5
16 Signal cable 0-10V 6
17 GND 7
18 Response signal 8
19 Not connected 9
20 Not connected 10
34
Electrical connections between distribution and indoor unit
Distribution Indoor unit
Terminal Description Terminal
L1
L2 L2
L3 L3
N N
Pe Pe
L
N N
Pe Pe
L1
L2 L2
L3 L3
N N
Pe Pe
Power supply, indoor unit 400V/ 3~/ 50Hz
Power supply, Smart-Control 230V/1~/ 50Hz
Power supply, Smart-Serv 400V/3~/ 50Hz 9kW
L1
L
L1
35
L3
-X1
Spannungsv. 400V
Bauseits
L2 L1 N PE
PE
-K1
Freigabe Verdichter
-> µPC - NO1
A1
-K1
Freigabe Verdichter
-> µPC - G
M
3
T3
T2
T1 PE
-K1
Spannungsv. 400V
Verdichter
1
-X2
Aussenmodul 1
-> ODU
L
-X2.1
Spannungsv. 230V
-> SMT I/O - Pout1
2
X1.1 X1.2 X1.3 X1.4 X1.5 K1
PR1
X2.1
X2.2
X2.3
X2.4
L3
L2
L1
N
PE
A2
14/NO
6T3
4T2
2T1
1
23
45
6
78
9
10
1412
11
L3
L2
L1
N
PE
A1
13/NO
5L3
3L2
1L1
2 3
4 5
6
7 8
9
10
L2
L1 L3
-X
Klemmblock
Inenmodul
N
3 4
NO5
-X2.2
Kondensatheizung
-> µPC - NO5
5 6 7 8 9
B3
-X2.4
Aussentemperatur
-> µPC - B3
10
DI2
-PR1
Phasenüberwachung
-> µPC - DI2
Y3
-X2.3
Steuersignal Lüfter
-> µPC - Y3
GND
DI1
-X2.3
Störmeldung Lüfter
-> µPC - DI1
GND
1
-ODU
Aussenmodul
-> X2
2345678910
123456789
10
-ODU
Klemmblock
Aussenmodul
1
2
-B3
NTC
Aussentemperatur
N
L
-HD
Heizwiderstand
Kondensatheizung
M
L
N PE
E1 GND 11 14
-FAN
EC Motor 230V
Verdampferlüfter
0 1 2 3 4 5 6 7 8 9 10 11
1/6
HTS 80-110
0
1 2 3 4 5 6 7 8 9 10 11
1/8/2019
Projekt Titel:
Enable compressor
Power supply 400V
Enable compressor
Power supply 400V
Outdoor unit 1
Phase monitoring
NTC
Heating resistor
EC Motor 230V
Terminal block
Outdoor unit
Terminal block
Project title: HTS 80-110
-> μPC - G
Provided by the customer
-> μPC - NO1
Compressor
-> ODU
-> μPC / DI2
Outside temperature
Condensate heating
Evaporator fan
Indoor unit
Outdoor unit
Power supply 230V
Condensate heating
Outside temperature
Fan control signal
Fan alarm code
-> SMT I/O - Pout1
-> μPC - NO5
REMKO HTS series

9 Circuit diagrams

36
G0
-Pout1
Spannungsversorgung 230V
-> µPC - J1
G
PE
PE
-Pin
Spannungsversorgung 230V
SMT I/O - Bauseits
N L
S0
Imp/kWh
+
-
-S25
Stromzähler S0
Wärmepumpe
S0
Imp/kWh
+
-
-S26
Stromzähler S0
Haushalt
1
M
PE N L
-Pout1
Versorgung 230V
Interne Pumpe A43
13 1
4
-S27
Volumenstrom, Imp.
Warmwasser
M
N SP DP
-A10
Umschaltventil 230V
Warmwasserbereitung
S0
Imp/kWh
+
-
-S28
Stromzähler S0
PV Ertrag
S0
Imp/kWh
+
-
-S29
Stromzähler S0
PV Einspeisung
M
N SP DP
-A11
Umschaltventil 230V
2. Wärmeerzeuger
U
t
­+
-A40
Signal PWM
Solarkreis
U
t
­+
-A41
Signal 0-10V / PWM
1. gem. Kreis
U
t
­+
-A42
Signal 0-10V / PWM
ungem. Kreis
1
M
PE N L
-A13
Pumpe 230V
2. gem. Kreis
U
t
­+
-A43
Signal PWM
Interne Pumpe
Power Actuator Output Actuator Output Actuator OutputActuator Supply
Sensor Inputs Actuator Signal Actuator Signal SPI OT Interfaces Bus Interfaces Rc
Systemregler SMT I/O
PE N L
PE N L
PE N L
PE N A10 L
PE N A11 L
PE N A12 L
PE N A13 L
PE N A14 L
PE N A01
PE N A02
PE N A03
PE N A04
PE N A20 A21
PE N A22 A23
PE N A24 A25
S25 +5V GND
S26 +5V GND
S27 +5V GND
S28 +5V GND
S29 +5V GND
GND A40
GND A41
GND A42
GND A43
GND A44
GND A45
GND A46
MI MO CLK nSS GND
OT1 OT1
OT2 OT2
+12V B1 A1 GND
B2 A2
B3 A3
R GND
-SMT_I/O_UNTEN
Systemregler
M
N SP DP
-A14
Umschaltventil 230V
Separater Kühlkreis
1
M
PE N L
-A01
Pumpe 230V
Solarkreis
U
t
­+
-A46
Signal 0-10V / PWM
2. gem. Kreis
1
M
PE N L
-A02
Pumpe 230V
1. gem. Kreis
1
M
PE N L
-A03
Pumpe 230V
ungem. Kreis
1
M
PE N L
-A04
Pumpe 230V
Trinkwasser Zirkulation
+12V
-12V
Spannungsvers.
-> SMT Touch
GND
M
N Auf Zu
-A20/A21
Mischventil 230V
1. gem. Kreis
GND
-B2/A2
Kommunikation
-> µPC - J6
- +
M
N Auf Zu
-A22/A23
Ventil 230V
Bypass
B
-B3/A3
Kommunikation
-> Raumsensor - B/A
A
1
2
-RC
Kodierwiderstand
Geräteabhängig
M
N Auf Zu
-A24/A25
Mischventil 230V
2. gem. Kreis
Kodierwiderstände:
HTS 80 -> 10 Ohm
HTS 110 -> 20 Ohm
HTS 80 -> 10 Ohm
HTS 110 -> 20 Ohm
0 1 2 3 4 5 6 7 8 9 10 11
2/6
HTS 80-110
0
1 2 3 4 5 6 7 8 9 10 11
1/8/2019
Projekt Titel:
Project title: HTS 80-110
Coding resistors:
System controller SMT I/O
Sensor Inputs Actuator Signal Actuator Signal OT Interfaces Bus Interfaces
Actuator OutputActuator OutputActuator OutputActuator SupplyPower
SPI
Electricity meter S0
Power supply 230V
Changeover valve 230V
Changeover valve 230V
Pump 230V
Changeover valve 230V
Pump 230V
System controller
Pump 230V
Pump 230V
Pump 230V
Mixed valve 230V
Valve 230V
Mixed valve 230V
Power supply 230V
Power supply 230V
Electricity meter S0
Medium ow rate, Imp.
Electricity meter S0
Electricity meter S0
Signal PWM
Signal 0-10V / PWM
Signal 0-10V / PWM
Signal PWM
Signal 0-10V / PWM
Power supply
Communication
Communication
Coding resistor
Heat pump
Internal pump A43
Hot water preparation
2. Heat generator
2nd mixed circuit
Separate cooling circuit
Solar circuit
1st mixed circuit
Unmixed circuit
Drinking water circulation
GND 1st mixed circuit
Bypass
2nd mixed circuit
SMT I/O - Provided by the
customer
Household
Hot water
PV yield
PV feed-in
Solar circuit
1st mixed circuit
Unmixed Circuit 1
Internal pump
2nd mixed circuit
-> SMT Touch
-> μPC - J6
-> Room sensor - B/A
Device-dependent
-SMT_I/O_BOTTOM
Open
Open
Open
Close
Close
Close
37
13 1
4
-S23
Volumenstrom, Imp.
Solarkreis
3 1 4 2 5
-S24/S15
PT1000 / Vol. Imp.
RL / Vol. Wärmep.
1
2
-S01
PT1000
Kollektorfühler
1
2
-S02
PT1000
Speicherfühler, Solar
RJ45
-RJ45
Kommunikation
-> SMT Touch
1
2
-S03
PT1000
Vorlauf, Solar
1
2
-S04
PT1000
Rücklauf, Solar
1
2
-S05
PT1000 / Impuls
Zirkulation
1
2
-S06
PT1000
Vorlauf, 2. gem. Kreis
1
2
-S08
PT1000
Warmwasserspeicher
G0
-A32
Spannung 230V
-> µPC - G0
1
2
-S09
PT1000
Pufferspeicher
1
2
-S10
PT1000
Außentemperatur
1
2
-S11
PT1000
Rücklauf, 1. gem. Kreis
1
2
-S12
PT1000
Vorlauf, 1. gem. Kreis
1
2
-S13
PT1000
Vorlauf, Wärmepumpe
Potential Free Outputs
Sensor InputsSensor InputsSensor InputsSensor Inputs
Systemregler SMT I/O
In A30
In A31
In A32
In A33
In A34
S20 +5V GND S40 S41
S21 +5V GND S42 S43
S22 +5V GND S44 S45
S23 +5V GND S46 S47
S24 +5V GND S48 S49
S01 GND
S02 GND
RJ45
S03 GND
S04 GND
S05 GND
S06 GND
S07 GND
S08 GND
S09 GND
S10 GND
S11 GND
S12 GND
S13 GND
S14 GND
S15 GND
S16 GND
-SMT_I/O_OBEN
Systemregler
L
-A32
Freigabe E-Heizer
-> EHZ - ST2
1
2
-S14
PT1000
Rücklauf, 2. gem. Kreis
In
-A34
Potentialfreier Kontakt
Sammelstörmeldung
A34
S16
-S16
Brücke / Öffner-K.
EVU Sperre
GND
Bei Verwendung einer EVU Sperre darf nur der Verdichter Spannungslos geschaltet werden!Verdichter Spannungslos geschaltet werden!
0 1 2 3 4 5 6 7 8 9 10 11
3/6
HTS 80-110
0
1 2 3 4 5 6 7 8 9 10 11
1/8/2019
Projekt Titel:
Project title: HTS 80-110
System controller SMT I/O
Medium ow rate, Imp.
PT1000 / Vol. Imp.
Communication
PT1000 / Impulse
Potential-free contact
Enable E-heater
Solar circuit
RF / Vol. Heat Pump
-> SMT Touch
Circulation
General alarm signal
Inlet, 2nd mixed circuit
Hot water storage tank
Bu󰀨er tank
Outside temperature
Return ow, 1st mixed circuit
Inlet, 1st mixed circuit
Inlet, heat pump
Return ow, 2nd mixed circuit
Inlet, Solar
Return ow, Solar
Collector probe
Storage tank probe, Solar
Sensor Inputs Sensor Inputs Sensor Inputs Sensor Inputs
Potential-Free Outputs
Jumper / NC terminal
System controller
Voltage 230V
Power utility block
When using a power utility block, only power to compressor may be switched!
-SMT_I/O_TOP
REMKO HTS series
38
N
-J1
Spannungsv. 230V
-> SMT I/O - Pout1
L
GND
-DI2
Phasenfolge
-> Klemmblock PR1
DI2
1
2
-B1
NTC
Wasser Eintritt
1
2
-B2
NTC
Wasser Austritt
B3
-B3
Aussentemperatur
-> Klemmblock X2.4
1
2
-B4
NTC
Sauggas
1
2
-B5
NTC-HT
Heißgas
S
J11
-J11
Steuersignal
Expansionsventil
1 3
2
-B6
RAZ 0-5V
Niederdruck
1 3
2
-B7
RAZ 0-5V
Hochdruck
GND
-J6
Kommunikation
-> SMT I/O - B2/A2
G
-NO1
Freigabe Verdichter
-> Klemmblock K1
A2
NO1
B2 DI1
-DI1
Störmeldung Lüfter
-> Klemmblock X2.3
J7
J8
J9
J10
J11
J12 J13 J14
J1 J2 J3
J6
J4 J5
Kätekreis Regler µPC
1 2 3 4 1 23 456
pLAN
R-/T-
R+/T+
GND
Vout
R-/T-
R+/T+
GND
C1 NO1 NO2 NO3
C2 NO4 NO5 NO6
NO7 C3 NC7
G G0
+Vdc GND +5VR
B1
B2
B3
B4
B5
B6
B7
GND +Vdc
GND +
-
DI1
DI2
DI3
DI4
DI5
DI6
DI7 DIC1
GND Y1 Y2 Y3
-µPC
Kältekreis Regler
1 2
-NO2
Ausgang 230V
4 - Wege Ventil
P
1
2
-DI3
Öffner-Kontakt
Hochdruckschalter
NO5
-NO5
Kondensatheizung
-> Klemmblock X2.2
GND
-Y3
Lüfter Steuersignal
-> Klemmblock X2.3
Y3
6
0 1 2 3 4 5 6 7 8 9 10 11
4/6
HTS 80-110
0
1 2 3 4 5 6 7 8 9 10 11
1/8/2019
Projekt Titel:
Project title: HTS 80-110
Cold circuit controller μPC
Power supply 230V
Control signal
Enable compressor
Condensate heating
Output 230V
Phase sequence
Outside temperature
Communication
NC contact
Fan control signal
Fan alarm code
-> SMT I/O - Pout1
Expansion valve
-> Terminal block K1
-> Terminal block X2.2
4-way valve
-> T erminal block PR1
-> T erminal block X2.4
-> SMT I/O - B2/A2
High pressure switch
-> T erminal block X2.3
-> Terminal block X2.3
Suction gas
Heat gas
Low pressure
High pressure
Water inlet
Water outlet
Cooling cycle controller
39
USB
-USB
Kommunikation
-> LAN - / WLAN Adapter
Smart-Control Touch
USB
RJ45
GND +12V
-SMT_Touch
Bedienteil
RJ45
-RJ45
Kommunikation
-> SMT I/O - RJ45
GND
-12V
Spannungsvers.
-> SMT I/O - 12V
+12V
Raumsensor
A V+ V­B
-RS1
Raumsensor
ungem. Kreis
Raumsensor
A V+ V­B
-RS2
Raumsensor
1. gem. Kreis
Raumsensor
A V+ V­B
-RS3
Raumsensor
2. gem. Kreis
B3
-B/A
Kommunikation
-> SMT I/O - B3/A3
A3
Jeder Raumsensor benötigt eine eindeutige Geräteadresse!
-> Siehe Bedienunsanleitung des Raumsensors. -> Siehe Bedienunsanleitung des Raumsensors.
0 1 2 3 4 5 6 7 8 9 10 11
5/6
HTS 80-110
0
1 2 3 4 5 6 7 8 9 10 11
1/8/2019
Projekt Titel:
Project title: HTS 80-110
Communication
Control element
Communication
Power supply
Room sensor Room sensor Room sensor
-> LAN - / WLAN adapter
-> SMT I/O - RJ45
-> SMT I/O - 12V
Unmixed circuit 1st mixed circuit 2nd mixed circuit
Smart Control Touch
Room sensor
Each space probe requires a unique device address!
-> See the operating instructions for the space probe.
Room sensor
Room sensor
Communication
-> SMT I/O - B3/A3
REMKO HTS series
40
PE
-EHZ
Spannungsvers. 400V
Bauseits
L1L2L3
N
A32
-ST2
Freigabe E-Heizer
-> SMT I/O - A32
N
-ST2
N, PE E-Heizer
-> X2.2
PE
PE
-ST1
Stecker Spannung 400V
Elektro Heizstab
123456PE
1
-ST2
Stecker Steuerleitung
Elektro Heizstab
23PE
0 21
L-ST L1 N-ST N-LL
L N
-SN1
X1
X2
-H1
1
2
-R1
K2.1
K2.2
A1
11
21
A1
11
21
A2
14
24
A2
14
24
STB 95°C
30°C - 78°C
-EHZ
Elektro Heizstab
PE
-EHZ
Spannungsvers. 3x230V
Bauseits
LLLNN
N
A32
-ST2
Freigabe E-Heizer
-> SMT I/O - A32
N
-ST2
N, PE E-Heizer
-> X2.2
PE
PE
-ST1
Stecker Spannung 400V
Elektro Heizstab
123456PE
1
-ST2
Stecker Steuerleitung
Elektro Heizstab
23PE
0 21
L-ST L1 N-ST N-LL
L N
-SN2
X1
X2
-H2
1
2
-R2
K2.1
K2.2
A1
11
21
A1
11
21
A2
14
24
A2
14
24
STB 95°C
30°C - 78°C
-EHZ.
Elektro Heizstab
Elektro Heizstab 3x230V
Elektro Heizstab 400V
0 1 2 3 4 5 6 7 8 9 10 11
6/6
HTS 80-110
0
1 2 3 4 5 6 7 8 9 10 11
1/8/2019
Projekt Titel:
PE
-EHZ
Spannungsvers. 400V
Bauseits
L1L2L3
N
PE
-ST1
Stecker Spannung 400V
Elektro Heizstab
123456PE
1
-ST2
Stecker Steuerleitung
Elektro Heizstab
23PE
0 21
L-ST L1 N-ST N-LL
L N
-SN1
X1
X2
-H1
1
2
-R1
K2.1
K2.2
A1
11
21
A1
11
21
A2
14
24
A2
14
24
STB 95°C
30°C - 78°C
PE
-EHZ
Spannungsvers. 3x230V
Bauseits
LLLNN
N
PE
-ST1
Stecker Spannung 400V
Elektro Heizstab
123456PE
1
-ST2
Stecker Steuerleitung
Elektro Heizstab
23PE
0 21
-SN2
0 1 2 3 4 5 6 7 8 9 10 11
Project title: HTS 80-110
Electric heating element 400V
Electric heating element 3x230V
Enable E-heater
Power supply 400V
Electric heating element
Plug voltage 400V Power supply 3x230V Plug voltage 400V
Plug for control line
Plug for control line
N, PE E-heater
-> SMT I/O - A32
Provided by the customer
Electric heating element Provided by the customer Electric heating element
Electric heating element
Electric heating element
Enable E-heater
N, PE E-heater
Electric heating element
41
L3
-X1
Spannungsvers. 400V
Bauseits
L3
-X1
Spannungsv. 400V
-> INV
L2
L2/N
L1
L1/L
N
PE
PE 1
-X2
Aussenmodul 1
-> ODU
L
-X2.1
Spannungsv. 230V
-> SMT I/O - Pout1
2
N
3
X1.1 X1.2 X1.3 X1.4 X1.5
X2.1
X2.2
X2.3
X2.4
L3
L2
L1
N
PE
1
23
45
6
78
9
10
L3
L2
L1
N
PE
2 3
4 5
6
7 8
9
10
-X
Klemmblock
Innenmodul
4
NO5
-X2.2
Kondensatheizung
-> µPC - NO5
5 6 7 8 9
B3
-X2.4
Aussentemperatur
-> µPC - B3
10
Y3
-X2.3
Steuersignal Lüfter
-> µPC - Y3
DI1
-X2.3
Störmeldung Lüfter
-> µPC - DI1
GND
1
-ODU
Aussenmodul 1
-> X2
2345678910
123456789
10
-ODU
Klemmblock
Aussenmodul
1
2
-B3.
NTC
Aussentemperatur
N
L
-HD
Heizwiderstand
Kondensatheizung
M
L
N
PE
E1 GND 11 14
-FAN
EC Motor 230V
Verdampferlüfter
HTS 90 und HTS 130
Bei der HTS 90 fallen L2 und L3 weg!
In diesem Fall ist der Nullleiter N an
der Klemme L2/N des Inverters
angeschlossen.
In diesem Fall ist der Nullleiter N an
der Klemme L2/N des Inverters
angeschlossen.
0 1 2 3 4 5 6 7 8 9 10 11
1/8
0
1 2 3 4 5 6 7 8 9 10 11
1/28/2019
Projekt Titel:
HTS 90-130-200-260
HTS 90 and HTS 130
On the HTS 90 machine, L2 and L3
are not required!
In this case, the neutral wire N is
connected to terminal L2/N on the
inverter.
Power supply 400V
Power supply 400V
Outdoor unit 1
Power supply 230V
Condensate heating
Outside temperature
Fan control signal
Fan alarm code
Heating resistor
EC Motor 230V
Terminal block
Outdoor unit 1
Terminal block
-> SMT I/O - Pout1
-> μPC - NO5
-> μPC - B3
-> μPC - Y3
-> μPC - DI1
Condensate heating
Evaporator fan
Indoor unit
Outdoor unit
Project title: HTS 90-130-200-260
Outside temperature
-> INV
Provided by the customer
-> ODU
REMKO HTS series
42
Projekt Titel:
HTS 90-130-200-260
L3
-X1
Spannungsvers. 400V
Bauseits
L3
-X1
Spannungsv. 400V
-> INV
L2
L2/N
L1
L1/L
N
PE
PE 1
-X2
Aussenmodul 1
-> ODU1
L
-X2.1-X3.1
Spannungsv. 230V
-> SMT I/O - Pout1
2
N
3 4
NO5
-X2.2-X3.2
Kondensatheizung
-> µPC - NO5
5 6 7 8 9
X1.1 X1.2 X1.3 X1.4 X1.5
X2.1
X2.2
X2.3
X2.4
X3.4
X3.3
X3.2
X3.1
L3
L2
L1
N
PE
1
23
45
6
78
9
10
11
1213
1415
16
1718
19
20
L3
L2
L1
N
PE
2 3
4 5
6
7 8
9
10
12 13
14 15
16
17 18
19
20
-X.
Klemmblock
Innenmodul
B3
-X2.4
Aussentemperatur
-> µPC - B3
10 1
-X3
Aussenmodul 2
-> ODU2
2 3 4 5 6
Y3
-X2.3-X3.3
Steuersignal Lüfter
-> µPC - Y3
7 8
DI1
-X3.3
Störmeldung Lüfter
-> µPC - DI1
GND
1
-ODU1
Aussenmodul 1
-> X2
2345678910
11
-ODU2
Aussenmodul 2
-> X3
12131415161718
123456789
10
-ODU1
Klemmblock
Aussenmodul 1
123456789
10
-ODU2
Klemmblock
Aussenmodul 2
1
2
-B3.1
NTC
Aussentemperatur
1
2
-B3.2
NTC
Aussentemperatur
N
L
-HD1
Heizwiderstand
Kondensatheizung
N
L
-HD2
Heizwiderstand
Kondesatheizung
M
L
N PE
E1
GND
11
14
-FAN1
EC Motor 230V
Verdampferlüfter
M
L N PE
E1 GND 11 14
-FAN2
EC Motor 230V
Verdampferlüfter
HTS 200 und HTS 260
0 1 2 3 4 5 6 7 8 9 10 11
2/8
0
1 2 3 4 5 6 7 8 9 10 11
1/28/2019
HTS 200 and HTS 260
Project title: HTS 90-130-200-260
Power supply 400V
-> INV
Power supply 230V
Condensate heating
Outside temperature
Fan control signal
Fan alarm code
-> SMT I/O - Pout1
-> μPC - NO5
-> μPC - B3
-> μPC - Y3
-> μPC - DI1
Power supply 400V
Outdoor unit 2
Outdoor unit 1
Terminal block
Indoor unit
Provided by the customer
-> ODU2
-> ODU1
Heating resistorHeating resistor
EC Motor 230VEC Motor 230V
Outdoor unit 1
Outdoor unit 2
Terminal block
Terminal block
Condensate heatingCondensate heating
Evaporator fanEvaporator fan
Outdoor unit 1
Outdoor unit 2
Outside temperatureOutside temperature
43
Projekt Titel:
HTS 90-130-200-260
G0
-Pout1
Spannungsversorgung 230V
-> µPC - J1
G
PE
PE
-Pin
Spannungsversorgung 230V
SMT I/O - Bauseits
N L
S0
Imp/kWh
+
-
-S25
Stromzähler S0
Wärmepumpe
S0
Imp/kWh
+
-
-S26
Stromzähler S0
Haushalt
1
M
PE N L
-Pout1
Versorgung 230V
Interne Pumpe A43
13 1
4
-S27
Volumenstrom, Imp.
Warmwasser
M
N SP DP
-A10
Umschaltventil 230V
Warmwasserbereitung
S0
Imp/kWh
+
-
-S28
Stromzähler S0
PV Ertrag
S0
Imp/kWh
+
-
-S29
Stromzähler S0
PV Einspeisung
M
N SP DP
-A11
Umschaltventil 230V
2. Wärmeerzeuger
U
t
­+
-A40
Signal PWM
Solarkreis
U
t
­+
-A41
Signal 0-10V / PWM
1. gem. Kreis
U
t
­+
-A42
Signal 0-10V / PWM
ungem. Kreis
1
M
PE N L
-A13
Pumpe 230V
2. gem. Kreis
U
t
­+
-A43
Signal PWM
Interne Pumpe
Power Actuator Output Actuator Output Actuator OutputActuator Supply
Sensor Inputs Actuator Signal Actuator Signal SPI OT Interfaces Bus Interfaces Rc
Systemregler SMT I/O
PE N L
PE N L
PE N L
PE N A10 L
PE N A11 L
PE N A12 L
PE N A13 L
PE N A14 L
PE N A01
PE N A02
PE N A03
PE N A04
PE N A20 A21
PE N A22 A23
PE N A24 A25
S25 +5V GND
S26 +5V GND
S27 +5V GND
S28 +5V GND
S29 +5V GND
GND A40
GND A41
GND A42
GND A43
GND A44
GND A45
GND A46
MI MO CLK nSS GND
OT1 OT1
OT2 OT2
+12V B1 A1 GND
B2 A2
B3 A3
R GND
-SMT_I/O_UNTEN
Systemregler
M
N SP DP
-A14
Umschaltventil 230V
Separater Kühlkreis
1
M
PE N L
-A01
Pumpe 230V
Solarkreis
U
t
­+
-A46
Signal 0-10V / PWM
2. gem. Kreis
1
M
PE N L
-A02
Pumpe 230V
1. gem. Kreis
1
M
PE N L
-A03
Pumpe 230V
ungem. Kreis
1
M
PE N L
-A04
Pumpe 230V
Trinkwasser Zirkulation
+12V
-12V
Spannungsvers.
-> SMT Touch
GND
M
N Auf Zu
-A20/A21
Mischventil 230V
1. gem. Kreis
GND
-B2/A2
Kommunikation
-> µPC - J6
- +
M
N Auf Zu
-A22/A23
Ventil 230V
Bypass
B
-B3/A3
Kommunikation
-> Raumsensor - B/A
A
1
2
-RC
Kodierwiderstand
Geräteabhängig
M
N Auf Zu
-A24/A25
Mischventil 230V
2. gem. Kreis
Kodierwiderstände:
HTS 90 -> 620 Ohm
HTS 130 -> 430 Ohm
HTS 200 -> 750 Ohm
HTS 260 -> 510 Ohm
HTS 90 -> 620 Ohm
HTS 130 -> 430 Ohm
HTS 200 -> 750 Ohm
HTS 260 -> 510 Ohm
0 1 2 3 4 5 6 7 8 9 10 11
3/8
0
1 2 3 4 5 6 7 8 9 10 11
1/28/2019
Project title: HTS 90-130-200-260
Coding resistors:
Electricity meter S0
Power supply 230V
Power supply 230V
System controller
Power supply 230V
Changeover valve 230V
Changeover valve 230V
Pump 230V
Changeover valve 230V
Pump 230V
Pump 230V
Pump 230V
Pump 230V
Mixed valve 230V
Valve 230V
Mixed valve 230V
Electricity meter S0
Medium ow rate, Imp.
Electricity meter S0
Electricity meter S0
Signal PWM
Signal 0-10V / PWM
Signal 0-10V / PWM
Signal PWM
Signal 0-10V / PWM
Power supply
Communication
Coding resistor
Communication
Heat pump
Internal pump A43
Hot water preparation
2. Heat generator
2nd mixed circuit
Separate cooling circuit
Solar circuit
1st mixed circuit
Unmixed circuit
Drinking water circulation
1st mixed circuit
Bypass
2nd mixed circuit
Household
Hot water
PV yield
PV feed-in
Solar circuit
1st mixed circuit
Unmixed circuit
Internal pump
2nd mixed circuit
-> SMT Touch
-> μPC - J6
Device-dependent
-> Room sensor - B/A
System controller SMT I/O
Sensor Inputs Actuator Signal Actuator Signal OT Interfaces Bus Interfaces
-SMT_I/O_BOTTOM
Actuator OutputActuator OutputActuator OutputActuator SupplyPower
-Pout1
SPI
Provided by the customer
Open
Open
Open
Close
Close
Close
REMKO HTS series
44
Projekt Titel:
HTS 90-130-200-260
13 1
4
-S23
Volumenstrom, Imp.
Solarkreis
3 1 4 2 5
-S24/S15
PT1000 / Vol. Imp.
RL / Vol. Wärmep.
1
2
-S01
PT1000
Kollektorfühler
1
2
-S02
PT1000
Speicherfühler, Solar
RJ45
-RJ45
Kommunikation
-> SMT Touch
1
2
-S03
PT1000
Vorlauf, Solar
1
2
-S04
PT1000
Rücklauf, Solar
1
2
-S05
PT1000 / Impuls
Zirkulation
1
2
-S06
PT1000
Vorlauf, 2. gem. Kreis
1
2
-S08
PT1000
Warmwasserspeicher
G0
-A32
Spannung 230V
-> µPC - G0
1
2
-S09
PT1000
Pufferspeicher
1
2
-S10
PT1000
Außentemperatur
1
2
-S11
PT1000
Rücklauf, 1. gem. Kreis
1
2
-S12
PT1000
Vorlauf, 1. gem. Kreis
1
2
-S13
PT1000
Vorlauf, Wärmepumpe
Potential Free Outputs
Sensor InputsSensor InputsSensor InputsSensor Inputs
Systemregler SMT I/O
In A30
In A31
In A32
In A33
In A34
S20 +5V GND S40 S41
S21 +5V GND S42 S43
S22 +5V GND S44 S45
S23 +5V GND S46 S47
S24 +5V GND S48 S49
S01 GND
S02 GND
RJ45
S03 GND
S04 GND
S05 GND
S06 GND
S07 GND
S08 GND
S09 GND
S10 GND
S11 GND
S12 GND
S13 GND
S14 GND
S15 GND
S16 GND
-SMT_I/O_OBEN
Systemregler
L
-A32
Freigabe E-Heizer
-> EHZ - ST2
1
2
-S14
PT1000
Rücklauf, 2. gem. Kreis
In
-A34
Potentialfreier Kontakt
Sammelstörmeldung
A34
S16
-S16
Brücke / Öffner-K.
EVU Sperre
GND
Bei Verwendung einer EVU Sperre darf nur der Verdichter Spannungslos geschaltet werden!Verdichter Spannungslos geschaltet werden!
0 1 2 3 4 5 6 7 8 9 10 11
4/8
0
1 2 3 4 5 6 7 8 9 10 11
1/28/2019
Project title: HTS 90-130-200-260
System controller
System controller SMT I/O
Medium ow rate, Imp.
PT1000 / Vol. Imp.
PT1000 / Vol. Imp.
Communication
PT1000 / Impulse
Solar circuit
RF / Vol. Heat Pump
Collector probe
-> SMT Touch
Circulation
Inlet, 2nd mixed circuit
Hot water storage tank
Bu󰀨er tank
Outside temperature
Return ow, 1st mixed circuit
Inlet, 1st mixed circuit
Inlet, heat pump
Return ow, 2nd mixed circuit
Inlet, Solar
Return ow, Solar
Storage tank probe, Solar
Jumper / NC terminal
Power utility block
When using a power utility block, only power to compressor may be switched!
Sensor Inputs Sensor Inputs Sensor Inputs Sensor Inputs
Potential-Free Outputs
In
In
In
In
In
Enable E-heater
Voltage 230V
Potential-free contact
-> EHZ - ST2
General alarm signal
-SMT_I/O_TOP
45
Projekt Titel:
HTS 90-130-200-260
9
-J2
Freigabe Inverter
-> INV
10 N
-J1
Spannungsv. 230V
-> SMT I/O - Pout1
L
1
2
-B1
NTC
Wasser Eintritt
1
2
-B2
NTC
Wasser Austritt
5
-J10
Kommunikation
-> INV
9
-B3
Außentemperatur
-> Klemmblock X2.4
4 3
1
2
-B4
NTC
Sauggas
1
2
-B5
NTC-HT
Heißgas
S
J11
-J11
Steuersignal
Expansionsventil
1 3
2
-B6
RAZ 0-5V
Niederdruck
1 3
2
-B7
RAZ 0-5V
Hochdruck
GND
-J6
Kommunikation
-> SMT I/O - B2/A2
A2 B2
-DI1
Störmeldung Lüfter
-> Klemmblock X2.3 / X3.3
J7
J8
J9
J10
J11
J12 J13 J14
J1 J2 J3
J6
J4 J5
Kätekreis Regler µPC
1 2 34 12 345 6
pLAN
R-/T­R+/T+ GND
Vout R-/T­R+/T+ GND
C1 NO1 NO2 NO3
C2 NO4 NO5 NO6
NO7 C3 NC7
G G0
+Vdc GND +5VR
B1
B2
B3
B4
B5
B6
B7
GND +Vdc
GND +
-
DI1
DI2
DI3
DI4
DI5
DI6
DI7 DIC1
GND Y1 Y2 Y3
-µPC
Kältekreis Regler
1 2
-NO2
Ausgang 230V
4 - Wege Ventil
P
1
2
-DI3
Öffner-Kontakt
Hochdruckschalter
4
-NO5
Kondensatheizung
-> Klemmblock X2.2 / X3.2
6/16
-Y3
Steuersignal Lüfter
-> Klemmblock X2.3 / X3.3
6
0 1 2 3 4 5 6 7 8 9 10 11
5/8
0
1 2 3 4 5 6 7 8 9 10 11
1/28/2019
Project title: HTS 90-130-200-260
Refrigerant circuit controller μPC
Enable inverter
Power supply 230V
NTC
Outside temperature Communication
Control signal
Output 230V
Condensate heating
Fan control signal
-> INV
-> SMT I/O - Pout1
Water inlet
-> T erminal block X2.4 -> INV
Expansion valve
4-way valve
-> T erminal block X2.2 / X3.2
-> Terminal block X2.3 / X3.3
Suction gas
Heat gas
Low pressure
High pressure
Water outlet
Cooling cycle controller
Communication
Fan alarm code
NC contact
-> SMT I/O - B2/A2
-> Terminal block X2.3 / X3.3
High pressure switch
REMKO HTS series
46
Projekt Titel:
HTS 90-130-200-260
DC Choke
L1/L
-INV
Spannungsv. 400V
Inverter
L2/N L3 PE
power +
speed drive
L1/L
L2/N
L3
PE
U
V
W
PE
1 2 3 4 5 6 7 8 9 10
C1
C2
-INV
power+ Inverter
GND
-INV
Kommunikation
-> µPC - J10
R+/T+ R-/T-
+Vdc
-INV
Freigabe Inverter
-> µPC - J2
GND
M
3
-M
Spannungsv.
Verdichter
Bei der HTS 90 fallen L2 und L3 weg!
In diesem Fall ist der Nullleiter N an
der Klemme L2/N des Inverters
angeschlossen.
In diesem Fall ist der Nullleiter N an
der Klemme L2/N des Inverters
angeschlossen.
0 1 2 3 4 5 6 7 8 9 10 11
6/8
0
1 2 3 4 5 6 7 8 9 10 11
1/23/2019
Project title: HTS 90-130-200-260
Power supply 400V
Power + Inverter
On the HTS 90 machine, L2 and L3
are not required!
In this case, the neutral wire N is
connected to terminal L2/N on the
inverter.
Inverter
Communication
Enable inverter
Power supply
-> μPC - J10
-> μPC - J2
Compressor
47
Projekt Titel:
HTS 90-130-200-260
USB
-USB
Kommunikation
-> LAN - / WLAN Adapter
Smart-Control Touch
USB
RJ45
GND +12V
-SMT_TOUCH
Bedienteil
RJ45
-RJ45
Kommunikation
-> SMT I/O - RJ45
GND
-12V
Spannungsvers.
-> SMT I/O - 12V
+12V
Raumsensor
A V+ V­B
-RS1
Raumsensor
ungem. Kreis
Raumsensor
A V+ V­B
-RS2
Raumsensor
1. gem. Kreis
Raumsensor
A V+ V­B
-RS3
Raumsensor
2. gem. Kreis
B3
-B/A
Kommunikation
-> SMT I/O - B3/A3
A3
Jeder Raumsensor benötigt eine eindeutige Geräteadresse!
-> Siehe Bedienunsanleitung des Raumsensors. -> Siehe Bedienunsanleitung des Raumsensors.
0 1 2 3 4 5 6 7 8 9 10 11
7/8
0
1 2 3 4 5 6 7 8 9 10 11
1/28/2019
Project title: HTS 90-130-200-260
Each space probe requires a unique device address!
-> See the operating instructions for the space probe.
Smart Control Touch
Room sensor
Room sensor
Room sensor
Communication
Room sensor Room sensor Room sensor
Control element
Communication
Power supply
Communication
-> LAN - / WLAN adapter
Unmixed circuit
1st mixed circuit 2nd mixed circuit
-> SMT I/O - RJ45
-> SMT I/O - 12V
-> SMT I/O - B3/A3
REMKO HTS series
48
Projekt Titel:
HTS 90-130-200-260
PE
-EHZ
Spannungsvers. 400V
Bauseits
L1L2L3
N
A32
-ST2
Freigabe E-Heizer
-> SMT I/O - A32
N
-ST2
N, PE E-Heizer
-> X2.2
PE
PE
-ST1
Stecker Spannung 400V
Elektro Heizstab
123456PE
1
-ST2
Stecker Steuerleitung
Elektro Heizstab
23PE
0 21
L-ST L1 N-ST N-LL
L N
-SN1
X1
X2
-H1
1
2
-R1
K2.1
K2.2
A1
11
21
A1
11
21
A2
14
24
A2
14
24
STB 95°C
30°C - 78°C
-EHZ
Elektro Heizstab
PE
-EHZ
Spannungsvers. 3x230V
Bauseits
LLLNN
N
A32
-ST2
Freigabe E-Heizer
-> SMT I/O - A32
N
-ST2
N, PE E-Heizer
-> X2.2
PE
PE
-ST1
Stecker Spannung 400V
Elektro Heizstab
123456PE
1
-ST2
Stecker Steuerleitung
Elektro Heizstab
23PE
0 21
L-ST L1 N-ST N-LL
L N
-SN2
X1
X2
-H2
1
2
-R2
K2.1
K2.2
A1
11
21
A1
11
21
A2
14
24
A2
14
24
STB 95°C
30°C - 78°C
-EHZ.
Elektro Heizstab
Elektro Heizstab 3x230V
Elektro Heizstab 400V
0 1 2 3 4 5 6 7 8 9 10 11
8/8
0
1 2 3 4 5 6 7 8 9 10 11
1/28/2019
PE
-EHZ
Spannungsvers. 400V
Bauseits
L1L2L3
N
A32
N PE
PE
-ST1
Stecker Spannung 400V
Elektro Heizstab
123456PE
1
-ST2
Stecker Steuerleitung
Elektro Heizstab
23PE
0 21
L-ST L1 N-ST N-LL
L N
-SN1
X1
X2
-H1
1
2
-R1
K2.1
K2.2
A1
11
21
A1
11
21
A2
14
24
A2
14
24
STB 95°C
30°C - 78°C
PE
-EHZ
Spannungsvers. 3x230V
Bauseits
LLLNN
N
A32
N PE
PE
-ST1
Stecker Spannung 400V
Elektro Heizstab
123456PE
1
-ST2
Stecker Steuerleitung
Elektro Heizstab
23PE
0 21
L-ST L1 N-ST N-LL
-SN2
0 1 2 3 4 5 6 7 8 9 10 11
Project title: HTS 90-130-200-260
Enable E-heater
N, PE E-heater
-> SMT I/O - A32
Electric heating element 400V
Power supply 400V
Provided by the customer
Plug voltage 400V
Electric heating element
Plug for control line
Electric heating element
Electric heating element
Electric heating element 3x230V
Electric heating element
Plug voltage 400V
Plug for control line
Provided by the customer
Electric heating element
Electric heating element
Enable E-heater
N, PE E-heater
49
REMKO HTS series
Legend for circuit diagrams
E-heater Elektric heater Imp. Impulse mix.: mixed PV: Photovoltaic PWM: Phase width modulation unmix.: unmixed Vol. Medium flow rate
50

10 Index

C
Circuit diagrams ........................ 36
Contact sensor ......................... 1
1
D
Disposal of equipment .....................6
E
Electrical connection
Indoor module ....................... 10
Outdoor module ...................... 11
Environmental protection ...................6
I
Intended use ............................ 5
O
Outdoor sensor ......................... 12
S
Safety
Dangers of failure to observe the safety
notes ............................... 4
General ............................. 4
Identification of notes ................... 4
Notes for inspection .................... 5
Notes for installation ....................5
Notes for maintenance .................. 5
Personnel qualifications ................. 4
Safety notes for the operator ............. 5
Safety-conscious working ................4
Unauthorised modification ...............5
Unauthorised replacement part manufacture
. 5
T
Temperature sensors .....................11
Terminal assignment, overview ....... 17, 20, 33
W
Warranty ............................... 5
51
REMKO QUALITY WITH SYSTEMS
Air-Conditioning | Heating | New Energies
Telephone +49 (0) 5232 606-0 Telefax +49 (0) 5232 606-260
E-mail info@remko.de URL www.remko.de
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 32791 Lage
Hotline within Germany
+49 (0) 5232 606-0
Hotline International
+49 (0) 5232 606-130
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
Loading...