REMKO HGM Series, HGU Series Assembly And Operating Instructions Manual

Assembly and operating instructions
REMKO Heating cycle groups HGM / HGU
Instructions for the Technician
0154-2016-12 Edition 1, en_GB
Read the instructions prior to performing any task!
Read these operating instructions carefully before commis­sioning / using this device!
These instructions are an integral part of the system and must always be kept near or on the device.
Subject to modifications; No liability accepted for errors or mis­prints!
Installation and operating instructions (translation of the orig­inal)

Table of contents

1 Safety and usage instructions............................................................................................................. 4
1.1 General safety notes....................................................................................................................... 4
1.2 Identification of notes...................................................................................................................... 4
1.3 Personnel qualifications.................................................................................................................. 4
1.4 Dangers of failure to observe the safety notes................................................................................ 4
1.5 Safety-conscious working............................................................................................................... 4
1.6 Safety instructions for the operator................................................................................................. 5
1.7 Safety notes for installation and inspection tasks........................................................................... 5
1.8 Unauthorised modification and changes......................................................................................... 5
1.9 Intended use................................................................................................................................... 5
1.10 Safety-conscious working............................................................................................................. 5
1.11 Warranty........................................................................................................................................ 5
1.12 Transport and packaging.............................................................................................................. 6
1.13 Environmental protection and recycling........................................................................................ 6
2 Technical data....................................................................................................................................... 7
2.1 Unit data for pump groups HGM / HGU.......................................................................................... 7
2.2 Unit dimensions and pump group components HGM..................................................................... 8
2.3 Unit dimensions and pump group components HGU...................................................................... 9
2.4 Pump unit data.............................................................................................................................. 10
2.5 Pump unit dimensions................................................................................................................... 11
2.6 Pressure losses............................................................................................................................. 11
2.7 Delivery heights and electrical power............................................................................................ 12
3 Unit description................................................................................................................................... 12
4 Installation and assembly.................................................................................................................. 13
4.1 Installation..................................................................................................................................... 13
4.2 Wall installation............................................................................................................................. 13
4.3 Installation on the distributor......................................................................................................... 15
4.4 Mounting the actuator .................................................................................................................. 16
4.5 Gravity brake................................................................................................................................. 17
4.6 Replace the inlet and the return flow............................................................................................. 17
4.7 Replacement of the pump............................................................................................................. 18
4.8 Positioning of the electric cables................................................................................................... 19
4.9 Electrical wiring............................................................................................................................. 19
4.10 Installation example.................................................................................................................... 21
5 Troubleshooting.................................................................................................................................. 22
6 Exploded view and spare parts......................................................................................................... 24
6.1 HGM.............................................................................................................................................. 24
6.2 HGU.............................................................................................................................................. 25
7 Index..................................................................................................................................................... 26
3
REMKO Heating cycle groups
1 Safety and
usage instructions

1.1 General safety notes

Carefully read the operating manual before com­missioning the units for the first time. It contains useful tips and notes such as hazard warnings to prevent personal injury and material damage. Failure to follow the directions in this manual not only presents a danger to people, the environment and the system itself, but will void any claims for liability.
Keep this operating manual and the refrigerant data sheet near to the units.

1.2 Identification of notes

This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation.The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by sym­bols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.
DANGER!
CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or mate­rial and environmental damage.
NOTICE!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.
This symbol highlights useful tips and recom­mendations as well as information for efficient and fault-free operation.

1.3 Personnel qualifications

Personnel responsible for commissioning, opera­tion, maintenance, inspection and installation must be able to demonstrate that they hold a qualifica­tion which proves their ability to undertake the work.
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.
DANGER!
This combination of symbol and signal word warns of a situation in which there is immediate danger, which if not avoided may be fatal or cause serious injury.
WARNING!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury.

1.4 Dangers of failure to observe the safety notes

Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.
In particular, failure to observe the safety notes may pose the following risks:
n The failure of important unit functions. n The failure of prescribed methods of mainte-
nance and repair.
n Danger to people on account of electrical and
mechanical effects.

1.5 Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.
4
1.6 Safety instructions for the oper­ator
The operational safety of the units and compo­nents is only assured providing they are used as intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified per­sonnel.
n The existing regulations concerning accident
prevention must be adhered to.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with equipment parts or components
can lead to burns or injury.
n Ensure that electrical energy does not pose a
risk.
n Regulations of the VDE and the local energy
supply company must be adhered to.

1.7 Safety notes for installation and inspection tasks

n The operator must ensure that all inspection
and installation work is carried out by author­ised and qualified personnel who have thor­oughly read the operating manual.
n Works on the pump/system may only be car-
ried out whilst at a standstill as a matter of prin­ciple.
n Appropriate hazard prevention measures must
be taken to prevent risks to people when per­forming installation, repair, maintenance or cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
n Regional regulations and laws as well as the
Water Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n The units and components must be kept at an
adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
n Safety devices may not be modified or
bypassed.
Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufacturer ensure safety. The use of other parts may invalidate liability for resulting consequences.

1.9 Intended use

The heating cycle group is only approved for oper­ation as a heating cycle group. It serves to trans­port the operating medium of water into closed heating cycles.
Any different or additional use is a non-intended use. The manufacturer/supplier assumes no lia­bility for damages arising from a non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
The threshold values specified in the technical data must not be exceeded.

1.10 Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.

1.11 Warranty

For warranty claims to be considered, it is essential that the ordering party or its representative com­plete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the "Gen­eral business and delivery conditions". Further­more, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.

1.8 Unauthorised modification and changes

The operational safety of the pump group that was delivered is guaranteed only with intended use in accordance with section 1.9 of the operating instructions. Under no circumstances should the threshold values specified in the datasheet be exceeded.
5
REMKO Heating cycle groups

1.12 Transport and packaging

The devices are supplied in a sturdy shipping con­tainer. Please check the equipment immediately upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to children!

1.13 Environmental protection and recycling

Disposing of packaging
All products are packed for transport in environ­mentally friendly materials. Make a valuable contri­bution to reducing waste and sustaining raw mate­rials. Only dispose of packaging at approved collection points.
Disposing of the units and their components
For the manufacture of the units and components, only recyclable materials have been used. Help protect the environment by ensuring that the units or components (for example batteries) are not dis­posed of in household waste, but only in accord­ance with local regulations and in an environmen­tally safe manner, e.g. using authorised disposal and recycling specialists or council collection points.
6

2 Technical data

2.1 Unit data for pump groups HGM / HGU

Technical properties
Pump group HGM HGU
Maximum operating temperature °C 95
Max. operating pressure bar 10
Heating cycle side, internal thread Inches 1"
Storage cycle side, external thread Inches 1 1/2"
Pump Wilo Stratos Para 25 / 1-7 T1
Compatible media Water, water-Glycol mixture (maximum 30%)
Thermometer measurement range °C/°F 0-120°C / 30-250°F
Weight kg 6.9 5.85
Materials
Pump group HGM HGU
Ball valve and check valve
Body made of brass: UNI EN 12164 - CW617N UNI EN 12164 - CW614N
Hydraulic seals PTFE, Viton, EPDM
Motorised mixing valve
Body made of brass: UNI EN 12165 - CW617N ---
Turning part made of brass: UNI EN 12164 - CW614N ---
Hydraulic seals EPDM
Insulation half-shells
Body EPP
Body, seal
Body, therm. conductivity (20°C) W/mK 0.039
kg/m
3
60
Body, therm. conductivity (40°C) W/mK 0.041
7
250
380
190
2
1
4
3
6
7
5
4
1
=
2
=
5
=
3
=
4
=
REMKO Heating cycle groups

2.2 Unit dimensions and pump group components HGM

Dimensions
Fig. 1: Unit dimensions for pump group HGM
Pump group G G1 L H
HGM 1" IG
Components
1 1/2" AG
125 mm 340 mm
Fig. 2: Pump group components HGM
1: Circulation pump Wilo Stratos Para 25 / 1-7 T1 2: Ball valve 3: Ball valve with integrated check valve 4: Thermometer
5: Motorised mixing valve 6: Extension 7: Insulation
8

2.3 Unit dimensions and pump group components HGU

250
380
190
2
1
4
3
6
5
4
1
=
2
=
=
3
=
4
Dimensions
Fig. 3: Unit dimensions for pump group HGU
Pump group G G1 L H
HGU 1" IG
Components
1 1/2" AG
125 mm 340 mm
Fig. 4: Pump group components HGU
1: Circulation pump Wilo Stratos Para 25 / 1-7 T1 2: Ball valve 3: Ball valve with integrated check valve
9
4: Thermometer 5: Ball valve 6: Insulation
REMKO Heating cycle groups

2.4 Pump unit data

Technical data
Pump group HGM / HGU
Pump type Wilo Stratos Para 25 / 1-7 T1
Maximum delivery volume
Maximum delivery height m 7.0
Speed rpm 1200 - 4450
Mains voltage 1~230V ± 10% in accordance with DIN IEC 60038
Energy Efficiency Index ( EEI ) £ 0.23
Frequency Hz 50/60 Hz
Insulation class F
Enclosure class IP 44
m
3
4.5
Rated input P1 W 5 - 70
Nominal width for pipe connection Rp Inch
es
Connection flange thread G Inch
es
Permitted ambient temperature °C + 40
Maximum relative humidity £ 95%
Heating water (in accordance with VDI 2035/VdTÜV
Water/glycol mixture, maximum mixture ratio is 30% (in
mixtures with glycol, the delivery data of the pump must
be corrected according to the higher viscosity and
depending on the mixture ratio percentage.)
Permitted conveying media
Ethylene/propylene glycol with corrosion protection
- Standard oxygen binding agent
- Standard corrosion protection agent
- Standard combination products
- Standard cooling brines
1"
1 1/2"
Tch 1466)
inhibitors
Permitted medium temperature °C 95
Maximum operating pressure at the pump bar 6.0
Weight kg 2.4
10

2.5 Pump unit dimensions

b4
b5
l
2
l
0
l
1
l
3
a
1
a
2
a
3
21
A
B
A
[m3/h]
B
[m3/h]
[mbar]
[mbar]
a a
Fig. 5: Pump unit dimensions
Wilo Stratos Para 25 / 1-7 T1
l
0
a
1
a
2
a
3
l
1
l
2
l
3
b
4
Dimensions in mm 180 116 32 94 90 56 138 42 41

2.6 Pressure losses

b
5
Fig. 6: Diagram of pressure losses in the pump group HGM / HGU
1: Operational mode; constant differential pressure 2: Operational mode; variable differential pressure A: Resistance / delivery height [mbar] B:
Delivery rate [m3/h]
a: Mixing valve R 3/4
11
2
1
1
4
3
A
B
2
1
2
3
4
5
REMKO Heating cycle groups

2.7 Delivery heights and electrical power

Fig. 7: Delivery heights and electrical power of the Wilo Stratos Para 25 / 1-7 T1pump
1: External operating mode via analogue-in 0-10V 2: External operating mode via pump shaft model
(PSM)

3 Unit description

These pump groups HGM / HGU enable circulation of the heat conducting medium via the inlet. The pump group HGM regulates the temperature of the heat conducting medium via a motorised mixing valve. This pump group with controllable tempera­ture is therefore ideal for operating normal heating systems with temperature regulation. Temperature regulation of the Inlet takes place depending on the inlet and return temperatures of probes S12 and S11.
The pump groups comprise the following: Pump, ball valve for inlet and return flow, thermometer for inlet and return flow, check valve against the heating cycle and thermal insulation.
The pump group HGM also has an integrated mixing valve
The two insulation half-shells [1, 2] serve as heat insulation for the pump group and therefore enable energy to be saved. The pump insulation was developed to guarantee heat insulation and to pre­vent the electric motor from overheating. The check valve that is integrated into the body of the return flow's ball valve prevents incorrect circula­tion when the pump is switched off.
Fig. 8: Unit components
A: HGM B: HGU 1: Front part of the insulation 2: Rear part of the insulation 3: Unit inlet equipped with secondary circuit ball
valve, a motorised mixing valve and a ther­mometer
4: Unit return flow equipped with secondary circuit
ball valve with an integrated check valve and a thermometer
5: Wall bracket
12

4 Installation and assembly

2
1
3

4.1 Installation

CAUTION!
Each individual hydraulic component must be installed by qualified personnel because the high temperatures and pressures of the liquid can cause personal injury.
NOTICE!
Do not use any grease or oils during
assembly, since they can destroy the seals. If necessary, dirt particles as well as grease and oil residue must be flushed out of the supply lines.
When selecting the operating medium, the
general state-of-the-art must be taken into consideration (e.g. VDI 2035).
Protect against external forces (e.g. shock,
impact, vibration).

4.2 Wall installation

CAUTION!
Observe the distance between the piping and the wall specified in point 7.
1. Remove the pre-installed pump group from the packaging.
2. Open the insulation cover half-shells by pulling the front side [1] and the rear side [2] apart.
Possible installations include:
n Wall installation n Installation on the distributor
After installation, all installation areas must be checked for leaks.
3. Remove the insulation [3].
4. Remove the inlet [4] and the return flow [5].
5. Install the pump group wall bracket on a suit-
able wall. The wall bracket is equipped with long holes to aid height adjustment. Fix the wall bracket to the wall using the enclosed wall plugs.
13
110 mm
A
110 mm
o 8 mm
45 mm
2
4
5
6
7
3
REMKO Heating cycle groups
8. Turn the controller of the return flow's ball
valve (7) to an angle of 45°; in this position, the ball valve bypasses the check valve and nullifies the effect of the valve. This improves the flow of the water and the air that is to be bled in the filling phase. Fill the system and check for leaks.
A: Dowel hole = 8 mm
6. Attach the rear side [2] of the insulation half­shell to the wall bracket. Install the inlet [4] and the return flow [5] on the wall bracket by lifting the insulation slightly. The distance between the pipe axis and the wall surface is thus around 54 mm.
9. Open the ball valve of the return flow [7].
10. Install the electric cables (see the positioning
of the cables section).
11. Insert the pump's insulation [3].
7. Use the screw connection enclosed in the
packaging to install the piping for the inlet and the return flow; ensure that the connec­tions are suitable for the pipe dimensions (connections with flat seals are recom­mended). If a pump is connected in a series to the pump group (e.g. boiler pump), in prac­tice, a fixture to separate the heating cycles hydraulically is to be installed, in order to pre­vent a malfunction of the two pumps or the heat pump.
14
1
45
12. Close the pump group using the insulation half-shell [1].

4.3 Installation on the distributor

The pump groups can be installed on distributors with an integrated hydraulic compensator, on standard distributors with a separate hydraulic compensator and on series distributors. For optimum installation, the nozzles of the distributor should be at least 60mm away from the wall.
1. First carry out installation steps 1-4 for wall installation.
2. To aid installation, start the installation in the middle of the distributor and then continue with the outer connections; install the inlet [4] and the return flow [5] on the distributor using the screw connection enclosed in the pack­aging or using the required connecting pieces (flat-sealing connections are recom­mended).
3. Insert the insulation half-shell [2]; if the dis­tributor is installed too close to the wall, you must insert the rear side [2] of the two insula­tion half-shells before you install the inlet and the return flow [4] and [5].
15
2
2
3
2
1
3
4
1
a
2
b
5
6 7
REMKO Heating cycle groups

4.4 Mounting the actuator

The actuator is installed as follows:
1. Mount the rotation lock [1] on the mixing valve housing.
2. Attach the adapter [2] onto the mixing valve plug [3] until it stops. Observe the flat area!
3. Set the mixing valve plugs so that the nose of the adapter [a] faces down in the axis direc­tion of the connection thread. The mixing valve plugs seal the inlet (full bypass mode, cold) in this position.
4. Set the actuator [4] on the mixing valve axis.
4. Insert the insulation [3] by pushing down the
top side of the rear insulation half-shell [2].
5. Set the rotation direction indicator [5] on the actuator according to the figure.
6. Attach the hand adjustment handle [6] with the arrow marking in the blue area [b] on the mixing drive shaft (condition when delivered: anti-clockwise against the stop, operational position "A" Automatic).
7. Attach the screw [7] with the serrated washer and tighten the screw.
5. Continue as described in point [9] for wall installation.
6. Open the ball valve of the return flow again.
7. Install the electric cables (see: positioning of
the cables section).
8. Close the pump group using the front part of the insulation [1].
Fig. 9: Mounting the 3-way mixing valve
16
A B
A
B
9 99

4.5 Gravity brake

The fitting group is delivered pre-assembled. When operating the heating system, the slot of the gravity brake assembly must be in the horizontal position.
Fig. 10: Gravity brake
A: Closed B: Open
Operating position: Stop valve closed, flow is only possible in the pumping direction.
The gravity brake must be opened for commis­sioning and maintenance work (filling and rinsing). Blocking function not active: Stop valve open, flow is possible in the both directions. During heating operation, the gravity brake must be moved back to the operating position.
When the circulation pump is switched off, a low level of gravity circulation is still possible in heating systems depending on the operating pressure and despite the block valve. Block valves are not leakproof flow limiters.

4.6 Replace the inlet and the return flow

Unmixed heating cycle group
In order to change the flow direction, proceed as follows:
1. Loosen the connection [9]
2. Replace the inlet and the return line
3. Tighten the connections again
Fig. 11: Inlet
A: Left B: Right
17
A
B
9 99
9
9
9
9
6
6
4 4
10
1
3
11
10
1
3
11
1
2
3
a
4
6
b
5
7 8
REMKO Heating cycle groups
Mixed heating cycle group
In order to change the flow direction, proceed as follows:
1. Loosen the connection [9] and the screw [6]
2. Remove the actuator [4]
Fig. 12: Inlet
A: Left B: Right
3. Loosen the cover [10] and [11] using the spanner SW46
4. Mount the mixing valve plugs [3] on the other side
5. Tighten the cover again and apply a torque of 45 Nm
6. Mount the rotation lock [1] on the other side
8. Set the operating switch [8] to manual opera-
tion
9. Set the rotation direction indicator [5] on the actuator [4] according to the figure
10. Attach the hand adjustment handle [7] on the mixing valve axis
NOTICE!
The hand adjustment handle can only be lightly pressed into a locking position. Do not use any force. Turn the hand adjustment handle clock­wise until it stops. The arrow marking of the hand adjustment handle is in the blue area.
11. Set the actuator on the mixing valve axis
12. Insert the screw [6] with the serrated lock
washer and tighten the screw applying a torque of > 5 Nm
13. Set the operating switch back to Automatic operation
7. Set the mixing valve plugs [3] so that the nose [a] of the adapter [2] faces down. The mixing valve plugs seal the downward outlet (full bypass mode, cold) in this position

4.7 Replacement of the pump

The pump groups are constructed in such a way that pumps of different types and brands can be connected. If pumps and cable connections from other manufacturers are to be used, minor changes to the insulation may be required. They can be made by the installer.
18
2

4.8 Positioning of the electric cables

The electric cables must be installed by qualified personnel, in order to avoid endangering people's safety and material damage. The insulation half­shells were developed in such a way to ensure the greatest degree of flexibility possible with regard to cable arrangement in the insulation. There are appropriate recesses for cable harnesses and these enable side access to the insulation (2).
The correct mixing valve running direction for the heating cycle station HGM
If, after the unit has been reinstalled, the wrong running direction has been set on the mixing valve motor (controller adjusts to hot and the mixing valve moves to position 0, instead of 10, the two connections (brown and black cable) of the mixing valve motor must be interchanged.
Remove the mixing valve motor
To disassembly the mixing valve motor, lift up the cover on the rotating head of the motor and com­pletely unscrew the screw in the rotating head. The mixing valve motor cannot be removed.

4.9 Electrical wiring

DANGER!
All electrical installation work is to be per­formed by specialist companies. Disconnect the power supply when connecting the elec­trical terminals.
The pump and the mixing vale must be connected to the I/O module of the heat pump according to the wiring diagram that is enclosed in the heat pump documentation folder.
The mixing valve must be wired on the I/O module as follows:
Brown mixing valve cable (mixing valve opens) Black mixing valve cable (mixing valve closes) Blue mixing valve cable on N (neutral conductor)
If the controller used requires an inlet/return flow sensor, they must be inserted in the designated immersion sleeves.
All the connecting and sensor cables must be routed downward in the heating cycle station. To do this, corresponding slots are cut out on the rear of the thermal insulation shell, where the cable can be clamped. The inlet and return flow sensor must be secured against slipping out using the locking screw.
19
PE N A20 A21
-SMTIO
A20
Mixer 230V
M
N Open
-A20
Mixer
-Heating cycle floor
bl
br
sw
L-XN PE
A41 GND
-SMTIO
A41
Pump 0-10V
1
M
U N
-A41
Pump
Heating cycle floor
-Power supply A41
br
bl
gnge
ws
br
L
-X
N
PE
A42 GND
-SMTIO
A42
Pump 0-10V
1
M
U N
-A42
Pump
Heating cycle radiator
-Power supply A42
br
bl
gnge
-Heating cycle radiator
ws
br
-Heating cycle floor
Heating cycle floor
Closed
REMKO Heating cycle groups
Terminal connections when connecting to REMKO Heat pumps, types WKF & WKF compact
Fig. 13: Remko HGM / HGU connection terminals
20
Pump floor cycle
-Heating cycle pump heating cycle
-Heating cycle pump floor floor heating
Heating cycle pump floor
Heating cycle pump radiator
Pump radiator cycle
Unregulated 230 V
Unregulated 230 V
A
B
C
D
B
AB
A
HGM
HGU
KK
HK
FB
Fig. 14: Connection terminals for installing unregulated heating cycle pumps

4.10 Installation example

Fig. 15: Example hydraulic diagram
A: Outdoor unit B: WFK indoor unit C: Storage tank D: Second heat generator (max. 20 kW)
FB: Floor heating cycle HK: Heater heating cycle KK: Cooling cycle
21
REMKO Heating cycle groups

5 Troubleshooting

Fault description
Pump does not run when power supply is switched on
Pump makes noises
Power supply undervoltage
Power supply over­voltage
Motor jammed
Cause Remedy
Electrical fuse defective, pump has no power
Cavitation caused by insuffi­cient inlet pres­sure
Power supply overloaded
Faulty feed from the energy supply company
e.g. due to deposits
Check the fuses, eliminate the power interruption.
Increase the system pressure within the permissible area, check the delivery height setting and set a lower height if necessary
The motor is switched off in the case of overvoltage or undervoltage. It starts again automatically as soon as the voltage is again in the per­mitted area. SSM relay is active. Off: 165 V AC / On: 195 V AC
Faulty feed from the energy supply company. The motor is switched off in the case of overvoltage or undervoltage. It starts again automatically as soon as the voltage is again in the permitted area. SSM relay is active. Off: 265 V AC / On: 245 V AC
If the motor jams, a maximum of 5 restarts at 30 second intervals take place. If the motor remains jammed, it is switched off permanently. It can only be switched back on again by switching off the power for more than 30 seconds and then switching it on again. The unjamming programme runs during each start process. The SSM relay is active as long as the internal error counter is not ZERO.
Motor over­load
Short circuit/ earth leakage
Contact error The module is
Running empty
Deposits in the pump
Motor defective The motor is switched off after a short circuit. It is switched on again
not connected correctly. Con­nection between motor and module inter­rupted
Air in the pump The motor is switched off after a defined period of time when running
If the power consumption of the motor exceeds the limit for more than 60 seconds, the "Overload" error is reported. The motor is stopped and started again after a 30 second pause. If no overloading occurs within the next 2 minutes, the internal error counter is reset. Otherwise, the motor is switched off permanently after 5 unsuccessful restarts. This can only be reset by switching the power off for more than 30 seconds. The SSM relay is active as long as the internal error counter is not ZERO
after 30 seconds. The motor is switched off permanently after 5 short cir­cuits. This can only be reset by switching the power off for more than 30 seconds. The SSM relay is active as long as the internal error counter is not ZERO
If the contact between the motor and the module fails, the motor is switched off. A restart occurs after 30 seconds. After the motor has been switched off for the fifth time, it is switched off permanently. This can only be reset by switching the power off for more than 30 seconds. The SSM relay is active as long as the internal error counter is not ZERO.
under dry running conditions. It starts again after a delay of 30 seconds. If no dry run occurs within the next 2 minutes, the internal error counter is reset. Otherwise, the motor is switched off permanently after 5 unsuc­cessful restarts. This can only be reset by switching the power off for more than 30 seconds. The SSM relay is active as long as the internal error counter is not ZERO.
22
Fault description
Module over­temperature
Cable break Control is defec-
Cause Remedy
The air supply to the module cooling element is restricted
tive, control line is defective
The motor is switched off if an overtemperature situation occurs. A restart occurs after 30 seconds. After the motor has been switched off for the fifth time, it is switched off permanently. This can only be reset by switching the power off for more than 30 seconds. The SSM relay is active as long as the internal error counter is not ZERO.
A cable break is registered for the pumps that are controlled via a 0-10 V signal and that are equipped with software with a cable break function if the inbound control signal is less than 0.5 V. The pump turns at min­imum speed.
23
2
1
4
3
7
8
6
5
REMKO Heating cycle groups

6 Exploded view and spare parts

6.1 HGM

Exploded view of the unit
We reserve the right to modify the dimensions and design as part of the ongoing technical development process
Spare parts list
No. Designation Description HGM
1 Heating cycle pump Wilo Stratos Para 25 / 1-7 T1 1120909
2 Ball valve, red Ball valve with thermometer, dimensions: G 1 1/2" x G 1" 1121960
3 Ball valve, blue Ball valve with thermometer, dimensions: G 1 1/2" x G 1" 1121962
4 Thermometer, red Thermometer, inlet 1121965
5 Thermometer, blue Thermometer, return flow 1122965
6 Mixing valve 3-way mixing valve, flat sealing, connection G 1 1/2" 1121969
7 Adapter Pipe connection for mixing valve return flow 1122969
8 Insulation Heating cycle group insulator HGM, complete 1121961
Without figure
Mixing valve motor Actuator for mixing valve 230 V, running time 120 s 1121970
EDP
number
Screw connection set Screw connection, dimension: G 1" x 1 1/2" (two units) 1121963
When ordering spare parts, please always state the EDP number, unit number and unit type (see name plate)!
24

6.2 HGU

2
1
4
3
8
6
5
7
Exploded view of the unit
We reserve the right to modify the dimensions and design as part of the ongoing technical development process
Spare parts list
No. Designation Description HGU
1 Heating cycle pump Wilo Stratos Para 25 / 1-7 T1 1120909
2 Ball valve, red Ball valve with thermometer, dimensions: G 1 1/2" x G 1" 1121960
3 Ball valve, blue Ball valve with thermometer, dimensions: G 1 1/2" x G 1" 1121962
4 Thermometer, red Thermometer, inlet 1121965
5 Thermometer, blue Thermometer, return flow 1122965
6 Ball valve Ball valve, pump connection, G 1 1/2" AG x G 1 1/2" AG 1122960
7 Adapter Pipe connection for return flow 1123969
8 Insulation Heating cycle group insulator HGU, complete 1121961
Without figure
Screw connection set Screw connection, dimension: G 1" x 1 1/2" (two units) 1121963
When ordering spare parts, please always state the EDP number, unit number and unit type (see name plate)!
EDP
number
25
REMKO Heating cycle groups

7 Index

A
Assembly
Installation example ...................21
Installation of the actuator ..............16
Installation on the distributor ............15
Positioning of the electric cables .........19
Replacement of the pump ..............18
Wall installation ......................13
C
Components .......................8, 9, 12
D
Delivery heights ........................12
Dimensions ............................9
Pump ..............................11
Pump group ..........................8
E
Electric cabling .........................19
Electrical connection .....................20
Electrical power .........................12
Environmental protection ...................6
I
Install the actuator .......................16
Installation example .....................21
Installation of the actuator .................16
Intended use ............................5
Replace the inlet and return flow ........17, 18
Replace the inlet and the return flow ......17, 18
Replace the pump ......................18
Replacement of the pump .................18
S
Safety
Dangers of failure to observe the safety
notes ...............................4
General .............................4
Identification of notes ...................4
Instructions for the operator ..............5
Note for inspection work .................5
Note for installation work ................5
Personnel qualifications .................4
Safety-conscious working ..............4, 5
Unauthorised modification ...............5
Unauthorised replacement part manufacture . 5
T
Technical properties of the pump groups ......7
U
Unit data
Pump ..............................10
Pump groups .........................7
Unit dimensions .........................9
Pump ..............................11
Pump group ..........................8
Unit disposal ............................6
P
Packaging, disposal ......................6
Positioning of the electric cables ............19
Pressure losses .........................11
Pump group materials .....................7
R
Recycling ..............................6
W
Wall installation .........................13
Warranty ...............................5
26
Consulting
Thanks to intensive training, our consultants are always completely up-to-date in terms of technical knowledge. This has given us the reputation of being more than just an excellent, reliable supplier: REMKO, a partner helping you find solutions to your problems.
Distribution
REMKO offers not just a well established sales network both nationally and internationally, but also has exceptionally highly­qualified sales specialists. REMKO field staff are more than just sales representatives: above all, they must act as advisers to our customers in air conditioning and heating technology.
SFlbCustomer Service
Our equipment operates precisely and reliably. However, in the event of a fault, REMKO customer service is quickly at the scene. Our comprehensive network of experienced dealers always guarantees quick and reliable service.
REMKO INTERNATIONAL
… and also right in your neighbourhood! Make use of our experience and advice
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
REMKO GmbH & Co. KG Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 606-0 Telefax +49 5232 606-2 60 E-mail info@remko.de Website www.remko.de
Loading...