REMKO HGM, HGU Assembly And Operating Instructions Manual

Assembly and operating instructions
REMKO PUMP GROUPS HGM / HGU
Instructions for the Technician
0041-2017-11 Edition 2, en_GB
Read the instructions prior to performing any task!
Read these operating instructions carefully before commis­sioning / using this device!
These instructions are an integral part of the system and must always be kept near or on the device.
Subject to modifications; No liability accepted for errors or mis­prints!
Installation and operating instructions (translation of the orig­inal)

Table of contents

1 Safety and usage instructions............................................................................................................. 4
1.1 General safety notes....................................................................................................................... 4
1.2 Identification of notes...................................................................................................................... 4
1.3 Personnel qualifications.................................................................................................................. 4
1.4 Dangers of failure to observe the safety notes................................................................................ 4
1.5 Safety-conscious working............................................................................................................... 4
1.6 Safety instructions for the operator................................................................................................. 5
1.7 Safety notes for installation and inspection tasks........................................................................... 5
1.8 Unauthorised modification and changes......................................................................................... 5
1.9 Intended use................................................................................................................................... 5
1.10 Safety-conscious working............................................................................................................. 5
1.11 Warranty........................................................................................................................................ 5
1.12 Transport and packaging.............................................................................................................. 6
1.13 Environmental protection and recycling........................................................................................ 6
2 Technical data........................................................................................................................................ 7
2.1 Unit data for pump groups HGM / HGU.......................................................................................... 7
2.2 Unit dimensions and pump group components HGM..................................................................... 8
2.3 Unit dimensions and pump group components HGU...................................................................... 9
2.4 Pump unit data.............................................................................................................................. 10
2.5 Pump unit dimensions................................................................................................................... 11
2.6 Pressure losses............................................................................................................................. 11
2.7 Delivery heights and electrical power............................................................................................ 12
3 Unit description................................................................................................................................... 12
4
Installation and assembly.................................................................................................................. 13
4.1 Installation..................................................................................................................................... 13
4.2 Wall installation............................................................................................................................. 13
4.3 Installation on the distributor......................................................................................................... 15
4.4 Positioning of the electric cables................................................................................................... 16
4.5 Setting the mixing valve for the pump group HGM....................................................................... 17
4.6 Installation of the actuator for the pump group HGM.................................................................... 18
4.7 Replacement of the pump............................................................................................................. 19
4.8 Pump group layout........................................................................................................................ 20
4.9 Electrical connection..................................................................................................................... 21
4.10 Installation example.................................................................................................................... 22
5 Troubleshooting.................................................................................................................................. 23
6 Spare parts list for pump groups HGM / HGU.................................................................................. 25
7 Index..................................................................................................................................................... 27
3
REMKO PUMP GROUPS HGM / HGU
1 Safety and
usage instructions

1.1 General safety notes

Carefully read the operating manual before com­missioning the units for the first time. It contains useful tips and notes such as hazard warnings to prevent personal injury and material damage. Failure to follow the directions in this manual not only presents a danger to people, the environment and the system itself, but will void any claims for
.
liability Keep this operating manual and the refrigerant
data sheet near to the units.

1.2 Identification of notes

This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation.The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by sym­bols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.
DANGER!
CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or mate­rial and environmental damage.
NOTICE!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.
This symbol highlights useful tips and recom­mendations as well as information for efficient and fault-free operation.

1.3 Personnel qualifications

Personnel responsible for commissioning, opera­tion, maintenance, inspection and installation must be able to demonstrate that they hold a qualifica­tion which proves their ability to undertake the work.
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.
DANGER!
This combination of symbol and signal word warns of a situation in which there is immediate danger cause serious injury.
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury
, which if not avoided may be fatal or
WARNING!
.
1.4

Dangers of failure to observe the safety notes

Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.
In particular, failure to observe the safety notes may pose the following risks:
n The failure of important unit functions. n The failure of prescribed methods of mainte-
nance and repair
n Danger to people on account of electrical and
mechanical effects.
.

1.5 Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.
4
1.6 Safety instructions for the oper­ator
The operational safety of the units and compo­nents is only assured providing they are used as intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified per­sonnel.
n The existing regulations concerning accident
prevention must be adhered to.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with equipment parts or components
can lead to burns or injury
n Ensure that electrical energy does not pose a
risk.
n Regulations of the VDE and the local energy
supply company must be adhered to.
.

1.7 Safety notes for installation and inspection tasks

n The operator must ensure that all inspection
and installation work is carried out by author­ised and qualified personnel who have thor­oughly read the operating manual.
orks on the pump/system may only be car-
n W
ried out whilst at a standstill as a matter of prin­ciple.
n Appropriate hazard prevention measures must
be taken to prevent risks to people when per­forming installation, repair, maintenance or cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
n Regional regulations and laws as well as the
Water Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n The units and components must be kept at an
adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
n Safety devices may not be modified or
bypassed.
Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufacturer ensure safety use of other parts may invalidate liability for resulting consequences.
. The

1.9 Intended use

Due to the type and design of the pump group, it is only approved for operation as a heating cycle group. It serves to transport the operating medium of water into closed heating cycles.
Any different or additional use is a non-intended use. The manufacturer/supplier assumes no lia­bility for damages arising from a non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
The threshold values specified in the technical data must not be exceeded.

1.10 Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.

1.11 Warranty

For warranty claims to be considered, it is essential that the ordering party or its representative com­plete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the "Gen­eral business and delivery conditions". Further­more, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.

1.8 Unauthorised modification and changes

The operational safety of the pump group that was delivered is guaranteed only with intended use in accordance with section 1.9 of the operating instructions. Under no circumstances should the threshold values specified in the datasheet be exceeded.
5
REMKO PUMP GROUPS HGM / HGU

1.12 Transport and packaging

The devices are supplied in a sturdy shipping con-
. Please check the equipment immediately
tainer upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to children!

1.13 Environmental protection and recycling

Disposing of packaging
All products are packed for transport in environ­mentally friendly materials. Make a valuable contri­bution to reducing waste and sustaining raw mate­rials. Only dispose of packaging at approved collection points.
Disposing of the units and their components
For the manufacture of the units and components, only recyclable materials have been used. Help protect the environment by ensuring that the units or components (for example batteries) are not dis­posed of in household waste, but only in accord­ance with local regulations and in an environmen­tally safe manner, e.g. using authorised disposal and recycling specialists or council collection points.
6

2 Technical data

2.1 Unit data for pump groups HGM / HGU

Technical properties
Pump group HGM HGU
Maximum operating temperature °C 90
Max. operating pressure bar 10
IG threaded connections UNI EN 10226-1
AG threaded connections UNI ISO 228-1
Pump Wilo Stratos Para 25 / 1-7 T1
Compatible media Water, water-Glycol mixture (maximum 30%)
Thermometer measurement range 0-120°C, 30-250°F
Weight kg 6.9 5.85
Materials
Pump group HGM HGU
Ball valve and check valve
Body made of brass: UNI EN 12164 - CW617N UNI EN 12164 - CW614N
Hydraulic seals PTFE, Viton, EPDM
Motorised mixing valve
Body made of brass: UNI EN 12165 - CW617N ---
Turning part made of brass: UNI EN 12164 - CW614N ---
Hydraulic seals EPDM
Insulation half-shells
Body EPP
Body, seal
Body, therm. conductivity (20°C) W/mK 0.039
kg/m
3
60
Body, therm. conductivity (40°C) W/mK 0.041
7
2
1
4
3
6
7
5
4
1
=
2
=
5
=
3
=
4
=
REMKO PUMP GROUPS HGM / HGU

2.2 Unit dimensions and pump group components HGM

Dimensions
Fig. 1: Unit dimensions for pump group HGM
Pump group G G1 L H
HGM 1" IG
Components
1 1/2" AG
125 mm 363 mm
Fig. 2: Pump group components HGM
1: Circulation pump Wilo Stratos Para 25 / 1-7 T1 2: Ball valve 3: Ball valve with integrated check valve 4: Thermometer
5: Motorised mixing valve 6: Extension 7: Insulation
8

2.3 Unit dimensions and pump group components HGU

2
1
4
3
6
5
4
1
=
2
=
=
3
=
4
Dimensions
Fig. 3: Unit dimensions for pump group HGU
Pump group G G1 L H
HGU 1" F
Components
1 1/2" M
125 mm 363 mm
Fig. 4: Pump group components HGU
1: Circulation pump Wilo Stratos Para 25 / 1-7 T1 2: Ball valve 3: Ball valve with integrated check valve
9
4: Thermometer 5: Ball valve 6: Insulation
REMKO PUMP GROUPS HGM / HGU

2.4 Pump unit data

Technical data
Pump group HGM / HGU
Pump type Wilo Stratos Para 25 / 1-7 T1
Maximum delivery volume
Maximum delivery height m 7.0
Speed rpm 1200 - 4450
m
3
4.5
Mains voltage 1~230V ±
Energy Efficiency Index ( EEI ) £ 0.23
Frequency Hz 50/60 Hz
Insulation class F
Enclosure class IP 44
Rated input P1 W 5 - 70
Nominal width for pipe connection Rp
Connection flange thread G
Permitted ambient temperature °C + 40
Maximum relative humidity £ 95%
Permitted conveying media
Inch
es
Inch
es
Heating water (in accordance with VDI 2035/VdTÜV
Water/Glycol mixture: maximum mixture ratio is 1:1 (in
mixtures with Glycol, the delivery data of the pump
must be corrected according to the higher viscosity and
depending on the mixture ratio percentage.)
Ethylene/propylene glycol with corrosion protection
10% in accordance with DIN IEC 60038
1"
1 1/2"
T
ch 1466)
inhibitors
- Standard oxygen binding agent
- Standard corrosion protection agent
- Standard combination products
- Standard cooling brines
Permitted medium temperature °C 95
Maximum operating pressure at the pump bar 6.0
Weight kg 2.4
10

2.5 Pump unit dimensions

b4
b5
l
2
l
0
l
1
l
3
a
1
a
2
a
3
21
A
B
A
[m3/h]
B
[m3/h]
[mbar]
[mbar]
a a
Dimensions
Fig. 5: Pump unit dimensions
Wilo Stratos Para 25 / 1-7 T1
Dimensions in mm
l
0
180 116 32 94 90 56 138 42 41

2.6 Pressure losses

a
1
a
2
a
3
l
1
l
2
l
3
b
4
b
5
Fig. 6: Diagram of pressure losses in the pump group HGM / HGU
1: Operational mode; constant differential pressure 2: Operational mode; variable differential pressure A: Resistance / delivery height [mbar] B:
Delivery rate [m3/h]
a: Mixing valve R 3/4
11
2
1
2
1
4
3
5
REMKO PUMP GROUPS HGM / HGU

2.7 Delivery heights and electrical power

Fig. 7: Delivery heights and electrical power of the Wilo Stratos Para 25 / 1-7 T1pump
1: External operating mode via analogue-in 0-10V 2: External operating mode via pump shaft model
(PSM)

3 Unit description

These pump groups HGM / HGU enable circulation of the heat conducting medium via the inlet. The pump group HGM regulates the temperature of the heat conducting medium via a motorised mixing valve. This pump group with controllable tempera­ture is therefore ideal for operating normal heating systems with temperature regulation. T regulation of the Inlet takes place depending on the inlet and return temperatures of probes S12 and S11.
The pump groups comprise the following: Pump, ball valve for inlet and return flow, thermometer for inlet and return flow, check valve against the heating cycle and thermal insulation.
The pump group HGM also has an integrated mixing valve
The pump group with the heating cycle mixing valve consists of the components displayed in Fig. 8:
n Front part of the insulation (1) n Rear part of the insulation (2) n Insulation of the pump (3) n Unit inlet (4) equipped with secondary circuit
ball valve, a motorised mixing valve and a ther­mometer
n Unit return flow (5) equipped with secondary
circuit ball valve with an integrated check valve and a thermometer
emperature
Fig. 8: Unit components
The two insulation half-shells (1, 2) serve as heat insulation for the pump group and therefore enable energy to be saved. The pump insulation was developed to guarantee heat insulation and to pre­vent the electric motor from overheating. The check valve that is integrated into the body of the return flow's ball valve prevents incorrect circula­tion when the pump is switched of
f.
12

4 Installation and assembly

2
1
3
2

4.1 Installation

CAUTION!
Each individual hydraulic component must be installed by qualified personnel because the high temperatures and pressures of the liquid can cause personal injury
Possible installations are:
n Wall installation n Installation on the distributor
.

4.2 Wall installation

CAUTION!
You must adhere to the distance between the piping and the wall specified in point 7.
1. Remove the pre-installed pump group from the packaging.
2. Open the insulation cover half-shells by pulling the front side (1) and the rear side (2) apart.
3. Remove the insulation (3).
4. Remove the inlet (4) and the return flow (5).
5. Cut out the openings on the rear side of the
insulation (2).
13
2
4
5
6
7
3
REMKO PUMP GROUPS HGM / HGU
6. Install the pump group wall bracket on a suit-
able wall. The wall bracket is equipped with long holes to aid height adjustment. Fix the wall bracket to the wall using the enclosed wall plugs.
7. Attach the rear side (2) of the insulation half­shell to the wall bracket. Install the inlet (4) and the return flow (5) on the wall bracket by lifting the insulation slightly between the pipe axis and the wall surface is around 54 mm.
8. Use the screw connection enclosed in the packaging to install the piping for the inlet and the return flow; ensure that the connec­tions are suitable for the pipe dimensions (connections with flat seals are recom­mended). If a pump is connected in a series to the pump group (e.g. boiler pump), in prac­tice, a fixture to separate the heating cycles hydraulically is to be installed, in order to pre­vent a malfunction of the two pumps or the heat pump.
. So, the distance
9. T
10. Open the ball valve of the return flow (7).
11. Install the electric cables (see the positioning
12. Insert the pump's insulation (3).
urn the regulator of the return flow's ball valve (7) to an angle of 45°; in this position, the ball valve bypasses the check valve and nullifies the effect of the valve. This enables the water and the air that is to be bled in the filling phase to flow better. Fill the system and check for leaks.
of the cables section).
14
1
45
13. Close the pump group using the insulation half-shell (1).

4.3 Installation on the distributor

The pump groups can be installed on distributors with an integrated hydraulic compensator standard distributors with a separate hydraulic compensator and on series distributors. For optimum installation, the nozzles of the distributor should be at least 60mm away from the wall.
1. First carry out installation steps 1-4 for wall installation.
2. T
o aid installation, start the installation in the middle of the distributor and then continue with the outer connections; install the inlet (4) and the return flow (5) on the distributor using the screw connection enclosed in the packaging or using the required connecting pieces (flat-sealing connections are recom­mended).
, on
3. Insert the insulation half-shell (2); if the dis­tributor is installed too close to the wall, you must insert the rear side (2) of the two insula­tion half-shells before you install the inlet and the return flow (4 and 5).
15
2
2
3
2
1
2
REMKO PUMP GROUPS HGM / HGU

4.4 Positioning of the electric cables

The electric cables must be installed by qualified personnel, in order to avoid endangering people's safety and material damage. The insulation half­shells were developed in such a way to ensure the greatest degree of flexibility possible with regard to cable arrangement in the insulation. There are appropriate recesses for cable harnesses and these enable side access to the insulation (2).
4. Insert the insulation (3) by pushing down the top side of the rear insulation half-shell (2).
5. Continue as described in point (9) for wall installation.
6. Open the ball valve of the return flow again.
7. Install the electric cables (see: positioning of
the cables section).
8. Close the pump group using the front part of the insulation (1).
16
4.5 Setting the mixing valve for the
1
2
3
pump group HGM
The motorised mixing valve enables temperature regulation of the inlet by mixing hot or cold liquid. Regulation can be carried out manually using the rotary regulator or using an actuator
.
2. Move the rotary regulator (1) to the position where the arrow points to the value 10. This is the position in which there is no tempera­ture mixing.
The mixing valve that is integrated into the HGM has an integrated bypass that can be regulated. The bypass with the electrical actuator enables the advantages of inlet temperature control to be uti­lised. It enables the inlet temperature to be regu­lated if the return flow of the mixing valve is com­pletely closed. (Maximum fluctuation performance) The mixing valve has a turning angle of 90°.
In this way in the regulation area and prevents fluctuating tem­peratures, dangerous temperature spikes (e.g. in systems with underfloor heating) and continuous changes to the turning direction of the motor.
Attention: If there are large temperature differences between the temperature in the buffer tank and the temperature in the heating cycle, it is possible that the setpoint will not be reached even if the bypass is open. Obviously, the best possible regulation should be used.
To ensure precise calibration of the temperature, the heating cycle must be put into operation with the planned maximum inlet temperature. This is the only way to retain the setting precisely in oper­ation.
1. Install the rotary regulator (1) with the sup-
, it restricts the height of the temperature
plied screw
.
3. Activate the pump.
4. Loosen the bypass screw (2).
5. Position the bracket regulator (3) in order to
set the operating temperature and ensure that the bypass is closed completely as shown in the left picture in the diagram below and completely open as shown in the middle picture. T
ighten the screw (2).
17
2
4
3
5
1
2
8
1
REMKO PUMP GROUPS HGM / HGU
6. If regulation of the bypass is insuf
move the rotary regulator to the position that enables the desired temperature to be reached. Even if the rotary regulator was to be destroyed manually, the bypass still limits the inlet temperature.
ficient,

4.6 Installation of the actuator for the pump group HGM

The Actuator for the pump group is delivered with the components shown in the diagram.
Fig. 9: Installation of the actuator
1: Actuator 2: Ring with scale 3: Adapter for the mixing valve 5: Screw for fixing the drive
1. The ring with scale (2) is the reference point for the hot water proportion and must be aligned as shown in the right picture of the following diagram.
2. Insert the correctly-aligned ring (2) into the guide of the actuator (1).
3. Press and turn the rotary knob of the actuator fully in a clockwise direction and then release it.
4. Insert the adapter and screw in the locking
.
screw
18
4
3
5. Use the indent on the adapter as the refer­ence point.
6. Align the indent of the adapter (3) so that it corresponds to value 10 on the mixing valve.
8. Install the actuator cable and the heating cycle circulation pump on the regulator of the heat pump.
ou can obtain information about the terminal
Y connections from the installation instructions of the heat pump in the "Terminal connec­tions/legend" chapter.

4.7 Replacement of the pump

The pump groups are constructed in such a way that pumps of different types and brands can be connected. If pumps and cable connections from other manufacturers are to be used, minor changes to the insulation may be required. These can be made by the installer.
7. Install the actuator (1) in the position as shown in the diagram and fix everything with the locking screw
19
.
2
4
3
1
2 1
21
REMKO PUMP GROUPS HGM / HGU

4.8 Pump group layout

The distribution group with the motorised mixing valve can also be connected in a way that dif from the standard installation (inlet on the right and at the top). The possible installation configurations depend on the type of pump installed. The connec­tion options are shown in the diagrams below.
fers
1. Loosen the rotary valves (see the arrow) and uncouple the extension (2). Ensure that the flange is flat-sealing.
2. T
ranspose the installation positions of the
pump (1) and the extension (2).
Fig. 10: Pump group layout
1-4: Diagrams 1-4
As shown in diagram 1, the distribution group with the motorised mixing valve is delivered in the standard configuration; this means that the pump is on the right and the inlet on the top. The heating cycle group can be configured using the process shown in diagrams 2, 3 and 4.
3. Insert the flat seal and close the valves.
4. If necessary
applies to pumps that enable the motor to be aligned).
NOTICE!
Leave the ball valve with the red grip on the inlet with the pump and the ball valve with the blue grip on the return flow due to the flap valve. Adhere to the flow direction of the pump.
, turn the pump motor (this
20

4.9 Electrical connection

PE N A20 A21
-SMTIO
A20
Mixer 230V
M
N Open
-A20
Mixer
-Heating cycle floor
bl
br
sw
L-XN PE
A41 GND
-SMTIO
A41
Pump 0-10V
1
M
U N
-A41
Pump
Heating cycle floor
-Power supply A41
br
bl
gnge
ws
br
L
-X
N
PE
A42 GND
-SMTIO
A42
Pump 0-10V
1
M
U N
-A42
Pump
Heating cycle radiator
-Power supply A42
br
bl
gnge
-Heating cycle radiator
ws
br
-Heating cycle floor
Heating cycle floor
Closed
Terminal connections when connecting to REMKO Heat pumps, types WKF & WKF-compact
Fig. 11: Remko HGM / HGU connection terminals
21
Pump floor cycle
-Heating cycle pump heating cycle
-Heating
cycle pump floor floor heating
Heating cycle pump floor
Heating cycle pump radiator
Pump radiator cycle
Unregulated 230 V
Unregulated 230 V
A
B
C
D
B
AB
A
HGM
HGU
KK
HK
FB
REMKO PUMP GROUPS HGM / HGU
Fig. 12: Connection terminals for installing unregulated circulation pump heating cycles

4.10 Installation example

Fig. 13: Example hydraulic diagram
A: Outdoor unit B: WFK indoor unit C: Storage tank D: Second heat generator (max. 20 kW)
FB: Floor heating cycle HK: Heater heating cycle KK: Cooling cycle
22

5 Troubleshooting

Fault description
Pump does not run when power supply is switched on
Pump makes noises
Power supply undervoltage
Power supply overvoltage
Motor jammed
Cause Remedy
Electrical fuse defective, pump has no power
Cavitation caused by insuf cient inlet pres­sure
Power supply overloaded
Faulty feed from the energy supply company
e.g. due to deposits
Check the fuses, eliminate the power interruption.
Increase the system pressure within the permissible area, check the
fi-
delivery height setting and set a lower height if necessary
The motor is switched off in the case of overvoltage or undervoltage. It starts again automatically as soon as the voltage is again in the per­mitted area. SSM relay is active. Of
Faulty feed from the energy supply company. The motor is switched off in the case of overvoltage or undervoltage. It starts again automatically as soon as the voltage is again in the permitted area. SSM relay is active. Of
If the motor jams, a maximum of 5 restarts at 30 second intervals take place. If the motor remains jammed, it is switched of only be switched back on again by switching off the power for more than 30 seconds and then switching it on again. The unjamming programme runs during each start process. The SSM relay is active as long as the internal error counter is not ZERO.
f: 165 V AC / On: 195 V AC
f: 265 V AC / On: 245 V AC
f permanently. It can
Motor over­load
Short circuit/ earth leakage
Contact error The module is
Running empty
Deposits in the pump
Motor defective The motor is switched off after a short circuit. It is switched on again
not connected correctly nection between motor and module inter­rupted
Air in the pump The motor is switched off after a defined period of time when running
. Con-
If the power consumption of the motor exceeds the limit for more than 60 seconds, the "Overload" error is reported. The motor is stopped and started again after a 30 second pause. If no overloading occurs within the next 2 minutes, the internal error counter is reset. Otherwise, the motor is switched of only be reset by switching the power off for more than 30 seconds. The SSM relay is active as long as the internal error counter is not ZERO
after 30 seconds. The motor is switched of circuits. This can only be reset by switching the power off for more than 30 seconds. The SSM relay is active as long as the internal error counter is not ZERO
If the contact between the motor and the module fails, the motor is switched off. A restart occurs after 30 seconds. After the motor has been switched off for the fifth time, it is switched off permanently. This can only be reset by switching the power off for more than 30 seconds. The SSM relay is active as long as the internal error counter is not ZERO.
under dry running conditions. It starts again after a delay of 30 seconds. If no dry run occurs within the next 2 minutes, the internal error counter is reset. Otherwise, the motor is switched of cessful restarts. This can only be reset by switching the power off for more than 30 seconds. The SSM relay is active as long as the internal error counter is not ZERO.
f permanently after 5 unsuccessful restarts. This can
f permanently after 5 short
f permanently after 5 unsuc-
23
REMKO PUMP GROUPS HGM / HGU
Fault description
Module over­temperature
Cable break Control is defec-
Cause Remedy
The air supply to the module cooling element is restricted
tive, control line is defective
The motor is switched off if an overtemperature situation occurs. A restart occurs after 30 seconds. After the motor has been switched of for the fifth time, it is switched off permanently. This can only be reset by switching the power off for more than 30 seconds. The SSM relay is active as long as the internal error counter is not ZERO.
A cable break is registered for the pumps that are controlled via a 0-10 V signal and that are equipped with software with a cable break function if the inbound control signal is less than 0.5 V imum speed.
. The pump turns at min-
f
24

6 Spare parts list for pump groups HGM / HGU

21
9
3
4
5
7
8
10
6
11 13
12
14
Spare parts illustration
We reserve the right to modify the dimensions and design as part of the ongoing technical development process
25
REMKO PUMP GROUPS HGM / HGU
Spare parts list
No. Description Description HGM HGU
1 Ball valve, red
2 Ball valve, blue
3 Ball valve
4 Mixing valve
Thermometer
5
with dual scale
6 Actuator
With integrated thermometer 0-120°C (30 ­250°F). Pump connection with rotary nut 1 ½“ IG. Flat seal D45 x d33.3 x 2., dimension: G 1"1/2 UWM x G 1"
With integrated thermometer 0-120°C (30 ­250°F). Pump connection with rotary nut 1 ½“ IG. Flat seal D45 x d33.3 x 2., dimension: G 1"1/2 UWM x G 1"
Pump connection with rotary nut 1 ½“ IG. Flat seal D45 x d33.3 x 2., dimension: G 1"1/2 AG x G 1"1/2 UWM
With integrated controllable bypass. Pump con­nection with rotary nut 1 ½“ IG. Equipped with plastic rotary grip for manual control. Flat seal D45 x d33.3 x 2., dimension: G 1"1/2 AG x G 1"1/2 UWM x 1" AG,
Scale: 0 - 120°C (30 - 250°F), dimension: D 52 mm
Actuator for mixing valve with three-point regu-
, speed 120s/90°, turning angle 90°, torque
lator 10 (Nm), voltage 230V, frequency 50Hz. Com­plete with locking screw and pin to fix the actuator. Speed: 120 s (90°), Controller: 3-point
flow: 6 and 10 m3/h
EDP
number
1120960 1120960
1120962 1120962
--- 1120961
1120969 ---
1120965 1120965
1120970 ---
EDP
number
7 Connection-fitting set
8 Wall-mounted bracket
9 Rotary regulator
Circulation pump Wilo
10
Stratos Para 25 / 1-7
Extension
11
with T
-connection
12 Extension for HGM Dimension: G 1"1/2 x G 1"1/2 1120967 ---
13 Extension for HGU Dimension: G 1"1/2 x G 1"1/2 --- 1120964
Check valve /
14
gravity brake
When ordering spare parts, please always state the EDP no., unit number and unit type (see name plate)!
Sockets with flat seal. Dimension: G 1" x G 1"1/2 UWM
For pump group including screws and wall plugs. Hole distance: 90 mm
With locking screw for manual regulation of the mixing valve
Heavy-duty model (EEI <0.23 in accordance with EVP guidelines) equipped with a 1m-long cable. Dimension: G 1"1/2 x G 1"1/2. Distance: 180 mm. Maximum delivery height: 7 m
Dimension: G 1"1/2 UWM x G 1"1/2 AG x G 1" UWM
1102062 1102062
1120963 1120963
1120966 1120966
1120972 ---
1120909 1120909
1120971 ---
26

7 Index

C
Components ....................... 8,
9, 12
D
Delivery heights ........................ 12
Dimensions ............................. 9
Pump .............................. 11
Pump group .......................... 8
E
Electric cabling ......................... 16
Electrical connection ..................... 21
Electrical power .........................12
Environmental protection ...................6
I
Install the actuator .......................18
Installation
Installation example ................... 22
Installation of the actuator .............. 18
Installation on the distributor ............ 15
Positioning of the electric cables ......... 16
Pump group layout .................... 20
Replacement of the pump .............. 19
Setting the mixing valve ................ 17
Wall installation ...................... 13
Installation example ..................... 22
Installation of the actuator ................. 18
Intended use ............................ 5
P
Packaging, disposal ...................... 6
Positioning of the electric cables ............ 16
Pressure losses .........................11
Pump group layout ...................... 20
Pump group materials ..................... 7
R
Recycling .............................. 6
Replace the pump ...................... 19
Replacement of the pump ................. 19
S
Safety
Dangers of failure to observe the safety
notes ............................... 4
General ............................. 4
Identification of notes ................... 4
Instructions for the operator .............. 5
Note for inspection work .................5
Note for installation work ................ 5
Personnel qualifications ................. 4
Safety-conscious working ..............4, 5
Unauthorised modification ...............5
Unauthorised replacement part manufacture . 5
Set the mixing valve ..................... 17
Setting the mixing valve .................. 17
T
Technical properties of the pump groups .......7
U
Unit data
Pump .............................. 10
Pump groups ......................... 7
Unit dimensions ......................... 9
Pump .............................. 11
Pump group .......................... 8
Unit disposal ............................ 6
W
Wall installation ......................... 13
Warranty ............................... 5
27
Consulting
Thanks to intensive training, our consultants are always completely up-to-date in terms of technical knowledge. This has given us the reputation of being more than just an excellent, reliable supplier: REMKO, a partner helping you find solutions to your problems.
Distribution
REMKO offers not just a well established sales network both nationally and internationally, but also has exceptionally highly­qualified sales specialists. REMKO field staff are more than just sales representatives: above all, they must act as advisers to our customers in air conditioning and heating technology.
SFlbCustomer Service
Our equipment operates precisely and reliably. However, in the event of a fault, REMKO customer service is quickly at the scene. Our comprehensive network of experienced dealers always guarantees quick and reliable service.
REMKO INTERNATIONAL
… and also right in your neighbourhood! Make use of our experience and advice
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
REMKO GmbH & Co. KG Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 6 06-0 Telefax +49 5232 6 06-260 E-mail info@remko.de Website www.remko.de
Loading...