Read these instructions carefully before setting up/operating the unit!
Our guarantee becomes null and void if the unit is used improperly or if
modifications are made to the supplied unit.
Electronic Clock Thermostat
REMKO ATR-3
Contents Page
Functionality 4
Operating Controls 5
LCD Display of the Timer 6
Day and Night Temperature 6
Frost Protection Temperature 6
Hand Button 6
Off 6
Reset 6
Setting the Clock 7
Selecting the Operating Mode 7
Note: Always keep these operating instructions near or on the unit.
G
Contents Page
Setting the Timer 8
Setting the Functions 9
Setting the Parameters 10
Installation Instructions 10
Mounting the Control Unit 12
Mounting the Sensors 12
Settings for REMKO DVL 13
Wiring Diagram 14
Dimensions 14
Technical Data 15
3
Page 4
Functionality
Differential temperature control 2 sensor operation
The ATR-3 electronic clock thermostat gradually controls the speed of
REMKO DVL ceiling fans between 1 and a maximum of 14 and controls
a warm air heater.
The unit works with two sensors: a room temperature sensor at operating height and a ceiling temperature sensor. Unused warm air that rises
to the ceiling in high rooms is measured by the ceiling temperature sensor.
If the room temperature falls below the set target temperature
(adjustment knobs A und B) and, at the same time, the ceiling temperature is above the room temperature by a set differential value
(adjustment knob C), the REMKO DVL ceiling fans start running and
transport the warm air down. The warm energy from the ceiling area is
can be used again in the work area.
If the difference in temperature increases, the fan speed also increases
up to the maximum speed. The minimum and maximum fan speeds are
adjustable (adjustment knobs F and G). The fan performance is displayed by indicators (M) on the display of the weekly clock timer (K).
If the room temperature falls by a specific, adjustable value (adjustable
knob E) below the target value, the heat also switches on. The operating
mode is displayed by a LED (N)
A digital weekly clock timer with power reserve makes it possible to program heating and cooling off periods.
Proportional control 1 sensor operation
To meet special requirements, the unit can also be used for pure proportional control. In this case, the “Heating” and “Cooling” operating modes
may be selected.
In the 1 sensor mode, only the room temperature is measured. If the target value of the room temperature goes above or falls below the value
set on the control mechanism Xp (D), the ceiling fans start running.
If, during “Heating” mode, the room temperature falls by a specific, adjustable value below the target temperature, the heat also switches on.
If the heating relay is not regulated during “Cooling” mode, the air is only
circulated.
In the "Setting the Functions" menu, the operator can switch from differential temperature control to proportional control and from heating to
cooling is performed (see page 9).
The second sensor does not have a function. It can be used as a place
to perform measurements (display for 3 seconds after pressing the SET
program button).
4
Page 5
Operating Controls
H I J K
L
M
O
F
G
N
E D C B A
A Adjustment knob for the day temperature (target temperature)
B Adjustment knob for the night temperature (target temperature)
C Adjustment knob for the differential temperature (room to ceiling)
D Adjustment knob for the proportional temperature control
E Adjustment knob for the activation point of heating requirement
F Adjustment knob for the minimum speed of the ceiling fans
G Adjustment knob for the maximum speed of the ceiling fans
H Program buttons (progr. the clock, selecting the operating mode)
I Reset button (indented)
J Operating mode indicators
K Weekly clock timer display
L Heating/Cooling indicators (only for proportional control 1 sensor)
M Fan speed indicators
N LED display heating ON
O Terminal strip with fuse (6,3 A)
The values set in the figure above are only reference values and can vary from actual
values.
5
Page 6
LCD Display of the Clock Timer
The timer, day of the week and current temperature of the temperature sensor are shown on the
LCD display. By pressing the SET program button, the temperature of the 2nd temperature sensor can be displayed for approx. 3 seconds.
Day and Night Temperature
The target values for day and night temperature can be set independently of
one another and are standard for the control depending on the operating
mode (day or night operation). The minimum target values can be limited to
5°C by an internal setting.
Frost Protection Temperature
The frost protection temperature is fixed at 5 °C. By pressing the two program buttons + and – at the same time, the frost protection temperature can
be selected.
Hand Button
The > button makes it possible to change the current temperature operation (comfort temperature / cooling temperature) in automatic mode. The se-
lected temperature mode is displayed by indicators on the right-hand side of
the display. This function is deleted the next time the program is opened.
Off
By pressing the two program buttons ¹ and + at the same time, the control
is switched off. The operating mode is no longer displayed on the right-hand
side of the display. The unit continues to record the current temperature but
all control functions are completely switched off.
Reset
There are two different reset options:
1. Start up reset:
The RESET button makes impossible to restart the unit after operation has
been to interrupted due to a malfunction. The clock must be reset but the
program and parameter settings are retained.
2. Global reset:
To force the unit to restart with the factory settings, the buttons RESET, +
and – must be pressed at the same time. After the RESET button is released, the buttons + and – must be held down until the version number
(r 10...) appears on the display. The clock must be reset, Any previously entered individual timer program and any parameter settings are lost.
6
Page 7
Setting the Clock
The clock can be set once the ¹ program button
has been held down for 3 seconds or after the
unit restarts following a reset. If the clock has not
yet been reset, it blinks on the display.
When you press the SET program button, you are taken to the desired setting option (Hours -> Minutes -> Day of the week). The selected option
blinks on the display.
By pressing one of the program buttons + or –, the value of the selected option can be changed and the selection confirmed by pressing the SET button.
After confirming the day of the week, the clock starts accurate to the second. The unit returns to the operating mode from which the “
menu was accessed. If no button is pressed within 1 minute, the current
time automatically appears again.
Programming example: Monday, set 10:16
Display Button Explanation
1.
2. 20:30 +/- Hours blinking; change setting with [-]
3. 10:00 SET Confirm entry
4. 10:00 +/- Minutes blinking; change setting with [+]
5. 10:16 SET Confirm entry
6.
*
7.
*
¹
+/- Day of the week blinking; change setting with [+/-]
SET Confirm entry and transmit programming
Change time setting
Set Clock“
Selecting the Operating Mode
The main operating modes are selected by
pressing one of the three program buttons on the
left. You can select from the following modes:
Automatic ¹, Comfort á(continuous) and Cooling (continuous).
The Off and Frost protection T modes can be set by pressing the top and
middle or bottom and middle program buttons on the left at the same time.
The selected operating mode is displayed by indicators on the right-hand
side of the display. In the
tors also shows the currently valid temperature control (Comfort or Cooling).
No indicator is displayed in the
Automatic operating mode, one of the two indica-
Off operating mode.
7
Page 8
Entering a Timer Program
The timer program can be entered after the PROG
program button was pressed briefly. The program
point number appears on the display (PO1 to P16),
the corresponding time and day of the week on
which the respective temperature mode (Comfort temperature or Cooling temperature; see indicator on the right) will go into
effect.
When you press the SET program button, you are taken to the desired setting option (Program point number -> Time -> Day -> Temperature mode).
Each selected setting option blinks on the display.
By pressing the + or – program buttons, the value of the selected option can
be changed and your selection confirmed by pressing the SET button.
If you press the PROG program button while the program point number is
blinking, the unit returns to the operating mode from which the
“Enter Time Program” menu was accessed.
Inactive program points are identified by a - -:- - instead of the time.
The following are standard presets made at the factory:
Mo – So: starting at 06:00 o’clock Comfort temperature
Mo – Fr: starting at 22:00 o’clock Cooling temperature
Sa – So: starting at 23:00 o’clock Cooling temperature
There are several options for setting the days of the week:
Individual days Different activation times
Monday - Friday Same activation times
Monday - Saturday Same activation times
Monday - Sunday Same activation times
Saturday - Sunday Same activation times
Programming example:
Change P02 to: MO - SA, starting at 18:30; night operation; (P02)
Display Button Explanation
1. PROG Set timer program (change)
2. 22:00 P01 +/- Program selection P01 blinking; change setting with [+]
3. 22:00 P02 SET Confirm entry
4. 22:00 +/- Time setting blinking; change setting with [-]
5. 18:30 SET Complete entry
6.
' ' ' ' '
7.
' ' ' ' '
8.
9. P02 PROG P02 blinking; end programming with [PROG]
+/- Days blinking; change setting with [+]
SET Confirm entry
SET Arrow blinking next to night operation; keep setting
8
Page 9
Setting the Functions
If you press the PROG program button for 6 seconds, you are taken to a menu where various basic functions can be set. The functions are
shown on the left-hand side of the display and
the corresponding value or status on the right.
When you press the SET program button, you are taken to the desired setting option. The setting option blinks on the display.
By pressing the + or – program buttons, the value of the selected setting options can be changed and your selection confirmed by pressing the SET
button.
After confirming the last function, the unit returns to the operating mode from
which the
Make the following settings to use the unit with REMKO ceiling fans:
Programming: differential temperature control, 2 sensor operations
1. PROG Press for 6 seconds = Setting the functions
Differential/proportional control
(Setting: differential control)
Temp. limit below 5°C (Setting: 0)
Rotational direction analog output (Setting: 0-1)
Differential/proportional control
(Setting: proportional control)
Heating / Cooling (Setting: cooling)
9
Page 10
Setting the Parameters
When you press the PROG programming button
for 3 seconds, you are taken to a menu where the
various control parameters can be set. The values
to be set are not required for controlling the
REMKO ceiling fans. If you end up at this menu
by mistake, press the buttons below to exit the menu.
Programming instruction
Display Button Explanation
1. Display PROG Press for 3 seconds = Parameter setting
2. diFH 1.0 SET Confirm entry
3. AnLo 0 SET Confirm entry
4. AnHi 100 SET Confirm entry and end programming
Installation Instructions
For the authorised electrical installation personnel!
• Before mounting the temperature control, determine the following:
1. Number and mounting locations for the ceiling fans
2. Position of the sensors
3. Mounting location of the control unit
4. Dimensions and placement of power and control lines
• Follow the mounting and operating instructions for the ceiling fans. To-
tal power supply max. 6.3 A.
• Connection and service may only be performed by authorised electri-
cal personnel.
• Prior to performing any work on the unit, all power lines must be free
of electrical current and secured against switching on again.
• The connections for power lines, ceiling fans, temperature sensors
and any control lines for controlling a heater must be made in accordance with the wiring diagram on page 14.
• The unit made only be connected to lines that are permanently at-
tached in closed, dry rooms.
10
Page 11
• When installing the unit, make sure that the electrical lines, for exam-
ple, power supply and relay connection lines, cannot come into contact with low-current supply lines, such as sensor lines (minimum distance 4 mm for basic isolated line conductors).
• Make sure that there is adequate protection to prevent connection
conductors from becoming loose that meets the requirements of EN
60730 Part 1. This can be achieved, for example, by securing the lines
with cable bindings.
• Compliance with VDE 0100, EN 60730, Part 1, as well as all regula-
tions of the local EVU must be assured.
• Use the sensor lines in accordance with the requirements. Observe
the maximum line length and required minimum cross-sections!
Max. line length Line cross-section (Cu)
30 m 0.50 mm²
45 m 0.75 mm²
60 m 1.00 mm²
90 m 1.50 mm²
Caution: The unit can be damaged if it is connected improperly!
We are not liable for damages that are the result of incorrect con-
G
nection and/or improper use!
Note: If the unit does not function as expected, first check the
G
power supply and that the unit has been properly connected.
Note: When the indicators in the lower area of the weekly clock
timer display are blinking, this indicates that the ceiling fans have
G
been separated from the control unit as a result of a defect.
Operation/handling which does not comply with these
instructions is prohibited! In cases of non-compliance, we
assume no liability and the guarantee becomes null and void.
For the guarantee to be valid, the purchaser or his customer must
completely fill out the
units and send it back to REMKO GmbH & Co. KG.
"guarantee certificate" enclosed with all
11
Page 12
Mounting the Control Unit
The temperature control must be mounted outside of heavily trafficked
areas in a place that is easily accessible for making settings. If it is generally accessible, it must be protected against unauthorised use.
The supplied drilling stencil makes the
temperature control easier to install. The
attachment points can also be found in
the drawing to the left. Mounting materi-
145
Figures in mm
als must be supplied by the customer.
After the unit has been mounted, the in-
stalled lines are inserted from below into
99 99
the housing through the supplied screw
attachments once the lead-throughs
have been removed.
Mounting the Sensors
2 KTY temperature sensors are required to measure the differential temperature.
The upper temperature sensor
is installed in the ceiling area
min. 3 m
Temperature
Fan
Temperature
sensor, lower
1,5...2,0 m
sensor, upper
If the temperature sensor is mounted on a cold, outside wall, an insulation panel must be installed between the wall and the sensor by the customer.
The temperature sensors are connected to the temperature control with
2-wire lines. The connections are polarised. Make sure that the terminals
are assigned correctly: “LOWER” temperature sensor terminals 5 + 6;
“UPPER” temperature sensor terminals 6 + 7.
Specifications for checking proper operation of the KTY temperature
sensor:
Þ at 20°C: resistance value approx. 1879 Ω
Þ at 30°C: resistance value approx. 2035 Ω
and should have a minimum distance of 3 m to the ceiling fan.
Do not mount the sensor close
to air intake and outlet ducts.
The lower temperature sensor is
attached at a height of approx.
1.5 m and should not be in the
direct vicinity of the air current
from the ceiling fan.
12
Page 13
Settings for REMKO ceiling fans
Name Symbol
Switch differential
heating
Target value
minimum
Adjustment knob for
target temperature
day
Adjustment knob for
target temperature
night
Adjustment knob for
temperature
difference
Adjustment knob for
proportional
temperature control
diFH ± 0.1K.± 3.0K ± 02K
Sunt 0°C/5°C 0°C
â 0°C to 30°C
0°C to 30°C
dT 1K to 10K
Xp 1K to 5K 5K
Adjustment
range
Recommended
factory setting
Desired
temperature
Desired
temperature
Desired
differential
temperature
Customer
setting
Adjustment knob for
heating ON
Adjustment knob for
minimum speed
Adjustment knob for
maximum speed
Heating -10K to -1K -3K
Umin -..... + Fan speed very low
Umax - ..... + Maximum fan speed
The recommended factory settings help in programming and setting the
unit for most applications.
Different setting values can be adjusted to customer needs based on
structural givens and/or application-specific areas of use.
13
Page 14
Wiring Diagram
In connection with REMKO DVL
315 mA t
123456789
Room
Raum-fühler
sensor
Dimensions
242115
215
10 11 12 13 1415 16 1718 19 20 21 22 23 24 25 26
HeizungL' N'N LPE PE
Heating
Ceiling
Decken-fühler
sensor
Heizungs-
ansteuerung
Deckenventilator
Heat control
185
60
70
Ceiling fan
REMKODVL
REMKO DVL
Netzzuleitung 230V~ / 50 Hz
Power supply 230 V~ / 50 Hz
9999
15145
L
N
PE
6,3 A t
Front view Side view Drilling stencil
We reserve the right to make changes to dimensions and design in the interest of
technical progress.
14
Page 15
Technical Data
Temperature range
(Day and night temperature)
Temperature difference dT 1 to 10K, adjustable
Proportional control Xp 1 to 5K, adjustable
Heating
Clock timer
Sensor KTY semi-conductor sensors (polarised)
Operating current 230V AC, +10%, -15%
Internal consumption approx. 5 VA
Outputs: Fan output
Heating relay isolated contact (shutter)
Additional relay
0 to 30°C, adjustable; to 5 to 30°C
can be limited by an internal setting
-1 to -10K, distance from target value
adjustable
Electronic weekly clock timer,
power reserve clock approx. 10 minutes,
program is permanently saved
approx. 80 to 230 V gradually increasing
current (phase control) for the fan
isolated contact (two-way contact)
(switches on/off with phase control)
Analog output 0-10V, parallel to the phase control (Xp)
6,3A, 230V AC fan on the phase control
Max. line load currents
Housing Dimensions 242 x 185 x 115 mm (W x H x D)
Attachment wall-mounted
Protection type IP 54 (protected from spraying water)
Protection class Il in accordance with DIN EN 60335-1
Weight approx. 1500 g
10 (4)A, 250V AC heating relay
2 (2)A, 250V AC additional relay
1 mA max. on the analog output (0...10 V)
15
Page 16
REMKO GmbH & Co. KG
Klima- und Wärmetechnik
D-32791 Lage • Im Seelenkamp 12
D-32777 Lage • PO Box 1827
Phone +49 (5232) 606 - 0
Fax +49 (5232) 606260
E-Mail: info@remko.de
Internet: www.remko.de
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.