REMEHA P 500 Technical Information

Supplied By www.heating spares.co Tel. 0161 620 6677
Technical information
Remeha P 500
Remeha P500
• Pressurized boiler
• Heat output: 635 - 1900 kW
Supplied By www.heating spares.co Tel. 0161 620 6677
TABLE OF CONTENT
Remeha P 500
Preface 3
1 Description of the unit 3
1.1 General 3
1.2 Burners 3
2 Construction data 3
2.1 General 3
2.2 Sections 3
2.3 Casing 3
3 Technical data and dimensions 4
3.1 Dimensions 4
3.2 Technical data 4
3.3 Quotation specifi cations 5
4 Output data 5
4.1 Boiler effi ciency 5
4.2 Combustion effi ciency 5
5 Application data 5
5.1 L.P.H.W. version 5
5.1.1 Water temperature 5
5.1.2 Water pressure 5
5.1.3 Flow rate 5
5.1.4 Water treatment 6
5.2 Economisers 6
5.3 Flue gas discharge 6
5.4 Noise production 6
7 Assembly guidelines and installation requirements 7
7.1 General 7
7.2 Water connections 7
7.3 Boiler assembly 7
8 Instrument panels 8
8.1 Equipment contents 8
8.2 Instrument panel High/Low with hours run meters 8
8.3 Wiring diagram instrument panel High/Low with hours run meters 1 9
9 Commissioning 10
9.1 Pressurized boiler with gas burner 10
9.1.1 Commissioning procedure 10
9.1.2 Putting out of operation 10
9.2 Pressurized boiler with oil burner 10
9.2.1 Commissioning procedure 10
9.2.2 Putting out of operation 10
10 Fault Finding 11
11 Maintenance recommendations 11
11.1 General 11
11.2 Maintenance instructions 11
6 Installation requirements 7
6.1 Installation recommendations in the boiler house 7
Supplied By www.heating spares.co Tel. 0161 620 6677
PREFACE
These technical instructions contain useful and impor­tant information for the correct operation and maintenan­ce of the Remeha boiler, model P200 Read these instructions carefully before putting the boi­ler into operation; familiarise yourself with its control functions and operation, strictly observing the instructi­ons given. Failure to do so may invalidate warranty or prevent the boiler from operating. A competent Engineer, with the relevant certifi cation (i.e. CORGI, ACOPS, IEE regs. etc) must carry out the instal­lation and commissioning of the boiler. On completion a copy of the boiler log / commissioning sheet should be returned to Broag Ltd for record purpo­ses.
1 DESCRIPTION OF THE UNIT
1.1 General
High effi ciency pressurised boiler, suitable for use with natural gas and light oil, by means of a pressure jet burner. Also available with a condensing unit (ECO) (for natural gas only). The boiler meets the requirements of the CE regulations in the following directives:
- Gas appliance directive no. 90/396/EEC
- Electrical low voltage directive no. 73/23/EEC
- E.M.C. directive no. 89/336/EEC
- Effi ciency directive no. 92/42/EEC. Classifi cation type for evacuation of the combustion pro­ducts: B23.
If you have any questions, or if you need more informa­tion about specifi c subjects relating to this boiler, or it’s installation please do not hesitate to contact us. The data published in these technical instructions is based on the latest information (at date of publication) and may be subject to revisions. We reserve the right to continuous development in both design and manufacture, therefore any changes to the technology employed may not be retrospective nor may we be obliged to adjust earlier supplies accordingly.
1.2 Burners
In principle all CE-approved pressure jet burners are sui­table, subject to prior adjustment to the boiler capacity and boiler construction. The individual boiler satisfi es inspection requirement for central heating boilers.
2 CONSTRUCTION DATA
2.1 General
The boiler block consists of cast iron sections, which are assembled by means of tapered nipples. The boiler is a three-pass design. The boiler block is insulated with a 100-mm thick layer of glass wool.
2.2 Sections
The sections are made of pearlitic cast iron. Weights and measures of the sections:
- Front section: 220 kg H x W = 1252 x 1130mm
- Intermediate section: 250 kg H x W = 1238 x 1130 mm
- Rear section: 250 kg H x W = 1238 x 1130 mm
2.3 Casing
Steel casing, fi nished with a high-quality insulation. The front door is suitable for left or right opening as desired.
Fig. 01 Remeha P500
IL50
Supplied By www.heating spares.co Tel. 0161 620 6677
3 TECHNICAL DATA AND DIMENSIONS
3.1 Dimensions
Remeha P 500
Front view
Side view Rear view
Flow NG 150 - DIN2633 Return NG 150 - DIN2633 Flue ØD ext.
Flanges in accordance with BS 4505 PN 16
Fig. 02 Dimensions
00.15D.79.00006
3.2 Technical data
Number of sections 9 10 11 12 13 14 15 16 17 18 19 20
Nominal heat output kW 635 750 865 980 1095 1210 1325 1440 1555 1670 1785 1900
Nominal heat input
Hi /
NCV
Hs /
GCV
A mm 1350 1500 1650 1800 1950 2100 2250 2400 2550 2700 2850 3000
kW 706 834 962 1090 1218 1341 1468 1592 1719 1846 1973 2100
kW 784 926 1068 1210 1352 1488 1630 1767 1908 2049 2190 2331
B mm 1660 1810 1965 2115 2265 2415 2565 2715 2870 3020 3170 3320
Dimensions
C mm 1270 1420 1570 1720 1870 2020 2170 2320 2470 2620 2770 2920
ØD mm 400 400 400 400 500 500 500 500 500 500 500 500
t =
Water
resistance
Water contents litre 495 550 605 660 715 770 825 880 935 990 1045 1100
10°C
t =
20°C
mbar 149 166 180 194 189 200 213 234 262 295 337 382
mbar 37 42 45 47 49 50 53 59 66 74 84 96
Supplied By www.heating spares.co Tel. 0161 620 6677
Boiler weight (dry) kg 2650 2910 3175 3435 3695 3955 4220 4480 4740 5005 5265 5525
Combustion chamber
resistance
Combustion gas side
content
Flue gas flow rate kg/h 1102 1302 1502 1702 1901 2081 2292 2485 2683 2882 3080 3278
1)
mbar 1.7 2.3 3.0 3.8 3.9 4.8 5.0 5.9 5.5 6.0 6.5 7.0
3
m
0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9
Table 01 Technical data
1)
Determined with 20 % excess air.
3.3 Quotation specifi cations
- Heat exchanger manufactured from corrosion resi­stant “pearlite” cast iron
- Maximum operating pressure of 6 bar
- Maximum operating temperature of 95°C
- Sectional design with three passes for max effi ciency (gross 83%) and a generously sized combustion chamber for minimising NOX production
- Water cooled base and rear sections
- Large insulated door (hinged left or right) allowing easy access for service operations
- Powder coated enamel steel casing
- 80 - 100 mm thick glass wool insulation
- Suitable for use with a Natural gas, and/or 35 sec oil fi red pressure jet burner (matched with most popular burner manufacturers)
- Supplied as standard with on/off switch, temperature indication, control and high limit thermostats
- Effi ciency 83% (Hs - GCV)
- Manufactured to ISO 9001
- CE approved.
- Supplied in broken down form for ease of delivery and site access
4 OUTPUT DATA
4.1 Boiler effi ciency
Up to 90.2 % at Hi (81.3 % at Hs) at full load and up to
92.5 % at Hi (83.3 % at Hs) at part load.
Average water temperature 70°C (80/60°C).
5 APPLICATION DATA
5.1 L.P.H.W. version
5.1.1 Water temperature
Maximum water temperature is 110°C. The minimum acceptable return water temperature is, both for gas and oil fi red boilers 40°C, at a fl ow rate corresponding to a t of 20°C at nominal heat output.
5.1.2 Water pressure
Maximum pressure 6 bar. The boiler is suitable for open and sealed systems up to a maximum pressure of 6 bar and a minimum pres­sure of 0.8 bar. The boiler is suitable for installation in basement or rooftop boiler houses.
4.2 Combustion effi ciency
Up to 91.2 % at Hi (82.2 % at Hs) at full load and up to
95.5 % at Hi (86.0 % at Hs) at part load.
Note: Hi = NCV; Hs = GCV
5.1.3 Flow rate
The minimum fl ow rate through the boiler is obtained from the following formula:
Nominal heat output (kW) = m3/h
70
This minimum fl ow must be maintained for 5 minutes after the burner stops fi ring to avoid high temperature shutdown due to residual heat gain. Due to the design and manufacture of the boiler no specifi c minimum water fl ow requirement exists other than for over-temperature protection.
Supplied By www.heating spares.co Tel. 0161 620 6677
Remeha P 500
5.1.4 Water treatment
The system should be fi lled with mains cold water (for the UK this will usually have a pH of between 7 and 8). Pressurised installations with a boiler/system content ratio of 1:10 or less should not require water treatment, provided that the following conditions apply:
1. The system is fl ushed thoroughly to remove all fl uxes and debris and then fi lled completely once.
2. Make up water is limited to 5 % per annum.
3. The hardness of the water does not exceed 360 ppm (20°D).
All scale deposits will reduce the effi ciency of the boiler and should be prevented. However provided the above is complied with any scale produced will not be too detrimental to the boiler effi ciency and will not reduce the anticipated life expectancy of the boiler.
NOTE: Scale deposits in excess of 3 to 5 mm will reduce boiler effi ciency and greatly increase the risk of premature casting failure.
As most systems contain a variety of metals which can react with each other to cause corrosion. It is consid­ered good practice to provide some form of water treat­ment (especially in open vented systems) in order to prevent or reduce the following:
- Metallic corrosion;
- Formation of scale and sludge;
- Microbiological contamination;
- Chemical changes in the untreated system water.
Suitable chemicals and their use should be discussed with a specialist water treatment company prior to car­rying out any work. The specifi cation of the system and manufacturers recommendations must be taken into account, along with the age and condition of the system. New systems should be fl ushed thoroughly to remove all traces of fl ux, debris, grease and metal swarf generated during installation. Care to be taken with old systems to ensure any black metallic iron oxide sludge and other corrosive residues are removed, again by thoroughly fl ushing, ensuring that the system is drained completely from all low points.
NOTE: Please ensure that the new boiler plant is not in circuit when the fl ushing takes place, especially if cleansing chemicals are used to assist the process.
Under no circumstances is the boiler to be operated with cleaning chemicals in the system.
5.2 Economisers
ECO’s can be delivered upon request (for natural gas only). For specifi cations please refer to Technical infor­mation ECO 13/14/15.
5.3 Flue gas discharge
For the discharge of the fl ue gases, chimney draught is not required. Tests have shown that very good combustion results are obtained with zero draught at the boiler outlet.
5.4 Noise production
The noise level taken at a distance of 1 m around the boiler is approximately 75 to 90 dBA. The noise level at the chimney outlet will, depending on load, type of burner and chimney situation, vary from 75 to 90 dBA, measured at a distance of 1 m from the outlet. If this noise production gives rise to problems in the imme­diate vicinity, then noise reducing or absorbing measu­res should be taken.
100
90
2
N/m
-5
80
dB re 2x10
70
60
50
31,5 63 125 250 500 1000 2000 4000 8000
frequency (Hz)
full load
part load
NR 90
NR 80
NR 70
NR 60
Fig. 03 Noise level readings without burner silencer
To summarise:
- Minimise water loss;
- Prevent pumping over in open vented systems;
- Provide adequate air venting at all high points;
The values that have been taken are averages obtained from various measurements carried out at a distance of approximately 1 m around the boiler and at a height of approximately 1 m.
- Keep pH level between 7 - 9 when using additives;
- Maximum chlorine content of 200 mg/l;
- Take advice on the suitability of inhibitors.
Supplied By www.heating spares.co Tel. 0161 620 6677
6 INSTALLATION REQUIREMENTS
6.1 Installation recommendations in the boiler house
The necessary minimum installation space of the boiler can be seen from Fig. 04.
Fig. 04 Installation recommendations in the boiler house
04.15D.79.00001
H = 80mm without vibration damper H = 120mm with vibrationdamper
Fig. 05 Base details
00.15A.78.00001
Number
of
sections
9 1350
10 1500
11 1650
12 1800
13 1950
14 2100
15 2250
16 2400
17 2550
18 2700
19 2850
20 3000
A
mm
7 ASSEMBLY GUIDELINES AND INSTALLATION REQUIREMENTS
7.1 General
The Remeha boiler P 500 is delivered in individual parts. The sizes of the boiler parts are such that they all can
At the front of the boiler a fl ange is provided with 2 x G ½” threaded holes for the fi tting of the thermostat
pockets. enter the boiler house through a normal entrance. The casing and equipment parts are delivered in pac­kaged units. If necessary, the boiler can be put into operation without casing. The casing can be added at a later stage without dismantling the water connections.
7.3 Boiler assembly
Assembly and installation of a boiler delivered in indivi-
dual parts should only be undertaken by a recognised
and approved engineer and in accordance with the
assembly manual. Local regulations laid down by the
7.2 Water connections
relevant authorities must be adhered to. The water connections are at the rear of the boiler. The fl ow and return connections consist of a fl anged fl ow elbow and a fl anged return connection in accor­dance with DIN 2633. The return connection is provided with a G ¾” threaded hole in which a drain off cock is fi tted.
Supplied By www.heating spares.co Tel. 0161 620 6677
8 INSTRUMENT PANELS
Remeha P 500
8.1 Equipment contents
The panels contain all the necessary control and measu­ring instruments required to control the boiler. The con­nections have to be made on a terminal strip. The capil­laries and sensor wires, which come from the control panel, are placed in the instrument pockets that are fi tted at the front of the boiler.
12 3 6
Fig. 06 Layout of the instrument panel High/Low with hours run meters
00.03F.79.00004
See par. 8.2 for an instrument panel High/Low with hours run meters. Several extra options can be built into the panels. Ask our technical department.
8.2 Instrument panel High/Low with hours run meters
4 578
1. Operating switch (On/Off)
2. Control thermostat; setting between 35°C - 95°C
3. High/Low thermostat; setting between 35°C - 95°C
4. Hours run meter total running hours
5. Hours run meter full load running hours
6. Analoque thermometer water temperature
7. High limit thermostat 110°C (lock out)
8. Lock out warning lamp
9. Option for rematic® weather compensator
Supplied By www.heating spares.co Tel. 0161 620 6677
8.3 Wiring diagram instrument panel High/Low with hours run meters 1
1.) External control.
remove link; insert control pair (230 V)
2.) External control High/Low.
Fig. 07 Wiring diagram instrument panel High/Low with hours run meters
04.13C.SC.00001
Supplied By www.heating spares.co Tel. 0161 620 6677
9 COMMISSIONING
Remeha P 500
Note:
Commissioning to only be carried out by a qualifi ed engineer with the relevant training and certifi cation i.e. Acops-Corgi and a commissioning data sheet completed on site for issue to owner.
9.1 Pressurized boiler with gas burner
9.1.1 Commissioning procedure
If the boiler is to be put into operation again following a period of non-use, then the following procedure must be carried out :
- Open the main gas cock.
- Switch the weather-compensator (if fi tted) over to
manual operation (h).
- Turn the thermostats to their highest setting.
- Switch on the circulation pump.
- Switch on the main switch.
- Switch on the operation switch in the instrument panel.
- Consult burner manufacturers commissioning details.
Warning
If the instrument panel is fi tted with a weather compen­sator, set the program switch to ‘manual’ position (h). The following will now take place:
- The gas burner fan will start running so that during the purging time the combustion chamber will be ven­tilated with the air damper fully opened.
- The air damper will then go into start position.
- Ignition fl ame lights up and is checked.
- Then the control box gives the all clear signal for the burner to switch over to full load.
9.1.2 Putting out of operation
It is suffi cient to switch off the operation switch on the instrument panel. It is important that in the event of work being carried out on the burner, the boiler/burner unit must be completely electrically isolated and the main gas cock must be shut.5
9.2 Pressurized boiler with oil burner
9.2.1 Commissioning procedure
If the boiler is to be put into operation again following a period of non-use, then the following procedure must be carried out :
- Open the main oil cock.
- Switch the weather-compensator (if fi tted) over to
manual operation (h).
- Turn the thermostat to their highest setting.
- Switch on the circulation pump.
- Switch on the main switch.
- Switch on the operation switch in the instrument panel.
- Consult burner manufacturer commissioning details.
Warning
If the instrument panel is fi tted with a weather compen­sator, set the program switch to ‘manual’ position (h). The following will now take place:
- The oil burner fan will start running so that during the purging time the combustion chamber will be ventila­ted with the air damper fully opened.
- The air damper will then go into start position.
- Ignition fl ame lights up and is checked.
- Then the control box gives the all clear signal for the burner to switch over to full load.
9.2.2 Putting out of operation
It is suffi cient to switch off the operation switch on the instrument panel. It is important that in the event of work being carried out on the burner, the boiler/burner unit must be completely electrically isolated and the main oil cock must be shut.
10
Supplied By www.heating spares.co Tel. 0161 620 6677
10 FAULT FINDING
High Limit thermostat lock out:
- Check the water circulation (circulation pump). Reset the High Limit thermostat (Reset button is on the instrument panel under the cover cap of the High Limit thermostat).
- Advise the installer in the event of continued lockouts.
11 MAINTENANCE RECOMMENDATIONS
11.1 General
Depending on the operational conditions, the block and the burner must be checked and cleaned at least once a year for gas and at least twice a year for oil.
11.2 Maintenance instructions
Cleaning of the boiler:
- Put boiler out of operation.
- Open the front door, if necessary after dismantling the burner.
- Remove the retarders (only for the 9 - 16 sections).
- Clean the combustion chamber and fl ue passes using a suitable brush.
- Clean the removed retarders ( 9 - 16 sections).
- Remove the rear panel of the boiler and remove the cleaning cover (underneath the smoke box).
- Vacuum clean the boiler and the combustion cham­ber.
- Renew the front door seals after cleaning the boiler.
- Re-assemble the removed parts and close the front door.
- Re-assemble the burner (if dismantled).
- Check the boiler combustion side for leakage.
- Check the equipment for proper functioning and if necessary re-adjust the control and safety equipment.
- Carry out combustion analysis.
- Check the water connections.
11
Supplied By www.heating spares.co Tel. 0161 620 6677
Remeha P500
Broag Ltd.
Head office
Remeha house
Molly Millars Lane
Wokingham,
Berkshire RG41 2QP
Tel.: 0118 978 3434
Fax: 0118 978 6977
E-mail address:
boilers@broag-remeha.com
© Copyright
All technical and technological information contained in these technical instructions,
as well as any drawings and technical descriptions furnished by us remain our
property and shall not be copied in part or whole without our prior consent in writing.
Subject to alterations 52881/1000/0202/Ips.
12
Branch office
Unit 3, Kestrel Close,
Quarry Hill ind. Estate,
Ilkeston
Derbyshire DE7 4RD
Tel.: 0115 944 0778
Fax: 0115 944 0588
Loading...