Remeha P420-10 Technical Specifications

Boiler Type :
P420 - 10
Issue Date :
June 2012
MODEL : P420
No of SECTIONS : 10
Rated Output kW :
450 - 540
Efficiency % : NCV Full load (³)
88
Weight (dry) kgs :
As per Technical Manual
Seasonal Efficiency : % GCV
82.2
Overall Dim WxHxD mm :
1000 x 1690 x 2120
Radiated Losses w : *
413
BURNER TYPE
Pressure Jet
Fuel Available :
Nat Gas
Oil (35sec)
Dual Fuel
Fuel Consumption:
Check burner details
52 Kg/hr ##
Noise levels dB(A) :
Check burner details
Min Op Gas Press mbar :
Check burner details
HYDRAULICS
Water Content ltrs :
452
Min Return Temp °C
50
Resist @ 11°C t mbar :
66
Connection Size :
Resist @ 20°C t mbar :
20
Std Operating Temp °C :
80
Nom Flow Rate @ 11° C ∆t l/s :
Max Operating Temp °C :
Nom Flow Rate @ 20° C ∆t l/s :
6.45
High Limit Set Point °C :
110
Min Flow Ratet l/s : #
2.85
Max Op Press bars :
6
Test Press bar :
As per Assembly Manual
FLUE
Diameter mm :
250
Flue Gas Flow kgs/hr Gas : (¹)
972
Flue Type :
Conventional
Flue Gas Flow kgs/hr Oil : (¹)
900
Chamber Resist. mbar :
2.0
Flue Gas Temperature °C : (²)
<220
ELECTRICAL
Voltage :
230.1.50
Note: 1ph burners obtain their power supply via the boiler.
Fuse rating amps :
10Amp
3ph burners require a 3ph
supply + a 1ph to the boiler.
CONTROL OPERATION
Standard :
On / Off Thermostat
Temperature indication
L/O lamp
switch
High / Low
3 Position Switch Auto/Man/Test
10amp CB
Optional :
Hours Run Meters
Modulating(via burner)
TECHNICAL SPECIFICATION SHEET
Quick reference specification sheet full details can be found in the P420 series Installation/Service guide. General Details Corrosion resistant cast iron sectional boiler, jointed by conical nipples and ceramic rope, designed with three passes for high efficiency and low NOx emission. Large insulated door (hinged left or right) allowing easy access for cleaning. Powder coated enamel steel casing c/w fibreglass insulation. All of the P420 Boiler Range are supplied un-assembled for delivery to site. CE approved. Boiler Efficiency data to 92/42-EEC
(Avg)
2½”
11.73
High limit Thermostat Volt free run/lock indication On/Off
90
(¹) Boiler at full output average temperature 80/60°c (70°c mean)
Boiler temperature: 80 °C, Ambient temperature: 20 °C
(²)
(³) 70°c average temperature
* Maintenance consumption refer to boiler installation/service manual
# Based on ∆t of 45°c ## @ 12 bar pump pressure Ours is a policy of continuous development, we therefore reserve the right to alter specifications without prior notification. Remeha Commercial accept no liability for any loss or damage rising from any errors or omissions that may be inadvertently contained in this specification sheet.