The appliance complies with the standard model described in
declaration of compliance 1. It is manufactured and distributed
pursuant to the requirements of european directives. The original of
the declaration of compliance is available from the manufacturer.
Risk of injury and damage to equipment. Attention must be
paid to the warnings on safety of persons and equipment
Important information
Information must be kept in mind to maintain comfort
Reference
Z
Refer to another manual or other pages in this instruction
manual
DHW: Domestic hot water
Hi: Lower heating value LHV (Nett)
Hs: Higher heating value HHV (Gross)
2Important recommendations
For a proper operating of the boiler, follow carefully the
instructions.
Any intervention on the appliance and heating equipment
must be carried out by a qualified engineer.
The manufacturer is not liable for any improper use of the
appliance or failure to maintain or install the unit correctly
(the user shall take care to ensure that the system is
installed by a qualified engineer).
Work on electrical equipment must be carried out by a
qualified professional in compliance with the prevailing
regulations.
Check that the appliance is properly set for the type of gas
used.
Keep to the polarity shown on the terminals: phase (L),
neutral (N) and earth
Check the seal on the gas and water pipe connections.
We shall not accept any responsibility for any damage and
disturbance arising from not following these instructions.
4
.
Installation must be carried out in accordance with the prevailing
regulations, the codes of practice and the recommendations in these
instructions with the relevant certification ie: ACS, IEE regulations,
etc.
The first start-up is to be performed by your installation/
commissioning engineer.
Only original spare parts must be used.
Any work on the boiler unit is authorised only if carried out by a
qualified engineer.
Before commissioning, the factory settings of the appliance must be
compared with the local energy supply conditions. If the settings have
to be modified, this must be carried out by a qualified professional.
Condensing boilers require a flue gas discharge system or a fresh air
inlet specially adapted to the method of operation. Its execution
depends on the place of installation and the building.
Compliance with a minimum distance between the flue gas
evacuation system in forced flue mode or the boiler with combustible
substances must comply with current regulations. At nominal output,
the temperature of the components does not exceed 85 °C.
Work on electrical equipment must be carried out by a
qualified professional in compliance with the prevailing
regulations.
Installation and maintenance of the boiler must be carried out by a
qualified professional in compliance with prevailing local and national
regulations.
25/01/2011 - 300014883-001-KGas 110 Eco 115 / 65
5
3Description
3.1General
Gas 100 Eco 115 / 65 boilers are floor standing gas-fired condensing
boilers fitted with an "Open Therm" control interface which enable
direct weather compensation using Remeha single and multi boilers
controls or the customer can choose to use external control options
supplied by others without affecting boiler performance.
They are designed for closed circuit hot water boiler rooms with a
maximum operating temperature of 90°C. However, open vented
systems can be accommodated.
3.2Homologations
3.2.1General instructions
BoilerGas 110 Eco 65 / Gas 110 Eco 115
No. CECE-0063BS3826
Type
Flue gas dischargeChimney / Flue gas outlet
IgnitionAutomatic
GasNatural gas / Propane
3.2.2Gas categories
See chapter 5.2 "Important comments on the treatment of the
Z
heating circuit".
Installation is recommended on low temperature heating installations
(Underfloor heating, radiators, ...).
B
- C
- C33 - C43 - C53 - C63 - C
23
13
83
- C
93
Gas 110 Eco 65
Gas 110 Eco 115
Gas 110 Eco 65
Gas 110 Eco 115
CategoryType of gas used
II
2H3P
CategoryType of gas used
II
2H3P
Natural gas40 mbar
Propane60 mbar
Natural gas17 mbar25 mbar
Propane25 mbar57.5 mbar
Supply pressure (Gas pressure when the boiler
is not operating)
Maximum allowed on the gas valve
Working pressure
MinimumMaximum
6
Gas 110 Eco 115 / 6525/01/2011 - 300014883-001-K
3.3Main parts
•Gas 110 Eco 65
7
8
9
6
1 Fan air inlet
2 Return sensor
3 Heating body
4 Heat exchanger
5 Combined venturi and gas valve unit
6 Fan
7 Control panel
8 Burner
9 Flow temperature sensor
10 Ignition electrode + Ionization electrode
11 Sight glass
12 Front plate exchanger
13 Siphon
10
11
12
13
5
4
3
2
1
C001484
25/01/2011 - 300014883-001-KGas 110 Eco 115 / 65
7
•Gas 110 Eco 115
7
8
9
6
1 Fan air inlet
2 Return sensor
3 Heating body
4 Heat exchanger
5 Combined venturi and gas valve unit
6 Fan
7 Control panel
8 Burner
9 Flow temperature sensor
10 Ignition electrode + Ionization electrode
11 Sight glass
12 Front plate exchanger
13 Siphon
10
11
12
13
5
4
3
2
1
C001485
8
Gas 110 Eco 115 / 6525/01/2011 - 300014883-001-K
3.4Technical characteristics
3.4.1Boiler
- For operation on Natural Gas or Propane (See "Switching from
Natural Gas to Propane")
- The boiler is preset in the factory to operate on natural gas G20,
20 mbar (minimum 17 mbar)
- The boiler is suitable for room sealed or open flue applications
- Single-unit heat exchanger in aluminium/silicium alloy
- Cylindrical premix burner covered in metal fibres
3.4.2Control panel
Please read the following installation and commissioning
instructions carefully before operating your equipment. The
manufacturer shall not be liable for damage caused by the
failure to comply with these instructions and the warranty shall
no longer apply.
If work is carried out on the heating installation: assembly,
commissioning, maintenance and repair work on the
appliance and on the heating installation must be carried
out only by a qualified heating professional.
Before installation: Ensure that the mains power supply is
isolated.
Before commissioning: Check the seal on the gas and
water pipe connections.
- Centrifugal fan with combustive air intake silencer for a low noise
level
- Compact gas line with zero pressure regulator, two valves and filter
- Water condensation siphon with run-off pipe
- Automatic air vent
- Mechanical manometer
- Soundproofed boiler body
- A documentation pack.
The connection of the control panel must be carried out by
a qualified professional. For a proper operating of the
boiler, follow carefully the instructions.
Gas flow rate at nominal output (15 °C - 1013 mbar)
Natural gas G20
Propane
Efficiency 75/60 °C (DIN 4702 T8) (Hi)%106106
Efficiency 75/60 °C (DIN 4702 T8) (Hs)%95.595.5
Efficiency 40/30 °C (DIN 4702 T8) (Hi)%111102.5
Efficiency 40/30 °C (DIN 4702 T8) (Hs)%10092.4
Load and water temperature efficiency
(-100% Pn-Average temperature 70 °C) (Hi)
Load and water temperature efficiency
(-100% Pn-Average temperature 70 °C) (Hs)
Load and water temperature efficiency
(-30% Pn-Return temperature 30 °C) (Hi)
Load and water temperature efficiency
(-30% Pn-Return temperature 30 °C) (Hs)
Stand-by losses ∆T = 30KW125131
Mass flue gas flow rate - minimum/maximumKg/h20.5/10428.9/186
level in flue gases
CO
2
- Natural gas G20
- Propane
Available pressure at boiler outletPa100250
Average flue gas temperature (75/60 °C)°C6567.9
Connection to a chimney (internal diameter)mm100/150100/150
Emission NOx (Natural gas G20) - dry 0% O
2
Emission CO (Natural gas G20) - DIN 4702 Teil 8mg/kWh2131 (EN297A3)
NOx classification55
Maximum operating temperature°C9090
Maximum operating pressurebar44
Water resistance (∆T = 20K)mbar175230
Water resistance (∆T = 11K)mbar580830
Nominal water flow Pn to ∆T = 20K
Nominal water flow Pn to ∆T = 11K
Water content
Flow and return connection (diameter)1" 1/4 Male1" 1/4 Male
Condensation water pH3-53-5
Condensation water run-off (diameter)mm2525
Electrical specifications
Electrical connectionV/Hz230/50230/50
Power consumptionW88213
Degree of protectionDIN40050IP 21IP 21
1Heating outlet R 1 1/4 m
6Heating return R 1 1/4 m
7Condensates discharge (Ø 25 mm external)
8Automatic air vent
9Gas inlet R 3/4
Gas 110 Eco 65: 1100 mm
A
Gas 110 Eco 115: 1322 mm
Gas 110 Eco 65: 410 mm
B
Gas 110 Eco 115: 632 mm
Gas 110 Eco 65: 124 mm
C
Gas 110 Eco 115: 346 mm
Gas 110 Eco 65: 968 mm
D
Gas 110 Eco 115: 1190 mm
Gas 110 Eco 65: 152 mm
E
Gas 110 Eco 115: 374 mm
ØFForced flue connection Ø 100/150 mm
B
6
C
7
E
198420
173
158
118
R = Thread
G = Exterior cylindrical threading, sealed by sheet gasket
(1) Basic dimension 21 mm
adjustment possible: 21 to 40 mm
25/01/2011 - 300014883-001-KGas 110 Eco 115 / 65
11
3.6.2Boiler installed
Clear space should be left around the boiler:
- 70 cm in front of the boiler
- 40 cm above the boiler
•Gas 110 Eco 115 / 65
- 2.5 cm each side of the boiler
(Facilitates removal of the casing)
600
1263
A
C001486
A. Gas 110 Eco 65 = 1100
Gas 110 Eco 115 = 1322
12
Gas 110 Eco 115 / 6525/01/2011 - 300014883-001-K
3.7Hydraulic specifications
Depending on the flow, the following diagrams represent:
- the manometric heights of the heating
- loss of load in the boiler.
For a fixed flow, the manometric height available at the boiler outlet
is obtained by taking the difference between the manometric height
of the circulator pump and the loss of load in the boiler.
Optional 3-speed circulator pump for Gas 110 Eco 65 - UPS 25-70 130
For example: Gas 110 Eco 65 with UPS 25-70 130 pump:
manometric height available at 2.61 m
3
/h = 4.6 mWG - 1.6 mWG = 3
mWG (i.e. 3 mbar)
3
2.61 m
/h corresponds to a load of 61 kW and a ∆t of 20 K
A. Rated net head (mWG)
B. Flow rate (m
3
/h)
C. Loss of load Gas 110 Eco 65
Optional 3-speed circulator pump for Gas 110 Eco 115 - UPS 25-80 130
9
A
8
7
6
5
4
3
2
1
I
III
II
C
0
0,00,51,01,52,02,53,03,54,04,55,05,5
A. Rated net head (mWG)
3
B. Flow rate (m
/h)
C. Loss of load Gas 110 Eco 115
C001242
T=20K
B
25/01/2011 - 300014883-001-KGas 110 Eco 115 / 65
13
4Control and safety equipment
4.1Control panel
4.1.1General
The boiler is supplied with a standard set of defaults pre-programmed
for normal operation but can be tailored by the Engineer to suit most
site conditions. These values are set and read using the built in
control panel or with a notebook computer (with an interface and
software available on request).
4.1.2Layout of the control panel
For security the control has three levels of access:
- User level - free access
- Service level - access with service code by qualified personnel
- Factory level - access by PC with factory code (Remeha only).
"code"-display
Indicates on user level:
Additional indication on service level:Fan speed mode: alternate half digit '
Key "r":Program function: key to select the required mode
Key "w":Program function: key to select the required program within the selected mode
Key w + Symbol v:Switch function: burner switch HTG (manual override)
Key "l":Program function: key to save the settings
Key "l" + Symbol qSwitch function: burner switch DHW (manual override)
Key [+]:Program function: to select a higher setting
Key [+] + Symbol uSwitch function: pump manual override
Key [-]:Program function: to select a lower setting
Key [-] + Symbol n:Switch function: manual override (hand/auto)
Operating mode: only one digit
Setting mode: digit with dot
Read-out mode: digit with flashing dot
Shut-off mode: letter B
Forced full load: letter G
Forced part load: letter H
Failure mode: flashing digit
14
Gas 110 Eco 115 / 6525/01/2011 - 300014883-001-K
4.1.3Combined key functions (in operating mode only)
When the boiler is in the operating mode, keys with the illuminated
symbols above have a double function (Program and Switch).
To use them for a Program function press the key once - and for a
Switch function (either on or off) press the key and hold for
5 seconds.
The status of the switch function will be confirmed by the illuminated
symbol as follows:
•Key
"w" and symbol v:
- (symbol) not illuminated: HTG under normal control
- red (symbol) on: HTG off (manual override)
•Key
"l" and symbol q:
- (symbol) not illuminated: DHW under normal control
- red (symbol) on: DHW off (manual override)
•Key
[+] and symbol u:
- green (symbol) on: continuous pump operation
- (symbol) not illuminated: pump under boiler control
•Key
[-] and symbol n:
- green (symbol) on: HTG on (manual override)
4.1.4Display of values with more than two digits
- (symbol) not illuminated: HTG under normal control.
Manual override will stay active until deactivated, even if power is
switched off and then restored.
NOTE: In the Switch function, (in order to protect the boiler and the
installation) the flow temperature cannot exceed it’s pre-set
maximum. It is also not possible to change any parameters.
•Forced mode "high" (G>>)
By pressing the keys
"r" and [+] simultaneously in operating mode,
the boiler will burn at maximum power. The letter G will now appear
on the display.
By pressing the keys
[+] and [-] simultaneously, the boiler will return
to operating mode. Following a manual override the boiler will return
to normal (auto control) if no keys are used within a 15 minute period.
•Forced mode "low" (H>>)
By pressing the keys
"r" and [-] simultaneously in operating mode,
the boiler will burn at minimum power. The letter H will now appear
on the display. By pressing the keys
[+] and [-] simultaneously, the
boiler will return to operating mode. Following a manual override the
boiler will return to normal (auto control) if no keys are used within a
15 minute period.
The display has only two digits available therefore values over this
are displayed as follows:
- negative values will be indicated by a dot behind the last digit e.g.
= -10
- values from 00 to 99 will be indicated without any punctuation
marks
- values from 100 to 199 will be indicated by a dot between both
digits e.g. = 100, = 110, & = 199.
- values from 200 to 299 will be indicated by a dot behind every digit
e.g. = for 200, = 210, = 299.
25/01/2011 - 300014883-001-KGas 110 Eco 115 / 65
15
4.2Flow diagram control system
Press the "r"-key for the menuPress the "w"-key for the menu
"code"-displayx-display
Operating mode
§ 4.3
Z
Setting mode, user level
§ 4.5
Z
Setting mode, service level
§ 4.6
Z
Only digit or letter
- &,G,H,B
Digit or letter with fixed dot
)
*
M
Flow temperature or shut-off code
Flow temperature set-point
Pump run on time HTG
DHW temperature set-point
Boiler control setting
Base point internal compensation slope
Service engineer level only:
?
+
0
.
/
1
Flow temperature set-point during forced part load
High limit temperature set-point
Fan speed at full load (HTG)
Fan speed at part load (HTG and DHW)
Modulation start point ∆T (F/R)
Interface selection (control option)
DHW cut-in ∆T
Fan speed at full load (DHW)
Intern
N/a
N/a
Forced part load time after start (HTG)
Fan speed at start
2DHW control stop or boiler modulation set point (based on parameter )
3
4
5
6
7
;
8
=
@
DHW control mode
N/a
HTG cut-in ∆T (based on return)
N/a
Boiler type
Intern
Maximum delay time
Start point for 0 V analog signal
End point for 10 V analog signal
Intern
16
Gas 110 Eco 115 / 6525/01/2011 - 300014883-001-K
Read-out mode
§ 4.7
Z
Service engineer level only:
Speed mode
§ 4.8
Z
Digit or letter with flashing dot
)
?
8
*
Alternate half digit 'Fan speed
Actual flow temperature
Actual return temperature
Actual DHW temperature (with sensor)
Actual outdoor temperature (only if outdoor sensor fitted)
N/a
Flow temperature (set point)
Actual heat demand status
Calculated HTG cut-in temperature
Actual flow temperature rise
N/a
Failure mode
§ 4.9
Z
Flashing digit
!
"
#
Failure code
Operating code during failure
Flow temperature during failure
Return temperature during failure
DHW temperature during failure
N/a
4.3Operating mode (N>>)
During operation the "code"-display shows the status (position in
cycle) of the boiler, whilst the
temperature.
CodeDescription
Standby: there is no heat demand from control system
Ignition: ignition is activated for 2.4 seconds while the gas valve is openedHTG mode: the boiler operates in the HTG mode
!DHW mode: the three way valve or DHW pump activated
"Internal check
#Normal control stop during HTG (flow temperature > set-point + 5 °C)
$HTG pump run on
%DHW pump run on or for three way valve option, HTG pump run on with valve open to DHW (max. 5 minutes)
&Normal control stop during DHW (flow temperature > set point DHW + DHW control stop set point + 5 °C)
BShut-off mode
GForced full load
HForced part load
Pre-purge: before start-up, the boiler is purged for 4.2 seconds
Post-purge: when the heat demand has been met, the fan continues to operate for another 10 seconds
x-display indicates the actual flow
The digits or letters in the code-display have the following meaning:
25/01/2011 - 300014883-001-KGas 110 Eco 115 / 65
17
4.4Shut-off mode (B<<)
During shut-off mode condition the "code"-display will show a B,
whilst the
CodeDescription
B)
x-display indicates the cause with two flashing dots.
Maximum acceptable flow temperature rise exceeded. The boiler will shut off for ten minutes, then restart. Should the flow
Table below details cause of shut-off mode.
temperature conditions remain the same after 5 attempts, this code will be recorded as a shutdown failure. Boiler will not
lockout.
B)+
Contacts of the external interlock have opened during heat demand. The boiler will shut off for 120 seconds. Should the contacts close again during heat demand, the boiler will wait the remaining time from the 120 seconds before attempting a
restart.
B)Internal check on fan speed. After 5 attemps, the boiler will lockout. This code will be recorded.
B)Internal check on fan speed. After 5 attemps, the boiler will lockout. This code will be recorded.
BMaximum temperature difference between flow and return exceeded. The boiler will shut off for 150 seconds, then restart.
Should the temperature difference conditions remain the same after 10 attemps, this code will be recorded as a shut-down
failure. Boiler will not lockout.
BOne or several adjusted parameters out of range including some factory defaults which should not have been changed.
Check and reset parameters:
- Press the "reset"-key immediately followed by pressing the "r"-key for about 12 seconds,
-"code"-display shows 7,
-use [+] and [-] -keys to enter correct boiler parameter
(7=! for Gas 110 Eco 115, 7=#! for Gas 110 Eco 65)
-press "l"-key to confirm settings,
- check parameter settings and change were needed or desired.
NOTE: Shut-off mode is a normal boiler operating function and does
not represent a boiler failure.
However, this may indicate a system problem, an internal boiler
check or an incorrect parameter setting.
4.5Setting mode user level (<>>)
CodeDescriptionSetting rangePreset
)Pump run on time HTG
*
;
NOTE: Changing code ) and code * should only be on design
engineers advice.
Flow temperature set point
-& °C%
= pump run on 10 seconds
-"= pump run on in minutes
DHW temperature set point
Boiler control settingControl mode (modulating-on/off etc.)
Base point internal compensation slopeN/a
-$" °C(only with sensor)""
18
Gas 110 Eco 115 / 6525/01/2011 - 300014883-001-K
4.5.1Flow temperature set point ()
The required flow temperature is adjustable from 20 to 90 °C.
4.5.2Pump run on time HTG ())
Pump run on time can be adjusted (Please refer to installation
contractor)
- Press the "r" -key until the digit (with dot) appears in the
"code"-display.
- Press the "w"-key until the digit ) (with dot) appears in the
"code"-display.
- Set the required value, using the [+] and [-] -keys.
CodexDescription
)Pump runs on for 10 seconds
)<NPump runs on for 1 to 15 minutes (NN= to ")
- Press the "l"-key to store the new value (value will flash twice).
- Press the "reset"-key to return to operating mode.
NOTE: For continuous pump operation use manual override,
See chapter 4.1.3.
Z
25/01/2011 - 300014883-001-KGas 110 Eco 115 / 65
19
4.5.3DHW temperature set-point ( )
The DHW temperature is adjustable from 20 to 75 °C (factory
default 55 °C). Only with DHW priority sensor.
- Press the "r" -key until the digit (with dot) appears in the
"code"-display.
- Press the "w"-key until the digit (with dot) appears in the
"code"-display.
- Set the required value, using the [+] and [-] -keys.
4.5.4Boiler control setting (*)
The boiler is factory set to option (HTG modulating or on/off
with DHW on).
To change the control option:
- Press the "r" -key until the digit (with dot) appears in the
"code"-display.
- Press the "w"-key until the digit * (with dot) appears in the
"code"-display.
- Set the required X and Y values as listed below in using the
[+] and [-] -keys.
- Press the "l"-key to store the new value (value will flash twice).
- Press the "reset"-key to return to operating mode.
- Press the "l"-key to store the new value (value will flash twice).
- Press the "reset"-key to return to operating mode.
NOTE: there are further adjustments available on service level.
Please refer to your service engineer or contractor.
See chapter 4.6.7.
Z
"With the ""code""- display showing * - the
the method of boiler control in the first segment N> and the option
to turn the HTG and DHW on or off in the second segment >O". By
using codes from the table below a series of control options are
available.
Example: NO - Boiler enabled internal modulation with booster on * - HTG
and DHW on (as default)
! - Analog signal 0 -10 V on temperature - HTG on and DHW
off
- Boiler high/low - HTG off and DHW on
x-display will indicate
x-displayFirst segment N>Boiler control option
Boiler enabled internal modulation with booster on *
Boiler high/lowBoiler enabled internal modulation with booster off *
!Analog signal 0 - 10 V on temperature
"Analog signal 0 - 10 V on output %
Second segment >OOperation mode
HTG and DHW off
HTG and DHW on
HTG on and DHW offHTG off and DHW on
* NOTE: boiler setting * and have the same function
Description
20
Gas 110 Eco 115 / 6525/01/2011 - 300014883-001-K
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.