WARNING:
If the information in these instructions are not followed exactly,
a fi re or explosion may result causing property damage,
personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed
installer, service agency or the gas supplier.
Tested by:
918-531b
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any applianceDo not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
01/07/08
REGENCY
®
ULTIMATE Direct Vent Freestanding Gas Stove
To the New Owner:
Congratulations! You are the owner of a state-of-the-art ULTIMATE Direct Vent Gas Stove by FPI Fireplace
®
Products International Ltd. The Regency
provide you with all the warmth and charm of a woodstove, at the fl ick of a switch. The models U39-NG1,
and U39-LP1 of this series has been approved by Warnock Hersey for both safety and effi ciency. As it
also bears our own mark, it promises to provide you with economy, comfort and security for many trouble
free years to follow. Please take a moment now to acquaint yourself with these instructions and the many
features of your ULTIMATE Direct Vent Freestanding Gas Stove.
Gas Series of hand crafted appliances has been designed to
®
2
Regency
U39 ULTIMATE Direct Vent Freestanding Gas Stove
TABLE OF CONTENTS
SAFETY LABEL
Copy of Safety Label .....................................................4
REQUIREMENTS
MA Code - CO Detector ................................................5
INSTALLATION
Important Message ........................................................6
Regency® U39 ULTIMATE Direct Vent Freestanding Gas Stove
3
SAFETY LABEL
This is a copy of the label that accompanies
each ULTIMATE Direct Vent Freestanding
Gas Stove. We have printed a copy of the
contents here for your review. The safety
Copy of Safety Label for U39 Gas Stove
label is located on the inside of the drop
down pedestal door.
NOTE: Regency® units are constantly
being improved. Check the label on the
unit and if there is a difference, the label
on the unit is the correct one.
For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the Commonwealth
of Massachusetts.
For the State of Massachusetts, fl exible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm
with battery back up in the same room where the gas appliance is installed.
®
4
Regency
U39 ULTIMATE Direct Vent Freestanding Gas Stove
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
Regency® U39 ULTIMATE Direct Vent Freestanding Gas Stove
5
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The ULTIMATE Direct Vent Freestanding Gas
Stove must be installed in accordance with these
instructions. Carefully read all the instructions in
this manual fi rst. Consult the building authority
having jurisdiction to determine the need for a
permit prior to starting the installation.
Note: Failure to follow the instructions
could cause a malfunction of the
heater which could result in death,
serious bodily injury, and/or property
damage. Failure to follow these
instructions may also void your fi re
insurance and/or warranty.
Note: These instructions take preced-
ence over Simpson Dura-Vent
instructions.
SPECIFICATIONS
Fuels: U39-NG1 is approved for use with
natural gas.
U39-LP1 is approved for use with
liquefi ed petroleum gases (propane).
Electrical: 120V A.C. system.
Circulation Fan: Variable speed, 125/75.
Log Sets: Ceramic fi bre, 7 per set.
Vent System: Coaxial (6-5/8" outer / 4" inner
liner) rigid fl ue and termination cap.
INFORMATION FOR
MOBILE/
MANUFACTURED
HOMES AFTER
FIRST SALE
This Regency® product has been tested and
listed by Warnock Hersey as a Direct Vent
Wall Furnace to the following standards: CAN/
CGA-2.17-M91 and ANSI Z21.88b-2003/CSA
2.33b-2003.
This Direct Vent System Appliance must be
installed in accordance with the manufacturer's
installation instructions and the Manufactured
Home Construction and Safety Standard, Title
24 CFR, Part 3280, or the current Standard of
Fire Safety Criteria for Manufactured Home
Installations, Sites, and Communities ANSI/
NFPA 501A, and with CAN/CSA Z240-MH
Mobile Home Standard in Canada.
This appliance installation must comply with
the manufacturer's installation instructions and
local codes, if any. In the absence of local codes
follow the current National Fuel Gas Code, ANSI
Z223.1 and the current National Electrical Code
ANSI/NFPA 70 in the U.S.A., and the current
CAN/CGA B149 Gas Installation Code and the
current Canadian Electrical Code CSA C22.1
in Canada.
This Regency® Mobile/Manufactured
Home Listed appliance comes factory
equipped with a means to secure the
unit.
This Regency® Mobile/Manufactured
Home listed appliance comes equipped
with a dedicated #8 ground lug to which
an 18 gauge copper wire from the steel
chassis ground must be attached.
This appliance may only be installed
in an aftermarket permanently located,
manufactured (mobile) home, where
not prohibited by local codes.
This appliance is only use with the type
of gas indicated on the rating plate.
This appliance is not convertible for
use with other gases, unless a certifi ed
kit is used.
BEFORE YOU START
Safe installation and operation of this appliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of
the following:
INSTALLATION AND REPAIRS
SHOULD BE DONE BY A
QUALIFIED SERVICE PERSON.
THIS APPLIANCE SHOULD
BE INSTALLED, REPAIRED,
INSPECTED BEFORE USE AND
AT LEAST ANNUALLY BY A
QUALIFIED SERVICE PERSON.
MORE FREQUENT CLEANING MAY
BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, ETC.
IT IS IMPERATIVE THAT THE
CONTROL COMPARTMENT,
BURNERS AND CIRCULATING
AIR PASSAGEWAYS OF THE
APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES,
THE APPLIANCE SHOULD BE
LOCATED OUT OF TRAFFIC AND
AWAY FROM FURNITURE AND
DRAPERIES.
WARNING: FAILURE TO INSTALL
THIS APPLIANCE CORRECTLY
WILL VOID YOUR WARRANTY
AND MAY CAUSE A SERIOUS
HOUSE FIRE.
CHILDREN AND ADULTS
SHOULD BE ALERTED TO THE
HAZARDS OF HIGH SURFACE
TEMPERATURES, ESPECIALLY
THE FIREPLACE GLASS,
AND SHOULD STAY AWAY TO
AVOID BURNS OR CLOTHING
IGNITION.
YOUNG CHILDREN SHOULD
BE CAREFULLY SUPERVISED
WHEN THEY ARE IN THE SAME
ROOM AS THE APPLIANCE.
CLOTHING OR OTHER
FLAMMABLE MATERIAL SHOULD
NOT BE PLACED ON OR NEAR
THE APPLIANCE.
1) Provide adequate clearances for
servicing, proper operation and around
the air openings into the combustion
chamber.
2) The appliance may be installed on a fl at,
solid, continuous surface (e.g. wood, metal,
concrete). This may be the fl oor, or it can
be raised up on a platform to enhance
its visual impact. The appliance may be
installed on carpeting, tile, wood fl ooring
or other combustible material, because the
appliance's metal pedestal base extends the
full width and depth of the appliance. The
ULTIMATE Direct Vent Freestanding Gas
Stove can be installed in a wide variety of
ways and will fi t nearly any room layout.
It may be installed in a recessed position,
framed out into the room, or across a
corner.
3) The ULTIMATE Direct Vent Freestanding Gas
Stove is approved for alcove installations,
which meet the clearances as listed in the
"Locating Your Ultimate Gas Stove" section.
This unit is approved for manufactured
home installations, see "Rigid Pipe Venting
Arrangements" section for the required
vent arrangements. If installed into a
manufactured home the unit must be bolted
down to the fl oor.
®
6
Regency
U39 ULTIMATE Direct Vent Freestanding Gas Stove
INSTALLATION
4) This appliance is Listed for bedroom
installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
5) This appliance is Listed for Alcove
installations, maintain minimum Alcove
clearances as follows, minimum width of
48" (1219mm), a maximum depth of 36"
(914mm), and minimum ceiling height of
64"(1626mm).
6) We recommend that you plan your installation
on paper using exact measurements for
clearances and floor protection before
actually installing this appliance. Have a
qualifi ed building inspector review your plans
before installation.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform with
local Canadian Electrical Code.
2) The appliance when installed, must be
electrically grounded in accordance with
local codes, or in the absence of local codes
with the current National Electrical Code,
ANSI/NFPA 70 or CSA C22.1 Canadian
Electrical Code.
3) The appliance should be inspected for
shipping damage before use and serviced
annually by a professional service
person. More frequent cleaning may be
required due to excessive lint from carpeting,
bedding material, etc. It is imperative that
control compartments, and circulating air
passageways of the appliance be kept
clean and free from excessive lint from
carpeting.
4) See general construction and assembly
instructions. The appliance and vent should
be enclosed when installed in or passing
through a living area, where children may
come in contact with it.
5) This appliance must be connected to the
specifi ed vent and termination cap to the
outside of the building envelope. Never
vent to another room or inside a building.
Make sure that the vent is fi tted as per
the instructions starting in "Locating Your
Ultimate Gas Stove" section.
6) Inspect the venting system annually for
blockage and any signs of deterioration.
7) Venting terminals shall not be recessed into
a wall or siding.
8) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
9) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fi replace.
Emissions from burning wood or gas could
contain chemicals known to the State of California to cause cancer, birth defects or other
reproductive harm.
INSTALLATION
CHECKLIST
1) Loate your appliance. Refer to the following
sections:
a. Locating Your Ultimate Gas Stove
b. Exterior Vent Termination Locations
c. Clearance to Combustibles
d. Combustion and Ventilation Air
2) Install Louvers. Refer to the "Louver
Installation" section.
3) Choose a venting option and install
accordingly. Refer to the following sections
where applicable:
a. DV Stove Horizontal Vent Kit
Installation
b. Dura-Vent Termination Kit
c. Set Vent Restrictors. Refer to "Rigid
Pipe Venting Arrangement" section.
d. Converting a Class-A Metal Chimney
or Masonry Chimney to a Direct Vent
system.
4) Make gas connections. Refer to "Gas
Connection" section.
Test the pilot. Must be as per diagram. Refer
to "Pilot Adjustment" section.
5) If necessary, see the "Conversion from NG
to LPG" section and "Conversion to Lower
BTU Rating" section.
6) Test Gas Pressure. Refer to "Gas Pipe
Pressure Testing" section .
7) Install standard and optional features.
Refer to the following sections where
applicable:
a. Log Set
b. Front Door
c. Wall Thermostat
d. Remote Control
8) Final check. Refer to the "Final Check"
section.
Before leaving this unit with the customer,
the installer must ensure that the appliance is
fi ring correctly and operation fully explained
to customer.
This includes:
1) Clocking the appliance to ensure the correct
fi ring rate (rate noted on label) after burning
appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance
and the chimney connector. The farthest
distance is correct if the two clearances do
not coincide.
For example, if the appliance is set as indicated
in one of the fi gures but the connector is too
close, move the stove until the correct clearance
to the connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type of
installation with another in order to achieve
closer clearances.
This unit can be installed on a solid combustible
surface like a wood fl oor. This unit can also be
installed directly on carpeting or vinyl when the
bottom pedestal cover plate (provided with unit)
is installed.
Use the minimum clearances shown in the
diagrams below:
U39-NG1 & U39-LP1 Clearances
A Side Wall to Unit 7-1/2" / 190 mm
B Back Wall to Unit 6" / 150 mm
E Side Wall to Unit 2" / 50 mm
U39-NG1 & U39-LP1 Reference
Dimensions
C Back Wall to Flue Centerline 11"/280 mm
D Side Wall to Flue Centerline 20-1/2"/521 mm
F Side Wall to Flue Centerline 11"/280 mm
Minimum ceiling height is 36" / 914 mm from top
of unit.
Regency® U39 ULTIMATE Direct Vent Freestanding Gas Stove
7
INSTALLATION
Minimum ceiling
height is 36"/914mm
from top of unit.
A) Cross Corner
B) Room Divider
C) Island
D) Flat on Wall
E) Flat on Wall Corner
F) Flush with Wall/ Alcove
For Vent Termination requirements, see
"Exterior Vent termination Locations" section.
LOUVER
INSTALLATION
1) Attach the top & bottom louvers to the
side stove panel using 2 screws per
side.
VENTING
INTRODUCTION
The DV Stove Horizontal Vent Kit and the
Simpson Dura-Vent Direct Vent System Model
DV-GS venting systems, in combination with the
ULTIMATE Direct Vent Freestanding Gas Stove,
U39-NG1, and U39-LP1, have been tested and
listed as direct vent heater systems by Warnock
Hersey. If converting a Class-A Metal Chimney
or Masonry Chimney to a Direct Vent system,
see instructions in "Converting a Class-A Metal
Chimney or Masonry Chimey to a Direct Vent
System" section.
These units use the "balanced fl ue" technology
Co-Axial system. The inner liner vents products
of combustion to the outside while the outer
pipe draws outside combustion air into the
combustion chamber thereby eliminating the
need to use heated room air for combustion and
losing warm room air up the chimney.
Note: These flue pipes must not be
connected to any other appliance.
The gas appliance and vent system must be
vented directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each direct vent gas appliance must use it's own
separate vent system. Common vent systems
are prohibited.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8 ground
lug provided.
3) Appliance must be anchored to the fl oor with
the supplied anchoring methods.
LOCATING YOUR
ULTIMATE GAS STOVE
When selecting a location for your stove, ensure
that the clearances listed above are met as well
as ensuring that there is adequate accessibility
for servicing and proper operation.
Read all instructions carefully before starting the
IMPORTANT
installation. Failure to follow these instructions
may create a fi re or other safety hazard, and will
void the warranty. Be sure to check the venting
and clearance to combustible requirements.
Consult your local building codes before
beginning installation.
The location of the termination cap must conform
to the requirements in the "Exterior Vent Terminal
Locations" section.
COMBUSTION AND
VENTILATION AIR
The combustion air from this appliance is drawn
from outside the building through the outer fl ue.
Extra provision for combustion air inside the
room is not required.
®
8
Regency
U39 ULTIMATE Direct Vent Freestanding Gas Stove
EXTERIOR VENT TERMINAL LOCATIONS
INSTALLATION
with Dura-Vent termination cap (min. 12"/30cm)
horizontally from the centerline of the regulator.
H= Not to be installed above a meter/regulator assembly within (3'/90cm)
air inlet to any other appliance *(12"/30cm)
J= Clearance to service regulator vent outlet *(min. 36"/90cm)
K= Clearance to non-mechanical air supply inlet to building or the combustion
property *(min. 84"/2.1m)
L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m)
M= **Clearance above paved sidewalk or a paved driveway located on public
N= Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)***
Regency® U39 ULTIMATE Direct Vent Freestanding Gas Stove
12"/30cm)
A= Clearance above grade, veranda, porch, deck, or balcony *(min.
B= Clearance to window or door that may be opened *(12"/30cm)
horizontal distance of (24"/60cm) from the centerline of the terminal (min.
18"/46cm) check with local code.
C= Clearance to permanently closed window *(min. 12"/30cm)
D= Vertical clearance to ventilated soffi t located above the terminal within a
with Dura-Vent termination cap (min. 12"/30cm)
E= Clearance to unventilated soffi t (min. 12"/30cm)
F= Clearance to outside corner: with AstroCap Termination Cap (min. 6"/15cm),
Note: * As specifi ed in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.
G= Clearance to inside corner: with AstroCap Termination Cap (min. 6"/15cm),
**A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
9
INSTALLATION
4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Description
6” Pipe Length, Galvanized
6” Pipe Length, Black
7” Pipe Length, Galvanized
7” Pipe Length, Black
9” Pipe Length, Galvanized
9” Pipe Length, Black
12” Pipe Length, Galvanized
12” Pipe Length, Black
18” Pipe Length, Galvanized
18” Pipe Length, Black
24” Pipe Length, Galvanized
24” Pipe Length, Black
36” Pipe Length, Galvanized
36” Pipe Length, Black
48” Pipe Length, Galvanized
48” Pipe Length, Black
60” Pipe Length, Galvanized
60” Pipe Length, Black
Adjustable Length 3”-10”, Galvanized
Adjustable Length 3”-10”, Black
Adjustable Length 11”-14”, Galvanized
Adjustable Length 11”-14”, Black
Adjustable Length 17”-24”, Galvanized
Adjustable Length 17”-24”, Black
Adjustable Length 7”, Galvanized
Adjustable Length 7”, Black
Extension Pipe 8-1/2”, Galvanized
Extension Pipe 8-1/2”, Black
Adjustable Length 12”, Galvanized
Adjustable Length 12”, Black
Extension Pipe 16”, Galvanized
Extension Pipe 16”, Black
Simpson
Direct Vent Pro
46DVA-069084DT-6N/A4D6SV4L6
46DVA-06B908B4DT-6BN/A4D6BSV4LB6
N/AN/AN/A4D7N/AN/A
N/AN/AN/A4D7BN/AN/A
46DVA-099074DT-9N/AN/AN/A
46DVA-09B907B4DT-9BN/AN/AN/A
46DVA-129064DT-124D124D12SV4L12
46DVA-12B906B4DT-12B4D12B4D12BSV4LB12
46DVA-18N/A4DT-18N/A4D18SV4LA
46DVA-18BN/A4DT-18BN/A4D18BSV4LA
46DVA-249044DT-244D24D24SV4L24
46DVA-24B904B4DT-24B4D2B4D24BSV4LB24
46DVA-369034DT-364D34D36SV4L36
46DVA-36B903B4DT-36B4D3B4D36BSV4LB36
46DVA-489024DT-484D44D48SV4L48
46DVA-48B902B4DT-48B4D4B4D48BSV4LB48
46DVA-60N/AN/AN/AN/AN/A
46DVA-60BN/AN/AN/AN/AN/A
N/AN/AN/AN/A4DALN/A
N/AN/AN/AN/A4DALBN/A
Disc - See 46DV-08AN/A4DT-AJN/AN/AN/A
Disc - See 46DV-08AB911B4DT-AJBN/AN/AN/A
Disc - See 46DV-16A917 - N/A from FPI N/AN/AN/AN/A
Disc - See 46DV-16AB917BN/AN/AN/ASV4LBA24
N/AN/AN/A4D7AN/AN/A
N/AN/AN/A4D7ABN/AN/A
46DVA-08AN/AN/AN/AN/AN/A
46DVA-08ABN/AN/AN/AN/AN/A
N/AN/AN/A4D12AN/ASV4LA12
N/AN/AN/A4D12ABN/ASV4LBA12
46DVA-16AN/AN/AN/AN/AN/A
46DVA-16ABN/AN/AN/AN/AN/A
®
Simpson
Direct Vent GS
Discontinued
®
Selkirk
Direct-Temp™
American Metal
Products
Amerivent Direct
®
Metal-Fab
Sure Seal
®
Security
Secure Vent
®
45º Elbow, Galvanized
45º Elbow, Black
45º Elbow, Swivel, Galvanized
45º Elbow, Swivel, Black
90º Elbow, Galvanized
90º Elbow, Black
90º Elbow, Swivel, Galvanized
90º Elbow, Swivel, Black
90º Starter Elbow, Swivel, Galvanized*
Adaptor*
Ceiling Support
Cathedral Support Box
Wall Support/Band
Offset Support
Wall Thimble, Black
Wall Thimble Support Box/Ceiling Support
Firestop Spacer
Trim Plate, Black
Masonry Chimney Flashing
Brass Trim for Wall Thimble/Ceiling Support
10
46DVA-E459454DT-EL454D45LN/AN/A
46DVA-E45B945B4DT-EL45B4D45LBN/AN/A
Disc - See 46DVA-E45945GN/AN/A4D45LSV4E45
Disc - See 46DVA-
E45B
46DVA-E909904DT-EL90S4D90LSN/AN/A
46DVA-E90B990B
Disc - See 46DVA-E90990GN/AN/A4D90LSV4E90-1
Disc - See 46DVA-
E90B
N/AN/AN/AN/A4D90AN/A
N/AN/AN/AN/A4DDAN/A
N/A949 - N/A from FPI 4DT-CS4DFSP4DSPSV4SD
46DVA-CS9414DT-CSS4DRSB4DRSSV4CSB
46DVA-WS9884DT-WS/B4DWS4DWSSV4BM
46DVA-ES - N/A from FPI
46DVA-WT9424DT-WT4DWT4DWTSV4RSM
46DVA-DCN/AN/AN/AN/ASV4PF
46DVA-FS9634DT-FS4DFSP4DFSSV4BF
N/AN/A4DT-TP4DFPB4DCPSV4LA
N/AN/AN/AN/AN/AN/A
DISC.3951N/AN/AN/AN/A
945BGN/AN/A4D45LBSV4EB45
4DT-EL90SB
990BGN/AN/A4D90LBSV4EB90-1
989 - N/A from FPI 4DT-OSN/AN/ASV4SU
®
Regency
U39 ULTIMATE Direct Vent Freestanding Gas Stove
4D90LBSN/ASV4EBR90-1
INSTALLATION
4” x 6-5/8” Rigid Pipe Cross Reference Chart (Cont.)
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Restrictor Disk
Extended Vertical Termination Cap
Chimney Conversion Kit A
Chimney Conversion Kit B
Chimney Conversion Kit C
Chimney Conversion Kit Masonry
Mansonry Chimney Conversion Kit
(includes: Cap Adapter 18”x18” Flashing)
Wall Firestop
Colinear Flex Connectors
FPI
946-506/PVent Guard (Optional) for AstropCap946-205Vinyl Siding Shield for Riser Vent Terminal
510-994Rigid Pipe Adapter (Must use with all Rigid Piping)946-208/PVent Guard (Optional) for Riser Vent Terminal
640-530/PRiser Vent Terminal946-523/PAstroCap Horizontal Cap
DISC.9704DT-HKA4DHTK24DHTKASV - SHK
46DVA-KHA
(Changed Components)
DISC.9784DT-VKC4DVTK4DVTKSV - FK
46DVA-VCH991N/AN/AN/AN/A
46DVA-HC985N/AN/AN/AN/A
Disc - See 46DVA-HC9844DT-HHC4DHC4DHTSV4CHC-1
46DVA-VC9804DT-HVC4DVC4DVTSV4CGV-1
46DVA-SC9534DT-SC4DSC4DSCSV4FC
46DVA-F69434DT-AF64DF4DFSV4FA
46DVA-F12943S4DT-AF124DF124DF-12SV4FB
46DVA-VSS9504DT-VSN/A4DVSSV4VS
N/AN/A4DT-VSPN/AN/ASV4VS
46DVA-SNK149824DT-ST144D12S4DST14SV4STC14
N/A9814DT-ST364D36S4DST36SV4STC36
46DVA-RD929N/AN/AN/AN/A
46DVA-VCE930N/AN/AN/AN/A
46DVA-KCA931N/AN/AN/AN/A
46DVA-KCB932N/AN/AN/AN/A
46DVA-KCC933N/AN/AN/AN/A
46DVA-KMC934N/AN/AN/AN/A
46DVA-KCT935N/AN/AN/AN/A
46DVA-WFS947N/AN/AN/AN/A
46DVA-ADF923FN/AN/AN/AN/A
9714DT-HKB4DHTK14DHTKBSV - HK
946-206Vinyl Siding Standoff for AstroCap
*NOTE: When using Metal-Fab Sure Seal Rigid Piping please note that either the Adaptor (4DDA) or 90º Starter Elbow (4D90A)
must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).
Offset Pipe Selection:
Use this table to determine offset pipe lengths.
Pipe Length
0”(0mm)4-7/8”(124mm)13-3/8”(340mm)
6”(152mm)8”(203mm)16-1/2”(419mm)
9”(229mm)10-1/8”(257mm)18-5/8”(473mm)
12”(305mm)12-1/4”(311mm)20-3/4”(527mm)
24”(610mm)20-5/8”(524mm)29-1/8”(740mm)
36”(914mm)29”(737mm)37-1/2”(953mm)
48”(1219mm)37-7/16”(951mm)45-15/16”(1167mm)
NOTE:Horizontal runs of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards
the termination. Never allow the vent to run downward. This could cause high temperatures and
may present a possible fi re hazard.
4” x 6-5/8” Venting
Run (X)Rise (Y)
L
Y
X
Regency® U39 ULTIMATE Direct Vent Freestanding Gas Stove
For specifi c instructions or details on particular
venting components please visit the following
websites:
Simpson Direct Vent Pro: www.duravent.com
Selkirk Direct-Temp: www.selkirkcorp.com
American Metal Products Amerivent Direct:
www.americanmetalproducts.com
Metal-Fab Sure Seal: www.mtlfab.com
Security Secure Vent: www.securitychimneys.com
11
INSTALLATION
Alternate
Horizontal Termination Caps
RIGID PIPE VENTING SYSTEMS
Horizontal or Vertical Terminations
WARNING:
Do not combine venting components from
different venting systems.
However use of the the AstroCapTM and FPI
Riser is acceptable with all systems.
This product has been evaluated by Intertek for
using a Rigid Pipe Adaptor in conjunction with
Duravent Direct-Vent GS, Selkirk Direct-Temp,
Ameri Vent Direct venting and Security Secure
Vent systems. Use of these systems with the
Rigid Pipe adaptor is deemed acceptable
and does not affect the Intertek WHI listing of
components.
The FPI AstroCap
American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, Selkirk Direct-Temp. AstroCapTM is a proprietary trademark of FPI Fireplace
Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
TM
and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent GS,
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
12
Regency
®
U39 ULTIMATE Direct Vent Freestanding Gas Stove
INSTALLATION
INSTALLATION
PRECAUTIONS
These venting systems are engineered
products that have been designed and
tested for use with the U39-NG1, and
U39-LP1. The warranty will be voided
and serious fi re, health or other safety
hazards may result from any of the following
actions:
1) Installation of any damaged Direct Vent
component
2) Unauthorized modifi cation of the Direct
Vent System
3) Installation of any component part not
manufactured or approved by Simpson
Dura-Vent or Fireplace Products
International Ltd.
4) Installation other than as instructed
by Simpson Dura-Vent and Fireplace
Products International Ltd.
Warning: Always maintain
required clearances (air spaces)
to nearby combustibles to
prevent a fi re hazard. Do not fi ll
air spaces with insulation.
RIGID PIPE VENTING ARRANGEMENTS
Horizontal Terminations for All
Venting Systems
The shaded areas in the diagram below show
all allowable combinations of vertical runs
with horizontal terminations. Maximum one
90O elbow (two 45o elbows equal one 90o
elbow).
Propane and Natural Gas:
Residential, Manufactured and
Mobile Homes Installations
The venting arrangements diagrammed below,
have a min. of 75% (fl ue loss) effi ciency with Fan
Off, as required for manufactured homes. (Actual
effi ciency may be as high as 85%)
May be installed in Manufactured (Mobile)
Homes after fi rst sale.
Vertical Termination Systems for
Residential Manufactured and
Mobile Homes
The shaded area in the diagram below shows all
allowable combinations of straight vertical and
offset to vertical runs with vertical terminations.
Maximum two 45o elbows.
If the vent is ENCLOSED in a chase (min. size 9" x
9") maintain a 1-1/4" clearance to combustibles.
May be installed in Manufactured (Mobile)
Homes after fi rst sale.
Be sure to check the vent termination
clearance requirements from decks,
windows, soffi ts, gas regulators, air supply
inlets and public walkways as specifi ed
in the "Exterior Vent Terminal Locations"
section in your local building codes.
The gas appliance and vent system
must be vented directly to the outside
of the building, and never be attached
to a chimney serving a separate solid
fuel or gas-burning appliance. Each
direct vent gas appliance must use it's
own separate vent system. Common vent
systems are prohibited.
SAFETY
PRECAUTIONS FOR
THE INSTALLER
1) Wear gloves and safety glasses for
protection.
2)Exercise extreme caution when using
ladders or on roof tops.
3)Be aware of electrical wiring locations
in walls and ceilings.
To set the Vent restriction as
indicated in the diagram, simply
loosen the screws and push the
vent restrictor plate to the correct
position. Tighten the screws.
Vent Restrictor Position
Vent Restrictor setting at
38,000 Btu/h
Vent Restrictor setting at
30,000 Btu/h
Regency® U39 ULTIMATE Direct Vent Freestanding Gas Stove
13
INSTALLATION
Horizontal Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V H + H1
A) 3' Min. 2' Max.
B) 5' Min. 3' Max.
C) 8' Min. 4' Max.
With these options, maximum total
pipe length is 30 feet with minimum
of 8 feet total vertical and maximum
4 feet total horizontal.
Please note minimum 1 foot
between 90o elbows is required.
Lengths do not include elbow
indicated
Vent restrictor position A (fully
open), Refer to the "Venting Arrangement" section.
Vertical Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V H V1 V + V1 A) 1' Min. 1' Max. 1' Min. 2' Min.
B) 1' Min. 2' Max. 2' Min. 3' Min.
C) 2' Min. 3' Max. 2' Min. 4' Min.
D) 2' Min. 4' Max. 2' Min. 4' Min.
With these options, max. total pipe length is 30
feet with min. of 4 feet total vertical and max. 4 feet
total horizontal.
Please note min. 1 foot between 90
required.
Lengths do not include elbow indicated
Vent restrictor position A (fully open). Refer to
the "Venting Arrangement" section.
o
elbows is
14
Regency
®
U39 ULTIMATE Direct Vent Freestanding Gas Stove