Regency U39-NG, U39-LP User Manual

www.regency-fire.com
ULTIMATE U39
Direct Vent Freestanding Gas Stove
Owners &
Installation Manual
MODELS: U39-NG Natural Gas U39-LP Propane
WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4918-027b
FOR YOUR SAFETY What to do if you smell gas:
Do not try to light any appliance Do not touch any electrical switch: do not use any phone in your building. Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's instructions. If you cannot reach your gas supplier, call the fire department.
01/09/06
REGENCY
ULTIMATE Direct Vent Freestanding Gas Stove
To the New Owner:
Congratulations! You are the owner of a state-of-the-art ULTIMATE Direct Vent Gas Stove by FPI Fireplace Products International Ltd. The Regency Gas Series of hand crafted appliances has been designed to provide you with all the warmth and charm of a woodstove, at the flick of a switch. The models U39-NG, and U39­LP of this series has been approved by Warnock Hersey for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your ULTIMATE Direct Vent Freestanding Gas Stove.
UNIT SPECIFICATIONS
U39-NG & U39-LP
2
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
TABLE OF CONTENTS
Page Page
Safety Label
Safety Labels .......................................................................... 4
Installation
Specifications ..........................................................................5
Information for Mobile/Manufactured Home
After First Sale..................................................................5
Before You Start.......................................................................5
General Safety Information....................................................6
Installation Checklist..............................................................6
Clearances to Combustibles ...............................................6
Manufactured Mobile Home Requirements.......................7
Locating Your ULTIMATE Gas Stove ...................................7
Louver Installation...................................................................7
Combustion and Ventilation Air............................................7
Venting ......................................................................................7
Installation Precautions .........................................................7
Exterior Vent Terminal Locations .........................................8
Rigid Pipe Venting Components List..................................9
Rigid Pipe Venting Systems
Horizontal or Vertical Terminatioins ..........................10
Safety Precautions for the Installer ....................................11
Venting Arrangements - Horizontal
Terminations: All Systems ..........................................11
Venting Arrangements - Vertical Terminations ...............11
- Straight Vertical ...........................................................11
- Offset Vertical...............................................................11
Vent Restrictor Position .......................................................11
Horizontal and Vertical Venting With Two Elbows ..........12
DV Stove Horizontal Vent Kit................................................13
Dura-Vent Termination Kits .................................................15
Planning Your Dura-Vent Installation ................................15
Dura-Vent Venting Components Parts List......................15
Dura-Vent Horizontal Installation .......................................16
Dura-Vent Vertical Termination Installation .....................17
Offset Chart ............................................................................18
Cathedral Ceiling Installations ...........................................18
Support Extension - Round or Square ..............................19
Converting a Class-A Metal Chimney or Masonry
Chimney to a Direct Vent System ...............................19
- Instructions for Converting a Factory Built
Metal Chimney.............................................................19
- Instructions for Converting a Masonry Chimney...20
System Data Chart................................................................21
Gas Connection ....................................................................21
High Elevation........................................................................21
Conversion from Natural Gas to Propane........................22
Conversion to Lower BTU ...................................................23
Gas Pipe Pressure Testing ................................................23
Valve Description ..................................................................23
Aeration Adjustment .............................................................24
Log Installation ......................................................................24
Front Door Installation..........................................................25
Wiring Diagram .....................................................................26
Optional Wall Thermostat....................................................26
Optional Remote Control Installation................................26
Final Check ............................................................................27
Operating Instructions
Operating Instructions ..........................................................27
Lighting Procedure ...............................................................27
Shutdown Procedure............................................................27
First Fire ..................................................................................27
Convection Fan Operation...................................................28
Copy of Lighting Plate Instructions ....................................28
Adjusting Flame Height .......................................................28
Normal Operating Sounds of Gas Appliances ...............28
Maintenance
Maintenance Instructions ....................................................29
General Vent Maintenance ..................................................29
Gold Plated Doors ................................................................29
Log Replacement .................................................................30
Door Gasket...........................................................................30
Latch Adjustment ..................................................................30
Glass Replacement .............................................................30
Fan Maintenance...................................................................31
Removing Valve .....................................................................32
Replacement Parts List.......................................................33
Warranty
Warranty..................................................................................39
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
3
SAFETY LABEL
This is a copy of the label that accompa­nies each ULTIMATE Direct Vent Free­standing Gas Stove. We have printed a copy of the contents here for your review.
Copy of Safety Label for U39 Gas Stove
The safety label is located on the inside of the drop down pedestal door.
NOTE: Regency units are constantly be­ing improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length. For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type
valve.
4
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
INSTALLATION
IMPORTANT:
SAVE THESE
INSTRUCTIONS
The ULTIMATE Direct Vent Freestanding Gas Stove must be installed in accordance with these instructions. Carefully read all the in­structions in this manual first. Consult the building authority having jurisdiction to deter­mine the need for a permit prior to starting the installation.
Note: Failure to follow the instructions
could cause a malfunction of the heater which could result in death, serious bodily injury, and/or prop­erty damage. Failure to follow these instructions may also void your fire insurance and/or war­ranty.
Note: These instructions take prece-
dence over Simpson Dura-Vent instructions.
SPECIFICATIONS
Fuels: U39-NG is approved for use with nat-
ural gas. U39-LP is approved for use with lique-
fied petroleum gases (propane).
Electrical: 120V A.C. system. Circulation Fan: Variable speed, 125/75. Log Sets: Ceramic fibre, 7 per set. Vent System: Coaxial (6-5/8" outer / 4" inner
liner) rigid flue and termination cap.
Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.
This Regency Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the unit.
This Regency Mobile/Manufactured Home listed appliance comes equipped with a dedicated #8 ground lug to which an 18 gauge copper wire from the steel chassis ground must be attached.
This appliance may only be in­stalled in an aftermarket perma­nently located, manufactured (mo­bile) home, where not prohibited by local codes.
This appliance is only use with the type of gas indicated on the rating plate. This appliance is not con­vertible for use with other gases, unless a certified kit is used.
BEFORE YOU START
AND CIRCULATING AIR PASSAGE­WAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LO­CATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERA­TURES, ESPECIALLY THE FIRE­PLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
CLOTHING OR OTHER FLAMMA­BLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLI­ANCE.
1) Provide adequate clearances for servic-
ing, proper operation and around the air openings into the combustion chamber.
INFORMATION FOR
MOBILE/
MANUFACTURED
HOMES AFTER
FIRST SALE
Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
INSTALLATION AND REPAIRS SHOULD BE DONE BY A QUALI­FIED SERVICE PERSON. THIS AP-
This Regency product has been tested and listed by Warnock Hersey as a Direct Vent Wall Furnace to the following standards: CAN/CGA-
2.17-M91 and ANSI Z21.88b-2003/CSA 2.33b-
2003.
PLIANCE SHOULD BE INSTALLED, REPAIRED, INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A QUALIFIED SERVICE PERSON. MORE FREQUENT CLEANING MAY
This Direct Vent System Appliance must be installed in accordance with the manufactur­er's installation instructions and the Manufac­tured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, ETC. IT IS IMPERATIVE THAT THE CON­TROL COMPARTMENT, BURNERS
2) The appliance may be installed on a flat,
solid, continuous surface (e.g. wood, met­al, concrete). This may be the floor, or it can be raised up on a platform to enhance its visual impact. The appliance may be in­stalled on carpeting, tile, wood flooring or other combustible material, because the appliance's metal pedestal base extends the full width and depth of the appliance. The ULTIMATE Direct Vent Freestanding Gas Stove can be installed in a wide variety of ways and will fit nearly any room layout. It may be installed in a recessed position, framed out into the room, or across a corner.
3) The ULTIMATE Direct Vent Freestanding Gas Stove is approved for alcove installa­tions, which meet the clearances listed on page 7. This unit is approved for manufac­tured home installations, see page 11 for the required vent arrangements. If installed
5
INSTALLATION
into a manufactured home the unit must be bolted down to the floor.
4) This appliance is Listed for bedroom instal­lations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
5) This appliance is Listed for Alcove installa­tions, maintain minimum Alcove clearances as follows, minimum width of 48" (1219mm), a maximum depth of 36" (914mm), and minimum ceiling height of 64"(1626mm).
6) We recommend that you plan your installa­tion on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have a qualified building inspector review your plans before installation.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform
with local Canadian Electrical Code.
2) The appliance when installed, must be elec­trically grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/ NFPA 70 or CSA C22.1 Canadian Electrical Code.
3) The appliance should be inspected for shipping damage before use and serviced
annually by a professional service person. More frequent cleaning may be
required due to excessive lint from carpet­ing, bedding material, etc. It is imperative that control compartments, and circulating air passageways of the appliance be kept clean and free from excessive lint from carpeting.
4) See general construction and assembly instructions. The appliance and vent should be enclosed when installed in or passing through a living area, where children may come in contact with it.
8) Any safety glass removed for servicing must be replaced prior to operating the appliance.
9) To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fireplace.
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
INSTALLATION
CHECKLIST
1) Check Clearances to Combustibles (pages
6 and 7), location of unit (page 7) and venting requirements (pages 7 to 9).
2) Install Louvers, page 7.
3) Install venting, either with the DV Stove
Horizontal Vent Kit (page 10) or the Dura­Vent Termination kits (page 12). Set Vent Restrictors, page 9. If converting a Class­A Metal Chimney or Masonry Chimney to a Direct Vent system, see instructions on pages 19 to 21.
4) Make gas connections, page 21. Test the pilot. Must be as per diagram, page 29.
5) If necessary, convert to Propane (page 22) or convert to lower Btu rating (page 23).
6) Test Gas Pressure, page 23.
7) Install log set, see page 24.
8) Install Front Door Front, page 25.
9) Install optional Remote Control, or Wall Ther-
mostat, page 26.
10)Final check, page 27.
Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly and operation fully explained to
customer.
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances. Measure the clearance to both the appliance and the chimney connector. The farthest
distance is correct if the two clearances do not coincide.
For example, if the appliance is set as indicated in one of the figures but the connector is too close, move the stove until the correct clear­ance to the connector is obtained.
This appliance may be installed only with the clearances as shown in the situations pictured.
Do not combine clearances from one type of installation with another in order to achieve closer clearances.
This unit can be installed on a solid combustible surface like a wood floor. This unit can also be installed directly on carpeting or vinyl when the bottom pedestal cover plate (provided with unit) is installed.
Use the minimum clearances shown in the diagrams below:
U39-NG & U39-LP Clearances
A Side Wall to Unit 7-1/2" / 190 mm B Back Wall to Unit 6" / 150 mm E Side Wall to Unit 2" / 50 mm
U39-NG & U39-LP Reference
Dimensions
C Back Wall to Flue Centerline 11"/280 mm D Side Wall to Flue Centerline 20-1/2"/521 mm F Side Wall to Flue Centerline 11"/280 mm Minimum ceiling height is 36" / 914 mm from top of unit.
5) This appliance must be connected to the specified vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fitted as per the instruc­tions starting on page 7.
6) Inspect the venting system annually for blockage and any signs of deterioration.
7) Venting terminals shall not be recessed into a wall or siding.
6
This includes:
1) Clocking the appliance to ensure the cor-
rect firing rate (rate noted on label) after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibil­ity of the manufacturer.
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
INSTALLATION
Minimum ceiling
height is 36"/914mm
from top of unit.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8 ground lug provided.
3) Appliance must be anchored to the floor with the supplied anchoring methods.
LOCATING YOUR
ULTIMATE GAS STOVE
When selecting a location for your stove, ensure that the clearances listed above are met as well as ensuring that there is adequate accessibility for servicing and proper opera­tion.
LOUVER
INSTALLATION
1) Attach the top & bottom louvers to the
side stove panel using 2 screws per side.
COMBUSTION AND
VENTILATION AIR
The combustion air from this appliance is drawn from outside the building through the outer flue.
Extra provision for combustion air inside the room is not required.
VENTING
INTRODUCTION
The DV Stove Horizontal Vent Kit and the Simpson Dura-Vent Direct Vent System Model DV-GS venting systems, in combination with the ULTIMATE Direct Vent Freestanding Gas Stove, U39-NG, and U39-LP , have been tested and listed as direct vent heater systems by Warnock Hersey. If converting a Class-A Metal Chimney or Masonry Chimney to a Direct Vent system, see instructions on pages 19 to 21.
These units use the "balanced flue" technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer pipe draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These flue pipes must not be con-
nected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent sys­tems are prohibited.
IMPORTANT
Read all instructions carefully before starting the installation. Failure to follow these instruc­tions may create a fire or other safety hazard, and will void the warranty. Be sure to check the venting and clearance to combustible require­ments. Consult your local building codes before beginning installation.
The location of the termination cap must con­form to the requirements in the Exterior Vent Terminal Locations diagram on page 8.
A) Cross Corner B) Room Divider
C) Island D) Flat on Wall E) Flat on Wall Corner F) Flush with Wall/ Alcove
For Vent Termination require­ments, see page 8.
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
INSTALLATION PRECAUTIONS
These venting systems are engineered prod­ucts that have been designed and tested for use with the U39-NG, and U39-LP . The warran­ty will be voided and serious fire, health or other safety hazards may result from any of the following actions:
1) Installation of any damaged Direct Vent component
2) Unauthorized modification of the Direct Vent System
3) Installation of any component part not man­ufactured or approved by Simpson Dura-
7
INSTALLATION
EXTERIOR VENT TERMINAL LOCATIONS
horizontally from the centerline of the regulator.
H= Not to be installed above a meter/regulator assembly within (3'/90cm)
air inlet to any other appliance *(12"/30cm)
J= Clearance to service regulator vent outlet *(min. 36"/90cm)
K= Clearance to non-mechanical air supply inlet to building or the combustion
property *(min. 84"/2.1m)
L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m)
M= **Clearance above paved sidewalk or a paved driveway located on public
N= Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)***
horizontal distance of (24"/60cm) from the centerline of the terminal (min.
18"/46cm) check with local code.
A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm)
B= Clearance to window or door that may be opened *(12"/30cm)
C= Clearance to permanently closed window *(min. 12"/30cm)
D= Vertical clearance to ventilated soffit located above the terminal within a
8
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
15cm), with Dura-Vent termination cap (min. 12"/30cm)
15cm), with Dura-Vent termination cap (min. 12"/30cm)
E= Clearance to unventilated soffit (min. 12"/30cm)
F= Clearance to outside corner: with AstroCap Termination Cap (min. 6"/
G= Clearance to inside corner: with AstroCap Termination Cap (min. 6"/
Note: * As specified in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.
**A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
***Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
INSTALLATION
RIGID PIPE VENTING COMPONENTS LIST
All Simpson Dura-Vent components are available directly from FPI.
Description Simpson Dura-Vent Selkirk Amerivent
Direct VentGS
6" Pipe Length, Galvanized 908 4DT-6 N/A 6" Pipe Length, Black 908B 4DT-6B N/A 7" Pipe Length, Galvanized N/A N/A 4D7 7" Pipe Length, Black N/A N/A 4D7B 9" Pipe Length, Galvanized 907 4DT-9 N/A 9" Pipe Length, Black 907B 4DT-9B N/A 12" Pipe Length, Galvanized 906 4DT-12 4D12 12" Pipe Length, Black 906B 4DT-12B 4D12B 18" Pipe Length, Galvanized N/A 4DT-18 N/A 18" Pipe Length, Black N/A 4DT-18B N/A 24" Pipe Length, Galvanized 904 4DT-24 4D2 24" Pipe Length, Black 904B 4DT-24B 4D2B 36" Pipe Length, Galvanized 903 4DT-36 4D3 36" Pipe Length, Black 903B 4DT-36B 4D3B 48" Pipe Length, Galvanized 902 4DT-48 4D4 48" Pipe Length, Black 902B 4DT-48B 4D4B
Adjustable Length, 11"-14", Galv. 911 4DT-AJ N/A Adjustable Length, 11"-14", Black 911B 4DT-AJB N/A Adjustable Length, 17"-24", Black 917B N/A N/A Adjustable Length, 7" Galvinized N/A N/A 4D7A Adjustable Length, 7" Black N/A N/A 4D7AB Adjustable Length, 12" Galvinized N/A N/A 4D12A Adjustable Length, 12" Black N/A N/A 4D12AB
45O Elbow, Galvinized 945 4DT-EL45 4D45L 45O Elbow, Black 945B 4DT-EL45B 4D45LB 45O Elbow, Swivel, Galvinized 945G N/A N/A 45O Elbow, Swivel, Black 945BG N/A N/A 90O Elbow, Galvinized 990 4DT-EL90S 4D90LS 90O Elbow, Black 990B 4DT-EL90SB 4D90LBS 90O Elbow, Swivel, Galvinized 990G N/A N/A 90O Elbow, Swivel, Black 990BG N/A N/A
Ceiling Support 949 - n/a from FPI 4DT-CS 4DFSP Cathedral Support Box 941 4DT-CSS 4DRSB Wall Support/Band 988 4DT-WS/B 4DWS Offset Support 989 - n/a from FPI 4DT-OS N/A Wall Thimble, Black 942 4DT-WT 4DWT Wall Thimble Support Box/Ceiling Support 940 N/A N/A Firestop Spacer 963 4DT-FS 4DFSP Trim Plate, Black N/A 4DT-TP 4DFPB Brass Trim for Wall Thimble/Ceiling Support 3951 N/A N/A
Attic Insulation Shield 12" N/A N/A 4DAIS12 Attic Insulation Shield - Cold Climates 36" N/A N/A 4DAIS36
R
Direct-Temp
TM
Direct Vent
R
Basic Horizontal Termination Kit (A) 970 4DT-HKA 4DHTK2 Horizontal Termination Kit (B) 971 4DT-HKB 4DHTK1 Vertical Termination Kit 978 4DT-VKC 4DVTK
High Wind Vertical Cap 991 N/A N/A High Wind Horizontal Cap 985 N/A N/A Horizontal Square Termination Cap 984 4DT-HHC 4DHC Verical Termination Cap 980 4DT-HVC 4DVC Storm Collar 953 4DT-SC 4DSC
Adjustable Flashing, 0/12-6/12 943 4DT-AF6 4DF Adjustable Flashing, 6/12-12/12 943S 4DT-AF12 4DF12
Vinyl Siding Standoff 950 4DT-VS N/A Vinyl Siding Shield Plate N/A 4DT-VSP N/A
Snorkel Termination 14" 982 4DT-ST14 4D12S Snorkel Termination 36" 981 4DT-ST36 4D36S
946-506/P Vent Guard (Optional) 640-530/P Riser Vent Terminal 946-205 Vinyl Siding Shield for Riser Vent Terminal
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
946-208/P Vent Guard (Optional) - Riser Vent Terminal 946-523/P AstroCap Horizontal Cap 946-206 Vinyl Siding Standoff - AstroCap
9
INSTALLATION
Alternate
Horizontal
Termination
Caps
RIGID PIPE VENTING SYSTEMS
Horizontal or Vertical Terminations
WARNING:
Do not combine venting components from different venting systems.
However use of the the AstroCapTM and FPI Riser is acceptable with all systems.
This product has been evaluated by Intertek for using a Dura-Vent Flue Adaptor in conjunction with Selkirk Direct-Temp and Ameri Vent Direct venting systems. Use of these systems with the Direct Vent GS starting collar is deemed acceptable and does not affect the Intertek WHI listing of components.
The FPI AstroCap GS, American Metal Products, Ameri Vent Direct vent and Selkirk Direct-Temp. FPITM, and FPI AstroCapTM are the proprietary trademarks of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
TM
and FPI Riser Vent terminal is certified for installations using FPI venting systems as well as Simpson Dura-Vent®, Direct Vent
When using piping other than Simpson
Dura-Vent, 3 screws must be used to
secure rigid pipe to adaptor.
10
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
INSTALLATION
Vent or Fireplace Products Interna­tional Ltd.
4) Installation other than as instructed by Simpson Dura-Vent and Fireplace Prod­ucts International Ltd.
Warning: Always maintain re­quired clearances (air spaces) to nearby combustibles to pre­vent a fire hazard. Do not fill air spaces with insulation.
Be sure to check the vent termination clearance requirements from decks, win­dows, soffits, gas regulators, air supply inlets and public walkways as specified in the Exterior Vent Terminal Locations on page 8 and in your local building codes.
The gas appliance and vent system must be vented directly to the out­side of the building, and never be attached to a chimney serving a sep­arate solid fuel or gas-burning appli­ance. Each direct vent gas appliance
must use it's own separate vent system. Common vent systems are prohibited.
RIGID PIPE VENTING ARRANGEMENTS
Horizontal Terminations for All
Venting Systems
The shaded areas in the diagram below show all allowable combinations of verti­cal runs with horizontal terminations. Maximum one 90O elbow (two 45o elbows equal one 90o elbow).
Propane and Natural Gas:
Residential, Manufactured and
Mobile Homes Installations
The venting arrangements diagrammed below, have a min. of 75% (flue loss) efficiency with Fan Off, as required for manufactured homes. (Actual efficiency may be as high as 85%)
May be installed in Manufactured (Mobile)
Homes after first sale.
Vertical Termination Systems for
Residential Manufactured and
Mobile Homes
The shaded area in the diagram below shows all allowable combinations of straight verti­cal and offset to vertical runs with vertical terminations. Maximum two 45o elbows.
If the vent is ENCLOSED in a chase (min. size 9" x 9") maintain a 1-1/4" clearance to combustibles.
May be installed in Manufactured (Mobile)
Homes after first sale.
SAFETY
PRECAUTIONS FOR
THE INSTALLER
1) Wear gloves and safety glasses
for protection.
2) Exercise extreme caution when
using ladders or on roof tops.
3) Be aware of electrical wiring lo-
cations in walls and ceilings.
Vent Restrictor Position
To set the Vent restriction as indi­cated in the diagram, simply loosen the screws and push the vent restrictor plate to the correct posi­tion. Tighten the screws.
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
Vent Restrictor setting at
38,000 Btu/h
Vent Restrictor setting at
30,000 Btu/h
11
INSTALLATION
Horizontal Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V H + H1
A) 3' Min. 2' Max. B) 5' Min. 3' Max. C) 8' Min. 4' Max.
With these options, maximum total pipe length is 30 feet with minimum of 8 feet total vertical and maximum 4 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to page 11.
Vertical Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V H V1 V + V1
A) 1' Min. 1' Max. 1' Min. 2' Min. B) 1' Min. 2' Max. 2' Min. 3' Min. C) 2' Min. 3' Max. 2' Min. 4' Min. D) 2' Min. 4' Max. 2' Min. 4' Min.
With these options, max. total pipe length is 30 feet with min. of 4 feet total vertical and max. 4 feet total horizontal.
Please note min. 1 foot between 90o elbows is required.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to page 11.
12