WARNING:
If the information in these instructions are not followed exactly,
a fire or explosion may result causing property damage,
personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4918-027b
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fire department.
01/09/06
REGENCY
ULTIMATE Direct Vent Freestanding Gas Stove
To the New Owner:
Congratulations! You are the owner of a state-of-the-art ULTIMATE Direct Vent Gas Stove by FPI Fireplace
Products International Ltd. The Regency Gas Series of hand crafted appliances has been designed to provide
you with all the warmth and charm of a woodstove, at the flick of a switch. The models U39-NG, and U39LP of this series has been approved by Warnock Hersey for both safety and efficiency. As it also bears our
own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow.
Please take a moment now to acquaint yourself with these instructions and the many features of your
ULTIMATE Direct Vent Freestanding Gas Stove.
UNIT SPECIFICATIONS
U39-NG & U39-LP
2
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
3
SAFETY LABEL
This is a copy of the label that accompanies each ULTIMATE Direct Vent Freestanding Gas Stove. We have printed a
copy of the contents here for your review.
Copy of Safety Label for U39 Gas Stove
The safety label is located on the inside of
the drop down pedestal door.
NOTE: Regency units are constantly being improved. Check the label on the unit
and if there is a difference, the label on the
unit is the correct one.
For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter
licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type
valve.
4
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
INSTALLATION
IMPORTANT:
SAVE THESE
INSTRUCTIONS
The ULTIMATE Direct Vent Freestanding Gas
Stove must be installed in accordance with
these instructions. Carefully read all the instructions in this manual first. Consult the
building authority having jurisdiction to determine the need for a permit prior to starting the
installation.
Note: Failure to follow the instructions
could cause a malfunction of the
heater which could result in death,
serious bodily injury, and/or property damage. Failure to follow
these instructions may also void
your fire insurance and/or warranty.
Installations, Sites, and Communities ANSI/NFPA
501A, and with CAN/CSA Z240-MH Mobile
Home Standard in Canada.
This appliance installation must comply with the
manufacturer's installation instructions and local
codes, if any. In the absence of local codes
follow the current National Fuel Gas Code,
ANSI Z223.1 and the current National Electrical
Code ANSI/NFPA 70 in the U.S.A., and the
current CAN/CGA B149 Gas Installation Code
and the current Canadian Electrical Code CSA
C22.1 in Canada.
This Regency Mobile/Manufactured
Home Listed appliance comes factory
equipped with a means to secure the
unit.
This Regency Mobile/Manufactured
Home listed appliance comes
equipped with a dedicated #8 ground
lug to which an 18 gauge copper wire
from the steel chassis ground must be
attached.
This appliance may only be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited
by local codes.
This appliance is only use with the
type of gas indicated on the rating
plate. This appliance is not convertible for use with other gases,
unless a certified kit is used.
BEFORE YOU START
AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE
KEPT CLEAN.
DUE TO HIGH TEMPERATURES,
THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND
AWAY FROM FURNITURE AND
DRAPERIES.
WARNING: FAILURE TO INSTALL
THIS APPLIANCE CORRECTLY
WILL VOID YOUR WARRANTY AND
MAY CAUSE A SERIOUS HOUSE
FIRE.
CHILDREN AND ADULTS SHOULD
BE ALERTED TO THE HAZARDS
OF HIGH SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND SHOULD
STAY AWAY TO AVOID BURNS
OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN
THEY ARE IN THE SAME ROOM AS
THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE
PLACED ON OR NEAR THE APPLIANCE.
1) Provide adequate clearances for servic-
ing, proper operation and around the air
openings into the combustion chamber.
INFORMATION FOR
MOBILE/
MANUFACTURED
HOMES AFTER
FIRST SALE
Safe installation and operation of this appliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of the
following:
INSTALLATION AND REPAIRS
SHOULD BE DONE BY A QUALIFIED SERVICE PERSON. THIS AP-
This Regency product has been tested and
listed by Warnock Hersey as a Direct Vent Wall
Furnace to the following standards: CAN/CGA-
2.17-M91 and ANSI Z21.88b-2003/CSA 2.33b-
2003.
PLIANCE SHOULD BE INSTALLED,
REPAIRED, INSPECTED BEFORE
USE AND AT LEAST ANNUALLY BY
A QUALIFIED SERVICE PERSON.
MORE FREQUENT CLEANING MAY
This Direct Vent System Appliance must be
installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard,
Title 24 CFR, Part 3280, or the current Standard
of Fire Safety Criteria for Manufactured Home
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, ETC. IT
IS IMPERATIVE THAT THE CONTROL COMPARTMENT, BURNERS
2) The appliance may be installed on a flat,
solid, continuous surface (e.g. wood, metal, concrete). This may be the floor, or it can
be raised up on a platform to enhance its
visual impact. The appliance may be installed on carpeting, tile, wood flooring or
other combustible material, because the
appliance's metal pedestal base extends
the full width and depth of the appliance.
The ULTIMATE Direct Vent Freestanding
Gas Stove can be installed in a wide variety
of ways and will fit nearly any room layout.
It may be installed in a recessed position,
framed out into the room, or across a
corner.
3) The ULTIMATE Direct Vent Freestanding
Gas Stove is approved for alcove installations, which meet the clearances listed on
page 7. This unit is approved for manufactured home installations, see page 11 for
the required vent arrangements. If installed
5
INSTALLATION
into a manufactured home the unit must be
bolted down to the floor.
4) This appliance is Listed for bedroom installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
5) This appliance is Listed for Alcove installations, maintain minimum Alcove clearances
as follows, minimum width of 48" (1219mm),
a maximum depth of 36" (914mm), and
minimum ceiling height of 64"(1626mm).
6) We recommend that you plan your installation on paper using exact measurements
for clearances and floor protection before
actually installing this appliance. Have a
qualified building inspector review your
plans before installation.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform
with local Canadian Electrical Code.
2) The appliance when installed, must be electrically grounded in accordance with local
codes, or in the absence of local codes with
the current National Electrical Code, ANSI/
NFPA 70 or CSA C22.1 Canadian Electrical
Code.
3) The appliance should be inspected for
shipping damage before use and serviced
annually by a professional service
person. More frequent cleaning may be
required due to excessive lint from carpeting, bedding material, etc. It is imperative that
control compartments, and circulating air
passageways of the appliance be kept
clean and free from excessive lint from
carpeting.
4) See general construction and assembly
instructions. The appliance and vent should
be enclosed when installed in or passing
through a living area, where children may
come in contact with it.
8) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
9) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fireplace.
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
INSTALLATION
CHECKLIST
1) Check Clearances to Combustibles (pages
6 and 7), location of unit (page 7) and
venting requirements (pages 7 to 9).
2) Install Louvers, page 7.
3) Install venting, either with the DV Stove
Horizontal Vent Kit (page 10) or the DuraVent Termination kits (page 12). Set Vent
Restrictors, page 9. If converting a ClassA Metal Chimney or Masonry Chimney to a
Direct Vent system, see instructions on
pages 19 to 21.
4) Make gas connections, page 21. Test the
pilot. Must be as per diagram, page 29.
5) If necessary, convert to Propane (page 22)
or convert to lower Btu rating (page 23).
6) Test Gas Pressure, page 23.
7) Install log set, see page 24.
8) Install Front Door Front, page 25.
9) Install optional Remote Control, or Wall Ther-
mostat, page 26.
10)Final check, page 27.
Before leaving this unit with the customer, the
installer must ensure that the appliance is firing
correctly and operation fully explained to
customer.
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance
and the chimney connector. The farthest
distance is correct if the two clearances
do not coincide.
For example, if the appliance is set as indicated
in one of the figures but the connector is too
close, move the stove until the correct clearance to the connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type
of installation with another in order to
achieve closer clearances.
This unit can be installed on a solid combustible
surface like a wood floor. This unit can also be
installed directly on carpeting or vinyl when the
bottom pedestal cover plate (provided with unit)
is installed.
Use the minimum clearances shown in the
diagrams below:
U39-NG & U39-LP Clearances
A Side Wall to Unit7-1/2" / 190 mm
B Back Wall to Unit6" / 150 mm
E Side Wall to Unit2" / 50 mm
U39-NG & U39-LP Reference
Dimensions
C Back Wall to Flue Centerline 11"/280 mm
D Side Wall to Flue Centerline 20-1/2"/521 mm
F Side Wall to Flue Centerline 11"/280 mm
Minimum ceiling height is 36" / 914 mm from top
of unit.
5) This appliance must be connected to the
specified vent and termination cap to the
outside of the building envelope. Never vent
to another room or inside a building. Make
sure that the vent is fitted as per the instructions starting on page 7.
6) Inspect the venting system annually for
blockage and any signs of deterioration.
7) Venting terminals shall not be recessed into
a wall or siding.
6
This includes:
1) Clocking the appliance to ensure the cor-
rect firing rate (rate noted on label) after
burning appliance for 15 minutes.
2) If required, adjusting the primary air to
ensure that the flame does not carbon. First
allow the unit to burn for 15-20 min. to
stabilize.
CAUTION: Any alteration to the product
that causes sooting or carboning that
results in damage is not the responsibility of the manufacturer.
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
INSTALLATION
Minimum ceiling
height is 36"/914mm
from top of unit.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8
ground lug provided.
3) Appliance must be anchored to the floor
with the supplied anchoring methods.
LOCATING YOUR
ULTIMATE GAS STOVE
When selecting a location for your stove,
ensure that the clearances listed above are
met as well as ensuring that there is adequate
accessibility for servicing and proper operation.
LOUVER
INSTALLATION
1) Attach the top & bottom louvers to the
side stove panel using 2 screws per
side.
COMBUSTION AND
VENTILATION AIR
The combustion air from this appliance is drawn
from outside the building through the outer flue.
Extra provision for combustion air inside
the room is not required.
VENTING
INTRODUCTION
The DV Stove Horizontal Vent Kit and the
Simpson Dura-Vent Direct Vent System Model
DV-GS venting systems, in combination with
the ULTIMATE Direct Vent Freestanding Gas
Stove, U39-NG, and U39-LP , have been tested
and listed as direct vent heater systems by
Warnock Hersey. If converting a Class-A Metal
Chimney or Masonry Chimney to a Direct Vent
system, see instructions on pages 19 to 21.
These units use the "balanced flue" technology
Co-Axial system. The inner liner vents products
of combustion to the outside while the outer
pipe draws outside combustion air into the
combustion chamber thereby eliminating the
need to use heated room air for combustion and
losing warm room air up the chimney.
Note: These flue pipes must not be con-
nected to any other appliance.
The gas appliance and vent system must be
vented directly to the outside of the building, and
never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each direct vent gas appliance must use it's
own separate vent system. Common vent systems are prohibited.
IMPORTANT
Read all instructions carefully before starting
the installation. Failure to follow these instructions may create a fire or other safety hazard,
and will void the warranty. Be sure to check the
venting and clearance to combustible requirements. Consult your local building codes before
beginning installation.
The location of the termination cap must conform to the requirements in the Exterior Vent
Terminal Locations diagram on page 8.
A) Cross Corner
B)Room Divider
C) Island
D) Flat on Wall
E) Flat on Wall Corner
F) Flush with Wall/ Alcove
For Vent Termination requirements, see page 8.
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
INSTALLATION
PRECAUTIONS
These venting systems are engineered products that have been designed and tested for
use with the U39-NG, and U39-LP . The warranty will be voided and serious fire, health or other
safety hazards may result from any of the
following actions:
1) Installation of any damaged Direct Vent
component
2) Unauthorized modification of the Direct Vent
System
3) Installation of any component part not manufactured or approved by Simpson Dura-
7
INSTALLATION
EXTERIOR VENT TERMINAL LOCATIONS
horizontally from the centerline of the regulator.
H= Not to be installed above a meter/regulator assembly within (3'/90cm)
air inlet to any other appliance *(12"/30cm)
J= Clearance to service regulator vent outlet *(min. 36"/90cm)
K= Clearance to non-mechanical air supply inlet to building or the combustion
property *(min. 84"/2.1m)
L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m)
M= **Clearance above paved sidewalk or a paved driveway located on public
N= Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)***
horizontal distance of (24"/60cm) from the centerline of the terminal (min.
B= Clearance to window or door that may be opened *(12"/30cm)
C= Clearance to permanently closed window *(min. 12"/30cm)
D= Vertical clearance to ventilated soffit located above the terminal within a
8
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
15cm), with Dura-Vent termination cap (min. 12"/30cm)
15cm), with Dura-Vent termination cap (min. 12"/30cm)
E= Clearance to unventilated soffit (min. 12"/30cm)
F= Clearance to outside corner: with AstroCap Termination Cap (min. 6"/
G= Clearance to inside corner: with AstroCap Termination Cap (min. 6"/
Note: * As specified in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.
**A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
***Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
INSTALLATION
RIGID PIPE VENTING COMPONENTS LIST
All Simpson Dura-Vent components are available directly from FPI.
Do not combine venting components from
different venting systems.
However use of the the AstroCapTM and FPI
Riser is acceptable with all systems.
This product has been evaluated by Intertek for
using a Dura-Vent Flue Adaptor in conjunction
with Selkirk Direct-Temp and Ameri Vent Direct
venting systems. Use of these systems with
the Direct Vent GS starting collar is deemed
acceptable and does not affect the Intertek WHI
listing of components.
The FPI AstroCap
GS, American Metal Products, Ameri Vent Direct vent and Selkirk Direct-Temp. FPITM, and FPI AstroCapTM are the proprietary trademarks of FPI
Fireplace Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
TM
and FPI Riser Vent terminal is certified for installations using FPI venting systems as well as Simpson Dura-Vent®, Direct Vent
When using piping other than Simpson
Dura-Vent, 3 screws must be used to
secure rigid pipe to adaptor.
10
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
INSTALLATION
Vent or Fireplace Products International Ltd.
4) Installation other than as instructed by
Simpson Dura-Vent and Fireplace Products International Ltd.
Warning: Always maintain required clearances (air spaces)
to nearby combustibles to prevent a fire hazard. Do not fill air
spaces with insulation.
Be sure to check the vent termination
clearance requirements from decks, windows, soffits, gas regulators, air supply
inlets and public walkways as specified in
the Exterior Vent Terminal Locations on
page 8 and in your local building codes.
The gas appliance and vent system
must be vented directly to the outside of the building, and never be
attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas appliance
must use it's own separate vent system.
Common vent systems are prohibited.
RIGID PIPE VENTING ARRANGEMENTS
Horizontal Terminations for All
Venting Systems
The shaded areas in the diagram below
show all allowable combinations of vertical runs with horizontal terminations.
Maximum one 90O elbow (two 45o elbows
equal one 90o elbow).
Propane and Natural Gas:
Residential, Manufactured and
Mobile Homes Installations
The venting arrangements diagrammed below,
have a min. of 75% (flue loss) efficiency with
Fan Off, as required for manufactured homes.
(Actual efficiency may be as high as 85%)
May be installed in Manufactured (Mobile)
Homes after first sale.
Vertical Termination Systems for
Residential Manufactured and
Mobile Homes
The shaded area in the diagram below shows
all allowable combinations of straight vertical and offset to vertical runs with vertical
terminations. Maximum two 45o elbows.
If the vent is ENCLOSED in a chase (min. size 9" x
9") maintain a 1-1/4" clearance to combustibles.
May be installed in Manufactured (Mobile)
Homes after first sale.
SAFETY
PRECAUTIONS FOR
THE INSTALLER
1) Wear gloves and safety glasses
for protection.
2) Exercise extreme caution when
using ladders or on roof tops.
3) Be aware of electrical wiring lo-
cations in walls and ceilings.
Vent Restrictor Position
To set the Vent restriction as indicated in the diagram, simply loosen
the screws and push the vent
restrictor plate to the correct position. Tighten the screws.
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove
Vent Restrictor setting at
38,000 Btu/h
Vent Restrictor setting at
30,000 Btu/h
11
INSTALLATION
Horizontal Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V H + H1
A)3' Min. 2' Max.
B)5' Min. 3' Max.
C)8' Min. 4' Max.
With these options, maximum total
pipe length is 30 feet with minimum
of 8 feet total vertical and maximum
4 feet total horizontal.
Please note minimum 1 foot
between 90o elbows is required.
Lengths do not include elbow
indicated
Vent restrictor position A (fully
open), refer to page 11.
Vertical Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V H V1V + V1
A)1' Min. 1' Max. 1' Min. 2' Min.
B)1' Min. 2' Max. 2' Min. 3' Min.
C)2' Min. 3' Max. 2' Min. 4' Min.
D)2' Min. 4' Max. 2' Min. 4' Min.
With these options, max. total pipe length is 30 feet
with min. of 4 feet total vertical and max. 4 feet total
horizontal.
Please note min. 1 foot between 90o elbows is
required.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to
page 11.
12
Regency U39 ULTIMATE Direct Vent Freestanding Gas Stove