WARNING:
If the information in these instructions are not
followed exactly, a fi re or explosion may result
causing property damage, personal injury or loss
of life.
FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable
vapours and liquids in the vicinity of this or any
other appliance.
Installation and service must be performed by
a qualifi ed installer, service agency or the gas
supplier.
Tested by:
918-812
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas sup-
plier, call the fi re department.
www.hampton-fi re.com
This appliance may only be
installed in an aftermarket
permanently located, manufactured (USA only) or mobile
home, where not prohibited by
local codes.
This appliance is only for use
with the type of gas indicated
on the rating plate. This appliance is not convertible for
use with other gases, unless
a certifi ed kit is used.
04/12/11
HAMPTON
®
Direct Vent Freestanding Gas Stove
To the New Owner:
Congratulations!
You are the owner of a state-of-the-art Hampton® Gas Stove by REGENCY FIREPLACE PRODUCTS. The H27 is a hand
crafted appliance and has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of
a switch. The model H27 has been approved by Warnock Hersey for both safety and effi ciency. As it also bears our own
mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a
moment now to acquaint yourself with these instructions and the many features of your Hampton® Stove.
2
Hampton® H27 Direct Vent Freestanding Gas Stove
TABLE OF CONTENTS
SAFETY LABEL
Copy of Safety Label .....................................................4
REQUIREMENTS
MA Code - CO Detector.................................................6
INSTALLATION
Important Message ......................................................8
This is a copy of the label that accompanies
each Direct Vent Freestanding Gas Stove.
We have printed a copy of the contents here
for your review.
Listed:
VENTED GAS FIREPLACE HEATER
Certified for/Certifi e pour:
CANADA and U.S.A.
WN# 16378
Tested to: Gas-Fired Appliances For Use At High
Altitudes CGA 2-17-M91,ANSI Z21.88a-2007/CSA 2.33a-2007Vented Gas Fireplace Heaters
MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE
FACTORY EQUIPPED FOR NATURAL GAS Model:H27-NG
Minimum supply pressure
Manifold pressure High
Model/Modele:
H27-NG
Manifold pressure Low
Maximum Input
Minimum Input
Orifice size
Altitude
FACTORY EQUIPPED FOR PROPANE GAS Model:H27-LP
Minimum supply pressure
Manifold pressure High
Model/Modele:
H27-LP
Manifold pressure Low
Maximum Input
Minimum Input
Orifice size
Altitude
NOTE: Hampton® units are constantly being
improved. Check the label on the unit and if
there is a difference, the label on the unit is
the correct one.
Pression d'allimentation minimum
Pression la tubulure d' chappement lev e
Pression la tubulure d' chappement basse
é
D bit Calorifique maximum
é
D bit Calorifique minimum
à
à
Dimensions de l'orifice
L'altitude
ÉÉQUIP A L'UISINE POUR GAZ PROPANE
Pression d'allimentation minimum
Pression la tubulure d' chappement lev e
Pression la tubulure d' chappement basse
é
D bit Calorifique maximum
é
D bit Calorifique minimum
à
à
Dimensions de l'orifice
L'altitude
351
DO NOT REMOVE THIS LABEL /
NE PAS ENLEVER CETTE ÉTIQUETTE
351
Serial No./ No de serie
ééé
é
ééé
é
Minimum Clearances to Combustibles/Degagement Minimum De Materiaux Combustibles
Minimum ceiling height from top of unit:mm
Minimum plafond hauteur en haut de
l'appareil: 24"/610mm
A 6"/150mm
B 3"/75mm
Minimum clearance of Vent Terminal
to Outside Corner & Inside Corner:
with AstroCap 6"/150mm
with Dura-Vent Cap 12"/300mm
VENTED GAS FIREPLACE HEATER: This appliance must be installed in accordance with local codes, if any; if none,
follow:the national Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation Code, CSA B149.1.Electrical
Supply (115V, 1.13A, 60Hz).This vented gasfireplaceheater is notfor use with filters.
C 2" / 50mm
E 2"/50mm
FOYER AU GAZ À ÈVACUATION
r glements, selon les codes installation ANS Z223.1, National Fuel Gas Code ou CSA-B149.1 en vigueur.
èd’IAlimentation
électrique. Ne doitpasêtre utilisé avecun combustible solide.
FPI Fireplace Products International Ltd. Delta, BC, Canada
Made in Canada/Fabrique au Canada
For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the
Commonwealth of Massachusetts.
For the State of Massachusetts, fl exible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720
and a CO alarm with battery back up in the same room where the gas appliance is installed.
24"/610
: Installer l`appareil selon les codes ou reglements locaux, ou, en l`absence de tels
Left Side Wall
Horizontal
Pipe
Right Side Wall
Left Side Wall
Vertical
Pipe
Right Side Wall
Not for usewithsolid fuels.
See Manual for details
918-813
4
Hampton® H27 Direct Vent Freestanding Gas Stove
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
Hampton® H27 Direct Vent Freestanding Gas Stove
5
DIMENSIONS
** Shown with optional side shelves.
6
Hampton® H27 Direct Vent Freestanding Gas Stove
INSTALLATIONINSTALLATION
BEFORE YOU ST ART
Safe installation and operation of this appliance
requires common sense, however, we are required
by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
INSTALLATION AND REPAIR SHOULD
BE DONE BY AN AUTHORIZED
SERVICE PERSON. THE APPLIANCE
SHOULD BE INSPECTED BEFORE
USE AND AT LEAST ANNUALLY BY A
PROFESSIONAL SERVICE PERSON.
MORE FREQUENT CLEANING MAY
BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, BEDDING
MATERIAL, ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS, BURNERS
AND CIRCULATING AIR PASSAGEWAYS
OF THE APPLIANCE BE KEPT CLEAN.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE
IN THE SAME AREA AS THE APPLIANCE. TODDLERS, YOUNG CHILDREN
AND OTHERS MAY BE SUSCEPTIBLE
TO ACCIDENTAL CONTACT BURNS. A
PHYSICAL BARRIERS IS RECOMMENDED IF THERE ARE AT RISK INDIVIDUAL
IN THE HOUSE. TO RESTRICT ACCESS
TO A FIREPLACE OR STOVE, INSTALL
AN ADJUSTABLE SAFETY GATE TO
KEEP TODDLERS, YOUNG CHILDREN
AND OTHER AT RISK INDIVIDUALS OUT
OF THE ROOM AND AWAY FROM HOT
SURFACES.
CLOTHING OR OTHER FLAMMABLE
MATERIAL SHOULD NOT BE PLACED
ON OR NEAR THE APPLIANCE.
DUE TO HIGH TEMPERATURES, THE
APPLIANCE SHOULD BE LOCATED
OUT OF TRAFFIC AND AWAY FROM
FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS
APPLIANCE CORRECTLY WILL VOID
YOUR WARRANTY AND MAY CAUSE A
SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE
ALERTED TO THE HAZARDS OF HIGH
SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND
SHOULD STAY AWAY TO AVOID BURNS
OR CLOTHING IGNITION.
Hampton® H27 Direct Vent Freestanding Gas Stove
Hampton® H27 Direct Vent Freestanding Gas Stove
7
7
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The Direct Vent Freestanding Gas Stove must
be installed in accordance with these instructions.
Carefully read all the instructions in this manual fi rst.
Consult the building authority having jurisdiction
to determine the need for a permit prior to starting
the installation.
Note: Failure to follow the instructions could
cause a malfunction of the heater which
could result in death, serious bodily injury, and/or property damage. Failure to
follow these instructions may also void
your fi re insurance and/or warranty.
Note: These instructions take precedence over
Simpson Dura-Vent instructions.
SPECIFICATIONS
Fuels: H27-NG is approved for use with natural
gas.
H27-LP is approved for use with liquefi ed
petroleum gases (propane).
Electrical: 120V A.C. system.
Optional Circulation Fan:
This appliance installation must comply with the
manufacturer's installation instructions and local
codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI
Z223.1 and the current National Electrical Code
ANSI/NFPA 70 in the U.S.A., and the current
CAN/CGA B149 Gas Installation Code and the
current Canadian Electrical Code CSA C22.1
in Canada.
This Hampton® Mobile/Manufactured
Home Listed appliance comes factory
equipped with a means to secure the unit.
This Hampton® Mobile/Manufactured
Home listed appliance comes equipped
with a dedicated #8 ground lug to which
an 18 gauge copper wire from the steel
chassis ground must be attached.
This appliance may only be installed in
an aftermarket permanently located,
manufactured (USA only) or mobile
home, where not prohibited by local
codes.
This appliance is only for use with
the type of gas indicated on the rating
plate. This appliance is not convertible for use with other gases, unless
a certifi ed kit is used.
1) Provide adequate clearances for servicing,
proper operation and around the air openings
into the combustion chamber.
2) The appliance must be installed on a fl at, solid,
continuous surface (e.g. wood, metal, concrete).
This may be the fl oor, or it can be raised up
on a platform to enhance its visual impact. The
appliance may be installed on carpeting, tile,
wood fl ooring or other combustible material,
because the appliance's base extends the full
width and depth of the appliance. The Direct
Vent Freestanding Gas Stove can be installed
in a wide variety of ways and will fi t nearly any
room layout. It may be installed in a recessed
position, framed out into the room, or across
a corner.
3) The Direct Vent Freestanding Gas Stove is
approved for alcove installations, which meet
the clearances listed on in the "Clearance to
Combustibles" section. This unit is approved
for manufactured home installations, see
the "Manufactured Mobile Home Additional
Requirements" section and "Venting Arrangements" section for the required vent arrangements. If installed into a manufactured home
the unit must be bolted down to the fl oor.
4) This appliance is Listed for bedroom installations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
5) This appliance is Listed for Alcove installations,
maintain minimum Alcove clearances as follows, minimum width of 34-3/4" (882mm), a
maximum depth of 36" (914mm), and minimum
ceiling height of 51" (1295mm) from fl oor to
ceiling.
6) We recommend that you plan your installation on
paper using exact measurements for clearances
and fl oor protection before actually installing this
appliance. Have a qualifi ed building inspector
review your plans before installation.
This Hampton® product has been tested and listed
by ITS Testing Services as a Direct Vent Wall
Furnace to the following standards:
CGA-2.17-M91, and ANSI Z21.88a-2007/CSA
2.33a-2007.
This Direct Vent System Appliance must be installed
in accordance with the manufacturer's installation
instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280,
or the current Standard of Fire Safety Criteria
for Manufactured Home Installations, Sites, and
Communities ANSI/NFPA 501A, and with CAN/
CSA Z240-MH Mobile Home Standard in Canada.
8
Hampton® H27 Direct Vent Freestanding Gas Stove
INSTALLATION
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform with
local Canadian Electrical Code.
2) The appliance when installed, must be electrically grounded in accordance with local codes,
or in the absence of local codes with the current
National Electrical Code, ANSI/NFP A 70 or CSA
C22.1 Canadian Electrical Code.
3) The appliance should be inspected for shipping
damage before use and serviced annually by a professional service person. More frequent
cleaning may be required due to excessive
lint from carpeting, bedding material, etc. It
is imperative that control compartments, and
circulating air passageways of the appliance
be kept clean and free from excessive lint from
carpeting.
4) See general construction and assembly instructions. The appliance and vent should be
enclosed when installed in or passing through a
living area, where children may come in contact
with it.
5) This appliance must be connected to the specifi ed vent and termination cap to the outside of
the building envelope. Never vent to another room or inside a building. Make sure that
the vent is fi tted as per the instructions starting
in the "Exterior Vent T erminal Locations" section.
6) Inspect the venting system annually for blockage and any signs of deterioration.
7) Venting terminals shall not be recessed into a
wall or siding.
8) Any safety glass removed for servicing must
be replaced prior to operating the appliance.
9) To prevent injury, do not allow anyone who is
unfamiliar with the operation to use the fi replace.
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
INSTALLATION
CHECKLIST
1) Locate your appliance. Refer to the following
sections:
a. Clearances to Combustibles
b. Locating Your Gas Stove
c. For venting requirements, see "Venting
Introduction" to "Rigid Pipe Venting
Systems" sections.
2) Install Optional Fan. Refer to the "Optional Fan
Installation" section.
3) Set vent restrictor. Refer to the
"Vent Restrictor Position" section.
4) Install venting:
a. Check all venting requirements. See
"Vent Restrictor Position" to Rigid Pipe
Venting Systems" sections
b. Vertical Termination with Co-linear Flex
System
c. DV Stove Horizontal Vent Kit
d. Minimum Horizontal Termination
e. Dura-Vent Termination Kit
5) Make gas connections. Refer to the "Gas Connection" section.
Test the pilot. Must be as per diagram in the
"Maintenance Instruction" section.
If converting to Propane, make changes prior.
Refer to the "Conversion from Natural Gas to
Propane" section.
6) Test Gas Pressure. Refer to the "Pressure
Testing" section.
7) Install standard and optional features. Refer to
the following sections where applicable:
a. Log Set Installation
b. Decorative Door Grill
c. Wall Thermostat
d. Remote Control
8) Final check. Refer to the "Final Check" section.
Before leaving this unit with the customer, the
installer must ensure that the appliance is fi ring cor-
rectly and operation fully explained to customer.
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance and
the chimney connector. The farthest distance is correct if the two clearances do not coincide.
For example, if the appliance is set as indicated in
one of the fi gures but the connector is too close,
move the stove until the correct clearance to the
connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type of
installation with another in order to achieve
closer clearances.
This unit can be installed on a solid combustible
surface like a wood fl oor. This unit can also be
installed directly on carpeting or vinyl.
Use the minimum clearances shown in the diagrams below:
H27-NG & H27-LP Clearances
A Left Side Wall to Unit*6" / 150 mm
B Back Wall to Unit 3" / 75 mm
C Vertical Vent Pipe to Back Wall
2" / 50 mm
E Unit Corner to Wall 2" / 50 mm
Unit Top to Alcove Ceiling 24" / 610 mm
Minimum ceiling height is 24" /610 mm from top
of unit.
Hampton® H27 Direct Vent Freestanding Gas Stove
This includes:
1) Clocking the appliance to ensure the correct
fi ring rate (rate noted on label) after burning
appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow the
unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
9
INSTALLATION
LOCATING YOUR
GAS STOVE
When selecting a location for your stove, ensure
that the clearances listed above are met as well
as ensuring that there is adequate accessibility
for servicing and proper operation.
A) Cross Corner
B) Room Divider
C) Island
D) Flat on Wall
E) Flat on Wall Corner
F) Flush with Wall/Alcove
For Vent Termination requirements,
see "Exterior Vent Terminal Locations"
section.
OPTIONAL FAN
INSTALLATION
Fan Kit Contains:
Qty. Description
1 Fan Assembly c/w green wire attached
1 Thermodisc
1 power cord
2 2-1/4" x 20 hex nut
1 Fan Speed Control
1) a) Remove the rear access panel on the
back of the stove by removing the 2 screws
under the rear panel.
screw
b) Lift off the 2 bolts at the top.
Take care not to cut wires when
lowering the panel.
screw
3) Remove the Top Control Panel Assembly
by removing the three screws.
Top Control Panel Assembly
4) Remove the nylon hole plug from the control
panel.
5) Install the fan speed controller onto the
control panel and secure with nut and
washer. Connect the red and black wires
from the wire harness to speed controller.
NOTE: Speed control wires must be in
the down position when control panel is
in place.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8
ground lug provided.
3) Appliance must be anchored to the fl oor
with the supplied anchoring methods.
COMBUSTION AND
VENTILA TION AIR
The combustion air from this appliance is drawn
from outside the building through the outer fl ue.
Extra provision for combustion air inside the
room is not required.
Fan Speed
Controller
6) Push black knob onto speed control.
Bolts
Lift Rear Panel off the 2 top bolts
2) Disconnect the red and grey wires.
7) Re-attach control panel with 3 screws,
reversing step 3.
10
Hampton® H27 Direct Vent Freestanding Gas Stove
INSTALLATION
8) Place the blower close to the base of the unit and feed the long red
and black wires through the opening of the base of the unit and the
short red and black wires through the small hole at the base of the
unit.
9) Slide Thermodisc into the bracket on the left side of the rear fi re-
box.
12) Before re-attaching the rear access panel, the valve wires and the
fan wires need to be connected.
Re-connect the red and grey valve wires.
Connect the fan wires.
Thermodisc
Braket
11) Mount the blower assembly in position under the base of the stove
and secure with the 2 supplied bolts (2-1/4" #20 hex head)
This appliance is equipped with a three pronged (grounding) plug for your protection against shock hazard and should be
plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
Thermodisc
WARNING: Electrical Grounding Instructions
13) Slide the Rear Access Panel back into position and secure with 2
screws.
Hampton® H27 Direct Vent Freestanding Gas Stove
11
INSTALLATION
VENTING
INTRODUCTION
The Horizontal Termination Kit and other
approved venting systems as per table on next page,
in combination with the Direct Vent Freestanding
Gas Stoves, H27-NG, and H27-LP, have been
tested and listed as direct vent heater systems by
Warnock Hersey.
These units use the "balanced fl ue" technology
Co-Axial system. The inner liner vents products
of combustion to the outside while the outer pipe
draws outside combustion air into the combustion
chamber thereby eliminating the need to use heated
room air for combustion and losing warm room air
up the chimney.
Note: These fl ue pipes must not be
connected to any other appliance.
The gas appliance and vent system must be vented
directly to the outside of the building, and never
be attached to a chimney serving a separate solid
fuel or gas burning appliance. Each direct vent gas
appliance must use it's own separate vent system.
Common vent systems are prohibited.
IMPORTANT
Read all instructions carefully before starting the
installation. Failure to follow these instructions may
create a fi re or other safety hazard, and will void the
warranty. Be sure to check the venting and clearance to combustible requirements. Consult your
local building codes before beginning installation.
The location of the termination cap must conform
to the requirements in the "Exterior Vent Terminal
Locations" section.
INSTALLATION
PRECAUTIONS
These venting systems are engineered products
that have been designed and tested for use with the
H27-NG, and H27-LP. The warranty will be voided
and serious fi re, health or other safety hazards may
result from any of the following actions:
1) Installation of any damaged Direct Vent component
2) Unauthorized modifi cation of the Direct Vent
System
3) Installation of any component part not manufactured by approved venting systems as per
table on next page or FPI Fireplace Products
International Ltd.
4) Installation other than as instructed by approved
venting systems as per table on next page and
FPI Fireplace Products International Ltd.
Warning: Always maintain required
clearances (air spaces) to nearby
combustibles to prevent a fi re hazard.
Do not fi ll air spaces with insulation.
Be sure to check the vent termination clearance
requirements from decks, windows, soffi ts, gas
regulators, air supply inlets and public walkways as
specifi ed in the "Exterior Vent Terminal Locations"
section and in your local building codes.
The gas appliance and vent system must be
vented directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas-burning appliance.
Each direct vent gas appliance must use it's own
separate vent system. Common vent systems are
prohibited.
SAFETY PRECAUTIONS FOR
THE INSTALLER
1) Wear gloves and safety glasses for protection.
2) Exercise extreme caution when using ladders
or on roof tops.
3) Be aware of electrical wiring locations in walls
and ceilings.
VENT RESTRICTOR
POSITION
To set the Vent restriction as indicated in the diagrams in "Venting Arrangements" section, simply
loosen the screws and push the vent restrictor plate
to the correct position. Tighten the screws.
1) Remove all 4 screws that secure
the elbow to the unit using a 1/4"
magnetic nut driver.
Remove all 4 screws
and washers
12
ROTATING 45O ELBOW
2) Rotate the elbow 180
3) Secure the elbow by securing
it with the 4 screws.
o
Hampton® H27 Direct Vent Freestanding Gas Stove
EXTERIOR VENT TERMINAL LOCATIONS
INSTALLATION
1
Minimum Clearance Requirements
AClearance above grade, veranda, porch, deck, or balcony12"(30cm)12"(30cm)
BClearance to window or door that may be opened 12"(30cm)9" (23cm)
CClearance to permanently closed window**
DVertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm)
from the center line of the terminal (check with the local code)
EClearance to unventilated soffi t12"(30cm)12"(30cm)
FClearance to outside corner: with AstroCap and Vent Riser Termination Caps 6"(15cm)6"(15cm)
Clearance to outside corner: with all other approved Termination Caps.12"(30cm)12"(30cm)
GClearance to inside corner: with AstroCap and Vent Riser Termination Caps 6"(15cm) 6"(15cm)
Clearance to inside corner: with all other approved Termination Caps12"(30cm)12"(30cm)
HClearance to each side of center line extended above meter/regulator assembly 36"(90cm)
JClearance to service regulator vent outlet36"(90cm)*
KClearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance12"(30cm)9" (23cm)
LClearance to a mechanical air supply inlet
#3' (91cm) above if within 10' (3m) horizontally.
MClearance above paved sidewalk or a paved driveway located on public proper ty 84"(2.1m)
NClearance under veranda, porch, deck, or balcony 12"(30cm)
1
In accordance with current CSA B149.1, Natural Gas and Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
┼
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor
Clearance in accordance with local installation codes and the requirements of the gas supplier
*
a
3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly
b
3 feet (91cm) above - if within 10 feet (3m) horizontally
Canada
22"(56cm)22"(56cm)
a
72"(1.8m)36"(90cm)
┼
‡
USA
*
*
*
2
b
Hampton® H27 Direct Vent Freestanding Gas Stove
13
INSTALLATION
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Chimney Conversion Kit A (USA only)46DVA-KCAN/AN/AN/AN/ATM-4CA6
Chimney Conversion Kit B (USA only)46DVA-KCBN/AN/AN/AN/ATM-4CA7
Chimney Conversion Kit C (USA only)46DVA-KCCN/AN/AN/AN/ATM-4CA8
Chimney Conversion Kit Masonry
(USA only)
Wall Firestop46DVA-WFSN/AN/AN/AN/ATM-4TR
Colinear Flex Connectors46DVA-ADFN/AN/AN/AN/AN/A
FPI
946-506/PVent Guard (Optional) for AstroCap946-205Vinyl Siding Shield for Riser Vent Terminal
510-994Rigid Pipe Adaptor (Must use with all rigid piping)946-208/PVent Guard (Optional) for Riser Vent Terminal
640-530/PRiser Vent Terminal946-523/PAstroCap Horizontal Cap
946-605Starter Collar Increaser 4” x 6-5/8” to 5” x 8”946-206Vinyl Siding Standoff for AstroCap
Note: When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).
Offset Pipe Selection: Use this table to determine offset pipe lengths.
Pipe Length
(L)
0” (0mm)4-7/8” (124mm)13-7/8” (340mm)Simpson Direct Vent Pro: www.duravent.com
Note: Horizontal runs of vent must be level, or have a 1/4” rise for every 1 foot of run towards the termination.
Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard.
Run (X)Rise (Y)
46DVA-KMCN/AN/AN/AN/AN/A
4” x 6-5/8” VentingFor specifi c instructions on venting components - visit the
manufacturers website listed below.
Hampton® H27 Direct Vent Freestanding Gas Stove
15
INSTALLATION
RIGID PIPE VENTING SYSTEMS
Horizontal or Vertical Terminations
Alternate
Horizontal
Termination
Caps
WARNING:
Do not combine venting components from
different venting systems.
Vertical
Termination
Cap
Storm Collar
Flashing
Ceiling Firestop
Pipe Length
o
90 Elbow
Pipe
Length
Vinyl Siding
Standoff (Optional)
Horizontal
Termination
Cap
Wall Thimble
Adj.Pipe Length
However use of the the AstroCapTM and FPI
Riser is acceptable with all systems.
This product has been evaluated by Intertek
for using a Rigid Pipe Adaptor in conjunction
with Duravent Direct-Vent Pro, Selkirk DirectTemp, Ameri Vent Direct, ICC Excel venting
and Security Secure Vent systems. Use of
these systems with the Rigid Pipe adaptor is
deemed acceptable and does not affect the
Intertek WHI listing of components.
The FPI AstroCap
American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, Selkirk Direct-Temp and ICC Excel. AstroCapTM is a proprietary trademark of
FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent Pro are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
TM
and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent,
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
16
Hampton® H27 Direct Vent Freestanding Gas Stove
VENTING ARRANGEMENTS
INSTALLATION
Horizontal Terminations for
All Venting Systems
The shaded areas in the diagram below show all
allowable combinations of vertical runs with horizontal terminations. Maximum one 90O elbow (two
45o elbows equal one 90o elbow).
Propane and Natural Gas:
Residential, Manufactured and Mobile
Homes Installations
May be installed in Manufactured (Mobile) Homes
after fi rst sale.
Vertical Terminations Systems for
Residential Manufactured and Mobile Homes
The shaded area in the diagram below shows all allowable combinations of straight
vertical and offset to vertical runs with vertical terminations. Maximum two 45o
elbows.
If the vent is ENCLOSED in a chase (min. size 9" x 9") maintain a 1-1/4" clearance to
combustibles.
May be installed in Manufactured (Mobile) Homes after fi rst sale.
Offset to Vertical Terminations
Venting Arrangements - Horizontal Terminations using Dura-Vent venting system
The two diagrams show all allowable combinations of straight horizontal termination
with one 45
or FPI Riser Vent. Restrictor position "A".
Hampton® H27 Direct Vent Freestanding Gas Stove
o
elbow off the unit with Snorkels
and/or Riser Vent Termination
Snorkel Termination
Riser Vent Termination
17
INSTALLATION
One 90o elbow = Two 45o elbows.
Option V H + H1
A) 2' Min. 4' Max.
B) 3' Min. 5' Max.
C) 4' Min. 6' Max.
D) 5' Min. 7' Max.
E) 6' Min. 8' Max.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to the
"Vent Restrictor Position" section.
Horizontal Venting with Two (2) 90o Elbows
With these options, maximum total pipe length is 30
feet with minimum of 6 feet
total vertical and maximum
8 feet total horizontal.
Please note minimum 1
foot between 90o elbows
is required.
H1
H
V
Horizontal Venting with Two (2) 90o Elbows
o
elbow = Two 45o elbows.
One 90
Option H V H + H1
A) 1' Max. 1' Min. 3' Max.
B) 2' Max. 2' Min. 5' Max.
C) 3' Max. 4' Min. 6' Max.
D) 4' Max. 6' Min. 7' Max.
E) 5' Max. 8' Min. 8' Max.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to the "Vent
Restrictor Position" section.
With these options, max.
total pipe length is 30 feet
with min. of 8 feet total
vertical and max. 8 feet
total horizontal.
Please note min. 1 foot
between 90o elbows is
required.
18
Hampton® H27 Direct Vent Freestanding Gas Stove
Vertical Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
INSTALLATION
Option V H V + V1 A) 1' Min. 4' Max. 2' Min.
B) 2' Min. 5' Max. 3' Min.
C) 3' Min. 6' Max. 4' Min.
D) 4' Min. 7' Max. 5' Min.
E) 5' Min. 8' Max. 6' Min.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to the "Vent
Restrictor Position" section.
With these options, max. total
pipe length is 30 feet with min.
of 6 feet total vertical and max.
8 feet total horizontal.
Please note min. 1 foot
between 90o elbows is required.
V1
Vertical Venting with Two (2) 90o Elbows
H
V
o
elbow = Two 45o elbows.
One 90
Option H + H1 V A) 2' Max. 2' Min.
B) 3' Max. 3' Min.
C) 4' Max. 4' Min.
D) 5' Max. 5' Min.
E) 6' Max. 6' Min.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to the "Vent
Restrictor Position" section.
With these options, max. total
pipe length is 30 feet with min.
of 6 feet total vertical and max.
6 feet total horizontal.
Please note min. 1 foot
between 90o elbows is
required.
Hampton® H27 Direct Vent Freestanding Gas Stove
19
INSTALLATION
VERTICAL TERMINATION WITH CO-LINEAR FLEX SYSTEM
THE APPLIANCE MUST NOT BE
CONNECTED TO A CHIMNEY FLUE
SERVING A SEPARATE SOLID FUEL
BURNING APPLIANCE.
This appliance is designed to be attached to
two 3" (76mm) co-linear aluminium fl ex running
the full length of the chimney. See the Venting
Arrangements chart below for minimum and
maximum fl ue lengths. See chart below for
minimum distances from roof. Periodically check
that the vent is unrestricted.
Masonry chimneys may take various contours which the fl exible liner will accommodate. However, keep the fl exible liner as straight as possible, avoid unnecessary bending.
The Air Intake pipe must be attached to the inlet air collar of the termination cap.
Required Parts:
Part # Description
946-529 Co-linear DV Vertical
Termination Cap
948-305 3" Flex - 35 ft.
946-563 Co-Axial to Co-Linear Adapter Kit
which contains the following:
Co-linear Flex Adapter (270-585)
Outer Pipe (946-257)
Inner Pipe Adapter (946-219)
Venting Arrangements - Vertical Terminations
with Co-linear Flex System for both
Residential & Manufactured Homes
into Masonry Fireplaces
The shaded area in the diagram shows the allowable vertical
terminations. Note: Must remove 4 screws from stove collar
and rotate 130o to have collar facing straight back. Secure into
place with 4 screws.
Straight Vertical Terminations
Vertical Termination
Cap # 946-529
A maximum
of two certified
joiner kits
may be used
per length.
#948-305 (35 ft)
Exhaust
Flue
Co-linear DV
Flex Liner
20
Vent Restrictors
set at fully open,
Posiiton "A"
Outer
Pipe
with Kit#
946-563
Air Intake
Co-Linear
Flex
Adapter
with Kit#
946-563
Inner Pipe
Adapter
with Kit#
946-563
Hampton® H27 Direct Vent Freestanding Gas Stove
DV STOVE HORIZONTAL VENT KIT
DV 2 ft. Stove Vent Kit (Part # 946-1 16) and DV 4 ft. Stove V ent Kit (946-216) includes all the parts needed
to install the H27 Direct Vent unit with minimum horizontal and vertical vent dimensions. For installations
that require longer vertical and/or horizontal vents use the Dura-Vent system as shown in the "Dura-Vent
Termination Kit" and "Dura-Vent Venting Components" sections.
5) 1 Adjustable pipe section 13-1/2" to 24" (343mm x 610mm), 2 pcs.
6) 1 Thimble Cover
7) 1 Wall Thimble (2 pcs.)
8) 1 Adapter
9) 1 AstroCap Termination Cap
10) 2 Trim Collars
11) 1 Tube of Mill-Pac, high temperature sealant
12) 12 Screws, #8 x 1/2" Self tapping, Stainless Steel
Trim Collar
13) 14 Screws, #8 x 1/2" Self tapping, Black
14) 4 Screws #8 x 1-1/2" Drill Point, Black
15) 4 Screws #8 x 1-1/2" Drill Point, Stainless Steel
16) 8 Wood screws #8 x 1"
4" ID Liner
Spacer
Spring
Trim
Collar
4 ft. Pipe Length
with Kit # 946-216
or 2 ft. Pipe Length with
Kit # 946-116
Adapter
Thimble
Cover
Adjustable Pipe
Length 13-1/2" - 24",
2 pieces
INSTALLATION
AstroCap
Termination Cap
(Part# 946-523/P)
Wall Thimble
(required for
combustible walls)
Note:
a) Liner sections should be con-
tinuous without any joints or
seams.
b) This is an approved system, there-
fore components in this system
must not be substituted for any
other manufacturer's products.
DV STOVE HORIZONTAL VENT KIT (#946-116 & #946-216) INSTALLATION
Review the following sequence of instructions
which are typical of most installations. The sequence may vary depending on wall thickness.
See the "Exterior Vent Terminal Locations"
section for vent location and clearance
dimensions, and "Vent Restrictor Position"
section to set the Vent Restrictor to the
correct position.
1) Set the unit in its desired location. Check
to determine if wall studs will be in the way
of the venting system, adjust location until
all clearances are met and there are no
obstructions.
Note: A 1-1/2"(38mm) clearance around the
outer pipe must be maintained except
that only a 1" (25mm) clearance is
needed at the termination end.
IMPORTANT:
Do not locate termination hood where
excessive snow or ice buildup may
occur. Be sure to check vent termination area after snow falls, and clear to
prevent accidental blockage of venting
system. When using snow blowers,
make sure snow is not directed towards
vent termination area.
2) Assemble a trial fi t to determine the vertical
centerline for the vent termination.
a) Cut a 9-1/2" x 9-1/2" (241mm x 241
mm) square hole on both the interior
and exterior wall.
b) Install wall thimbles on both interior
and exterior wall with 4 wood screws
(#8 x 1") per thimble.
c) Attach the 2 piece adjustable pipe sec-
tion to the vent terminal and slide into
position from the exterior. The larger
diameter end of the adjustable pipe
goes to the vent terminal.
d) Install the 90
o
elbow onto the adjustable pipe to determine the vertical
centerline.
Note: if the centerline cannot be met,
the adjustable sections will have to
be cut.
e) Cut the 4 ft. section of rigid pipe to
length. Attach the 45
pipe, and ensure that the pipe length
when cut (with the 45
o
elbow to the rigid
o
elbow) will seat
onto both the starter collar and the 90
elbow. Crimped section of rigid pipe
seats into the 90
o
elbow. Only cut
the uncrimped side of pipe.
Dismantle all pipe sections including vent
terminal.
o
Hampton® H27 Direct Vent Freestanding Gas Stove
21
INSTALLATION
3) Attach the 4" dia. fl ex liner to the vent ter-
minal ensuring that the fl ex overlaps the
collar of the vent terminal by a minimum
of 1-3/8"(35mm). Use Mill-Pac to seal
and secure with 3 of the #8 x 1/2" screws
(stainless steel).
4) Attach the adjustable pipe section to the
vent terminal using Mill-Pac and/or high
temperature silicone and attach with 3 of
the #8 x 1/2" screws (stainless steel).
NOTE: For best results and optimum per-
formance with each approved venting system, it is highly recommended
to apply “Mill-Pac” sealant (supplied)
to every inner pipe connection. Failure to do so may result in drafting
or performance issues not covered
under warranty. Silicone (red RTV)
is optional.
Note: If installing ter-
mination on a
siding covered
wall, a vinyl siding standoff or
furring strips
must be used to
ensure that the
termination is not
recessed into the
siding. For vinyl siding standoff
installation refer to the Dura-Vent
Termination instructions.
5) Slide the partially connected pipe and
vent terminal assembly through the wall
thimbles (from the exterior into the interior)
and secure the cap to the exterior wall with
4 of the supplied screws (#8 x 1-1/2" drill
point, stainless steel). Note: pilot holes will
need to be drilled through the wall thimble
on all 4 corners.
Note: The four screws provided for the
vent cap should be replaced with
appropriate fasteners for stucco,
brick, concrete, or other types of
sidings.
9) Secure the 4" dia. fl ex liner to the 4" adapter
with Mill-Pac and 3 of the #8 x 1/2" screws
(stainless steel).
10) Slide the decorative Thimble Cover over the
pipe sections and secure with 4 screws (#8
x 1-1/2" drill point, black) to the wall.
o
11) Slide the 90
elbow and the 4 ft. pipe section (crimp end
up) over the 4" dia. fl ex liner.
12) Install the spring spacers onto the pipe sections.
13) Secure the 4" dia. fl ex liner with adapter
onto the stove collar. Put a bead of Mill-Pac
around the appliance adapter and secure
with 3 screws (#8 x 1/2, stainless steel).
14) Attach the 45o elbow onto the starter collar by
sealing with Mill-Pac and/or high temperature
silicone and securing with 3 of the #8 x 1/2"
(black) screws.
15) Attach the pipe section to the 45o elbow by
sealing with Mill-Pac and/or high temperature
silicone and securing with 3 of the #8 x 1/2"
screws (black). Pipe seams should be facing
the wall.
16) Attach the 90o elbow onto the pipe section by
sealing with Mill-Pac and/or high temperature
silicone and securing with 3 of the #8 x 1/2"
screws (black).
17) Slide the adjustable pipe section onto the 90o
elbow. Slide the trim collar over the adjustable pipe sections to cover the joint of the
telescopic section.) The fl ex may have to be
compressed back in order for the adjustable
pipe to properly mate to the elbow. Seal with
Mill-Pac and/or high temperature silicone and
secure with 3 of the #8 x 1/2" screws (black).
Pipe seams facing down.
18) Install the trim collar over the starter collar
and secure with a #8 x 1/2" screw (black).
elbow (crimp end up), the 45o
Note: The pipe seam should be
facing down.
Note: To make the installation more aes-
thetically pleasing, we recommend
framing out a square that the cap
can be mounted on.
22
6) A bead of non-hardening mastic should
be run around both the termination and
vinyl siding standoff to prevent water from
entering and to make a tight seal between
the cap and the standoff.
7) Stretch the 4" dia. fl ex liner out fully and get
a trial fi t of the liner onto the 4" dia. starter
collar.
8) Cut the 4" dia. fl ex liner to the desired
size.
Hint: leave an extra 12" to 16" of length,
this will make the fi nal assembly easier to
work with.
If the pipe needs to be touched up, use only
Stove Brite High Temperature Metallic Black
Stove Paint.
Hampton® H27 Direct Vent Freestanding Gas Stove
INSTALLATION
RESIDENTIAL AND MANUFACTURED HOMES / MOBILE HOMES
MINIMUM HORIZONTAL TERMINATION INSTALLATIONS
Planning Your venting Installation
See the "Exterior Vent T erminatal Locations"
section for requirements. The H27 is approved
for a minimum horizontal termination with the
FPI Riser Vent Kit. See the diagram for minimum
and maximum pipe lengths.
When planning your installation, it will be necessary to select the proper length of vent pipe
for your particular requirements. Determine the
minimum clearance to combustibles from the
rear of the unit to the wall. It is also important to
note the wall thickness. Before cutting the vent
hole through the wall ensure that ALL vent and
termination clearances (see the "Exterior Vent
Terminal locations" section) will be met.
*If this is an outside corner, the minimum distance
between the vent and the outside corner is 6"
(15cm). See "F" on the diagram in the "Exterior
Vent Terminal Locations" section.
FPI Riser Vent
*
**Min.
6-1/2"
(165mm)
#640-530/P
Max. 15-1/2"
(394mm)
You will require the following components with your new Hampton® Rear Vent Direct Vent Freestanding Gas Stove. Please review your product to make sure you have everything you need. In
the event that you are missing any part, contact your dealer. Decorative brass or chrome trim kits
are available from Simpson Dura-Vent for their wall thimbles, as well
as a square wall thimble cover.
Horizontal
Terminal
Part# 640-530/P
Vinyl Siding
Standoff (Optional)
Part #946-205
Adapter
Part #946-219/P
(required)
Decorative
Wall Trim
Pipe Length (max. 18")
Part (6-5/8" Dia)
(4" Dia.)
Wall Thimble
(required for
combustible walls)
Min. 2" (51mm)
If outside corner see note * above.
Max. 23-1/2"
(597mm)
FPI
Min. 3"
(76mm)
NOTE: Ensure compliance with the outside
vent terminal location before cutting hole as
both dimensions must be met.
Hampton® H27 Direct Vent Freestanding Gas Stove
Riser
Vent
#640-530/P
Note: These are the minimum pieces re-
quired. Other parts may be required
for your particular installation.
Minimum components for a Horizontal Installation:
640-944 Horizontal Termination Kit which includes:
1 6-5/8" Dia. x 18" Black Pipe
1 4" Dia. x 18" Aluminum Vent
1 Wall Penetration Heat Shield (Wall Thimble) (2 pcs)
1 640-530/P Riser Vent Terminal
1 Decorative Wall Trim (Black)
1 948-128 Tube Mill-Pac
Screws
946-219/P 1 Adapter
Optional Components:
946-204 45
and 4" Aluminum Vent
946-205 Vinyl Siding Shield for Riser Vent
Terminal
946-208/P Vent Guard
o
Elbow - 6-5/8" Black pipe
23
INSTALLATION
DURA-VENT TERMINATION KIT
Planning Y our Dura-Vent
Installation
There are two basic types of Dura-Vent Direct
Vent System installations: horizontal termination
and vertical termination. Confi rm the maximum
horizontal run and maximum vertical rise from the
diagrams in the "Venting Arrangement" section.
When planning your installation, it will be necessary to select the proper length of vent pipe
for your particular requirements. For horizontal
installations, determine the minimum clearance
from the rear of the unit to the wall. It is also
important to note the wall thickness. (The wall
Dura-Vent Vertical
Termination Installation
Vertical
Terminal
Storm Collar
Flashing
(0-12/6-12)
Vertical Termination Kit
Part # 46DVA-KVA
thimble is suitable for 2 x 4 or 2 x 6 wall construction.) Select the amount of vertical rise desired
for "vertical-to-horizontal" type installations.
Warning: Always maintain required
clearances (air spaces) to nearby
combustibles to prevent a fire
hazard. Do not fi ll air spaces with
insulation.
The minimum clearance requirements between
the outer wall of the vent pipe and nearby
combustible surfaces is 1-1/2", except when
passing through a wall, ceiling, or at the termination where the use of a fi restop or wall thimble
reduces the required clearance to 1".
Dura-Vent Horizontal
(D)
Termination Installation
*Horizontal Termination Kit
Part # 46DVA-KHA
Be sure to check the vent termination clearance
requirements from decks, windows, soffi ts, gas
regulators, air supply inlets and public walkways
as specifi ed in the "Exterior Vent T erminal Loca-
tions" section and in your local building codes.
To determine the length of vent pipe required
for vertical installations, measure the distance
from the unit fl ue outlet to the ceiling, the ceiling
thickness, the vertical rise in an attic or second
storey, and allow for suffi cient vertical height
above the roof line.
For multi-storey applications, fi re stops are
required at each fl oor level. If an offset is
needed, additional pipe, elbows and supports
will be required.
Do not exceed the maximum number of elbows.
o
One 90
for horizontal terminations and two 45o
for vertical termination.
(A)
Cathedral
Ceiling
Support Box
Ceiling
Firestop
Round Support
Box/Wall Thimble
Pipe Length
*Round Support
Box/Wall Thimble
(included in 46DVA-KHA)
*Adj.Pipe Length
(included in #46DVA-KHA)
o
*90 Elbow
(included in 46DVA-KHA)
Pipe Length
(included in 46DVA-KHA)
*Horizontal
Termination Cap
(included in 46DVA-KHA)
Dura-Vent® and Direct Vent Pro are registered and/or proprietary
trademarks of Simpson Dura-Vent Co. Inc.
Hampton® H27 Direct Vent Freestanding Gas Stove
Y ou will require the following components with
your new Direct Vent Freestanding Gas Stove.
Please review your product to make sure you
have everything you need. In the event that
you are missing any part, contact your dealer.
Note: These are the minimum pieces re-
quired. Other parts may be required
for your particular installation. See
above for a list of vent parts.
INSTALLATION
If installing termination on a siding covered wall,
a vinyl siding standoff or furring strips can be
used in order to ensure that the termination is
not recessed into siding.
The vinyl siding standoff is required for walls
with vinyl siding.
Minimum components for a Dura-Vent
Horizontal Installation:
A) Dura-Vent Horizontal Termination Kit
B) Wall Thimble (required for combustible
walls)
Minimum components for a Dura-Vent
Vertical Termination:
D) Dura-Vent Vertical Termination Kit. See
above for pipe lengths.
HORIZONTAL
TERMINATIONS
1) Set the unit in its desired location. Check to
determine if wall studs are in the way when
the venting system is attached. If this is the
case, you may want to adjust the location
of the unit.
2) Assemble the desired combination of pipe
and elbow to the appliance adapter with pipe
seams oriented down. Offset the pipe seams
as double seams in one place will cause the
outer pipe to take an oval shape. Kit comes
complete with 18" of straight vent - 6-5/8" dia.
black outer pipe and 4" dia. inner vent.
Diagram 1
a) The horizontal run of vent should have a
1/4 inch rise for every 1 foot of run towards
the termination. Never allow the vent to run
downward. This could cause high temperatures and may present the possibility of a
fi re.
b) The location of the horizontal vent termination
on an exterior wall must meet all local and
national building codes, and must not be
blocked or obstructed. Refer to the "Exterior
Vent Terminal Locations" section.
c)Snorkel Terminations:
For installations requiring a vertical rise
on the exterior of the building, 14-inch and
36-inch tall Snorkel Terminations as shown
in Diagram 2 are available, as well as the
standard Riser Vent. Follow the same installation procedures as used for standard
Horizontal Termination. NEVER install the
snorkel upside down.
*Diagram 2a: As specifi ed in CGA B149 Instal-
lation Code. Local codes or regulations may
require different clearances.
Diagram 2b
NOTE: For Snorkel terminations in ABOVE
grade installations, follow national or
local code requirements.
Below Grade Snorkel Installation
If the Snorkel T ermination must be installed
below grade, i.e. basement application,
proper drainage must be provided to prevent
water from entering the Snorkel T ermination.
Refer to Installation instructions for details..
Do not attempt to enclose the Snorkel within
the wall, or any other type of enclosure.
4) Install wall penetration heat shield in the
center of the 9-1/2" round hole and attach
with wood screws. The four wood screws
provided should be replaced with appropriate fasteners for stucco, brick, concrete, or
other types of sidings. Diagram 3.
5) If installing termination on a siding covered
wall, a vinyl siding standoff or furring strips
must be used to ensure that the termination
is not recessed into the siding. Diagram
3.
6) Take the Riser Vent terminal and separate
the Backing Plate from the Riser Vent Front
by removing 8 screws as shown in diagram
4.
3) With the pipe attached to the stove, slide
the stove into its correct location, and mark
the wall for a 9-1/2" (inside dimensions)
round hole. The center of the round hole
should line up with the centerline of the
horizontal pipe, as shown in diagram 1. Cut
and frame the 9-1/2 round hole in the exterior wall where the vent will be terminated.
If the wall being penetrated is constructed
of non-combustible material, i.e. masonry
block or concrete, a 7" diameter hole is
acceptable.
Hampton® H27 Direct Vent Freestanding Gas Stove
Diagram 2a
Diagram 3
25
INSTALLATION
Diagram 4
7) Install the Backing Plate into the wall penetration heat shield and attach using 4 screws.
Dia. 4.
8) Connect all pipe sections to unit and install
into wall:
a) Measure pipe length required and cut to
length. Hint: use the cut end of the 6-5/8"
dia. outer pipe at the vent terminal end.
b) Push the pipe sections completely together,
the minimum pipe overlap is 1-1/4". Secure
all outer pipe joints by using at least two
screws. Locate the screws at the bottom of
the pipe so that the screw heads are hidden
on the fi nal installation.
NOTE: For best results and optimum
performance with each approved venting system, it is highly recommended
to apply “Mill-Pac” sealant (supplied) to
every inner pipe connection. Failure to
do so may result in drafting or performance issues not covered under warranty.
Silicone (red RTV) is optional.
c) Before connecting the vent pipe to the vent
termination, slide the black decorative wall
thimble cover over the vent pipe, then slide
the Wall Penetration Heat Shield (Part #
946-202) over the vent pipe. Dia. 3.
d) Slide the appliance and vent assembly
towards the wall carefully inserting the vent
pipe into the riser vent terminal assembly. It
is important that the vent pipe extends into
the Riser Vent Backing Plate a suffi cient
distance so as to result in a minimum pipe
overlap of 1-1/4 inches. Secure the connection between the vent pipe and the vent
cap by attaching the two sheet metal strips
extending from the Riser Vent Backing Plate
into the outer wall of the vent pipe. Use
two aluminum screws provided to connect
the strips to the pipe section. Bend any
remaining portion of the sheet metal strip
back towards the vent cap and cut off any
excess, it will be concealed by the decorative wall thimble cover. See diagram 5.
Diagram 5
8) Slide the decorative wall thimble up to the
wall surface being careful not to scratch the
paint. See diagram 5.
9) Back outside: Apply sealant to the 4" inner
fl ue and slide the Riser Vent Front into the
Backing Plate and fasten with 8 screws.
VERTICAL
TERMINATIONS
1) Maintain the 1-1/2" clearances, except when
passing through a wall, ceiling, or at the
termination where the use of a fi restop or
wall thimble reduces the required clearance
to 1". Do not pack air spaces with insulation.
Check the "Venting Arrangement" section
for the maximum vertical rise of the venting
system and the maximum horizontal offset
limitations.
2) Set the gas appliance in its desired location.
Drop a plumb bob down from the ceiling
to the position of the appliance fl ue exit,
and mark the location where the vent will
penetrate the ceiling. Drill a small hole at
this point. Next, drop a plumb bob from
the roof to the hole previously drilled in
the ceiling, and mark the spot where the
vent will penetrate the roof. Determine if
ceiling joists, roof rafters or other framing
will obstruct the venting system. You may
wish to relocate the appliance or to offset,
as shown in diagram 8 to avoid cutting load
bearing members.
26
IMPORTANT:
When connecting the pipe to the Riser
Vent, apply Mill-Pac to the inner pipe on
the Riser Vent T erminal, around the bead.
Ensure that the vent pipe is pushed past
the bead for a secure fi t.
10) Seal around the outer edge of the Riser
Vent Backing Plate.
Diagram 7
Hampton® H27 Direct Vent Freestanding Gas Stove
Diagram 8
Diagram 10: The upper half of the fl ashing is
installed under the roofi ng material and not
nailed down until the chimney is installed. This
allows for small adjustments.
INSTALLATION
7) Ensure vent is vertical and secure the base
of the fl ashing to the roof with roofi ng rails,
slide storm collar over the pipe section and
seal with a mastic.
8) Install the vertical termination cap by twist
locking it.
Notes:
a) For multistorey vertical installations,
a Ceiling Fire stop is required at the
second fl oor, and any subsequent fl oor.
Diagram 12. The opening should be
framed to 10 " x 10" inside dimensions,
in the same manner as shown in diagram
9.
3) T o install the Round Support Box/Wall Thimble in a fl at ceiling, cut a 10 inch square hole
in the ceiling centred on the hole drilled in
Step 2. Frame the hole as shown in diagram
9.
Diagram 9
4) Assemble the desired lengths of black pipe
and elbows necessary to reach from the
appliance adapter up though the Round
Support Box. Insure that all pipes and elbow
connections are in the fully twist-locked
position and sealed.
Note: If an offset is necessary in the attic
to avoid obstructions, it is important
to support the vent pipe every 3 feet,
to avoid excessive stress on the
elbows, and possible separation.
Wall straps are available for this
purpose. See diagram 5.
Galvanized pipe and elbows may be utilized
in the attic as well as above the roofl ine.
The galvanized fi nish is desirable above
the roofl ine due to its higher corrosion
resistance.
Continue to add pipe sections through the
fl ashing until the height of the vent cap
meets the minimum height requirements
specifi ed in diagram 11 or local codes.
Note that for steep roof pitches, the vertical
height must be increased. A poor draft, or
down drafting can result from high wind
conditions near big trees or adjoining roof
lines, in these cases, increasing the vent
height may solve the problem.
b) Any occupied areas above the fi rst fl oor,
including closets and storage spaces,
through which the vertical vent passes,
must be enclosed.
Diagram 12
Offset Chart
NOTE: For best results and optimum per-
formance with each approved venting
system, it is highly recommended to
apply “Mill-Pac” sealant (supplied) to
every inner pipe connection. Failure
to do so may result in drafting or
performance issues not covered
under warranty. Silicone (red RTV)
is optional.
5) Cut a hole in the roof centred on the small
drilled hole placed in the roof in Step 2. The
hole should be of suffi cient size to meet
the minimum requirements for clearance
to combustibles of 1-1/4". Slip the fl ashing
under the shingles (shingles should overlap
half the fl ashing) as per diagram 10.
6) Continue to assemble pipe lengths.
Hampton® H27 Direct Vent Freestanding Gas Stove
Diagram 11
Roof Pitch Minimum Vent Height
Feet Meters
fl at to 7/12 2 0.61
over 7/12 to 8/12 2 0.61
over 8/12 to 9/12 2 0.61
over 9/12 to 10/12 2.5 0.76
over 10/12 to 11/12 3.25 0.99
over 11/12 to 12/12 4 1.22
over 12/12 to 14/12 5 1.52
over 14/12 to 16/12 6 1.83
over 16/12 to 18/12 7 2.13
over 18/12 to 20/12 7.5 2.29
over 20/12 to 21/12 8 2.44
27
INSTALLATION
CONVERTING CLASS-A
METAL CHIMNEY OR
MASONRY CHIMNEY TO
DIRECT VENT
SYSTEM
There are two different types of direct vent
conversion systems listed below. Follow the
appropriate directions for your installation.
A) Through an existing factory built metal
chimney going through the ceiling: A typical
conversion of this type is shown in diagram
1. The concept of direct vent conversion is
to connect an adaptor to an Underwriters
Laboratories (UL) listed 4 inch diameter
aluminum fl ex pipe which is then passed
down through the center of the existing metal
chimney system. Three sizes of T op Adaptors
are available from Simpson Dura-Vent. The
Retro Connector is attached to the bottom
of the fl ex pipe. The Top Adaptor and the
Retro Connector are attached to the existing chimney with sheet metal screws. The
appliance is then connected to the chimney
with appropriate black direct vent pipe and
an adjustable length section.
B) Through the wall of an existing masonry
chimney: A typical conversion of an existing masonry chimney is shown in Diagram
6. A Top Adaptor and Flashing are used at
the top of the masonry chimney. The 4 inch
aluminum liner is connected to the adaptor
and is passed down the chimney and out
through the masonry wall and attached to
the Retro Connector. The Retro Connector
is attached to the masonry wall and then
connected to the direct vent pipe leading to
the appliance.
Prior to installation and connection of the
vent system to a factory-built or masonry
chimney, the chimney must be inspected and
thoroughly cleaned by a qualifi ed service
person, such as a certifi ed chimney sweep
or home inspection service.
The use of an existing chimney as an air intake
is not covered under the ANSI Z21.88a-2007,
CSA 2.33a-2007 test methods and the resulting ITS/WHI product certifi cation. The
code Authority Having Jurisdiction must
be consulted prior to proceeding with this
installation method.
Converting a Factory Built Metal
Chimney
1) Remove the existing chimney cap.
2) Measure the distance from the top end of the
chimney to the bottom of the ceiling support
box, add 3" (76mm) to this measurement,
and cut a section of the 4" fl ex pipe to that
length (the fl ex should already be extended
to its nominal length).
3) Connect the end of the fl ex pipe section to
Termination
Cap
Top Adaptor
Existing
Metal
Chimney
System
Retro
Connector
Aluminum
Flex Pipe
Any Simpson
Dura-Vent
black direct vent
pipe plus an
adjustable length
to make a
proper connection.
of the chimney system, and center the
adaptor on the top of the chimney pipe.
Drill four 1/8" diameter holes through the
adaptor and into the chimney top. Insure
that you are in fact, drilling into the metal
on the chimney. Twist-lock the T ermination
Cap onto the Adaptor. (Diagram 3 and 4).
5) Pull the fl ex pipe down through the ceiling
Diagram 3
Diagram 4
support box, until it protrudes approximately
3" (76mm). Connect the fl ex pipe to the Retro
Connector by slipping it into the
4-3/4" diameter sleeve on the top side of
the Connector. Use 3 sheet metal screws
to assemble these two parts.
6) Push the fl ex pipe back up into the ceiling
support box, center the Retro Connector, and
attach it to the support box, or decorative
sleeve for double wall solid packed pipe,
with the sheet metal screws (supplied).
The holes in the Retro Connector are prepunched. Diagram 5.
The direct vent system must not be connected to a damaged factory-built or masonry
chimney.
For factory built, zero clearance, and masonry chimneys cleanout doors and caps
or plugs for cleanout tee fi ttings and ash
dumps shall be secured in place and sealed
before installing a Direct Vent system within
the chimney.
If the appliance shuts off during operation,
contact a qualifi ed service person to de-
termine if a negative pressure and/or leaky
chimney condition exists. Do not operate the
appliance until the problem is corrected.
Approved for US Installations Only
28
Diagram 1
the underside of the Top Adaptor using 3
sheet metal screws. Diagram 2.
4) Pass the fl ex pipe down through the center
Diagram 2
Diagram 5
7) The connection between the appliance and
the Retro Connector may be completed with
sections of black direct vent pipe, together
with an adjustable length.
Hampton® H27 Direct Vent Freestanding Gas Stove
INSTALLATION
7) Ensure vent is vertical and secure the base
of the fl ashing to the roof with roofi ng rails,
slide storm collar over the pipe section and
seal with a mastic.
8) Install the vertical termination cap by twist
locking it.
Notes:
a) For multistorey vertical installations,
a Ceiling Fire stop is required at the
second fl oor, and any subsequent fl oor.
Diagram 12. The opening should be
framed to 10 " x 10" inside dimensions,
in the same manner as shown in diagram
9.
b) Any occupied areas above the fi rst fl oor,
including closets and storage spaces,
through which the vertical vent passes,
must be enclosed.
If your home has a cathedral ceiling (no attic
space between the ceiling and the roof), install
the chimney and support as follows.
1) Situate the chimney in a convenient location as near as possible to the appliance
outlet. Cut and frame a hole in the roof for
the support. The sides of this hole must be
vertical with 1 1/4" clearance.
2) Place the support in the opening. Lower it
to the correct height as determined by the
table and diagram below.
Using a level, make sure the support is
vertical. If the support extends above the
roof, cut it fl ush with the top of the roof.
Nail the support to the frame opening using
(8) 3" spiral nails or #8 x 1-1/2" screws.
Hampton® H27 Direct Vent Freestanding Gas Stove
Note: If you are using a 6" square support
you may fi nd it diffi cult to screw it in
place because it is fairly small inside.
Simpson Dura-Vent has provided angle
brackets with this support which can be
screwed to the outside of the support
box and nailed to surrounding framing as
required. Use a minimum of four #8 x 1/2"
screws per bracket. In some cases these
brackets may need to be trimmed (e.g.:
to fi t under a fl ashing). Place the Finish
Collar around the support and fasten it to
the ceiling using the screws provided.
3) Use appropriate roof fl ashing. Place the
fl ashing under the upper shingles and on
top of the lower shingles approximately half
of the fl ashing should be under the shingles.
4) Assemble the desired lengths of Black
Pipe and Elbows necessary to reach from
the appliance adapter up through the support box and fl ashing to proper height as
per Dia. 12, local codes or in the "Venting
Arrangement" section. Ensure that all pipe
and elbow connections are in their fully twist
lock position.
5) Ensure vent is vertical and secure fl ashing to
the roof with roofi ng nails. Slide the storm
collar over the pipe section and seal with a
mastic.
6) Twist lock the vent cap on to the last section.
Support Extensions - Round
(RDSE)
or Square (SQSE)
Steep pitched cathedral ceilings may require
the use of a support extension. This piece fi ts
down inside the support and can be adjusted to
increase the support's length by up to 22". The
extension is attached to the support using the
eight metal screws provided. Be sure there is
at least a 2 inch overlap where the extension
joins the support.
HIGH ELEVATION
This unit is approved in Canada for altitude to
4500 ft. (CAN/CGA-2.17-M91). For Natural Gas
installations above 4500 ft. follow current CAN/
CGA-B149.1.
GAS CONNECTION
The gas connection is a 3/8" NPT 90o elbow.
The gas line can be rigid pipe or to make installation easier, use a listed fl exible connector
and/or copper tubing if allowed by local codes.
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
codes.
For USA installations follow local codes and/
or the current National Fuel Gas Code, ANSI
Z223.1.
When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so that
gas lines can be easily disconnected for burner
and/or valve servicing. Flare nuts for copper lines
and fl ex connectors are usually considered to
meet this requirement.
IMPORT ANT : AL WA YS CHECK FOR
GAS LEAKS WITH A SOAP AND
WATER SOLUTION OR GAS LEAK
DETECTOR. DO NOT USE OPEN
FLAME FOR LEAK TESTING.
Note: Prior to any pressure testing of the gas
supply piping system that exceeds
test pressures of 1/2 psig, this appliance must be disconnected from
the piping system. If test pressures
equal to or less than 1/2 psig are used
then this appliance must be isolated
from the piping system by closing
its individual manual shut-off valve
during the testing.
SYSTEM DATA - H27
For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes: Natural Gas Propane
Burner #42 #54
Max. Input Rating
- Natural Gas 25,000 Btu/h
- Propane 23,000 Btu/h
Min. Input Rating
- Natural Gas 12,500 Btu/h
- Propane 11,500 Btu/h
Supply Pressure
Natural Gas min. 5.0" w.c.
Propane min. 12.0" w.c.
The burner aeration is factory set but may need
adjusting due to either the local gas supply, air supply or altitude.
Natural Gas 3-16" (4.76 mm)
Propane 1/4" (6.4 mm)
The aeration adjustment gears are located on the
right side of the burner box. Remove the Hampton®
Logo plate on the right side of the unit to access
the adjustment gears.
To adjust the aeration: use the allen key to turn
the turning gear which will adjust the air shutter.
Open the air shutter for a blue fl ame or close it for
a more yellow fl ame. This adjustment is performed
by a qualifi ed installer. The factory setting should
be suffi cient for most installations.
Clockwise to open,
counter-clockwise to close.
GAS PIPE
PRESSURE TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual
shut-off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a 1/8" wide fl at
screwdriver.
3) Attach manometer to "IN" and/or "OUT" pres-
sure tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON" posi-
tion. Read manometer.
5) The pressure check should be carried out with
the unit burning and the setting should be within
the limits specifi ed on the safety label.
6) When fi nished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" fl at screwdriver.
Note: Screw should be snug, but do not over
tighten
1) Gas on/off knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection
5) Main Operator
6) Outlet Pressure Tap (Manifold Pressure)
7) Inlet Pressure Tap (Supply Pressure)
8) Pilot Outlet
9) Main Gas Outlet
10) Flange Securing Screw Holes
11) Alternative TC Connection Point
12) Thermoelectric Unit
13) Additional Valve Mounting Hole
Caution: Carbon will be produced if the air
shutter is closed too much.
Note: Any damage due to carboning resulting
from improperly setting the aeration
controls is NOT covered under warranty.
Note: Aeration Adjustment should only be
performed by an authorized Hampton®
Installer at the time of installation or
service.
30
Valve Description
Hampton® H27 Direct Vent Freestanding Gas Stove
INSTALLATION
CONVERSION KIT #434-969 FROM NG TO LP
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !!
NOTE: See page 4 for P33-4 conversion instructions and page 7 for E33S / U32S conversion instructions.
Each Kit contains one LPG
Conversion Kit and one DC
Sparker Kit.
LPG Conversion Kit Contains:
Qty. Part # Description
1 904-163 Burner Orifi ce #54
1 918-590 Decal "Converted to
LPG"
1 908-528 Red "LPG" label
1 904-529 5/32" Allen Key
1 910-037 LPG Injector
(Pilot Orifi ce)
1 918-480 Instruction Sheet
DC Sparker Kit Contains:
Qty. Part # Description
1 820-475 Bracket DC Sparker
1 820-476 Bracket DC Sparker
1 904-153 Washer #8 External Star
1 904-330 Nut 8-32 Hex
1 904-438 Plug Nylon 0.750 Hole,
Black (for H25 / H27
only)
1 904-531 Bushing Split Plastic
0.500 in.
1 904-543 Screw 8-32 x 3/4 Pan
Head
2 904-553 Screw #8 x 1/2 Type
"B", Black Oxide
1 910-073 Spark Generator
Battery Holder
1 910-074 Spark Generator
Switch C/W Wire
1 910-078 Battery Size AA
Energizer En91
2 910-199 Clip Wire Holder
1 910-903 Wire Fan To Power Cord
Ground 30 in.
b) Remove burner by removing the 2
screws on each side and then lifting
the burner tray out.
Screws
Note: Use a magnetic type
screwdriver if possible.
Pilot assembly is now accessible for
steps 4) to 9).
3) Pull off the pilot cap to expose the pilot
orifi ce.
4) Unscrew the pilot orifi ce with the Allen
key and replace with the LPG pilot orifi ce
in the kit and replace pilot cap.
5) Remove burner orifi ce with a 1/2"
wrench and discard. Use another
wrench to hold on to the elbow behind
the orifi ce.
Burner Orifi ce
6) Reinstall new burner orifi ce LPG
stamped #54 and tighten.
Installation of the LPG
Conversion Kit:
1) Shut off the gas supply.
2)
a) Lift off the Cast Top and Cast Front,
remove the glass front (refer to Glass
Replacement section in the H25 /
H27 manual) and carefully remove
the logs and lava rock (refer to Log
Installation section in manual).
Hampton® H27 Direct Vent Freestanding Gas Stove
31
INSTALLATION
7) Turn control knob to the “OFF” position.
8) Remove the black protection cap by
hand from the high-low knob (Fig.1).
Fig. 1
9) Insert a 5/32” or 4mm Allen wrench into
the hexagonal key-way of the screw
(Fig. 2), rotate it counter-clockwise until
it is free and extract it.
12) Using the Allen wrench as shown in
Fig.4, rotate the screw clockwise until
snug, do not overtighten.
Fig.4
WARNING!
Do not overtighten the screw.
Recommended to grip
the wrench by the short side.
13) Verify that if the conversion is from
NG to LPG, the screw must be reassembled with the red o-ring visible
(Fig. 5).
15) Reverse step 2.
16) Attach the label "This unit has been
converted to LPG" near or on top of the
serial # decal.
17) Replace yellow "NG" label with red
"LPG" label.
18) Check for gas leaks.
19) Check inlet and outlet pressures.
20) Check operation of fl ame control.
21) Check for proper fl ame appearance and
glow on logs.
Fig.2
10) Check that the screw is clean and if
necessary remove dirt.
11) Flip the screw (Fig. 3).
Red o-ring visible
LPG Configuration
Fig.5
14) Re-assemble the black protection cap
(Fig. 6).
Fig. 6
32
Fig.3
WARNING!
Also check that the pilot and
main burner injectors
are appropriate for the gas type.
Hampton® H27 Direct Vent Freestanding Gas Stove
INSTALLATION
Installation of the DC Sparker
for the H27 Unit Only:
1) Remove the control panel by unscrewing
the 2 screws.
2) First, remove the Piezo Ignition Wire
from the Piezo Ignitor. Then remove the
Piezo Ignitor from the control panel.
5) Remove the stove’s rear panel by unscrew-
ing the two screws.
6) Attach the ground wire to the grounding
stud.
7) Attach the ground wire to the grounding
stud.
11) Attach the ground wire to the DC spark
mounting bracket.
12) Attach the DC sparker generator wires to
the DC sparker.
13) Install the supplied battery into the DC
Sparker Box by opening the battery
compartment.
NOTE: The battery in the DC Sparker
Box will need to be replaced annually.
Battery
Compartment
3) Plug up the Piezo hole with the plastic
bushing.
4) Attach the DC sparker generator
connector to the valve with a screw.
8) Attach the Piezo ignition wire to the DC
Sparker.
Piezo
Ignitor
14) Attach the heat shield to the DC sparker,
then mount onto the stove using the
velcro already attached to the DC
Sparker mounting bracket.
Note: We recommend attaching the
DC sparker box to the bottom rear of
the stove (or place this in a convenient
location, away from the heat source).
9) Insert both the ground wire and the DC
sparker generator wire through the hole
of the DC spark heat shield.
15) Tie up the loose wire with the wire clip.
10) Install the plastic bushing over the
outside of the hole.
Hampton® H27 Direct Vent Freestanding Gas Stove
33
INSTALLATION
LOG SET INSTALLATION
Read the instructions below carefully and refer to the diagrams. If the logs are broken do not use the unit until they are
replaced. Broken logs can interfere with the pilot operation.
The gas log kit (Part #350-930) contains the following:
a) Rear Log
b) Left Side Front Log
c) Right Side Front Log
d) Center Front Log
e) Embers 902-156
f) Platinum Embers 946-669
A
(supplied with packaged manual)
4) Place the rear log on the 2 rear log locating pins on the rear
of the burner with the fl at side to the back.
A
Left Front Log
Pin
NOTE: Rear
B
B
B
C
D
1) Shut off the gas supply.
2) Lift off the Cast Top, remove Cast Front - then remove the
Glass Door (see manual pg. 41).
3) Carefully remove the logs from the box and unwrap them.
The logs are fragile, handle with care - do not force into
position.
A
Tabs
Right Front Log
Pin
The Front Right Log
front edges should
be placed parallel
against the front
34
NOTE: This is
a rear view.
Tabs
Hampton® H27 Direct Vent Freestanding Gas Stove
INSTALLATION
5) Take the embers and place on the burner in the space be-
tween the 2 front logs. Do not put embers on the burner in
the area between the front logs and the rear log. See photo
below.
Separate platinum embers and place at the front of the burner
in and around where the embers are placed. Avoid stacking
platinum embers.
A
B
C
EmbersEmbers
6) Place the center cross log D so it rests in the notch located
on the top of the rear log - position as shown below.
Platinum
Embers
Logs must be oriented as shown below.
7) Test fi re to ensure proper light off (make sure fl ame fl ows
smoothly from one end of burner to the other). If there is
any fl ame hesitation, check that area for any blockage of
the burner ports.
8) Re-install the Glass door and Cast Front and Cast Top.
A
D
B
C
D
Hampton® H27 Direct Vent Freestanding Gas Stove
35
INSTALLATION
OPTIONAL SIDE SHELVESIN-
STALLATION
1) Lift off the Cast Top.
2) Install 2 bolts with lock washers on the inside
top of the left and right side cast panels - (do
not tighten bolts all the way).
Bolts
3) Slide side shelf down on to bolts.
WALL THERMOSTAT
A wall thermostat may be installed if desired.
Connect the wires as per the wiring diagrams.
Note that the wires are connected to the "TH"
on the gas valve. Use table below to determine
the maximum wire length:
Note: Preferable if the thermostat is installed
on an interior wall.
Hampton® offers an optional programmable
thermostat but any 250-750 millivolt rated nonanticipator type thermostat that is CSA, ULC or
UL approved may be used.
CAUTION
Do not connect the millivolt
wall thermostat wires
to the 120V wires.
Thermostat Wire Table
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System)
Wire SizeMax. Length
14 GA.50 Ft.
16 GA.32 Ft.
18 GA.20 Ft.
20 GA.12 Ft.
22 GA.9 Ft.
REMOTE CONTROL
Use the Hampton® Remote Control Kit approved
for this unit. Use of other systems may void
your warranty.
The remote control kit comes with a hand held
transmitter, a receiver and a wall mounting
plate.
1) Choose a convenient location on the wall
to install the receiver and the receptacle box (pro-
tection from extreme heat is very important).
Run wires from the fi replace to that location,
use Thermostat Wire T able.
2) Connect the wires as per the wiring diagram
below.
CAUTION
Do not connect the
millivolt remote control wires
to the 120V wires.
3) Install 3 AAA alkaline batteries in transmitter
and 4 AA alkaline batteries in the receiver.
Install the receiver and its cover in the wall.
Switch the remote receiver to "remote"
mode. The remote control is now ready for
operation.
4) Tighten bolts to secure.
5) Repeat steps 3 & 4 for the other side.
6) Re-install the Cast Top.
36
Hampton® H27 Direct Vent Freestanding Gas Stove
INSTALLATION
FINAL CHECK
Before leaving this unit with the customer, the
installer must ensure that the appliance is fi ring
correctly. This includes:
1) Clocking the appliance to ensure the correct fi ring rate (rate noted on label) at 15
minutes.
If any of the original wires as supplied with the
appliance must be replaced, it must be replaced
with CSA type SEW (200oC) or its equivalent.
This heater does not require a 120V A.C. supply for operation. In case of a power failure, the
burner switch and the optional remote control/
thermostat will continue to operate. However, a
120V A.C. power supply is needed for the fan/
blower operation.
For NATURAL GAS Units and Units NOT Equipped with DC Spark Boxes
2) If required, adjusting the primary air to
ensure that the fl ame does not carbon.
First allow the unit to burn for 15 min. to
stabilize.
3) Check for proper draft.
WIRING DIAGRAMS
Caution: Ensure that the wires do
not touch any hot surfaces and are
away from sharp edges.
Any alteration to the product that causes
CAUTION
sooting or carboning that results in damage
to the exterior facia is not the responsibility
of the manufacturer.
CAUTION: Label all wires prior
to disconnection when servicing
controls. Wiring errors can cause
improper and dangerous operation.
Hampton® H27 Direct Vent Freestanding Gas Stove
37
INSTALLATION
For PROPANE Units and Units Equipped with DC Spark Boxes*
*For installation of the DC Spark Box refer to the LP Conversion instructions in this manual.
38
WARNING: Electrical Grounding Instructions
This appliance is equipped with a three pronged (grounding) plug for your protection
against shock hazard and should be plugged directly into a properly grounded three-prong
receptacle. Do not cut or remove the grounding prong from this plug.
Hampton® H27 Direct Vent Freestanding Gas Stove
OPERATING INSTRUCTIONS
INSTALLATION
OPERATING
INSTRUCTIONS
1) Read and understand these instructions before
operating this appliance.
2) Check to see that all wiring is correct and
enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass in the door frame is properly
positioned. Never operate the appliance with
the glass removed. Never strike the glass.
5) Verify that the venting and cap are unobstructed.
6) Verify log placement. If the pilot cannot be
seen when lighting the unit - the logs have
been incorrectly positioned.
7) The unit should never be turned off, and on
again without a minimum of a 60 second wait.
LIGHTING
PROCEDURE
located at the top right hand corner (rear) of
the stove.
2) Turn gas control knob so indicator points to
"OFF" position and allow 5 minutes for any
gas in the combustion chamber to escape.
3) Turn gas control knob counterclockwise
so indicator points to the "PILOT" position.
Depress the gas control knob fully. Depress
the igniter button several times until the
pilot lights. After approximately one minute,
release the gas control knob. The pilot fl ame
should continue to burn. If the pilot does not
remain lit, repeat operation allowing a longer
period before releasing gas control knob.
4) When the pilot stays lit, turn the gas knob
further counterclockwise to the "ON" position.
5) Use the thermostat or remote control to turn
on the unit.
6) Rotate the fl ame height regulator to adjust
the fl ame height higher or lower.
SHUTDOWN
PROCEDURE
DO NOT ATTEMPT TO CLEAN THE GLASS
WHILE IT IS STILL HOT!
Note: When the glass is cold and the appli-
ance is lit, it may cause condensation
and fog the glass. This condensation
is normal and will disappear in a few
minutes as the glass heats up.
DO NOT BURN THE APPLIANCE
WITHOUT THE GLASS FRONT IN
PLACE.
During the fi rst few fi res, a white fi lm
may develop on the glass front as part
of the curing process. The glass should
be cleaned or the fi lm will bake on and
become very diffi cult to remove. Use a
non-abrasive cleaner and NEVER clean
the glass while it is hot.
ADJUSTING FLAME HEIGHT
Your heater has an adjustable fl ame to tailor the
look and heat output to your specifi c needs. It is
adjusted by turning the fl ame adjustment dial on
the gas control valve.
Turn clockwise to adjust the fl ame higher, coun-
terclockwise for a lower fl ame.
IMPORTANT
To ignite or reignite the pilot,
the door to the fi rebox must
be opened.
Only when the pilot holds, without pressure
being applied to the control knob, should the
door to the fi rebox be closed. The unit must never be operated with the glass or door
open.
NOTE: For all propane units and units
equipped with electric spark boxes, see
"Copy of Lighting Plate Instructions" section for more details.
IMPORTANT: Gas on/off knob cannot be
turned from "PILOT" to "OFF" unless it is
partially depressed.
1) Turn stove OFF using the Burner "ON/OFF"
switch remote or thermostat. Switches are
Hampton® H27 Direct Vent Freestanding Gas Stove
1) Use the thermostat or remote control to turn
off the main burner.
2) Turn the main gas control clockwise to the
"OFF" position to turn off the pilot (push
knob in slightly).
3) Turn off all electric power to appliance if
service is to be performed.
FIRST FIRE
The FIRST FIRE in your stove is part of the
paint curing process. T o ensure that the paint is
properly cured, it is recommended that you burn
your fi replace for at least four (4) hours the fi rst
time you use it with the fan on. When fi rst oper-
ated, the unit will release an odour caused by the
curing of the paint and the burning off of any oils
remaining from manufacturing. Smoke detectors
in the house may go off at this time. Open a few
windows to ventilate the room for a couple of
hours. The glass may require cleaning.
AUTOMATIC
CONVECTION
FAN OPERATION
The fan operates automatically - turn the knob at
the top right rear corner to adjust to the desired
speed. The fan will turn on as the stove comes up
to operating temperature. After the unit has been
turned off and the unit cooled to below a useful
heat output range the fan will shut off automatically .
3939
OPERATING INSTRUCTIONS
COPY OF THE LIGHTING PLATE INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
NFPA 54, or Natural Gas and Propane Installation Codes, CSA B149.1. (Australia: A S5601-2004, New Zealand: NZS 5261)
WARNING: If you do not follow these instructions exactly, a fireor explosion may result causing property damage,
or additional information consult a qualified installer, service agency or gas supplier.
A) This appliance has a pilot which must be lighted by hand, following the instructions below exactly
B) BE FORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the fl
air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
-Do not try to light any appliance
-Do not touch any electric switch, do not use any phone in your building
-Im mediately call your gas supplier from a neighbors phone. Follow the gas supplier’s instructions.
-If you cannot reach your gas supplier, call the fire department.
C) Us
repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D) Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and
to replace any part of the control system and any gas control which has been under water.
E) This appliance needs fresh air for safe operation and must be installed so there are provisions adequate combustion + ventilation air.
1/
.
oor because some gas is heavier than
try to
LIGHTING INSTRUCTIONS
STOP! Read the safety information above on this label.
FOR UNITS NOT EQUIPPED WITH ELECTRIC SP
1)
Push in gas control knob slightly and turn clockwise
“OFF”. Knob cannot be turned from “PILOT” to “OFF” unless
knob is pushed in slightly. Do not force.
PILOT BURNER
VEILLEUSE
THERMOPILE
ELEMENT
THERMOELECTRIQUE
2) Wait fi ve (5) minutes to clear out any gas. If you then smell gas
STOP! follow “B” in the safety information above on this label. If
you don’t smell gas, go to the next step.
3) Turn knob on gas control counterclockwiseto “PILOT”.
4) Push in control knob all the way and hold in. Immediately push
black button on spark igniter until pilot lights. Continue to hold the
control knob in for about 1/2 minute after the pilot is lit. Release
knob and it will pop back up. Pilot should remain lit. If it goes out,
repeat steps 3) and 4).
knob does not pop up when released, stop and immediately call
If
your service technician or gas supplier.
If the pilot will not stay lit after several tries, turn the gas control
knob to “OFF” and call your service technician or gas supplier.
5) Turn gas control knob counterclockwiseto “ON”.
6) Use rocker switch to operate main burner.
ARK:
OFF
TO TURN OFF GAS APPLIANCE
1) Turn off
2) Push in the gas control knob slightly a
3) Turn off all electric power to the applianc
the flame switch.
You may shut off
nd turn clockwiseto “OFF”. Do not force.
e if service is to be perfor
the pilot during prolonged non use periods to conserve fuel.
l
. Keep burner
appliance.
UNITS EQUIPPED WITH ELECTRIC SPARK BOXES:
FORALL PROP
to
1) Push in gas control knob slightly and turn to “PILOT” position.
2) Push in control knob all the way and hold in untilthe pilot lights
up. Continue to hold the control knob in for about 20 seconds
after the pilot is lit. Release knob.
3) Push in gas control knob slightly and turn to "ON" position.
4) Turn ON the flame switch.
med.
ANE UNITS
AND
40
40
DO NOT REMOVE THIS INSTRUCTION PLATE
Hampton® H27 Direct Vent Freestanding Gas Stove
918-474b
MAINTENANCE
NORMAL OPERATING
SOUNDS OF
GAS APPLIANCES
It is possible that you will hear some sounds
from your gas appliance. This is perfectly normal
due to the fact that there are various gauges
and types of steel used within your appliance.
Listed below are some examples. All are normal operating sounds and should not be considered
as defects in your appliance.
Blower:
Hampton® gas appliances use high tech blowers
to push heated air farther into the room. It is not
unusual for the fan to make a "whirring" sound
when ON. This sound will increase or decrease
in volume depending on the speed setting of
your fan speed control.
Burner Tray:
The burner tray is positioned directly under the
burner tube(s) and logs and is made of a different gauge material from the rest of the fi rebox
and body. Therefore, the varying thicknesses of
steel will expand and contract at slightly different
rates which can cause "ticking" and "cracking"
sounds. Y ou should also be aware that as there
are temperature changes within the unit these
sounds will likely re-occur. Again, this is normal
for steel fi reboxes.
Blower Thermodisc:
When this thermally activated switch turns ON
it will create a small "clicking" sound. This is the
switch contacts closing and is normal.
2) Clean glass (never when unit is hot), appliance, and door with a damp cloth. Never
use an abrasive cleaner.
3) The heater is fi nished in a porcelain fi nish or
with a heat resistant paint and should only
be refi nished with heat resistant paint (not
with wall paint).
Never use an abrasive cleaner on the por-
celain fi nish as it may scratch the surface.
4) Make a periodic check of burner for proper
position and condition. Visually check the
fl ame of the burner periodically, making sure
the fl ames are steady; not lifting or fl oating.
If there is a problem, call a qualifi ed service
person.
5) Caution: Label all wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous operation.
6) The appliance and venting system must be
inspected before use, and at least annually,
by a qualifi ed fi eld service person, to ensure
that the fl ow of combustion and ventilation
air is not obstructed.
During the annual service call, the burner
should be removed from the burner tray
and cleaned. Replace the embers but do
not block the pilot.
7) Keep the area near the appliance clear and
free from combustible materials, gasoline,
and other fl ammable vapours and liquids.
CAUTION: ANY SAFETY SCREEN
OR GUARD REMOVED FOR
SERVICING AN APPLIANCE
MUST BE REPLACED PRIOR TO
OPERATING THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT
BE PLACED ON OR NEAR THE
APPLIANCE.
8) Each time the appliance is lit, it may cause
condensation and fog the glass. This
condensation and fog is normal and will
disappear in a few minutes as the glass
heats up.
Never operate the appliance without the
glass properly secured in place.
9) Periodically check the pilot fl ames. Correct
fl ame pattern has three strong blue fl ames: 1
fl owing around the thermopile and 1 around
the thermocouple, and 1 fl owing across the
rear of the burner (it does not have to be
touching the burner).
Note: If you have an incorrect fl ame pat-
tern, contact your Hampton® dealer
for further instructions.
Pilot Flame:
While the pilot fl ame is on it can make a very
slight "whisper" sound.
Gas Control Valve:
As the gas control valve turns ON and OFF, a
dull clicking sound may be audible, this is normal
operation of a gas regulator or valve.
Unit Body/Firebox:
Different types and thicknesses of steel will
expand and contract at different rates resulting
in some "cracking" and "ticking" sounds will be
heard throughout the cycling process.
MAINTENANCE
INSTRUCTIONS
1) Always turn off the valve before cleaning.
For relighting, refer to lighting instructions.
Keep the burner and control compartment
clean by brushing and vacuuming at least
once a year. When cleaning the logs, use a
soft clean paint brush as the logs are fragile
and easily damaged.
WARNING: CHILDREN AND
ADUL TS SHOULD BE ALERTED
TO THE HAZARDS OF HIGH
SURFACE TEMPERATURE AND
SHOULD ST AY A WA Y T O AVOID
BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD
BE CAREFULLY SUPERVISED
WHEN THEY ARE IN THE SAME
ROOM AS THE APPLIANCE.
DO NOT USE THIS APPLIANCE
IF ANY P ART HAS BEEN UNDER
WATER. IMMEDIATELY CALL A
QUALIFIED SERVICE TECHNICIAN TO INSPECT THE APPLIANCE AND TO REPLACE ANY
PART OF CONTROL SYSTEM
AND ANY GAS CONTROL WHICH
HAS BEEN UNDER WATER.
Top View of pilot fl ame
Incorrect fl ame pattern will have small, probably
yellow fl ames, not coming into proper contact
with the rear of the burner or thermopile.
Top View of pilot fl ame
Hampton® H27 Direct Vent Freestanding Gas Stove
41
MAINTENANCE
GENERAL VENT
MAINTENANCE
Conduct an inspection of the venting system
semi-annually. Recommended areas to inspect
as follows:
1) Check the Venting System for corrosion in
areas that are exposed to the elements.
These will appear as rust spots or streaks,
and in extreme cases, holes. These components should be replaced immediately.
2) Remove the Cap, and shine a fl ashlight
down the Vent. Remove any bird nests, or
other foreign material.
3) Check for evidences of excessive condensation, such as water droplets forming in the
inner liner, and subsequently dripping out the
joints, Continuous condensation can cause
corrosion of caps, pipe, and fi ttings. It may
be caused by having excessive lateral runs,
too many elbows, and exterior portions of the
system being exposed to cold weather.
4) Inspect joints, to verify that no pipe sections
or fi ttings have been disturbed, and conse-
quently loosened. Also check mechanical
supports such as Wall Straps, or plumbers'
tape for rigidity.
1) Lift off the Cast Top.
2) Open front access panel and remove 2 - 7/16"
bolts from locations shown below.
3) Remove the 2 - 7/16" bolts which secure
the top of the cast front on both the left and
right side as shown.
5) Lift the Glass Front Assembly up.
6) a) Remove the glass and replace with the
new glass.
b) Remove logs and replace the newer
logs.
7) Reinstall the door and Cast Front and Top.
Replacement Part # 946-327 Glass
WARNING: Do not operate appliance with
glass panel removed, cracked or broken.
Replacement of the glass should be done by
a licensed or qualifi ed service person.
Note: Wearing gloves will protect your
hands while handling glass.
FAN MAINTENANCE
If your fan requires maintenance or replacement, access to the fan is through the rear
access panel on the back of the unit. NOTE:
the unit MUST NOT be operated without
the fan access panel securely in place and
correctly sealed.
5) Verify proper operation after servicing.
LOG REPLACEMENT
The unit should never be used with broken logs.
Turn off the gas valve and allow the unit to cool
before opening door to carefully remove the
logs. The pilot light generates enough heat to
burn someone. If for any reason a log should
need replacement, you must use the proper
replacement log. The position of these logs
must be as shown in the diagram under Log
Installation.
Note: Improper positioning of logs may
create carbon build-up and will alter
the unit’s performance which is not
covered under warranty.
GLASS
REPLACEMENT
Y our stove is supplied with high temperature, 5
mm Neoceram ceramic glass that will withstand
the highest heat that your unit will produce. In
the event that you break your glass by impact,
purchase your replacement door from an authorized Hampton® dealer only, and follow our
step-by-step instructions for replacement.
4) Lift off Cast Front - place on a soft surface.
5) On top of fi rebox - undo 2 latches.
IMPORTANT: These fans collect a lot of
dust from within your home. Ensure you
maintain these fan motors on a regular basis
by vacuuming out the fan squirrel cages,
around the motor, and around the grills on
the back of the stove.
WARNING:
Electrical Grounding Instructions
This appliance is equipped with
a three pronged (grounding) plug
for your protection against shock
hazard and should be plugged
directly into a properly grounded
three-prong receptacle. Do not cut
or remove the grounding prong
from this plug.
IMPORTANT
Disconnect power supply
before servicing
To Remove Fan:
1) Unplug or disconnect power source to
stove.
42
Hampton® H27 Direct Vent Freestanding Gas Stove
MAINTENANCE
screws
2) Remove the rear access panel on the back
of the stove by removing the 2 screws under
the rear panel, then lift off the 2 screws at
the top. Take care not to cut wires when
lowering the panel.
screws
bolts
Lift Rear Panel off the 2 top bolts
3) Unclip the black and white wires from the
fan motor.
3) Disconnect gas line to stove.
4) Disconnect 3/8" NPT pipe from 90o elbow
on valve or fl ex connector.
5) Disconnect the two (2) switch wires from
valve.
6) Disconnect piezo wire.
7) Lift off the Cast Top and remove the Cast
Front and glass door (refer to pg. 41).
8) Carefully remove the logs and embers.
9) Remove burner by removing the 2 screws
on each side and then lifting the burner tray
out.
Note: Use a magnetic type screwdriver if
possible.
11) Carefully lift the burner tray assembly out.
12) T o remove the valve, remove the 4 screws (2
per bracket) that hold the valve to the valve
bracket assembly.
13) To replace the burner tray assembly, simply
reverse these instructions.
To remove valve from valve assembly, continue.
14) Remove two (2) thermopile wires.
4) Remove the 2 bolts holding the fan to the
rear base. Disconnect the green ground
wire from the right side of the fan as soon
as you can reach it.
Replacing the Fan:
Reverse the above steps (1 - 4). Make sure the
fan wires and the ground wire are reattached.
REMOVING VALVE
If your valve requires maintenance or replacement, use the following instructions:
Note: Always close off the gas supply before
removing the valve.
1) If optional fan is installed, disconnect power
source to stove.
2) Remove access panel.
Screws
10) Remove all 6 screws holding the burner tray
assembly in place.
15) Remove thermocouple with a 9 mm (metric)
wrench.
16) Remove pilot nut with an 11 mm wrench.
17) Remove valve to orifi ce nut with a 13/16"
wrench.
18) Remove inlet pipe with pipe wrench. Note
orientation of 90o elbow.
19) Remove two (2) phillips head M5 screws on
each side of the valve.
20) Remove valve and remove gas out 90o brass fi tting. Note orientation of fi tting.
INSTALLING
V ALVE ASSEMBL Y
1) To install a new valve assembly, reverse in-
structions for removing valve. See assembly
steps 1-12.
2) Check for leaks and manifold pressure. See
Gas Pressure Test instructions.
3) To reinstall valve, reverse instructions for
removing valve assembly, steps 13-19.
Hampton® H27 Direct Vent Freestanding Gas Stove
43
PARTS LIST
MAIN ASSEMBL Y
Part # Description Part # Description Part # Description
1) 356-101** Casting - Top
3) 356-111** Casting - Front
4) 356-121** Casting - Side Right
356-131** Casting - Side Left
5) 356-141** Casting - Leg (each)
6) 356-941** Casting - Side Shelf (set)
9) 260350 Gasket for Rear Relief
Plate
10) 290-015 Rear Relief Plate
350-524 Front Door Assembly
18) 350-002 Door Support
19) 350-006 Door Frame
22) 41225 Gasket - Tadpole
23) 940-327/P Replacement Glass
24) 350-007 Glass Bracket
30) 948-219 Hampton® Logo
38) * Firebox
43) 948-255 Latch c/w Hook
918-812 Manual
Baffl e Restrictor Assembly
44) 350-005 Restrictor
45) 350-004 Baffl e Plate for Firebox
48) 350-022 Casting Mount Bracket
49) * Fan Air Divider
50) W260260 Top Relief Frame Gasket
51) 942-117 Top Relief Frame
52) W260280 Top Relief Plate Gasket
53) 770-066F Top Relief Plate
54) * Capscrew 1/4 x 1-3/4 NC
55) * Side Shield
57) W260108 Gasket for Inner Flue
58) W842051 Gasket for Flue Adaptor
59) 945F Dura-Vent Collar
79) * Stove Base
114) * Wire Tie
115) * Wire Tie Mount
910-704 Wire Harness - Fan End
134) 356-003 Rear Panel
135) 280-033 Rear Control Panel
136) 910-241 Burner ON/OFF Switch
137) * Hole Plug 0.375
908-106 Decal Rear Control Panel
350-917 Fan Assembly Complete
-120 V (Option)
144) 910-157/P Fan Motor 120 V
145) 910-233 Fan Thermodisc Auto On/
Off
146) 910-794 Power Cord (120 V)
148) 910-330 Fan Speed Control (120 V)
149) 904-569 Knob - Fan Speed Control
150) 356-004 Heat Shield
*Note: Not available as a replacement part.
**Last digit of part number indicates colour:
1=Charcoal Grey, 5=Timberline,
7=Seaside Sand
Diagram - next page.
44
Hampton® H27 Direct Vent Freestanding Gas Stove
MAIN ASSEMBL Y
1
54
53
52
51
PARTS LISTPARTS LIST
54
137
149
136
135
148
134
50
6
4
30
55
2
45
44
24
19
59
57
38
150
6
79
30
79
Hampton® H27 Direct Vent Freestanding Gas Stove
Hampton® H27 Direct Vent Freestanding Gas Stove
146
144
5
5
5
5
45
45
I
L
P
O
T
O
L
68
67
68
66
87
75
89
70
69
63
64
60
86
65
71
82
80
73
74
88
90
PARTS LIST
BURNER & LOG ASSEMBLY
Part # Description
350-574/P Valve Assembly S.I.T. - Natural Gas
60) 910-478 Valve S.I.T. - Natural Gas / Propane
904-430 #42 Orifi ce - NG.
904-163 #54 Orifi ce - LP
63) 910-190 Piezo Ignitor & Nut
64) 908-672 Control Panel Decal
65) 490-061 Switch Plate
936-170 Orifi ce Gasket
66) 910-038 Pilot Assy-S.I.T.-3 fl ame-NG
910-039 Pilot Assy-S.I.T.-3 fl ame-LP
67) * Pilot Holder
68) W840470 Pilot Assembly Gasket
69) * Valve Shield
70) * Valve Bracket
71) 260-042 Valve Gasket
73) * Valve Cover Plate
74) * Valve Access Door
75) 350-930 Log Set
80) 350-530 Burner Assembly - Natural Gas
82) 350-020 Log Tray Rear
86) 260-565 Air Shutter Gear Assembly - Female
87) 904-565 Hex Key 3/16"
88) 350-019 Burner Box Gasket
89) * Air Shutter Gear Assembly - Male
90) * Burner Box
434-969 Conversion Kit from Natural Gas to Propane
*Note: Not available as a replacement part.
46
Hampton® H27 Direct Vent Freestanding Gas Stove
WARRANTY
WARRANTY
Hampton Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit
thoroughly before it leaves our facility. FPI Fireplace Products International Ltd. is pleased to extend this limited lifetime warranty to the original purchaser of
a Hampton Product. This warranty is not transferable.
The Warranty: Limited Lifetime
External casting, not directly in contact with the fi re, such as hobs, sides, ash lips, legs, fronts and fi re doors, are covered against cracks and warps resulting from manufacturer
defects, parts and subsidized labour* for three (3) years from the date of purchase and parts only thereafter.
The combustion chamber, heat exchanger, burner tubes/pans and logs are covered under the Limited Lifetime Warranty for fi ve (5) years for parts and subsidized labour*
and parts only thereafter.
Glass is covered for lifetime against thermal breakage only, parts and subsidized labour* for fi ve (5) years and parts only thereafter from date of purchase.
Electrical and mechanical components such as blowers, switches, wiring, thermodiscs, FPI remote controls, spill switches, thermopiles, thermocouples, pilot assembly
components, and gas valves are covered for two years parts and one year subsidized labour* from the date of purchase. Blowers and valves replaced under warranty are
considered repairs and continue as if new with appliance. ie. twelve (12) months from original purchase date of appliance with a minimum of three (3) months coverage from
date of replacement.
FPI venting components are covered parts and subsidized labour* for three (3) years from date of purchase.
Simpson Dura-Vent venting components are covered by Simpson Dura-Vent Inc. warranty.
Repair/replacement parts purchased by the consumer from FPI after the original coverage has expired on the unit will carry a 90 day warranty, valid with a receipt only. Any
item shown to be defective will be repaired or replaced at our discretion. No labor coverage is included with these parts.
Conditions:
Porcelain/Enamel - Absolute perfection is neither guaranteed nor commercially possible. Any chips must be reported and inspected by an authorized dealer within three days
of installation. Reported damage after this time will be subject to rejection.
Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FPI's option, through an accredited distributor or agent
provided that the defective part be returned to the distributor or agent Transportation Prepaid, if requested.
It is the general practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated
for manufacturer defect.
The authorized selling dealer is responsible for all in-fi eld service work carried out on your Hampton product. FPI will not be liable for results or costs of workmanship from
unauthorized service persons or dealers.
At all times FPI reserves the right to inspect product in the fi eld which is claimed to be defective.
All claims must be submitted to FPI by authorized selling dealers. It is essential that all submitted claims provide all of the necessary information including customer name,
purchase date, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint (charcoal units), porcelain (including pinholes, scratches and minor shade mismatch), door or glass
gasketing or trim.
At no time will FPI be liable for any consequential damages which exceed the purchase price of the unit. FPI has no obligation to enhance or modify any unit once manufactured. ie. as products evolve, fi eld modifi cations or upgrades will not be performed.
FPI will not be liable for travel costs for service work.
Installation and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.
Embers, door and glass, gaskets, door handles, paint are not covered under the terms of this warranty policy.
Any unit which shows signs of neglect or misuse is not covered under the terms of this warranty policy.
The warranty will not extend to any part which has been tampered with or altered in any way, or in our judgment has been subject to misuse, improper installation, negligence
or accident, spillage or downdrafts caused by environmental or geographical conditions, inadequate ventilation, excessive offsets, negative air pressure caused by mechanical
systems such as furnaces, fans, clothes dryer, etc.
Freight damage to stoves and replacement parts is not covered by warranty and is subject to a claim against the freight carrier by the dealer.
FPI will not be liable for acts of God, or acts of terrorism, which cause malfunction of the appliance.
Performance problems due to operator error will not be covered by this warranty policy.
Products made or provided by other manufacturers and used in conjunction with the operation of this appliance without prior authorization from FPI, may nullify your warranty on this product.
Any alteration to the unit which causes sooting or carboning that results in damage to the interior / exterior facia is not the responsibility of FPI.
* Subsidy according to job scale as predetermined by FPI.
Hampton® H27 Direct Vent Freestanding Gas Stove
47
Register your Regency® warranty online
www.regency-fi re.com
Reasons to register your product online today!
• View and modify a list of all your registered products.
• Request automatic email notifi cation of new product updates.
• Stay informed about the current promotions, events, and special
offers on related products.
Installer: Please complete the following information
Dealer Name & Address: ______________________________________________
___________________________________________________________________
Installer: ___________________________________________________________
Phone #: ___________________________________________________________
Date Installed: ______________________________________________________
Serial No.: __________________________________________________________
Hampton® and AstroCap™ are trademarks of FPI Fireplace Products International Ltd.