REFCO VG-64 User Manual

VG-64
x 2 are,
7640126 683775
DIGITAL VACUUM GAUGE
FEATURES
• Ultra fine resolution (as low as 1 Micron)
• ½ second response time
Auto shut off
• Easy access cleaning port
SPECIFICATIONS
Sensor Type Thermistor Connector Type Standard ¼ inch male flare fitting. Vacuum Range 0 – 12,000 Microns (0 – 1,600
Pascals) with vacuum increasing/ decreasing indicator when above 12,000 Microns
Scale Microns, PSI, InHg, milliBars, Pascals,
Torr, milliTorr
Resolution 0-200: 1 Micron
201-500: 5 Microns 501-1,000: 10 Microns 1,001-2,000: 50 Microns 2,001-5,000: 250 Microns 5,001-8,000: 500 Microns
8,001-12,000: 1,000 Microns Operating 35°F to 125°F ( 2°C to 52°C) Temp.Range Overpressure 500 PSI maximum Accuracy +/-10% (100 to 1000 microns) Power Source 9 Volt Alkaline Battery Battery Life Over 35 Hours Auto Shutoff After 10 minutes when vacuum reading
is above 12,000 Microns (12 Torr) Weight 6.7 ounces Dimensions ²H X 3²W X 1¼²D
Refrigeration Service Products and Components
HVAC/R
Service Products
Digital Vacuum Gauge
Vakuummessgerät Vacuomètre
VG-64
4503171
HVAC/R
Service Products
VG-64
4503171
REFCO Manufacturing Ltd.
CH-6285 Hitzkirch (Switzerland) Telefon +41 41 919 72 82
OPERATING CONTROLS
Turning the vacuum gauge ON: Press and hold the ON button for approximately 3 seconds, until the display appears.
• Turning the vacuum gauge OFF: Press the OFF button. To prolong battery life, when vacuum reading is above 12,000 Microns for approximately 10 minutes, the VG­64 will automatically turn OFF.
CONNECTING THE
VG-64
VG-64 TO THE VACUUM SYSTEM
The VG-64 should be connected to the vacuum system at the vacuum port. The "Auxiliary Port" is primarily for cleaning And should normally be closed with the supplied cap. It is possible to connect the VG-64 in-line, however it may restrict flow and increase the evacuation time.
• Changing the scale: Press the Scale button to change the display to the next scale. The scale order is: Microns, PSI, Inches of mercury (InHg), milliBars, Pascals, Torr and milliTorr. The VG-64 will keep the scale settings even if the power is turned OFF.
UNDERSTANDING THE DISPLAY
When the vacuum reading is above 12,000 Microns
(1,600 Pascals), the first line of the display shows "Atm." The second line displays a bar graph to indicate the direction in which the vacuum is moving. When the bar graph is moving from left to right, the pressure is increasing. When the bar graph is moving from right to left, the pressure is decreasing. The speed of the bar graph indicates how fast the pressure is increasing or decreasing. The bar graph indicator may be inaccurate for a few seconds after the evacuation of the system has begun.
• The bar graph disappears if the vacuum does not change for approximately 10 seconds.
• When the vacuum reading is below 12,000 Microns (1,600 Pascals), the vacuum in the selected units is displayed.
CLEANING THE VG-64 VACUUM SENSOR
It is recommended that the VG-64 sensor be cleaned periodically to maintain unit accuracy. Oil and other contaminants reduce the accuracy of the VG-64 unit. Follow the instructions below for cleaning.
• Close the vacuum port with the supplied cap. Open the auxiliary port.
• Use an eyedropper to pour approximately 2 teaspoons of ordinary rubbing alcohol into the auxiliary port.
• Close the auxiliary por t with the supplied cap. Both the vacuum and auxiliary por ts should now be closed.
• Shake the VG-64 unit for approximately 10 seconds. A slight movement of the vacuum sensor in the case is normal and does not affect the internal connection in any way.
• Open both the vacuum and the auxiliary ports. Empty the alcohol and air dry the sensor.
• Close both the vacuum and the auxiliary ports with the supplied caps when the VG-64 is not used. This prevents contamination of the sensor.
CHECKING HVAC SYSTEMS FOR LEAKS
When checking a system for leaks use only copper tubing and a vacuum proof valve. Generally standard hoses will not hold a vacuum. If using the blank-off valve on the vacuum pump check it for leaks periodically. At the beginning of the test the VG-64 reading may increase due to a system equalization. The vacuum reading should hold after a minimum of 5 minutes. If the reading continues to increase it may indicate a leak in the system.