Universal Condensate Pump
Combi
x 1
x 1 (1m)
PH#2
x 1 (1,5 m)
x 1 (1,5 m)
x 1
x 1 (2 m)
x 1
x 1 (2m)
x 3
x 5
View installation video at www.condensate-pumps.com
1
ON
ON
ON
ON
1 2
ON
1 2
Low
up to 18K Btu/h
(5.3kW)
2
3
1 2
Medium Low
up to 42K Btu/h
(12kW)
1 2
Medium High
up to 72K Btu/h
(21.1kW)
1 2
Full Power
up to 120K Btu/h
(35kW)
When Indoor Evaporator Unit is powered from the Outdoor Condenser Unit. Below examples are for reference only.
Evaporator Unit (Indoor)
Condenser Unit (Outdoor)
**Orange:
To use fail-safe
operation.
1. Remove the violet
wire from indoor live.
2. Connect the orange
wire to indoor live.
3. Change alarm relay
to fail-safe operation.
NL 3
**Orange
Violet
NC NO
COM
NO
COM
NC
Condensate Pump
Grey
Fuse 10A
Alarm
Relay
(typical) Data
100-240vac~
Brown
Blue
Alarm Relay Operation Table
NL
Replaceable
Power Up LED Sequence
Pump Status Condensate Level
Unpowered N/A
Powered Below Alarm Level
Earth
Neutral
3
N
L
N
L
When Multi-Split System is installed
Default
Operation
Fail-Safe
Operation
Evaporator Units (Indoor)
N L3
Powered Alarm-Activated
To change Alarm Relay Operation:
1. Unplug pump
2. Move DIP switch positions to
3. Plug pump in
4. Wait for one green LED blink
5. Move DIP switch positions to
6. Wait for one red LED blink
7. Reset DIP switch positions to
8. Wait for one green LED blink
9. Unplug pump
10. Set the DIP switches back to the desired capacity
configuration. (Low, Medium-Low, Medium-High, High)
11. Plug Pump in and check that power up LED sequence
matches the desired alarm relay operation
12. Done.
To reset default alarm relay operation repeat
steps 1 thru 11.
**Orange:
To use fail-safe operation.
1. Remove the violet wire from indoor live.
2. Connect the orange wire to indoor live.
3. Change alarm relay to fail-safe operation.
VRF Condenser Unit
(Outdoor)
N
L
3
N
L
(typical) Data
Earth
Neutral
100-240vac~
Condensate Pump
Violet
NC
Blue
Brown
Safety Circuit
**Orange
NO
Grey
COM
Replaceable
Fuse 10A
NO
Alarm
Relay
COM
NC
N
L
www.condensate-pumps.com
4a 4b
Horizontal installation Vertical installation
2
1
1
5a
Horizontal installation
1
2
View installation video at www.condensate-pumps.com