Pilz PSSnet GW1 MOD-EtherCAT User Manual

PSSnet GW1 MOD-EtherCAT
Gateways
Operating Manual-1002692-EN-02
Preface
This document is a translation of the original document.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
SD means Secure Digital
Content
Section 1 Introduction 5
1.1 Validity of documentation 5
1.2 Retaining the documentation 5
1.3 Definition of symbols 5
Section 2 Overview 6
2.1 Module features 6
2.2 Unit view 7
2.2.1 Front 7
2.2.2 Top 8
2.2.3 Right-hand side 8
2.2.4 Bottom 9
Section 3 Safety 10
3.1 Intended use 10
3.1.1 Electromagnetic compatibility 10
3.1.1.1 Connecting the earth cables 11
3.1.1.2 Cable routing 12
3.1.1.3 Equipotential bonding 12
3.1.1.4 Shielding 13
3.1.1.5 Lighting in the control cabinet 13
3.1.1.6 Testing the EMC-compliance of an installation 13
3.2 Safety regulations 14
3.2.1 Use of qualified personnel 14
3.2.2 Warranty and liability 15
3.2.3 Disposal 15
3.3 Safety during installation 15
Section 4 Function description 16
4.1 Operation 16
4.1.1 Block diagram 16
4.2 Modbus/TCP 17
4.2.1 Modbus/TCP data ranges (Server connections) 17
4.2.2 Data transfer limits 17
4.2.3 Function codes (Client connections) 18
4.3 EtherCAT 19
4.4 Translation tables 20
4.4.1 Payload 20
4.4.2 Diagnostic data 20
4.5 Interfaces 23
Section 5 Installation 24
5.1 General installation guidelines 24
5.1.1 Dimensions 25
5.2 Mounting distances 26
5.3 Supply voltage 26
5.4 Install Gateway 27
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
3
Content
Section 6 Commissioning 28
6.1 General wiring guidelines 28
6.2 Wiring the units 28
6.2.1 Cable requirements 28
6.2.2 Terminals 29
6.3 Terminal configuration 29
6.4 Interfaces 29
6.4.1 RJ45 interface 29
6.4.1.1 RJ45 connection cable 30
6.5 Address setting 30
6.5.1 IP address setting 30
Section 7 Operation 32
7.1 Display elements 32
7.1.1 Display elements for device diagnostics 32
7.2 Web server 33
7.2.1 Password management 33
7.2.2 Call web server 34
7.3 Exchange Gateway 34
Section 8 Technical Details 35
Section 9 Order reference 38
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
4

Introduction

1
1.1
1.2
1.3
Introduction

Validity of documentation

This documentation is valid for the product PSSnet GW1 MOD-EtherCAT. It is valid until new documentation is published.
This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.

Retaining the documentation

This documentation is intended for instruction and should be retained for future reference.

Definition of symbols

Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could lead to serious injury and death and indicates preventive measures that can be taken.
ATTENTION!
This refers to a hazard that can lead to a less serious or minor injury plus material damage, and also provides information on preventive measures that can be taken.
CAUTION!
This describes a situation in which the product or devices could be dam­aged and also provides information on preventive measures that can be tak­en. It also highlights areas within the text that are of particular importance.
Information
This gives advice on applications and provides information on special fea­tures.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
5

Overview

2
2.1
Overview

Module features

The PSSnet GW1 MOD-EtherCAT
} operates as a protocol converter between Modbus/TCP and EtherCAT,
} can be used to exchange data between products that support Modbus/TCP or Ether-
CAT . For example, this may be a control system from the automation system PSS 4000 from Pilz on one side and a third-party product on the other. The third party product must support EtherCAT .
Features of the PSSnet GW1 MOD-EtherCAT:
} Can be used with Pilz products that support Modbus/TCP:
– Control systems from the automation system PSS 4000 (e.g. PSSu H)
– Compact/modular 3rd generation PSS-range programmable safety systems (e.g.
PSS SB 3006-3 ETH-2, PSS(1) SB CPU3 ETH-2)
– Operator terminals PMI with Modbus/TCP interface (e.g. PMI 5)
– Motion control systems (e.g. PMCprimo Drive3, PMCprimo DriveP, PMCprimo 16+)
} 1 x RJ45 socket for connection to Modbus/TCP,
} Can manage up to 8 Modbus/TCP connections
} Can operate as a Modbus/TCP connection Server,
} Web server for managing and configuring the Gateway,
} Supports CANopen over EtherCAT,
} Operates as a Slave in the EtherCAT network,
} Transmission rate 10 MBit/s (10BaseT) and 100 MBit/s (100BaseTX),
} 2 x RJ45 socket for connection to EtherCAT,
} supports autonegotiating,
} LEDs for displaying the communication status and errors,
} input/output data
– up to 512 Bytes acyclical data (SDO),
– in total (RxPDO and TxPDO) max. 512 Bytes,
– additionally it is possible to transfer data between the control systems,
} supply voltage
– 20 ms buffer in case of supply interruptions,
– plug-in connection terminals (either spring-loaded terminal or screw terminal).
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
6
Overview
2.2
2.2.1

Unit view

Front

22,5 (0,88“)
Front view
: LEDs for displaying the communication status and faults
: EtherCAT interfaces X1 and X2 (RJ45)
: MAC address
: Barcode with the item number, serial number and version of the Gateway
: 2D code with the MAC address
is registered trademark and patented technology, licensed by Beckhoff
Automation GmbH, Germany
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
7
Overview
2.2.2

Top

Top
: Modbus/TCP interface (RJ45)
: DIP switch for IP address
OFFON
128
IP-ADDRESS
64 32 16
8 4
2 1
2.2.3

Right-hand side

1
2
4
8
16
110,4 (4,35“)
32
64
128
IP-Address
96 (3,78“)
Right-hand side
: QR code with a link to the Pilz homepage with further information on the Gateway
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
8
Overview
2.2.4

Bottom

Bottom
: Supply voltage connection
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
9

Safety

3
3.1
Safety

Intended use

The product serves as a protocol converter between Modbus/TCP and EtherCAT. It can be used with various Pilz products as well as third-party products, provided they support the documented properties and requirements.
} Modbus/TCP
The Gateway can be used with products that operate as connection Client during data
exchange. The product must support at least one of the documented function codes .
} EtherCAT
The Gateway can be used as a passive subscriber (Slave) in a EtherCAT network. The
basic functions of communication via EtherCAT correspond to the System Description published by the EtherCAT User Group.
The Gateway may not be used for safety-related functions.
Intended use includes making the electrical installation EMC-compliant. The product is de­signed for use in an industrial environment. It is not suitable for use in a domestic environ­ment, as this can lead to interference.
The following is deemed improper use in particular:
} Any component, technical or electrical modification to the product
} Use of the product outside the areas described in this manual
} Use of the product outside the technical details (see chapter entitled "Technical De-
tails")
3.1.1

Electromagnetic compatibility

To ensure electromagnetic compatibility the correct procedures must be carried out during installation.
A device is electromagnetically compatible if:
} It functions without error in a given electromagnetic environment
} It does not adversely affect its own environment.
Electromagnetic interference can reach the devices through:
} Fields
} Power supplies
} Earth cabling
} Bus connections
} Interfaces
} Input and output cables
The interference can be transferred from the producer (source) to the receiver (interference sink) via the coupling routes.
Interference reaches the interference sink (e.g. the control system devices) in various ways:
} DC coupling:
DC coupling occurs if the source and sink of interference have common cable connec-
tions. The common cable presents complex resistances, inducing potential differences.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
10
Safety
Typical sources of interference are switches/relays, running motors or varying potentials
for other systems on the same power supply.
} Capacitive (electrical) coupling:
A different potential between the source and interference sink (e.g. two cables) creates
an electrical field. Coupling is proportional to the rate of voltage change.
Typical sources of interference are contactors, static discharge, parallel signal cables.
} Inductive (magnetic) coupling:
A live cable produces a magnetic field which also surrounds adjacent cables. Interfer-
ence voltage is induced. Coupling is proportional to the rate of current change.
Typical sources of interference are mains cables running in parallel, live cables, high
frequency cables, inductors, transformers, motors.
} Electromagnetic coupling:
A cable can emit a signal as a radio wave. This wave is then picked up by another ca-
ble.
Typical sources of interference are transmitters such as radios, sparks from spark
plugs, welding equipment, etc.
3.1.1.1
CAUTION!
Powerful HF transmitters should only be operated at a distance of more than 0.6 m.
} Static discharge:
Static discharge occurs where there are very high differences in potential between two
points. If the two points are brought closer together or if the potential difference is in­creased, discharges can occur in the air gaps.
Typical sources of interference are people who are statically charged from a synthetic
carpet, for example.
Connecting the earth cables
Please note:
} A conductor cross section of at least 2.5 mm
2
should be used for the connection to the
central earth bar. Connections should be kept as short as possible.
} Connections to the earth bar should always be in star form.
} Connect together the 0V connections on all the 24 V power supplies and earth the 0 V
mains at a single point, or ensure that measures are in place to monitor for earth faults.
Earthed supply voltages offer the best noise immunity.
} The connection of the 0 V supply to the central earth bar or earth fault monitor must be
in accordance with relevant national regulations (such as EN 60204-1, NFPA 79:17-7, NEC: Article 250).
} Connections should be protected from corrosion.
} Flexible earthing straps should be used on moving earth parts (e.g. machine parts,
gates). Ensure these earthing straps are as short and wide as possible.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
11
Safety
3.1.1.2
Cable routing
It is possible to differentiate between cables according to their function. The
following groups exist:
}
Group 1: Data and supply lines for DC voltages below 60 V and AC voltages below 25 V
} Group 2: Data and supply lines for DC voltages from 60 V to 400 V and AC voltages
from 25 V to 400 V.
} Group 3: Supply lines above 400 V
Cabling inside buildings:
} The cable groups listed above should be laid separately.
} Cables of the same group can be laid within the same cable duct.
} Cables from group 1 and group 2 should be laid in separate groups or in cable ducts
which are at least 10 cm apart.
} Cables from group 1 and group 3 should be laid in separate groups or in cable ducts
which are at least 50 cm apart.
} Data and signal lines should be laid as close as possible to an earthed surface.
Cabling to open air systems:
} As far as possible use metal conduits. These should be electrically connected and
earthed.
} Ensure there is sufficient protection against lightning by using metal conduits earthed at
both ends, or concrete cable ducts with reinforcements connected across the joints.
3.1.1.3
Equipotential bonding
Potential differences can occur if the devices are connected to different earth or ground connections. Even cable shields that are connected at either end and have different earth connections can cause potential differences. In order to avoid interference, equipotential bonding cables must be installed.
In doing so you must ensure the following:
} Select a low impedance equipotential bonding cable.
} Select the following as standard values for the cross section of the equipotential bond-
ing cables:
– 16 mm
– 25 mm
2
for equipotential bonding cable up to 200 m in length
2
for equipotential bonding cable over 200 m in length
} If the control system devices are connected with shielded signal cables which are
earthed at either end, the impedance is calculated as follows:
– Impedance equipotential bonding cable = 10 % of shield impedance.
} Use copper or galvanised steel equipotential bonding cable.
} Connect equipotential bonding cables to the earth bar over as wide a surface area as
possible.
} As short a distance as possible should be kept between the equipotential bonding cable
and signal cable.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
12
Safety
3.1.1.4
Shielding
Interference currents must be diverted to cable shields via shield bars.
In doing so you must ensure the following:
} Connect the shields with low impedance to the shield bar or earth bar.
} Use cables with braided screening, with a minimum cover area of 80 %.
} When laying cables without equipotential bonding or using foil shields: Connect the
shield at one end.
} If possible, use metal or metallised plugs to connect cables for serial data transfer. Al-
ways refer to the regulations relating to the fieldbus systems.
} If the shield is not to be connected at the end of the cable, it must have no connection
to the connector housing.
} If the shield is to be connected, connect it to the shield bar at the point where the cable
enters the cabinet, without making a break in the cable. Use metal cable clamps which cover the shield over a wide surface area. Route the shield as far as the units, but do not connect it to the units.
Digital inputs and outputs do not need shielded cables.
However, if the connection cables have a shield, it should be connected at one end.
Analogue inputs and the incremental encoder inputs on speed monitors should always be connected using shielded cables.
3.1.1.5
3.1.1.6
Lighting in the control cabinet
Use low interference panel lighting for inside the control cabinet.
Testing the EMC-compliance of an installation
You can use the list below to check that the installation of the Gateway is EMC-compliant.
Check Measures Done
Are there areas with a high probability of interference?
EMC protection in these areas should be planned
with particular care. (e.g. computers running, process control areas, dis­tribution cabinets, cable casing, frequency convert­ers, hand-held radios etc.).
Are areas where comput-
If necessary shield the whole area. ers are running or areas such as process control rooms sufficiently shielded from electromagnetic cou­pling?
Does the cable layout take into account the principles of EMC compliance?
Some important points: Lay cables close to earth,
keep clear of other electrical equipment, keep ca-
bles in ducts separate from other parts of the in-
stallation, keep cables as short as possible, avoid
multiple crossovers.
Is the supply voltage free of interference?
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
Supplies with interference voltages should be fit-
ted with a mains filter.
13
Safety
Check Measures Done
EMC characteristics of in­dividual units / all units tested once installed?
Earthed parts connected correctly?
Cable groups laid sepa­rately?
Are the shields connected correctly?
Equipotential bonding car­ried out?
Test EMC characteristics under operating condi-
tions, e.g. while hand-held radios are in use, or
HF frequency generators are close by. Test static
discharge with operating personnel, test mutual
interference between units under different operat-
ing conditions.
The connections between the units, racking bars,
earth conductors and shield bars are important.
Inactive metal parts should be connected over a
wide surface area and earthed at a central point;
with insulated metal: Remove insulation or use
special contact fixings; protect the connection
from corrosion; connect the cabinet doors to the
body of the cabinet using earthing straps.
Separate cables into groups. Supply and signal
leads should be laid separately.
Use shielded cables for analogue and data leads;
use metallic plugs; connect cable shields to shield
bar at point of entry to cabinet; connect cable
shields over a wide surface area and with low im-
pedance.
If the installation extends over a wide area: lay
equipotential bonding cable.
3.2
3.2.1
Are inductive loads switched?
24 VDC power supply? Power supplies must conform to EN
Sufficient fuse protection should be used with in-
ductive loads
60742:9/1995, EN 60950-1:2006/A11:2009 or EN
50178: 10/97.

Safety regulations

Use of qualified personnel

The products may only be assembled, installed, programmed, commissioned, operated, maintained and decommissioned by competent persons.
A competent person is someone who, because of their training, experience and current pro­fessional activity, has the specialist knowledge required to test, assess and operate the work equipment, devices, systems, plant and machinery in accordance with the general standards and guidelines for safety technology.
It is the company’s responsibility only to employ personnel who:
} Are familiar with the basic regulations concerning health and safety / accident preven-
tion
} Have read and understood the information provided in this description under "Safety"
} And have a good knowledge of the generic and specialist standards applicable to the
specific application.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
14
Safety
3.2.2
3.2.3
3.3

Warranty and liability

All claims to warranty and liability will be rendered invalid if
} The product was used contrary to the purpose for which it is intended
} Damage can be attributed to not having followed the guidelines in the manual
} Operating personnel are not suitably qualified
} Any type of modification has been made (e.g. exchanging components on the PCB
boards, soldering work etc.).

Disposal

When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act).

Safety during installation

The product requires a 24 VDC supply. Check that the external power supply provides this voltage.
The tolerance of the supply voltage must comply with the technical details. Safe operation cannot be guaranteed outside this range.
Protect the external power supply by fitting a fuse between the external power supply and the product. The size of the fuse will depend on the specification of the external power sup­ply, the conductor cross section and on local regulations.
WARNING!
Risk of electrocution!
Safe electrical isolation must be ensured for the external power supply that generates the supply voltage. Failure to do so could result in electric shock.
The power supplies must comply with EN 60950-1:2006/A11:2009, EN 61558-2-6:11/1997.
WARNING!
Risk of electrocution!
When voltage is applied, contact with live components could result in seri­ous or even fatal injury from an electric shock.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
15

Function description

4
4.1
Function description

Operation

The Gateway
} operates as a protocol converter between Modbus/TCP and EtherCAT,
} operates on the Modbus/TCP side as connection Server and on the EtherCAT-side as
Slave,
} Uses an LED to indicate whether there is data traffic via the connection
} Uses an LED to indicate the interface used for this data traffic
} If the connection to EtherCAT or to Modbus/TCP is no longer available, the payload is
retained with the current values
} is exclusively designed for exchanging non-safety-related data
The Gateway is interposed in the data flow between the connected devices.
4.1.1
Protocol conversion, Modbus/TCP to EtherCAT
} Signal path from EtherCAT Master to Modbus/TCP interface
EtherCAT Master
-> Data input/output Modbus/TCP interface
} Signal path from Modbus/TCP-enabled product to EtherCAT Master:
Modbus/TCP
-> EtherCAT output X2 on the Gateway -> EtherCAT-Master
-> EtherCAT input X1 on the Gateway -> Protocol conversion
-> Modbus/TCP
-> Data input/output Modbus/TCP interface -> Protocol conversion

Block diagram

2x EtherCAT
24 V
0 V
Power
Modbus/TCP
Mapping
Block diagram
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
16
Function description
4.2
4.2.1

Modbus/TCP

The Gateway can manage a max. of 8 Modbus/TCP connections. The Gateway is always the connection Server. The connection Clients may be various devices, e.g. PC, control system, display unit. They can access the Gateway simultaneously.
Port number "502" in the Gateway is set as the default for data exchange via a Modbus/ TCP connection.

Modbus/TCP data ranges (Server connections)

The product supports the following Modbus/TCP data areas:
Data area Modbus syntax Example
Coils (Bit) 0x00000 … 0x65535 [read/write]
Discrete Inputs (Bit) 1x00000 … 1x65535 [read only]
Input Register (Wort/16 Bits) 3x00000 … 3x65535 [read only]
0x[xxxxx] 0x00031
1x[xxxxx] 1x08193
3x[xxxxx] 3x00002
4.2.2
Holding Register (Wort/16 Bits) 4x00000 … 4x65535 [read/write]
Modbus/TCP data areas
Information
Addressing for Pilz systems starts at "0". On devices from other manufactur­ers, addressing may start at "1".
Please refer to the operating manual provided by the relevant manufacturer.
4x[xxxxx] 4x00805

Data transfer limits

This table contains the maximum data lengths supported per telegram:
Data transfer Max. data length per tele-
gram
Read data (Bit) FC 01 (Read Coils) 1 … 2000
FC 02 (Read Discrete In­puts)
Read data (Word) FC 03 (Read Holding Regis-
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
1 … 125
ters)
FC 04 (Read Input Register)
17
Function description
Data transfer Max. data length per tele-
Write data (Bit) FC 05 (Write Single Coil) 1 Bit
gram
FC 15 (Write Multiple Coils) 1 … 1968
4.2.3
Write data (Word) FC 06 (Write Single Regis-
1 Word
ter)
FC 16 (Write Multiple Regis-
1 … 123 Words
ters)
Read and write data (Word) FC 23 (Read/Write Multiple
Registers)
Data transfer limits
Read 1 … 125 Words Write 1 … 121 Words
Information
There may be some restrictions in data length, depending on the device that is used. Please refer to the information stated in the operating manual of the relevant unit.

Function codes (Client connections)

The connection Client can access the Gateway's data areas using the following function codes (FC):
Data area Modbus syntax Example
FC 01 Read Coils The connection Client reads
bit data from the connection Server, data length = 1 Bit, content, content: input/output data (data received from 0x)
FC 02 Read Discrete Input The connection Client reads
FC 03 Read Holding Register The connection Client reads
FC 04 Read Input Register The connection Client reads
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
bit data from the connection Server, data length = 1 Bit, content, content: input/output data (data received from 1x)
word data from the connec­tion Server, data length = 1 Word, content: diagnostic word (data received from 4x)
word data from the connec­tion Server, data length = 1 Word, content: diagnostic word (data received from 3x)
18
Function description
Data area Modbus syntax Example
FC 05 Write Single Coil The connection Client writes
FC 06 Write Single Register The connection Client writes
FC 15 Write Multiple Coils The connection Client writes
to one bit datum in the con­nection Server, data length = 1 Bit, content: input data (send data to 0x)
to one word datum in the connection Server, data length = 1 Word, content: input data (send data to 4x)
to multiple bit data in the connection Server, data length = 1 Bit, content: input data (send data to 0x)
4.3
FC 16 Write Multiple Registers The connection Client writes
to multiple word data in the connection Server, data length = 1 Word, content: input data (send data to 4x)
FC 23 Read/Write Multiple Regis-
ters
The connection Client reads and writes multiple word data within a telegram (receive data from 3x and send data to 4x)

EtherCAT

The manufacturer's ID, the device ID and any functions supported by a field device are de­fined in a device description file. The device description file (Electronic Data Sheet, EDS) is fieldbus-dependent. The content and format of a device description file are specified in the fieldbus standard. The file is needed in order to include an unknown field device in the re­spective fieldbus configuration tool and in order to configure the plant-specific require­ments.
An EDS file in XML format is used for EtherCAT devices.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
19
Function description
4.4
4.4.1

Translation tables

Only Register 4x is represented in the tables. The same assignment applies for Registers 0x, 1x, and 3x.

Payload

EtherCAT Modbus
SDO
Subindex
PDO Index Index
RxPDO 0x1600 2000 1 4x00001 Low Byte
TxPDO 0x1A2 2002 1 4x00129 Low Byte
(hex) Register Byte
2 High Byte
3 4x00002 Low Byte
4 High Byte
5 … 20 4x00003 …
4x00016
2 High Byte
Low Byte High Byte
4.4.2
3 4x00130 Low Byte
4 High Byte
5 … 20 4x00133 …
4x00144
Key to abbreviations:
TxPDO: Transmit Process Data Object
RxPDO: Receive Process Data Object
Low Byte High Byte

Diagnostic data

EtherCAT Byte Modbus Register Access type Meaning in EtherCAT
200a:001 4x01001 Low Byte RO IP address (Modbus), HL Byte
200a:002 High Byte RO IP address (Modbus), HH Byte
200a:003 4x01002 Low Byte RO IP address (Modbus), LL Byte
200a:004 High Byte RO IP address (Modbus), LH Byte
200a:005 4x01003 Low Byte RO Subnet Mask (Modbus), HL Byte
200a:006 High Byte RO Subnet Mask (Modbus), HH Byte
200a:007 4x01004 Low Byte RO Subnet Mask (Modbus), LL Byte
200a:008 High Byte RO Subnet Mask (Modbus), LH Byte
200a:009 4x01005 Low Byte RO Gateway (Modbus), HL Byte
200a:010 High Byte RO Gateway (Modbus), HH Byte
200a:011 4x01006 Low Byte RO Gateway (Modbus), LL Byte
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
20
Function description
EtherCAT Byte Modbus Register Access type Meaning in EtherCAT
200a:012 High Byte RO Gateway (Modbus), LH Byte
200a:013 4x01007 Low Byte RO DHCP activated (Modbus)
200a:014 High Byte RO Reserved
200a:015 4x01008 Low Byte RO Max. number of Modbus connec-
200a:016 High Byte RO Reserved
200a:017 4x01009 Low Byte RO Current number of Modbus con-
200a:018 High Byte RO Reserved
200a:019 4x01010 Low Byte RO Modbus Port Number, L Byte, (de-
200a:020 High Byte RO Modbus Port Number, H Byte,
200a:021 4x01011 Low Byte RO Keep Alive Time of Modbus con-
tions
nections
fault: 502)
(default: 502)
nections in ms, L Byte, (default:
32000)
200a:022 High Byte RO Keep Alive Time of Modbus con-
nections in ms, H Byte, (default:
32000)
200a:023 4x01012 Low Byte RO Reserved
200a:024 High Byte RO Reserved
200a:025 4x01013 Low Byte RO Reserved
200a:026 High Byte RO Reserved
200a:027 4x01014 Low Byte RO Reserved
200a:028 High Byte RO Reserved
200a:029 4x01015 Low Byte RO Reserved
200a:030 High Byte RO Reserved
200a:031 4x01016 Low Byte RO Reserved
200a:032 High Byte RO Reserved
200a:033 4x01017 Low Byte RO Reserved
200a:034 High Byte RO Reserved
200a:035 4x01018 Low Byte RO Reserved
200a:036 High Byte RO Reserved
200a:037 4x01019 Low Byte RO Reserved
200a:038 High Byte RO Reserved
200a:039 4x01020 Low Byte RO EtherCAT Address
200a:040 High Byte RO EtherCAT Address
200a:041 4x01021 Low Byte RO EtherCAT Alias
200a:042 High Byte RO EtherCAT Alias
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
21
Function description
EtherCAT Byte Modbus Register Access type Meaning in EtherCAT
200a:043 4x01022 Low Byte RO
200a:044 High Byte RO Reserved
200a:045 4x01023 Low Byte RO
EtherCAT Link State Port 0
} Upper nibble: Loop state
– 1 = Loop closed
– 2 = Loop open
} Lower nibble: Link state
– 0 = No Link
– 1 = Link
e.g.: 0x10 = No link, Loop closed, 0x21 = Link, Loop open
EtherCAT Link State Port 1
} Upper nibble: Loop state
– 1 = Loop closed
– 2 = Loop open
} Lower nibble: Link state
– 0 = No Link
– 1 = Link
e.g.: 0x10 = No link, Loop closed, 0x21 = Link, Loop open
200a:046 High Byte RO Reserved
200a:047 4x01024 Low Byte RO
EtherCAT RUN State (LED ECAT­Stat)
} 0 = LED off
} 1 = Init
} 2 = Pre-Operational
} 4 = Safe-Operational
} 8 = Operational)
Key to LED statuses Display ele-
ments for device diagnostics [ 33]
200a:048 High Byte RO Reserved
200a:049 4x01025 Low Byte RO
EtherCAT ERR State (LED ECAT­Stat)
} 0 = LED off (No Error)
} 1 = LED on (Error)
Key to LED statuses Display ele-
ments for device diagnostics [ 33]
200a:050 High Byte RO Reserved
RO = Read Only
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
22
Function description
4.5

Interfaces

The Gateway has two EtherCAT interfaces and a Modbus/TCP interface to
} Receive data from the EtherCAT interface,
} Receive data from the Modbus/TCP interface,
} Send the translated data to the EtherCAT interface or to the Modbus/TCP interface.
– The Modbus/TCP data is translated for EtherCAT using the mapping table; the
same applies with the EtherCAT data for Modbus/TCP.
The connection to EtherCAT-enabled devices is made via the two 8-pin RJ45 sockets.
Information on displaying the downloaded fieldbus data and on configuration and manage-
ment of the Gateway can be found under Web server [
33].
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
23

Installation

5
5.1
Installation

General installation guidelines

} The Gateway should be installed in a single mounting area with a protection type of at
least IP54.
} Fit the Gateway to a horizontal mounting rail. The venting slots must face upwards and
downwards. Other mounting positions could destroy the device.
} Use the locking elements on the rear of the unit to attach it to a mounting rail.
} In environments exposed to heavy vibration, the unit should be secured against lateral
movement by using a fixing element (e.g. retaining bracket or end angle).
} The ambient temperature of the devices in the control cabinet must not exceed the fig-
ure stated in the technical details, otherwise air conditioning will be required.
} To comply with EMC requirements, the mounting rail must have a low impedance con-
nection to the control cabinet housing.
} Push the unit upwards or downwards before lifting it from the mounting rail.
} The description below assumes that the mounting rail is already installed.
CAUTION!
Damage due to electrostatic charging! Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive surface or by wearing an earthed armband.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
24
Installation
5.1.1

Dimensions

96 (3,78“)
128
1 2 4
8 16 32 64
110,4 (4,35“)
IP-Address
22,5 (0,88“)
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
25
Installation
5.2

Mounting distances

When installing the device in the control cabinet / mounting space it is essential to maintain a certain distance from the top and bottom, as well as to other heat-producing devices (see diagram). The values stated for the mounting distances are minimum specifications.
30 mm (1.81“)
20 mm (0.787“)
20 mm (0.787“)
5.3
Control cabinet wall / heat-producing device
30 mm (1.81“)
Mounting distances
Control cabinet wall / heat-producing device

Supply voltage

The Gateway requires a 24 VDC supply.
To achieve the lowest possible residual ripple (≤ 5%), we recommend that you install a
three-phase bridge rectifier or regulated supply.
Protect the external power supply by fitting a fuse between the external power supply and the control system. The size of the fuse will depend on the specification of the external power supply, the conductor cross section and on local and national regulations.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
26
Installation
5.4

Install Gateway

Use the locking elements on the rear of the product to attach it to a mounting rail.
1. Guide the product straight on to the mounting rail, so that the locking elements click into place.
2. Push the product back as far as it will go.
3. Make sure that the locking mechanisms click into position, connecting the product firmly into the mounting rail.
[2]
Install Gateway on top hat rail
[1]
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
27

Commissioning

6
6.1
Commissioning

General wiring guidelines

Please note:
} Information given in the "Technical details" must be followed.
} Max. continuous current that the external power supply must provide: 160 mA
} Use copper wiring that can withstand temperatures of up to 75 °C.
} Always connect the mounting rail to the functional earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.
} Separate the supply voltage cable from the analogue input current lines.
} For transducers located outside the control cabinet: Where the cable enters the control
cabinet, the cable shield must be connected to the earth potential over a wide surface area and with low impedance (connect in star).
} The power supply must meet the regulations for extra low voltages with safe separation.
Information
Only connect and disconnect the Gateway when the supply voltage is switched off.
6.2
6.2.1
Please note the following when connecting the interfaces:
} The following minimum requirements of the connection cable and connector must be
met:
– Only use standard industrial Ethernet cable and connectors.
– Only use double-shielded twisted pair cable and shielded RJ45 connectors (indus-
trial connectors).
– Only use 100BaseTX cable in accordance with the Ethernet standard (min. Catego-
ry 5)
} Measures to protect against interference:
– Ensure the requirements for the industrial use of EtherCAT are met, as stated in
the Installation Manual published by the User Group.

Wiring the units

Cable requirements

Screw terminals:
} Minimum conductor cross section on field connection terminals = 0.25 mm
} Maximum conductor cross section on field connection terminals for the functional earth
= 2.5 mm
} Torque setting with screw terminals: 0.50 Nm.
2
(AWG12),
2
(AWG24),
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
28
Commissioning
34
Spring-loaded terminals:
} Minimum conductor cross section on field connection terminals = 0.2 mm
} Maximum conductor cross section on field connection terminals = 2.5 mm
} Terminal points per connection: 2,
} Stripping length: 9 mm.
2
(AWG24),
2
(AWG12),
6.2.2
6.3
6.4

Terminals

The plug-in terminals for the inputs and outputs are not supplied with the system. You can select between spring-loaded terminals and a screw connection.

Terminal configuration

Module supply Terminal configuration X4
4-pin female connec­tor
Terminal configuration
1 +24 V infeed for module supply
2 0 V infeed for module supply
3 Not connected
4 Functional earth
12

Interfaces

The following minimum requirements must be met:
} Ethernet standards (min. Category 5) 100BaseTX
} Double-shielded twisted pair cable for industrial Ethernet use
} Shielded RJ45 connectors (industrial connectors)
6.4.1
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02

RJ45 interface

RJ45 socket, 8-pin PIN Standard Crossover
Interface assignment of RJ45 socket
n.c. = not connected

1 TD+ (Transmit+) RD+ (Receive+)
2 TD- (Transmit-) RD- (Receive-)
3 RD+ (Receive+) TD+ (Transmit+)
4 n.c. n.c.
5 n.c. n.c.
6 RD- (Receive-) TD- (Transmit-)
7 n.c. n.c.
8 n.c. n.c.
29
Commissioning
6.4.1.1
RJ45 connection cable
RJ45 connection cable
: RJ45 connector, 8-pin
: 100BaseTX cable, max 100 m length
CAUTION!
With the plug in connection please note that the data cable and connector have a limited mechanical load capacity. Appropriate design measures should be used to ensure that the plug-in connection is insensitive to in­creased mechanical stress (e.g. through shock, vibration). Such measures include fixed routing with strain relief, for example.
6.5
6.5.1

Address setting

IP address setting

The first three bytes of the IP address are: 192.168.0. The last byte of the IP address can be configured.
The subnet mask is: 255.255.255.0.
The last byte of the IP address is configured using the DIP switches. Value range: 1 ...255.
Information
The IP address should only be set when the module is switched off (no volt­age applied).
The settings are only transferred when booting. Any changes made to the settings during operation will not be transferred.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
30
Commissioning
There are various options for setting the last byte of the Gateway's IP address.
1. Use of the DHCP Server is enabled
DHCP is automatically enabled on a new module. In this case the IP address is taken
from the DHCP Server, if the DIP switch is set to 0. The module waits for approx. 15 seconds to receive an address from a DHCP Server, in which time it uses the default IP address 192.168.0.1.
– Set the DIP switch to 0.
2. Setting via the DIP switch
The IP address that is set at the DIP switch is used. DHCP is therefore disabled.
– Set the DIP switch to a value between 1 – 254.
3. Enable DHCP via DIP switch
If the DIP switch is set to 255, DHCP is always used, irrespective of the configuration in
the web server.
– Set the DIP switch to 255.
Example: DIP switch: 00010100 (20 decimal)
1 2 3 4 5 6 7 8
ON
(MSB) (LSB)
DIP switch setting: 20 (decimal) as the value for the last byte of the IP address
DIP switch
"IP address"
Meaning Example:
IP address 020
OFF ON
1 0 128
2 0 64
3 0 32
4 0 16
5 0 8
6 0 4
7 0 2
8 0 1
DIP switch IP address
D
D
D
D
D
D
D
D
D
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
31

Operation

1
2
3
7
7.1
7.1.1
Operation

Display elements

Status LEDs on the front provide information on the module's activity.
LED on
LED flashes
LED flashes briefly
LED flashes once periodically
LED flashes twice periodically
LED flashes tree times periodically
LED off
LED display symbols

Display elements for device diagnostics

LED LED status Meaning
Pwr/Stat
LED LED status Meaning
Link/Trf
Green Fault-free operation
Red Internal error (module error) or IP address
conflict
No supply voltage or device is defective
Green Link present, 100 Mbit/s
Green Traffic present, 100 Mbit/s
Red Max. 15 sec. after power-up: Still waiting
for answer from DHCP Server. After more than 15 sec.: The default IP ad­dress 192.168.0.1 is already used in the network. In this case the module cannot be reached via Ethernet.
Red No Modbus/TCP connection
Red Incorrect Register range (during Client re-
quest)
Orange Link present, 10 Mbit/s
Orange Traffic present, 10 Mbit/s
No link
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
32
Operation
1
1
2
LED status
LED
ECATStat
1)
MeaningGreen Red
Gateway in "OPERATIONAL" status
Gateway in "SAFE-OPERATIONAL" status
Gateway in "PRE-OPERATIONAL" status
No supply voltage or Gateway is in the "INIT" state
A critical error or an error in the application has occurred
Status of the Gateway has been changed by an error in an application
A watchdog timeout has occurred in the application
Configuration error or error in the register data or object data
Fault-free operation
1)
In certain situations the LED ECATStat alternates red and green.
7.2
7.2.1
LED LED status Meaning
Link/Act In
Green Bus connection present at X1
Green Data traffic present at X1
No bus connection present at X1
Link/Act Out
Green Bus connection present at X2
Green Data traffic present at X2
No bus connection present at X2

Web server

A web server is implemented within the Gateway; it is started once the Gateway is connect­ed to the supply voltage.
The web server is intended for use with Internet Explorer or Firefox.
Make sure that Javascript and Cookies are enabled in your browser's security settings.

Password management

} For access to the web server, two users have been preset in its delivery condition.
Users Access type Password
User Read access only 1111
User Read and write access 0000
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
33
Operation
} Access without a password is not possible.
} User names and passwords can be changed.
} If the password is changed and the new password is forgotten, you have no longer the
option to access the web server via the gateway. In this case, the gateway has to be sent to Pilz and reset to the original delivery status. Thereby all settings will be lost. Ensure that the (new) password is saved reliably once the password has been changed.
} Ensure that the configuration with the passwords of the delivery status is saved before
changing the passwords.
1. Call up the web server.
2. Copy these files to a PC using FTP:
– eth_cfg.xml (Ethernet configuration),
– password.xml (user definition).
7.2.2
7.3

Call web server

1. Connect the Gateway to the PC.
2. Call up the following HTML page:
http://192.168.0.xxx
– For xxx, enter the value that you have set as the last byte of the IP address.
3. Enter the user name and password correctly and log on to the web server.
4. Select the option you require from the options in the overview and then follow the in­structions.

Exchange Gateway

When exchanging the Gateway, the current configuration should be saved first, so that the configuration can be imported into the new Gateway.
Recommended procedure:
1. Call up the web server and save the configuration.
– Copy these files to a PC using FTP:
eth_cfg.xml (Ethernet configuration),
password.xml (user definition).
2. Switch off the supply voltage.
3. Disconnect all cables from the Gateway.
4. Remove the Gateway from the mounting rail.
5. Install the new Gateway in accordance with the Installation Manual, Installation [
6. Incorporate the Gateway into the network, Address setting [
– Make sure that the settings for the IP address are exactly the same as they were on
the old module.
7. Copy the configuration data to the new Gateway via FTP.
8. Restart the Gateway via the web server.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
24].
30].
34

Technical Details

8
General 311601
Approvals CE, GOST, cULus Listed Content of QR code http://www.pilz.com/QR311601
Electrical data 311601
Supply voltage
for Module supply Voltage 24 V Type DC Output of external power supply (DC) 3,0 W
Status indicator LED
Fieldbus interface 311601
Fieldbus interface EtherCAT Unit type Slave Protocol CANopen over EtherCAT Maximum data length of the fieldbus interface
Input 512 Byte Output 512 Byte
Input/output combined 512 Byte Transmission rates 100 MBit/s Connection RJ45 Operating modes Auto-MDIX Galvanic isolation Yes Type of galvan. isolation Functional insulation
MODBUS 311601
Number of MODBUS connections 8 Connection type RJ45 Device type Server Permitted address range MODBUS/TCP port 1 - 65535 Operating mode Auto-MDIX, Autonegotiation Default port MODBUS/TCP 502 Transmission rates 10 MBit/s, 100 MBit/s Galvanic isolation Yes
Times 311601
Supply interruption before de-energisation 20 ms Keep alive time default value 32000 ms
Environmental data 311601
Ambient temperature
In accordance with the standard EN 60068-2-14
Temperature range 0 - 60 °C Storage temperature
In accordance with the standard EN 60068-2-1/-2
Temperature range -25 - 70 °C
Technical Details
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
35
Technical Details
Environmental data 311601
Climatic suitability
In accordance with the standard EN 60068-2-30, EN 60068-2-78
Humidity 93 % r. h. at 40 °C Condensation Not permitted EMC EN 61131-2 Vibration
In accordance with the standard EN 60068-2-6
Frequency 5,0 - 150,0 Hz
Max. acceleration 1g Shock stress
In accordance with the standard EN 60068-2-27
Acceleration 15g
Duration 11 ms Max. operating height above sea level 2000 m Airgap creepage
In accordance with the standard EN 61131-2
Overvoltage category II Protection type
In accordance with the standard EN 60529
Mounting (e.g. cabinet) IP54
Housing IP20
Terminals IP20
Potential isolation 311601
Potential isolation between EtherCAT and system voltage Type of potential isolation Functional insulation Rated surge voltage 500 V Potential isolation between MODBUS and system voltage Type of potential isolation Functional insulation Rated surge voltage 500 V
Mechanical data 311601
DIN rail
Top hat rail 35 x 7,5 EN 50022 Material
Bottom PC
Front PC Cross section of external conductors with screw ter-
minals
1 core flexible 0,25 - 2,50 mm², 24 - 12 AWG
2 core with the same cross section, flexible with
0,20 - 1,50 mm², 24 - 16 AWG
crimp connectors, no plastic sleeve
2 core with the same cross section, flexible without
0,20 - 1,50 mm², 24 - 16 AWG
crimp connectors or with TWIN crimp connectors Torque setting with screw terminals 0,50 Nm Connection type Spring-loaded terminal, plug in; Screw terminal,
plug in
Cross section of external conductors with spring-load-
0,20 - 2,50 mm², 24 - 12 AWG
ed terminals: flexible with/without crimp connector
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
36
Technical Details
Mechanical data 311601
Spring-loaded terminals: Terminal points per connec-
2
tion Stripping length 9 mm Dimensions
Height 96,0 mm
Width 22,5 mm
Depth 110,4 mm Weight 90 g
The standards current on 2012-10 apply.
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
37

Order reference

9
Order reference
Product type Features Order no.
PSSnet GW1 MOD-Ether­CAT
Order reference: Acces­sories
Product type Features Order no.
Set spring terminals 1 set of spring-loaded terminals 783 542
Set screw terminals 1 set of screw terminals 793 542
Order reference
Communication module for connection to EtherCAT 311 601
Operating Manual PSSnet GW1 MOD-EtherCAT 1002692-EN-02
38
© Pilz GmbH & Co. KG, 2011
of the equipment. We accept no responsibility for the validity, accuracy and entirety of the text and graphics presented in this information. Please contact our Te chnical Support if you have any questions.
Back cover
Sachnummer Printed in Germany
1002692-EN-02, 2013-06 Printed in Germany
© Pilz GmbH & Co. KG, 2011
...
In many countries we are represented by our subsidiaries and sales partners.
Please refer to our homepage for further details or contact our headquarters.
Technical support
+49 711 3409-444 support@pilz.com
are registered and protected trademarks
®
, the spirit of safety
®
, SafetyNET p
®
, SafetyEYE
®
, SafetyBUS p
®
, PVIS
®
, PSS
®
, PSEN
®
, Primo
®
, PNOZ
®
, PMI
®
Pilz GmbH & Co. KG Felix-Wankel-Straße 2 73760 Ostfildern, Germany Telephone: +49 711 3409-0 Telefax: +49 711 3409-133 E-Mail: pilz.gmbh@pilz.de Internet: www.pilz.com
, PMCprotego
®
, PIT
®
, Pilz
®
of Pilz GmbH & Co. KG in some countries. We would point out that product features may vary from the details stated in this document, depending on the status at the time of publication and the scope
InduraNET p
Loading...