Magnetic safety switches for monitoring the position of movable guards in
accordance with EN 60947-5-3
Approvals
PSEN 1.2p-23
Unit features
` The actuator PSEN 1,2-20 belongs
to the safety switch
` 2 reed contacts (N/O)
` Assured operating distance: 8 mm
` Assured release distance: 26 mm
` Round design
` Works magnetically
` Switching voltage 24 VDC
Unit description
The safety switch meets the requirements of EN 60204-1 and IEC 60204-
1.
The safety switch is approved for use
in potentially explosive atmospheres in
accordance with EN 50021, Ex area
Category 3, Zone 2 (gas) and 22 (dust),
(II 3GD EEx nC IIC T6).
The safety switch only complies with
EN 60947-5-3 in conjunction with the
actuator PSEN 1,2-20 and its approved evaluation devices.
The safety switch should only be connected to the evaluation devices listed
under "Connections".
Function description
If the actuator is within the response
range, the magnets switch the reed
contacts on the safety switch. If the
actuator is outside the response range
(safety gate open), the reed contacts
on the safety switch will switch.
energisation contacts satisfy the
requirements of category 3 in accordance with EN 954-1 and the
requirements of a PDF with single-fault tolerance (PDF-S).
–Delay time ≥ 30 s: Delay-on de-
energisation contacts satisfy the
requirements of Category 1 in
accordance with EN 954-1 and
the requirements of a PDF with
designed reliability (PDF-D).
Schaltabstand/Operating distance/
Schaltabstand/Operating distance/
Schaltabstand/Operating distance/
Schaltabstand/Operating distance/
Schaltabstand/Operating distance/
s
s
s
s
s
= 26
= 26
= 26
= 26
= 26
ar
ar
ar
ar
ar
s
s
s
s
s
= 8
= 8
= 8
= 8
= 8
ao
ao
ao
ao
ao
s
s
s
s
s
= 0,5
= 0,5
= 0,5
= 0,5
= 0,5
omin
omin
omin
omin
omin
Portee de travail
Portee de travail
Portee de travail
Portee de travail
Portee de travail
Ein/On/Marche
Ein/On/Marche
Ein/On/Marche
Ein/On/Marche
Ein/On/Marche
Aus/Off/Arrêt
Aus/Off/Arrêt
Aus/Off/Arrêt
Aus/Off/Arrêt
Aus/Off/Arrêt
` In the following commissioning cas-
es, check the function that detects
shorts across contacts:
– On evaluation devices with DC
supply voltage: Overall cable resistance ≥ 15 Ohms per channel
– On evaluation devices with AC
supply voltage: Overall cable resistance ≥ 25 Ohms per channel
– For details of how to perform the
test for shorts across the contacts, please refer to the operating manual for the relevant
evaluation device.
Connections
NOTICE
The colour marking for the connection
lead only applies for the cable that Pilz
supplies as an accessory.
The safety switch is shown in an unoperated condition.
2.2
Belegung des 4-pol. M8Stiftsteckers/Assignment
of the 4-pin M8 male connector/Repérage du connecteur mâle M8 à 4 pôles
sition. However, the safety switch
and actuator must be installed so
that the two notches are exactly opposite each other (see diagram:
"Operating distances").
` A nib on the actuator prevents it
twisting (see diagram: "Dimensions"). Drill diameter: 2 mm.
` If possible, do not install the safety
switch and actuator on to ferromagnetic material. Changes to the operating distances are to be expected.
` The torque setting for the M30 nuts
is max. 300 Ncm.
` The actuator should be secured us-
ing an M4 or M5 screw made of
non-magnetic material (e.g. Messing).
` The distance between two systems
comprising safety switch and actuator must be at least 25 mm.
` Safety switch and actuator
– Keep away from iron swarf
– Do not expose to strong mag-
netic fields
– Do not expose to heavy shock or
vibration
– Do not use as a limit stop
Adjustment
` The safety switch may only be used
with the corresponding actuator
PSEN 1,2-20.
` Always test the function with one of
the approved evaluation devices.
` The stated operating distances (see
Technical details) only apply when
the safety switch and actuator are
installed facing each other in parallel. Switching distances may deviate if other arrangements are used.
Note the maximum permitted lateral and vertical offset (see "Operating distances" and "Max. lateral
and vertical offset").
This data sheet is only intended for use
during configuration. For installation
and operation, please refer to the operating instructions supplied with the
unit.
Dimensions
Safety switch
SW36
28
M30x1,5
6,7
Actuator
Kerben oben
Indentations on top
Encoches vers le haut
4
29
36
1,75
30
M8x1
7
2.2
5,5
14
Technical details
ATEX categoryII 3GD EEx nC IIC T6
Switching distances
Assured operating distance S
Min. operating distance S
Assured release distance S
Switching voltage24 V
Max. switching current for reed contacts0.50 A
Max. breaking capacity for reed contacts10.0 W
Max. switch frequency1 Hz
ActuatorPSEN 1,2-20
Ambient temperature-10 - 55 °C
Vibration to EN 60947-5-2
Frequency10 - 55 Hz
Amplitude1.00 mm
Shock stress30 g , 11 ms
Connection typeM8
CableLiYY 4 x 0,25 mm
Protection typeIP65, IP67
Housing materialPBT