Pilz P1W03 Data Sheet

Electronic Monitoring Relays
True power monitoring
P1W03
Technical Details P1W03
Electrical data
Supply voltage Tolerance 85 ... 110 % Frequency range 50 ... 60 Hz Power consumption Approx. 4 VA
Output circuit
Motor operation: Output voltage Terminating impedance > 1 kW Output current DC: 0 ... 20 mA or 4 ... 20 mA Terminating impedance < 0.5 kW Generator operation: Output voltage Terminating impedance > 2 kW
True power converter for 1 and 3-phase power supplies with analogue true value output
Features
with a 2.2 kW (400 V) rating
For frequencies up to 200 Hz
Analogue output 0 ... 20 mA
or 4 ... 20 mA or 0 ... 10 V and 10 ... 0 V
2-phase current measurement
(Aron wiring principle)
Offset compensation
Amplification factor
Short reaction times
Suitable for current transformers
Suitable for frequency-regulated
drives
Output current DC: 0 ... -10 mA Terminal impedance < 0.5 kW
Measuring circuit
Measuring voltage 3AC: 24, 42, 48, 110, 120, 230, 240,
Tolerance 85 ... 110 % Frequency range 30 ... 200 Hz Adjustable measuring range limit values 1 A version: 0.2; 0.4; 0.6; 0.8; 1 A
Max. overload 1 A version: 1.2 A; 6 A/max. 3 s
Reaction time Approx. 50 ms (when 63% change in
Start-up suppression time 0.5 ... 20 s adjustable Requirements for current transformer 1 A version: 1.5 ... 7.5 VA, Class 3
Mechanical data
Max. cross section of external conductor 2 x 2.5 mm
Torque setting for connection terminals 1.2 Nm (screws) Dimensions (H x W x D) 75 x 90 x 110 mm Weight 460 g
1 AC: 24, 42, 48, 110, 120, 230, 240, 400 V
DC: 0 ... 10 V or 10 ... 0 V
DC: 0 ... -10 V
400, 415, 440, 460, 500, 550 V
5 A version: 1, 2, 3, 4, 5 A
5 A version: 6 A; 25 A/max. 3 s
output voltage occurs)
4
5A version: 2.5 ... 15 VA, Class 3
2
Single-core or multi-core with crimp connector
Description
The true power monitor is enclosed in a 90 mm wide P-75 housing. A three-phase AC current and a single phase control voltage is required for operation. Features:
2 versions, each with 5 adjustable
measuring ranges up to max. 1 A or up to max. 5 A
Adjustable amplification factor via
potentiometer: 0 ... 10
Offset correction via
potentiometer: 0 ... 10 V
Adjustable start-up suppression
time
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-238-07/00 Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de
LED for supply voltage
P1W03 measures the load current of the motor. The unit calculates the true power from the size of the load and the supply voltage and applies a signal proportional to true power to the outputs. One current, one voltage and an inverse voltage output are available. P1W03 is suitable for measuring frequency-controlled motors. The output signal is only proportional to the power if the frequency is constant.
Electronic Monitoring Relays
True power monitoring
P1W03
Internal wiring diagram
4
k1 k3
I
M1IM3
U/I1 W/I3
, IM3 Measuring currents
I
M1
n Measuring range factor U
Measuring voltages
L1... L3
cos j Power factor
L1 L2 L3 A2A1
n*I
M3
n*I
M1
Timing diagram
Generator operation
Power supply
Multiplexer voltage
Multiplexer current
10 V 20 mA
+
0
-
U
L1, L2, L3
I
= I
M1, M3
Start-up suppression time
t
a
x Amplification factor
x
= U
cos j*k
U*I
M
M
*
t
a
PWTrue power DP Offset
U
A
"x"
U
A
I
A
"x"
DP
P
W
-DP
P
W
&
U
I
P
A
U
U
A
N U
U
A
I
I
A
UAOutput voltage
UAInverse output voltage I
Output current
A
10 V 20 mA
"x"
U
A
I
A
-P
max
UAOutput voltage IAOutput current
P
P
max
Motor operation
-10 mA
U
A
-20 V
W
P
Motor operation
max
P
W
IAOutput current 4 ... 20 mA
UAInverse output voltage
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-238-07/00 Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de