Datasheet UB1000-18GM75-I-V15 DataSheet (Pepperl Fuchs)

Ultrasonic sensor UB1000-18GM75-I-V15
Technical data
General specifications
Sensing range 70 ... 1000 mm Adjustment range 90 ... 1000 mm Dead band 0 ... 70 mm Standard target plate 100 mm x 100 mm Transducer frequency approx. 255 kHz Response delay approx. 125 ms
Indicators/operating means
Model Number
UB1000-18GM75-I-V15
Single head system
Features
•Analog output 4mA...20mA
• Measuring window adjustable
• Selectable sound lobe width
•Program input
• Synchronization options
• Deactivation option
• Temperature compensation
• Very small unusable area
Diagrams
Characteristic response curve
Distance Y [mm]
250
flat surface 100 mm x 100 mm
200
150
100
5
0
-50
-100
-150
-200
round bar, Ø 25 mm
-250 0 200 400 600 800 1000 1200 1400 1600
Y
X
wide sound lobe narrow sound lobe
Distance X [mm]
LED yellow solid yellow: object in the evaluation range
LED red solid red: Error
Electrical specifications
Operating voltage U No-load supply current I
Input/Output
B
0
Synchronization 1 synchronous connection, bi-directional
Synchronization frequency
Common mode operation 40 Hz Multiplex operation 40 Hz /n, n = number of sensors
Input
Input type 1 program input
Output
Output type 1 analog output 4 ... 20 mA Resolution 0.35 mm Deviation of the characteristic curve ± 1 % of full-scale value Repeat accuracy ± 0.1 % of full-scale value Load impedance 0 ... 300 Ohm Temperature influence ± 1.5 % of full-scale value
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F) Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type Connector M12 x 1 , 5-pin Degree of protection IP67 Material
Housing brass, nickel-plated Transducer epoxy resin/hollow glass sphere mixture; foam polyurethane,
Mass 60 g
Factory settings
Output evaluation limit A1: 90 mm
Beam width wide
Compliance with standards and directives
Standard conformity
Standards EN 60947-5-2:2007 + A1:2012
Approvals and certificates
UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval CCC approval / marking not required for products rated 36 V
yellow, flashing: program function, object detected
red, flashing: program function, object not detected
10 ... 30 V DC , ripple 10 % 45 mA
0-level: -U 1-level: +4 V...+U input impedance: > 12 k synchronization pulse: 100 µs, synchronization interpulse
...+1 V
B
SS
B
period: 2 ms
lower evaluation limit A1: -U A2: +4 V ... +U input impedance: > 4.7 k, pulse duration: 1 s
B
... +1 V, upper evaluation limit
B
cover PBT
evaluation limit A2: 1000 mm output function: rising ramp
IEC 60947-5-2:2007 + A1:2012 EN 60947-5-7:2003 IEC 60947-5-7:2003
Release date: 2016-04-13 11:16 Date of issue: 2016-04-13 204535_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1
Ultrasonic sensor UB1000-18GM75-I-V15
Dimensions
LEDs
4
24
M12 x 1
M18 x 1
Additional Information
Programming the analog output mode
Rising ramp A1 < A2:
A1
Falling ramp A2 < A1:
A2
48
75
85
object range
A2
A1
Electrical Connection
Standard symbol/Connections:
(version I)
U
Core colours in accordance with EN 60947-5-2.
Pinout
Wire colors in accordance with EN 60947-5-2
1 BN 2 WH 3 BU 4 BK 5 GY
(BN)
1
(WH)
2
(GY)
5
(BK)
4
(BU)
3
2
+ U
B
Teaching input
Sync.
Analog output
- U
B
1
5
4
3
(brown) (white) (blue) (black) (gray)
Release date: 2016-04-13 11:16 Date of issue: 2016-04-13 204535_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Ultrasonic sensor UB1000-18GM75-I-V15
Accessories
UB-PROG2
Programming unit
OMH-04
Mounting aid for round steel ø 12 mm or sheet 1.5 mm ... 3 mm
BF 18
Mounting flange, 18 mm
BF 18-F
Mounting flange with dead stop, 18 mm
BF 5-30
Universal mounting bracket for cylindrical sensors with a diameter of 5 ... 30 mm
UVW90-K18
Ultrasonic -deflector
V15-G-2M-PVC
Female cordset, M12, 5-pin, PVC cable
M18K-VE
Description of Sensor Functions
Programming procedure
The sensor features a programmable analog output with two programmable evaluation boundaries. Programming the evaluation boundaries and the operating mode is done by applying the supply voltage -U input for at least 1 s. LEDs indicate whether the sensor has recognized the target during the programming procedure.
Note:
Evaluation boundaries may only be specified directly after Power on. A time lock secures the adjusted switching points against unintended mod­ification 5 minutes after Power on. To modify the evaluation boundaries later, the user may specify the desired values only after a new Power On.
Note:
If a programming adapter UB-PROG2 is used for the programming procedure, button A1 is assigned to -UB and button A2 is assigned to +UB.
Programming the analog output
Rising ramp
1. Place the target at the near end of the desired evaluation range
2. Program the evaluation boundary by applying -U
3. Disconnect the Teach-In input from -U
4. Place the target at the far end of the desired evaluation range
5. Program the evaluation boundary by applying +U
6. Disconnect the Teach-In input from +U
Falling ramp
1. Place the target at the far end of the desired evaluation range
2. Program the evaluation boundary by applying -U
3. Disconnect the Teach-In input from -U
4. Place the target at the near end of the desired evaluation range
5. Program the evaluation boundary by applying +U
6. Disconnect the Teach-In input from +U
B
B
B
B
B
to save the evaluation boundary
B
to save the evaluation boundary
B
to save the evaluation boundary
B
to save the evaluation boundary
Adjusting the sound cone characteristics:
The ultrasonic sensor enables two different shapes of the sound cone, a wide angle sound cone and a small angle sound cone.
or +UB to the Teach-In input. The supply voltage must be applied to the Teach-In
B
to the Teach-In input (yellow LED flashes)
to the Teach-In input (yellow LED flashes)
to the Teach-In input (yellow LED flashes)
to the Teach-In input (yellow LED flashes)
1. Small angle sound cone
• switch off the power supply
•connect the Teach-In input wire to -U
• switch on the power supply
• the red LED flashes once with a pause before the next.
• yellow LED: permanently on: indicates the presence of an object or disturbing object within the sens-
ing range
• disconnect the Teach-In input wire from -U
2. Wide angle sound cone
• switch off the power supply
•connect the Teach-In input wire with +U
• switch on the power supply
• the red LED double-flashes with a long pause before the next.
• yellow LED: permanently on: indicates an object or disturbing object within the sensing range
• disconnect the Teach-In input wire from +U
B
and the changing is saved
B
B
and the changing is saved
B
Factory settings
See technical data.
Display
The sensor provides LEDs to indicate various conditions.
Release date: 2016-04-13 11:16 Date of issue: 2016-04-13 204535_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
pause
pause
3
Ultrasonic sensor UB1000-18GM75-I-V15
During Normal operation
Proper operation
Object in evaluation range No object in evaluation range
Interference (e.g. compressed air)
During sensor programming
Object detected No object detected Object uncertain (programming invalid)
Red LED Yellow LED
Off Off On
Off
Flashes
On
Remains in previous state
On Off
Flashes
Off Off
Synchronization
This sensor features a synchronization input for suppressing ultrasonic mutual interference ("cross talk"). If this input is not connected, the sensor will operate using internally generated clock pulses. It can be synchronized by applying an external square wave. The pulse duration must be 100 µs. Each falling edge of the synchronization pulse triggers transmission of a single ultrasonic pulse. If the synchronization signal remains low for 1 second, the sensor will revert to normal operating mode. Normal operating mode can also be activated by opening the signal connection to the synchronization input (see note below). If the synchronization input goes to a high level for > 1 second, the sensor will switch to standby mode. In this mode, the outputs will remain in the last valid output state.
Note:
If the option for synchronization is not used, the synchronization input has to be connected to ground (0 V) or the sensor must be operated via a V1 cordset (4-pin). The synchronization function cannot be activated during programming mode and vice versa.
The following synchronization modes are possible:
1. Several sensors (max. number see technical data) can be synchronized together by interconnecting their respective synchronization inputs. In this case, each sensor alternately transmits ultrasonic pulses in a self multiplexing mode. No two sensors will transmit pulses at the same time (see note below).
2. Multiple sensors can be controlled by the same external synchronization signal. In this mode the sensors are triggered in parallel and are syn­chronized by a common external synchronization pulse.
3. A separate synchronization pulse can be sent to each individual sensor. In this mode the sensors operate in external multiplex mode (see note below).
4. A high level (+U
Note:
Sensor response times will increase proportionally to the number of sensors that are in the synchronization string. This is a result of the multiplex­ing of the ultrasonic transmit and receive signal and the resulting increase in the measurement cycle time.
) on the synchronization input switches the sensor to standby mode.
B
Installation conditions
If the sensor is installed at places, where the environment temperature can fall below 0 °C, for the sensors fixation, one of the mounting flanges BF18, BF18-F or BF 5-30 must be used. In case of direct mounting of the sensor in a through hole using the steel nuts, it has to be fixed at the middle of the housing thread. If a fixation at the front end of the threaded housing is required, plastic nuts with centering ring (accessories) must be used.
Release date: 2016-04-13 11:16 Date of issue: 2016-04-13 204535_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
4
Loading...