Pentax TDIAP502730, TDIAP520830, TDIAP521030 User Manual

TDIAP502730, TDIAP520830,
& TDIAP521030
Airflow Switches
SPECIFICATION DATA
FEATURES
• Models available with compression or barb fittings
• SPDT contacts on automatic reset models
• SPST n. c. contacts on manual reset models
• Electrical switch enclosed in metal box with cover
• Reliable pneumatic operation
• UL and CSA Listed, FM approved
• Adjustable setpoint
GENERAL
Airflow Differential Pressure Switches are used to sense positive, negative, or differential air pressure in HVAC systems. They provide high or low limit with alarm or high limit shutdown with manual reset.
Copyright © 1996 Honeywell Inc. • All Rights Reserved
77-4023-1
TDIAP502730, TDIAP520830, & TDIAP521030 AIRFLOW SWITCHES
DESCRIPTION
Airflow Differential Pressure Switches are used to sense positive, negative, or differential air pressure in HVAC systems. They provide high or low limit with alarm or high limit shutdown with manual reset.
SPECIFICATIONS
Models:
TDIAP502730: auto reset, compression fittings also
available as 14004866-001 for panel mounting
TDIAP520830: auto reset, barb fittingsTDIAP521030: compression fittings, manual reset
Setpoint:
TDIAP520830, TDIAP502730: Adjustable 0.05 to
12.0 in. wc (0.0018 to 2.98 kPa)
TDIAP521030: Adjustable 0.30 to 12.0 in. wc (0.0108
to 2.98 kPa)
Connections:
Electric:
Screw terminals with cup washers Knockout for 1/2-in. conduit
Pneumatic:
Compression fittings for 1/4-in. (6 mm) O.D. rigid or
semirigid tubing
Barb fittings for 1/4-in. (6 mm) O.D. polyethylene tubing
Switching Differential, Nonadjustable:
TDIAP520830, TDIAP502730: 0.02 ±0.01 in. wc (0.72
±0.36 Pa) at minimum setpoint to approximately
0.80 in. wc (0.029 kPa)at maximum setpoint. Normally open contacts close on a pressure rise above setpoint and normally closed contacts open on a pressure rise above setpoint.
TDIAP521030: 50% of setpoint at minimum setting to
2.5 in. wc at maximum setpoint. Contact opens on pressure rise above setpoint and remain open until pressure drops below setpoint plus differential and reset button is fully depressed.
Switching Action:
SPDT contacts on auto reset models. Normally open
contacts close on a pressure rise above setpoint and normally closed contacts open on a pressure rise above setpoint.
SPST normally closed on manual reset model, contact
opens on pressure rise above setpoint. Must be manually reset.
Maximum Differential Pressure:
0.5 psi, 13.85 in. wc, or 3.44 kPa
Electrical Rating:
TDIAP520830, TDIAP502730 and 14004866:
278 VA Pilot duty, 24V ac; 300 VA Pilot duty, 120 to 277V ac; 15A non-inductive to 277V ac maximum 10 mA at 5V dc (gold-flash contacts)
TDIAP521030:
20A resistive 125 to 277V ac 3/4 hp, 125V ac 1-1/2 hp, 250V ac 6000 cycles
Listings:
UL and CSA Listed FM approved
Operating Temperature:
–40 to 190F (–40 to 88C)
Mounting Position:
Diaphragm must be vertical with input connections down.
Dimensions in Inches (Millimeters):
5.55 (141)
TRIAP521030 ONLY
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis MN 55408-0524
Honeywell Latin American Division
Miami Lakes Headquarters 14505 Commerce Way Suite 500 Miami Lakes FL 33016
77-4023-1 Rev. 5-96
XX-XXXX
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 2C9
Honeywell Europe S.A.
3 Avenue du Bourget B-1140 Brussels Belgium
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers
2
5 (127)
6 (152)
3.1
(78)
Honeywell Asia Pacific Inc.
Room 3213-3225 Sun Hung Kai Centre No. 30 Harbour Road Wanchai Hong Kong
Helping You Control Your World
C6981
Loading...