Pentax T812C1000 Installation Instructions

0 (0)

T812, TS812 Thermostats

INSTALLATION INSTRUCTIONS

APPLICATION

The T812 and TS812 Thermostats are low voltage, controls for heat only, cool only or heating and cooling systems. See Table 1.

Table 1. Model Descriptions.

 

 

 

 

 

Model

Voltage

System

Anticipator

 

 

 

 

 

 

 

 

T812A

24 Vac

Heat only

Adjustable

 

 

 

.18A to 1.2A @

 

 

 

30

Vac

 

 

 

 

T812B

12 Vdc

Heat only

.18A to 1.2A @

 

 

 

12

Vdc

 

 

 

 

T812C

24 Vac

Heat and

Adjustable

 

 

Cool

.18A to 1.2A @

 

 

 

30

Vac

 

 

 

 

T812D

24 Vac

Cool only

Fixed 24 Vac to

 

 

 

30

Vac

 

 

 

 

TS812A

750 mV

Heat only

.1A @ .75 Vdc

 

 

 

 

 

MERCURY NOTICE

If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.

Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.

INSTALLATION

When Installing this Product...

1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After installation is complete, check out product operation as provided in these Instructions.

CAUTION

Electrical Shock Hazard.

Can cause personal injury or equipment damage.

Disconnect power supply before beginning installation.

Location

Locate the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature.

Do not mount the thermostat where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from the sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) area such as outside wall behind the thermostat.

® U.S. Registered Trademark

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copyright © 2004 Honeywell International Inc. •

• All Rights Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

69-1606ESF-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pentax T812C1000 Installation Instructions

T812, TS812 THERMOSTATS

MOUNTING HOLE

(THERMOSTAT SNAP SWITCH CONTACTS

TO WALL)

TEMPERATURE MOUNTING SETTING LEVER TABS (3)

3.Connect the thermostat wires to the appropriate terminals on the thermostat back. See Fig. 4-8 for typical hookup diagrams.

4.Push any excess wire back through the hole and plug any opening to prevent drafts that could affect thermostat performance.

5.Adjust the heat anticipator (select models) to match the current draw of the system primary control. See Heat Anticipator Setting section.

6.Fasten the thermostat to the wall with screws through the mounting holes on the upper left and right sides of the device. See Fig. 2.

7.Replace the thermostat cover.

MOUNTING HOLES (2) USED TO MOUNT THERMOSTAT TO WALL (FOR MODELS WITH SUBBASE).

SCREWS (3)

BIMETAL

ADJUSTABLE HEAT

ELEMENT

USED

ANTICIPATOR

TO MOUNT

 

ADJUSTABLE

SCALE

THERMOSTAT

 

ONTO

HEAT ANTICIPATOR

 

SUBBASE

INDICATOR LEVER

MOUNTING HOLE

 

 

(THERMOSTAT TO WALL)

 

 

M20496A

Fig. 1. Internal view of T812 with adjustable heat anticipator.

Wiring and Mounting

All wiring must comply with local codes and ordinances.

MOUNTING HOLES (2) USED TO MOUNT THERMOSTAT TO WALL (FOR MODELS WITHOUT SUBBASE).

M20883

Fig. 2. Mounting hole locations for models without subbase.

T812 and TS812 Models Without Subbase

1.In replacement applications, inspect the old wires for frayed or cracked insulation and replace any wires in poor condition; in new installations, run two wires to the location.

2.Grasping the thermostat cover on the top and the bottom with one hand, push in on the bottom center and pull outward until the cover snaps free from the thermostat base.

M20889

Fig. 3. Mounting hole locations for models with subbase.

T812 Models With Subbase

1.In replacement applications, inspect the old wires for frayed or cracked insulation and replace any wires in poor condition; in new installations, run the appropriate number of wires to the location.

2.Grasping thermostat cover on top and bottom with one hand, push in on bottom center and pull outward until cover snaps free from thermostat base.

3.Disconnect thermostat from subbase by unscrewing the three screws under the thermostat cover. See Fig. 1.

4.Connect the wires to the terminals on the front of the subbase. See Fig. 4-8.

5.Push any excess wire back through the hole and plug any opening to prevent drafts that could affect thermostat performance.

6.Loosely fasten thermostat subbase to the wall with a screw through the right mounting hole. Adjust the subbase so it is approximately level and start the second screw through the left mounting slot.

7.Level the thermostat subbase for appearance only; it is not required for accurate operation.

8.Tighten the mounting screws. See Fig. 3.

9.Mount the thermostat to the thermostat subbase by tightening the three screws. See Fig. 1.

10.Adjust the heat anticipator (select models) to match the current draw of the system primary control. See Heat Anticipator Setting section.

11.Replace the thermostat cover.

69-1606ESF-3

2

T812, TS812 THERMOSTATS

T812A

THERMOSTAT

 

 

 

COMBINATION FAN

 

R

W

 

AND LIMIT CONTROL

 

 

 

 

 

 

LIMIT FAN

 

 

 

 

 

L1

 

 

 

 

(HOT)

 

TH

TR

 

 

 

TH

TR

 

1

 

 

 

 

GAS VALVE

TRANSFORMER

L2

 

 

 

 

 

FAN

 

 

 

 

 

 

 

MOTOR

 

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND

 

OVERLOAD PROTECTION AS REQUIRED.

M20437

Fig. 4. T812A in typical gas heating system.

TS812

THERMOSTAT

R W

PILOT CONTROL (IF USED)

LIMIT

CONTROL

MILLIVOLT

GENERATOR

TH1 TH2 PP PP

M20438A

Fig. 5. Typical hookup to TS812A in millivolt system.

T812B

THERMOSTAT

W R

TO 12 Vdc 1

POWER SUPPLY

GAS VALVE

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION

AS REQUIRED.

M20439

Fig. 6. T812B in 12 Vdc application.

T812C

THERMOSTAT

R W Y G

HEAT FAN

1

COOL

L1

L2

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M20440

Fig. 7. T812C in heating and cooling system.

T812D

THERMOSTAT

R Y

COOL

1

L1

L2

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M20441

Fig. 8. T812D in cooling only application.

3

69-1606ESF-3

SETTING AND CHECKOUT

Temperature Setting

Move the temperature setting lever to the desired setpoint on the thermostat scaleplate, see Fig. 1, to control the temperature to desired point. (On positive off models, the control circuit is broken when the lever is moved to the extreme lowest setting of the temperature scale.)

Heat Anticipator Setting (Select Models)

IMPORTANT

1.Use this thermostat only with controls that have current rating equal to (or within) the rating of the heat anticipator.

2.Setting the heat anticipator allows the thermostat to maintain accurate temperature control.

Models with an adjustable heat anticipator should be adjusted to match the current draw of the primary control for optimum thermostat performance. To adjust, move the anticipator indicator lever to correspond to the control rating. See Fig. 1.

If the setting and current rating are not available, wire the thermostat into the system, but do not attach it to the wall. If the thermostat is already mounted, remove it from the wall, leaving it connected to the system wiring.

Connect an ammeter of the appropriate range (about 0.0A to 2.0A) between the terminals on the back of the thermostat. Move the temperature setting lever to a low setting so the contacts are broken. In cold weather, it may be necessary to hold the switch so the controls remain open. Allow the system to operate through the ammeter for one minute. Adjust the anticipator to match the meter reading.

NOTE: For best performance, the heat anticipator can require further adjustment. To lengthen burneron time, move the indicator to a higher number, but not more than one-half scale marking at a time. To shorten burner-on time, move the indicator in the opposite direction.

Cool Anticipator (Select Models)

Models with a cooling anticipator have a 24 Vac to 30 Vac fixed anticipator.

Checkout

CAUTION

Shorting Hazard.

Can damage heat anticipator.

Do not check operation by shorting across system control terminals.

Observe the system through at least one complete automatic cycle. Make certain that the system operates as intended. Check for correct operation of positive off switch, if used.

Calibration

This thermostat is carefully calibrated at the factory and cannot be field-adjusted.