DataVU Recorders
Introducing DataVU, our family of recorders. The range includes DataVU 6, an a󰀨ordable and user friendly entry level paperless recorder and DataVU 7, an advanced recorder o󰀨ering a high level of functionality to its users. The recorders are ideal for use in industrial and scientic processes such as food and beverage, life
DataVU 6
The DataVU 6 paperless recorder features a resistive
touchscreen and an intuitive, icon-based operation and
visualisation concept that makes it very easy to use. There
are di󰀨erent versions of the DataVU 6 available for process data recording. These range from the device version without measuring input in which up to 24 process values are read
(master) or received (slave) from external systems via
Modbus, through to a device version with six measuring inputs (universal analogue inputs), two analogue outputs, 12 digital inputs, and 12 individually switchable digital inputs/ outputs. In the version with FDA-compliant data recording all the requirements are met in accordance with 21 CFR Part
11.
DataVU 6 provides a rst class 5.7” TFT colour display
for viewing data
DataVU 6 has a TFT display for high image quality, this provides excellent
levels of contrast for improved visibility and the 640 x 480 pixel screen provides sharp denition for images and information to be clearly viewed.
The screen supports wide viewing angles with minimal colour distortions
and loss of contrast making it ideal for use in all industrial environments.
www.west-cs.com
Features
The DataVU 6 can display data using the default visualisations, such as curve diagram (vertical or
horizontal), bar graph, text image (numerical), or digital diagram. For batch related processes a special batch recording is available which allows the storage of additional information. In addition, users can create up to six individual process screens with up to 100 objects per process screen to t their requirements using the setup program. In addition to the setup program further powerful PC programs are available, e.g.
for the evaluation of archived data and for the administration of access control.
Digital Diagram Text Image
• Up to 6 digital channels in one group on one screen
• Vertical display (digital tracks
running from top to bottom)
• Horizontal display (digital tracks running from right to left)
Inputs / Outputs
Option 1, option 2:
3 analogue inputs, 6 digital inputs,
1 analogue output each
Option 3:
12 digital inputs/outputs, incl. 1 high-speed
External Inputs
Up to 24 analogue inputs Up to 24 binary inputs
Relay Outputs
1 relay (changeover contact)
counting input (up to 12.5 kHz)
• Numerical display of the measured values from up to 6 analogue channels in one group
Additional display of up to 6 digital channels in one group as
a symbol B1 to B6
Analogue channels can be displayed individually
Report
Logging of a batch record
Display of the completed batch as a report or curve diagram
Power Supply
AC 100...240V +10/-15%,
48...63Hz AC/DC 20...30V, 48...63Hz
Interface
1 x Ethernet 10/100 Mbits/sec 1x USB host (ash drive) 1x USB device (setup) 1x RS232/RS485 (Modbus master/slave or barcode scanner)
Internal Channels
6 math channels (optional) 6 logic channels (optional)
6 counters/integrators 1 high-speed counter
Operation
Touchscreen (resistive)
Display
14,5 cm (5,7”) TFT colour screen 640 x 480 pixel, 65536 colours
Measurement Data Memory
Internal memory:
1 GByte (data transfer via interface or USB ash drive)
Software
Setup program PCC, PCA3000 PCS, PCAT