Parker PSSCCNA, PSSN8M8A, PSSCENA, PSSSE24A, PSSN8M12A Installation & Service Instructions Manual

...
0 (0)
Pneumatic Division
(03-05-2019)
INDEX
Click here to view bookmarks.
Richland, Michigan USA
www.parker.com/pneumatics
H SERIES FIELDBUS SYSTEM
Bulletin Number Bulletin Description
E100P Rev. C 32 Point Valve Driver Series A, PSSV32A Instructions
E101P Rev. D DeviceNet Adapter Series A, PSSCDM12A, PSSCDM18PA Instructions
E102P Rev. E PROFIBUS Adapter Series A, PSSCPBA Instructions
E104P Rev. D EtherNet/IP Adapter Series A, PSSCENA Instructions
E105P Rev. C 24VDC Expansion Power Supply Series A, PSSSE24A Instructions
E106P Rev. F 24VDC Input Module Series A, PSSN8M8A, PSSN8M12A, PSSN8M23A, PSSP8M8A,
PSSP8M12A, PSSP8M23A, PSSN16M12A Instructions
E107P Rev. D 24VDC Output Module Series A, PSST8M23A, PSST8M12A, PSST8M8A,
PSST16M23A, PSST16D25A, PSST16M12A Instructions
E109P Rev. C Relay Output Module Series A, PSSTR4M12A Instructions
E110P Rev. C 24VDC Analog Input Module Series A, PSSNACM12A, PSSNAVM12A Instructions
E111P Rev. C 24VDC Analog Output Module Series A, PSSTACM12A, PSSTAVM12A Instructions
E112P Rev. B I/O RS-232 ASCII Module Series A, PSSS23A Instructions
E115P Rev. 1 Industrial Automation Wiring and Grounding Guidelines
E116P Rev. 1 Safety Guidelines for Application Installation & Maintenance of Solid State Control
E117P Rev. C Extension Units, Series A, PSSEXT1, PSSEXT3 Instructions
DNET-UM072C-EN DeviceNet Media, Design & Installation Guide
PSS-RN001B-EN-E Rev. A I/O ControlNet Adapter, PSSCCNA Release Notes
PSS-RN002A-EN-E Rev. B I/O EtherNet I/P Adapter, PSSCENA Release Notes
PSS-SG001A-EN-P Serial Bus System, Selection Guide
PSS-UM001A-EN-P Rev. C DeviceNet Adapters, PSSCDM12A, PSSCDM18PA, User Manual
V345P Rev. 2 25-Pin, D-Sub Cable, Installation & Service Instructions
V459P Rev. B Modufl ex Fieldbus, Installation & Service Instructions
V464P Rev. B Turck Fieldbus, Installation & Service Instructions
Safety Guide PDN Safety Guide
!
Pneumatic Division
Mod
PSSV32A
Net
Fault
PSSV32A
Outputs 25- 32 Connector
Outputs 1- 24 Connector
Richland, Michigan 49083
Installation & Service Instructions E100P
H Series Fieldbus 32 Point Valve Driver, Series A (PSSV32A)
ISSUED: February, 2016 Supersedes: December, 2006
Doc.# E100P, EN# 160064, Rev. C
!
WARNING
• To avoid unpredictable system behavior that can cause personal
injury and property damage:
• Disconnect electrical supply (when necessary) before installation,
servicing, or conversion.
• Disconnectairsupplyanddepressurizeallairlinesconnectedtothis
product before installation, servicing, or conversion.
• Operatewithin themanufacturer’sspeciedpressure,temperature, andotherconditionslistedintheseinstructions.
• Medium must be moisture-free if ambient temperature is below freezing.
• Serviceaccordingtoprocedureslistedintheseinstructions.
• Installation, service, and conversion of these products must be performed by knowledgeable personn el who understand how
pneumatic products are to be applied.
• Afterinstallation,servicing,orconversion,airandelectricalsupplies (whennecessary)shouldbe connected and the producttestedfor proper function and leakage. If audible leakage is present, or the
product does not operate properly, do not put into use.
• Warningsandspecicationsontheproductshouldnotbecoveredby
paint, etc. If masking is not possible, contact your local representative for replacement labels.
Safety Guide
For more complete information on recommended application guidelines, see the Safety Guide section of Pneumatic Division catalogs or you can download the Pneumatic Division Safety Guide at: www.parker.com/safety
Introduction
Follow these instructions when installing, operating, or servicing the product.
H Series Fieldbus 32 Point Valve Driver, Series A
(PSSV32A)
The sealed IP67 housing of these modules requires no enclosure. (Note that environmental requirements other than IP67 may require an additional appropriate housing.) The PSSV32A module is shown below.
The PSSV32A valve driver module provides an interface between the H Series Fieldbus serial bus system and the H Series ISO valve assembly. This module will always be the last module on the H Series Fieldbus serial bus. It controls 32 digital outputs at 24VDC. Depending on valve selection, it can control up to 32 single solenoid valves or 16 double solenoid valves.
WARNING
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.
This document and other information from Parker Hannifin Corporation, its subsidiaries and authorized distributors provide product and/or system options for further investigation by users having technical expertise. It is important that you analyze all aspects of your application, including consequences of any failure and review the information concerning the product or systems in the current product catalog. Due to the variety of operating conditions and applications for these products or systems, the user, through its own analysis and testing, is solely responsible for making the final selection of the products and systems and assuring that all performance, safety and warning requirements of the application are met.
The products described herein, including without limitation, product features, specifications, designs, availability and pricing, are subject to change by Parker Hannifin Corporation and its subsidiaries at any time without notice.
EXTRA COPIES OF THESE INSTRUCTIONS ARE AVAILABLE FOR INCLUSION IN EQUIPMENT / MAINTENANCE MANUALS THAT UTILIZE THESE PRODUCTS. CONTACT YOUR LOCAL REPRESENTATIVE.
H Series Fieldbus 32 Point Valve Driver, Series A (PSSV32A) E100P
!
!
!
!
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the
Application, Installation and Maintenance of Solid State Controls
(available online at www.parker.com/pneu/hseriesfieldbus) describes some important differences between solid state equipment and hard­wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Parker Hannifin Corporation be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Parker Hannifin Corporation cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Parker Hannifin Corporation with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Parker Hannifin Corporation is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
ATTENTION
Environment and Enclosure
This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as “enclosed” equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
NOTE: See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the publication E115P (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.
WARNING Identifies information about practices or
circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION Identifies information about practices or
 • IdentifyaHazard
 • AvoidaHazard
 • RecognizetheConsequence
SHOCK HAZARD
BURN HAZARD Labels may be located on or inside the
Identifies information that is critical for successful application and understanding of the product.
circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
Labels may be located on or inside the
equipment to alert people that dangerous voltage may be present.
equipment to alert people that surfaces may be dangerous temperatures.
ATTENTION
PreventingElectrostaticDischarge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
 •Touchagroundedobjecttodischargepotentialstatic.  •Wearanapprovedgroundingwriststrap.  •Donottouchconnectorsorpinsoncomponentboards.  •Donottouchcircuitcomponentsinsidetheequipment.  •Ifavailable,useastatic-safeworkstation.  •Whennotinuse,storetheequipmentinappropriate
static-safe packaging.
2
H Series Fieldbus 32 Point Valve Driver, Series A (PSSV32A) E100P
!
Outputs
25- 32
Connector
Outputs
1- 24
Connector
MounttheI/OBase
To mount the I/O base on a wall or panel, use the screw holes provided in the base.
IMPORTANT
The I/O module must be mounted on a grounded metal mounting plate or other conductive surface.
A mounting illustration for the base with an adapter is shown below.
* Depending on the type and number of manifolds, this dimension
may vary. Refer to Catalog 0600P-# for additional information.
2.0
(50)
Adapter
4.02
(102)
1.81 (46)
Inches
(mm)
1.9
(47.2)
2.0
(50)
Drill and Tap
for M4 Screw
0.87 (22)
Installthe32PointValveDriver
ToInstallthe32PointValveDriver,ProceedasFollows:
1. Assemble the valve driver to the manifold interface plate using four M4 screws, torqued 11 to 13 in. lbs.
2. Plug the 32 point valve driver onto the previous mounting base or communication adapter.
Wirethe32PointValveDriver
Following are wiring instructions for the 32 point valve driver. Use the appropriate harness assembly based on your manifold
wiring/interconnect system.
3.02
(76.6)
3.13
(79.4)
5.39
(137.0)
5.98*
(151.9)
2.39
(60.7)
4.32
(109.8)
Drill and Tap
for M6 Screw
Harness Assembly Kit Numbers
1 to 24 Outputs 25 to 32 Outputs
HA, HB PS5624P PS5632P
H1, H2, H3 PS4024P PS4032P
Plug the 2X15 connector into the valve driver module for 1-24 outputs. If you have more than 24 outputs, plug the 2X5 connector into the valve driver module for 25-32 outputs.
Plug the 2X10 and 1X10 connectors into the interconnect board in the valve manifold.
EDS File Requirements
The EDS file is available online at www.parker.com/pneu/ hseriesfieldbus
ATTENTION
Make sure all four screws are securely tightened to properly seal the connections against leaks and maintain IP67 requirements.
3
H Series Fieldbus 32 Point Valve Driver, Series A (PSSV32A) E100P
CommunicateWithYourModule
I/O messages are sent to (consumed) and received from (produced) the I/O modules. These messages are mapped into the processor’s memory. The 32 point valve driver produces 1 byte of input data (scanner Rx - status), and consumes 1 byte of I/O data (scanner Tx).
DefaultDataMapforthe32PointValveDriver
PSSV32A
Message Size: 1 Byte
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Produce 0 Output Output Output Output Output Output Output Output 7 6 5 4 3 2 1 0
Produce 1 Output Output Output Output Output Output Output Output 15 14 13 12 11 10 9 8
Produce 2 Output Output Output Output Output Output Output Output 23 22 21 20 19 18 17 16
Produce 3 Output Output Output Output Output Output Output Output 31 30 29 28 27 26 25 24
Produce 4 Fault Fault Fault Fault Fault Fault Fault Fault 28-31 24-27 20-23 16-19 12-15 8-11 4-7 0-3
Consume 0 Output Output Output Output Output Output Output Output 7 6 5 4 3 2 1 0
Consume 1 Output Output Output Output Output Output Output Output 15 14 13 12 11 10 9 8
Consume 2 Output Output Output Output Output Output Output Output 23 22 21 20 19 18 17 16
Consume 3 Output Output Output Output Output Output Output Output 31 30 29 28 27 26 25 24
Setupthe32PointValveDriverinControlNet
Step1:Load32PointValveDriverEDSletoRSLinx
 •DownloadEDSlefromwww.parker.com/pneu/hserieseldbus
• Onyourcomputer,followStartRockwellSoftwareRSLinx
ToolsEDSHardwareInstallationTool to load the EDS file to RSLinx
Step2:AddControllerandCommunicationModuletothe  RSLogix5000I/OConguration
 •Addacontrollerandacommunicationmodule(HSeriesFieldbus
PSSCCNA or Rockwell 1738-ACNR) to I/O configuration. Reference pages 4-1 through 4-7 of Rockwell publication 1734-UM008 (follow www.rockwell.comSupportSupport
OverviewOnline manuals and literatureI/O1734 POINT and 1734D POINT Block I/O and find POINT I/O ControlNet
Adapter User Manual) for a similar setup procedure.
Step3:Add32PointValveDrivertoRSLogix5000  I/OConguration.
If your RSLogic 5000 is Version 15.X or greater:
 •HighlightthePSSCCNA under I/O configuration, right click and
select NewModule.
 •ChoosethePSSV32A module from the list of Parker modules.
Setupthe32PointValveDriverinDeviceNet
Step1:Load32PointValveDriverEDSletoRSLinx
 •DownloadEDSlefromwww.parker.com/pneu/hserieseldbus  •Onyour computer,followStartRockwellSoftwareRSLinx
ToolsEDSHardwareInstallationTool to load the EDS file to RSLinx
Step2:ConguretheDeviceNetScannerSubnet
 •Reference Chapter 4 of the H Series Fieldbus DeviceNet
Adapters User Manual PSS-UM001 for detailed information. Make sure to add PSSV32A to the DeviceNet Adapter’s scanlist.
Step3:AddtheHSeriesFieldbusDeviceNetAdaptertothe
DeviceNet
Scanner’sScanlist
 •Reference Chapter 5 of the H Series Fieldbus DeviceNet
Adapters User Manual PSS-UM001 for detailed information.
Step4:Use32PointValveDriverinRSLogix5000
 •AccessPSSV32AdataviaDeviceNetScannerintheladderlogic
program.
 •Enteraname(optional)andclickOK.
Notice that the 32 Point Valve Drive Module is now under I/O
Configuration.
4
H Series Fieldbus 32 Point Valve Driver, Series A (PSSV32A) E100P
If your RSLogic 5000 is Version 13.X:
 •Highlightthe1738-ACNR under I/O configuration, right click and
select NewModule.
 •ChoosetheGeneric 1738 module from the list of Allen-Bradley
modules.
 •Enter a name (optional), an appropriate slot number and the
connection parameters as shown in this screen capture.
Setupthe32PointValveDriverinEtherNet/IP
Step1:Load32PointValveDriverEDSletoRSLinx
 •DownloadEDSlefromwww.parker.com/pneu/hserieseldbus
• Onyourcomputer,followStartRockwellSoftwareRSLinx
ToolsEDSHardwareInstallationTool to load the EDS file to RSLinx
Step2:SetIPAddressforEtherNet/IPScannerandAdapter
 •Set IP address using Rock well BootP/DHCP utility fo r
EtherNet/IP scanner and PSSCENA or 1738-AENT adapter. Reference pages 3-7 through 3-10 of Rockwell publication 1734-UM011 (follow www.rockwell.comSupportSupport
OverviewOnline manuals and literatureI/O1734 POINT and 1734D POINT Block I/O and find POINT I/O Ethernet
Adapter User Manual) for similar information.
Step3:AddEtherNet/IPScannerandAdaptertoRSLogix  5000I/Oconguration.
 •AddEtherNet/IPscannerandPSSCENAor1738-AENTadapter
to I/O configuration. Reference pages 4-4 to 4-8 of Rockwell publication 1734-UM011 for similar information.
Step4:Add32PointValveDrivertoRSLogix5000  I/OConguration.
If your RSLogic 5000 is Version 15.X or greater:
 •HighlightthePSSCENA under I/O configuration, right click and
select NewModule.
 •ChoosethePSSV32A module from the list of Parker modules.
 •ChooseNext to set RPI.  •ChooseFinish. Notice that the 32 Point Valve Driver Module is
now under the I/O configuration.
Step4:DownloadtheProgramtotheControllerand  CongurethePSSCCNAor1738-ACNRAdapter.
 •Reference pages 4-11 through 4-15  of Rockwell publication
1734-UM008 for similar setup procedure.
Step5:ScheduleI/OModuleConnections
 •Reference pages 4-15 through 4-19  of Rockwell publication
1734-UM008 for similar setup procedure.
Step6:AccessModuleDataviathePSSCCNAor1738-ACNR
Adapter.
 •Makesurethe32outputsofPSSV32AappearinControllerTags.
Use the information in the ladder logic program to access module data.
 •Enteraname(optional)andclickOK.
 •Referencepages4-19through4-22ofRockwellpublication
1734-UM008 for similar information.
Notice that the 32 Point Valve Drive Module is now under I/O
Configuration.
5
H Series Fieldbus 32 Point Valve Driver, Series A (PSSV32A) E100P
If your RSLogic 5000 is Version 13.X:
 •Highlightthe1738-AENT under I/O configuration, right click and
select NewModule.
 •ChoosetheGeneric 1738 module from the list of Allen-Bradley
modules.
 •Enter a name (optional), an appropriate slot number and the
connection parameters as shown in this screen capture.
Setupthe32PointValveDriverinProbus
Step1:CongureValveDriverModuleinSSTProbus  CongurationUtility
Note: SST-PFB-CLXis used here for example.  For different Probusscanners,refertoappropriatedocumentationforsetup
information.
 •DownloadGSDlefromwww.parker.com/pneu/hserieseldbus
• InSSTProbusCongurationUtility,followLibraryAdd GSD
to load the GSD file to SST Profibus.
 •InSSTProbusCongurationUtility,followBrowseSearchfor
devices to load the GSD file to SST Profibus
 •Rightclickonthefounddevice,follow GSD les and click on
appropriate GSD for PSSV32A.
 •AddPSSV32AasslavetoSST-PFB-CLXmaster.
Detailed information can be found in the SST-PFB-CLX User Guide
 •
(Ver. 1.4 715-0022), which is available on www.woodhead.com.
Step2:AddSSTProbusScannerinRSLogix5000  I/OConguration
Add SST-PFB-CLX scanner I/O configuration. Reference pages 36
 •
to 39 of the SST-PFB-CLX User Guide, for detailed information.
 •Notice that the SST-PFB-CLX scanner is now under the I/O
configuration.
 •ChooseNext to set RPI.  •ChooseFinish. Notice that the 32 Point Valve Driver Module is
now under the I/O configuration.
Step5:AccessModuleDataviathePSSCENAor1738-AENT
Adapter and Create Ladder Program.
 •Makesurethe32outputsofPSSV32AappearinControllerTags.
Use the information in the ladder logic program to access module data.
Step3:AccessModuleDataviatheSST-PFB-CLXScanner and Create Ladder Program.
 •Reference Chapter 7 of the SST-PFB-CLX User Guide for
addressing information.
 •Referencepages4-13through4-14ofRockwellpublication
1734-UM011 for similar information.
Step6:DownloadtheProgramtotheController
 •Referencepages4-13through4-14ofRockwellpublication
1734-UM011 for similar information.
6
H Series Fieldbus 32 Point Valve Driver, Series A (PSSV32A) E100P
Mod
PSSV32A
Net
Fault
PSSV32A
Module Status Indicator
Network Status Indicator
Output Fault Status Indicator
TroubleshootWiththeIndicators
Indication Probable Cause Module Status
Off No power applied to device Green Device operating normally Flashing Green Device needs commissioning due to missing, incomplete, or incorrect configuration Flashing Red Recoverable fault Red Unrecoverable fault - may require device replacement Flashing Red/Green Device is in self-test
Indication Probable Cause
NetworkStatus
Device is not on line:
Off
- Device has not completed dup_MAC-id test.
- Device not powered - check module status indicator. Flashing Green Device is on line but has no connections in the established state. Green Device is on line and has connections in the established state. Flashing Red One or more I/O connections in timed-out state.
Red
Flashing Red/Green
Critical link failure - failed communication device. Device detected error that prevents it from communicating on the network.
Communication faulted device - the device has detected a network access error and is in communication faulted state. Device has received and accepted an Identity Communication Faulted Request - long protocol message.
Indication Probable Cause Output Fault Status
Off Outputs operating normally Red Over current, short circuit or over temperature detected on one or more outputs. (On-State only)
7
H Series Fieldbus 32 Point Valve Driver, Series A (PSSV32A) E100P
Specications –
32 Point Valve Driver
Outputs per Module 32, sourcing Voltage Drop, On-State Output, Maximum 0.2VDC Voltage, Off-State Output, Maximum 28.8VDC Voltage, On-State Output,
Maximum 28.8VDC Minimum 10VDC Nominal 24VDC
Output Current Rating 200 mA per channel, not to exceed 6.0 A per module Output Surge Current, Maximum 0.5 A for 10 ms, repeatable every 3 seconds Current Leakage, Off-State Output, Maximum 0.1 mA Current, On-State Output Minimum 200 mA per channel Output Delay Time OFF to ON, Maximum1 0.1 ms Output Delay Time, ON to OFF, Maximum1 0.1 ms External DC Power Supply Voltage Range 10 to 28.8VDC External DC Power Supply Voltage Nominal 24VDC
GeneralSpecications
LED Indicators 1 output status 1 green/red network status, logic side 1 green/red module status, logic side
PointBus Current, Maximum 75 mA @ 5VDC Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F) Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F) Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5 to 95% non-condensing Shock IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g Non-operating 50g
Vibration IEC60068-2-6 (Test Fc, Operating): 5g @ 10 to 500Hz
ESD Immunity IEC 61000-4-2: 6kV contact discharges 8kV air discharges
Radiated RF Immunity IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
EFT/B Immunity IEC 61000-4-4: ±3kV at 5kHz on signal ports
Surge Transient Immunity IEC 61000-4-5: ±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports
Conducted RF Immunity IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Emissions CSPR 11: Group 1, Class A
Enclosure Type Rating Meets IP65/66/67 (when marked) Mounting Base Screw Torque #8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel Wiring Category2 1 - on signal ports Certifications: c-UL-us UL Listed Industrial Control Equipment,
(when product is marked) certified for US and Canada CE
compliant with: EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity
C- Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
1. OFF to ON or ON to OFF delay is time from a valid output “on” or “off” signal to output energization or de-energization.
2. Use this Conductor Category information for planning conductor routing. Refer to Publication E115P, “Industrial Automation Wiring and Grounding Guidelines”.
Following are specifications for the 32 point valve driver.
European Union 89/336/EEC EMC Directive,
8
Pneumatic Division
PSSCDM12A
!
!
Richland, Michigan 49083
WARNING
Installation & Service Instructions E101P
H Series Fieldbus DeviceNet Adapters, Series A
(PSSCDM12A, PSSCDM18PA)
ISSUED: February, 2016 Supersedes: December, 2006
Doc.# E101P, EN# 160064, Rev. D
To avoid unpredictable system behavior that can cause personal injury and property damage:
• Disconnectelectricalsupply(whennecessary)beforeinstallation,
servicing, or conversion.
• Disconnectairsupplyanddepressurizeall airlinesconnected to
this product before installation, servicing, or conversion.
• Operatewithinthemanufacturer’sspeciedpressure,temperature,
and other conditions listed in these instructions.
• Medium must be moisture-free if ambient temperature is below freezing.
• Serviceaccordingtoprocedureslistedintheseinstructions.
• Installation, service, and conversion of these products must be performed by knowledgeable personnel who understand how
pneumatic products are to be applied.
• After installation, servicing, or conversion, air and electrical supplies(whennecessary)shouldbe connectedandthe product
tested for proper function and leakage. If audible leakage is present, or the product does not operate properly, do not put into use.
• Warnings and specifications on the product should not be
covered by paint, etc. If masking is not possible, contact your local representative for replacement labels.
Safety Guide
For more complete information on recommended application guidelines, see the Safety Guide section of Pneumatic Division catalogs or you can download the Pneumatic Division Safety Guide at: www.parker.com/safety
DeviceNet Out
DeviceNet In
X10
PWR
Mini 7/8" Connector
Node Address Switches
Mini 7/8" Auxiliary Power Connector
M12
PSSCDM12A
Connector
Node Address
Adapter Status
DeviceNet
X1
Status
PointBus Status
System Power
Adapter Power
Switches
Mini 7/8" Auxiliary Power Connector
PSSCDM18PA
DNet
DNet
X10
Out
In
X1
PWR
PSSCDM18PA
Adapter Status
DeviceNet Status
PointBus Status
System Power
Adapter Power
Introduction
Follow these instructions when installing, operating, or servicing the product.
H Series Fieldbus DeviceNet Adapters, Series A
(PSSCDM12A, PSSCDM18PA)
The sealed IP67 housing of these adapters requires no enclosure. (Note that environmental requirements other than IP67 may require an additional appropriate housing.) DeviceNet connectors are sealed Micro (M12) or Mini (7/8") styles. The DeviceNet adapters are shown below.
H Series Fieldbus DeviceNet Adapters User Manual
The H Series Fieldbus DeviceNet Adapters User Manual PSS­UM001A-EN-P is available online at www.parker.com/pneu/ hseriesfieldbus
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.
This document and other information from Parker Hannifin Corporation, its subsidiaries and authorized distributors provide product and/or system options for further investigation by users having technical expertise. It is important that you analyze all aspects of your application, including consequences of any failure and review the information concerning the product or systems in the current product catalog. Due to the variety of operating conditions and applications for these products or systems, the user, through its own analysis and testing, is solely responsible for making the final selection of the products and systems and assuring that all performance, safety and warning requirements of the application are met.
The products described herein, including without limitation, product features, specifications, designs, availability and pricing, are subject to change by Parker Hannifin Corporation and its subsidiaries at any time without notice.
EXTRA COPIES OF THESE INSTRUCTIONS ARE AVAILABLE FOR INCLUSION IN EQUIPMENT / MAINTENANCE MANUALS THAT UTILIZE THESE PRODUCTS. CONTACT YOUR LOCAL REPRESENTATIVE.
WARNING
H Series Fieldbus DeviceNet Adapters, Series A (PSSCDM12A, PSSCDM18PA) E101P
!
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the
Application, Installation and Maintenance of Solid State Controls
(available online at www.parker.com/pneu/hseriesfieldbus) describes some important differences between solid state equipment and hard­wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Parker Hannifin Corporation be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Parker Hannifin Corporation cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Parker Hannifin Corporation with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Parker Hannifin Corporation is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
ATTENTION
Environment and Enclosure
This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as “enclosed” equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
NOTE: See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the publication E115P (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.
WARNING Identifies information about practices or
circumstances that can cause an explosion in a hazardous environment, which may lead to
!
IMPORTANT
ATTENTION Identifies information about practices or
!
 • IdentifyaHazard
 • AvoidaHazard
 • RecognizetheConsequence
SHOCK HAZARD
BURN HAZARD Labels may be located on or inside the
personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
Labels may be located on or inside the
equipment to alert people that dangerous voltage may be present.
equipment to alert people that surfaces may be dangerous temperatures.
ATTENTION
!
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
 •Touchagroundedobjecttodischargepotentialstatic.  •Wearanapprovedgroundingwriststrap.  •Donottouchconnectorsorpinsoncomponentboards.  •Donottouchcircuitcomponentsinsidetheequipment.  •Ifavailable,useastatic-safeworkstation.  •Whennotinuse,storetheequipmentinappropriatestatic-
safe packaging.
2
H Series Fieldbus DeviceNet Adapters, Series A (PSSCDM12A, PSSCDM18PA) E101P
Mount the Adapter and I/O Base
To mount the adapter on a wall or panel, use the screw holes provided in the adapter.
A mounting illustration for the adapter with I/O bases is shown below.
Adapter
4.02
(102)
1.81
(46)
Inches
(mm)
1.9
(47.2)
2.0
(50)
I/O Module Ground
Drill and Tap
for M4 Screw
0.87 (22)
2.0
(50)
I/O Module Ground
3.13
(79.4)
3.02
(76.6)
5.39
(137.0)
* Depending on the type and number of manifolds, this dimension
may vary. Refer to Catalog 0600P-# for additional information.
5.98*
(151.9)
Drill and Tap
for M6 Screw
2.39
(60.7)
4.32
(109.8)
Grounding
Each H Series Fieldbus base has two mounting holes, with the one on the right being the means to ground each module. Each module must be grounded.
InstalltheMountingBaseasFollows:
1. Lay out the required points as shown above in the drilling dimension drawing.
2. Drill the necessary holes for #8 (M4) machine or self-tapping screws.
3. Mount the adapter and I/O bases using #8 (M4) screws.
4. Ground the system using the ground lug connection in the I/O base. (The ground lug connection is also a mounting hole.)
3
H Series Fieldbus DeviceNet Adapters, Series A (PSSCDM12A, PSSCDM18PA) E101P
Set the Node Address
Valid node addresses are 00 through 63. Set the node address using either the rotary switches, RSNetWorx for
DeviceNet™, DeviceNetManager™, or another software configuration tool. Setting the switches at any number from 64 through 99 lets the software have address control.
Each module is shipped with the switches set for node address 63. Remove the caps on the front of the module to access the switches (refer to the illustrations on page 1). The two switches are:
 • X10(mostsignicantdigit)–leftsideofmodule
 • X1(leastsignicantdigit)–rightsideofmodule
This example shows the node address set at 63.
To reset the node address, use a small blade screwdriver to rotate the switches. Line up the small notch on the switch with the number setting you wish to use and then cycle power.
The rotary switches are read periodically. If the switches have been changed since the last time they were read and they no longer match the on line address, a minor fault will occur, which is indicated by a flashing red Adapter Status LED. Settings of 64 through 99 cause the module to use the last valid node address stored internally. Example: The last setting internally was 40. If a change is made to 68, and then you power up, the address will default to 40.
The module is equipped with AutoBaud detect. AutoBaud lets the module read the settings already in use on your DeviceNet network and automatically adjusts to follow those settings.
EDS File Requirements
The EDS files are available online at www.parker.com/pneu/ hseriesfieldbus
OpenCongurationMethod
For using H Series Fieldbus DeviceNet Adapters without RSNetWorx™ or RSLogix™ 5000, refer to document “User Guide: Configuration of the H Series Fieldbus™ Pneumatics Platform using CIP™ Explicit Messaging", which is available online at www.parker. com/pneu/hseriesfieldbus
4
H Series Fieldbus DeviceNet Adapters, Series A (PSSCDM12A, PSSCDM18PA) E101P
!
Male In Connector
Female Out Connector
Male In Connector
Female Out Connector
Male In Connector
Wire the DeviceNet Adapters
Following are wiring instructions for the DeviceNet Adapters.
PSSCDM12A(MicroM12A-CodingKey)
(view into connector) Pin 1 - Drain Pin 2 - +V Pin 3 - -V Pin 4 - CAN_High Pin 5 - CAN_Low
PSSCDM18PA (Mini 7/8")
DeviceNetAuxiliaryPower(Mini7/8")
(view into connector) Pin 1 - Drain Pin 2 - +V Pin 3 - -V Pin 4 - CAN_High Pin 5 - CAN_Low
(view into connector) Pin 1 - User Power + Pin 2 - Adapter Power + Pin 3 - Adapter Power ­Pin 4 - User Power -
NOTE: User power is the 24VDC power for field devices. Adapter power is the 24VDC power for adapter. It is converted to
5VDC to power H Series Fieldbus modules.
ATTENTION
Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements.
5
H Series Fieldbus DeviceNet Adapters, Series A (PSSCDM12A, PSSCDM18PA) E101P
TroubleshootwiththeIndicators
PSSCDM18PA
DNet
Out
DNet
In
X10
PWR
X1
Indication Probable Cause Adapter Status
Off No power applied to device Green Device operating normally Flashing Red Recoverable fault Red Unrecoverable fault -
may require device replacement Flashing Red/Green Device is in self-test
Indication Probable Cause DeviceNet Status
Off Device is not on line:
- Device attempting to Autobaud
- Device has not completed dup_MAC-id test
- Device not powered - check module status indicator
Flashing Green Device is on line but has no connections in the established state
Green Device is on line and has connections in the established state
Flashing Red One or more I/O connections in timed-out state
Red Critical link failure - failed communication device. Device detected error that prevents it from communicating on the network. (Possible duplicate MAC ID or baud rate mismatch).
PSSCDM18PA
Adapter Status Indicator
Adapter Status
DeviceNet Status
PointBus Status
System Power
Adapter Power
DeviceNet Status Indicator
PointBus Status Indicator
System Power Indicator
Adapter Power Indicator
Indication Probable Cause PointBus Status
Off Device is not on line:
- Device has not completed dup_MAC-id test
- Device not powered - check module status indicator
Flashing Green Device is on line but has no connections in the established state
Green Device is on line and has connections in the established state
Flashing Red One or more I/O connections in timed-out state
Red Critical link failure - failed communication device. Device detected error that prevents it from communicating on the network. (Possible duplicate MAC ID or baud rate mismatch).
Flashing Red/Green
Communication faulted device - the device has detected a network access error and is in communication faulted state. Device has received and accepted an Identity Communication Faulted Request - long protocol message.
Indication Probable Cause
SystemPower*
Off Not active - Field power is off, overloaded backplane or dc-dc converter problem.
Green System power on - dc-dc converter active (5V).
Indication Probable Cause
AdapterPower**
Off Not active - Field power is off. Green System power on, 24V present.
* System Power Indicator shows the 5V power output from the dc-dc converter. ** Adapter Power Indicator shows the 24V power input to the dc-dc converter.
6
H Series Fieldbus DeviceNet Adapters, Series A (PSSCDM12A, PSSCDM18PA) E101P
Specications
Following are specifications for the DeviceNet adapters.
DeviceNetAdapters-PSSCDM12A,PSSCDM18PA
ExpansionI/OCapacity • DeviceNetadapterbackplanecurrentoutput=1.0Amaximum. See the list below for backplane current consumption for each I/O catalog number and the current consumption for each of the modules connected to the DeviceNet adapter. Verify that it is below 1.0A.
• Backplanecurrentcanbeextendedbeyond1.0AwithaPSSSE24ABackplane Extension Power Supply. The PSSSE24A can supply up to an additional 1.3A of backplane current.
• MultiplePSSSE24Amodulescanbeusedtoreachthe maximum of 63 modules.
Cat. No. PointBus Current Requirements PSSN8xxx 75 mA
PSSP8xxx 75 mA PSST8xxx 75 mA PSSTR4M12A 90 mA PSSNACM12A 75 mA PSSNAVM12A 75 mA PSSTACM12A 75 mA PSSTAVM12A 75 mA PSSS23A 75 mA PSSV32A 75 mA
DeviceNet Communication Rate 125K bit/s (500m maximum) 250K bit/s (250m maximum) 500K bit/s (100m maximum)
DeviceNetPowerSpecications
Power Supply Note: In order to comply with CE Low Voltage Directives (LVD), you must use either a NEC Class 2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to power this adapter. A SELV supply cannot exceed 30V rms, 42.4V peak or 60VDC under normal conditions and under single fault conditions. A PELV supply has the same rating and is connected to protected earth.
Input Voltage Rating 24VDC nominal DeviceNet Input Voltage Range 11-25VDC DeviceNet specification Input Overvoltage Protection Reverse polarity protected
DeviceNetPowerRequirements 24VDC(+4%=25VDC)@30mAmaximum
PowerSupplySpecications
Power Supply Note: In order to comply with CE Low Voltage Directives (LVD), you must use either a NEC Class 2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to power this adapter. A SELV supply cannot exceed 30V rms, 42.4V peak or 60VDC under normal conditions and under single fault conditions. A PELV supply has the same rating and is connected to protected earth.
Input Voltage Rating 24VDC 10-28.8VDC range
Input Overvoltage Protection Reverse polarity protected Inrush Current 6A maximum for 10ms
PointBusOutputCurrent 1Amaximum@5VDC+5% (4.75-5.25)
FieldSidePowerRequirements,Maximum 24VDC(+20%=28.8VDC)@400mA
Interruption Output voltage will stay within specifications when input drops out for 10ms at 10V with maximum load
GeneralSpecications
LED Indicators 1 green/red Adapter status 1 green/red DeviceNet status 1 green/red PointBus status 1 green System Power (PointBus 5V power) 1 green Adapter Power (24V from field supply)
PowerConsumption,Maximum 8.1W@28.8VDC
7
H Series Fieldbus DeviceNet Adapters, Series A (PSSCDM12A, PSSCDM18PA) E101P
GeneralSpecications(continued)
PowerDissipation,Maximum 2.8W@28.8VDC
ThermalDissipation,Maximum 9.5BTU/hr.@28.8VDC
Isolation Voltage 50V rms (continuous-voltage withstand rating) Tested at 1250VAC rms for 60s
Field Power Bus Nominal Voltage 24VDC Supply Voltage 10-28.8VDC range Supply Current 10A maximum
Dimensions Inches (Millimeters) 4.41H x 2.83W x 2.56D (112H x 72W x 65D) Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F) Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F) Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5-95% non-condensing Shock IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g Non-operating 50g
Vibration IEC60068-2-6 (Test Fc, Operating):
5g@10-500Hz
ESD Immunity IEC 61000-4-2: 6kV contact discharges 8kV air discharges
Radiated RF Immunity IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
EFT/B Immunity IEC 61000-4-4: ±4kV at 5kHz on power ports ±3kV at 5kHz on signal ports
Surge Transient Immunity IEC 61000-4-5: ±1kV line-line(DM) and ±2kV line-earth(CM) on power ports ±2kV line-earth(CM) on shielded ports
Conducted RF Immunity IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Emissions CSPR 11: Group 1, Class A
Enclosure Type Rating Meets IP65/66/67 (when marked) Mounting Base Screw Torque #8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel
1
Wiring Category
1 - on power ports
1 - on communications ports Weight Imperial (Metric) 0.80 lb. (0.36 kg) Certifications: (when product is marked) c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada CE European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity
C-Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
ODVA ODVA conformance tested to DeviceNet specifications
1. Use this Conductor Category information for planning conductor routing. Refer to Publication E115P, “Industrial Automation Wiring and Grounding Guidelines”.
8
Pneumatic Division
!
!
Richland, Michigan 49083
WARNING
To avoid unpredictable system behavior that can cause personal injury and property damage:
• Disconnectelectricalsupply(whennecessary)beforeinstallation,
servicing, or conversion.
• Disconnectairsupplyanddepressurizeall airlinesconnected to
this product before installation, servicing, or conversion.
• Operatewithinthemanufacturer’sspeciedpressure,temperature,
and other conditions listed in these instructions.
• Medium must be moisture-free if ambient temperature is below freezing.
• Serviceaccordingtoprocedureslistedintheseinstructions.
• Installation, service, and conversion of these products must be performed by knowledgeable personnel who understand how
pneumatic products are to be applied.
• After installation, servicing, or conversion, air and electrical supplies(whennecessary)shouldbe connectedandthe product
tested for proper function and leakage. If audible leakage is present, or the product does not operate properly, do not put into use.
• Warnings and specifications on the product should not be
covered by paint, etc. If masking is not possible, contact your local representative for replacement labels.
Safety Guide
For more complete information on recommended application guidelines, see the Safety Guide section of Pneumatic Division catalogs or you can download the Pneumatic Division Safety Guide at: www.parker.com/safety
Installation & Service Instructions E102P
H Series Fieldbus PROFIBUS Adapter, Series A (PSSCPBA)
ISSUED: February, 2016 Supersedes: April, 2007
Doc.# E102P, EN# 160064, Rev. E
Introduction
Follow these instructions when installing, operating, or servicing the product.
H Series Fieldbus PROFIBUS Adapter, Series A
(PSSCPBA)
The sealed IP67 housing of these adapters requires no enclosure. (Note that environmental requirements other than IP67 may require an additional appropriate housing.) PROFIBUS connectors are sealed M12 (micro) style. The PROFIBUS adapter is shown below.
Shielding (See page 3 for details)
PSSCPBA
PSSCPBA
M12 Connector
Station Address Switches
Profibus Out Profibus In
X10
X1
Profibus DP
Adapter Status
Profibus Status
PointBus
Status
H Series Fieldbus PROFIBUS Adapter User Manual
The H Series Fieldbus PROFIBUS Adapter User Manual PSS-UM002A­EN-P is not available at this time. Please refer to Rockwell Automation 1734 POINT I/O PROFIBUS Adapter User Manual 1734-UM005B-EN-P for similar setup infor mation, which is available online at http://literature.rockwellautomation.com/.
Mini 7/8" Auxiliary
PWR
System Power
Adapter Power
Power Connector
WARNING
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.
This document and other information from Parker Hannifin Corporation, its subsidiaries and authorized distributors provide product and/or system options for further investigation by users having technical expertise. It is important that you analyze all aspects of your application, including consequences of any failure and review the information concerning the product or systems in the current product catalog. Due to the variety of operating conditions and applications for these products or systems, the user, through its own analysis and testing, is solely responsible for making the final selection of the products and systems and assuring that all performance, safety and warning requirements of the application are met.
The products described herein, including without limitation, product features, specifications, designs, availability and pricing, are subject to change by Parker Hannifin Corporation and its subsidiaries at any time without notice.
EXTRA COPIES OF THESE INSTRUCTIONS ARE AVAILABLE FOR INCLUSION IN EQUIPMENT / MAINTENANCE MANUALS THAT UTILIZE THESE PRODUCTS. CONTACT YOUR LOCAL REPRESENTATIVE.
H Series Fieldbus PROFIBUS Adapter, Series A (PSSCPBA) E102P
!
!
!
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the
Application, Installation and Maintenance of Solid State Controls
(available online at www.parker.com/pneu/hseriesfieldbus) describes some important differences between solid state equipment and hard­wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Parker Hannifin Corporation be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Parker Hannifin Corporation cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Parker Hannifin Corporation with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Parker Hannifin Corporation is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
ATTENTION
Environment and Enclosure
This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as “enclosed” equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
NOTE: See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the publication E115P (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.
WARNING Identifies information about practices or
circumstances that can cause an explosion in a hazardous environment, which may lead to
!
IMPORTANT
ATTENTION Identifies information about practices or
 • IdentifyaHazard
 • AvoidaHazard
 • RecognizetheConsequence
SHOCK HAZARD
BURN HAZARD Labels may be located on or inside the
personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
Labels may be located on or inside the
equipment to alert people that dangerous voltage may be present.
equipment to alert people that surfaces may be dangerous temperatures.
ATTENTION
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
 •Touchagroundedobjecttodischargepotentialstatic.  •Wearanapprovedgroundingwriststrap.  •Donottouchconnectorsorpinsoncomponentboards.  •Donottouchcircuitcomponentsinsidetheequipment.  •Ifavailable,useastatic-safeworkstation.  •Whennotinuse,storetheequipmentinappropriatestatic-
safe packaging.
2
H Series Fieldbus PROFIBUS Adapter, Series A (PSSCPBA) E102P
Inches
(mm)
2.0
(50)
2.0
(50)
1.9
(47.2)
4.02
(102)
1.81 (46)
4.32
(109.8)
5.39
(137.0)
Drill and Tap
for M4 Screw
2.39
(60.7)
3.02
(76.6)
3.13
(79.4)
5.98*
(151.9)
0.87 (22)
Adapter Ground
PROFIBUS Adapter
Drill and Tap
for M6 Screw
I/O Module Ground
I/O Module Ground
Mount the Adapter and I/O Base
To mount the adapter on a wall or panel, use the screw holes provided in the adapter.
A mounting illustration for the adapter with I/O bases is shown below.
* Depending on the type and number of manifolds, this dimension
may vary. Refer to Catalog 0600P-# for additional information.
InstalltheMountingBaseasFollows:
1. Lay out the required points as shown above in the drilling dimension drawing.
2. Drill the necessary holes for #8 (M4) machine or self-tapping screws.
3. Mount the adapter using #8 (M4) screws.
4. Ground the system using the ground lug connection in the I/O base. (The ground lug connection is also a mounting hole.)
Grounding and Shielding
Grounding: Each H Series Fieldbus base has two mounting
holes, with the one on the right being the means to ground each module. Each module must be grounded.
Shielding: For PROFIBUS adapter, both PROFIBUS IN and PROFIBUS OUT metal shells are connected to the top screw hole metal ring. Shielded PROFIBUS cordsets are required to help reduce the effects of electrical noise coupling. One example of such a cordset is Brad Harrison's “360° Shielded Head” cordset, which can be found at www.connector.com. For more Grounding and Shielding information, please refer to E115P, “Industrial Automation Wiring and Grounding Guidelines”.
3
H Series Fieldbus PROFIBUS Adapter, Series A (PSSCPBA) E102P
Set the Station Address
To set the station address, adjust the switches on the front of the module (refer to the illustration on page 1). Use a small blade screwdriver to rotate the switches. Line up the small notch on the switch with the number setting you wish to use. The two switches are most significant digit (MSD) and least significant digit (LSD). The switches can be set from 01 through 99. The module reads the switches at power-up only.
This example shows the node address set at 63.
GSD File Requirements
Current functionality of a PROFIBUS adapter requires a GSD file. The file is easy to install and is available online at:
www.parker.com/pneu/hseriesfieldbus
4
H Series Fieldbus PROFIBUS Adapter, Series A (PSSCPBA) E102P
!
Male In Connector
Female Out Connector
Male In Connector
Wire the PROFIBUS Adapter
Following are wiring instructions for the PROFIBUS Adapter.
PSSCPBA(MicroM12,B-CodingReverseKey)
(view into connector) Pin 1 - +5VBUS Pin 2 - A-Line Pin 3 - GNDBUS Pin 4 - B-Line Pin 5 - Not Used
Note: Please refer to page 3, Mount the Adapter and I/O Base, for shielding information.
PSSCPBA Male Auxiliary (Mini 7/8")
(view into connector) Pin 1 - User Power ­Pin 2 - Adapter Power ­Pin 3 - Protective GND Pin 4 - Adapter Power + Pin 5 - User Power +
NOTE: User power is the 24VDC power for field devices. Adapter power is the 24VDC power for adapter. It is converted to
5VDC to power H Series Fieldbus modules.
ATTENTION
Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements.
5
H Series Fieldbus PROFIBUS Adapter, Series A (PSSCPBA) E102P
Profibus Out
PSSCPBA
Adapter Status
Profibus Status
PointBus Status
System Power
Adapter Power
Profibus In
X10
PWR
X1
Profibus DP
PSSCPBA
Adapter Status Indicator
Profibus Status Indicator
PointBus Status Indicator
System Power Indicator
Adapter Power Indicator
TroubleshootwiththeIndicators
Indication Probable Cause Adapter Status
Off No power supplied Hardware check in progress Initialization in progress
Green Operating normally Red Hardware check fault
Indication Probable Cause
ProbusStatus
Off No power supplied Bus is off line
Green Bus is on line (data exchange) Flashing Green Adapter has received a CLEAR
command from the master Red Error in PROFIBUS initialization.
No modules installed in the backplane. Flashing Red 1Hz:
- Check_Configuration telegram rejected.
- Maximum number of I/O modules in master configuration overridden. 2Hz:
- SetPrm telegram rejected.
- The first byte in user parameter data does not equal zero.
- Maximum number of user parameter bytes overridden.
Indication Probable Cause PointBus Status
Off No power supplied Hardware check in progress Initialization in progress
Green Normal operation Flashing Red 1Hz:
- Incorrect I/O module installed.
- I/O module removed from backplane.
Red Critical link failure (BUS_OFF).
Indication Probable Cause
SystemPower*
Off Not active field. Power is off, overloaded backplane or dc-dc converter problem.
Green System power (5V) present.
Indication Probable Cause
AdapterPower**
Off Field power not applied. Green Field power (24V) applied.
* System Power Indicator shows the 5V power output from the dc-dc converter. ** Adapter Power Indicator shows the 24V power input to the dc-dc converter.
6
H Series Fieldbus PROFIBUS Adapter, Series A (PSSCPBA) E102P
Specications
Following are specifications for the PSSCPBA PROFIBUS adapter.
PROFIBUSAdapter-PSSCPBA
ExpansionI/OCapacity • PROFIBUSadapterbackplanecurrentoutput=1.0Amaximum. See the list below for backplane current consumption for each I/O catalog number and the current consumption for each of the modules connected to the PROFIBUS adapter. Verify that it is below 1.0A.
• Backplanecurrentcanbeextendedbeyond1.0AwithaPSSSE24ABackplane Extension Power Supply. The PSSSE24A can supply up to an additional 1.3A of backplane current.
• MultiplePSSSE24Amodulescanbeusedtoreachthe maximum of 63 modules.
Cat. No. PointBus Current Requirements PSSN8xxx 75 mA
PSSP8xxx 75 mA PSST8xxx 75 mA PSSTR4M12A 90 mA PSSNACM12A 75 mA PSSNAVM12A 75 mA PSSTACM12A 75 mA PSSTAVM12A 75 mA PSSS23A 75 mA PSSV32A 75 mA
PowerSupplySpecications
Power Supply Note: In order to comply with CE Low Voltage Directives (LVD), you must use either a NEC Class 2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to power this adapter. A SELV supply cannot exceed 30V rms, 42.4V peak or 60VDC under normal conditions and under single fault conditions. A PELV supply has the same rating and is connected to protected earth.
Input Voltage Rating 24VDC nominal 10-28.8VDC range
Input Overvoltage Protection Reverse polarity protected Inrush Current 6A maximum for 10ms PointBus Output Current 1A maximum @ 5VDC +5% (4.75-5.25
FieldSidePowerRequirements,Maximum 24VDC(+20%=28.8VDC)@400mA
Interruption Output voltage will stay within specifications when input drops out for 10ms at 10V with maximum load
GeneralSpecications
LED Indicators 1 green/red Adapter status 1 green/red PROFIBUS status 1 green/red PointBus status 1 green System Power (PointBus 5V power) 1 green Adapter Power (24V from field supply)
Power Consumption, Maximum 8.1W @ 28.8VDC Power Dissipation, Maximum 2.8W @ 28.8VDC Thermal Dissipation, Maximum 9.5 BTU/hr. @ 28.8VDC Isolation Voltage 50V rms
(continuous-voltage withstand rating) Tested at 1250VAC rms for 60s Field Power Bus
Nominal Voltage 24VDC Supply Voltage 10-28.8VDC range Supply Current 10A maximum
Dimensions Inches (Millimeters) 4.41H x 2.83W x 2.56D (112H x 72W x 65D)
7
H Series Fieldbus PROFIBUS Adapter, Series A (PSSCPBA) E102P
GeneralSpecications(continued)
Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F) Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F) Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5-95% non-condensing Shock IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g Non-operating 50g
Vibration IEC60068-2-6 (Test Fc, Operating): 5g @ 10-500Hz
ESD Immunity IEC 61000-4-2: 6kV contact discharges 8kV air discharges
Radiated RF Immunity IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
EFT/B Immunity IEC 61000-4-4: ±4kV at 5kHz on power ports ±2kV at 5kHz on communications ports
Surge Transient Immunity IEC 61000-4-5: ±1kV line-line(DM) and ±2kV line-earth(CM) on power ports ±2kV line-earth(CM) on shielded ports
Conducted RF Immunity IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Emissions CSPR 11: Group 1, Class A
Enclosure Type Rating Meets IP65/66/67 (when marked) Mounting Base Screw Torque #8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel Wiring Category
1
1 - on power ports
1 - on communications ports Weight Imperial (Metric) 0.80 lb. (0.36 kg) Certifications: (when product is marked) c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada CE European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity
C-Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
1. Use this Conductor Category information for planning conductor routing. Refer to Publication E115P, “Industrial Automation Wiring and Grounding Guidelines”.
8
Pneumatic Division
ControlNet
A
PSSCCNA
Adapter Status
PointBus Status
ControlNet A Status
ControlNet B Status
System Power
Adapter Power
ControlNet
B
X10
PWR
X1
PSSCCNA
TNC Style Connectors
Mini 7/8" Auxiliary Power Connector
Node Address Switches
!
!
Richland, Michigan 49083
WARNING
To avoid unpredictable system behavior that can cause personal injury and property damage:
• Disconnectelectricalsupply(whennecessary)beforeinstallation,
servicing, or conversion.
• Disconnectairsupplyanddepressurizeall airlinesconnected to
this product before installation, servicing, or conversion.
• Operatewithinthemanufacturer’sspeciedpressure,temperature,
and other conditions listed in these instructions.
• Medium must be moisture-free if ambient temperature is below freezing.
• Serviceaccordingtoprocedureslistedintheseinstructions.
• Installation, service, and conversion of these products must be performed by knowledgeable personnel who understand how
pneumatic products are to be applied.
• After installation, servicing, or conversion, air and electrical supplies(whennecessary)shouldbe connectedandthe product
tested for proper function and leakage. If audible leakage is present, or the product does not operate properly, do not put into use.
• Warnings and specifications on the product should not be
covered by paint, etc. If masking is not possible, contact your local representative for replacement labels.
Installation & Service Instructions E103P
H Series Fieldbus ControlNet Adapter, Series A (PSSCCNA)
ISSUED: February, 2016 Supersedes: December, 2006
Doc.# E103P, EN# 160064, Rev. D
Introduction
Follow these instructions when installing, operating, or servicing the product.
H Series Fieldbus ControlNet Adapter, Series A
(PSSCCNA)
The sealed IP67 housing of the adapter requires no enclosure. (Note that environmental requirements other than IP67 may require an additional appropriate housing.) ControlNet connectors are two redundant TNC style network connectors and one mini style power connector. The ControlNet adapter is shown below.
Safety Guide
For more complete information on recommended application guidelines, see the Safety Guide section of Pneumatic Division catalogs or you can download the Pneumatic Division Safety Guide at: www.parker.com/safety
H Series Fieldbus ControlNet Adapter User Manual
The H Series Fieldbus ControlNet Adapter User Manual PSS­UM003A-EN-P is not available at this time. Please refer to Rockwell Automation 1734 POINT I/O ControlNet Adapter User Manual 1734-UM008A-EN-P for similar setup information, which is available online at http://literature.rockwellautomation.com/.
WARNING
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.
This document and other information from Parker Hannifin Corporation, its subsidiaries and authorized distributors provide product and/or system options for further investigation by users having technical expertise. It is important that you analyze all aspects of your application, including consequences of any failure and review the information concerning the product or systems in the current product catalog. Due to the variety of operating conditions and applications for these products or systems, the user, through its own analysis and testing, is solely responsible for making the final selection of the products and systems and assuring that all performance, safety and warning requirements of the application are met.
The products described herein, including without limitation, product features, specifications, designs, availability and pricing, are subject to change by Parker Hannifin Corporation and its subsidiaries at any time without notice.
EXTRA COPIES OF THESE INSTRUCTIONS ARE AVAILABLE FOR INCLUSION IN EQUIPMENT / MAINTENANCE MANUALS THAT UTILIZE THESE PRODUCTS. CONTACT YOUR LOCAL REPRESENTATIVE.
H Series Fieldbus ControlNet Adapter, Series A (PSSCCNA) E103P
!
!
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the
Application, Installation and Maintenance of Solid State Controls
(available online at www.parker.com/pneu/hseriesfieldbus) describes some important differences between solid state equipment and hard­wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Parker Hannifin Corporation be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Parker Hannifin Corporation cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Parker Hannifin Corporation with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Parker Hannifin Corporation is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
ATTENTION
Environment and Enclosure
This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as “enclosed” equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
NOTE: See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the publication E115P (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.
WARNING Identifies information about practices or
circumstances that can cause an explosion in a hazardous environment, which may lead to
!
IMPORTANT
ATTENTION Identifies information about practices or
!
 • IdentifyaHazard
 • AvoidaHazard
 • RecognizetheConsequence
SHOCK HAZARD
BURN HAZARD Labels may be located on or inside the
personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
Labels may be located on or inside the
equipment to alert people that dangerous voltage may be present.
equipment to alert people that surfaces may be dangerous temperatures.
ATTENTION
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
 •Touchagroundedobjecttodischargepotentialstatic.  •Wearanapprovedgroundingwriststrap.  •Donottouchconnectorsorpinsoncomponentboards.  •Donottouchcircuitcomponentsinsidetheequipment.  •Ifavailable,useastatic-safeworkstation.  •Whennotinuse,storetheequipmentinappropriate
static-safe packaging.
2
H Series Fieldbus ControlNet Adapter, Series A (PSSCCNA) E103P
Inches
(mm)
Adapter
2.0
(50)
2.0
(50)
1.9
(47.2)
4.02
(102)
1.81 (46)
4.32
(109.8)
5.39
(137.0)
Drill and Tap
for M4 Screw
I/O Module Ground
2.39
(60.7)
3.02
(76.6)
3.13
(79.4)
5.98*
(151.9)
0.87 (22)
Drill and Tap
for M6 Screw
I/O Module Ground
Before You Begin
To effectively use your adapter, note the following considerations.
Understanding Messaging
Class 3 (Explicit Message) requests through the adapter to a specific I/O module may not always receive a response from the I/O module. In the case where the I/O module does not reply to the request, the adapter responds with an error code indicating a time-out.
Establish I/O Connections
When you power up an H Series Fieldbus I/O system and establish I/O connections, the outputs transition to the Idle state, applying Idle state data before going to RUN mode. This occurs even when the controller making the connection is already in RUN mode.
Mount the Adapter and I/O Base
To mount the adapter on a wall or panel, use the screw holes provided in the adapter.
A mounting illustration for the adapter with I/O bases is shown below.
CongureAutobaud
The adapter cannot reconfigure an I/O module that you previously configured to operate at a fixed baud rate. When you reuse an H Series Fieldbus I/O module from another H Series Fieldbus I/O system, configure the module to autobaud before using it with the adapter.
Grounding
Each H Series Fieldbus base has two mounting holes, with the one on the right being the means to ground each module. Each module must be grounded.
* Depending on the type and number of manifolds, this dimension
may vary. Refer to Catalog 0600P-# for additional information.
InstalltheMountingBaseasFollows:
1. Lay out the required points as shown above in the drilling dimension drawing.
2. Drill the necessary holes for #8 (M4) machine or self-tapping screws.
3. Mount the adapter using #8 (M4) screws.
4. Ground the system using the ground lug connection in the I/O base. (The ground lug connection is also a mounting hole.)
3
H Series Fieldbus ControlNet Adapter, Series A (PSSCCNA) E103P
Set the Node Address
To set the node address, adjust the switches on the front of the module (refer to the illustration on page 1). Use a small blade screwdriver to rotate the switches. Line up the small notch on the switch with the number setting you wish to use. The two switches are most significant digit (MSD) and least significant digit (LSD). The switches can be set from 01 through 99. The module reads the switches at power-up only.
This example shows the node address set at 63.
The rotary switches are read periodically. If the switches have been changed since the last time they were read and they no longer match the on line address, a minor fault will occur, which is indicated by a flashing red Adapter Status LED.
EDS File Requirements
The EDS file is available online at www.parker.com/pneu/ hseriesfieldbus
Add ControlNet Adapter to RSLogix 5000
I/OConguration
To add your PSSCCNA to RSLogix 5000 I/O configuration, follow these steps:
 •InRSLogix5000,highlighttheControlNet Scanner, right click
and select New Module.
 •ChooseNext to set RPI.  •ChooseFinish. Notice that the PSSCCNA is now under the I/O
configuration.
If your RSLogic 5000 is Version 13.X:
 •Choosethe1738-ACNR/A from the list of modules.
 •Entera name,anappropriate nodeaddress,and chassissize.
Make sure to choose Compatible Module for Electronic Keying setting.
If your RSLogic 5000 is Version 15.X or greater:
 •ChoosethePSSCCNA module from the list of Parker modules.
 •Enteraname,anappropriateaddressandchassissize.
 •ChooseNext to set RPI.  •ChooseFinish. Notice that the 1738-ACNR is now under the
I/O configuration
4
H Series Fieldbus ControlNet Adapter, Series A (PSSCCNA) E103P
!
Male In Connector
Wire the ControlNet Adapter
Following are wiring instructions for the ControlNet Adapter.
TNC Cables
 • ConnectTNCcablestoChannelAorBforsinglemedia.  • ConnectTNCcablestoChannelAandBforredundantmedia.
PSSCCNAAuxiliaryPower(Mini7/8")
(view into connector) Pin 1 - User Power + Pin 2 - Adapter Power + Pin 3 - Adapter Power ­Pin 4 - User Power -
NOTE: User power is the 24VDC power for field devices. Adapter power is the 24VDC power for adapter. It is converted to
5VDC to power H Series Fieldbus modules
ATTENTION
Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements.
5
Loading...
+ 314 hidden pages