Panasonic S-07MM2U6, S-09MM2U6, S-12MM2U6, S-15MM2U6, S-18MM2U6 installation

INSTALLATION INSTRUCTIONS
VRF System Air Conditioner
This air conditioner uses the refrigerant R410A.
Model No.
Indoor Units
Type Indoor Unit Type
7 9 12 15 18
Read through the Installation Instructions before you proceed with the installation. In particular, you will need to read under the “IMPORTANT!” section at the top of the page.
Nominal Capacity
F616519
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
This air conditioner shall be installed in accordance with
National Wiring Regulations.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or
WARNING
CAUTION
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over-
heating at connection points and a possible fire hazard.
• To prevent possible hazards from insulation failure,
the unit must be grounded.
• This equipment is strongly recommended to be installed
with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD). Otherwise, it may cause electrical shock and fire in case of equipment breakdown or
insulation breakdown.
unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
When Wiring
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
Select an installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
Keep the fire alarm and the air
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
outlet at least 5 feet (1.5 m) away from the unit.
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
WARNING
• When performing piping work do not mix air except for specified refrigerant (R410A) in refrigeration cycle. It causes capacity down, and risk of explosion and injury due to high tension
inside the refrigerant cycle.
• Check for a leaking refrigerant! Refrigerant gas may produce a toxic gas if it
comes in contact with fire.
• Do not add or replace refrigerant other than specified type. It may cause product damage, burst and injury etc.
2
• Do not leak refrigerant while piping work for an installation or re-installation, and while repairing refrigeration parts. Handle liquid refrigerant carefully as it may cause
frostbite.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
CAUTION
• Do not touch the air inlet or the sharp aluminum fins of the outdoor unit. You may get injured.
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
WARNING
• This product must not be modified or disassembled under any circumstances. Modified or disassembled unit may cause fire, electric shock or injury.
• Do not clean inside the indoor and outdoor units by users. Engage authorized dealer or specialist for cleaning.
• In case of malfunction of this appliance, do not repair by yourself. Contact to the sales dealer or service dealer for a repair.
Check of Density Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent. With the recent increase in the number of high density buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).
Others
CAUTION
• Do not sit or step on the unit, you may fall down accidentally.
• Do not touch the air inlet or the sharp aluminum fins of the outdoor unit. You may get injured.
• Do not stick any object into the FAN CASE. You may be injured and the unit may be damaged.
ASHRAE and the International Mechanical Code of the ICC as well as CSA provide guidance and define safeguards related to the use of refrigerants, all of which define a Refrigerant Concentration Level (RCL) of 25 pounds (11.3 kg) per 1,000 cubic feet (28.3 m3) for R410A refrigerant. For additional guidance and precautions related to refrigerant safety, please refer to the following documents:
International Mechanical Code 2012 (IMC-2012) (or more recently revised) ASHRAE 15 ASHRAE 34
3
CONTENTS
Page Page
IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Please Read Before Starting
1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Unit
1-3. Type of Copper Tube and Insulation Material
1-4. Additional Materials Required for Installation
2. SELECTING THE INSTALLATION SITE . . . . . . . . . 6
Indoor Unit
8. HOW TO INSTALL WIRELESS REMOTE
CONTROLLER RECEIVER . . . . . . . . . . . . . . . . . . 19
N OT E
Refer to the Operating Instructions attached to the optional Wireless Remote Controller Receiver.
9. EXTERNAL STATIC PRESSURE SETTING . . . . . 20
9-1. How to Set on PC Board
9-2. Operating the Timer Remote Controller (CZ-
RTC2)
9-3. Operating the High-spec Wired Remote
Controller (CZ-RTC3)
3. HOW TO INSTALL THE INDOOR UNIT . . . . . . . . . . 7
Slim Low Static Ducted Type (Type M2) . . . . . . . . . 7
3-1. Required Minimum Space for Installation and
Service
3-2. Preparations Before Installation
3-3. For Bottom Intake
3-4. Installing the Duct
3-5. Suspending the Indoor Unit
3-6. Installing the Drain Pipe
3-7. Checking the Drainage
4. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . 12
4-1. General Precautions on Wiring
4-2. Recommended Wire Length and Wire
Diameter for Power Supply System
4-3. Wiring System Diagrams
5. HOW TO PROCESS TUBING . . . . . . . . . . . . . . . . 16
5-1. Connecting the Refrigerant Tubing
5-2. Connecting Tubing Between Indoor and Outdoor
Units
5-3. Insulating the Refrigerant Tubing
5-4. Taping the Tubes
5-5. Finishing the Installation
10. APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Names of Parts
Care and Cleaning
Troubleshooting
Tips for Energy Saving
6. PRECAUTIONS ON TEST RUN . . . . . . . . . . . . . . 19
7. HOW TO INSTALL THE TIMER REMOTE CONTROLLER (CZ-RTC2) OR HIGH-SPEC WIRED REMOTE CONTROLLER (CZ-RTC3)
(OPTIONAL PART) . . . . . . . . . . . . . . . . . . . . . . . . 19
N OT E
Refer to the Operating Instructions attached to the optional Timer Remote Controller or optional High­spec Wired Remote Controller.
4
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Flathead screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or keyhole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
Part Name Figure Q’ty Remarks
Washer 8 For suspension fitting
For gas pipe /
1
Flare insulator
liquid pipe connection
For gas pipe /
1
liquid pipe connection
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16”(8 mm).
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 4. ELECTRICAL WIRING for details.
CAUTION
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
Clamper
Drain hose insulation
Drain hose
L=131
Hose band
Short-circuit connection
4 For flare connection
For drain pipe
2
connection
For unit & PVC pipe
1
connection
For drain hose
2
connection
For high static pressure (Located on the
1
back of the electrical component box lid. )
Use 3/8”(M10) for suspension bolts.
Suspension bolts and nuts are field supply.
5
2. SELECTING THE INSTALLATION SITE
Indoor Unit
AVOID:
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room directly. This may cause “condensation” on the air discharge ports, causing them to spray or drip water.
locations where the remote controller will be splashed with water or affected by dampness or humidity.
installing the remote controller behind curtains or furniture.
locations where high-frequency emissions are generated.
DO:
select an appropriate position from which every corner of the room can be uniformly cooled.
select a location where the ceiling is strong enough to support the weight of the unit.
select a location where tubing and drain pipe have the shortest run to the outdoor unit.
allow room for operation and maintenance as well as unrestricted air flow around the unit.
install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in the installation manual packed with the outdoor unit.
allow room for mounting the remote controller about
3.3 ft. (1 m) off the floor, in an area that is not in direct sunlight nor in the flow of cool air from the indoor unit.
The elevation (Slim Low Static Ducted) between the bottom unit and the floor surface should be at least 8 feet (2.4 m).
If the elevation (Slim Low Static Ducted) between them is less than 8 feet (2.4 m), install a filter or a protective device (field supply) not to touch the electrical parts or fan with hands.
8 feet (2.4 m) or more
Floor
● If the indoor unit is installed on the ceiling where the temperature or humidity inside is high (over 86°F(30°C)/RH: 70%), add insulating material to the surface of the unit to avoid dew condensation.
6
Fig. 2-1
3. HOW TO INSTALL THE INDOOR UNIT
25-13/64 (640)
Slim Low Static Ducted Type (Type M2)
3-1. Required Minimum Space for Installation and
This air conditioner is usually installed above the
The minimum space for installation and service is
*H dimension means the minimum height of the unit.
Select the *H dimension such that a downward slope
The diagram shows the detailed dimensions of the
Service
ceiling so that the indoor unit and ducts are not visible. Only the air intake and air outlet ports are visible from below.
shown in the diagram. (Fig. 3-1)
of at least 1/100 is ensured as indicated in “3-6. Installing the Drain Pipe”.
indoor unit. (Fig. 3-2)
6
(145)
5-45/64
1-9/64 (29)
Flange for air outlet duct
22-13/64 (564)
(Suspension bolt pitch)
(194)
7-41/64
1-1/2 (38)
(126)
4-61/64
(Flange for air outlet duct)
25-13/64 ((6-19/64)x4)
(Suspension bolt pitch)
27-1/4 (692)
640 (160x4)
5-ø1/8 (ø3.1(Hole))
29-17/32 (750)
32-7/16 (824)
26-49/64 (680)
3-51/64 (96)
2-19/32 (66)
1-1/32 (26)
(27)
1-1/16
4
Inspection access
(17-23/32”x17-23/32”)
(Field supply)
1-29/64 (37)
5-29/32 (150)
5
10
9
(450x450)
7
32-7/16” (824)
(Suspension bolt pitch)
Min. 7-7/8”
(200) or more
Min. 4” (100 mm) or more for bottom air intake
Refrigerant tubing joint (liquid tube)
1
Refrigerant tubing joint (gas tube)
2
Upper and bottom drain port (O.D.1.05 inch (26.7 mm))
3
Suspension lug
4
Power supply outlet (for conduit ø7/8” (ø22 mm))
5
Flange for air outlet duct
6
Cover plate
7
Electrical component box
8
Filter
9
Control wiring outlet (for inter-unit control wiring, group control wiring
0
and remote controller wiring)(ø11/16” (ø17 mm))
(564)
22-13/64”
Flange for air outlet duct
Min. 25/32” (20) or more
Min. 25/32” (20) or more
1-7/64 (28) 1-3/16 (30)
3-3/16 (81)
Min. 7-7/8” (200) or more
Refrigerant tubing
Min. 25-5/8” (650)
3-5/16
7
1
Water inlet
2
1-19/64 (33) 6-1/32 (153)
8
5-29/32
(150)
7-7/8 (200)
55/64 (22)
1-37/64 (40)
(155)
6-7/64
4-23/32
(23)
19/32
29/32
(23)
35/64 (14)
(120)
5-13/64
(15)
10-ø1/8 (ø3.1)(Hole)
35/64 (14)
8-21/32
(132)
(220)
27-23/32 (704)(29/32)
* Filter Uninstalled
8-21/32
(220)
Electrical component box
Inspection
access
17-23/32”
x
17-23/32”
(450x450)
or more
Unit: inch (mm)
(200)
7-7/8”
*H=Min. 9-1/2”
Ceiling
Unit: inch (mm)
2-ø1/8 (ø3.1)
(Hole)
(84)
25/64 (10)
5-5/8
(143)
3-5/32 (80)
3
5-13/64
(132)
29/32 (23)
*H=Min. (240)
Fig. 3-1
1-3/16 (30)
9-3/8 (238)1-47/64 (44)
35/64 (14)
Fig. 3-2
3-2. Preparations Before Installation
(1) Confirm the positional relationship between the unit and
suspension bolts. (Fig. 3-3)
Install the inspection opening on the control box side
where maintenance and inspection of the control box and drain pump are easy. Install the inspection opening also in the lower part of the unit.
3-3. For Bottom Intake
For bottom intake, replace the cover plate and Frame Filter Assy net in the procedure shown in the diagram.
(1) Remove the frame filter assy.
Remove the cover plate. (Fig. 3-4)
Air intake
Air discharge Air intake
A
(Inspection access)
27-1/2 (700)
Ceiling
Allow view A
Inspection access
(Field supply)
31-1/2 (800)
Unit: mm
Fig. 3-3
(2) Make sure the range of the unit’s external static
pressure is not exceeded. (See the technical documentation for the range of the external static pressure setting.)
(3) Open the installation hole. (Pre-set ceilings)
Once the installation hole is opened in the ceiling
where the unit is to be installed, pass refrigerant piping, drain piping, inter-unit control wiring, and remote controller wiring to the unit’s piping and wiring holes. See “5. HOW TO PROCESS TUBING”, “3-6. Installing the Drain Pipe” and “4. ELECTRICAL WIRING”.
After opening the ceiling hole, make sure ceiling is
level if needed. It might be necessary to reinforce the ceiling frame to prevent shaking. Consult an architect or carpenter for details.
Frame Filter Assy
Cover plate
Air discharge
Dummy hole
Fig. 3-4
(2) Refer to the diagram to attach the cover plate and
frame filter assy in the direction of the arrow. (Fig. 3-5) Note: Attach the cover plate with the dummy holes downward.
Dummy hole
Cover plate
Frame Filter Assy
Air discharge
Air intake
Fig. 3-5
(3) Attach the frame filter assy (supplied) in the manner
shown in the diagram. (Fig. 3-6)
Main unit
Attach the Frame Filter Assy to the main unit while pushing the tip of the latches in the direction of the arrow.
Frame Filter Assy
In case of bottom side In case of back side
8
Fig. 3-6
3-4. Installing the Duct
Connect the duct supplied in the field as shown in Fig. 3-7.
Flange
(Field supply) Connection screw (x10) Rectangular solid duct
(Field supply)
Main unit
Flange
Insulation material
(Field supply)
Hole-in-anchor Hole-in-plug
Suspension bolt
(M10 or 3/8”) (field supply)
Concrete
Insert
Ceiling tiles
Ceiling support
Air inlet side
Air outlet side
Fig. 3-7
Air inlet side
Attach the duct and intake-side flange (field supply).
Connect the flange to the main unit with 10 - ø1/8”
(ø3.1) (Hole) screws.
Wrap the intake-side flange and duct connection area with aluminum tape or something similar to prevent air escaping.
CAUTION
When attaching a duct to the intake-side, be sure to attach an air filter inside the air passage on the intake-side. (Use an air filter whose dust collecting efficiency is at least 50% in a gravimetric technique.) The included filter is not used when the intake duct is attached.
Air outlet side
Connect the duct according to the air outside of the
outlet-side flange.
Wrap the outlet-side flange and the duct connection area with aluminum tape or something similar to prevent air escaping.
CAUTION
Fig. 3-8 Fig. 3-9
WARNING
It is important that you use extreme care in supporting the indoor unit inside the ceiling. Ensure that the ceiling is strong enough to support the weight of the unit. Before hanging the unit, test the strength of each attached suspension bolt.
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts referring to the dimensional data as shown in Fig. 3-1. Tubing must be laid and connected inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the tubing into position for connection to the unit before placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to protrude
from the ceiling as shown in Fig. 3-8. (Cut the ceiling material, if necessary.)
(3) Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the 4 suspension bolts as shown in Fig. 3-10 and 3-11. Use 1 nut and 1 washer for the upper part, and 2 nuts and 1 washer for the lower part, so that the unit will not fall off the suspension lugs.
Nuts and washers (use for upper and lower)
Suspension bolt
Suspension lug
Suspension bolt
Be sure to insulate the duct to prevent condensation
from forming. (Material: glass wool or polyethylene foam, 1 inch (25 mm) thick)
Use electric insulation between the duct and the wall
when using metal ducts to pass metal laths of the net or fence shape or metal plating into wooden buildings.
Be sure to explain about the way of maintaining and
cleaning local procurements (air filter, grille [both air outlet and suction grille], etc.) to your customer.
3-5. Suspending the Indoor Unit
Depending on the ceiling type:
Insert suspension bolts as shown in the diagram.
(Fig. 3-8) or
Use existing ceiling supports or construct a suitable
support as shown in the diagram. (Fig. 3-9)
Double nuts
Fig. 3-10
9
Notch
Hexagonal nut
Double nuts
Fig. 3-11
Loading...
+ 19 hidden pages