Thank you for the purchase of Temperature controller KT9.
This manual contains instructions for the mounting, functions, operations and notes when
operating the KT9.
For model confirmation and unit specifications, please read this manual carefully before
starting operation.
To prevent accidents arising from the misuse of this controller, please ensure the
operator receives this manual.
Notes
• This instrument should be used according to the specifications described in t he manual.
If it is not used according to the specifications, it may malfunction or cause fire.
• Be sure to follow the warnings, cautions and notices. If they are not observed, it could cause
serious injury or accidents.
• The contents of this instruction manual are subject to change without notice.
• Care has been taken to assure that the contents of this instruction manual are correct, but if
there are any doubts, mistakes or questions, please inform our sales department.
• This instrument is designed to be installed in a control panel. If it is not, measures must be
taken to ensure that the operator cannot touch power terminals or other high voltage
sections.
• Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
• Matsushita Electric Works, Ltd. is not responsible for any damage or secondary damage(s)
incurred as a result of using this product, including any indirect damage.
• To pull out the inner assembly, release the hooks at the top and bottom of the instrument
with thin, hard tweezers. (If the hooks are released too far, they may be broken, or IP66
function could deteriorate. Do not pull out the inner assembly except when repairing the
instrument.)
SAFETY PRECAUTIONS
(
Be sure to read these precautions before using our products.
The safety precautions are classified into categories: “Warning” and “Caution”.
Depending on circumstances, procedures indicated by
results, so be sure to follow the directions for usage.
Warning
Procedures which may lead to dangerous conditions and cause death or serious
injury, if not carried out properly.
Caution
Procedures which may lead to dangerous conditions and cause superficial to medium
injury or physical damage or may degrade or damage the product, if not carried out
properly.
This instrument is intended to be used under the following environmental conditions
(IEC61010-1): Overvoltage category
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50
that does not change rapidly
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current
is flowing
• No water, oil or chemicals or where the vapors of these substances can come into
direct contact with the unit
Note: Do not install this instrument near flammable material even though the case of
this instrument is made of flame-resistant resin.
Avoid setting this instrument directly on flammable material.
s
, Pollution degree 2
(32 to 122 )
22.. WWiirriinngg pprreeccaauuttiioonns
Caution
• Use the solderless terminal with an insulation sleeve that fits in the M3 screw when
wiring the KT9 Series.
• The terminal block of this instrument is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened with
the terminal screw.
• Tighten the terminal screw within the specified torque.
If excessive force is applied to the screw when tightening, the terminal screw or
case may be damaged.
• Do not apply a commercial power source to the sensor which is connected to the
input terminal nor allow the power source to come into contact with the sensor.
• This controller does not have built-in power switch, circuit breaker or fuse.
It is necessary to install them near the controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC po wer source, do not confuse polarity when using direct current (DC).
(1) Supply voltage ---------------------- 1: 100 to 240V AC 2: 24V AC/DC
(2) Input type ----------------------------- 1: Multi-input (Thermocouple, RTD, DC current
and DC voltage can be selected
by keypad operation)
(3) Control output (OUT1) ----------- 1: Relay contact 2: Non-contact voltage
3: DC current
(4) Alarm output ------------------------- 1: A1 output 2: A1 output + A2 output
(5) Heating/Cooling control (OUT2) output:
0: Not available 1: Relay contact
2: Non-contact voltage 3: DC current
(6) Heater burnout alarm ------------- 0: Not available 1: Available (5A) 2: Available
(10A) 3: Available (20A) 4: Available (50A)
(Heater burnout alarm is not available for the DC
current output)
(7) Serial communication ------------- 1: Applied (The number is added only when Serial
communication is applied.)
1
(The alarm type and Energized /Deenergized
can be selected by keypad operation)
Indicates the PV (process variable) with a red LED.
Indicates the SV (main set value) or MV (manipulated variable) with a green LED.
The green LED lights when SV1 is selected.
The green LED lights when SV2 is selected.
When OUT1 or Heating output is on, the green LED lights.
(For the DC current output type, this flashes corresponding to the output manipulated
variable in 0.25 second cycles)
When OUT2 is on, the yellow LED lights.
(For the DC current output type, this flashes corresponding to the output manipulated
variable in 0.25 second cycles)
When Heater burnout alarm output or sensor burnout alarm output is on, the red LED lights.
(When Heater burnout alarm is added and if indication is overscale or underscale,
the red LED lights as well)
The yellow LED flashes during auto-tuning or auto-reset.
(9) TX/RX indicator
The yellow LED flashes during Serial communication.
(10) A1 indicator
When A1 output is on, the red LED lights.
(1 1) A2/LA indicator
When A2 output is on, the red LED lights.
(12) Increase key: Increases the numeric value.
(13) Decrease key: Decreases the numeric value.
(14) Mode key: Selects the setting mode or registers the set value.
(By pressing the Mode key, the set value or selected value can be registered.)
(15) OUT/OFF key
• If OUT/OFF function is selected during OUT/OFF function selection, the control out put
is turned on or off.
Once the control output OFF function is enabled, the function cannot be released ev en
if the power to the instrument is turned OFF and turned ON again.
To cancel the function, press the OUT/OFF key again for approx. 1 second.
If Auto/Manual control function is selected from OUT/OFF function selection, automatic
•
control is performed when the power to the controller is turned on. In this status, if the
OUT/OFF key is pressed, the automatic control output is switched to manual control
output and vice versa. However, this function can be switched only in the PV/SV
display mode.
Notice
When setting the specifications and functions of this controller, connect terminals 2
and 3 for power source first, then set them referring to “5. Setup” before performing “3.
Mounting to the control panel” and “4. Wiring”.
3.1 Site selection
This instrument is intended to be used under the following environmental
conditions (IEC61010-1): Overvoltage category
, Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
(1) A minimum of dust, and an absence of corrosive gases
(2) No flammable, explosive gases
(3) No mechanical vibrations or shocks
(4) No exposure to direct sunlight, an ambient temperature of 0 to 50
(32 to 122
) that does not change rapidly
(5) An ambient non-condensing humidity of 35 to 85%RH
(6) No large capacity electromagnetic switches or cables through which large
current is flowing
(7) No water, oil or chemicals or where the vapors of these substances can
come into direct contact with the unit
3.2 External dimensions (Unit: mm)
Gasket
Screw type mounting bracket
Terminal cover
96
96
(Fig. 3.2-1)
3.3 Panel cutout (Unit: mm)
130
11.5
n×96-3
98.5
104.5
(*): When terminal cover is used
0
+0.8
□92
+0.5
0
Lateral close mounting
n: Number of units mounted
91
106.2
IP66 specification may be compromised, and all
□92
+0.8
0
Caution: If lateral close mounting is used for the controller,
As the case is made of resin, do not use excessive force while screwing in the
mounting bracket, or the case or screw type mounting bracket could be damaged.
The torque is approximately 0.12N•m.
Mount the controller vertically to the flat, rigid panel to ensure it adheres to the
Dust-proof/Drip-proof specification (IP66).
Mounting panel thickness: 1 to 15mm.
Insert the instrument from the front side of the panel.
Attach the mounting bracket by the holes at the top and bottom of the case and sec u re
in place with the sc re ws .
Turn the power supply to the instrument off before wiring or checking.
Working or touching the terminal with the power switched on may result in
severe injury or death due to Electric Shock.
Moreover, the instrument must be grounded before the power supply to the
instrument is turned on.
4.1 Terminal arrangement
• OUT1 : Control output 1
(Heating output)
• OUT2 : Control output 2
(Cooling output)
• RELAY : Relay contact output
Warning
• V/A : Non-contact voltage
output/DC curren t ou tput
• The terminal block of KT9 series is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened
with the terminal screw.
• Dotted lines show options.
• If A2 (option) and Heater burnout alarm (option) are applied together, use
terminals 12-13 for A2, and 9-10 for the Heater burnout alarm.
• If the Heating/Cooling control (option) and Heater burnout alarm (option) are
applied together, use terminals 9-10 for the Heating/Cooling control, and 12-13
for the Heater burnout alarm.
Lead wire solderless terminal
Use a solderless terminal with an insulation sleev e in which an M3 screw fits as shown
below.
• Use a thermocouple and compensating lead wire according to the sensor input
specifications of this cont ro l l er.
• Use the 3-wire RTD according to t he sensor input sp ec ifi c ations of t h is cont r oll e r.
• This controller does not have built-in power switch, circuit breaker or fuse.
It is necessary to install them i n t he circuit near the external controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
• When using a relay contact output type, use a relay externally according to the
capacity of the load to protect the buil t-in relay contact .
• When wiring, keep the input wire (Thermoc ouple, RTD, etc.) away from AC sources
or load wires to avoid external interference.
For the thermocouple and RTD input, the sensor input charact ers and temperature unit
are indicated on the PV display and the input range high limit value is indicated on the SV
display for approx. 3 seconds after the power is turned on. See (Table 5-1).
For DC input, the sensor input characters are indicated on the PV display and the scaling
high limit value is indicated on the SV display. See (Table 5-1).
If any other value is set during the scaling high limit setting, the set value is indicated on
the SV display.
During this time, all outputs and the LED indicators are in OFF status.
Control will then start and the PV (process variable) will be indicated on the PV display
and SV1 or SV2 will be indicated on the SV display.
While control output OFF function is working,
release the function, press the OUT/OFF key for approx. 1 second.
To
(Table 5-1)
Sensor input
K
J
R
S
B
E
T
N
PL-
C (W/Re5-26)
Pt100
JPt100
4 to 20mA DC
0 to 20mA DC
0 to 1V DC
0 to 10V DC
1 to 5V DC
0 to 5V DC
PV displaySV displayPV displaySV display
is indic ated on the PV display.
Scaling high limit value
15
Page 16
[
]
y
pp
5.1 Operation flow chart
Outline of operation procedure
Operation before running
[Step 1 Initial setting]: Set Input type, Alarm type, control action,
etc. in Auxiliary function setting mode 2.
[Step 2 Adjusting item] : Set PID values and Alarm values in the
Sub setting mode.
[Step 3 Lock setting]: Set the Set value Lock, SV high limit and SV low
[Step 4 Run setting] : Set SV1 (desired value) in the Main setting mode.
limit in Auxiliary function setting mode 1 (If Step 3
is not necessary, skip this step.)
Control output OFF function or
Auto/Manual control function
Press key for approx. 1sec.
PV/SV display
Alarm 1 (A1) setting procedure
[Numbers (1) to (5) are indicated on the flow chart.]
(1) [A1 type]: Select an alarm type
[If an alarm type except for
are indicated and they can be set if necessary.]
output ON (Ene rgized:
(3) [A1 hysteresis]: Set A1 hysteresis.
(4) [A1 action delayed timer]: Set A1 action delayed time.
(If input enters alarm action range and setting times has passed,
the alarm is activated.)
(5) [A1 value]: Set action point of A1 output.
[Note] If an alarm type is changed, the alarm set value
becomes 0 (0.0). Therefore it is necessary to reset it.
Press the ke
Press the key
for approx. 3sec.
is selected, items (2) to (5)
) or OFF (Deenergized: ).
.
Output MV indication
Press the key.
[Main setting mode] [Sub setting mode]
SV1 (Desired value)
PV
SV
SV
SV2 (Desired value)
PV
Reverts to PV/SV display.
SV
SV
Explanation of key
: This means that
is pressed, the set
if
value is saved, and the
controller proceeds to the
next setting item.
PV
OUT1 proportional
PV SV
OUT2 proportional
PV SV
PV SV
PV SV
PV
OUT1 proportional
PV SV
OUT2 proportional
PV SV
(5)
PV SV
Press the while holding down the key.
AT/Auto-reset
SV
/
Selection
band
Set value
band
Set value
Integral time
Set value
Derivative time
Set value
ARW
SV
Set value
cycle
Set value
cycle
Set value
A1 value
Set value
• If AT is cancelled during the process,
PID values revert to previous value.
• Auto-reset is automatically cancelled
in 4 minutes.
• Set the value with , keys.
• ON/OFF action when set to 0 or 0.0
• Set the value with , keys.
• Available when Heating/Cooling
control (OUT2) is added
• Set the value with , keys.
• PD action when set to 0, and auto-
reset can be performed.
• Set the value with , keys.
• PI action when set to 0
• Set the value with , keys.
• Available for PID action
• Set the value with , keys.
• Not available for DC current output or
when OUT1 is ON/OFF action
• Set the value with , keys.
• Not available when OUT2 is ON/OFF
action
• Set the value with , keys.
• Not available if
during A1 type selection
is selected
Press for a
Auxiliary function setting mode 1
Set value Lock
PV
PV
PV
Sensor correction
PV
Communication protocol
PV SV
Instrument number
PV
Communication speed
PV
PV
PV
SV
Selection
SV high limit
SV
Set value
SV low limit
SV
Set value
SV
Set value
Selection
SV
Set value
SV
Selection
Parity
SV
Selection
Stop bit
SV
Selection
rox. 3sec while holdingdown .
• Make a selection with
keys.
• If Lock 1 or Lock 2 is selected,
AT or Auto-reset does not work.
• Be sure to select Lock 3 when
using Serial communication.
• Set the value with
• Set the value with , keys.
• Set the value with
• Make a selection with, keys.
• Not available for
• Set the value with , keys.
• Make a selection with, keys.
• Make a selection with, keys.
• Not available if
during Communication protocol
selection
•
Make a selection with, keys.
• Not available if
during Communication protocol
selection
,
, keys.
, keys.
indication
is selected
is selected
A2 value
PV SV
Set value
• Set the value with , keys.
• Not available if
during A2 type selection
is selected
Reverts to the PV/SV display.
Setting items with dotted lines are optional
Heater burnout alarm value
PV
.
SV
Set value
• Set the value with
• OFF when set to 0.0
, keys.
and they appear only when the options are
added.
Reverts to the PV/SV display.
16
Page 17
[
Input type (character indication) and range
K –200 to 1370 :
–199.9 to 400.0
J –200 to 1000
R 0 to 1760
S 0 to 1760
B 0 to 1820
E –200 to 800
T –199.9 to 400.0
N –200 to 1300
0 to 1390 :
PLC
(W/Re5-26) 0 to 2315 :
Pt100 –199.9 to 850.0 :
JPt100 –199.9 to 500.0 :
Pt100 –200 to 850
JPt100 –200 to 500
:
:
:
:
:
:
:
:
:
:
K –320 to 2500
–199.9 to 750.0 :
J –320 to 1800
R 0 to 3200 :
S 0 to 3200 :
B 0 to 3300 :
E –320 to 1500 :
T –199.9 to 750.0 :
N –320 to 2300 :
PL- 0 to 2500 :
C(W/Re5-26) 0 to 4200 :
Pt100 –199.9 to 999.9 :
JPt100 –199.9 to 900.0 :
Pt100 –300 to 1500
JPt100 –300 to 900 :
4 to 20mA DC –1999 to 9999:
0 to 20mA DC –1999 to 9999:
0 to 1V DC –1999 to 9999:
0 to 5V DC –1999 to 9999:
1 to 5V DC –1999 to 9999:
0 to 10V DC –1999 to 9999:
:
:
:
Alarm type
High limit alarm: The alarm action is deviation setting from the SV. The alarm is activated
if the input value reaches the high limit set value. Character indication:
Low limit alarm: The alarm action is
deviation setting to the SV. The alarm is activated
if the input value goes under the low limit set value. Character indication:
High/Low limits alarm: Combines High limit and Low limit alarm actions. When input value
reaches high limit set value or goes under the low limit set value, the alarm is
activated. Character indication:
High/Low limit range alarm: When input value is between the high limit set value and low
limit set value, the alarm is activated. Character indication:
Process alarm: Within the scale range of the controller, alarm action points can be set
at random and if the input reaches the randomly set action point, the alarm is
activated.
Character indication: Process high alarm
, Process low alarm
Alarm with standby function: When the power to the controller is turned on, even if the input
enters the alarm action range, the alarm is not activated. (If the controller is
allowed to keep running, once the input exceeds the alarm action point, the
standby function will be released.)
Character indication:
High limit alarm with standby : Low limit alarm with standby : High/Low limits alarm with standby :
PV
Scaling high limit
PV
Scaling low limit
PV
Decimal point place
PV
PV
OUT1 high limit
PV
Press the and keys for approx. 3sec.
Auxiliary function setting mode 2]
Input type
SV
Selection
SV
Set value
SV
Set value
SV
Selection
PV filter time
constant
SV
Set value
SV
Set value
• Make a selection with the
• Default value:
• Set the value with the
• Available for DC current, DC voltage input
• Set the value with the
• Available for DC current, DC voltage input
• Make a selection with the
• Available for DC current, DC voltage input
• Set the value with the
• Set the value with the
• Not available for ON/OFF action
, keys.
, keys.
, keys.
, keys.
, keys.
, keys.
(1)
PV
PV
A1 action Energized/
(2)
Deenergized setting
PV
A2 action Energized/
Deenergized
PV
(3)
(4)
A1 hysteresis
PV SV
A2 hysteresis
PV SV
A1 action delayed
PV SV
A1 type
SV
A2 type
SV
SV
SV
timer
Selection
Selection
Selection
Selection
Set value
Set value
Set value
• Make a selection with the , keys.
• Default value:
• Make a selection with the , keys.
• Available when A2 is added
• Make a selection with the , keys.
• Not available if
is selected during A1
type selection
• Make a selection with the , keys.
• Not available if
is selected during A2
type selection
• Set the value with the , keys.
• Not available if
type selection
• Set the value with the , keys.
• Not available if
type selection
is selected during A1
is selected during A2
• Set the value with the , keys.
• Not available if
is selected during A1
type selection
OUT1 low limit
PV
OUT1 ON/OFF action
hysteresis
PV
OUT2 action mode
PV
PV
PV
PV
OUT2 high limit
OUT2 low limit
Overlap/Dead band
OUT2 ON/OFF action
hysteresis
PV
SV
Set value
SV
Set value
SV
Selection
SV
Set value
SV
Set value
SV
Set value
SV
Set value
• Set the value with the
• Not available for ON/OFF action
• Set the value with the
, keys.
, keys.
• Available for ON/OFF action
• Make a selection with the , keys.
• Available when Heat/Cool control (OUT2) is added
• Set the value with the
• Available when Heat/Cool control (OUT2) is added
• Set the value with the
, keys.
, keys.
• Available when Heat/Cool control (OUT2) is added
• Set the value with the
, keys.
• Available when Heat/Cool control (OUT2) is added
• Set the value with
, keys.
• Available when Heat/Cool control (OUT2) is added
17
A2 action delayed
timer
PV SV
Direct/Reverse control
PV
PV SV
Setting item not used
PV SV
SV2 indication
PV
AT bias
Set value
SV
Selection
Set value
Set value
SV
Selection
Output status selection
when input abnormal
PV
OUT/OFF key function
PV
SV
Selection
SV
Selection
Reverts to the PV/SV display.
• Set the value with the , keys.
• Not available if
is selected during A2
type selection
• Make a selection with the , keys.
• Default value:
• Set the value with the , keys.
• Available for thermocouple, RTD input
• Do not set this item even if is indicated
on the PV display.
• Selects whether SV2 is indicated or not.
• Default value:
(Indication)
• Make a selection with the , keys.
• Available only when input is DC current and DC
voltage with DC current output.
MV is indicated on the SV display.
While the output MV is indicated, the 1st decimal point from t he right on the SV
display flashes in 0.5 second cycles.
By pressing the
5.4 Sub setting mode
The sub setting mode can be selected by pressing the
the
The set value can be increased or decreased by pressing the
The set value is registered by pressing the
selected.
Character
(PV display)
/
Name, Function, Setting range
SV1 0
• Sets SV1.
• Setting range: SV low limit to SV high limit, or
scaling low limit value to scaling high limit value
SV2 0
• Sets SV2.
• Not available if Serial communication (option) is added.
• Setting range: SV low limit to SV high limit, or
scaling low limit value to scaling high limit value
key again, the unit reverts to the PV/SV display mode.
key.
Name, Function, Setting range
AT setting/Auto-reset setting Cancel
• Sets AT (auto-tuning) or Auto-reset (offset correction).
• Auto-reset can be performed only in PD or P action.
(Auto-reset cannot be performed when the control action is PID, PI
or ON/OFF action)
[Auto-tuning]
• If Auto-tuning “Perform” is selected and the
the AT indicator flashes and the unit reverts to the PV/SV display
mode.
• When Auto-tuning is finished, the AT indicator is turned off and P, I, D,
ARW values are automatically set.
• During auto-tuning, none of the settings can be carried out.
• If Auto-tuning is cancelled during the process, P, I, D, ARW values
return to the previous value.
• If OUT/OFF key is pressed during auto-tuning, control output OFF
function activates, and pressing the OUT/OFF key again cancels the
PID auto-tuning.
• If PID auto-tuning does not finish in 4 hours after starting, PID
• Sets the action point for A1 output.
Set ting the value to 0 or 0.0 disables the function.
(excluding Proces s high and Proces s low alarm)
• Not available if No alarm action is selected during A1 type selection.
• Setting range: See (Table 5.4-1).
A2 value setting
• Sets the action point for A2 output.
Set ting the value to 0 or 0.0 disables the function.
0
(excluding Process high and low alarm)
• Not available if A2 (option) is not added or if No alarm action is
selected during A2 type selection.
• Setting range and default value are the same as those of A1 value setting.
.
and
measured
current
value are
displayed
alternately.
HB (Heater burnout alarm) value setting 0.0A
• Sets the heater current value for Heater burnout alarm.
• Available only when the Heater burnout alarm (option) is added.
• When OUT1 is OFF, heater current value shows the previous value as
when OUT1 was ON.
• Setting the value to 0.0 disables the function.
I t is recommended to set approx. 80% of the heater current value
(set value) considering the voltage fluctuation.
• Upon returning to set limits, the alarm will stop.
• Setting range: Rating 5A: 0.0 to 5.0A Rating 10A: 0.0 to 10.0A
Rating 20A: 0.0 to 20.0A Rating 50A: 0.0 to 50.0A
Setting range of A1 and A2
(Table 5.4-1)
Alarm type Setting range
High limit alarm –Input span to input span ( ) *1
Low limit alarm –Input span to input span ( ) *1
High/Low limits alarm 0 to input span ( ) *1
High/Low limit range alarm 0 to input span ( ) *1
Process high alarm Input range low limit to input range high limit *2
Process low alarm Input range low limit to input range high limit *2
High limit alarm with standby –Input span to input span ( ) *1
Low limit alarm with standby –Input span to input span ( ) *1
High/Low limits alarm with standby 0 to input span ( ) *1
• When the input has a decimal point, negative low limit value is –199.9, and positive
high limit value is 999.9.
• All alarm types except Process alarm are
deviation setting from the SV.
*1: For DC input, the input span is the same as the scaling span.
*2: For DC input, input range low (or high) limit value is the same as the scaling low
(or high) limit value.
5.5 Auxiliary function setting mode 1
In the PV/SV display mode, if the
holding down the
key, Auxiliary function setting mode 1 can be selected.
The set value can be increased or decreased by pressing the
If the
key is pressed, the set value is registered and the next setting item is
• Locks the set value to prevent setting errors
The setting item to be locked depends on the selection.
• PID auto-tuning or auto-reset does not work if Lock 1 or Lock 2 is selected.
• When selecting Lock, select Lock 1, Lock 2 or Lock 3 after setting the
necessary items in the status Unlock.
•
(Unlock): All set values are changeable.
(Lock 1): None of the set values can be changed.
(Loc k 2): Only main setting mode can be changed.
(Lock 3): All set values except input type can be changed. However,
they return to their previo us value after the power is turned off because
they are not written in the non-volatile memory. Be sure to use
Lock 3 when changing the set value frequently via communication.
(When Lock 1 or Lock 2 is selected, if the value changed by the
communication function is the same as the previous one, it is not
written in the non-volatile memory.) Do not change any setting item
in Auxiliary function setting mode 2. If any item in the mode is changed,
it will affect other setting items such as SV and Alarm value.
SV high limit setting
1370
• Sets SV high limit.
• Setting range: SV low limit to input range high limit value
DC input: SV low limit to scaling high limit value
(The placement of the decimal point follows the selection)
SV low limit setting –200
• Sets SV low limit.
• Setting range: Input range low limit value to SV high limit
Sensor correction setting 0.0
DC input: Scaling low limit value to SV high limit
(The placement of the decimal point follows the selection)
• Sets correction value for the sensor.
• Setting range: –100.0 to 100.0
( ), For DC input, –1000 to 1000
(The placement of the decimal point follows the selection)
Communication protocol selection
• Selects the communication protocol.
• Available only when Serial communication (option) is applied.
• Not available if
• Modbus ASCII mode:
is indicated
, Modbus RTU mode:
Instrument number setting 0
• Sets the instrument number. (Communication cannot be carried out
unless an instrument number is individually set when communicating
by connecting plural instruments in serial communication.)
• Available only when Serial communication (option) is added.
• Setting range: 0 to 95
Communication speed selection 9600bps
• Selects a speed equal to that of the host computer.
(Communication cannot be performed unless the speeds are equal)
• Available only when Serial communication (option) is added.
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control
(option) is not applied
• Setting range: OUT2 low limit value to 105%
(Setting higher than 100% is effective to DC current output type.)
OUT2 low limit setting 0%
• Sets the low limit value of OUT2.
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control
(option) is not applied
• Setting range: –5% to OUT2 high limit value
(Setting less than 0% is effective to DC current output type.)
Overlap band/Dead band setting 0.0
• Sets overlap band and dead band value for OUT1 and OUT2.
+ Set value: Dead band
– Set value: Overlap band
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control
(option) is not applied
• Setting range: –100.0 to 100.0
( )
DC input: –1000 to 1000 (The placement of the decimal
point follows the selection)
OUT2ON/OFF action hysteresis setting 1.0
• Sets ON/OFF action hysteresis for OUT2.
• Available only when Heating/Cooling control (option) is applied
• Setting range: 0.1 to 100.0
( )
For DC input, 1 to 1000 (The placement of the decimal
point follows the selection)
A1 type selection
• Selects A1 type.
No alarm
action
• Selecting item
No alarm action :
High limit alarm :
Low limit alarm :
High/Low limits alarm :
High/Low limit range alarm :
Process high alarm :
Process low alarm :
High limit alarm with standby :
Low limit alarm with standby :
High/Low limits alarm with standby:
• Selects either Direct (Cooling) or Reverse (Heating)
Reverse
(Heating) action
control action.
• Selecting item
Reverse (Heating):
AT bias setting 20
Direct (Cooling):
• Sets the bias value for performing PID auto-tuning.
• Not available for DC input
• Setting range: 0 to 50
With a decimal point,0.0 to 50.0
Setting item not used
(0 to 100)
(0.0 to 100.0 )
When Serial communication (option) is applied, this item appears.
However, do not set this item.
SV2 indication selection Indication
• Selects whether SV2 is indicated or not.
• Selecting item
(Indication) (No indication)
Output status selection when input abnormal Output OFF
• Selects the output status of OUT1 and OUT2 (option) when DC input is
overscale or underscale. See “Input abnormality indication” on pages 40, 41.
• Available only for DC current output with DC input
•
: OFF(4mA) or OUT1(OUT2) low limit
: Outputs a value between OFF(4mA) and ON(20mA) or between
OUT1(OUT2) low limit value and OUT1(OUT2) high limit value,
depending on a deviation.
OUT/OFF key function selection
• Selects the OUT/OFF key function.
OUT/OFF
function
• Selecting item
(OUT/OFF function), (Auto/Manual control function)
ARW function
ARW (Anti-reset windup) prevents overshoot caused by the integral action. The smaller
the ARW value, the less the overshoot caused by the integral action in the transition
status, however it takes time until stabilization.
Sensor correction function
This corrects the input value from the sensor. When a sensor cannot be set at a
location where control is desired, the sensor measuring temperature may deviat e from
the temperature in the controlled location. When controlling with plural controllers,
the accuracy of sensors affects the control.
Therefore, sometimes the measured temperatures (input value) do not concur. In such a
case, the control can be set at the desired temperature by adjusting t he input value of
sensors.
SV1/SV2 external selection
SV1 or SV2 can be selected by the external operation.
• Between terminals 14 and 17 open: SV1 can be selected.
• Between terminals 14 and 17 closed: SV2 can be selected.
• Set value memory number cannot be changed during setting mode or PID auto-tuning.
26
When the alarm output indicator is lit, the alarm output (terminals 7-8 or 12-13) is
conducted (ON). When the alarm output indicator is unlit, the alarm output is not
conducted (OFF). See (Fig. 5.6-1).
[If the alarm action Deenergized is selected]
When the alarm output indicator is lit, the alarm output (terminals 7-8 or 12-13) is not
conducted (OFF). When the alarm output indicator is unlit, the alarm output is
conducted (ON). See (Fig. 5.6-2).
A1 hysteresis
A1 hysteresis
ON
ON
OFF
SV setting+ A1 set point
OFF
SV setting
+ A1 set point
High limit alarm (When Energized is set) High limit alarm (When Deenergized is set)
(Fig. 5.6-1) (Fig. 5.6-2)
5.7 Control output OFF function
Control output OFF function [
]
• A function to pause the control action or turn the control output of the unused
ins trument of the plural units OFF even if the power to the instrument is supplied.
[
] is indicated on the PV display while the function is working.
• Once the Control output OFF function is enabled, the function cannot be released
even if the power to the instrument is turned OFF and ON again.
To cancel the function, press the
key again for approx. 1 second.
5.8 Auto/Manual control function
PV/SV display
mode
(Manual control)
• To use this function, it is necessary to select Auto/Manual
c ontrol function during the OUT/OFF key function selection.
• First, press the
key.
The MV (manipulated variable) on the SV display can be
increased or decreased by pressing the
or key
and the control is performed.
• The 1st decimal point from the right on the SV display flashes.
• By pressing the
key again, the mode reverts to the
PV/SV display (automatic control) mode.
(When the power supply to the instrument is turned on,
automatic control starts)
After the controller is mounted to the cont ro l panel and wiring is c ompleted, operat e t he
unit following the procedures below.
(1) Turn the power supply to the KT9 Series ON.
For approx. 3 seconds after the power is switched ON, sens or input charact ers and
temperature unit are indicated on the PV display, and the input range high limit value
is indicated on the SV display. See (Table 6-1).
For the DC input, for appro x. 3 second s after the power is switched ON, sensor input
characters are indicated on the PV display , and the scaling high limit value is indicated
on the SV display. See (Table 6-1).
However, if the scaling high limit value has been changed during the Scaling high limit
setting, the changed value is indicated on the SV display.)
(During this time, all outputs and the LED indicators are in OFF status)
After that, the PV (process variable) is indicated on the PV display, and SV1 or
SV2 is indicated on the SV display.
(When the Control output OFF function is working, “
PV display)
(Table 6-1)
Sensor input
K
J
R
S
B
E
T
N
PL-
C (W/Re5-26)
Pt100
JPt100
4 to 20mA DC
0 to 20mA DC
0 to 1V DC
0 to 10V DC
1 to 5V DC
0 to 5V DC
PV display SV display PV display SV display
Scaling high limit value
” is indicated on the
(2) Input each set value.
Input each set value, referring to “5. Setup”.
(3) Turn the load circuit power ON.
Control action starts so as to keep the control target at the SV.
High limit alarm with standbyLow limit alarm with standby
ON
OFF
A1
set point
ON
A1 hysteresis
A1 hysteresis
ON
Alarm action
OFF
A1
set point
High/Low limits alarm with standby
SV setting
A1 hysteresis
+ A1
set point
OFF
A1
set point
SV setting
+ A1
set point
Alarm action
ON
OFF
A1
set point
SV setting
A1
set point
: Standby functions.
A2 output is turned ON when terminals 12 and 13 are connec ted.
A1 and A2 indicators light when their output terminals are connected (ON), and go off
when they are not connected (OFF).
Proportional action is the action during which the control output varies in proportion to
the deviation between the SV and the PV (processing temperature).
If the proportional band is narrowed, even if the output changes by a slight variat ion
of the processing temperature, better control results can be obtained as the offset
decreases.
However, if the proportional band is narrowed too much, even slight disturbances
may cause variation in the processing temperature, control action changes to
ON/OFF action and the so-called hunting phenomenon occurs.
Therefore, when the processing temperature comes to the balanced position near
the SV and a constant temperature is mai ntained, the most suitable value is selected
by gradually narrowing the proportional band while obs erving the c ontr ol results.
(2) Integral tim e (I )
Integral action is used to eliminate offset. When the integral time is shortened, the
returning speed to the se t point is a c cel er ate d. However , the cycle of oscillation is also
accelerated and the control becomes unstable.
(3) Derivative time (D)
Derivativ e action is used to restore the c hange in the processing t emperature according
to the rate of change. It reduces the amplitude of overshoot and undershoot width.
If the derivative time is shortened, restoring value becomes small, and if the derivative
time is extended, an excessive returning phenomenon may occur and the control
system may oscillate.
8.2 PID auto-tuning of this controller
In order to set each value of P, I, D and ARW automatically, the auto-tuning process
should be made to fluctuate to obtain an optimal value.
Sometimes the auto-tuning process will not fluctuate if auto-tuning is performed
at or near room temperature. Therefore auto-tuning might not finish normally.
(A) In the case of a large difference between the SV an d p ro c e s s ing temp e rature as
the temperatu re i s ri sing
When AT bias is set to 20
than the SV.
Temperature 20 lower than the SV
SV
(4)
Temperature
AT starting point
(1)
(Fig. 8.2-1)
, the AT process will fluctuate at the temperature 20 lower
(1) Calculating PID constant
(2) PID constant calculated
(3) Controlled by the PID
(C) In the case of a large difference between the SV and processing temperature as
the temperature is falling
When AT bias is set to 20 , the
higher than the SV.
Temperature 20 higher t han the SV
AT process will fluctuate
at the temperature 20
(1) Calculating PID constant
(2) PID constant calculated
Temperature
(3) Controlled by the PID
constant set by auto-tuning
(4) AT bias value
SV
(4)
AT starting point
Time
(1)
(2)
(Fig. 8.2.3)
8.3 Auto-reset (offset correction)
Auto-reset is performed to correct the offset at the poi nt at wh ic h PV in dic at ion
is stabilized within the proportional band during the PD action.
Since the corre cted val ue is int ernally mem o riz e d, it is not necessary to perform
the auto-reset again as long as th e pr oces s is the s am e.
However, when the proportional band is set to 0, the corrected value is cleared.
RTD : Pt100, JPt100, 3-wire system
Allowable input lead wire resistance, 10
or less per wire
DC current : 0 to 20mA DC, 4 to 20mA DC
Input impedance, 50
[50
shunt resistor (AKT4810, sold separately) must be
connected between input terminals]
Allowable input current 50mA or less
[If 50
shunt resistor (AKT4810, sold separately) is used]
DC voltage : 0 to 1V DC
Input impedance, 1M
or more
Allowable input voltage 5V or less
Allowable signal source resistance 2k
or less
0 to 10V DC, 0 to 5V DC, 1 to 5V DC
Input impedance, 100k
or more
Allowable input voltage 15V DC or less
Allowable signal source resistance 100
or less
Control output (OUT1)
Relay contact : 1a1b
Control capacity, 3A 250V AC (resistive load)
1A 250V AC (inductive load cosø=0.4)
Electrical life, 10 0,0 00 c ycl es
+2
Non-contact voltage : 12
V DC maximum 40mA (short circuit protected)
0
DC current : 4 to 20mA DC
Load resistance, maximum 550
A1 output
When A1 action is set as Energized, the alarm action point is set by
deviation
from the SV (except Process alar m ).
When the input is out of the range, the out put turns ON or OFF (in the case of
High/Low limit range alarm).
When the alarm action is set as Deenergized, the output acts conversely.
Setting accuracy : The same as the Indic ation acc uracy
Action : ON/OFF action
Hysteresis : Thermocouple, RTD input, 0. 1 t o 100. 0
( )
DC current, voltage input, 1 to 1000
(The placement of the decimal point fol l ows t he selection)
Output : Relay contact 1a
Control capacity, 3A 250V AC (resistive load)
Electrical life, 10 0,0 00 c ycl es
Control action
• PID action (with auto-tuning function)
• PI action: When derivative time i s set to 0
• PD action (with aut o-r eset functi on): When integral time is set to 0
• P action (with auto-reset function): When integral and derivative times are set to 0
38
Page 39
• ON / O F F act i on: When OUT1 proportional band is set to 0
OUT1 proportional band (P)
Thermocouple: 0 to 1000
RTD: 0.0 to 999.9
(0.0 to 999.9 )
(0 to 2000)
DC current, voltage: 0.0 to 100.0%
(ON/OFF action when set to 0
(
), 0.0
) or 0.0%)
(
Integral time (I) : 0 to 1000sec (Off when set to 0)
Derivative time (D) : 0 to 300sec (Off when set to 0)
OUT1 proportional cycle : 1 to 120sec (Not available for DC current output type)
ARW : 0 to 100%
OUT1 hysteresis : Thermocouple, RTD input: 0.1 to 100. 0
( )
DC current, voltage input: 1 to 1000 (The placement
of the decimal point foll ow s the selection)
SV1/SV2 external selection: SV 1 and SV 2 c an be se lec ted by ext ern al c ontact .
Contact open between terminals 14 and 17 : SV1
Contact closed between terminals 14 and 17: SV2
Contact current: 6mA
Supply voltage: 100 to 240V AC 50/60Hz, 24V AC/DC 50/60Hz Al lowa ble vol tage fluctuation range100 to 240V AC : 85 to 264V AC
24V AC/DC : 20 to 28V AC/DC
Ambient temperature : 0 to 50
(32 to 122
)
Ambient humidity : 35 to 85%RH (no condensation)
Power consumption : Approx. 8V A
Circuit insulation configuration
Ground
1
2
3
4
5
6
7
8
Power
source
OUT1
A1 output
A
Insulated
A2 output or Heater
burnout alarm output
CT input
15
16
18
12
13
SV2
11
Communication
14
C
17
14
D
17
Input
10
9
OUT2 or Heater
burnout alarm output
B
19
20
• When OUT1 is non-contact voltage or DC c urrent output type and OUT2 is Non-
contact voltage or DC current output type, A is not insulated from B.
• When OUT1 is non-contact voltage or DC current output type, A is not insulated from
C, and A is not insulated from D.
When OUT2 is non-contact voltage or DC current output type, B is not insulated from
C, and B is not insul a ted from D.
Insulation resistance
10M
or more, at 500V DC for other combinations exc ept t he abov e ment i oned
Between input terminal and ground terminal, 1.5kV AC for 1 minute
Between input terminal and power te rmi nal, 1.5kV AC for 1 minute
Between output terminal and ground terminal, 1.5kV AC for 1 minute
Between output terminal and power terminal, 1.5kV AC for 1 minute
Between power terminal and ground terminal, 1.5kV AC for 1 minute
Weight : Approx. 370g
External dimension : 96 x 96 x 98.5mm (W x H x D)
Material : Case, Flame-resistant resin
Color : Case, Ash gray
Attached function
[Sensor correction function]
[Set value lock function]
[Input abnormality indication]
Output
selection
when input
abnormal
Contents and
Indication
Overscale
Measured value
has exceeded
Indication range
high limit value.
"
" flashes.
Underscale
Measured value
has dropped
below Indication
range low limit
value.
"
" flashes.
OUT1 OUT2
Direct actionReverse actionDirec t ac tion
ON (20mA) or
OUT1 high
limit value
OFF (4mA) or
OUT1 low
limit value
(*)
OFF (4mA) or
OUT1 low limit
value
ON (20mA) or
OUT1 high limit
OFF (4mA) or
OUT1 low
limit value
value (*)
OFF (4mA) or
OUT1 low limit
value
Output status
Only for DC input and DC current output type, [Output status selection when input
abnormal] is available. For other inputs and outputs except for DC input and DC
current output, the output status will be the same one as when OFF is selected
during [Output status selection when input abnormal].
For manual control, the preset manipulated variable (MV) is outputted.
(*): Outputs a value between OFF (4mA) and ON (20mA) or between OUT1 (OUT2)
low limit value and OUT1 (OUT2) high limit value, depending on deviation.
Thermocouple, RTD input:
Input Input range Indication range Control range
K,T
–199.9 to 400.0 –199.9 to 450.0 –205.0 to 450.0
–199.9 to 750.0
–199.9 to 850.0 –209.0 to 850.0
–199.9 to 850.0 –199.9 to 900.0 –210.0 to 900.0
Pt100
–200 to 850 –210 to 900 –210 to 900
–199.9 to 999.9 –199.9 to 999.9 –211.0 to 1099.9
–300 to 1500
–318 to 1600 –318 to 1600
–199.9 to 500.0 –199.9 to 550.0 –206.0 to 550.0
JPt100
–200 to 500 –207 to 550 –207 to 550
–199.9 to 900.0 –199.9 to 999.9 –211.0 to 999.9
–300 to 900
–312 to 1000 –312 to 1000
For the thermocouple inputs other than the above, both the Indic ati on range and
Control range are: Input range low limit v al ue – 50
limit value + 50
(100 )
(100 ) to Input range hi gh
OFF or
OUT2 low
limit value
ON or
OUT2 high
limit value(*)
OFF or
OUT2 low
limit value
Indication range : [Scaling low limit value – Scaling span x 1%] to [Scaling high
limit value + Scaling span x 10%]
However, if the input value goes out of the range –1999 to
9999, the PV displ ay flashes “
” or “”.
Control range : [Scaling low limit value – Scaling span x 1%] to [Scaling high
limit value + Scaling span x 10%]
• DC input disconnection: When DC input is disconnected, PV display flashes
“
“
” for 4 to 20mA DC and 1 to 5V DC inputs, and
” for 0 to 1V DC input.
For 0 to 20mA DC, 0 to 5V DC and 0 to 10V DC inputs, the PV
display indicates the value corresponding with 0mA or 0V input.
[Burnout]
When the thermocouple or RTD input is burnt out, OUT1 is turned off (for DC
current output type, OUT1 low limit value) and the PV displa y flas hes “
[Self-diagnosis]
The CPU is monitored by a watchdog timer, and when an abnormal status is
found on the CPU, t h e c ontroller is switched to warm-up status.
Thermocouple input type)
[Automatic cold junction temperature compensation]
(
This detects the temperatur e at the connecting terminal between thermocouple
and the instrument, and always maintains the same status as when the reference
junction is located at 0
(32
.
)
[Power failure countermeasure]
The setting data is backed up in non-volatile IC me m ory.
[Warm-up indication]
All outputs are turned OFF in the warm-up status .
With thermocouple and RTD input, for approx. 3 seconds after the power is
switched ON, sensor input characters and temperature unit are indicated on the
PV display, and the input range high limit value is indicated on the SV display.
With the DC input, f or approx. 3 s econds after the powe r is switched ON, sensor
input characters are indicated on the PV display, and scaling high limit value is
indicated on the SV display.
(However, if the scaling high limit value has been changed during the Scaling
high limit setting, the changed value will be indicated on the SV display.)
[Auto/Manual control switching]
If Auto/Manual control function is selected during OUT/OFF key function
selection, automatic control can be switched to manual control and vice versa
by pressing the OUT/OFF key.
When the control action is changed from automatic to manual contr ol and vice
versa, the balanceless-bump less function works to prevent sudden change of
manipulated variable.
When the control action is changed from automatic to manual control, the 1st
decimal point from the right on the SV display flashes.
The manipulated variable (MV) on the SV display can be increased or decreased
by pressing the
or key and the control is performed.
(When the power supply to the instrument is turned on, automatic control starts)
41
”.
Page 42
Accessories inclu d ed : Inst ruction manual 1 copy
For rating 50A : AKT4816 1 piece
Accessories sold separately:
Terminal cover (AKT9801) 1 piece
50
shunt resistor (AKT4810) 1 piece
9.2 Optional specifications
Alarm 2 (A2)
When A2 action is set as Energized, the alarm action point is set by
deviation from
OUT1 SV (except Process alarm).
When the input is out of the range, the output turns ON or O FF (in the cas e of
High/Low limit range alarm).
When the alarm action is set as Deenergized, the output acts conversely.
When A2 option is added, one more option Heater burnout alarm or Heat ing/Cooling
control can be added.
Setting accur a c y : The same as the Indicating accuracy
Action : ON/OFF action
Hysteresis : Thermocouple, RTD input, 0.1 to 100. 0
( )
DC current, voltage input, 1 to 1000
(The placement of the decimal point follows the selection)
Output : Relay contact, 1a
Control capacity, 3A 250V AC (resistive load)
Electrical life, 100,000 cycles
HB (Heater burnout alarm)
Watches the heater current with CT (current transformer), and detects the heater
burnout.
Heater burnout alarm is activated when sensor is burnt out or when indication is
overscale or underscale. (To detect Heater burnou t, a CT fo r 5 0 A can also be used fo r
5A, 10A and 20A ratings, however, this is not suitable for small ampere ratings due to a
low degree of accuracy. For a 20A rating or less, use a CT designated for 20A.)
• When the Heater burnout alarm option is applied, one more option A2 output or
Heating/Cool in g cont rol can be add ed.
• This option cannot be applied to DC current output type.
Heater rated current : 5A, 10A, 20A, 50A, Must be specified
Setting accuracy : Within
5% of heater rated current
Action : ON/OFF action
Output : Relay contact, 1a
Control capacity, 3A 250V AC (resistive load)
Electrical life, 100,000 cycles
Heating/Cooling control
When the Heating/Cooling control opti on is added, one m ore option A2 output or
Heater burnout alarm can be added.
OUT2 proportional band : 0.0 to 10.0 times OUT1 pr oport ional band
(ON/OFF action when set to 0.0)
OUT2 integral time : The same as that of OUT1
OUT2 derivative ti me : The sa me as th at o f OUT 1
OUT2 proportional cycle : 1 to 120 seconds
Overlap band/Dead band :
Thermocouple, RTD input: –100.0 to 100.0
( )
DC current, voltage input: –1000 to 1000 (The placement of the decimal
point follow s the selec tion)
Thermocouple, RTD input: 0.1 to 100.0
DC current, voltage input: 1 to 1000 (The placement of the decimal
point follows the selection)
Output Relay contact, 1a
Control capacity, 3A 250V AC (resistive load)
1A 250V AC (inductive load cosø=0.4)
Electrical life, 100,000 cycles
Non-contact voltage output
12
DC current output, 4 to 20mA DC
Load resistance, maximum 550
OUT2 action mode selection function:
One cooling mode can be selected by k eypad operation from the f ollowing.
Air cooling (Linear characteristic)
Oil cooling (1.5th power of the linear characteristic)
Water cooling (2nd power of the linear characteri s tic)
Serial communication
The following operations can be carried out from the external computer.
When this option is added, SV2 setting is not available.
(1) Reading and setting of SV, PID and various set values
(2) Reading of the PV and action status
(3) Change of the functions
Cable length : Max. communication distance 1000m,
Cable resistance; Within 50
Communication line : EIA RS-485
Communication method : Half-duplex communication start stop synchronous
Communication speed : 2400, 4800, 9600, 19200bps (Selectable by keypad)
Parity : Even, Odd and No parity (Selectable by keypad)
Stop bit : 1, 2 (Selectable by keypad)
Communication protocol : Modbus RTU, Modbus ASCII (Selectable by keypad)
Connectable number of units : Maximum 31 units to 1 host comput er
Communication error detection : Parity, checksum (LRC, CRC)
+2
V DC maximum 40mA (short circuit protected)
0
( )
10. Troubleshooting
If any malfunctions occur, refer to the following items aft e r c h ec k i ng t he power of the
Turn the power supply to the instrument off before wiring or checking.
Working or touching the terminal with the power switched on may result in
severe injury or death due to Electric Shock.
• Control output OFF function is working.
Press the OUT/OFF key for approx. 1 second to
release the function.
• Burnout of thermocouple, RTD or disconnection of DC voltage
(0 t o 1 V D C ) . Change each sensor.
How to check whether the sensor is burnt out
[Thermocouple]
If the input terminals of the instrument are shorted, and
if a value around room temperature is indicated, the
instrument is likely to be operating normally, however,
the sensor may be burnt out .
[RTD]
If approx. 100
of resistance is connected to the input
terminals between A-B of the instrument and between
B-B is shorted, and if a value around 0
(32 ) is
indicated, the instrument is likely to be operating
normally, however, the sensor may be burnt out.
[DC voltage (0 to 1V DC)]
If the input terminals of the instrument are shorted, and if a
scaling low limit value is indicated, the instrument is likely
to be operating normally, however, the signal wire may be
disconnected.
• Check whether the input terminals of thermocouple, RTD or
DC voltage (0 to 1V DC) are securely mounted to the
instrument input terminal.
Connect the sensor terminals to the instrument input
terminals securely.
• The input signal wire for DC voltage (1 to 5V DC) or DC
current (4 to 20mA DC) may be disconnected.
Replace the input signal wire.
How to check whether the input signal wire is disconnected
[DC voltage (1 to 5V DC)]
If the input to the input terminal of this c ontroller is 1V DC
and if scaling low limit value is indicated, the controller is
likely to be operating normally, however, the input signal
wire may be disconnected.
[DC current (4 to 20mA DC)]
If the input to the input terminal of this controller is 4mA DC
and scaling low limit value is indicated, the controller is
likely to be operating normally, however, the input signal
wire may be disconnected.
• Check whether the input signal wire of DC voltage (1 to 5V
DC) and DC current (4 to 20mA DC) is securely connected
to the input terminal of this controller.
Ensure that they are wired properly.
• Check whether the polarity of thermocouple or
compensating lead wire is correct.
• Check whether codes (A, B, B) of the RTD agree with the
controller terminal.
Ensure that they are wired properly.
The value set during
the Scaling low limit
setting remains on the
PV display.
The indication of
PV display is
abnormal or unstable.
[] is indicated
on the PV display.
• Check whether the input signal wire for DC voltage
(0 to 5V DC, 0 to 10V DC) or DC current (0 to 20mA DC)
is disconnected.
How to check whether the input signal wire is disconnect ed
[DC voltage (0 to 5V DC, 0 to 10V)]
If the input to the input terminal of this c ontroller is 1V DC
and if a value corresponding to1V DC is indicated, the
controller is likely to be operating normally, however, the
input signal wire may be disconnected.
[DC current (0 to 20mA DC)]
If the input to the input terminal of this controller is 1mA DC
and if a value corresponding to 1mA DC is indicated,
the controller is likely to be operating normally, however,
the input signal wire may be disconnected.
• Check whether the input lead wire terminals for DC voltage
(0 to 5V DC, 0 to 10V DC) or DC current (0 to 20mA DC)
are securely connected to the instrument input terminals.
• Check whether the sensor input and temperature unit
or ) setting are correct.
(
Set the sensor input and the temperature unit properly.
• Sensor correcting value is unsuitable.
Set it to a suitable value.
• Sensor specification is improper.
Set the sensor specification properly.
• AC may be leaking into the sensor circuit.
Use an ungrounded type sensor.
• There may be equipment that interferes with or makes
noise near the controller.
Keep equipment that interferes with or makes noise away
from the controller.
The internal memory is defective.
Please contact our main office or dealers.
10.2 Key operation
Problem Presumed cause and solution
Unable to set SV, P,
I, D, proportional cycle,
alarm value, etc.
The value does not
change by the
,
keys.
The setting indication
does not change within
the input range even
if the
, keys
are pressed, and new
values are unable to
be set.
• Set value lock (Lock 1 or Lock 2) is selected.
Release the lock selection.
• During PID auto-tuning or auto-reset.
Cancel the auto-tuning if necessary.
Auto-reset ends 4 minutes after starting.
• SV high limit or low limit may be set at the point where the
value does not change.
Set it to a suitable value while in Auxiliary function setting
mode 1.
If any unexplained malfunctions occur, make inquiries at our agency or us.
• The sensor is out of order.
Replace the sensors.
• Check whether the sensor is securely mounted to the
instrument input terminal.
Check whether control output terminals are securely
mounted to the actuator input terminals.
Mount the sensor or control output terminal securely.
• Check whether the wiring of sensor or control output terminals
is correct.
• OUT1 low limit value is set to 100% or higher in Auxiliary
function setting mode 2.
Set it to a suitable value while in Auxiliary function setting
mode 2.
• OUT1 high limit value is set to 0% or less in Auxiliary
function setting mode 2.
Set it to a suitable value while in Auxiliary function setting
mode 2.
11. Character table
Photocopiable material
[Main setting mode]
Character Setting item Default value Data
SV1 0
[Sub setting mode]
Character Setting item
AT
Auto-reset
OUT1 proportional band 10
OUT2 proportional band 1.0 times
Integral time 200 seconds
Derivative time 50 seconds ARW 50%
A1 value 0
A2 value 0
SV2 0
OUT1 proportional cycle
OUT2 proportional cycle
HB (Heater burnout alarm) value 0.0A
Relay contact output: 30sec
Non-contact voltage output: 3sec
Relay contact output: 30sec
Non-contact voltage output: 3sec