Thank you for purchasing this Panasonic product.
Please read these instructions carefully before attempting to install, operate or service
the Panasonic product. Failure to comply with instructions could result in personal injury
or property damage. Please explain to users how to operate and maintain the product
after installation, and this booklet should be presented to users.
Please retain this booklet for future reference.
Page 2
GENERAL SAFETY INFORMATION
For Your Safety
To reduce the risk of injury, loss of life, electric shock, fire, malfunction, and damage to
equipment or property, always observe the following safety precautions.
Explanation of symbol word panels
The following symbol word panels are used to classify and describe the level of hazard, injury, and
property damage caused when the denotation is disregarded and improper use is performed.
WARNING
CAUTION
The following symbols are used to classify and describe the type of instructions to be observed.
This symbol is used to alert users to a specific operating procedure that must be followed
in order to operate the unit safely.
This symbol is used to alert users to a specific operating procedure that must not be
performed.
This symbol is used to alert users not to disassemble the equipment.
This symbol is used to alert users to make sure of grounding when using the equipment
with the grounding terminal.
WARNING
WARNING
To reduce the risk of fire, electric shock or injury to persons, observe the following :
Use this unit only in the manner intended by the manufacturer. If you have any questions,
contact the manufacturer.
Before servicing or cleaning unit, switch power off at service panel and lock the service
disconnecting means to prevent power from being switched on accidentally. When the
service disconnecting means cannot be locked, securely fasten a prominent warning device,
such as a tag, to the service panel.
Installation work and electrical wiring must be done by qualified person(s) in accordance with
all applicable codes and standards, including fire-rated construction.
Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney)
of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer's
guideline and safety standards such as those published by the National Fire Protection Association
(NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE) and the local code authorities.
When cutting or drilling into wall or ceiling, do not damage electrical wiring and other
hidden utilities.
Ducted fans must always be vented to the outdoors.
Denotes a potential hazard that could result in serious
injury or death.
Denotes a hazard that could result in minor injury.
If this unit is to be installed over a tub or shower, it must be marked as appropriate for the
application and be connected to a GFCI(Ground Fault Circuit Interrupter) - protected branch
circuit.
These models are UL listed for tub and shower enclosures.
Canada only: Not to be installed in a ceiling thermally insulated to a value greater than R40.
Do not disassemble the unit for reconstruction.
2
Page 3
GENERAL SAFETY INFORMATION CONTINUED
WARNING
When this product is no longer being operated, please remove the product to prevent the
possibility of falling.
Ceiling joist must be subjected to static load more than five times the weight of the product.
Do not install with a method which is not approved in the instructions.
Do not use this fan with any solid-state speed control device. Solid state controls may cause
harmonic distortion which can cause motor humming noise.
This product must be properly grounded.
CAUTION
Do not install this ventilating fan where interior room temperature may
exceed 104°F(40°C).
Make sure that the electric service supply voltage is AC 120V, 60Hz.
Prohibited
Follow all local electrical and safety codes, as well as the National
Electrical Code (NEC) and the Occupation Safety and Health Act (OSHA).
Always disconnect the power source before working on or near the fan,
motor, light fixture or junction box.
Protect the supply wiring from sharp edges, oil, grease, hot surfaces,
chemicals or other objects.
Do not kink the supply wiring.
Provide make up air for proper ventilation.
For general ventilating use only. Do not use to exhaust hazardous or
explosive materials and vapors.
Do not install the unit where ducts are configured as shown
in Fig.A.
Not for use in cooking area. (Fig.B)
The special-purpose or dedicated parts, such as mounting
fixtures, must be used if such parts are provided.
Prohibited
Prohibited
Prohibited
(Cooking area)
Do not install above or
inside this area
45
equipment
45
Cooking
Fig. B
Adaptor
Floor
PLEASE READ PRIOR TO INSTALLING THIS FAN
Spot and Continuous Ventilation: These fans are designed to run continuously ensuring a healthy
environment at low CFM levels 24 hours a day. By utilizing the optional CustomVent Multi-Speed module
the fans are built to run continuously at a pre-set lower level (FV-05-11VKSL1 and FV-05-11VKL1: 0, 30,
40, 50, 60, 70, 80, 90, 100 CFM; FV-11-15VKL1: 0, 50, 60, 70, 80, 90, 100, 110, 120 CFM). The setting is
dependent on the size of the house and the individual wishes of the homeowner. It is crucial that the
installer pre-set the lower setting during the installation. Please refer to the chart below and the
switch indication on page 6.
3
Page 4
PLEASE READ PRIOR TO INSTALLING THIS FAN CONTINUED
These fans are also built to take care of the homeowner’s spot ventilation needs when the room is
occupied. The basic fan models allow a choice of three speeds. When fans are equipped with the optional
Multi-Speed module, these models kick up to a maximum level of 150 CFM for the FV-11-15VKL1 and 110
CFM for the FV-05-11VKSL1 and FV-05-11VKL1 either when the switch is turned on or activated by the
optional Condensation Sensor module or the optional Motion Sensor module.
A High/Low Delay Timer, located inside the fan unit, is utilized to return the fan back to the pre-set
Continuous ventilation mode. The installer needs to consult with the homeowner for the desired
setting on the timer (0 - 60 minutes) and make the adjustments during the installation.
Two Bedrooms
33
38
43
48
53
58
63
68
73
78
83
88
93
Three Bedrooms
40
45
50
55
60
65
70
75
80
85
90
95
100
Four Bedrooms
48
53
58
63
68
73
78
83
88
93
98
103
108
Five Bedrooms
55
60
65
70
75
80
85
90
95
100
105
110
DESCRIPTION
These products are listed by UL under UL file No. E78414.
These products use a sirocco fan driven by a DC motor powered by an integral transformer. The motor is
designed to have long operating life, high dynamic response, higher speed ranges with saving energy.
The grille covering the fan body is a spring-loaded, quick remove type. A damper for preventing air counter
flow is provided. The blower uses a high-capacity sirocco fan developed to reduce the noise level.
The lighting unit is an energy-saving LED lighting device that uses two 7W LED lamps and produces almost
the same illumination as a standard 60W incandescent lamp.
FCC Note: This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in
a particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning this product on and off, the user is encouraged to try to correct the
interference by one of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect equipment into outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Warning: This equipment must be installed by qualified person in accordance with the provided installation
instructions; and all applicable codes and standards. Also, any changes or modifications not expressly
approved by the party responsible for compliance could void the user’s authority to operate this equipment.
DoC Responsible Party:
Customer Call Support:
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Risk of Fire: Type IC-Inherently Protected, Only Use LED Lamp, Max 7W, Type GU24.
Panasonic Corporation of North America
Two Riverfront Plaza, Newark, NJ 07102
1-866-292-7299
UNPACKING
Unpack and carefully remove the unit from carton.
Refer to the Supplied Accessories list to verify that all parts are present.
4
Page 5
SUPPLIED ACCESSORIES
Part namePart name
AppearanceAppearanceQuantityQuantity
Installation
Grille
1
instructions
Warranty
Flex-Z Fast
bracket
TM
1
Tapping screw
(ST4.2X20)
7W
LED lamp
2
Self-drilling
screw
DIMENSIONS
1 1/2 (38)
FV-05-11VKL1
FV-11-15VKL1
12 1/8 (307)
10 1/4 (260)
FV-05-11VKSL1
13 (330)
10 1/4 (260)
3 7/8 (100)
3 7/8 (98)
5 7/8 (148)
3 7/8 (100)
5 7/8 (148)
FV-11-15VKL1
No.No.
3
4
5
6
7
13 (330)
Blade
Grille
Lens
Motion sensor location
(FV-MSVK1 not included)
Junction box
Adaptor
Multi-Speed module
(FV-05-11VKSL1 only,
other models not included)
sheet
1 (26)
15
7 3/8 (190)
Part name
4 5/8 (116)
Unit: inches (mm)
13
FV-11-15VKL1
3 1/4 (81)
14
14
Part name
81
Connector cover
92
Base PCB box
10
Pick-A-Flow switch
Lighting
11
12
LED lamp
13
Fan
14
Damper
Flex-Z Fast bracket
15
unit
body
2
1
4
4
3 1/2 (88)
6 3/8 (163)
TM
WIRING
Fan body
DC-Motor
Multi-Speed module
(FV-05-11VKSL1
only, other models
not included)
The WhisperGreen Select Line of ventilation fans employs innovative, state-of-the-art technologies that
provide a number of customizable unique features that lead to improved indoor air quality. Please
read the installation manual first in order to realize the benefits of this customizable, modular fan.
Optimum Ventilation Performance:
Duct length, elbows and other factors increase static pressure which can hinder the performance of most
ventilation fans. This fan utilizes SmartFlow microchip technology that monitors the static pressure in the
system and speeds up or slows down the rpm of the fan depending upon the amount of resistance within
the ducts. This feature allows the fan to perform as rated and avoid potential installation issues.
Outstanding Energy Savings:
The WhisperGreen Select Line of fans are built using DC motor technology. The DC motor is 30% - 70%
more energy efficient than the minimum ENERGY STAR requirements.
Pick-A-Flow Feature
11080
( )
130
50
110 150
MODEL
MODEL
05-11
11-15
AIR VOLUME CFM
All the WhisperGreen Select base models of fans come with Pick-A-Flow
speed options. The Pick-A-Flow switch on the face of all WhisperGreen
Select fans allows the option to choose 50 – 80 – 110 CFM for the
FV-05-11VKL1, FV-05-11VKSL1 or 110 – 130 – 150 CFM for the
FV-11-15VKL1. These fans can run continuously or intermittently,
depending upon the needs of the owner.
Pick-A-Flow
switch
AIR VOLUME CFM
05-11
MODEL
11-15
MODEL
( )
50
11080
130
11015 0
Air volume type (CFM)
FV-05-11VKSL1
FV-05-11VKL1
FV-11-15VKL1
50
11080130
Factory setting
11080 CFM
150130 CFM
INDICATION (PLUG ‘N PLAY FUNCTION DEVICES)
PLUG ‘N PLAY Modular Component Accessories
Sold Separately, Not Included With Base Model Fan
AIR VOLUME CFM
MODEL
MODEL
05-11
11-15
110 150
50
130
( )
11080
Note that there is ONLY ONE
Plug ‘N Play slot to insert the
Multi-Speed module within the
base model fan. There are TWO
interchangeable Plug ‘N Play
slots to insert the Condensation
Sensor module, Motion Sensor
module or Nite-Glo LED Night
TM
Light module within the base
model fan.
FV-VS15VK1 Multi-Speed module allows the fan to run continuously
at lower speeds to maintain ventilation standards to meet Indoor
Air Quality and then boost up to high speed to meet intermittent
needs for ‘Spot’ or ‘Point Source’ exhaust needs. The FV-VS15VK1
Modular Component will operate for both the FV-05-11VKL1 and the
FV-11-15VKL1 matching the appropriate Multi-Speed setting shown
below. The FV-05-11VKSL1 comes with the FV-VS15VK1 Multi-Speed
module. It is not necessary to purchase this component.
Note the options on the face of the FV-VS15VK1 Multi-Speed module
to choose appropriate levels of airflow (CFM) and time delay before
returning back to low speed (TIME). Choosing the Pick-A-Flow setting
automatically adjusts the Multi-Speed setting accordingly. As an
example, if the Pick-A-Flow Multi-speed setting is 80 CFM, the
Multi-Speed settings adjust automatically to be 0, 30, 40, 50, 60 or 70
CFM at the lower speeds. The fan will ‘boost’ to the 80 CFM speed as
the high speed setting. Selecting a particular TIME option will cause
the fan to run for the selected amount of time before returning to
the lower speed setting chosen on the CFM dial.
Pick-A-Flow (CFM)
FV-05-11VKSL1,
FV-05-11VKL1
(plug-in FV-VS15VK1)
FV-11-15VKL1
(plug-in FV-VS15VK1)
50
80
110
110
130
150
Multi-Speed Air volume (CFM)
0
0
0
0
0
0
30
30
30
50
50
50
40
40
40
60
60
60
40
50
50
70
70
70
40
60
60
80
80
80
40
70
70
90
90
90
40
70
80
100
100
100
40
70
90
100
110
110
40
70
100
100
110
120
Delay Time (min)
45
Factory setting: 20 minutes.
Delay Time position “0“ : Manual wall switch control is 0 minute;
without manual wall switch control is 0.5 minute.
6
Page 7
INDICATION (PLUG ‘N PLAY FUNCTION DEVICES) CONTINUED
PLUG ‘N PLAY Modular Component Accessories
Sold Separately, Not Included With Base Model Fan
FV-CSVK1 Condensation Sensor module turns the base fan on or
boosts to higher speed when humidity is detected when used in
combination with the FV-VS15VK1. The Condensation Sensor works
based on calculations from the Psychrometric Chart, or combination
of Relative Humidity (RH) and Temperature. This allows the fan to
anticipate the formation of condensation and automatically turn on
when needed to expel humid air. The Condensation Sensor is pre-set
to run for 20 minutes; it will then check the RH and Temperature to
detect if the fan needs to run for another 20 minutes cycle.
FV-MSVK1 Motion Sensor module turns the base fan on or boosts
to higher speed when motion is detected when using in combination
with the FV-VS15VK1. The Motion Sensor is pre-set to run for 20
minutes; it will then re-check for movement; if detected the fan will
run for another 20 minutes cycle. The Motion Sensor detects within
the range shown below.
The distance that motion
can be detected is limited
to 10 feet (3m). The field
of view of the sensor is 90°.
(Room temperature is 25 C).
FV-NLVK1 Nite-Glo LED Night Light module automatically turns on
TM
when ambient light levels are met. Turning the dial on the Modular
Nite-Glo Component to ‘DARK’ is ideal if the fan is in an isolated room
with little ambient light from nearby rooms. Turning the dial to
‘BRIGHT’ is ideal if there is light spill from nearby rooms. (Note that it is
necessary to connect wall switch when only plug in FV-NLVK1, fan can
operate on high speed with wall switch control, fan can also operate
on low speed when used in combination with the FV-VS15VK1.)
MOTION (PLUG ‘N PLAY FUNCTION DEVICES)
PLUG ‘N PLAY Modular
Components used in
Combinations
Human
active
Fan
active
Module FV-MSVK1,
FV-CSVK1 (Not
included)
INSIDE
At low
speed
When motion or
excess humidity is
detected, fan runs
at high speed.
PLUG ‘N PLAY Modular Component Accessories
Sold Separately, Not Included With Base Model Fan
FV-CSVK1 + FV-MSVK1
Turns the fan on for 20 minutes when either
motion or excess humidity is detected.
FV-CSVK1 + FV-VS15VK1
Cycles the fan to high speed from low speed
for the amount of time selected on the Control
Dial based upon detection of excess humidity.
FV-MSVK1 + FV-VS15VK1
Cycles the fan to high speed from low speed
for the amount of time selected on the Control
Dial based upon motion within the room.
Motion
OUTSIDE
Remains running
at high speed until
the delay time has
passed.
FV-CSVK1 only
FV-MSVK1 only
FV-CSVK1 + FV-VS15VK1
FV-MSVK1 + FV-VS15VK1
Fan
operation
Fan
ON/OFF
Fan
Hi/Low speed
Time delay
operation
20 minutes
time delay
Depend on
FV-VS15VK1 Time
delay setting
7
Page 8
INSTALLATION (PLUG ‘N PLAY FUNCTION DEVICES)
You can purchase the specified Plug ‘N Play devices that are explained on page 6-7 and install them in positions
2
, and . Position can only be used with Multi-Speed module (model FV-05-11VKSL1 already have
this control installed), position and can be used for any of the other optional control modules.
1. Remove the connector cover
3
2
3
2
from position , or .
3
2. Plug in the specified devices to Base PCB box and fix to the slot, till hear the sound installed in place.
Connector
cover
2
3
Base PCB box
Slot
2
3
Clasp
Squeeze tabs on the Clasp to
remove. Squeeze, insert and
release the tabs on Clasp to replace.
INSTALLATION (NEW CONSTRUCTION)
The fan position between joists from 16" to 24"
on center can be adjusted flexibly.
CAUTION
Please wear gloves during the installation
work as follow.
1. Disconnet plug connector from receptacle and
remove adaptor from fan body by removing the
machine screw (M4X6) before installation. (Fig.1)
IMPORTANT:
Remove the tape from damper and adaptor
before installation. As shown below:
Adaptor
2. Bend down 4 tabs for positioning, install the
Flex-Z Fast bracket to joists by using 2 tapping
screws (ST4.2X20) (Please prepare the screws and
put on Flex-Z Fast bracket before Flex-Z Fast
TM
TMTM
bracket is installed on joist). (Fig.2)
3.
Adjust the length of Flex-Z Fast bracket as the
spacing between joists, and install to joists by
using 2 tapping screws (ST4.2X20). (Fig.3)
4. Remove junction box cover and secure conduit
or stress relief to junction box knock-out hole.
(Fig.4)
5. Install a circular duct and secure it with clamps,
or ties and seal it with mastic or approved foil tape.
4 inch 6 inch circular duct is needed to connect to
relevant part of common adaptor. (Fig.4)
6. Install the adaptor to Flex-Z Fast bracket by
using 2 self-drilling screws. (Fig.4)
8
Damper
Tape
TM
TM
Machine screw
(M4X6)
Joist
2 Tapping screws
(ST4.2X20)
Knock-out
hole
Junction box
cover
Fan body
2 Tapping screws
(ST4.2X20)
Conduit
2 Self-drilling screws
Adaptor
Circular duct
Fig.1
Bend down
4 tabs
Fig.2
Joist
Fig.3
Mastic or
approved
foil tape
Fig.4
Page 9
INSTALLATION (NEW CONSTRUCTION) CONTINUED
7. Refer to wiring diagram on page 5.
Follow all the local electrical safety codes as well
as the National Electrical Code (NEC).
Using UL approved wire nuts, connect house
power wires to ventilating fan wires. (Fig.5)
CAUTION
Mount junction box cover carefully so that
lead wires are not pinched.
8. Insert fan body and slide into adaptor assy with some
strength, untill the flange overlaps the Flex-Z Fast
bracket. Secure the fan body to Flex-Z Fast bracket
TM
TM
by using 2 self-drilling screws, plug connector to
receptacle and secure the fan body to adaptor by
using machine screw (M4X6). (Fig.6)
CAUTION
Secure machine screw (M4X6) to
hole and not touch the Flex-Z Fast bracket.
Please fix the screw carefully to avoid screw
slip teeth.
9. Finish ceiling work. Ceiling hole should be aligned
with the inside edge of the flange. (Fig.7)
10. Remove the tapes from louver and springs before
installation. Remove screw (M4X8) and light cover.
(Fig.8)
IMPORTANT:
Replace the sensor cover before the installation
(only for plug-in Motion sensor module FV-MSVK1).
As shown below:
Keep on pressing the clasps when removing the ornamental cover.
Gloves
the suitable
TM
FV-05-11VKSL1
FV-05-11VKL1
FV-11-15VKL1
Junction
box
Netural to
white
Live to black
(Light)
Joist
Plug connector
Receptacle
(270)
10 1/2
After finishing the ceiling job, fill gap between flange
and ceillng with caulk or other sealant to prevent air
leakage
Conduit
Machine
screw
(M4X6)
Ceiling
10 1/2
(270)
Earth ground to green
Wire nut
Live to black
(Fan)
Netural to white
Two red wires (Connect
to a general manual
wall switch)
2 Self-drilling
screws
Unit: inches (mm)
Fig.5
Fig.6
Fig.7
Ornamental
cover
Insert the sensor cover (attachment for FV-MSVK1) into slot.
Sensor
cover
11. Install the LED lamps. (Fig.9)
12. Install light cover. (Fig.10)
13. Insert the grille mounting spring on the wiring side
into the slot and insert the plug connector into the
housing of the lighting unit. (Fig.11 of page 10)
Tapes
Remove screw
(M4X8)
Light cover
LED lamp
Light cover
Fig.8
Fig.9
Secure
screw
(M4X8)
Fig.10
9
Page 10
INSTALLATION (NEW CONSTRUCTION) CONTINUED
CAUTION
Before turn on the light, make sure the
connector at the correct position. If not,
the lighting can’t work.
The claw of connector must latch the rib
completely.
14. Plug in the specified devices as your choice
(refer to installation on page 8). Insert the
motion sensor (FV-MSVK1 only) or LED night
light (FV-NLVK1 only) into slot of the grille.
Fix the lead wire into the clasp (Fig.11).
15. Adjust Pick-A-Flow switch; if used, adjust the
FV-VS15VK1 Multi-Speed module. (Fig.12)
Refer to indication on page 6.
16. Insert the other mounting spring into the slot
as shown and mount grille to fan body. (Fig.13)
CAUTION
Mount grille carefully so that lead wire of
lighting unit is not pinched.
INSTALLATION (RETROFIT)
WARNING
Disconnect power source before working
on unit.
1. Remove the existing fan and cut ceiling openning.
Secure the Flex-Z Fast bracket to joists by using 4
tapping screws (ST4.2x20) (Please prepare the
screws and put on Flex-Z Fast bracket before
Flex-Z Fast bracket is installed on joist).
TM
Existing ductwork and wiring left in place. (Fig.14)
2. Follow the step 1, 4, 5 on page 8 and step 7 on
page 9. (Before connect the circular duct to the
adaptor, should pull down the circular duct from
the ceiling)
3. Install the adaptor to Flex-Z Fast bracket by using
2 self-drilling screws. (Fig.15)
4. Secure the fan body to Flex-Z Fast bracket by
using 2 self-drilling screws, plug connector to
receptacle and secure the fan body to adaptor
by using machine screw (M4X6). (Fig.16)
TM
TM
TM
TM
Ceiling
Plug
connector
Lighting
unit
Rib
Ceiling (already existed)
Knock-out
hole
Gloves
Claw
Junction box
cover
Ceiling
Joist
Inser plug
connector
Ceiling
Grille
Conduit
Conduit
Circular duct
4 Tapping
screws (ST4.2x20)
10 7/8
Circular duct
2 Self-drilling screws
Mounting spring
Mounting spring
(275)
Motion sensor
(FV-MSVK1 only)
Clasp
LED night light
(FV-NLVK1 only)
Fig.11
Ceiling
Grille
Fig.12
Gloves
Fig.13
Unit: inches (mm)
Joist
10 7/8
(275)
Fig.14
Mastic or
approved
foil tape
Joist
Fig.15
CAUTION
Secure machine screw (M4X6) to the suitable
hole and not touch the Flex-Z Fast bracket.
Please fix the screw carefully to avoid screw
slip teeth.
5. Follow the step 10 to 16 on page 9 to 10.
10
TM
Ceiling
Machine screw (M4X6)
2 Self-drilling screws (Fix the
flange and Flex-Z Fast bracket through the ceiling)
TM
Flange
Fig.16
Page 11
MAINTENANCE (CLEANING)
WARNING
Disconnect power source before working on unit.
CAUTION
Routine maintenance must be done every year.
Please wear gloves during the cleaning work.
Never use gasoline, benzene, thinner or any other
such chemicals for cleaning the ventilating fan.
Do not immerse motor in water when cleaning.
Do not soak resin parts in water over 140 F (60 C).
1. Clean grille. (Don’t put into hot water. Use non-abrasive
kitchen detergent, wipe dry with clean cloth) (Fig.17)
2. The grille should be dry after cleaning.
3. Remove dust and dirt from fan body using a vacuum
cleaner. (Fig.18)
4. Using a cloth dampened with kitchen detergent, remove
any dirt from fan body. Wipe dry with clean cloth. (Fig.19)
5. Reinstall grille.
Gloves
Fig.17
Ceiling
Vacuum
cleaner
Fig.18
Ceiling
Gloves
Fig.19
MAINTENANCE (REPLACEMENT OF LAMP)
WARNING
Disconnect power source before working on unit.
The lamp’s glass is fragile, be careful when the lamp
is replaced.
Make sure the temperature of lens and lighting
unit has cooled down before maintenance
(cleaning) or replacement of lamp.
CAUTION
Remove dust and dirt from light cover and lens,
before replace the lamps.
The LED lamps should be replaced as the specified
type. The supplied LED lamps are not intended for
other use.
1. Remove grille by pulling down one mounting spring
(Fig.20). Remove plug connector then pull down the other.
(For models plug-in FV-MSVK1 or FV-NLVK1: Pull down the
mounting spring that without lead wire passed side, and
remove motion sensor or LED night light as shown in Fig.20)
(Squeeze mounting spring and pull down carefully)
2. Remove the screw as shown in step of Fig.21.
Remove the light cover as shown in step of Fig.21.
3. Replace the LED lamps (CX-GU24-H-B, 7W) as shown in
step 1 and step 2 of Fig.22.
4. Install the
step 1 and step 2 of Fig.9 (Page 9).
5. Install light cover. (Fig.10 of page 9)
LED lamps (CX-GU24-H-B, 7W) as shown in
Ceiling
Plug
connector
Gloves
Rib
Claw
Lens
Remove
plug
connector
Lighting
unit
Remove screw
(M4X8)
Light cover
LED lamp
Mounting spring
Motion sensor
(FV-MSVK1 only)
Clasp
LED night light
(FV-NLVK1 only)
Grille
Fig.20
Fig.21
Fig.22
11
Page 12
PRACTICAL GUIDE TO INSTALLATION
Properly insulate the area around the fan to
minimize building heat loss and gain. (Fig.23)
Loose fill or batt insulation can be placed
directly over the fan housing in the attic.
Our fans and fan/light combination units do
not create excessive heat that is a common
problem with recessed light fixtures or some
4 inches or 6 inches roof jack, wall cap,
or soffit vent with backdraft damper
Mechanically connect duct to termination
and seal with mastic or approved foil
faced tape
2-3 ft straight run before elbow
In attic installation,
caulk box to drywall
competitor’s fan/light combination. Our
efficient, cool-running motors and our LED
lighting unit do not create enough ambient
heat to be subjected to these limitations.
Short piece of flexible duct helps
alignment and absorbs sound.
Clamps plus mastic or approved
foil faced tape at all flex joints
Foil tape tightly covers all metal
duct joints (glue PVC joints)
SPECIFICATIONS
Specifications for Base Model fans
Duct
diameter
(inches)
4 or 6
Model No.
FV-05-11VKSL1
FV-05-11VKL1
FV-11-15VKL1
Air
direction
Exhaust
Exhaust
Voltage
(V)
Frequency
(Hz)
HVI Certified performance based on HVI Procedures 915, 916, and 920.
Specifications for Multi Speed fans
Model No.
FV-05-11VKSL1,
FV-05-11VKL1
(Plug-in
FV-VS15VK1)
FV-11-15VKL1
(Plug-in
FV-VS15VK1)
Air
direction
Exhaust
Exhaust
Voltage
(V)
Frequency
(Hz)
Duct
diameter
(inches)
Reference performance based on HVI Procedures 915, 916, and 920. [( ) Standby wattage.]
Air volume
at 0.1"WG
(CFM)
50
80
110
110<0.3
130
150
Air volume
at 0.1"WG
(CFM)
100
90
80
70
60
50
40
30
0
120
110
100
90
80
70
60
50
0
Noise
(sones)
<0.3
<0.3
0.4
<0.3
0.6
Noise
(sones)
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
Speed
(rpm)
750
825
965
650
680
730
Speed
(rpm)
915
865
825
795
770
750
730
725
665
650
645
640
635
630
625
620
*
Power (W)
Fan
3.6
6.0
11.0
8.5
12.0
16.5
Power (W)
Fan
8.7
7.0
6.0
4.7
3.9
3.6
2.8
2.5
9.5
8.5
6.9
5.7
5.0
4.3
4.0
3.2
Lighting
unit
Lighting
14
14
unit
14
14
Insulation
3
Weight
lb.
11.5(5.2)
11.7(5.3)
Weight
lb.
11.5(5.2)
11.7(5.3)
PRODUCT
SERVICE
Warning Concerning Removal of Covers. The unit should be serviced by qualified technicians only.
Your product is designed and manufactured to ensure a minimum of maintenance. Should your unit
require service or parts, call Panasonic Call Center at 1-866-292-7299 (USA) or 1-800-669-5165 (Canada).
Panasonic Corporation of North America
Two Riverfront Plaza, Newark, NJ 07102
www.panasonic.com