CS-A73KE
WARNING
!!
!
This service information is designed for experienced repair technicians only and is not designed for use by the general public. It does not contain
warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product. Products powered by electricity
should be serviced or repaired only by experienced professional technicians. Any attempt to service or repair the product or products dealt with
in this service information by anyone else could result in serious injury or death.
!!
PRECAUTION OF LOW TEMPERATURE
!
!!
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigeration circuit.
!!
Features
• High Efficiency
• Compact Design
• Comfort Enviroment
– 8 hours of sleep mode operation
– Air purifying filter with deodorizing function
to reduce dust, smoke and odours.
• Random Auto Restart
– Auto restart at randomly after power failure
• Removable and Washable
Front Panel
• Quality Improvement
– Gas leakage protection
– Prevent compressor reverse rotation
– 2-stage OLP to protect compressor
• Service Improvement
– Easy fan motor replacement procedure
• Operation Improvement
– Economy mode to reduce electrical power
consumption.
– Powerful mode to reaches the desired room
temperature quickly.
• Long Installation Piping
– CS/CU–A73KE, CS/CU–A93KE, long piping up to 10
meter.
– CS/CU–A123KE, long piping up to 15 meter.
– 1 –
Functions
Remote Control
CS-A73KE
OFF / ON I
MODE
FAN SPEED
AIR SWING
Operation OFF / ON
Operation Mode Selection
• AUTOAutomatic Operation Mode
• HEATHeating Operation Mode
• COOLCooling Operation Mode
• DRYSoft Dry Operation Mode
Indoor Fan Speed Selection
• h j kLow Speed
l
• h j kMedium Speed
lll
• h j kHigh Speed
lllll
• AUTO FANAutomatic Fan Speed
Airflow Direction Control
• AUTOAutomatic Airflow Direction
Control
• MANUALAirflow Direction Manual Control
TEMP.
ON-TIMER
OFF-TIMER
TIMER
SET
CANCEL
CLOCK
Room Temperature Setting
• Temperature Setting (16°C to 30°C)
• Automatic Operation
8 HI
a
a
a
9 Lo
Operation with 2°C higher than
standard temperature.
Operation with standard
temperature.
Operation with 2°C lower than
standard temperature.
Timer Operation Selection
• 24-hour, OFF / ON Real Timer Setting.
Time / Timer Setting
• Hours and minutes setting.
Timer Operation Set / Cancel
• ON Timer and OFF Timer setting and
cancellation.
Clock Setting
• Current time setting.
POWERFUL
ECONOMY
Powerful Mode Operation OFF/ON
Economy Mode Operation OFF/ON
– 2 –
SLEEP
Sleep Mode Operation OFF / ON
CS-A73KE
Functions
Indoor Unit
POWER I
AUTO
OFF / ON
TEST RUN
OFF / ON
Power Switch OFF / ON
Auto Operation Button
• Used when the remote control cannot be
used.
Remote Control Signal Receiving
Sound
• It can be controlled by pressing Auto
Operation Button for 10 seconds.
Operation Test Running / Pump
Down Switch
• Used when test running or servicing.
Operation Indication Lamps (LED)
• POWER (Red)......Lights up in operation,
blinks in Automatic
Operation Mode judging
• SLEEP (Orange).....Lights up in Sleep
Mode Operation
• TIMER (Orange).....Lights up in Timer
Setting
• POWERFUL
• ECONOMY
(Orange).....
(Green).....
Lights up in Powerful
Mode Operation
Lights up in Economy
Mode Operation
Operation Mode
• Heating, Cooling, Soft Dry and
Automatic Mode.
Random Auto Restart Control
• Operation is restarted randomly after power
failure at previous setting mode.
Anti-Freezing Control
• Anti-Freezing control for indoor heat
exchanger. (Cooling and Soft Dry)
Sleep Mode Auto Control
• Indoor Fan operates at low speed.
• Operation stops after 8 hours.
Indoor Fan Speed Control
• High, Medium and Low.
• Automatic Fan Speed Mode
– Heating: Fan speed varies from Me →
SLo in accordance with indoor
heat exchanger.
– Cooling: Fan rotates at Hi and Me
speed. Deodorizing control is
available.
– Soft Dry: Fan rotates at SLo speed.
Deodorizing control is available.
Airflow Direction Control
• Automatic air swing and manual adjusted
by remote control for vertical airflow.
• Manually adjusted by hand for horizontal
airflow.
Starting Current Control
Time Delay Safety Control
• Restarting is inhibited for appro. 3 minutes.
Powerful Operation
• Reaches the desired room temperature
quickly.
Economy Operation
• To reduce electrical power consumption.
– 3 –
7 Minutes Time Save Control
• Cooling Operation only.
Hot-Start Control
• The indoor fan remain stop until the indoor
heat exchanger temperature reaches 30°C
• The indoor fan will operate at SLo and Lo
when indoor heat exchanger temperature
reaches 30°C - 39°C
–
Functions
Outdoor Unit
CS-A73KE
CU-A73KE, CU-A93KE
Compressor Reverse Rotation
Protection Control
• To protect compressor from reverse
rotation when there is a instantaneous
power failure.
Overload Protector
• 2-Stage OLP to protect the compressor.
Overload Protector will trip when
– Temperature of compressor increases to
120°C.
– High temperature or high current flows to
compressor.
(Refer circuit diagram for OLP
characteristic)
60 Secs. Forced Operation Control
• Once the compressor is activated, it does
not stop within the first 60 secs. However, it
stops immediately with remote control stop
signal.
Outdoor Fan Operation Control
•
Inner protector.
CU-A123KE
Deice Control
• To prevent frosting at outdoor heat
exchanger. (Only for Heating Operation)
•
Temperature of outdoor heat exchanger is
sensed by TRS (Thermal Reed Switch).
Overload Protection Control
• Outdoor fan stops when indoor heat
exchanger temperature rises to 51°C and
above, and restarts when the indoor heat
exchanger temperature drops to 49°C and
below.
• Compressor stop when indoor heat exchanger temperature reaches 65°C or
above. (Heating Operation Only)
Compressor Protection Control
• If the outdoor fan motor is not running after
compressor starts for 50 secs., compressor
will stop. (Cooling and Soft Dry Operation
only).
4-Way Valve Control
• When the unit is switched to "OFF" during
Heating Operation, 4-way valve stays at
Heating position for 5 minutes.
B: BLUE
BR: BROWN
BL: BLACK
W: WHITE
R: RED
O: ORANGE
P: PINK
Y/G : YELLOW/
Resistance of Indoor Fan Motor Windings
MODEL
CONNECTION
YELLOW-BLUE
YELLOW-BROWN
BROWN-ORANGE
ORANGE-WHITE
WHITE-RED
Resistance of Outdoor Fan Motor Windings
MODEL
CONNECTION
BLUE-YELLOW
YELLOW-RED
CU-A73KE
CWA95245
260.5 Ω
446.0 Ω
Resistance of Compressor Windings
REDBLUE
MODEL
CONNECTION
C-R
C-S
CU-A73KE
2RS127D3CA04
4.023
8.803
GREEN
CS-A73KE
CWA92288
536.5 Ω
77.1 Ω
43.9 Ω
42.7 Ω
111.4 Ω
CU-A93KE
CU-A93KE
2PS174D3AA02
2.798 Ω
5.432 Ω
CS-A93KE
CWA92296
450.8 Ω
56.9 Ω
74.2 Ω
37.3 Ω
122.6 Ω
@
@
@
CU-A123KE
2KS224D5CA02
CS-A123KE
CWA92290
457.4 Ω
56.1 Ω
61.2 Ω
25.3 Ω
142.5 Ω
CU-A123KE
CWA95381
174.5 Ω
331.0 Ω
2.211 Ω
2.924 Ω
B
COMPRESSOR
R
CAPACITOR
Y
B
W
FAN MOTOR
B
CAPACITOR
R
J9990083
CS/CU-A73KE/A93KE/A123KE
A73KE07.DWG
– 15 –
CS-A73KE
Operation Details
1) Cooling Mode Operation
Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
• When the compressor is stopped by Power Switch or Remote Control, it restarts after 3 minutes when the Power
Switch or Remote Control is turned ON.
• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3
minutes.
7 minutes Time Saved Control
• The compressor will start automatically if it has stopped for 7 minutes if the room temperature is between the
compressor ON temperature and OFF temperature.
Starting Current Control
• When the compressor, outdoor fan motor & indoor fan motor are simultaneously started, the indoor fan motor will
operate 1.6 second later.
Anti-Freezing Control
• If the temperature of the indoor heat exchanger
falls continously below 2°C for 4 minutes or more,
the compressor turns off to protect the indoor heat
exchanger from freezing. The fan speed setting
remains the same.
• Compressor recommences when the indoor heat
exchanger temperature rises to 10°C (Recovery).
* 3 minutes waiting of Time Delay Safety Control
is valid for Cooling Operation.
Compressor Reverse Rotation
Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake
air and indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid).
Indoor Heat
Exchanger
Temperature
(°C)
10
2
Recovery
4 min
Compressor OFF
•
Compressor starts for > 5 minutes
• ∆ T < 2.5°C for 2 minutes
∆ T = Intake air temperature – Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
Compressor
➡➡
OFF
– 16 –
Compressor
restarts
(3 minutes waiting)
CS-A73KE
Operation Details
Compressor Protection Control
• After the compressor starts for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and
restart automatically. (Time Delay Safety Control is valid).
Comp. operates for 50 secs.
and
Fan Motor OFF
• If the above phenomenon is repeated for 3 times, the compressor will stops.
• The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
Automatic Fan Speed Mode
When Automatic Fan Speed is selected at Remote Control during cooling operation.
• Fan speed rotates in the range of Hi to Me.
• Deodorizing Control.
Indoor
Fan
stopstopstop
stop
40"
➡➡
.
.
.
✕
.
1
SLoSLoSLoSLo
30"
Compressor
OFF
20"
40"
30"160"
Compressor
restarts
(3 minutes waiting)
.
.
.
✕
.
2
Comp.
ONONOFF
* 1 Fan Speed is Hi until the compressor stops (when the room temperature reaches
setting temperature).
* 2 Fan Speed is Me after the compressor restarts.
* SLo: Indoor Fan rotates at 4 second intervals at low speed.
– 17 –