Panasonic CU-2S18NBU-1 User Manual

Order No: PHAAM1111121A1
Outdoor Unit CU-2S18NBU-1
WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public. It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product. Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service or repair the product or products dealt with in this service information by anyone else could result in serious injury or death.
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerantion circuit.
PRECAUTION OF LOW TEMPERATURE
TABLE OF CONTENTS
1. Safety Precautions.............................................3
2. Specification.......................................................5
3. Dimensions.........................................................7
4. Refrigeration Cycle Diagram.............................8
5. Block Diagram....................................................9
6. Wiring Connection Diagram............................10
7. Electronic Circuit Diagram..............................11
8. Printed Circuit Board.......................................12
8.1 Main Printed Circuit Board .........................12
8.2 Noise Filter Printed Circuit Board...............13
9. Installation Information ...................................14
9.1 Check Points ..............................................14
10. Installation Instruction.....................................15
10.1 SELECT THE BEST LOCATION ...............15
10.2 INSTALL THE OUTDOOR UNIT................17
10.3 CONNECT THE PIPING............................17
10.4 EVACUATION OF THE EQUIPMENT.......18
10.5 CONNECT THE CABLE TO THE
OUTDOOR UNIT........................................18
10.6 HEAT INSULATION ...................................19
11. Operation Control.............................................20
© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2011. Unauthorized copying and distribution is a violation of law.
12.12
Valve close detection control......................23
12.13 Compressor discharge high pressure
protection control ........................................23
13. Servicing Mode.................................................24
13.1 Pump Down Operation ...............................24
13.2 Test Operation............................................24
13.3 Wiring Error Check .....................................24
13.4 Power Save Mode ......................................25
13.5 Mode priority function .................................25
14. Troubleshooting Guide....................................26
14.1 Self Diagnosis Function..............................26
15. Disassembly and Assembly Instructions ......28
15.1 Outdoor Unit Removal Procedure ..............28
16. Technical Data ..................................................31
16.1 Operation Characteristics...........................31
17. Exploded View and Replacement Parts List..41
2
1. Safety Precautions
Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.
Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and
main circuit for the model installed.
The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below. Incorrect installation or servicing due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the following indications.
WARNING CAUTION
The items to be followed are classified by the symbols:
Carry out test running to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
1. Do not modify the machine, part, material during repairing service.
2. If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit.
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to properties.
This symbol denotes item that is PROHIBITED from doing.
WARNING
3. Do not wrench the fasten terminal. Pull it out or insert it straightly.
Engage authorized dealer or specialist for installation and servicing. If installation or servicing done by the user is defective, it will cause
4. water leakage, electrical shock or fire.
5. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.
Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage,
6. fire or electrical shock.
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
7. done, the set will drop and cause injury.
For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single
8. outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD).
9.
Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown.
Do not use joint cable for indoor / outdoor connection cable. Use specified indoor / outdoor connection cable, refer to Installation
10.
Instructions CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor / outdoor connection. Clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat up or fire at the connection.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
11. cause heat-up or fire at the connection point of terminal, fire or electrical shock.
When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg. air etc. mix into refrigerant cycle
12. (piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may
13. climb up to outdoor unit and cross over the handrail and causing accident.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and
14. telephone. Otherwise, it may cause electrical shock in case equipment breakdown or insulation breakdown.
15. Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.
Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with
16. other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the
17. flare may break and cause refrigerant gas leakage.
For R410A models, when connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only R410A materials.
18.
Thickness of copper pipes used with R410A must be more than 0.8mm (1/32”). Never use copper pipes thinner than 0.8mm (1/32”). It is desirable that the amount of residual oil is less than 40 mg/10m (0.0008 oz/ft).
During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrigeration
19.
piping and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).
3
WARNING
During pump down operation, stop the compressor before remove the refrigeration piping. (Removal of refrigeration piping while
20.
compressor is operating and valves are opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).
After completion of installation or service, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant
21. contacts with fire.
22. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire.
23. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.
24. Must not use other parts except original parts describe in catalog and manual.
25. Using of refrigerant other than the specified type may cause product damage, burst and injury etc.
CAUTION
Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of
1. the unit, it may cause fire.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
2. furniture.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may
3. break and cause refrigerant gas leakage.
4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.
5. Select an installation location which is easy for maintenance.
Pb free solder has a higher melting point than standard solder; typically the melting point is 50°F – 70°F (30°C – 40°C) higher. Please use
6.
a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C). Pb free solder will tend to splash when heated too high (about 1100°F / 600°C). Power supply connection to the air conditioner. Power supply cord shall be UL listed or CSA approved 4 conductors with minimum AWG12 wires. Power supply point should be in an easily accessible place for power disconnection in case of emergency.
7. In some countries, permanent connection of this air conditioner to the power supply is prohibited.
Fix power supply connection to a circuit breaker for the permanent connection. Use NRTL approved fuse or circuit breaker (rating refers to name plate) for the permanent connection.
Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigerant parts. Take
8. care of the liquid refrigerant, it may cause frostbite.
9. Installation or servicing work: It may need two people to carry out the installation or servicing work.
10. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
11. Do not sit or step on the unit, you may fall down accidentally.
12. Do not touch the sharp aluminum fin, sharp parts may cause injury.
4
2. Specification
Model Outdoor Unit CU-2S18NBU-1
Indoor Unit Combination 3.2kW + 3.2kW
Power Source
Capacity
Running Current A 7.6 - 6.9
Cooling Operation
Maximum Current A 13.6
Starting Current A 7.8
Minimum Circuit Ampacity A 20
Dimension
Connection Cable 3 + 1 (Earth) ø1.5 mm2
Pipe Length Range (1 room) m (ft) 3 ~ 25 (9.8 ~ 82.0)
Maximum Pipe Length (Total Room) m (ft) 50 (164.0)
Refrigerant Pipe Diameter
Compressor
Air Circulation
Fan Speed High RPM 650
Heat Exchanger
Air Volume High m3/min (ft3/min) 37.2 (1313)
Refrigerant Control Device Expansion Valve
Refrigerant Oil FV50S
Refrigerant (R410A) g (oz) 1.92k (67.8)
Indoor Operation Range Cooling
Outdoor Operation Range Cooling
Electrical
Data
Noise
Net Weight kg (Ib) 69 (152)
Rated Output W 1.30k
Rated Output W 60
Tube Material Copper
Dry Bulb Wet Bulb
Power Input kW 1.45 (0.39 ~ 1.84)
EER W/W 3.37 (5.38 ~ 3.18)
BTU/hW 11.50 (18.45 ~ 10.85)
Sound Pressure Level dB-A 48
Sound Power Level dB 62
Height mm (inch) 795 (31-5/16)
Width mm (inch) 875 + 95 (34-15/32 + 3-3/4)
Depth mm (inch) 320 (12-5/8)
Liquid Side mm (inch) 6.35 (1/4)
Gas Side mm (inch) 9.52 (3/8)
Type Hermetic (Rotary)
Motor Type DC Brushless (4-poles)
Type Propeller Fan
Motor Type DC Brushless (8-poles)
Type Plate fin configuration forced draft type
Fin Material Aluminum
Row/Stage 2/36
FPI 19
Maximum °F 89.6 73.4
Minimum °F 60.8 51.8
Maximum °F 109.4 78.8
Minimum °F 60.8 51.8
kW 4.89 (2.10 ~ 5.86)
BTU/h 16700 (7200 ~ 20000)
Note
Specifications are subject to change without notice for further improvement.
1 Phase, 208-230V, 60Hz
(Power supply from outdoor unit)
5
Multi split combination possibility:
o A single outdoor unit enables air conditioning of up to two separate rooms for CU-2S18NBU-1.
Outdoor Unit CU-2S18NBU-1 A B
2.8 kW CS-S9NKUW-1
Wall
Capacity range of connectable indoor units From 5.6 kW to 6.4 kW
1 room maximum pipe length (m (ft)) 25 (82.0) Allowable elevation (m (ft)) 15 (49.2) Total allowable pipe length (m (ft)) 50 (164.0) Total pipe length for maximum chargeless length (m (ft)) 20 (65.6)
Piping Length
Additional gas amount over chargeless length (g/m (oz/ft)) 20 (0.2)
Remarks for CU-2S18NBU-1
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor unit that will be connected to outdoor unit must be within connectable capacity range of indoor unit.
(as shown in the table above) Example: The indoor units’ combination below is possible to connect to CU-2S18NBU-1. (Total nominal capacity of indoor units is between 5.6 kW to 6.4 kW)
1) Two CS-S9NKUW-1 only. (Total nominal cooling capacity is 5.6 kW)
2) One CS-S9NKUW-1 and one CS-S12NKUW-1. (Total nominal cooling capacity is 6.0 kW)
3.2 kW CS-S12NKUW-1
Note: “●” : Available
Outdoor Unit
CU-2S18NBU-1
Indoor unit combination Capacity (kW) Input Power (W)
Operation Class (kW)
One-room Operation
Two-room Operation
2.8 2.82 1.81 ~ 3.27 850 390 ~ 1020 4.5 4.1 0.5
3.2
2.8 + 2.8 4.89 2.09 ~ 5.86 1450 390 ~ 1920 7.6 6.9 0.5 + 0.5
2.8 + 3.2 4.89 2.10 ~ 5.86 1450 390 ~ 1870 7.6 6.9 0.5 + 0.6
3.2 + 3.2
Operation
Mode
Cooling
Cooling
Rating Min - Max Rating Min - Max
3.21 1.85 ~ 3.75 1000 390 ~ 1230 5.2 4.7 0.6
4.89 2.10 ~ 5.86 1450 390 ~ 1840 7.6 6.9 0.6 + 0.6
Current (A)
208V 60Hz
Current (A)
230V 60Hz
Moisture Removal
Volume (L/h)
Outdoor Unit
CU-2S18NBU-1
Indoor unit combination Capacity (BTU/h) Input Power (W)
Operation Class (kW)
One-room Operation
Two-room Operation
2.8 9600 6200 ~ 11200 850 390 ~ 1020 4.5 4.1 1.1
3.2
2.8 + 2.8 16700 7100 ~ 20000 1450 390 ~ 1920 7.6 6.9 1.1 + 1.1
2.8 + 3.2 16700 7200 ~ 20000 1450 390 ~ 1870 7.6 6.9 1.1 + 1.3
3.2 + 3.2
Operation
Mode
Cooling
Cooling
Rating Min - Max Rating Min - Max
10900 6300 ~ 12800 1000 390 ~ 1230 5.2 4.7 1.3
16700 7200 ~ 20000 1450 390 ~ 1840 7.6 6.9 1.3 + 1.3
Current (A)
208V 60Hz
Current (A)
230V 60Hz
Moisture Removal
Volume (Pt/h)
Specifications are subject to change without notice for further improvement.
6
3. Dimensions
7
4. Refrigeration Cycle Diagram
8
5. Block Diagram
9
6. Wiring Connection Diagram
10
7. Electronic Circuit Diagram
11
8. Printed Circuit Board
8.1 Main Printed Circuit Board
12
8.2 Noise Filter Printed Circuit Board
13
9. Installation Information
9.1 Check Points
QUICK GUIDE
PIPING & ELECTRICAL SPECIFICATION
Indoor(ID) & Outdoor(OD) units:
Possible Combination Patterns
Outdoor (OD): CU-2S18NBU-1
Indoor (ID): 2 UNITS OF
CS-S9NKUW-1
Outdoor (OD): CU-2S18NBU-1
Indoor (ID): 2 UNITS OF
CS-S12NKUW-1
Outdoor (OD): CU-2S18NBU-1
Indoor (ID): 1 UNIT OF
CS-S9NKUW-1
+ 1 UNIT OF CS-S12NKUW-1
Capacity
Refrigerant
(Btu/h)
16700 R410A
Piping size
Gas Liquid
ø3/8"
(ø9.52mm)
ø1/4"
(ø6.35mm)
Standard
pipe
length
24.6 ft 49.2 ft 9.8 ft 82.0 ft 164.0 ft 65.6 ft 0.2 oz / ft
Max.
Elevation
Min. pipe length for
each ID
unit
Max. from
OD to
each ID
Max.
total
length
Min. total
pipe
length for
additional
gas
Additional refrigerant
Power supply
208/230V
60 Hz MCA 20A MOP 25A
Power
OD-ID
supply
connection
wire size
wire size
AWG12 AW G16
Example:
If total piping length of all installed indoor units is at 68.6 ft, the quantity of additional refrigerant should be 0.6 oz .......... (68.6 – 65.6) ft x 0.2 oz/ ft
= 0.6 oz.
14
10. Installation Instruction
10.1 SELECT THE BEST LOCATION
10.1.1 OUTDOOR UNIT
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.
There should not be any animal or plant which could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
Recommended installation height for outdoor unit should be above the seasonal snow level.
Refrigerant piping size
Outdoor Unit CU-2S18***
Liquid - side ø1/4" thickness 1/32"
Gas - side ø3/8" thickness 1/32"
Outdoor Unit CU-2S18***
Min. total piping length for
additional gas
If total piping length of all indoor units exceeds the minimum length listed above, additionally charge with 0.2 oz of refrigerant (R410A) for each additional feet of piping.
Allowable piping length of each indoor unit (min. ~ max.) 9.8 ft ~ 82.0 ft
Allowable total piping length of all indoor unit 164.0 ft or less
Height difference between indoor and outdoor unit
Height difference between indoor unit
65.6 ft
Allowable piping length
Outdoor Unit CU-2S18***
Outdoor unit located on upper side
Outdoor unit located otherwise
Outdoor unit located on upper side
Outdoor unit located otherwise
10.1.2 Outdoor Unit Installation Diagram
This illustration is for explanation purposes only.
* Note: Respective indoor unit installation procedure shall
refer to instruction manual provided in the indoor unit packaging.
49.2 ft or less
24.6 ft or less
24.6 ft or less
49.2 ft or less
15
Outdoor Unit Installation Guidelines
Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below.
For any of the below installation patterns, the wall height on the exhaust side should be 47 1/4" or less.
16
10.2 INSTALL THE OUTDOOR UNIT
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and horizontally with bolt nut (ø13/32").
2. When installing on a roof, please consider strong winds and earthquakes. Please fasten the installation stand firmly with bolt or nails.
Model A B C D
CU-2S18*** 24-1/8" 5-5/32" 5/8" 14-3/16"
10.3 CONNECT THE PIPING
Remove the control board cover (resin) from the outdoor unit by loosening three screws.
10.3.1 Connecting the Piping to Outdoor Unit
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut (locate at valve) onto the copper pipe. Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.
Do not overtighten, over tightening may cause gas leakage.
Piping size Torque
1/4" (0.02 ft) [18 N•m (13.3 Ibf. ft)]
3/8" (0.03 ft) [42 N•m (31.0 Ibf. ft)]
1/2" (0.04 ft) [55 N•m (40.6 Ibf. ft)]
5/8" (0.05 ft) [65 N•m (47.9 Ibf. ft)]
3/4" (0.06 ft) [100 N•m (73.8 Ibf. ft)]
10.3.2 Gas Leak Checking
Pressure test to system to 400 PSIG with dry nitrogen, in stages. Thoroughly leak check the system. If the pressure holds, release the nitrogen and proceed to section 10.4.
17
10.4 EVACUATION OF THE EQUIPMENT
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the gas side 3-way valve.
2. Connect the micron gauge between vacuum pump and service port of outdoor units.
3. Turn on the power switch of the vacuum pump and make sure that connect digital micron gauge and to pull down to a value of 500 microns.
4. To make sure micron gauge a value 500 microns and close the low side valve of the charging set and turn off the vacuum pump.
5. Disconnect the vacuum pump house from the service port of the 3-way valve.
6. Tighten the service port caps of gas side 3-way valve at a torque of 13.3 Ibf.ft with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “Open” using a hexagonal wrench (5/32").
8. Mount valve caps onto the 2-way valve and 3­way valve.
Be sure to check for gas leakage.
CAUTION
If micron gauge value does not descend 500 microns, take the following measures:
o If the leak stops when the piping connections are tightened further, continue working from step e. o If the leak does not stop when the connections are retightened, repair location of leak. o Do not release refrigerant during piping work for installation and reinstallation. o Take care when handling the liquid refrigerant, it may cause frostbite.
10.5 CONNECT THE CABLE TO THE OUTDOOR UNIT
1. Remove Control Board Cover (Metal) by loosening 2 screws.
2. Remove Valve Cover (Metal) by loosening 2 screws.
3. Remove Plugs.
4. Fix the conduit connectors to the knock out holes with lock-nuts, then secure them.
5. Connecting wire between indoor unit and outdoor unit should be UL listed or CSA approved 4 conductor wires minimum AWG16 in accordance with local electric codes.
6. Wire Connection to the power supply (208/230V 60Hz) through circuit breaker.
Connect the UL listed or CSA approved wires minimum AWG12 to the terminal board, and connect to other end of the wires to circuit breaker.
7. Connect the power supply cord and connecting wires between indoor unit and outdoor unit according to the diagram as shown.
18
t
8. For wire stripping and connection requirement, refer to the diagram below.
9. Secure the power supply cord and connecting cables onto the control board with the holder.
10. Attach the control board cover (metal and resin) and valve cover back to the original position with screw.
10.6 HEAT INSULATION
se a material with good heat-resistant properties as the heat insulation for
Liquid-side pipes
CAUTION
he pipes. Be sure to insulate both the gas-side and liquid-side pipes. If the pipes are not adequately insulated, condensation or water leakages may occur.
Gas-side pipes
Cutting and Flaring the Piping
1 Please cut using pipe cutter and then remove the burrs. 2 Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3 Please make flare after inserting the flare nut onto the copper pipes.
Material shall
withstand 248°F or
higher
19
11. Operation Control
11.1 Cooling Operation
11.1.1 Outdoor fan control
When cooling operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted according to figure below:
11.1.2 Powerful Operation 1
During cooling operation, this control is to concentrate outdoor unit capability to the powerful operation enabled indoor unit by temporary stop the capability supply to low load demand indoor units.
Operation start condition: o Powerful operation ON for targeted indoor unit.
Operation content: o If other indoor units (where Powerful operation are OFF) achieve setting temperature continuously for 1
minutes after received powerful command from indoor unit, then capability supply to other indoor units are stopped for minimum 3 minutes. Capability supply stop period follows powerful operation period.
Operation stops when comply either one of the following conditions:
o When other indoor units (where Powerful operation are OFF) is lower than setting temperature. o When the powerful operation is OFF for all indoor units. o When Quiet operation received from 1 indoor unit. o When protection control starts.
11.1.3 Powerful Operation 2
During cooling operation, this control is to provide fast cooling operation compare to normal operation.
Operation start if all condition below are complied:
o Powerful operation ON for indoor unit.
Operation content:
o Outdoor fan speed will adjust automatically. o Compressor frequency will adjust automatically.
Operation stop when comply either one of the follow conditions:
o When the powerful operation is OFF for all indoor units.
20
12. Protection Control
12.1 Freeze Prevention control (Cool)
When received freeze prevention signal from indoor unit, the compressor frequency changes according to indoor heat exchanger temperature.
When indoor unit request capability OFF due to freeze condition , immediately the capability supply to targeted indoor unit stops.
12.2 Dew Prevention control (Cool)
When received dew prevention signal from indoor unit, the compressor frequency changes according to indoor intake temperature and indoor heat exchanger temperature.
12.3 Electronic Parts Temperature Rise Protection 1 (Cool)
This control prevents electronic parts temperature rise during cooling overload condition.
Start conditions:
o Outdoor ambient temperature is at protection region as shown in figure below:
o Outdoor unit total current is above 5.5A
Control content
o Outdoor fan speed is adjusted accordingly.
Control stop condition
o When outdoor ambient temperature is back to normal region.
During this control, outdoor fan speed does not reduce for Quiet operation.
12.4 Electronic Parts Temperature Rise Protection 2 (Cool)
This control prevents electronic parts temperature rise during cooling/dry operation.
Start conditions:
o Total current is at protection region as shown in figure below:
Control content
o Outdoor fan speed is adjusted accordingly.
Control stop condition
o When total current is back to normal region.
During this control, outdoor fan speed does not reduce for Quiet operation.
21
12.5 Cooling overload control (Cool)
This control detect outdoor pipe temperature and perform the compressor frequency restriction during cooling operation.
12.6 Time Delay Safety Control (Restart Control)
The compressor will not restart within three minutes after compressor is stopped.
This control is not applicable if the power supply reset.
12.7 30 seconds Force Operation
Once the compressor starts operation, it will not stop its operation for 30 seconds in order to cycle back compressor oil.
However, it can be stopped using remote control or Auto OFF/ON button at indoor unit.
12.8 Total Current Control
By referring to table below, during normal (default) operation, the running current refer to Hi values and during Power Save Mode, the running current refer to Lo values.
When the outdoor unit total running current (AC) exceeds X value, compressor frequency will decrease.
If the running current does not exceed X value for 5 seconds, compressor frequency will increase.
However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3
minutes.
Operation Mode
Cooling/Soft Dry (A)
Cooling/Soft Dry (B)
Hi 14.0 17.5
Lo 7.8 17.5
Hi 14.0 17.5
Lo 7.8 17.5
X (A) Y (A)
CU-2S18NBU-1
12.9 IPM (power transistor) Protection Control
Overheating Prevention Control
o If IPM temperature rises to 176°F, outdoor fan speed will be increased. o When the IPM temperature rises to 203°F, compressor operation will stop immediately. o Compressor operation restarts when temperature decreases to 194°F. o If IPM temperature detected less than -22°F, IPM is judged as open circuit (“F96” is indicated).
DC Peak Current Control
o When IPM DC current exceeds set value of 30.0 ± 3.0 A, the compressor will stop. o If the DC peak current detected within 30 seconds after operation starts, compressor will restart after 1
minute.
o If the DC peak current detected 30 seconds or more after operation starts, compressor will restart after 2
minute.
o Within 30 seconds after compressor restarts, if the DC peak current is exceeded set value continuously for 7
times, all indoor and outdoor relays will be cut off (“F99” is indicated).
Error reset can be done by power supply reset.
22
12.10 Compressor Protection Control (Gas leak detection control 1)
Control start conditions
o For 5 minutes, the compressor continuously operates and total current is low. o During Cooling or Soft Dry operation:
Indoor intake temperature — indoor piping temperature is below 39.2°F.
Control content
o Compressor stops (and restart after 3 minutes) o If the conditions above happen 4 times within 60 minutes, the unit will stop operation (“F91” is indicated).
12.11 Compressor Protection Control (Gas leak detection control 2)
This control detect gas leakage condition to prevent compressor damage.
Control start condition
o All connected indoor units capability supply ON. o Compressor ON with maximum frequency. o Compressor discharge temperature high.
Control content
o Compressor OFF during this control (“F91” is memorized in EEPROM) o If the above conditions happen 2 times within 60 minutes, indoor units’ Timer LED will blinks (“F91” is
indicated at all indoor units)
12.12 Valve close detection control
This control detects 3-way valve close condition to prevent damage to refrigerant cycle.
Start conditions:
o For all connected indoor units, if Indoor intake temperature — indoor piping temperature are between 28.4°F
and 35.6°F continuously for 5 minutes after compressor ON at first cooling operation.
o The first cooling operation is defined as cooling operation is ON for less than 8 minutes after new installation
or after pump down.
Control content
o During this control, compressor stop, indoor units’ Timer LED will blink. (“F91” is indicated at indoor units)
Error reset can be done by power supply reset or reset by using remote control.
12.13 Compressor discharge high pressure protection control
This control protect by using high pressure switch during operation.
Start conditions
o High pressure switch is activated (from normally close to open) when outdoor operation mode is cooling
during compressor running.
Control 1 content
o Compressor stop when high pressure switch is opened and restart after high pressure switch closed. If this
condition happen 4 times within 30 minutes, “F94” is indicated.
o After 30 minutes, counter is reset if this condition does not happen for 4 times.
Control 1 stop conditions
o Power supply reset o Reset by using remote control
23
13. Servicing Mode
13.1 Pump Down Operation
Operate the pump down according to the following procedures. 1 Confirm the valve on the liquid side and gas
side is open.
2 Press PUMP DOWN switch (SW1) on the
display printed circuit board for more than 5 seconds. Pump down (cooling) operation is performed for 15 minutes.
3 Set the liquid side 3 way valve to close
position and wait until the pressure gauge indicates 1.45 PSI.
4 Immediately set the gas side valve to close
position and then press the PUMP DOWN switch (SW1) to stop the pump down operation. Note: Pump down operation will stop automatically after 15 minutes if PUMP DOWN switch (SW1) is not pressed again. Pump down operation cannot be restarted until 3 minutes after compressor is stopped.
LED 2 3 4 5 Message
○ ○ ○ ○ ○ ○ ○ ○ ○
Status
2 minutes before operation end
1 minute before operation end
Pump down operation end
Pump down operation progress
3 minutes before operation end
: Flashing
13.2 Test Operation
Test operation can be carried out using OPERATION TEST switch (SW2) on the display printed circuit board inside the outdoor unit. For cooling test, press the TEST OPERATION switch (SW2) for more than 5 seconds. LED 1 and LED 2 will illuminate when shift into cooling test operation.
13.3 Wiring Error Check
This product capable to correcting the wiring errors automatically by following procedures.
1 Confirm the valve on the liquid side and gas
side is open.
2 Press WIRING CHECK switch (SW3) on the
display printed circuit board for more than 10 seconds to start wiring check operation.
3 Wiring check process will complete in
approximately 10 minutes. However, wiring check operation will not start within 3 minutes after compressor is stopped. When outdoor air temperature is less than 41°F or unit has abnormality, wiring check will not start. (See
NOTE 2). The LED 2 to 6 in display printed circuit board inside the outdoor unit indicate whether correction is possible or not and the status of the correction, as shown in the table below.
LED 2 3 4 5 6 Message
ROOM A B - - -
All flashing Automatic correction impossible
LED 2, 4, 6 and LED 3,
5 alternatively flashing
Flashing one after
Status
another
Other than above Unit has abnormally (Note 4)
If automatic correct is impossible, check the indoor unit wiring and piping manually.
Wiring check in progress
Automatic correction completed
24
NOTE
1. For two rooms, LED 4 and 5 are not illuminated after wiring operation complete.
2. If the outdoor air temperature is less than 41°F or unit has abnormality, wiring operation will not start.
3. After wiring check operation is complete, LED indication will illuminated until normal operation starts.
4. Follow the product diagnosis procedure. (Check the diagnostic label at the control board cover.)
5. When LED 1 only illuminate, indicates that outdoor unit is operating normally.
13.4 Power Save Mode
Power Save Mode can be enabled by pushing POWER SAVE switch (SW4) to ON before power supply ON.
When Power Save Mode is ON, the unit can be operate at lower running current where the breaker capacity not
achieve the requirement.
13.5 Mode priority function
Mode priority function can be enabled by pushing MODE PRIORITY switch (SW5) to ON before power supply ON.
When Mode Priority Function is ON, the mode priority is given to higher capacity indoor units.
25
14. Troubleshooting Guide
14.1 Self Diagnosis Function
The display screen of wireless remote control unit and the self-diagnosis LEDs (green) on the outdoor printed circuit board in the outdoor unit can be used to identify the location of the problem. Refer to the table below to identify and solve the cause of the problem, and then re-start the air conditioner system.
If the problem is solved and operation returns to normal. LED 1 illuminates and others LED are off.
Diagnosis
display
H11
H12
H15
H16
H27
H28
H32
H33
H36
H37
H64
H97
Abnormality
or
Protection
control
Indoor/outdoor
abnormal
communication
Indoor unit
capacity
unmatched
Compressor temperature
sensor
abnormality
Outdoor
current
transformer
(CT)
abnormality
Outdoor air
temperature
sensor
abnormality
Outdoor heat
exchanger
temperature
sensor 1
abnormality
Outdoor heat
exchanger
temperature
sensor 2
abnormality
Indoor/outdoor misconnection
abnormality
Outdoor gas
pipe
temperature
sensor
abnormality
Outdoor liquid
pipe
temperature
sensor
abnormality
Outdoor high
pressure
sensor
abnormality
Outdoor fan
motor
mechanism
lock
LED 6 LED 5 LED 4 LED 3 LED 2 LED 1 Abnormality
operation for
power supply
for 1 minutes
happen within
Judgment
After
1 minute
90s after
Continuous
for 5s
Continuous
for 5s
Continuous
for 5s
Continuous
for 5s
Continuous
for 5s
Continuous
for 5s
Continuous
2 times
30 minutes
Protection
Operation
Indoor fan only
operation can
start by entering into force cooling
operation
Heating
protection
operation only
Cooling
protection
operation only
Problem Check location
Indoor/outdoor
Indoor/outdoor
communication
not establish
Total indoor
capability more
than maximum
limit or less than
minimum limit, or
number of
indoor unit less
than two
Compressor
temperature
sensor open or
short circuit
Current
transformer
faulty or
compressor
faulty
Outdoor air
temperature
sensor open or
short circuit
Outdoor heat
exchanger
temperature
sensor 1 open or
short circuit
Outdoor heat
exchanger
temperature
sensor 2 open or
short circuit
Indoor and
outdoor rated
voltage different
Outdoor gas pipe
temperature
sensor open or
short circuit
Outdoor liquid
pipe temperature
sensor open or
short circuit
High pressure
sensor open
circuit during
compressor stop
Outdoor fan motor
lock or feedback
abnormal
wire terminal
Indoor/outdoor PCB
Indoor/outdoor connection wire
Indoor/outdoor connection wire
Indoor/outdoor PCB
Specification and combination table in catalogue
Compressor temperature sensor lead wire and connector
Outdoor PCB faulty or compressor faulty
Outdoor air temperature sensor lead wire and connector
Outdoor heat exchanger temperature sensor 1 lead wire and connector
Outdoor heat exchanger temperature sensor 2 lead wire and connector
Indoor and outdoor units check
Outdoor gas pipe temperature sensor lead wire and connector
Outdoor liquid pipe temperature sensor lead wire and connector
High pressure sensor
Lead wire and connector
Outdoor fan motor lead wire and connector
Fan motor lock or block
26
Diagnosis
display
H98
H99
F11
F17
F90
F91
F93
F94
F95
F96
F97
F98
F99
Abnormality
or
Protection
control
Indoor high
pressure
protection
Indoor
operating unit
freeze
protection
4-way valve
switching
abnormality
Indoor standby
units freezing
abnormality
Power factor
correction
(PFC) circuit
protection
Refrigeration
cycle
abnormality
Compressor
abnormal
revolution
Compressor
discharge
pressure overshoot protection
Outdoor cooling
high pressure
protection
Power transistor
module
overheating
protection
Compressor
overheating
protection
Total running
current
protection
Outdoor direct
current (DC)
peak detection
LED 6 LED 5 LED 4 LED 3 LED 2 LED 1 Abnormality
Judgment
4 times
happen within
30 minutes
3 times
happen within
40 minutes
4 times
happen within
10 minutes
2 times
happen within
20 minutes
4 times
happen within
20 minutes
4 times
happen within
30 minutes
4 times
happen within
20 minutes
4 times
happen within
30 minutes
3 times
happen within
30 minutes
3 times
happen within
20 minutes
Continuous
happen for 7
times
Protection
Operation
Problem Check location
Indoor high
pressure
protection
(Heating)
Indoor freeze
protection
(Cooling)
4-way valve
Switching
abnormal
Wrong wiring and
connecting pipe, expansion valve
leakage, indoor heat exchanger
sensor open circuit
Power factor
correction circuit
abnormal
Refrigeration
cycle abnormal
Compressor
abnormal
revolution
Compressor
discharge pressure
overshoot
Cooling high
pressure
protection
Power transistor module overheat
Compressor
overheat
Total current
protection
Power transistor
module current
protection
Check indoor heat exchanger
Air filter dirty
Air circulation
short circuit
Check indoor heat exchanger
Air filter dirty
Air circulation
short circuit
4-way valve
Lead wire and
connector
Check indoor/ outdoor connection wire and pipe
Indoor heat exchanger sensor lead wire and connector
Expansion valve lead wire and connector
Outdoor PCB faulty
Insufficient refrigerant or valve close
Power transistor module faulty or
compressor lock
Check refrigeration system
Check refrigeration system
Outdoor air circuit
PCB faulty
Outdoor air circuit
(fan motor)
Insufficient refrigerant
Check refrigeration system
Power source or compressor lock
Power transistor module faulty or
compressor lock
LED 1 illuminate is indicated that outdoor unit is operating normally. If the LED 1 is switched off or flashing, check the power supply and self-diagnosis indication.
---------- Illuminate
---------- Flashing
Blank
---------- OFF
27
15. Disassembly and Assembly Instructions
High Voltages are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks.
15.1 Outdoor Unit Removal Procedure
Caution! When handling electronic controller, be careful of electrostatic discharge.
15.1.1 Removing the Cabinet Top Plate and Cabinet Front Plate
1. Remove the cabinet top plate (remove the 8 screws).
2. Remove the 8 screws (1 on the center, 3 at the top and 4 at the bottom) securing the cabinet front plate, release the 2 hooks (1 each at the left and right), and pull the cabinet front plate toward front side.
WARNING
15.1.2 Remove the Control Board Cover and Particular Plates
3. Remove the control board cover (remove 3 screw).
4. Remove the particular plate (remove 2 screw).
5. Remove the particular plate (remove 2 screw).
28
15.1.3 Removing the Control P.C. Board
6. Remove the drip proof cover.
7. Disconnect the connectors (lead wires of the compressor, sensor, and others).
8. Remove the screw at the right side of the control box, and pull out the entire control box.
9. Release the control P.C. Board tab to remove the control P.C. Board.
15.1.4 Removing the Propeller Fan and Fan Motor
1. Follow the steps in 15.1.1 for removing the cabinet top plate and cabinet front plate.
2. Remove the propeller fan by removing the nut turning clockwise at its center.
29
3. Disconnect the fan motor connector from the control P.C. Board.
4. Loosen the 4 fan motor mounting screws then remove the fan motor.
30
16. Technical Data
16.1 Operation Characteristics
16.1.1 CS-S9NKUW-1 CU-2S18NBU-1
Cooling Characteristic
o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping length: 24.6ft o Compressor Freq: Fc
31
Piping Length Characteristic
o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F (DBT) o Compressor Freq: Fc
32
16.1.2 CS-S9NKUW-1x2 CU-2S18NBU-1
Cooling Characteristic
o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping length: 24.6ft o Compressor Freq: Fc
33
Piping Length Characteristic
o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F (DBT) o Compressor Freq: Fc
34
16.1.3 CS-S12NKUW-1 CU-2S18NBU-1
Cooling Characteristic
o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping length: 24.6ft o Compressor Freq: Fc
35
Piping Length Characteristic
o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F (DBT) o Compressor Freq: Fc
36
16.1.4 CS-S12NKUW-1x2 CU-2S18NBU-1
Cooling Characteristic
o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping length: 24.6ft o Compressor Freq: Fc
37
Piping Length Characteristic
o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F (DBT) o Compressor Freq: Fc
38
16.1.5 CS-S12NKUW-1+CS-S9NKUW-1 CU-2S18NBU-1
Cooling Characteristic
o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping length: 24.6ft o Compressor Freq: Fc
39
Piping Length Characteristic
o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F (DBT) o Compressor Freq: Fc
40
17. Exploded View and Replacement Parts List
Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
41
REF. NO. DESCRIPTION & NAME QTY. CU-2S18NBU-1 REMARK
1 BASE PAN ASS'Y 1 CWD52K1240A 2 SOUND-PROOF BOARD 1 CWH151230 3 FAN MOTOR BRACKET 1 CWD541127 5 CONDENSER COMPLETE 1 CWB32C2925 6 FAN MOTOR 1 EHDS80CAC O 8 PROPELLER FAN 1 CWH00K1006
9 NUT - PROPELLER FAN 1 CWH561038J 10 COMPRESSOR 1 5KD184XAB21 11 PACKING 3 CWB81043 12 ANTI - VIBRATION BUSHING 3 CWH50055 13 NUT - COMPRESSOR 3 CWH561049 16 ACUMULATOR 1 CWB131050 17 3-WAY VALVE (LIQUID) 2 CWB011601 O 18 3-WAY VALVE(GAS) 2 CWB011602 O 19 HOLDER COUPLING 1 CWH351170 20 STRAINER 1 CWB111062 21 STRAINER 2 CWB111063 22 EXPANSION VALVE 2 CWB051029 23 4-WAYS VALVE 1 CWB001057 24 DISCHARGE MUFFLER 1 CWB121042 25 PRESSURE SWITCH 1 CWA101007 26 UNION NUT 4 CWT251030 27 UNION NUT 4 CWT251031 28 SOUND PROOF MATERIAL 1 CWG302246 29 SOUND PROOF MATERIAL 1 CWG302520 30 SOUND PROOF MATERIAL 1 CWG302521 31 SOUND PROOF MATERIAL 1 CWG302522 32 SENSOR-COMPLETE 1 CWA50C2722 O 34 V-COIL COMPLETE 1 CWA43C2381 O 35 V-COIL COMPLETE 1 CWA43C2382 O 39 SENSOR-COMPLETE 1 CWA50C2710 O 40 SENSOR-COMPLETE 1 CWA50C2691 O 42 HOLDER-SENSOR 1 CWH32074 43 ELECTRONIC CONTROLLER-MAIN 1 CWA73C6132R O 44 ELECTRONIC CONT.-NOISE FILTER 1 CWA745975 O 47 REACTOR 1 G0C403J00001 O 48 TERMINAL BOARD ASS'Y 1 CWA28K1195 O 49 TERMINAL BOARD ASS'Y 2 CWA28K1196 O 50 CONTROL BOARD COVER(TOP) 1 CWH131333 52 CABINET TOP PLATE 1 CWE031131A 53 CONTROL BOARD COVER COMPLETE 1 CWH13C1209 54 CABINET FRONT PLATE CO. 1 CWE06K1071 55 CABINET SIDE PLATE( L ) 1 CWE041489A 56 CABINET SIDE PLATE( R ) 1 CWE041499A 57 WIRE NET 1 CWD041128A 58 HANDLE 1 CWE161010 60 INSTALLATION INSTRUCTION 1 CWF615180 61 MANIFOLD TUBE ASS'Y(GAS) 1 CWT07K1522 62 TUBE ASS'Y (LIQUID 1) 1 CWT026316 63 TUBE ASS'Y (LIQUID 2) 1 CWT026872 64 CONTROL BOARD COVER 1 CWH131364 65 CLIP FOR SENSOR HOLDER 3 CWH711010 66 BAG 1 CWG861154 67 BASE BOARD-COMPLETE 1 CWG62C1081 68 SHOCK ABSORBER (RIGHT) 1 CWG712879
42
REF. NO. DESCRIPTION & NAME QTY. CU-2S18NBU-1 REMARK
69 SHOCK ABSORBER (LEFT) 1 CWG712880 70 C.C.CASE 1 CWG565609 76 TERMINAL COVER 1 CWH171035 77 NUT - TERMINAL COVER 2 CWH7080300J
(Note)
All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
Printed in Malaysia
SB1111-0
43
Loading...