Panasonic CS-MKE18NKU, CU-5E36QBU Installation Manual

9. Installation Information
9.1 Check Points
16
10. Installation Instruction
10.1 Select The Best Location
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
Refrigerant piping size
Outdoor Unit CU-5E36***
Liquid - side ø1/4" (ø6.35 mm) thickness 1/32" (t0.8 mm)
Gas - side
* In case of indoor is CS-E24***, then ø1/2"
(ø12.7 mm) thickness 1/32" (t0.8 mm) gas-pipe size must be used together with CZ-MA2P (pipe size expander)
Min. total piping length for additional gas 147.6 ft (45 m)
If total piping length of all indoor units exceeds the
minimum length listed above, additionally charge with 0.2 oz (20g) of refrigerant (R410A) for each additional feet (meter) of piping.
Outdoor Unit CU-5E36***
Allowable piping length of each indoor unit (min. ~ max.) 9.8 ft ~ 82.0 ft (3 m ~ 25 m)
Allowable total piping length of all indoor unit 262.4 ft (80 m) or less
Height difference between indoor and outdoor unit
Height difference between indoor unit
ø3/8" (ø9.52 mm) thickness 1/32" (t0.8 mm)
*(ø1/2" (ø12.7 mm) thickness 1/32" (t0.8 mm))
Outdoor Unit CU-5E36***
Outdoor unit located on upper side
Outdoor unit located otherwise
Outdoor unit located on upper side
Outdoor unit located otherwise
Allowable piping length
49.2 ft (15 m) or less
24.6 ft (7.5 m) or less
24.6 ft (7.5 m) or less
49.2 ft (15 m) or less