Features and Applications ..............................................................................................................................4
Part Number Cross Reference ........................................................................................................................6
Parts and Descriptions ....................................................................................................................................7
INST ALLATION AND WIRING .............................................................................................................................17
Important Wiring Considerations .................................................................................................................17
Digital Room Sensor ...................................................................................................................................19
Wall Mounted Space CO
Duct Mounted CO2 Sensor ..........................................................................................................................20
Space Temperature Sensor ........................................................................................................................21
Remote SAT Reset Signal ..........................................................................................................................21
Supply Air & Return Air Temperature Sensor ..............................................................................................22
Outdoor Air Temperature Sensor ................................................................................................................23
Modulating Chilled Water Valve ..................................................................................................................36
Return Air Bypass .......................................................................................................................................37
12-Relay Expansion Module Wiring and Jumper Settings .........................................................................38
Airfl ow Monitoring Station Installation and Wiring ....................................................................................39
RNE 55 - 105 Ton Unit Two Compressors Wiring ........................................................................................40
Full Digital Module ......................................................................................................................................40
Water Source Heat Pump X-2 Module ........................................................................................................41
Two Condenser Head Pressure Module II ..................................................................................................42
WattMaster Controls Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101
E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
WattMaster Form: AA-RNE-TGD-01H
Copyright March 2015 WattMaster Controls, Inc.
www.aaon.com
AAON Manual Part Number: V20490
AAON® is a registered trademark of AAON, Inc., Tulsa, OK.
EBTRON® is a registered trademark of Ebtron, Inc., Loris, SC.
Neither WattMaster Controls, Inc. nor AAON®
assumes any responsibility for errors or omissions in this document.
This document is subject to change without notice.
TABLE OF CONTENTS
RNE 120 - 140 Ton Unit Four Compressors Wiring .....................................................................................43
Full Digital Module ......................................................................................................................................43
Water Source Heat Pump X-2 Module ........................................................................................................44
Two Condenser Head Pressure Module II ..................................................................................................46
START UP AND COMMISSIONING ....................................................................................................................48
Addressing & Powering Up ...........................................................................................................................48
Programming the Controller .........................................................................................................................49
INPUTS AND OUTPUTS .....................................................................................................................................50
Supply Air Tempering .................................................................................................................................55
Morning Warm Up .......................................................................................................................................60
Head Pressure Control ...............................................................................................................................61
Remote Control of HVAC Mode ..................................................................................................................61
Supply Air Temperature Setpoint Reset ......................................................................................................61
Air Flow Monitoring/Control .........................................................................................................................62
Supply Fan Control .....................................................................................................................................62
Duct Static Pressure Control .......................................................................................................................62
Duct Static Pressure Control for Filter Loading ...........................................................................................63
Building Pressure Control ...........................................................................................................................63
Single Zone VAV Mode ...............................................................................................................................64
Outdoor Air Lockouts ..................................................................................................................................65
Supply Air Cutoffs .......................................................................................................................................65
Force Modes or Overrides ..........................................................................................................................69
VAV Terminal Unit Controller Compatibility .................................................................................................69
VAV/Zone System .......................................................................................................................................69
System Confi gurations ..................................................................................................................................77
The RNE Modular Controller (OE332-23E-RNE-A) is designed with 7
analog inputs, 2 analog outputs, and 5 relay outputs. Each RNE Controller’s input and output capabilities can be expanded with the VCM-X
Expansion Module (OE333-23-EM), the 12 Relay Expansion Module
(OE358-23-12R), and the 4 Binary Input Expansion Module (OE35601-BI) by means of a modular cable.
The RNE Controller also allows various E-BUS modules to connect
directly to it. These would include the Full Digital Module, the Two
Condenser Head Pressure Module, and the Water Source Heat Pump
Modules.
Each RNE Controller can be confi gured for control of VAV Units (with
or without VAV/Zone Controllers), Constant Volume Units, and MakeUp Air Units. Features include the following:
• Up to a Combined Total of 20 Stages of Heating & Cooling
• Modulating Cooling Outputs (VFD Compressor or Chilled
Water Valve Control)
• Modulating Heating Output ( Hot Water Valve,
Steam Valve, SCR Electric Heat Control)
• Full Integration with the AAON
Natural Gas Controller
• Full Integration with the AAON
Hot Gas Reheat Controller
®
MODGAS-X Modulating
®
MHGRV-X Modulating
• Confi gurable for Heat Pump Applications
• Advanced Dehumidifi cation Capabilities
• Air Flow Monitoring of Outdoor Air, Supply Air,
and Return Air Streams
• Air Flow Control of Outdoor Air Damper
• Single Zone VAV Control
• Primary/Secondary Heating Control
• Adaptive Supply Air Reset
• Selectable Control Sensor
• Fan Proving Interlock
• Dirty Filter Alarm
• Emergency Shutdown Input (Smoke Detector/Firestat or
other Shutdown Conditions)
• Drybulb/Wetbulb Control of Economizer Operation
• Building Pressure Control
• Remote Override Capabilities
• IAQ Economizer Reset
•Title 24 Economizer Certifi ed
• 7-Day, 2-Event-per-Day Scheduling
• 14 Holiday Event Scheduling
• Optimal Start Scheduling
• Trend Logging Capability
• Static Pressure Control for Filter Loading Applications
•Accepts Remote HVAC Mode Selection Via Contact
Closure On VCM-X Expansion Module
• Confi gurable for AAON
®
PAC and DPAC Applications
• Heat Wheel - On/Off Control
• Confi gurable for R22 and R410-A refrigerant
• Head Pressure Control
• Full Digital Control
• Water Source Heat Pump Monitoring
Most common HVAC unit control applications can be confi gured using
only the RNE Controller. If the application requires more inputs and/
or outputs, optional expansion modules are available to provide for additional analog, binary, or digital inputs and outputs as required.
The available expansion module confi gurations allow for 4 or 8 addition-
al binary inputs, 4 additional analog inputs, 5 additional analog outputs,
and up to 16 additional binary (relay) outputs. The various expansion
modules plug into the RNE Controller by means of a modular cable.
4
RNE Modular Controller Field Technical Guide
OVERVIEW
Features and Applications
E-BUS Module Applications
The RNE Controller will interface with the Two Condenser Head
Pressure Module (OE370-23-HP2C2-A), the Full Digital Module
(OE370-23-FD-A), and the W ater Source Heat Pump Modules (OE33423-WPM-A, OE334-23-WPM-A20, OE334-23-WPM-A25, OE33423-WPM-A40, and OE334-23-WPM-22-A).
These E-BUS Modules allow independent control of multiple VFD
compressors, control of the condenser fan(s) or valve(s), and monitoring
functions for Water Source Heat Pump Units. See pages 40-47 of this
manual for detailed wiring and application details.
RNE Controller Applications
Variable Air Volume Unit
The RNE Controller can be confi gured to control a VFD Supply Fan
for Duct Static Pressure control. If the unit is not equipped with a VFD,
but Duct Static Pressure control is needed, a modulating Zoning Bypass
Damper can be controlled by the RNE Controller.
VAV units are typically designed for occupied Cooling with Morning
Warm-up Heating. This option is available with the RNE Controller.
The RNE Controller can also be used for a Zoning System that needs
Duct Static Pressure control and Occupied Cooling and Heating. The
RNE Controller also has the ability to be confi gured for Duct Static
Pressure Control by controlling the Supply Fan VFD for the purpose
of maintaining proper Duct Static Pressure in response to varying fi lter
loading conditions.
The RNE Controller allows Dehumidifi cation Priority on a VAV unit.
This could be useful on a building with a very low internal sensible
load, but which has a high internal and/or external latent load. During
VAV Dehumidifi cation, the RNE Controller activates Cooling based on
the Evaporator Coil Temperature and activates AAON® Modulating Hot
Gas Reheat to warm the Supply Air Temperature to the Active Supply
Air Temperature Setpoint.
Constant Air Volume Unit
The RNE Controller can be confi gured to activate a Constant Volume
Supply Fan. In most cases, this is a very basic unit with Space T emperature control. The RNE Controller can be used for kitchen, restaurant, or
lab environments that are 100% Outdoor Air part of the time and Return
Air part of the time. The Hood On input allows the RNE Controller to
know when to switch to 100% Outdoor Air control based on an exhaust
hood activating. The RNE Controller requires Outdoor and Indoor Air
Temperature Sensors to accomplish this application.
Make-Up Air Unit
The RNE Controller can be confi gured for 100% Outdoor Air control
for Make-Up Air. All HVAC Modes are determined from the Outdoor
Air Sensors. The Outdoor Air Volume must always be at least 50% or
higher to be confi gured for Outdoor Air control.
AAON® PAC (Precision Air Control)
This control scheme can only be used on Constant Volume HVAC units
that are equipped with a Return Air Bypass Damper and that use a Space
Temperature Sensor as the Controlling Sensor.
AAON® P AC Control provides improved moisture removal capabilities
while utilizing internal space loads for reheat by redirecting the Return
Air path from the upstream side of the DX Evaporator Coil to the downstream side of the coil.
For AAON® P AC confi gured units, the Return Air Bypass Damper is only
used during the Dehumidifi cation Mode. When the RNE Controller is in
Dehumidifi cation Mode, the Return Air Bypass Damper will modulate
open as the Space T emperature falls below the Cooling Setpoint. Modulation of the Return Air Bypass Damper is controlled using a proportional
range from 0% (when the Space Temperature is equal to the Cooling
Setpoint) up to 100% (when the Space T emperature falls to the halfway
point between the Cooling and Heating Setpoints). A separate Return Air
Damper Actuator will modulate the Return Air Damper slightly further
towards its closed position as the Return Air Bypass Damper opens. This
is to ensure that enough Return Air is bypassed around the Evaporator
Coil through the Return Air Bypass Damper to raise its temperature. The
rate which the Return Air Damper closes while the Return Air Bypass
Damper is open is user-adjustable.
AAON® DPAC (Digital Precision Air Control)
This control scheme can only be used on Constant Volume HVAC
units that are equipped with a Return Air Bypass Damper and VFD
Compressor(s). AAON® DPAC also uses a Space Temperature Sensor
as the Controlling Sensor.
The AAON® DP AC control scheme provides improved moisture removal
capabilities over the AAON® P AC control scheme and provides for tighter
temperature control by combining a VFD Compressor with the Return
Air Bypass Damper. See the Cooling Mode section starting on page 53
for detailed VFD Compressor operation. Refer to AAON® P AC Control
previously described for detailed Return Air Bypass Damper operation.
The VFD Compressor is used during both Cooling and Dehumidifi ca-
tion Modes. The Return Air Bypass Damper is used only during the
Dehumidifi cation Mode.
Standard Room Sensor - W/ Override & Slide AdjustOE213P94320
Standard Room Sensor - W/ Slide AdjustOE212P94100
Static Pressure Pickup TubeOE290S18780
Suction Pressure TransducerOE275-01N/A
System Manager TS II - Operator InterfaceOE392-10N/A
USB-Link 2 KitOE366R71870
ORION
PART NUMBER
AAON TULSA
PART NUMBER
6
RNE Modular Controller Field Technical Guide
OVERVIEW
Parts and Descriptions
PART NO.PART DESCRIPTIONILLUSTRATION
OE332-23E-RNE-A RNE Controller
The RNE Controller provides 7 analog inputs, 2 analog outputs, and 5
relays. It presently allows for the addition of the VCM-X Expansion Module, the 12 Relay Expansion Module, and hte 4 Binary Input Expansion
Module described below.
NOTE: Set-up, programming, and monitoring of the RNE Controller
requires one of the following communication interfaces—Prism 2 FrontEnd Software used with a personal computer, System Manager Touch
Screen II, or Modular Service Tool.
OE333-23-EM VCM-X Expansion Module
Includes: VCM-X Expansion Module mounted in plastic enclosure and
10 ft. I2C cable. The VCM-X Expansion Module adds VAV applications,
building pressure control, head pressure control, water source heat
pump monitoring, and other functions. It provides 4 additional analog
inputs, 2 binary inputs, 5 additional relays, and 3 analog outputs. It
connects with a modular cable to the RNE Controller.
OE358-23-12R VCM-X 12 Relay Expansion Module
Includes: 12 Relay Expansion Module mounted in plastic enclosure
and 10 ft. I2C cable. The VCM-X 12 Relay Expansion Module adds 12
confi gurable relays to the RNE Control System. It connects to the RNE
Controller using the included I2C cable.
POLARITY
WARNING
OBSERVE
POWER
24VAC
GND
EXP1
EXP2
RLY1
RLY2
RLY3
RLY4
RLYCOM
MADE IN USA
24 VAC POWER ONLY
WARNING!POLARITYMUST BEOBSERVED OR THE BOARDWILLBE DAMAGED
VCM-X Expansion Module
Orion No.:OE333-23-EM
PR OUT
GND
OE333-23-EM-AVCM-X EXPANSION MODULE
PR OUTGND
+V
SIG
GND
+VSIGGND
RELAY1 =RELAY3 =
RELAY2 =RELAY4 =
RELAY1 =RELAY3 =
ITIS SUGGESTED
THATYOU WRITETHE
DESCRIPTION OF
RELAY2 =RELAY4 =
THE RELAYOUTPUTS
YOUARE USING IN
THE BOXES
ITIS SUGGESTED
PROVIDEDABOVE
THATYOU WRITETHE
WITHAPERMANENT
DESCRIPTION OF
MARKER (SHARPIE®)
THE RELAYOUTPUTSYOUARE USING INTHE BOXESPROVIDEDABOVEWITHAPERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
JUMPER SETTINGS
MUSTBE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGSMUSTBE SETAS
SHOWN FOR
ANALOG INPUT
PROPER
JUMPER
OPERATION
SETTINGS
ANALOG INPUT
AI1
JUMPERSETTINGS
AI1
AI2
AI2
AI3
AI3
AI4
AI4
24 VAC POWER ONLY
WARNING!POLARITYMUST BE
OBSERVED OR THE BOARD
WILLBE DAMAGED
24 VAC POWER ONLY
WARNING!POLARITYMUST BE
OBSERVED OR THE BOARD
WILLBE DAMAGED
OE358-23-12R 12 RELAYEXPANSION MODULE
RLY1 =RLY7 =
RLY2 =RLY8 =
RLY3 =RLY9 =
RLY4 =RLY10 =
RLY5 =RLY11 =
RLY6 =RLY12 =
NOTE:
ITIS RECOMMENDEDTHAT YOU WRITE THE
DESCRIPTION OFTHE RELAYOUTPUTS YOU
ARE CONNECTINGTOTHE RELAY EXPANSION
MODULE INTHE BOXES PROVIDEDABOVE
USINGAPERMANENT MARKER (SHARPIE)
FOR FUTURE REFERENCE.
J1
EXP1
EXP2
I2C
EXPANSION
www.aaon.com
TO VCM-X INPUT
TERMINALSAI5 & GND
TO VCM-X INPUTTERMINALSAI5 & GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITALCOMPRESSOR
SUCTION PRESSURETRANSDUCER CONNECTIONFOR HVAC UNITS WITHOUTDIGITALCOMPRESSOR
BI1= EMERGENCYSHUTDOWN - N.C. INPUT
= DIRTYFILTER - N.O. INPUT
BI2
= PROOF OF FLOW - N.O. INPUT
BI3
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI1= HOOD ON - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
BI5
BI2
= DIRTYFILTER - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
BI6
BI3
= PROOF OF FLOW - N.O. INPUT
= HOOD ON - N.O. INPUT
BI7
BI4
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
= REMOTE FORCED HEATING - N.O. INPUT
BI5
= REMOTE FORCED COOLING - N.O. INPUT
BI6
NOTE:
= SMOKE DETECTOR - N.C. INPUT
BI7
ALLBINARYINPUTS MUST BE 24 VAC ONLY.
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
NOTE:
AO1=BUILDING PRESSURE CONTROL VFD OR
ALLBINARYINPUTS MUSTBE 24 VAC ONLY.
DAMPERACTUATOR (0-10 OR 2-10 VDC)
AO2
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
AO1=BUILDING PRESSURE CONTROLVFD OR
AO3
= MODULATING COOLING/DIGITALSCROLL
DAMPERACTUATOR (0-10 OR 2-10 VDC)
SIGNAL(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= MODULATING HEATING SIGNAL
AO2
THERM
AO4
= RETURNAIR DAMPERACTUATOR
(0-10 VDC OR 2-10 VDC)
4-20mA
(0-10 VDC)
0-10V
= MODULATING COOLING/DIGITALSCROLL
AO3
AO5
= RETURNAIR BYPASS DAMPERACTUATOR
0-5V
SIGNAL(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
THERM
= RETURNAIR DAMPERACTUATOR
AO4
THERM
GND
= GROUND FORANALOG OUTPUTS
4-20mA
4-20mA
(0-10 VDC)
0-10V
GND
= GROUND FORANALOG OUTPUTS
0-10V
= RETURNAIR BYPASS DAMPERACTUATOR
AO5
0-5V
0-5V
(0-10 VDC)
THERM
THERM
= GROUND FORANALOG OUTPUTS
GND
AI1= OUTDOORAIR RH SENSOR (0-5 VDC)
4-20mA
4-20mA
= GROUND FORANALOG OUTPUTS
GND
0-10V
AI2
= INDOORAIR RH SENSOR (0-5 VDC)
0-10V
0-5V
0-5V
A3
= ECONOMIZER FEEDBACK
I
THERM
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
THERM
AI1= OUTDOORAIR RH SENSOR (0-5 VDC)
4-20mA
4-20mA
GND
= GROUND FORANALOG INPUTS
AI2
= INDOORAIR RH SENSOR (0-5 VDC)
0-10V
0-10V
GND
= GROUND FORANALOG INPUTS
0-5V
AI3
= CO2 (0-10 VDC)
0-5V
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
THERM4-20mA
GND
= GROUND FORANALOG INPUTS
0-10V
= GROUND FORANALOG INPUTS
GND
I2C
0-5V
EXPANSION
I2C
EXPANSION
SETJUMPERAS
SHOWN WHEN
ONLY
THE 12 RELAY
EXPANSION MODULE
IS USED
EXP1
EXP2
WattMaster Label
#LB102034-01
www.orioncontrols.com
www.orioncontrols.com
WattMaster Label
#LB102034-01-A
Rev.: 1K
WattMaster Label
#LB102043
www.orioncontrols.com
®
J1
SETJUMPERAS
SHOWN WHEN BOTH
THE VCM EXPANSION
MODULEANDTHE
RELAYEXPANSION
MODULEARE USED
AAON No.:
R69190
RELAYCONTACT
RATING IS 1AMP
MAX @ 24 VAC
RELAYCONTACTRATING IS 1AMPMAX @ 24 VAC
RELAY1
RELAY2
RELAY
RELAY3
COMMON
RELAY4
RELAYCOMMON
PAGE
NO.
Page
18
OBSERVE
WARNING
POLARITY
I2C
EXPANSION
RELAY1
RELAY2
RELAY3
RELAY4
VCM
I2C
EXPANSION
RELAY
I2C
EXPANSION BOARD
EXPANSION
YS102228 REV 1
RLY5
RLY6
RLY7
RLY8
RLYCOM
RLY9
RLY10
RLY11
RLY12
RLYCOM
Pages
26-28
Page
38
OE356-01-BIVCM-X 4 Binary Input Expansion Module
Includes: 4 Binary Input Expansion Module mounted in Snap Track and
10 ft. I2C cable. Use the 4 Binary Input Expansion Module if your HVAC
unit only requires a Smoke Detector/Firestat, Dirty Filter, Proof of Flow,
or Remote Forced Occupied Inputs or all of these 4 inputs and you don’t
need any of the other inputs or outputs provided by the OE333-23-EM
VCM-X Expansion Module. The module connects to the RNE Controller
using the included I2C cable.
OE334-23-WSHP-X2 Water Source Heat Pump X2 Module
Includes: Water Source Heat Pump X2 Module in a plastic enclosure
with LCD display and E-BUS Modular cable. Provides monitoring and
compressor control for AAON Tulsa Water Source Heat Pump Units.
Used with the RNE Controller.
OE370-23-FD-A Full Digital Module
Includes: Full Digital Module in a plastic enclosure and E-BUS Modular
cable.Used with the RNE Controller. For AAON Tulsa units with multiple
Digital Scroll Compressors and that are not Water Source Heat Pump
Units.
RNE Modular Controller Field Technical Guide
GND
24VAC
Page
VCM BIN EXPBOARD
PWR
YS102364 REV1
COM
BI3
BI4
BI1
BI2
Y102374 REV 0S
WATTMASTER CONTROLS
MADE IN USA
29
Pages
41,44
R12
R53
R54
R11
4751
4751
4751
4751
TB3
+5V
1003
SIG 1
1002
10uF
GND
+5V
1003
www.orioncontrols.com
SIG 2
1002
10uF
GND
C2
+5V
1003
SIG 3
1002
10uF
GND
+5V
1003
SIG 4
1002
10uF
GND
4
R7
R9
300
BIN 1
4
R13
R14
BIN 2
300
1002
R23
COM
1002
R24
1002
R25
1002
R26
ADDRESS
1
OFF
2
4
8
SW1
PWR
D3
R1
D4
R2
D12
R3
D13
R4
Rc
RELAYS
SERIAL#
ANALOG
AO1
AO2
GND
PWM1-
PWM1+
R34 R50
PWM2-
PWM2+
SW2
1002
OFF
1002
1002
1002
R30
ALARM
R29
STAT
R28
COMM
C20
.01uF
Pages
40,43
OPTIONS
7
OVERVIEW
Parts and Descriptions
PART NO.PART DESCRIPTIONILLUSTRATION
OE370-23-HP2C2-A Two Condenser Head Pressure Module
Includes: Two Condenser Head Pressure Module in a plastic enclosure
and E-BUS Modular Cable. This module is used on units with 2 physically separate condenser sections and is able to monitor up to 4 individual
head pressure transducers (2 per section) to control the Condenser
Fans or Water Valves based on the highest of the 2 readings for each
section. It is also capable of monitoring a Heating Enable control signal
(Heat Pump Mode) and forces the Condenser Signal to 100% while in
this mode. This module can be used as a communicating module with
the RNE Controller.
OE210
OE211
OE212
OE213
Standard Room Sensor–Plain, w/Override,
w/Override & Slide Adjust & w/Slide Adjust Only
Includes: Standard Room Sensor - Plain, with Override, with Override
and Slide Adjust & with Slide Adjust only. For wall mounting. Use with
RNE Controller only. Connects to controller via fi eld fabricated wiring.
+5V
1003
SIG 1
1002
10uF
GND
+5V
1003
SIG 2
1002
10uF
GND
C2
+5V
1003
SIG 3
1002
10uF
GND
+5V
1003
SIG 4
1002
10uF
GND
R7
R9
BIN 1
R13
R14
BIN 2
R23
COM
R24
R25
R26
ADDRESS
1
OFF
2
4
8
SW1
PWR
OE217-00 Digital Room Sensor - Temp. Only
LCD Display and keypad allow for setpoint adjustment, override, and
display of certain status and setpoints. The OE217-00 is used with the
RNE Controller for room air temperature sensing applications. Uses I2C
cable.
OE217-01 Digital Room Sensor - Temp and Humidity
LCD Display and keypad allow for setpoint adjustment, override, and
display of certain status and setpoints. The OE217-01 is used with the
RNE Controller for room air temperature and humidity sensing applications. Uses Uses I2C cable.
PAGE
NO.
R53
R12
R11
R54
4751
4751
4751
4751
TB3
D3
R1
D4
R2
D12
R3
D13
R4
Rc
RELAYS
SERIAL#
ANALOG
AO1
AO2
GND
PWM1-
4
300
4
300
1002
1002
1002
1002
OVERRIDE ALARM
Display
OVERRIDE ALARM
Display
PWM1+
R34R50
PWM2-
PWM2+
SW2
1002
OFF
1002
1002
1002
R30
ALARM
R29
STAT
R28
COMM
C20
.01uF
TMP
GND
AUX
OUT
Override
Override
Pages
42,46
OPTIONS
Page
21
Page
19
Page
19
OE256-01 CO2 Wall-Mounted Sensor
Used with the RNE for CO2 sensing applications where wall mounting in
the space is desired. Connects to the RNE Controller with an I2C cable
of required length. Cable sold separately.
OE256-02 CO2 Duct Sensor with Pickup Tube
Used with the RNE Controller for duct mounted CO2 sensing applications. Connects to the RNE Controller with an I
length. Includes: Duct Mounted CO
Airfl ow Pickup Tube and 10 ft. I2C Cable.
Digital Sensor Cable Assembly
Includes: Digital Sensor Cable Assembly. Cable assembly has male
RJ-45 modular connectors on both ends. For use with the Digital Room
Temperature Sensor, Digital Room & Temperature Sensor, Wall Mounted
CO2 Sensor & Duct Mounted CO2 Sensor. These cables are used
with the OE332-23E-RNE – RNE Controller and the OE742-31-VAVZ,
OE742-32-VAVZ, OE744-31-VAVZ, and OE744-32-VAVZ – VAV/Zone
Controller Actuator Packages. The TSDRSC Cables are available in 5,
Sensor, Integral Aspiration Box,
2
10, 25, 40, 80, 120 & 160 feet lengths. The maximum length of cable
allowed is 160 feet for a CO2 Sensor and 160 Feet for a Digital Room
Sensor. The total combined length of cable allowed when both a CO2
Sensor and Digital Room Sensor is used is 160 feet.
MS000029 Cable Coupler for TSDRSC Cables
Includes: Sensor Cable Coupler. Used to connect TSDRSC cables
together when lengths inbetween available cable sizes are required.
Female RJ-45 to Female RJ-45. Maximum 1 Cable Coupler per cable
run.
2
C cable of required
Page
19
Page
20
Page
19
Page
19
8
RNE Modular Controller Field Technical Guide
OVERVIEW
Parts and Descriptions
PART NO.PART DESCRIPTIONILLUSTRATIONPAGE NO.
OE230
OE231
Duct Temperature Sensor - 6” Probe
Duct Temperature Sensor - 12" Probe
OE230 = 6″ probe length. OE231 = 12″ probe length. Used for return or
supply air temperature sensing applications. Includes: 10k Ohm Duct
Temperature Sensor, 2 wire only.
OE250 Outdoor Air Temperature Sensor
Used for temperature sensing applications. Includes: 10k Ohm Outside
Air Temperature Sensor, 2 wire, mounted in a weatherproof handy box
only.
OE258-01 Building Static Pressure Sensor
Used for Building Pressure Sensing. Includes: -0.25 to +0.25″ W.C., 0-5
VDC, 24 VAC/VDC supply power Building Pressure Sensor only.
Includes: 0-5 VDC, Room Mounted Relative Humidity Transmitter only.
Used for room air humidity sensing applications.
OE265-13 Outdoor Air Temperature & Humidity Sensor
Includes: 0-5 VDC, Outside Air Relative Humidity Transmitter mounted
in a weatherproof, round handy box only. Used for outside air humidity
sensing applications.
Includes: 0-5 VDC, Return Air Relative Humidity Transmitter mounted in a
weatherproof, round handy box only. Used for return air humidity sensing
applications.
OE271 Duct Static Pressure Sensor
Used for duct static pressure sensing applications. Includes: 0-5″ W.C.,
0-5 VDC, Static Pressure Sensor only.
OE275-01 Suction Pressure Transducer
Includes: Suction Line Pressure Transducer with modular cable. The cable
is supplied with a modular connector on one end and bare stripped wires
on the other end. The OE275-01 Suction Pressure Transducer is used to
monitor refrigerant suction line pressure of a DX cooling coil when a digital
compressor is used. The Suction Pressure Transducer is provided with a
¼″ SAE Flare connection for connection to the refrigerant suction line.
OE281-04 Bypass Damper Actuator
Includes: OE281-04 Modulating Damper Actuator. Used when a terminal
unit is to be used as a bypass damper for fi eld or factory controls mounted
by others. Accepts a 0-10 VDC signal.
Page 32
Page 18
Pages
40,41
43,44
Page 37
RNE Modular Controller Field Technical Guide
9
OVERVIEW
STATUS
Parts and Descriptions
PART NO:PART DESCRIPTIONILLUSTRATIONPAGE NO.
OE290 Static Pressure Pick-up Tube
Used with OE271 Static Pressure Sensor for static pressure sensing applications. Includes: Static Pressure Pick-up Tube with 1 ft. length of FRP tubing,
gasketed mounting bracket, and screws.
OE392-10 System Manager TS II Operator Interface
The System Manager TS II provides a direct, graphic-enhanced, menu-driven
link to enable the system operator to view the status and adjust the setpoints
of any controller on the RNE control system. The System Manager TS II is
equipped with a 4.3” 480 x 272 WQVGA RGB TFT LCD Touch Screen
Display. The System Manager TS is furnished with hardware for fl ush
mounting into hollow drywall or surface mounting on concrete brick or
plaster surfaces. Includes: System Manager TS with 12 ft. long pigtail cable
assembly.
OE391-12 Modular Service Tool SD
Includes: Modular Service Tool SD, power supply, communication cables,
adapter plug, and (4) AA batteries. Used to program and monitor all Orion
controllers.
OE392-12 Modular System Manager SD
Includes: Modular System Manager SD with 4 Gigabyte SD card and 12 ft.
long pigtail cable assembly. Used to program and monitor all Orion
controllers. Designed for hollow core wall mounting. When System Manager
is to be mounted on a solid wall (concrete), you will also need to order the
solid wall mounting bracket below. Modular System Manager and
communication cables.
Mode
Selecti on
13
2
654
9
708
-
Page 18
See the
System
Manager
Touch
Screen II
Technical
Guide
See the RNE
Controller
Operator
Interfaces
SD
Technical
Guide
See the RNE
Controller
Operator
Interfaces
SD
Technical
Guide
EB101505 Solid Wall Mounting Bracket for Modular System
Manager SD
Includes: 22 gauge galvanized sheet metal mounting bracket with mounting
holes and wire routing opening. Dimensions are 9.25″W x 8.00″H x 0.50″DP.
The Wall Mounting Bracket provides wiring clearance between the System
Manager and the wall mounting surface when the System Manager is to be
mounted on a concrete or other solid wall surface. Not for use with System
Manager TS.
OE361-13 CommLink 5 Communications Interface
The CommLink 5 connects to your control system using a USB computer
connection to provide direct on-site communications with the control system
from a computer with the Prism 2 software installed. For remote communications, see OE415-02 IP Module Kit.
Includes: CommLink 5, 6 ft. long USB cable, and 120/24 VAC power supply.
Required on all networked systems or if direct computer or remote computer
connection is required. Connects to your computer’s USB 1.1 or 2.1 port.
Prism 2 computer front-end software must be installed on the direct connected or remote connected computer in order to communicate with your system.
10
RNE Modular Controller Field Technical Guide
N/A
See the
CommLink
5 Technical
Guide
OVERVIEW
Parts and Descriptions
PART NO.PART DESCRIPTIONILLUSTRATIONPAGE NO.
OE415-02 IP Module Kit - Internet/LAN Connection
Used for Internet or Local Area Network communications with the control
system. Field installs by plugging into the CommLink IV circuit board and
provides an addressable Ethernet connection to the controls system from
any computer connected to your building’s LAN. It can also be confi gured to
allow access to the control system from the Internet through your LAN if your
Ethernet fi rewall is confi gured for this option.
Includes: IP Link module, 10 ft. long Ethernet cable, and installation instructions. Prism 2 computer front-end software must be installed on the remote
computer in order to dial-up and communicate with the controls system.
OE366 USB-Link 2 Kit
The USB-Link 2 is a pocket-sized communications interface used to connect
a laptop computer to your controls system for programming and monitoring
purposes, utilizing a modular cable to allow connection to the service port
connector on the controllers and a USB cable to connect to a laptop computer.
Includes: USB-Link 2 for multiple or single loop systems, USB cable, modular
connection cable, two mini-DIN to terminal adapters, and Prism 2 software.
OE364-22 MiniLink Polling Device
Control enclosure is for indoor use only. Used with all Orion controllers to
provide network communications, zone voting, alarming, and tenant logging
capabilities. A MiniLink Polling Device is required on each loop of a Networked system. Includes: MiniLink Polling Device mounted in the EE00007501 control enclosure. Control Enclosure cover is shown removed in picture.
See the IP
Module
Technical
Guide
See the
USB-Link 2
Technical
Guide
U1
CX7
RV1
CX3
VREF
U3
U4
CX2
R4
LED 1
LED 2
EPROM
POWER
C8
C7
R25
R26
V1
1
AIN
R27
THERM
4-20mA
U12
0-10V
R31
OFF=0-5V
D4
+5V
GND
24VAC
C11
D5
TB2
TB1
U7
P1
CX1
C4
C1
R3
YS101818P552
X1
CX4
PROCESSORPBOARD
C1
C2
CX5
U5
RAM
CX2
AIN2
THERM
4-20mA
0-10V
GND
AIN 2
AIN 1
X1
CX6
C3
U6
PHILIPS
U10
YS101900PMINILINK
D1
POLLING
U1
DEVICE
1
REV. 1
R1
U6
CX1
C3
U2
CX6
RN2
U11
R2
WDOG
R24
C10
C9
RN3
LD4
PROC.
LOOP
NETWORK
DRIVER
DRIVER
DRIVER
X2
CX15
CX14
CX13
P3
R28
U14
U15
U13
R29
R30
LD6
LD5
NETWORK
LOCAL LOOP
LOOP
2
4
8
1
32
16
P5
P4
SHLD
T
R
SHLD
T
R
ADD
OFF
TB3
TB4
SW1
See the
CommLink
IV Technical
Guide
OE365-15EBA
E-BUS Adapter Board
The E-BUS Adapter Board is used for connecting the EBTRON®, GreenTrolTM
or Paragon Airfl ow Measurement Digital Transmitter to the VCB-X Control
System. The E-BUS Adapter Board connects to the VCB-X Controller with an
EBC E-BUS cable. Cable supplied separately.
OE508 Prism 2 Front-End Computer Software
Prism 2 provides standard, easy to understand status screens for each
type of RNE equipment installed. Prism software has provisions for custom
screens which allow fl oor plans, equipment photos, or user-defi ned summary
screens to be implemented to meet their own individual needs. All controlling
setpoints, trend logs, and alarm conditions are accessed in the Prism environment. Prism can be confi gured for direct on-site installation, remote modem
connection, or TCP/IP Internet connection to several installations.
OE437-03 Communication Surge Protector Kit
Used to isolate power surges to the communications wiring caused by
lightning strikes for communications wiring loops that are routed outdoors or
between buildings. One kit is required at each point where the communications wiring leaves or enters a building.
Includes: Communication Bus Surge Protector, Base Module, and Mounting/
Wiring Instructions.
See
Page 39.
See the
Prism 2
Technical
Guide
N/A
RNE Modular Controller Field Technical Guide
11
OVERVIEW
Parts and Descriptions
PART NO.PART DESCRIPTIONILLUSTRATIONPAGE NO.
OE377-0000042
OE377-0000041
OE332-23GPCX
MHGRV-X Controller
The MHGRV-X Controller controls a Modulating Hot Gas Reheat Valve to
maintain a desired Supply Air Temperature and Dehumidifi cation setpoint.
The MHGRV-X Controller connects to the RNE Controller via an I2C
cable. Available only from AAON®.
MODGAS-X Controller
The MODGAS-X Controller modulates up to (2) gas valves to maintain
a desired Discharge Air Temperature. It also controls the speed of the
induced draft fan to maintain proper combustion in the heat exchanger.
The MODGAS-X Controller connects to the RNE Controller via an I2C
cable. Available only from AAON®.
GPC-X Controller
The GPC-X Controller provides the fl exibility to control, schedule, and/or
monitor equipment such as unit heaters, exhaust fans, motorized louvers,
etc. The GPC-X has (6) confi gurable inputs which will accept signals from
thermistor temperature sensors, 4-20mA or 0-5 VDC transmitters, or dry
contact closures. An additional modular input is provided for connection
of an OE271 Static Pressure Sensor. The GPC-X has (5) relay outputs for
on/off control and (2) analog outputs. The GPC-X also has (5) separate
2-events-per-day schedules, each with its own optimal start functions built
in. In addition, the GPC-X provides Lead/Lag start capabilities. Use the
GPC-X to provide additional schedules for your controllers.
TB3
CLG OVR
GND
HTG OVR
RHTIN
SHLD
R
SAT
T
PJ1
R12
PU
D2
PJ1
2
I C IN
D1
R19
+24VAC
YS101826PREV 1
MODULATING
GAS BOARD
R
SHLD
T
D8
V4
24VAC
GND
R4
2
I C OUT
COMM
VR1
RV1
C3
D6
R11R1D5R3R3
R20
WDOG
U2
C12
CX6
U6
U1
D1
D1
C13
C2
GND
C4
P1
TB4
P1
RV1
SAT
+VDC
C1
VR1
R7
D1
P
R15
WDOG
POWER
CX6
U6
U1
C7
U5
C2
C4
P1
R13R5R6D4D3
R2
U2
R1
C3
CX1
1
PHILIPS
U5
CX5
C1
X1
YS101818P552
PROCESSORPBOARD
STATUS
RESET
LIMIT
O
F
F
1
RSTIN
AUX IN
GND
HEATEN
2
4
J01
8
16
C2
32
64
128
ADD
R8
D2
R9
R1R3R1
P
R2
U2
C3
CX1
R1
1
PHILIPS
PHILIPS
U5
CX5
C1
YS101818
552 PROCESSOR
BOARD
C1
R18
L1
C8
L2
V5
R31
D11
R38
I2C IN
TB2
R26
R26
C6
R25
POWER
TB3
FAN
V1
CW/HW
CB/HB
CG/HR
CR/HG
+VDC
GND
GND
AUX IN
RSTIN
CX2
DISCHARGE
SETPOINT
R4
K1
YS101894 REV 1
HOTGAS REHEAT
V2
COMP
R2
U1
AUX IN
SETUP
THERM
STEP
4-20MA
0-10V
C4
C2
R9R8R7
RAM
EPROM
U4
CX4
U3
CX3
TB1
O
F
F
1
AUX
COM
LO SPD
FAN
2
4
8
16
32
64
LO SPD
FAN
AUX
128
ADD
CX2
EPROM
RAM
SERIAL#
K2
V3
VALVE
R17
K3
AUX
V4
TB5
FAN
R23
K4
COMP
U5
VALVE
AUX
CX5
COM
RESETLIMIT
SW1
ADD
128
SETPOINT
STATUS
R39
1286416
POWER
R40
V1V3K3V2
K2
K1
FT
N/A
16
421
8
64
32
SW2
ADD
1
2
32
4
8
C15
N/A
SER. #:
U4
CX4
U3
GAS
CX3
VALVE
D9
VOUT
GND
C13
V5
TB4
See GPC-X
Technical
Guide
OE310-21-LP Lighting Controller
Adds lighting control capability to the RNE Control System. Lighting Controller provides up to (7) independent time schedules. Provisions for photocell or light sensor light level control are also provided. Lighting Controller
only provides Pilot Duty Relay Outputs. An external Lighting Contactor
must be provided by others. If a Light Sensor OE259 is to be used with
the Lighting Controller, it must also be ordered from WattMaster. Includes:
Lighting Controller with Backplate.
OE259 Light Sensor
Ambient Light Sensor
(Use with Lighting Controller for light sensing.)
24VDC power, 1m Ohm to 1.5k Ohm output signal. Supplied with weatherproof handy box for outdoor or indoor mounting. Light Sensor threads into
conduit fi tting. Includes: Light Sensor and weatherproof handy box.
Correct wiring of the RNE Modular Controller is the most important
factor in the overall success of the controller installation process. In
general, most RNE Controllers are factory installed and wired at the
AAON®factory . It is also possible to purchase these controllers through
your local AAON®/Orion representative for installation in the fi eld.
Some of the following information pertains to fi eld wiring and may not
apply to your installation since it was pre-wired at the factory. However ,
in the unlikely event that troubleshooting of the controller is required,
it is a good idea to be familiar with the system wiring, no matter if it
was factory or fi eld wired.
Controller Mounting
The RNE Controller is housed in a plastic enclosure. It is designed to be
mounted by using the 3 mounting holes in the enclosure base. The RNE
Controller needs to be installed in an environment which can maintain
a temperature range between -30°F and 150°F not to exceed 90% RH
levels (non-condensing). It is important to mount the controller in a
location that is free from extreme high or low temperatures, moisture,
dust, and dirt. Be careful not to damage the electronic components when
mounting the controller. See Table 1 for a list of the required operating
conditions for the RNE Controller and associated expansion modules.
Considerations
The RNE Controller and expansion modules must be connected to a
24 VAC power source of the proper size for the calculated VA load
requirements. All transformer sizing should be based on the VA rating
listed in Table 1.
Device
Control
OE332-23E-RNE
RNE Modular Controller
Voltage
24VAC8
VA Load
Temperature
-30°F to
150°F
(Non-
Humidity
Condensing)
90% RH
WARNING: When using a single transformer to power more
than one controller or expansion module, the correct polarity must
always be maintained between the boards. Failure to observe
correct polarity will result in damage to the RNE Controller and
expansion modules.
Please carefully read and apply the following information when wiring
the RNE Controller or the Expansion Modules. See Figure 6 on page
18 for the RNE Controller wiring diagram. See Figures 17 and 18 on
pages 26 and 27 for Expansion Module Wiring.
1. All wiring is to be in accordance with local and national
electrical codes and specifi cations.
2. Minimum wire size for 24 VAC wiring should be 18-gauge.
3. Minimum wire size for all sensors should be 24-gauge.
Some sensors require 2-conductor wire and some require
3-or 4-conductor wire.
4. Be sure that all wiring connections are properly inserted
and tightened into the terminal blocks. Do not allow wire
strands to stick out and touch adjoining terminals which
could potentially cause a short circuit.
5. When communication wiring is to be used to interconnect
RNE Controllers together or to connect to other
communication devices, all wiring must be plenum-rated,
minimum 18-gauge, 2-conductor, twisted pair with shield.
WattMaster can supply communication wire that meets this
specifi cation and is color coded for the network or localloop. Please consult your WattMaster distributor for
information. If desired, Belden #82760 or equivalent wire
may also be used.
6. Before applying power to the RNE Controller, be sure to
recheck all wiring connections and terminations
thoroughly.
OE333-23-EM
VCM-X Expansion Module
OE358-23-12R
12 Relay Expansion
Module
OE356-01-BI
4 Binary Expansion
Module
24VAC10
24VAC15
24VAC5
-30°F to
150°F
-30°F to
150°F
-30°F to
150°F
90% RH
90% RH
90% RH
Table 1: Voltage and Environment Requirements
RNE Modular Controller Field Technical Guide
17
INSTALLATION AND WIRING
RNE Controller Wiring
For Stand Alone Applications,
Connect To System Manager. For Network
Applications Connect To Next Controller And/Or
MiniLink PD On Local Loop.
Local Loop
RS-485
9600 Baud
All Comm Loop Wiring Is
T to T, R to R & SHLD to SHLD
Straight Thru
RNE Controller
Zone
Zone
Note:
All Relay Outputs Are Normally Open
And Rated For 24 VAC Power Only.
1 Amp Maximum Load.
R - 24VAC
G - Fan ON/OFF Only
AI1 SETAI2 SET AI3 SET
AI4 SETAI5 SETAI7 SET
See Individual
Component Wiring
Diagrams For Detailed
Wiring Of Analog Inputs
And Outputs
Jumpers
Splice If Required
OE271
Static Pressure
Transducer
Connect To Digital Room Sensor And/Or
Connect To
Expansion Module(s)
(When Used)
Digital CO Sensor
Relay Output Contacts
R2 Through R5 May Be UserConfigured For The Following:
Note: A Total Of 20 Relays Are Available By
Adding Relay Expansion Modules. All
Expansion Module Relay Outputs Are User
Configurable As Listed Above.
GND
24VAC
Size Transformer For Correct
Total Load.
RNE Controller = 8 VA
2
Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.
Line Voltage
Connect FRP Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere
Figure 6: OE332-23E-RNE – RNE Controller Wiring
18
RNE Modular Controller Field Technical Guide
INSTALLATION AND WIRING
Digital Room Sensor & Wall Mounted Space CO2 Sensor
Digital Room Sensor
The OE217-00 Digital Room Sensor is used to sense Space Temperature and the OE217-01 Digital Room Sensor is used to sense Space
Temperature and Space Humidity. The Sensor connects to the RNE
Controller with the TSDRSC modular cable. It can be daisy-chained
with the OE256-01 CO2 Sensor for applications requiring both a room
CO2 sensor and room temperature sensor. It should be mounted at approximately 5 Ft. above the fl oor on the wall in an area that does not have
drafts or is exposed to direct sunlight. See Figure 7 for wiring details.
Note: When Only The
Is Used, It
Connects Directly To The RNE
Controller Using AOf The
Appropriate Length.
Allowed Is 160 Feet. See For
Connection When The Space CO Sensor Is
Also Used.
Digital Room Sensor
TSDRSC Cable
The Maximum Length
Figure 8
2
OVERRIDEALARM
Display
Override
Wall Mounted Space CO2 Sensor
The OE256-01 Wall Mounted Space CO2 Sensor is used to monitor
CO2 levels in the space served by the HVAC unit. The CO2 Sensor connects to the RNE Controller with the TSDRSC modular cable. It can be
daisy-chained with the Digital Room Sensor (OE217) for applications
requiring both a room CO2 sensor and room temperature sensor. It should
be mounted at approximately 5 Ft. above the fl oor on the wall in an area
that does not have drafts or is exposed to direct sunlight. See Figure 8
for wiring details and installation notes. A Duct Mounted
can be used if desired instead of the Wall Mounted Space CO2 Sensor.
See Figure 9 on page 20 for Duct Mounted CO2 Sensor wiring details.
I1 SET
AI1
AI2 SET AI3 SET
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
4-20mA
AI2
0-10V
0-5V
THERM
4-20mA
AI3
0-10V
0-5V
THERM
EMERGENCY SHUTDOWN
4-20mA
AI4
0-10V
0-5V
THERM
4-20mA
AI5
0-10V
0-5V
THERM
4-20mA
AI7
0-10V
0-5V
ANALOG INPUT JUMPER SETTINGS
MUST BE SETAS SHOWN FOR
PROPER OPERATION
STATIC
WattMaster Label
#LB102033-01
PRESSURE
RNE Controller
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
I2C
EXPANSION
I2C DIGITAL
SENSOR
CO
2
Sensor
Digital Room Sensor
Figure 7: OE217-00/01 – Digital Room Sensor Wiring
CO Sensor
2
Note: When a Digital Room Sensor Is
Used In Combination With The
Ther Always
Sensor,CO Senso
Connects To The RNE Controller First
2
Using a TSDRSC Cable Of The
Length. The Digital Room Sensor Then
Connects To The CO Sensor With
AnotherCable.
TSDRSC
2
At Least 5 Feet Above Floor. See The
C Sensor Technical GuideO
2
Wiring Details.
CO
2
Required
Mount Sensor(s)
For Further
Digital Room Sensor
OVERRIDEALARM
Display
Override
I1 SET
AI1
AI2 SET AI3 SET
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
RNE Controller
TSDRSC Cable
4-20mA
AI2
0-10V
0-5V
THERM
4-20mA
AI3
0-10V
0-5V
THERM
EMERGENCY SHUTDOWN
4-20mA
AI4
0-10V
0-5V
THERM
4-20mA
AI5
0-10V
0-5V
THERM
4-20mA
AI7
0-10V
0-5V
ANALOG INPUTJUMPER SETTINGS
MUSTBE SET AS SHOWN FOR
PROPER OPERATION
STATIC
WattMaster Label
#LB102033-01
PRESSURE
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
I2C
EXPANSION
TSDRSC Cable
I2C DIGITAL
SENSOR
TSDRSC Cable
Figure 8: OE256-01 – Wall Mounted Space CO2 Sensor Wiring
RNE Modular Controller Field Technical Guide
19
OVERVIEW
Ducted Mounted CO2 Sensor
Zone
Zone
Duct Mounted CO2 Sensor
The OE256-02 CO2 Sensor is used for sensing the current CO2 level
in the HVAC unit’s return air stream. This is useful when you want an
average CO2 reading in the area served by the HVAC unit or when you
don’t want a wall mounted CO2 sensor due to sensor tampering concerns
in the space.
Note:
1.) The CO Sensor Always Connects To The RNE Controller
Using A TSDRSC Cable Of The Required Length. If Also
Using A Digital Room Sensor, Connect The Digital Room
Sensor To The C Sensor Using Another TSDRSC Cable
Of The Required Length. The Total Length Of Cable For All
Sensor Cables Combined Cannot Exceed 160 Feet.
Wall Mounted
Digital Room Sensor
OVERRIDEALARM
Display
Override
2
O
2
TSDRSC Cable
Duct Mounted CO Sensor
2
The OE256-02 Duct Mounted Return Air CO
the OE256-01 CO2 Sensor and the WattMaster Aspiration Box Assembly .
The Duct Mounted Return Air CO
the return air duct of the HVAC unit and uses its integral aspiration box
to sample the CO
tion information in Figure 9 below for wiring and installation details.
level in the duct. See the dimensional and installa-
2
Sensor is designed to be mounted in
2
Sensor is comprised of
2
RNE Controller
RS-485 COMMUNICATION LOOP. WIRE“R”TO“R”,“T”TO“T”“SHLD”TO“SHLD”
RS-485 COMMUNICATION LOOP. WIRE“R”TO“R”,“T”TO“T”“SHLD”TO“SHLD”
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
OE332-23-VCMX-AVCM-X CONTROLLER
AI1= SPC (SPACETEMPERATURE SENSOR)
AI1= SPC (SPACETEMPERATURE SENSOR)
= SAT(SUPPLYAIRTEMPERATURE SENSOR)
AI2
AI2
= SAT(SUPPLYAIRTEMPERATURE SENSOR)
= RAT(RETURNAIRTEMPERATURE SENSOR)
AI3
AI3
= RAT(RETURNAIRTEMPERATURE SENSOR)
= OAT(OUTDOORAIRTEMPERATURE SENSOR)
AI4
AI4
= OAT(OUTDOORAIRTEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
AI5
AI5
= SUCTION PRESSURE SENSOR
= SPACETEMPERATURE SENSOR SLIDEADJUST
AI7
AI7
= SPACETEMPERATURE SENSOR SLIDEADJUST
OR VOLTAGE RESETSOURCE
OR VOLTAGE RESETSOURCE
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
E-BUS
CONNECTOR
ANALOG INPUT
ANALOG INPUT
JUMPER
JUMPER
SETTINGS
SETTINGS
THERM
LEDNAMESTATUS1STATUS2
THERM
4-20mA
4-20mA
AI1
AI1
0-10V
NORMALOPERATION01
0-10V
0-5V
0-5V
SATFAIL12
THERM
THERM
OATFAIL22
4-20mA
4-20mA
AI2
AI2
AI3
AI4
AI5
AI5
AI7
ANALOG INPUTJUMPER SETTINGS
ANALOG INPUTJUMPER SETTINGS
MUSTBE SETAS SHOWN FOR
MUSTBE SETAS SHOWN FOR
PROPER OPERATION
PROPER OPERATION
PRESSURE
PRESSURE
AI3
AI4
AI7
STATIC
STATIC
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
0-10V
0-10V
0-5V
0-5V
WattMaster Label
WattMaster Label
#LB102073-01-A
#LB102033-01
SPCFAIL32
MODULEALARM42
MECHCOOLFAIL13
MECHHEATFAIL23
FANPROOFFAIL33
DIRTYFILTER43
EMERGENCYSHUTDOWN53
LOWSAT14
HIGHSAT24
CONT.TEMPCOOLFAIL34
CONT.TEMPHEATFAIL44
PUSHBUTTONOVR15
ZONEOVR25
OUTPUTFORCEACTIVE06
EXPANSION
EXPANSION
Rev.: 1A
RELAYCONTACTRATING IS 1AMP
RELAYCONTACT
MAX @ 24 VAC
RATING IS 1AMPMAX @ 24 VAC
RELAYCOMMON
RELAYCOMMON
FAN
FAN
RELAY2
RELAY2
RELAY3
RELAY3
RELAY4
RELAY4
RELAY5
RELAY5
AAON No.:
V07150
LEDBLINKCODES
24 VAC POWER ONLY
24 VAC POWER ONLY
WARNING!POLARITYMUST BE OBSERVED
WARNING!POLARITYMUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
OR THE CONTROLLER WILLBE DAMAGED
2
2
IC
IC
2
2
IC DIGITAL
IC DIGITAL
SENSOR
SENSOR
OBSERVE
POLARITY
WARNING
Connection Of Wall
Mounted
Digital Room Sensor
(When Used)
Figure 9: OE256-02 - Duct Mounted CO2 Sensor Wiring
20
RNE Modular Controller Field Technical Guide
TSDRSC Cable
INSTALLATION AND WIRING
Remote Supply Air
Temperature Reset Signal
(By Others)
0-5 VDC or 0-10 VDC Signal
GND
Note:
Either The Slide Offset Option For The Space Temperature
Sensor Or The Remote Supply Air Temperature Reset
Signal Option (By Others) May Be Connected To AI7 On
The RNE Controller. Only One Option Is Allowed, Not Both.
AI7
GND
RNE Controller
AI1
AI1 SET
AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
AI2
AI3
AI4
AI5
AI7
Regardless of Whether the Remote
SAT Reset Signal Has Been
Configured For 0-5 or 0-10 VDC,
Jumper Must Be Set For 0-10V
AI7 SET
Remote SAT Reset Signal
Space Temperature Sensor
The OE210, OE211, OE212, OE213 Space Temperature Sensor is typically used for constant volume HVAC unit applications controlling one
zone. The Space T emperature Sensor is a 10K T ype III thermistor sensor
and should be mounted approximately 5 feet above the fl oor in the space
that is to be controlled. The Space Temperature Sensor is available as a
sensor only, sensor with override button, sensor with slide adjust, and
sensor with slide adjust and override confi gurations.
When the Remote Supply Air T emperature Reset Signal option is needed,
the Slide Offset option on the Room Sensor cannot be used. Only one
of these options may be used on the RNE Controller.
See Figure 10 below for complete Space Temperature Sensor wiring
details.
Note:
Either The Slide Offset Option For The Space
Temperature Sensor Or The Remote Supply
Air Temperature Reset Signal Option (By
Others) May Be Connected To An AI7 On
The RNE Controller. Only One Option Is
Allowed, Not Both.
AI1
Space Temperature Sensor
TMP
W
A
R
M
GND
E
R
C
O
O
OVR
L
E
R
AUX
Wire Required For
Sensors With Slide
Adjust Option Only
AI7
GND
Remote SAT Reset Signal
A Remote Supply Air T emperature Reset Signal can be connected to AI7
for applications requiring remote reset of the Supply Air Temperature
Setpoint.
When the Slide Offset option on the Room Sensor is used, the Remote
Supply Air Temperature Reset Signal cannot be used. Only one of these
options may be used on the RNE Controller.
The RNE Controller can accept either a 0-5 VDC signal or a 0-10 VDC
signal on this input.
See Figure 11 below for complete Remote SAT Reset Signal wiring
details.
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Set Jumper For THERM
When Space Sensor Slide
Adjust Is Wired To AI7
AI7 SET
Figure 10: OE210, OE211, OE212, OE213 – Space Temperature Sensor Wiring
Figure 11: Remote Supply Air Temperature Reset Signal Wiring
RNE Controller
RNE Modular Controller Field Technical Guide
21
INSTALLATION AND WIRING
SAT & RAT Sensor Wiring
Zone
Zone
Supply Air & Return Air Temperature
Sensor
The OE231 Supply Air & Return Air Temperature Sensors must be
wired as shown in Figure 12 below for proper operation. The Supply
Air & Return Air Temperature Sensors are 10K Type III thermistor
sensors. The Supply Air Temperature Sensor should be mounted in the
unit discharge plenum or in the supply air duct. The Return Air Temperature Sensor should be mounted in the return air duct. If the system
has a Zoning Bypass Damper installed, be sure the return air sensor is
located upstream of the bypass duct connection.
Note: The Supply Air Temperature Sensor Always
Wires To The AI2 Input On The RNE Controller Unless
Using The MODGAS II And/Or MHGRV II Controllers
As Stand-Alone.
Supply Air Temperature Sensor
NOTE: If your AAON® HVAC unit is using the AAON®
MODGAS-X Controller and/or the AAON® MHGRVX Controller, the Supply Air Temperature Sensor must
always be connected to the RNE Controller unless you
are using the AAON® MODGAS-X and/or AAON®
MHGRV-X Controllers as stand-alone.
Mount In HVAC
Unit Supply
Air Duct
Return Air Temperature Sensor
Mount In HVAC
Unit Return
Air Duct
GND
GND
AI2
AI3
RNE Controller
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Be Sure The Jumper Is Set For THERM
On AI2 & AI3 For Supply
& Return Air Temperature Sensors
When Used
Figure 12: OE230 / OE231 – Supply Air and Return Air Temperature Sensor Wiring
22
RNE Modular Controller Field Technical Guide
INSTALLATION AND WIRING
OAT Sensor Wiring
Outdoor Air Temperature Sensor
The OE250 Outdoor Air Temperature Sensor must be wired as shown
in Figure 13 below for proper operation of the RNE Controller. The
Outdoor Air Temperature Sensor is a 10K Type III thermistor sensor.
The sensor should be mounted in the upright position as shown in an
area that is protected from the elements and direct sunlight. Be sure to
make the wiring splices inside of the Outdoor Air Temperature Sensor
weather-tight enclosure.
Outdoor Air
Temperature Sensor
Make Splice Connections
Inside Sensor Enclosure
As Shown. Seal All Conduit
Fittings With Silicone
Sealant
CAUTION: Be sure to mount the Outdoor Air Temperature
Sensor in an area that is not exposed to direct sunlight. The shaded
area under the HVAC unit rain hood is normally a good location.
Unused conduit opening(s) must have closure plugs installed and
must be coated with sealing compound to provide a rain-tight seal.
Water can damage the sensor.
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI4
GND
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Be Sure Jumper Is Set
For THERM
On AI4 For Outdoor
Air Temperature Sensor
Mount Sensor Outdoors
In Shaded Protected
Area & In Upright
Position As Shown
Figure 13: OE250 – Outdoor Air Temperature Sensor Wiring
RNE Controller
RNE Modular Controller Field Technical Guide
23
INSTALLATION AND WIRING
24 VAC Power Source
Sized For Actuator VA Load
24 VAC
GND
2-10 VDC
Output
RNE Controller
GND
AO1
AI1
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
AI2
AI3
AI4
AI5
AI7
Economizer Damper Actuator
(Belimo Actuator Shown)
Y1 3
+ 2
COM - 1
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturer Wiring
Instructions
Economizer Feedback 5
NOTE: For Economizer
Actuator Feedback Signal,
SeeWiring For The
VCM-X Expansion Module.
AI3
Economizer Damper Actuator Wiring
Zone
Zone
Economizer Damper Actuator
The Economizer Damper Actuator signal voltage output is a 2-10 VDC
output. This signal output is used by the RNE Controller to modulate
the Economizer Damper Actuator in order to control the amount of
Outdoor Air delivered to the HVAC unit for Free Cooling and/or Indoor
Air Quality requirements. See Figure 14 for detailed wiring.
WARNING: It is very important to be certain that all wiring is
correct as shown in the wiring diagram below. Failure to observe
the correct polarity will result in damage to the actuator or RNE
Controller.
Figure 14: Economizer Damper Actuator Wiring
24
RNE Modular Controller Field Technical Guide
INSTALLATION AND WIRING
+
_
3 (Y)
5 (U)
2 (+)
1 (-)
Supply Fan VFD Signal and Zoning Bypass Damper Actuator
Supply Fan VFD Signal or Zoning
Bypass Damper Actuator Signal
The Supply Fan VFD or Zoning Bypass Damper Actuator Signal is a
0-10 VDC output. This signal output can be connected to the Supply
Fan Variable Frequency Drive to modulate the Supply Fan speed and
control Duct Static Pressure utilizing the Duct Static Pressure Sensor
connected to the RNE Controller. Alternatively, it can be connected to a
Zoning Bypass Damper Actuator that will modulate the Zoning Bypass
Damper Actuator to control Duct Static Pressure utilizing the Duct Static
Pressure Sensor connected to the RNE Controller. A Duct Static Pressure
Sensor must be connected in order for the VFD or Zoning Bypass Damper
Actuator to operate. See Figures 15 and 16 below for detailed wiring.
Caution:
The VFD Unit Must Be Configured For 0-10 VDC Input.
The Input Resistance At The VFD Must Not Be Less
Than 1000 Ohms When Measured At The VFD
Terminals WithAll Input Wires Removed.
0-10VDC Input From AO2
GND
Shield
Supply Fan Variable Frequency Drive
(By Others)
Note:
Wire To The VFD Using 18 GA Minimum 2
Conducter Twisted Pair With Shield Cable.
Wire Shield To GND As Shown
CAUTION: Variable Frequency Drive units can cause large
transient noise spikes which can cause interference to be propagated
on other electronic equipment. Use shielded wire wherever possible
and route all sensor and controller wiring away from the Variable
Frequency Drive and the HVAC Unit electrical wiring.
AI1 SET
AI1
AI2 SET AI3 SET
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
AO2
GND
Shield
RNE Controller
Figure 15: Supply Fan VFD Wiring
24 VAC Power Source
Sized For Actuator VA Load
Bypass Damper Actuator
(Belimo Actuator Shown)
Figure 16: Zoning Bypass Damper Actuator Wiring
Belimo Actuator Wiring Shown.
Consult Factory For Other
Manufacturer Wiring Instructions.
GND
24 VAC
0-10 VDC
AO2
GND
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
RNE Controller
RNE Modular Controller Field Technical Guide
25
Zone
Y1 3
+ 2
COM - 1
Economizer Feedback 5
INSTALLATION AND WIRING
Zone
VCM-X Expansion Module Input Wiring for the RNE Controller
VCM-X Expansion Module for RNE
Three different Expansion Modules are available for use with the RNE
Controller to provide additional inputs and outputs beyond those found
on the RNE Controller.
The VCM-X Expansion Module ( OE333-23-EM) provides 8 Binary
Inputs, 4 Analog Inputs, 4 Relay Outputs, and 5 Analog Outputs. See
Figures 17 and 18 for complete wiring details.
Hood On - N.O. Contact
Remote Forced Dehumidification
N.O. Contact
10 VA Minimum Power
Required For
VCM-X Expansion Module
Building Pressure
Plastic Tubing To Building
Pressure Sensing Locations
Economizer Damper Actuator
(Belimo Actuator Shown)
Outdoor Air
Humidity Sensor
VAC OR DC
Indoor Air
Humidity Sensor
VOUT (0-5V)
Transducer
HIGH
The VCM-X Expansion Module can be used in conjunction with the
12-Relay Expansion Module (OE358-23-12R-A).
The 4 Binary Input Expansion Module (OE356-01-BI) can be used in
place of the VCM-X Expansion Module if your system does not need
any other inputs or outputs.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and
24VAC-to-24VAC. Failure to observe polarity will result in damage to one
or more of the boards. Expansion Modules must be wired in such a way
that the expansion modules and the controller are always powered
together. Loss of power to the expansion module will cause the controller
to become inoperative until power is restored to the expansion module.
VCM-X Expansion Module
24 VAC POWER
POLARITY
WARNING
OBSERVE
PR OUT
GND
B 1I
B 2I
B 3I
B 4I
B 5I
B 6I
B 7I
BI8
AI1
AI2
AI3
AI4
GND
GND
Modular Cable
Connect To Next Expansion
Board (When Used)
ITIS SUGGESTED
THATYOU WRITE THE
DESCRIPTION OF
THE RELAYOUTPUTS
YOUARE USING IN
THE BOXES
PROVIDEDABOVE
WITHA PERMANENT
MARKER (SHARPIE®)
JUMPER SETTINGS
24 VAC POWER ONLY
ONLY
WARNING!POLARITYMUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILLBE DAMAGED
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED
VCM-X Expansion Module
Orion No.:OE333-23-EM
OE333-23-EM-AVCM-X EXPANSION MODULE
PR OUTGND
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY1 =RELAY 3 =
RELAY2 =RELAY 4 =
RELAY1 =RELAY3 =
RELAY2 =RELAY4 =
ITIS SUGGESTEDTHATYOU WRITETHEDESCRIPTION OFTHE RELAYOUTPUTSYOUARE USING INTHE BOXESPROVIDEDABOVE
VCM-X Expansion Module Output Wiring for the RNE Controller
The expansion modules can be used individually or together to provide
the required inputs and outputs for your specifi c applications.
The VCM-X Expansion Module must be connected to 24 VAC as shown
in the wiring diagram below. Please see Table 1 on page 17 for correct
VA requirements to use when sizing the transformer(s) used for power ing the expansion module.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in
damage to one or more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the
controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative
until power is restored to the expansion module.
24 VAC
GND
10 VA Minimum
Power Required For
VCM-X Expansion
Module
VCM-X Expansion
Module
POLARITY
WARNING
OBSERVE
24 VAC POWER
24 VAC POWER ONLY
ONLY
WARNING!POLARITYMUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILLBE DAMAGED
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED
PR OUT
GND
+V
SIG
GND
RELAY1 =RELAY3 =
RELAY2 =RELAY4 =
ITIS SUGGESTED
THATYOU WRITE THE
DESCRIPTION OF
THE RELAYOUTPUTS
YOUARE USING IN
THE BOXES
PROVIDEDABOVE
WITHA PERMANENT
MARKER (SHARPIE®)
JUMPER SETTINGS
www.aaon.com
VCM-X Expansion Module
Orion No.:OE333-23-EM
TO VCM-X INPUT
OE333-23-EM-AVCM-X EXPANSION MODULE
TERMINALS AI5 & GND
PR OUT
TO VCM-X INPUT
GND
TERMINALSAI5 & GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITALCOMPRESSOR
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY1 =RELAY3 =
BI1 = EMERGENCY SHUTDOWN - N.C. INPUT
BI2
RELAY2 =RELAY4 =
BI3
BI4
ITIS SUGGESTED
BI5
BI1= HOOD ON - N.O. INPUT
THATYOU WRITETHEDESCRIPTION OFTHE RELAYOUTPUTSYOUARE USING INTHE BOXESPROVIDEDABOVEWITHAPERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
MUST BE SETAS
JUMPER SETTINGS
ANALOG INPUT
= DIRTYFILTER - N.O. INPUT
BI2
BI6
= PROOF OF FLOW - N.O. INPUT
BI3
BI7
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI8
= REMOTE FORCED HEATING - N.O. INPUT
BI5
= REMOTE FORCED COOLING - N.O. INPUT
BI6
NOTE:
BI7
= SMOKE DETECTOR - N.C. INPUT
ALL BINARY INPUTS MUSTBE 24 VAC ONLY.
BI8
= REMOTE DEHUMIDIFICATION - N.O. INPUT
SHOWN FOR
PROPER
ANALOG INPUT
NOTE:
AO1 = BUILDING PRESSURE CONTROL VFD OR
OPERATION
ALLBINARYINPUTS MUSTBE 24 VAC ONLY.
MUSTBE SETAS
AO2
SHOWN FOR
PROPER
JUMPER
AO1=BUILDING PRESSURE CONTROLVFD OR
OPERATION
AO3
SETTINGS
AO2
THERM
AO4
ANALOG INPUT
4-20mA
AI1
JUMPER
0-10V
AO3
AO5
SETTINGS
0-5V
THERM
THERM
AO4
GND
4-20mA
4-20mA
AI1
AI2
0-10V
GND
0-10V
AO5
0-5V
0-5V
THERM
THERM
GND
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
4-20mA
4-20mA
AI2
AI3
GND
0-10V
AI2
0-10V
0-5V
0-5V
A3
I
THERM
AI4
THERM
AI1= OUTDOORAIR RH SENSOR (0-5 VDC)
4-20mA
4-20mA
GND
AI3
AI4
0-10V
AI2
= INDOORAIR RH SENSOR (0-5 VDC)
0-10V
GND
0-5V
AI3
= CO2 (0-10 VDC)
0-5V
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
THERM4-20mA
GND
AI4
0-10V
GND
I2C
0-5V
EXPANSION
Note:
All Relay Outputs Are Normally
Open And Rated For 24 VAC
Power Only. 1 Amp Maximum
Load.
A Total Of 20 Relays Are Available By
Adding Relay Expansion Modules. All
Expansion Module Relay Outputs Are User
Configurable As Listed Above.
R1
Configurable Relay Output #1
R2
Configurable Relay Output #2
R3
Configurable Relay Output #3
R4
Configurable Relay Output #4
A1O
AO2
AO3
AO4
AO5
Either A Building Pressure
Damper Actuator Or a
Building Pressure Relief
Fan VFD Can Be Used,
-
Building Pressure Control
Damper Actuator
1 COM
2 +
3Y1
Building Pressure
Relief Fan VFD
+
COM
Modulating Heating
(0 to 10 VDC
Or 2 to 10 Input)
+
COM
Modulating Chilled Water Valve
(0 To 10 Or 2 To 10 VDC Input)
+
COM
Return Air
Damper Actuator
(0-10 VDC)
1 COM
2 +
3Y1
Return Air Bypass
Damper Actuator
(0-10 VDC)
1 COM
2 +
3Y1
Belimo Actuator Wiring
Shown. Consult Factory
Modular Cable
Connect To Next Expansion
Board (When Used)
Notes:
1.) The Modulating Chilled Water Valve Used Must Be Capable Of Accepting Either A 0-10 VDC or 2-10 VDC Input. The Modulating Cooling Output Voltage Is User
Configurable For These Voltages. The Modulating Heating Devices Used Must Be Capable of Accepting Either A 0-10 VDC or 2-10 VDC Input. The Modulating Heating
Output Voltage Is User- Configurable For These Voltages. These Voltage Outputs Must Also Be Configured When You Are Setting Up The RNE Controller(s) Operating
Parameters.
2.) Each Modulating Heating Or Cooling Device Used On The RNE Controller Must Have (1) Relay Output Configured For Each Device Used, In Order To Enable The
Modulating Heating And/Or Cooling Device's Sequence. This Relay Output Must Be Configured When Setting Up The RNE Controller Operating Parameters.