Orion RNE Modular User Manual

Factory Packaged Controls
LED BLINK C ODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION 0 1
OATFAIL 0 2
SATFAIL 1 2
SPC FAIL 3 2
MODULE ALARM 4 2
MECH COOL FAIL 1 3
MECH HEAT FAIL 2 3
FANPROOF FAIL 3 3
DIRTY FILTER 4 3
EMERGENCY SHUTDOWN 5 3
LOW SAT 1 4
HIGH SAT 2 4
CONT. TEMP COOL FAIL 3 4
CONT. TEMP HEAT FAIL 4 4
PUSH BUTTON OVR 1 5
ZONE OVR 2 5
OUTPUT FORCE ACTIVE 0 6
RNE Modular Controller
Technical Guide
RNE Modular Controller: Tulsa - SS1045
Requires Service Tool Code: SS1056 Version 1.0 and up
www.aaon.com
www.orioncontrols.com
RNE MODULAR CONTROLLER
Orion No.:OE332-23E-RNE-A
AI1 = SPC (SPACE TEMPERATURE SENSOR) AI2
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
AI3
= RAT(RETURN AIR TEMPERATURE SENSOR)
AI4
= OAT(OUTDOOR AIR TEMPERATURE SENSOR)
AI5
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
AI7
= SPACETEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESETSOURCE
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
E-BUS
CONNECTOR
ANALOG INPUT
JUMPER
SETTINGS
THERM
4-20mA
AI1
0-10V 0-5V
THERM
4-20mA
AI2
0-10V 0-5V
THERM
4-20mA
AI3
0-10V 0-5V
THERM
4-20mA
AI4
0-10V 0-5V
THERM 4-20mA
AI5
0-10V
0-5V
THERM
4-20mA
AI7
0-10V 0-5V
ANALOG INPUT JUMPER SETTINGS MUST BE SETAS SHOWN FOR PROPER OPERATION
WattMaster Label
STATIC
#LB102121
PRESSURE
Rev.: 1A
EXPANSION
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
2
IC
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY COMMON
FAN
RELAY2
RELAY3
RELAY4
RELAY5
AAON No.:
V17110
24 VAC POWER ONLY
2
I C DIGITAL
SENSOR
TABLE OF CONTENTS
OVERVIEW ............................................................................................................................................................4
Features and Applications ..............................................................................................................................4
Part Number Cross Reference ........................................................................................................................6
Parts and Descriptions ....................................................................................................................................7
RNE Controller Dimensions .........................................................................................................................13
VCM-X Expansion Module for RNE Dimensions .........................................................................................14
12-Relay Expansion Module Dimensions ..................................................................................................15
4 Binary Input Expansion Module Dimensions .........................................................................................15
RNE Controller Component Locations ........................................................................................................16
INST ALLATION AND WIRING .............................................................................................................................17
Important Wiring Considerations .................................................................................................................17
RNE Controller Wiring ..................................................................................................................................18
Digital Room Sensor ...................................................................................................................................19
Wall Mounted Space CO
Duct Mounted CO2 Sensor ..........................................................................................................................20
Space Temperature Sensor ........................................................................................................................21
Remote SAT Reset Signal ..........................................................................................................................21
Supply Air & Return Air Temperature Sensor ..............................................................................................22
Outdoor Air Temperature Sensor ................................................................................................................23
Economizer Damper Actuator .....................................................................................................................24
Supply Fan VFD Signal or Zoning Bypass Damper Actuator Signal ...........................................................25
VCM-X Expansion Module Input Wiring for the RNE Controller ................................................................26
VCM-X Expansion Module Output Wiring for the RNE Controller .............................................................27
8 Binary Inputs ............................................................................................................................................28
4 Binary Inputs ............................................................................................................................................29
Outdoor Air Humidity Sensor ......................................................................................................................30
Indoor Wall-Mounted Humidity Sensor .......................................................................................................31
Return Air Mounted Humidity Sensor ..........................................................................................................32
Title 24 Economizer Actuator Feedback .....................................................................................................33
Building Pressure Sensor ...........................................................................................................................33
Building Pressure Control Output ...............................................................................................................34
Modulating Heating Device .........................................................................................................................35
Modulating Chilled Water Valve ..................................................................................................................36
Return Air Bypass .......................................................................................................................................37
12-Relay Expansion Module Wiring and Jumper Settings .........................................................................38
Airfl ow Monitoring Station Installation and Wiring ....................................................................................39
RNE 55 - 105 Ton Unit Two Compressors Wiring ........................................................................................40
Full Digital Module ......................................................................................................................................40
Water Source Heat Pump X-2 Module ........................................................................................................41
Two Condenser Head Pressure Module II ..................................................................................................42
Sensor ...............................................................................................................19
2
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 E-mail: mail@wattmaster.com Visit our web site at www.orioncontrols.com WattMaster Form: AA-RNE-TGD-01H Copyright March 2015 WattMaster Controls, Inc.
www.aaon.com
AAON Manual Part Number: V20490 AAON® is a registered trademark of AAON, Inc., Tulsa, OK. EBTRON® is a registered trademark of Ebtron, Inc., Loris, SC. Neither WattMaster Controls, Inc. nor AAON® assumes any responsibility for errors or omissions in this document. This document is subject to change without notice.
TABLE OF CONTENTS
RNE 120 - 140 Ton Unit Four Compressors Wiring .....................................................................................43
Full Digital Module ......................................................................................................................................43
Water Source Heat Pump X-2 Module ........................................................................................................44
Two Condenser Head Pressure Module II ..................................................................................................46
START UP AND COMMISSIONING ....................................................................................................................48
Addressing & Powering Up ...........................................................................................................................48
Programming the Controller .........................................................................................................................49
INPUTS AND OUTPUTS .....................................................................................................................................50
RNE Controller Inputs ....................................................................................................................................50
RNE Controller Outputs .................................................................................................................................50
Expansion Module Inputs & Outputs ...........................................................................................................51
4 Binary Input Expansion Module ................................................................................................................52
12-Relay Expansion Module ..........................................................................................................................52
SEQUENCE OF OPERATION .............................................................................................................................53
Operation Modes ...........................................................................................................................................53
Occupied/Unoccupied Mode of Operation ..................................................................................................53
HVAC Modes of Operation ..........................................................................................................................53
Vent Mode and Cooling Mode .....................................................................................................................53
Economizer Operation ................................................................................................................................55
Supply Air Tempering .................................................................................................................................55
Dehumidifi cation Mode ...............................................................................................................................56
Heating Mode ..............................................................................................................................................58
Morning Warm Up .......................................................................................................................................60
Head Pressure Control ...............................................................................................................................61
Remote Control of HVAC Mode ..................................................................................................................61
Supply Air Temperature Setpoint Reset ......................................................................................................61
Air Flow Monitoring/Control .........................................................................................................................62
Supply Fan Control .....................................................................................................................................62
Duct Static Pressure Control .......................................................................................................................62
Duct Static Pressure Control for Filter Loading ...........................................................................................63
Building Pressure Control ...........................................................................................................................63
CAV/MUA Dual Mode (Hood On/Off Operation) .........................................................................................63
MUA Unoccupied Operation .......................................................................................................................63
IAQ (CO
Pre-Heater Operation ..................................................................................................................................64
Heat Wheel .................................................................................................................................................64
Single Zone VAV Mode ...............................................................................................................................64
Outdoor Air Lockouts ..................................................................................................................................65
Supply Air Cutoffs .......................................................................................................................................65
RNE Controller Alarms ................................................................................................................................66
VAV/Zone Controller Alarms ........................................................................................................................67
Scheduling ..................................................................................................................................................68
Internal Trend Logging ................................................................................................................................68
Force Modes or Overrides ..........................................................................................................................69
VAV Terminal Unit Controller Compatibility .................................................................................................69
VAV/Zone System .......................................................................................................................................69
) Operation ...................................................................................................................................64
2
TROUBLESHOOTING .........................................................................................................................................70
APPENDIX ...........................................................................................................................................................76
System Confi gurations ..................................................................................................................................77
INDEX...................................................................................................................................................................80
RNE Modular Controller Field Technical Guide
3
OVERVIEW
Features and Applications
Features
The RNE Modular Controller (OE332-23E-RNE-A) is designed with 7 analog inputs, 2 analog outputs, and 5 relay outputs. Each RNE Control­ler’s input and output capabilities can be expanded with the VCM-X Expansion Module (OE333-23-EM), the 12 Relay Expansion Module (OE358-23-12R), and the 4 Binary Input Expansion Module (OE356­01-BI) by means of a modular cable.
The RNE Controller also allows various E-BUS modules to connect directly to it. These would include the Full Digital Module, the Two Condenser Head Pressure Module, and the Water Source Heat Pump Modules.
Each RNE Controller can be confi gured for control of VAV Units (with or without VAV/Zone Controllers), Constant Volume Units, and Make­Up Air Units. Features include the following:
Up to a Combined Total of 20 Stages of Heating & Cooling
Modulating Cooling Outputs (VFD Compressor or Chilled
Water Valve Control)
Modulating Heating Output ( Hot Water Valve,
Steam Valve, SCR Electric Heat Control)
Full Integration with the AAON
Natural Gas Controller
Full Integration with the AAON
Hot Gas Reheat Controller
®
MODGAS-X Modulating
®
MHGRV-X Modulating
Confi gurable for Heat Pump Applications
Advanced Dehumidifi cation Capabilities
Air Flow Monitoring of Outdoor Air, Supply Air,
and Return Air Streams
Air Flow Control of Outdoor Air Damper
Single Zone VAV Control
Primary/Secondary Heating Control
Adaptive Supply Air Reset
Selectable Control Sensor
Fan Proving Interlock
Dirty Filter Alarm
Emergency Shutdown Input (Smoke Detector/Firestat or
other Shutdown Conditions)
Drybulb/Wetbulb Control of Economizer Operation
Building Pressure Control
Remote Override Capabilities
IAQ Economizer Reset
Title 24 Economizer Certifi ed
7-Day, 2-Event-per-Day Scheduling
14 Holiday Event Scheduling
Optimal Start Scheduling
Trend Logging Capability
Static Pressure Control for Filter Loading Applications
Accepts Remote HVAC Mode Selection Via Contact
Closure On VCM-X Expansion Module
Confi gurable for AAON
®
PAC and DPAC Applications
Heat Wheel - On/Off Control
Confi gurable for R22 and R410-A refrigerant
Head Pressure Control
Full Digital Control
Water Source Heat Pump Monitoring
Most common HVAC unit control applications can be confi gured using only the RNE Controller. If the application requires more inputs and/ or outputs, optional expansion modules are available to provide for ad­ditional analog, binary, or digital inputs and outputs as required.
The available expansion module confi gurations allow for 4 or 8 addition- al binary inputs, 4 additional analog inputs, 5 additional analog outputs, and up to 16 additional binary (relay) outputs. The various expansion modules plug into the RNE Controller by means of a modular cable.
4
RNE Modular Controller Field Technical Guide
OVERVIEW
Features and Applications
E-BUS Module Applications
The RNE Controller will interface with the Two Condenser Head Pressure Module (OE370-23-HP2C2-A), the Full Digital Module (OE370-23-FD-A), and the W ater Source Heat Pump Modules (OE334­23-WPM-A, OE334-23-WPM-A20, OE334-23-WPM-A25, OE334­23-WPM-A40, and OE334-23-WPM-22-A).
These E-BUS Modules allow independent control of multiple VFD compressors, control of the condenser fan(s) or valve(s), and monitoring functions for Water Source Heat Pump Units. See pages 40-47 of this manual for detailed wiring and application details.
RNE Controller Applications
Variable Air Volume Unit
The RNE Controller can be confi gured to control a VFD Supply Fan for Duct Static Pressure control. If the unit is not equipped with a VFD, but Duct Static Pressure control is needed, a modulating Zoning Bypass Damper can be controlled by the RNE Controller.
VAV units are typically designed for occupied Cooling with Morning Warm-up Heating. This option is available with the RNE Controller. The RNE Controller can also be used for a Zoning System that needs Duct Static Pressure control and Occupied Cooling and Heating. The RNE Controller also has the ability to be confi gured for Duct Static Pressure Control by controlling the Supply Fan VFD for the purpose of maintaining proper Duct Static Pressure in response to varying fi lter loading conditions.
The RNE Controller allows Dehumidifi cation Priority on a VAV unit. This could be useful on a building with a very low internal sensible load, but which has a high internal and/or external latent load. During VAV Dehumidifi cation, the RNE Controller activates Cooling based on the Evaporator Coil Temperature and activates AAON® Modulating Hot Gas Reheat to warm the Supply Air Temperature to the Active Supply Air Temperature Setpoint.
Constant Air Volume Unit
The RNE Controller can be confi gured to activate a Constant Volume Supply Fan. In most cases, this is a very basic unit with Space T empera­ture control. The RNE Controller can be used for kitchen, restaurant, or lab environments that are 100% Outdoor Air part of the time and Return Air part of the time. The Hood On input allows the RNE Controller to know when to switch to 100% Outdoor Air control based on an exhaust hood activating. The RNE Controller requires Outdoor and Indoor Air Temperature Sensors to accomplish this application.
Make-Up Air Unit
The RNE Controller can be confi gured for 100% Outdoor Air control for Make-Up Air. All HVAC Modes are determined from the Outdoor Air Sensors. The Outdoor Air Volume must always be at least 50% or higher to be confi gured for Outdoor Air control.
AAON® PAC (Precision Air Control)
This control scheme can only be used on Constant Volume HVAC units that are equipped with a Return Air Bypass Damper and that use a Space Temperature Sensor as the Controlling Sensor.
AAON® P AC Control provides improved moisture removal capabilities
while utilizing internal space loads for reheat by redirecting the Return Air path from the upstream side of the DX Evaporator Coil to the down­stream side of the coil.
For AAON® P AC confi gured units, the Return Air Bypass Damper is only used during the Dehumidifi cation Mode. When the RNE Controller is in Dehumidifi cation Mode, the Return Air Bypass Damper will modulate open as the Space T emperature falls below the Cooling Setpoint. Modula­tion of the Return Air Bypass Damper is controlled using a proportional range from 0% (when the Space Temperature is equal to the Cooling Setpoint) up to 100% (when the Space T emperature falls to the halfway point between the Cooling and Heating Setpoints). A separate Return Air Damper Actuator will modulate the Return Air Damper slightly further towards its closed position as the Return Air Bypass Damper opens. This is to ensure that enough Return Air is bypassed around the Evaporator Coil through the Return Air Bypass Damper to raise its temperature. The rate which the Return Air Damper closes while the Return Air Bypass Damper is open is user-adjustable.
AAON® DPAC (Digital Precision Air Control)
This control scheme can only be used on Constant Volume HVAC units that are equipped with a Return Air Bypass Damper and VFD Compressor(s). AAON® DPAC also uses a Space Temperature Sensor as the Controlling Sensor.
The AAON® DP AC control scheme provides improved moisture removal capabilities over the AAON® P AC control scheme and provides for tighter temperature control by combining a VFD Compressor with the Return Air Bypass Damper. See the Cooling Mode section starting on page 53 for detailed VFD Compressor operation. Refer to AAON® P AC Control previously described for detailed Return Air Bypass Damper operation.
The VFD Compressor is used during both Cooling and Dehumidifi ca- tion Modes. The Return Air Bypass Damper is used only during the Dehumidifi cation Mode.
RNE Modular Controller Field Technical Guide
5
OVERVIEW
Part Number Cross Reference
PART DESCRIPTION
RNE Modular Controller OE332-23E-RNE-A V17110
VCM-X Expansion Module OE333-23-EM R69190
VCM-X 12-Relay Expansion Module OE358-23-12R R69180
VCM-X 4 Binary Input Expansion Module OE356-01-BI R82940
Full Digital Module OE370-23-FD-A R74870
Two Condenser Head Pressure Module II OE370-23-HP2C2 V20660
WSHP-X2 Module OE334-23-WSHP-X2 V48820
MHGRV-X Module OE377-00-00042 N/A
MODGAS-X Module OE377-00-00041 N/A
Building Static Pressure Sensor OE258-01 R37030
Bypass Damper Actuator OE281-04 N/A
Cable Coupler for TSDRSC Cables MS000029 N/A
CO
Sensor - Duct Mounted OE256-02 R82970
2
CO
Sensor - Space OE256-01 R82960
2
CommLink 5 Communications Interface OE361-13 V32950
Digital Room Sensor - Temp & Humidity OE217-01 R83870
Digital Room Sensor - Temp. Only OE217-00 R83860
Digital Sensor Cable Assembly TSDRSC-XX N/A
Duct Static Pressure Sensor OE271 P87100
Duct Temperature Sensor - 12" Probe OE231 R44940 / P87140
Duct Temperature Sensor - 6" Probe OE230 R36340
E-BUS Adapter Board OE365-15-EBA V15840
GPC-X Controller OE332-23-GPCX N/A
IP Module Kit OE415-02 R66770
MiniLink Polling Device OE364-22 N/A
Modular Service Tool SD - Operator Interface OE391-12 V28140
Modular System Manager SD - Operator Interface OE392-12 V36570
Outdoor Air RH Sensor - 3% - 0-5 VDC Output OE265-13 R34700
Outdoor Air Temperature Sensor OE250 P87150
Return Air RH Sensor - 3% - 0-5 VDC Output OE265-14 R34650
Room Mounted RH Sensor - 3% - 0-5 VDC Output OE265-11 R34690
Standard Room Sensor - Plain OE210 R31480
Standard Room Sensor - W/ Override OE211 P87040
Standard Room Sensor - W/ Override & Slide Adjust OE213 P94320
Standard Room Sensor - W/ Slide Adjust OE212 P94100
Static Pressure Pickup Tube OE290 S18780
Suction Pressure Transducer OE275-01 N/A
System Manager TS II - Operator Interface OE392-10 N/A
USB-Link 2 Kit OE366 R71870
ORION
PART NUMBER
AAON TULSA
PART NUMBER
6
RNE Modular Controller Field Technical Guide
OVERVIEW
Parts and Descriptions
PART NO. PART DESCRIPTION ILLUSTRATION
OE332-23E-RNE-A RNE Controller
The RNE Controller provides 7 analog inputs, 2 analog outputs, and 5 relays. It presently allows for the addition of the VCM-X Expansion Mod­ule, the 12 Relay Expansion Module, and hte 4 Binary Input Expansion Module described below.
NOTE: Set-up, programming, and monitoring of the RNE Controller
requires one of the following communication interfaces—Prism 2 Front­End Software used with a personal computer, System Manager Touch Screen II, or Modular Service Tool.
OE333-23-EM VCM-X Expansion Module
Includes: VCM-X Expansion Module mounted in plastic enclosure and 10 ft. I2C cable. The VCM-X Expansion Module adds VAV applications, building pressure control, head pressure control, water source heat pump monitoring, and other functions. It provides 4 additional analog inputs, 2 binary inputs, 5 additional relays, and 3 analog outputs. It connects with a modular cable to the RNE Controller.
OE358-23-12R VCM-X 12 Relay Expansion Module
Includes: 12 Relay Expansion Module mounted in plastic enclosure and 10 ft. I2C cable. The VCM-X 12 Relay Expansion Module adds 12 confi gurable relays to the RNE Control System. It connects to the RNE Controller using the included I2C cable.
POLARITY
WARNING
OBSERVE
POWER
24VAC
GND
EXP1
EXP2
RLY1
RLY2
RLY3
RLY4
RLYCOM
MADE IN USA
24 VAC POWER ONLY
WARNING!POLARITYMUST BE OBSERVED OR THE BOARD WILLBE DAMAGED
VCM-X Expansion Module
Orion No.:OE333-23-EM
PR OUT GND
OE333-23-EM-AVCM-X EXPANSION MODULE
PR OUT GND
+V SIG GND
+V SIG GND
RELAY1 = RELAY3 =
RELAY2 = RELAY4 =
RELAY1 = RELAY3 =
ITIS SUGGESTED THATYOU WRITETHE DESCRIPTION OF
RELAY2 = RELAY4 =
THE RELAYOUTPUTS YOUARE USING IN THE BOXES
ITIS SUGGESTED
PROVIDEDABOVE
THATYOU WRITETHE
WITHAPERMANENT
DESCRIPTION OF
MARKER (SHARPIE®)
THE RELAYOUTPUTS YOUARE USING IN THE BOXES PROVIDEDABOVE WITHAPERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
JUMPER SETTINGS MUSTBE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGS MUSTBE SETAS
SHOWN FOR
ANALOG INPUT
PROPER
JUMPER
OPERATION
SETTINGS
ANALOG INPUT
AI1
JUMPER SETTINGS
AI1
AI2
AI2
AI3
AI3
AI4
AI4
24 VAC POWER ONLY
WARNING!POLARITYMUST BE OBSERVED OR THE BOARD WILLBE DAMAGED
24 VAC POWER ONLY
WARNING!POLARITYMUST BE OBSERVED OR THE BOARD WILLBE DAMAGED
OE358-23-12R 12 RELAYEXPANSION MODULE
RLY1 = RLY7 =
RLY2 = RLY8 =
RLY3 = RLY9 =
RLY4 = RLY10 =
RLY5 = RLY11 =
RLY6 = RLY12 =
NOTE: ITIS RECOMMENDEDTHAT YOU WRITE THE DESCRIPTION OFTHE RELAYOUTPUTS YOU ARE CONNECTINGTOTHE RELAY EXPANSION MODULE INTHE BOXES PROVIDEDABOVE USINGAPERMANENT MARKER (SHARPIE) FOR FUTURE REFERENCE.
J1
EXP1
EXP2
I2C
EXPANSION
www.aaon.com
TO VCM-X INPUT TERMINALSAI5 & GND
TO VCM-X INPUT TERMINALSAI5 & GND
SUCTION PRESSURE TRANSDUCER CONNECTION FOR HVAC UNITS WITHOUT DIGITALCOMPRESSOR
SUCTION PRESSURE TRANSDUCER CONNECTION FOR HVAC UNITS WITHOUT DIGITALCOMPRESSOR
BI1= EMERGENCYSHUTDOWN - N.C. INPUT
= DIRTYFILTER - N.O. INPUT
BI2
= PROOF OF FLOW - N.O. INPUT
BI3
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI1= HOOD ON - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
BI5
BI2
= DIRTYFILTER - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
BI6
BI3
= PROOF OF FLOW - N.O. INPUT
= HOOD ON - N.O. INPUT
BI7
BI4
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
= REMOTE FORCED HEATING - N.O. INPUT
BI5
= REMOTE FORCED COOLING - N.O. INPUT
BI6
NOTE:
= SMOKE DETECTOR - N.C. INPUT
BI7
ALLBINARYINPUTS MUST BE 24 VAC ONLY.
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
NOTE:
AO1=BUILDING PRESSURE CONTROL VFD OR
ALLBINARYINPUTS MUST BE 24 VAC ONLY.
DAMPERACTUATOR (0-10 OR 2-10 VDC)
AO2
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
AO1=BUILDING PRESSURE CONTROL VFD OR
AO3
= MODULATING COOLING/DIGITALSCROLL
DAMPERACTUATOR (0-10 OR 2-10 VDC)
SIGNAL(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= MODULATING HEATING SIGNAL
AO2
THERM
AO4
= RETURNAIR DAMPERACTUATOR
(0-10 VDC OR 2-10 VDC)
4-20mA
(0-10 VDC)
0-10V
= MODULATING COOLING/DIGITALSCROLL
AO3
AO5
= RETURNAIR BYPASS DAMPERACTUATOR
0-5V
SIGNAL(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
THERM
= RETURNAIR DAMPERACTUATOR
AO4
THERM
GND
= GROUND FORANALOG OUTPUTS
4-20mA
4-20mA
(0-10 VDC)
0-10V
GND
= GROUND FORANALOG OUTPUTS
0-10V
= RETURNAIR BYPASS DAMPERACTUATOR
AO5
0-5V
0-5V
(0-10 VDC)
THERM
THERM
= GROUND FORANALOG OUTPUTS
GND
AI1= OUTDOORAIR RH SENSOR (0-5 VDC)
4-20mA
4-20mA
= GROUND FORANALOG OUTPUTS
GND
0-10V
AI2
= INDOORAIR RH SENSOR (0-5 VDC)
0-10V
0-5V
0-5V
A3
= ECONOMIZER FEEDBACK
I
THERM
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
THERM
AI1= OUTDOORAIR RH SENSOR (0-5 VDC)
4-20mA
4-20mA
GND
= GROUND FORANALOG INPUTS
AI2
= INDOORAIR RH SENSOR (0-5 VDC)
0-10V
0-10V
GND
= GROUND FORANALOG INPUTS
0-5V
AI3
= CO2 (0-10 VDC)
0-5V
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
THERM 4-20mA
GND
= GROUND FORANALOG INPUTS
0-10V
= GROUND FORANALOG INPUTS
GND
I2C
0-5V
EXPANSION
I2C
EXPANSION
SETJUMPERAS SHOWN WHEN
ONLY THE 12 RELAY EXPANSION MODULE IS USED
EXP1
EXP2
WattMaster Label
#LB102034-01
www.orioncontrols.com
www.orioncontrols.com
WattMaster Label #LB102034-01-A
Rev.: 1K
WattMaster Label
#LB102043
www.orioncontrols.com
®
J1
SETJUMPERAS SHOWN WHEN BOTH THE VCM EXPANSION MODULEANDTHE RELAYEXPANSION MODULEARE USED
AAON No.:
R69190
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY1
RELAY2
RELAY
RELAY3
COMMON
RELAY4
RELAY COMMON
PAGE
NO.
Page 18
OBSERVE
WARNING
POLARITY
I2C
EXPANSION
RELAY1
RELAY2
RELAY3
RELAY4
VCM
I2C
EXPANSION
RELAY
I2C
EXPANSION BOARD
EXPANSION
YS102228 REV 1
RLY5
RLY6
RLY7
RLY8
RLYCOM
RLY9
RLY10
RLY11
RLY12
RLYCOM
Pages 26-28
Page 38
OE356-01-BI VCM-X 4 Binary Input Expansion Module
Includes: 4 Binary Input Expansion Module mounted in Snap Track and 10 ft. I2C cable. Use the 4 Binary Input Expansion Module if your HVAC unit only requires a Smoke Detector/Firestat, Dirty Filter, Proof of Flow, or Remote Forced Occupied Inputs or all of these 4 inputs and you don’t need any of the other inputs or outputs provided by the OE333-23-EM VCM-X Expansion Module. The module connects to the RNE Controller using the included I2C cable.
OE334-23-WSHP-X2 Water Source Heat Pump X2 Module
Includes: Water Source Heat Pump X2 Module in a plastic enclosure with LCD display and E-BUS Modular cable. Provides monitoring and compressor control for AAON Tulsa Water Source Heat Pump Units. Used with the RNE Controller.
OE370-23-FD-A Full Digital Module
Includes: Full Digital Module in a plastic enclosure and E-BUS Modular cable.Used with the RNE Controller. For AAON Tulsa units with multiple Digital Scroll Compressors and that are not Water Source Heat Pump Units.
RNE Modular Controller Field Technical Guide
GND
24VAC
Page
VCM BIN EXPBOARD
PWR
YS102364 REV1
COM
BI3
BI4
BI1
BI2
Y102374 REV 0S
WATTMASTER CONTROLS
MADE IN USA
29
Pages 41,44
R12
R53
R54
R11
4751
4751
4751
4751
TB3
+5V
1003
SIG 1
1002
10uF
GND
+5V
1003
www.orioncontrols.com
SIG 2
1002
10uF
GND
C2
+5V
1003
SIG 3
1002
10uF
GND
+5V
1003
SIG 4
1002
10uF
GND
4
R7
R9
300
BIN 1
4
R13
R14
BIN 2
300
1002
R23
COM
1002
R24
1002
R25
1002
R26
ADDRESS
1
OFF
2 4 8
SW1
PWR
D3
R1
D4
R2
D12
R3
D13
R4
Rc
RELAYS
SERIAL#
ANALOG
AO1
AO2
GND
PWM1-
PWM1+
R34 R50
PWM2-
PWM2+
SW2
1002
OFF
1002
1002
1002
R30
ALARM
R29
STAT
R28
COMM
C20
.01uF
Pages 40,43
OPTIONS
7
OVERVIEW
Parts and Descriptions
PART NO. PART DESCRIPTION ILLUSTRATION
OE370-23-HP2C2-A Two Condenser Head Pressure Module
Includes: Two Condenser Head Pressure Module in a plastic enclosure and E-BUS Modular Cable. This module is used on units with 2 physical­ly separate condenser sections and is able to monitor up to 4 individual head pressure transducers (2 per section) to control the Condenser Fans or Water Valves based on the highest of the 2 readings for each section. It is also capable of monitoring a Heating Enable control signal (Heat Pump Mode) and forces the Condenser Signal to 100% while in this mode. This module can be used as a communicating module with the RNE Controller.
OE210 OE211 OE212 OE213
Standard Room Sensor–Plain, w/Override, w/Override & Slide Adjust & w/Slide Adjust Only
Includes: Standard Room Sensor - Plain, with Override, with Override and Slide Adjust & with Slide Adjust only. For wall mounting. Use with RNE Controller only. Connects to controller via fi eld fabricated wiring.
+5V
1003
SIG 1
1002
10uF
GND
+5V
1003
SIG 2
1002
10uF
GND
C2
+5V
1003
SIG 3
1002
10uF
GND
+5V
1003
SIG 4
1002
10uF
GND
R7
R9
BIN 1
R13
R14
BIN 2
R23
COM
R24 R25 R26
ADDRESS
1
OFF
2 4 8
SW1
PWR
OE217-00 Digital Room Sensor - Temp. Only
LCD Display and keypad allow for setpoint adjustment, override, and display of certain status and setpoints. The OE217-00 is used with the RNE Controller for room air temperature sensing applications. Uses I2C cable.
OE217-01 Digital Room Sensor - Temp and Humidity
LCD Display and keypad allow for setpoint adjustment, override, and display of certain status and setpoints. The OE217-01 is used with the RNE Controller for room air temperature and humidity sensing applica­tions. Uses Uses I2C cable.
PAGE
NO.
R53
R12
R11
R54
4751
4751
4751
4751
TB3
D3
R1
D4
R2
D12
R3
D13
R4
Rc
RELAYS
SERIAL#
ANALOG
AO1
AO2
GND
PWM1-
4
300
4
300
1002
1002
1002
1002
OVERRIDE ALARM
Display
OVERRIDE ALARM
Display
PWM1+
R34R50
PWM2-
PWM2+
SW2
1002
OFF
1002
1002
1002
R30
ALARM
R29
STAT
R28
COMM
C20
.01uF
TMP
GND
AUX OUT
Override
Override
Pages 42,46
OPTIONS
Page 21
Page 19
Page 19
OE256-01 CO2 Wall-Mounted Sensor
Used with the RNE for CO2 sensing applications where wall mounting in the space is desired. Connects to the RNE Controller with an I2C cable of required length. Cable sold separately.
OE256-02 CO2 Duct Sensor with Pickup Tube
Used with the RNE Controller for duct mounted CO2 sensing applica­tions. Connects to the RNE Controller with an I
TSDRSC-05 TSDRSC-10 TSDRSC-25 TSDRSC-40 TSDRSC-80 TSDRSC-120 TSDRSC-160
length. Includes: Duct Mounted CO Airfl ow Pickup Tube and 10 ft. I2C Cable.
Digital Sensor Cable Assembly
Includes: Digital Sensor Cable Assembly. Cable assembly has male RJ-45 modular connectors on both ends. For use with the Digital Room Temperature Sensor, Digital Room & Temperature Sensor, Wall Mounted CO2 Sensor & Duct Mounted CO2 Sensor. These cables are used with the OE332-23E-RNE – RNE Controller and the OE742-31-VAVZ, OE742-32-VAVZ, OE744-31-VAVZ, and OE744-32-VAVZ – VAV/Zone Controller Actuator Packages. The TSDRSC Cables are available in 5,
Sensor, Integral Aspiration Box,
2
10, 25, 40, 80, 120 & 160 feet lengths. The maximum length of cable allowed is 160 feet for a CO2 Sensor and 160 Feet for a Digital Room Sensor. The total combined length of cable allowed when both a CO2 Sensor and Digital Room Sensor is used is 160 feet.
MS000029 Cable Coupler for TSDRSC Cables
Includes: Sensor Cable Coupler. Used to connect TSDRSC cables together when lengths inbetween available cable sizes are required. Female RJ-45 to Female RJ-45. Maximum 1 Cable Coupler per cable run.
2
C cable of required
Page 19
Page 20
Page 19
Page 19
8
RNE Modular Controller Field Technical Guide
OVERVIEW
Parts and Descriptions
PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.
OE230 OE231
Duct Temperature Sensor - 6” Probe Duct Temperature Sensor - 12" Probe
OE230 = 6 probe length. OE231 = 12 probe length. Used for return or supply air temperature sensing applications. Includes: 10k Ohm Duct Temperature Sensor, 2 wire only.
OE250 Outdoor Air Temperature Sensor
Used for temperature sensing applications. Includes: 10k Ohm Outside Air Temperature Sensor, 2 wire, mounted in a weatherproof handy box only.
OE258-01 Building Static Pressure Sensor
Used for Building Pressure Sensing. Includes: -0.25 to +0.25 W.C., 0-5 VDC, 24 VAC/VDC supply power Building Pressure Sensor only.
OE265-11 Room Mounted RH Sensor - 3% - 0-5 VDC Output
Includes: 0-5 VDC, Room Mounted Relative Humidity Transmitter only. Used for room air humidity sensing applications.
OE265-13 Outdoor Air Temperature & Humidity Sensor
Includes: 0-5 VDC, Outside Air Relative Humidity Transmitter mounted in a weatherproof, round handy box only. Used for outside air humidity sensing applications.
Page 22
Page 23
Page 33
Page 31
Page 30
OE265-14 Return Air RH Sensor - 3% - 0-5 VDC Output
Includes: 0-5 VDC, Return Air Relative Humidity Transmitter mounted in a weatherproof, round handy box only. Used for return air humidity sensing applications.
OE271 Duct Static Pressure Sensor
Used for duct static pressure sensing applications. Includes: 0-5 W.C., 0-5 VDC, Static Pressure Sensor only.
OE275-01 Suction Pressure Transducer
Includes: Suction Line Pressure Transducer with modular cable. The cable is supplied with a modular connector on one end and bare stripped wires on the other end. The OE275-01 Suction Pressure Transducer is used to monitor refrigerant suction line pressure of a DX cooling coil when a digital compressor is used. The Suction Pressure Transducer is provided with a ¼ SAE Flare connection for connection to the refrigerant suction line.
OE281-04 Bypass Damper Actuator
Includes: OE281-04 Modulating Damper Actuator. Used when a terminal unit is to be used as a bypass damper for fi eld or factory controls mounted by others. Accepts a 0-10 VDC signal.
Page 32
Page 18
Pages 40,41 43,44
Page 37
RNE Modular Controller Field Technical Guide
9
OVERVIEW
STATUS
Parts and Descriptions
PART NO: PART DESCRIPTION ILLUSTRATION PAGE NO.
OE290 Static Pressure Pick-up Tube
Used with OE271 Static Pressure Sensor for static pressure sensing applica­tions. Includes: Static Pressure Pick-up Tube with 1 ft. length of FRP tubing, gasketed mounting bracket, and screws.
OE392-10 System Manager TS II Operator Interface
The System Manager TS II provides a direct, graphic-enhanced, menu-driven link to enable the system operator to view the status and adjust the setpoints of any controller on the RNE control system. The System Manager TS II is equipped with a 4.3” 480 x 272 WQVGA RGB TFT LCD Touch Screen Display. The System Manager TS is furnished with hardware for fl ush mounting into hollow drywall or surface mounting on concrete brick or plaster surfaces. Includes: System Manager TS with 12 ft. long pigtail cable assembly.
OE391-12 Modular Service Tool SD
Includes: Modular Service Tool SD, power supply, communication cables, adapter plug, and (4) AA batteries. Used to program and monitor all Orion
controllers.
OE392-12 Modular System Manager SD
Includes: Modular System Manager SD with 4 Gigabyte SD card and 12 ft. long pigtail cable assembly. Used to program and monitor all Orion controllers. Designed for hollow core wall mounting. When System Manager is to be mounted on a solid wall (concrete), you will also need to order the solid wall mounting bracket below. Modular System Manager and communication cables.
Mode
Selecti on
13
2
654
9
708
-
Page 18
See the System Manager Touch Screen II Technical Guide
See the RNE Controller Operator Interfaces SD Technical Guide
See the RNE Controller Operator Interfaces SD Technical Guide
EB101505 Solid Wall Mounting Bracket for Modular System
Manager SD
Includes: 22 gauge galvanized sheet metal mounting bracket with mounting holes and wire routing opening. Dimensions are 9.25W x 8.00H x 0.50DP. The Wall Mounting Bracket provides wiring clearance between the System Manager and the wall mounting surface when the System Manager is to be mounted on a concrete or other solid wall surface. Not for use with System Manager TS.
OE361-13 CommLink 5 Communications Interface
The CommLink 5 connects to your control system using a USB computer connection to provide direct on-site communications with the control system from a computer with the Prism 2 software installed. For remote communica­tions, see OE415-02 IP Module Kit.
Includes: CommLink 5, 6 ft. long USB cable, and 120/24 VAC power supply. Required on all networked systems or if direct computer or remote computer connection is required. Connects to your computer’s USB 1.1 or 2.1 port. Prism 2 computer front-end software must be installed on the direct connect­ed or remote connected computer in order to communicate with your system.
10
RNE Modular Controller Field Technical Guide
N/A
See the CommLink 5 Technical Guide
OVERVIEW
Parts and Descriptions
PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.
OE415-02 IP Module Kit - Internet/LAN Connection
Used for Internet or Local Area Network communications with the control system. Field installs by plugging into the CommLink IV circuit board and provides an addressable Ethernet connection to the controls system from any computer connected to your building’s LAN. It can also be confi gured to allow access to the control system from the Internet through your LAN if your Ethernet fi rewall is confi gured for this option.
Includes: IP Link module, 10 ft. long Ethernet cable, and installation instruc­tions. Prism 2 computer front-end software must be installed on the remote computer in order to dial-up and communicate with the controls system.
OE366 USB-Link 2 Kit
The USB-Link 2 is a pocket-sized communications interface used to connect a laptop computer to your controls system for programming and monitoring purposes, utilizing a modular cable to allow connection to the service port connector on the controllers and a USB cable to connect to a laptop com­puter.
Includes: USB-Link 2 for multiple or single loop systems, USB cable, modular connection cable, two mini-DIN to terminal adapters, and Prism 2 software.
OE364-22 MiniLink Polling Device
Control enclosure is for indoor use only. Used with all Orion controllers to provide network communications, zone voting, alarming, and tenant logging capabilities. A MiniLink Polling Device is required on each loop of a Net­worked system. Includes: MiniLink Polling Device mounted in the EE000075­01 control enclosure. Control Enclosure cover is shown removed in picture.
See the IP Module Technical Guide
See the USB-Link 2 Technical Guide
U1
CX7
RV1
CX3
VREF
U3
U4
CX2
R4
LED 1
LED 2
EPROM
POWER
C8
C7 R25
R26
V1
1
AIN
R27
THERM
4-20mA
U12
0-10V
R31
OFF=0-5V
D4
+5V
GND
24VAC
C11
D5
TB2
TB1
U7
P1
CX1
C4
C1
R3
YS101818P552
X1
CX4
PROCESSORPBOARD
C1
C2
CX5
U5
RAM
CX2
AIN2
THERM
4-20mA
0-10V
GND
AIN 2
AIN 1
X1
CX6
C3
U6
PHILIPS
U10
YS101900PMINILINK
D1
POLLING
U1
DEVICE
1
REV. 1
R1
U6
CX1
C3
U2
CX6
RN2
U11
R2
WDOG
R24
C10
C9
RN3
LD4
PROC.
LOOP
NETWORK
DRIVER
DRIVER
DRIVER
X2
CX15
CX14
CX13
P3
R28
U14
U15
U13
R29
R30
LD6
LD5
NETWORK
LOCAL LOOP
LOOP
2
4
8
1
32 16
P5
P4
SHLD
T
R
SHLD
T
R
ADD
OFF
TB3
TB4
SW1
See the CommLink IV Technical Guide
OE365-15­EBA
E-BUS Adapter Board
The E-BUS Adapter Board is used for connecting the EBTRON®, GreenTrolTM or Paragon Airfl ow Measurement Digital Transmitter to the VCB-X Control System. The E-BUS Adapter Board connects to the VCB-X Controller with an EBC E-BUS cable. Cable supplied separately.
OE508 Prism 2 Front-End Computer Software
Prism 2 provides standard, easy to understand status screens for each type of RNE equipment installed. Prism software has provisions for custom screens which allow fl oor plans, equipment photos, or user-defi ned summary screens to be implemented to meet their own individual needs. All controlling setpoints, trend logs, and alarm conditions are accessed in the Prism environ­ment. Prism can be confi gured for direct on-site installation, remote modem connection, or TCP/IP Internet connection to several installations.
OE437-03 Communication Surge Protector Kit
Used to isolate power surges to the communications wiring caused by lightning strikes for communications wiring loops that are routed outdoors or between buildings. One kit is required at each point where the communica­tions wiring leaves or enters a building. Includes: Communication Bus Surge Protector, Base Module, and Mounting/ Wiring Instructions.
See Page 39.
See the Prism 2 Technical Guide
N/A
RNE Modular Controller Field Technical Guide
11
OVERVIEW
Parts and Descriptions
PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.
OE377-00­00042
OE377-00­00041
OE332-23­GPCX
MHGRV-X Controller
The MHGRV-X Controller controls a Modulating Hot Gas Reheat Valve to maintain a desired Supply Air Temperature and Dehumidifi cation setpoint. The MHGRV-X Controller connects to the RNE Controller via an I2C cable. Available only from AAON®.
MODGAS-X Controller
The MODGAS-X Controller modulates up to (2) gas valves to maintain
a desired Discharge Air Temperature. It also controls the speed of the induced draft fan to maintain proper combustion in the heat exchanger.
The MODGAS-X Controller connects to the RNE Controller via an I2C cable. Available only from AAON®.
GPC-X Controller
The GPC-X Controller provides the fl exibility to control, schedule, and/or monitor equipment such as unit heaters, exhaust fans, motorized louvers, etc. The GPC-X has (6) confi gurable inputs which will accept signals from thermistor temperature sensors, 4-20mA or 0-5 VDC transmitters, or dry contact closures. An additional modular input is provided for connection of an OE271 Static Pressure Sensor. The GPC-X has (5) relay outputs for on/off control and (2) analog outputs. The GPC-X also has (5) separate 2-events-per-day schedules, each with its own optimal start functions built in. In addition, the GPC-X provides Lead/Lag start capabilities. Use the GPC-X to provide additional schedules for your controllers.
TB3
CLG OVR
GND
HTG OVR
RHTIN
SHLD
R
SAT
T
PJ1
R12
PU
D2
PJ1
2 I C IN
D1
R19
+24VAC
YS101826PREV 1 MODULATING GAS BOARD
R
SHLD
T
D8
V4
24VAC
GND
R4
2
I C OUT
COMM
VR1
RV1
C3
D6
R11R1D5R3R3
R20
WDOG
U2
C12
CX6 U6
U1
D1
D1
C13
C2
GND
C4
P1
TB4
P1
RV1
SAT
+VDC
C1
VR1
R7
D1
P
R15
WDOG
POWER
CX6
U6
U1
C7
U5
C2
C4
P1
R13R5R6D4D3
R2
U2
R1
C3
CX1
1
PHILIPS
U5
CX5
C1
X1
YS101818P552 PROCESSORPBOARD
STATUS
RESET LIMIT
O
F
F
1
RSTIN
AUX IN
GND
HEATEN
2
4
J01
8
16
C2
32
64
128
ADD
R8
D2
R9
R1R3R1
P
R2
U2
C3
CX1
R1
1
PHILIPS
PHILIPS
U5
CX5
C1
YS101818 552 PROCESSOR BOARD
C1
R18
L1
C8
L2
V5
R31
D11
R38
I2C IN
TB2
R26
R26
C6
R25
POWER
TB3
FAN
V1
CW/HW
CB/HB
CG/HR
CR/HG
+VDC
GND
GND
AUX IN
RSTIN
CX2
DISCHARGE SETPOINT
R4
K1
YS101894 REV 1
HOTGAS REHEAT
V2
COMP
R2
U1
AUX IN SETUP
THERM
STEP
4-20MA
0-10V
C4
C2
R9R8R7
RAM
EPROM
U4
CX4
U3
CX3
TB1
O
F
F
1
AUX
COM
LO SPD
FAN
2 4 8 16 32 64
LO SPD
FAN
AUX
128
ADD
CX2
EPROM
RAM
SERIAL#
K2
V3
VALVE
R17
K3
AUX
V4
TB5
FAN
R23
K4
COMP
U5
VALVE
AUX
CX5
COM
RESETLIMIT
SW1
ADD
128
SETPOINT
STATUS
R39
1286416
POWER
R40
V1 V3K3V2
K2
K1
FT
N/A
16
421
8
64
32
SW2
ADD
1
2
32
4
8
C15
N/A
SER. #:
U4
CX4
U3
GAS
CX3
VALVE
D9
VOUT
GND
C13
V5
TB4
See GPC-X Technical Guide
OE310-21-LP Lighting Controller
Adds lighting control capability to the RNE Control System. Lighting Con­troller provides up to (7) independent time schedules. Provisions for photo­cell or light sensor light level control are also provided. Lighting Controller only provides Pilot Duty Relay Outputs. An external Lighting Contactor must be provided by others. If a Light Sensor OE259 is to be used with the Lighting Controller, it must also be ordered from WattMaster. Includes: Lighting Controller with Backplate.
OE259 Light Sensor
Ambient Light Sensor
(Use with Lighting Controller for light sensing.) 24VDC power, 1m Ohm to 1.5k Ohm output signal. Supplied with weather­proof handy box for outdoor or indoor mounting. Light Sensor threads into conduit fi tting. Includes: Light Sensor and weatherproof handy box.
N/A
N/A
12
RNE Modular Controller Field Technical Guide
OVERVIEW
RNE Modular Controller Dimensions
5.985.98
8.388.38
0.290.29
7.837.83
2.752.75
1.49
4.104.10
0.700.70
Figure 1: OE332-23E-RNE – RNE Modular Controller Dimensions
OBSERVE
WARNING
POLARITY
0.980.98
RNE Modular Controller Field Technical Guide
13
OVERVIEW
VCM-X Expansion Module for RNE Dimensions
5.98
2.75
24 VAC POWER
24 VAC POWER ONLY
ONLY
WARNING! POLARITYMUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILL BE DAMAGED
MUST BE OBSERVED OR THE BOARD WILL BE DAMAGED
VCM-X Expansion Module
Orion No.:OE333-23-EM
OE333-23-EM-A VCM-X EXPANSION MODULE
PR OUT
TO VCM-X INPUT
GND
TERMINALS AI5 & GND
PR OUT
TO VCM-X INPUT
GND
TERMINALS AI5 & GND
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY 1 = RELAY 3 =
RELAY 2 = RELAY 4 =
RELAY 1 = RELAY 3 =
IT IS SUGGESTED THATYOU WRITE THE DESCRIPTION OF
RELAY 2 = RELAY 4 =
THE RELAYOUTPUTS YOUARE USING IN THE BOXES
IT IS SUGGESTED
PROVIDEDABOVE
THATYOU WRITE THE
WITHA PERMANENT
DESCRIPTION OF
MARKER (SHARPIE®)
THE RELAYOUTPUTS YOUARE USING IN THE BOXES PROVIDEDABOVE
ANALOG INPUT
WITHA PERMANENT MARKER (SHARPIE®)
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
ANALOG INPUT
PROPER
JUMPER
OPERATION
SETTINGS
THERM
ANALOG INPUT
4-20mA
AI1
0-10V
JUMPER
0-5V
SETTINGS
THERM
THERM
4-20mA
4-20mA
AI2
AI1
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
AI3
AI2
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
AI4
AI3
0-10V
0-10V
0-5V
0-5V
THERM 4-20mA
AI4
0-10V
I2C
0-5V
EXPANSION
I2C
WattMaster Label
EXPANSION
#LB102034-01
www.aaon.com
BI1 = EMERGENCY SHUTDOWN - N.C. INPUT
= DIRTY FILTER - N.O. INPUT
BI2
= PROOF OF FLOW - N.O. INPUT
BI3
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
= REMOTE FORCED HEATING - N.O. INPUT
BI5
BI1 = HOOD ON - N.O. INPUT
= DIRTY FILTER - N.O. INPUT
BI2
= REMOTE FORCED COOLING - N.O. INPUT
BI6
= PROOF OF FLOW - N.O. INPUT
BI3
= HOOD ON - N.O. INPUT
BI7
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
= REMOTE FORCED HEATING - N.O. INPUT
BI5
= REMOTE FORCED COOLING - N.O. INPUT
BI6
NOTE:
= SMOKE DETECTOR - N.C. INPUT
BI7
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
AO1 = BUILDING PRESSURE CONTROL VFD OR
NOTE:
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
AO2
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
AO1 = BUILDING PRESSURE CONTROL VFD OR
AO3
= MODULATING COOLING/DIGITALSCROLL
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
AO2
= MODULATING HEATING SIGNAL
AO4
= RETURN AIR DAMPERACTUATOR
(0-10 VDC OR 2-10 VDC)
(0-10 VDC)
AO3
= MODULATING COOLING/DIGITALSCROLL
AO5
= RETURN AIR BYPASS DAMPERACTUATOR
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
AO4
= RETURN AIR DAMPERACTUATOR
GND
= GROUND FOR ANALOG OUTPUTS
(0-10 VDC)
GND
= GROUND FOR ANALOG OUTPUTS
AO5
= RETURN AIR BYPASS DAMPERACTUATOR
(0-10 VDC)
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
GND
= GROUND FOR ANALOG OUTPUTS
= INDOOR AIR RH SENSOR (0-5 VDC)
AI2
GND
= GROUND FOR ANALOG OUTPUTS
= ECONOMIZER FEEDBACK
I
A3
= BUILDING STATIC PRESSURE (0-5 VDC)
AI4
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
= GROUND FOR ANALOG INPUTS
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
AI2
= GROUND FOR ANALOG INPUTS
GND
= CO2 (0-10 VDC)
AI3
= BUILDING STATIC PRESSURE (0-5 VDC)
AI4
= GROUND FOR ANALOG INPUTS
GND
= GROUND FOR ANALOG INPUTS
GND
EXPANSION
www.orioncontrols.com
I2C
www.orioncontrols.com
AAON No.:
RELAY CONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY CONTACT RATING IS 1AMP MAX @ 24 VAC
WattMaster Label
#LB102034-01-A
EXPANSION
R69190
RELAY 1
RELAY 2
RELAY 1
RELAY 3
RELAY 2
RELAY 4
RELAY 3
RELAY
RELAY 4
COMMON
RELAY COMMON
Rev.: 1L
I2C
8.38
7.83
0.29
POLARITY
WARNING
OBSERVE
0.98
VCM
0.70
4.10
Figure 2: OE333-23-EM – VCM-X Expansion Module for RNE Dimensions
14
RNE Modular Controller Field Technical Guide
1.49
OVERVIEW
12-Relay & 4 Binary Input Expansion Module Dimensions
Figure 3: OE358-23-12R – 12-Relay Expansion Module Dimensions
Figure 4: OE356-01-BI – 4 Binary Input Expansion Module Dimensions
RNE Modular Controller Field Technical Guide
15
OVERVIEW
RNE Controller Component Locations
Modular Service Tool - Mini Din Connector
RS-485 Communications Loop Connection
Comm
RS-485 Communications Driver Chip
LED
Zone
Zone
PAL Chip
Relay Output Terminal Block
RAM Chip
E-BUS Connection
.
Auxiliary Voltage Out Terminal Block .
Signal Input Jumpers For Analog Inputs-Typ.
Analog Input
Terminal Block
Analog Output Terminal Block
EPROM Chip
Relay Output LED - Typ. of 5
Diagnostic Blink Code LEDs
Power LED
Address Switch
CPU
EEPROM
24 VAC Power Input
Static Pressure
(Modular Connector)
Expansion Module
(Modular Connector)
(Modular Connector)
Figure 5: OE332-23E-RNE – RNE Modular Controller Component Locations
16
RNE Modular Controller Field Technical Guide
Real Time
Clock Chip
Sensor
INSTALLATION AND WIRING
Important Wiring Considerations
General
Correct wiring of the RNE Modular Controller is the most important factor in the overall success of the controller installation process. In general, most RNE Controllers are factory installed and wired at the AAON®factory . It is also possible to purchase these controllers through your local AAON®/Orion representative for installation in the fi eld. Some of the following information pertains to fi eld wiring and may not apply to your installation since it was pre-wired at the factory. However , in the unlikely event that troubleshooting of the controller is required, it is a good idea to be familiar with the system wiring, no matter if it was factory or fi eld wired.
Controller Mounting
The RNE Controller is housed in a plastic enclosure. It is designed to be mounted by using the 3 mounting holes in the enclosure base. The RNE Controller needs to be installed in an environment which can maintain a temperature range between -30°F and 150°F not to exceed 90% RH levels (non-condensing). It is important to mount the controller in a location that is free from extreme high or low temperatures, moisture, dust, and dirt. Be careful not to damage the electronic components when mounting the controller. See Table 1 for a list of the required operating conditions for the RNE Controller and associated expansion modules.
Considerations
The RNE Controller and expansion modules must be connected to a 24 VAC power source of the proper size for the calculated VA load requirements. All transformer sizing should be based on the VA rating listed in Table 1.
Device
Control
OE332-23E-RNE
RNE Modular Controller
Voltage
24VAC 8
VA Load
Temperature
-30°F to 150°F
(Non-
Humidity
Condensing)
90% RH
WARNING: When using a single transformer to power more than one controller or expansion module, the correct polarity must always be maintained between the boards. Failure to observe correct polarity will result in damage to the RNE Controller and expansion modules.
Please carefully read and apply the following information when wiring the RNE Controller or the Expansion Modules. See Figure 6 on page
18 for the RNE Controller wiring diagram. See Figures 17 and 18 on pages 26 and 27 for Expansion Module Wiring.
1. All wiring is to be in accordance with local and national electrical codes and specifi cations.
2. Minimum wire size for 24 VAC wiring should be 18-gauge.
3. Minimum wire size for all sensors should be 24-gauge. Some sensors require 2-conductor wire and some require 3-or 4-conductor wire.
4. Be sure that all wiring connections are properly inserted and tightened into the terminal blocks. Do not allow wire strands to stick out and touch adjoining terminals which could potentially cause a short circuit.
5. When communication wiring is to be used to interconnect RNE Controllers together or to connect to other communication devices, all wiring must be plenum-rated, minimum 18-gauge, 2-conductor, twisted pair with shield. WattMaster can supply communication wire that meets this specifi cation and is color coded for the network or local loop. Please consult your WattMaster distributor for information. If desired, Belden #82760 or equivalent wire may also be used.
6. Before applying power to the RNE Controller, be sure to recheck all wiring connections and terminations thoroughly.
OE333-23-EM
VCM-X Expansion Module
OE358-23-12R
12 Relay Expansion
Module
OE356-01-BI
4 Binary Expansion
Module
24VAC 10
24VAC 15
24VAC 5
-30°F to 150°F
-30°F to 150°F
-30°F to 150°F
90% RH
90% RH
90% RH
Table 1: Voltage and Environment Requirements
RNE Modular Controller Field Technical Guide
17
INSTALLATION AND WIRING
RNE Controller Wiring
For Stand Alone Applications,
Connect To System Manager. For Network
Applications Connect To Next Controller And/Or
MiniLink PD On Local Loop.
Local Loop
RS-485
9600 Baud
All Comm Loop Wiring Is
T to T, R to R & SHLD to SHLD
Straight Thru
RNE Controller
Zone
Zone
Note:
All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only. 1 Amp Maximum Load.
R - 24VAC
G - Fan ON/OFF Only
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
See Individual
Component Wiring
Diagrams For Detailed
Wiring Of Analog Inputs
And Outputs
Jumpers
Splice If Required
OE271
Static Pressure
Transducer
Connect To Digital Room Sensor And/Or
Connect To Expansion Module(s) (When Used)
Digital CO Sensor
Relay Output Contacts R2 Through R5 May Be User­Configured For The Following:
1 - Heating Stages 2 - Cooling Stages 3 - Warm-up Mode Command (VAV Boxes) 4 - Reversing Valve (Air To Air Heat Pumps) 5 - Reheat Control (Dehumidification) 6 - Exhaust Fan Interlock 7 - Preheater For Low Ambient Protection 8 - Alarm 9 - Override 10 - Occupied 11 - OA Damper 12 - Heat Wheel 13 - Emergency Heat
Note: A Total Of 20 Relays Are Available By Adding Relay Expansion Modules. All Expansion Module Relay Outputs Are User Configurable As Listed Above.
GND
24VAC
Size Transformer For Correct Total Load. RNE Controller = 8 VA
2
Warning: 24 VAC Must Be Connected So That All Ground Wires Remain Common. Failure To Do So Will Result In Damage To The Controllers.
Line Voltage
Connect FRP Tubing To High Pressure Port (Bottom Tube) and Route To Static Pressure Pickup Probe Located In Unit Discharge. Leave Port Marked “Lo” Open To Atmosphere
Figure 6: OE332-23E-RNE – RNE Controller Wiring
18
RNE Modular Controller Field Technical Guide
INSTALLATION AND WIRING
Digital Room Sensor & Wall Mounted Space CO2 Sensor
Digital Room Sensor
The OE217-00 Digital Room Sensor is used to sense Space Tempera­ture and the OE217-01 Digital Room Sensor is used to sense Space Temperature and Space Humidity. The Sensor connects to the RNE Controller with the TSDRSC modular cable. It can be daisy-chained with the OE256-01 CO2 Sensor for applications requiring both a room CO2 sensor and room temperature sensor. It should be mounted at ap­proximately 5 Ft. above the fl oor on the wall in an area that does not have drafts or is exposed to direct sunlight. See Figure 7 for wiring details.
Note: When Only The Is Used, It
Connects Directly To The RNE Controller Using A Of The Appropriate Length. Allowed Is 160 Feet. See For Connection When The Space CO Sensor Is Also Used.
Digital Room Sensor
TSDRSC Cable
The Maximum Length
Figure 8
2
OVERRIDE ALARM
Display
Override
Wall Mounted Space CO2 Sensor
The OE256-01 Wall Mounted Space CO2 Sensor is used to monitor CO2 levels in the space served by the HVAC unit. The CO2 Sensor con­nects to the RNE Controller with the TSDRSC modular cable. It can be daisy-chained with the Digital Room Sensor (OE217) for applications requiring both a room CO2 sensor and room temperature sensor. It should be mounted at approximately 5 Ft. above the fl oor on the wall in an area that does not have drafts or is exposed to direct sunlight. See Figure 8
for wiring details and installation notes. A Duct Mounted can be used if desired instead of the Wall Mounted Space CO2 Sensor. See Figure 9 on page 20 for Duct Mounted CO2 Sensor wiring details.
I1 SET
AI1
AI2 SET AI3 SET
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
4-20mA
AI2
0-10V 0-5V
THERM 4-20mA
AI3
0-10V 0-5V
THERM
EMERGENCY SHUTDOWN
4-20mA
AI4
0-10V 0-5V
THERM 4-20mA
AI5
0-10V 0-5V
THERM 4-20mA
AI7
0-10V 0-5V
ANALOG INPUT JUMPER SETTINGS MUST BE SETAS SHOWN FOR PROPER OPERATION
STATIC
WattMaster Label
#LB102033-01
PRESSURE
RNE Controller
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
I2C
EXPANSION
I2C DIGITAL
SENSOR
CO
2
Sensor
Digital Room Sensor
Figure 7: OE217-00/01 – Digital Room Sensor Wiring
CO Sensor
2
Note: When a Digital Room Sensor Is
Used In Combination With The
The r Always
Sensor, CO Senso Connects To The RNE Controller First
2
Using a TSDRSC Cable Of The Length. The Digital Room Sensor Then Connects To The CO Sensor With Another Cable.
TSDRSC
2
At Least 5 Feet Above Floor. See The
C Sensor Technical GuideO
2
Wiring Details.
CO
2
Required
Mount Sensor(s)
For Further
Digital Room Sensor
OVERRIDE ALARM
Display
Override
I1 SET
AI1
AI2 SET AI3 SET
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
RNE Controller
TSDRSC Cable
4-20mA
AI2
0-10V 0-5V
THERM 4-20mA
AI3
0-10V 0-5V
THERM
EMERGENCY SHUTDOWN
4-20mA
AI4
0-10V 0-5V
THERM 4-20mA
AI5
0-10V 0-5V
THERM 4-20mA
AI7
0-10V 0-5V
ANALOG INPUTJUMPER SETTINGS MUSTBE SET AS SHOWN FOR PROPER OPERATION
STATIC
WattMaster Label
#LB102033-01
PRESSURE
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
I2C
EXPANSION
TSDRSC Cable
I2C DIGITAL
SENSOR
TSDRSC Cable
Figure 8: OE256-01 – Wall Mounted Space CO2 Sensor Wiring
RNE Modular Controller Field Technical Guide
19
OVERVIEW
Ducted Mounted CO2 Sensor
Zone
Zone
Duct Mounted CO2 Sensor
The OE256-02 CO2 Sensor is used for sensing the current CO2 level in the HVAC unit’s return air stream. This is useful when you want an average CO2 reading in the area served by the HVAC unit or when you don’t want a wall mounted CO2 sensor due to sensor tampering concerns in the space.
Note:
1.) The CO Sensor Always Connects To The RNE Controller
Using A TSDRSC Cable Of The Required Length. If Also Using A Digital Room Sensor, Connect The Digital Room Sensor To The C Sensor Using Another TSDRSC Cable Of The Required Length. The Total Length Of Cable For All Sensor Cables Combined Cannot Exceed 160 Feet.
Wall Mounted
Digital Room Sensor
OVERRIDE ALARM
Display
Override
2
O
2
TSDRSC Cable
Duct Mounted CO Sensor
2
The OE256-02 Duct Mounted Return Air CO the OE256-01 CO2 Sensor and the WattMaster Aspiration Box Assembly .
The Duct Mounted Return Air CO the return air duct of the HVAC unit and uses its integral aspiration box to sample the CO tion information in Figure 9 below for wiring and installation details.
level in the duct. See the dimensional and installa-
2
Sensor is designed to be mounted in
2
Sensor is comprised of
2
RNE Controller
RS-485 COMMUNICATION LOOP. WIRE “R” TO R”, T” TO“T” SHLD” TO SHLD”
RS-485 COMMUNICATION LOOP. WIRE “R” TO R”, T”TO “T” SHLD” TO SHLD”
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
OE332-23-VCMX-A VCM-X CONTROLLER
AI1 = SPC (SPACETEMPERATURE SENSOR)
AI1 = SPC (SPACETEMPERATURE SENSOR)
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
AI2
AI2
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
= RAT(RETURN AIR TEMPERATURE SENSOR)
AI3
AI3
= RAT(RETURN AIR TEMPERATURE SENSOR)
= OAT(OUTDOOR AIR TEMPERATURE SENSOR)
AI4
AI4
= OAT(OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
AI5
AI5
= SUCTION PRESSURE SENSOR
= SPACETEMPERATURE SENSOR SLIDE ADJUST
AI7
AI7
= SPACETEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESETSOURCE
OR VOLTAGE RESETSOURCE
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
E-BUS
CONNECTOR
ANALOG INPUT
ANALOG INPUT
JUMPER
JUMPER
SETTINGS
SETTINGS
THERM
LED NAME STATUS1 STATUS2
THERM
4-20mA
4-20mA
AI1
AI1
0-10V
NORMALOPERATION 0 1
0-10V
0-5V
0-5V
SAT FAIL 1 2
THERM
THERM
OAT FAIL 2 2
4-20mA
4-20mA
AI2
AI2
AI3
AI4
AI5
AI5
AI7
ANALOG INPUTJUMPER SETTINGS
ANALOG INPUTJUMPER SETTINGS
MUSTBE SET AS SHOWN FOR
MUSTBE SET AS SHOWN FOR
PROPER OPERATION
PROPER OPERATION
PRESSURE
PRESSURE
AI3
AI4
AI7
STATIC
STATIC
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
0-10V
0-10V
0-5V
0-5V
WattMaster Label
WattMaster Label
#LB102073-01-A
#LB102033-01
SPC FAIL 3 2
MODULEA LARM 4 2
MECH COOL FAIL 1 3
MECHHEAT FAIL 2 3
FAN PROOFFA IL 3 3
DIRTY FILTER 4 3
EMERGENCYSH UTDOWN 5 3
LOW SAT 1 4
HIGH SAT 2 4
CONT.TEMP COOL FAIL 3 4
CONT.TEMP HEAT FA IL 4 4
PUSH BUTTON OVR 1 5
ZONE OVR 2 5
OUTPUTFORCE ACTIVE 0 6
EXPANSION
EXPANSION
Rev.: 1A
RELAYCONTACT RATING IS 1AMP
RELAYCONTACT
MAX @ 24 VAC
RATING IS 1AMP MAX @ 24 VAC
RELAY COMMON
RELAY COMMON
FAN
FAN
RELAY2
RELAY2
RELAY3
RELAY3
RELAY4
RELAY4
RELAY5
RELAY5
AAON No.:
V07150
LED BLINK CODES
24 VAC POWER ONLY
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
OR THE CONTROLLER WILLBE DAMAGED
2
2
IC
IC
2
2
IC DIGITAL
IC DIGITAL
SENSOR
SENSOR
OBSERVE
POLARITY
WARNING
Connection Of Wall
Mounted
Digital Room Sensor
(When Used)
Figure 9: OE256-02 - Duct Mounted CO2 Sensor Wiring
20
RNE Modular Controller Field Technical Guide
TSDRSC Cable
INSTALLATION AND WIRING
Remote Supply Air
Temperature Reset Signal
(By Others)
0-5 VDC or 0-10 VDC Signal
GND
Note:
Either The Slide Offset Option For The Space Temperature Sensor Or The Remote Supply Air Temperature Reset Signal Option (By Others) May Be Connected To AI7 On The RNE Controller. Only One Option Is Allowed, Not Both.
AI7
GND
RNE Controller
AI1
AI1 SET
AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
AI2
AI3
AI4
AI5
AI7
Regardless of Whether the Remote
SAT Reset Signal Has Been
Configured For 0-5 or 0-10 VDC,
Jumper Must Be Set For 0-10V
AI7 SET
Remote SAT Reset Signal
Space Temperature Sensor
The OE210, OE211, OE212, OE213 Space Temperature Sensor is typi­cally used for constant volume HVAC unit applications controlling one zone. The Space T emperature Sensor is a 10K T ype III thermistor sensor and should be mounted approximately 5 feet above the fl oor in the space that is to be controlled. The Space Temperature Sensor is available as a sensor only, sensor with override button, sensor with slide adjust, and sensor with slide adjust and override confi gurations.
When the Remote Supply Air T emperature Reset Signal option is needed, the Slide Offset option on the Room Sensor cannot be used. Only one of these options may be used on the RNE Controller.
See Figure 10 below for complete Space Temperature Sensor wiring details.
Note:
Either The Slide Offset Option For The Space Temperature Sensor Or The Remote Supply Air Temperature Reset Signal Option (By Others) May Be Connected To An AI7 On The RNE Controller. Only One Option Is Allowed, Not Both.
AI1
Space Temperature Sensor
TMP
W
A R M
GND
E R C O O
OVR
L E R
AUX
Wire Required For Sensors With Slide Adjust Option Only
AI7
GND
Remote SAT Reset Signal
A Remote Supply Air T emperature Reset Signal can be connected to AI7 for applications requiring remote reset of the Supply Air Temperature Setpoint.
When the Slide Offset option on the Room Sensor is used, the Remote Supply Air Temperature Reset Signal cannot be used. Only one of these options may be used on the RNE Controller.
The RNE Controller can accept either a 0-5 VDC signal or a 0-10 VDC signal on this input.
See Figure 11 below for complete Remote SAT Reset Signal wiring details.
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Set Jumper For THERM
When Space Sensor Slide
Adjust Is Wired To AI7
AI7 SET
Figure 10: OE210, OE211, OE212, OE213 – Space Temperature Sensor Wiring
Figure 11: Remote Supply Air Temperature Reset Signal Wiring
RNE Controller
RNE Modular Controller Field Technical Guide
21
INSTALLATION AND WIRING
SAT & RAT Sensor Wiring
Zone
Zone
Supply Air & Return Air Temperature Sensor
The OE231 Supply Air & Return Air Temperature Sensors must be wired as shown in Figure 12 below for proper operation. The Supply Air & Return Air Temperature Sensors are 10K Type III thermistor sensors. The Supply Air Temperature Sensor should be mounted in the unit discharge plenum or in the supply air duct. The Return Air Tem­perature Sensor should be mounted in the return air duct. If the system has a Zoning Bypass Damper installed, be sure the return air sensor is located upstream of the bypass duct connection.
Note: The Supply Air Temperature Sensor Always Wires To The AI2 Input On The RNE Controller Unless Using The MODGAS II And/Or MHGRV II Controllers As Stand-Alone.
Supply Air Temperature Sensor
NOTE: If your AAON® HVAC unit is using the AAON®
MODGAS-X Controller and/or the AAON® MHGRV­X Controller, the Supply Air Temperature Sensor must always be connected to the RNE Controller unless you are using the AAON® MODGAS-X and/or AAON® MHGRV-X Controllers as stand-alone.
Mount In HVAC
Unit Supply
Air Duct
Return Air Temperature Sensor
Mount In HVAC
Unit Return
Air Duct
GND GND
AI2 AI3
RNE Controller
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Be Sure The Jumper Is Set For THERM
On AI2 & AI3 For Supply
& Return Air Temperature Sensors
When Used
Figure 12: OE230 / OE231 – Supply Air and Return Air Temperature Sensor Wiring
22
RNE Modular Controller Field Technical Guide
INSTALLATION AND WIRING
OAT Sensor Wiring
Outdoor Air Temperature Sensor
The OE250 Outdoor Air Temperature Sensor must be wired as shown in Figure 13 below for proper operation of the RNE Controller. The Outdoor Air Temperature Sensor is a 10K Type III thermistor sensor. The sensor should be mounted in the upright position as shown in an area that is protected from the elements and direct sunlight. Be sure to make the wiring splices inside of the Outdoor Air Temperature Sensor weather-tight enclosure.
Outdoor Air
Temperature Sensor
Make Splice Connections
Inside Sensor Enclosure
As Shown. Seal All Conduit
Fittings With Silicone
Sealant
CAUTION: Be sure to mount the Outdoor Air Temperature Sensor in an area that is not exposed to direct sunlight. The shaded area under the HVAC unit rain hood is normally a good location. Unused conduit opening(s) must have closure plugs installed and must be coated with sealing compound to provide a rain-tight seal. Water can damage the sensor.
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI4
GND
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Be Sure Jumper Is Set
For THERM
On AI4 For Outdoor
Air Temperature Sensor
Mount Sensor Outdoors
In Shaded Protected
Area & In Upright
Position As Shown
Figure 13: OE250 – Outdoor Air Temperature Sensor Wiring
RNE Controller
RNE Modular Controller Field Technical Guide
23
INSTALLATION AND WIRING
24 VAC Power Source
Sized For Actuator VA Load
24 VAC
GND
2-10 VDC
Output
RNE Controller
GND
AO1
AI1
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
AI2
AI3
AI4
AI5
AI7
Economizer Damper Actuator
(Belimo Actuator Shown)
Y1 3
+ 2
COM - 1
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturer Wiring
Instructions
Economizer Feedback 5
NOTE: For Economizer
Actuator Feedback Signal,
See Wiring For The
VCM-X Expansion Module.
AI3
Economizer Damper Actuator Wiring
Zone
Zone
Economizer Damper Actuator
The Economizer Damper Actuator signal voltage output is a 2-10 VDC output. This signal output is used by the RNE Controller to modulate the Economizer Damper Actuator in order to control the amount of Outdoor Air delivered to the HVAC unit for Free Cooling and/or Indoor Air Quality requirements. See Figure 14 for detailed wiring.
WARNING: It is very important to be certain that all wiring is correct as shown in the wiring diagram below. Failure to observe the correct polarity will result in damage to the actuator or RNE Controller.
Figure 14: Economizer Damper Actuator Wiring
24
RNE Modular Controller Field Technical Guide
INSTALLATION AND WIRING
+
_
3 (Y)
5 (U)
2 (+)
1 (-)
Supply Fan VFD Signal and Zoning Bypass Damper Actuator
Supply Fan VFD Signal or Zoning Bypass Damper Actuator Signal
The Supply Fan VFD or Zoning Bypass Damper Actuator Signal is a 0-10 VDC output. This signal output can be connected to the Supply Fan Variable Frequency Drive to modulate the Supply Fan speed and control Duct Static Pressure utilizing the Duct Static Pressure Sensor connected to the RNE Controller. Alternatively, it can be connected to a Zoning Bypass Damper Actuator that will modulate the Zoning Bypass Damper Actuator to control Duct Static Pressure utilizing the Duct Static Pressure Sensor connected to the RNE Controller. A Duct Static Pressure Sensor must be connected in order for the VFD or Zoning Bypass Damper Actuator to operate. See Figures 15 and 16 below for detailed wiring.
Caution:
The VFD Unit Must Be Configured For 0-10 VDC Input. The Input Resistance At The VFD Must Not Be Less Than 1000 Ohms When Measured At The VFD Terminals WithAll Input Wires Removed.
0-10VDC Input From AO2
GND Shield
Supply Fan Variable Frequency Drive
(By Others)
Note:
Wire To The VFD Using 18 GA Minimum 2 Conducter Twisted Pair With Shield Cable. Wire Shield To GND As Shown
CAUTION: Variable Frequency Drive units can cause large transient noise spikes which can cause interference to be propagated on other electronic equipment. Use shielded wire wherever possible and route all sensor and controller wiring away from the Variable Frequency Drive and the HVAC Unit electrical wiring.
AI1 SET
AI1
AI2 SET AI3 SET
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
AO2
GND
Shield
RNE Controller
Figure 15: Supply Fan VFD Wiring
24 VAC Power Source
Sized For Actuator VA Load
Bypass Damper Actuator
(Belimo Actuator Shown)
Figure 16: Zoning Bypass Damper Actuator Wiring
Belimo Actuator Wiring Shown.
Consult Factory For Other
Manufacturer Wiring Instructions.
GND
24 VAC
0-10 VDC
AO2 GND
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
RNE Controller
RNE Modular Controller Field Technical Guide
25
Zone
Y1 3
+ 2
COM - 1
Economizer Feedback 5
INSTALLATION AND WIRING
Zone
VCM-X Expansion Module Input Wiring for the RNE Controller
VCM-X Expansion Module for RNE
Three different Expansion Modules are available for use with the RNE Controller to provide additional inputs and outputs beyond those found on the RNE Controller.
The VCM-X Expansion Module ( OE333-23-EM) provides 8 Binary Inputs, 4 Analog Inputs, 4 Relay Outputs, and 5 Analog Outputs. See Figures 17 and 18 for complete wiring details.
+
LOW
See Economizer Actuator Wiring AO1 Controller
GND
0-5V
VIN
GND
24 VAC
+
+
-
For RNE
GND
EXC OUT COM
Emergency Shutdown - N.C. Contact Dirty Filter - N.O. Contact
Proof Of Flow - N.O. Contact Remote Forced Occupied - N.O. Contact Remote Forced Heating - N.O. Contact
Remote Forced Cooling - N.O. Contact
Hood On - N.O. Contact Remote Forced Dehumidification N.O. Contact
10 VA Minimum Power
Required For
VCM-X Expansion Module
Building Pressure
Plastic Tubing To Building Pressure Sensing Locations
Economizer Damper Actuator
(Belimo Actuator Shown)
Outdoor Air
Humidity Sensor
VAC OR DC
Indoor Air
Humidity Sensor
VOUT (0-5V)
Transducer
HIGH
The VCM-X Expansion Module can be used in conjunction with the 12-Relay Expansion Module (OE358-23-12R-A).
The 4 Binary Input Expansion Module (OE356-01-BI) can be used in place of the VCM-X Expansion Module if your system does not need any other inputs or outputs.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.
VCM-X Expansion Module
24 VAC POWER
POLARITY
WARNING
OBSERVE
PR OUT GND
B 1I B 2I B 3I B 4I B 5I B 6I B 7I BI8
AI1 AI2 AI3 AI4
GND GND
Modular Cable
Connect To Next Expansion
Board (When Used)
ITIS SUGGESTED THATYOU WRITE THE DESCRIPTION OF THE RELAYOUTPUTS YOUARE USING IN THE BOXES PROVIDEDABOVE WITHA PERMANENT MARKER (SHARPIE®)
JUMPER SETTINGS
24 VAC POWER ONLY
ONLY
WARNING!POLARITY MUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILL BE DAMAGED
MUST BE OBSERVED OR THE BOARD WILL BE DAMAGED
VCM-X Expansion Module
Orion No.:OE333-23-EM
OE333-23-EM-AVCM-X EXPANSION MODULE
PR OUT GND
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY1 = RELAY 3 =
RELAY2 = RELAY 4 =
RELAY1 = RELAY3 =
RELAY2 = RELAY4 =
ITIS SUGGESTED THATYOU WRITE THE DESCRIPTION OF THE RELAYOUTPUTS YOUARE USING IN THE BOXES PROVIDEDABOVE
ANALOG INPUT
WITHA PERMANENT MARKER (SHARPIE®)
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
ANALOG INPUT
PROPER
JUMPER
OPERATION
SETTINGS
THERM 4-20mA
ANALOG INPUT
AI1
0-10V
JUMPER
0-5V
SETTINGS
THERM
THERM
4-20mA
4-20mA
AI2
AI1
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
AI3
AI2
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
4-20mA
AI4
AI3
0-10V
0-10V
0-5V
0-5V
THERM 4-20mA
AI4
0-10V
I2C
0-5V
EXPANSION
I2C
WattMaster Label
EXPANSION
#LB102034-01
www.aaon.com
TO VCM-X INPUT TERMINALS AI5 & GND
TO VCM-X INPUT TERMINALS AI5 & GND
BI1 = EMERGENCY SHUTDOWN - N.C. INPUT
= DIRTY FILTER - N.O. INPUT
BI2
= PROOF OF FLOW - N.O. INPUT
BI3
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
= REMOTE FORCED HEATING - N.O. INPUT
BI5
BI1 = HOOD ON - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
BI6
= DIRTY FILTER - N.O. INPUT
BI2
= HOOD ON - N.O. INPUT
BI7
= PROOF OF FLOW - N.O. INPUT
BI3
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
= REMOTE FORCED HEATING - N.O. INPUT
BI5
NOTE:
= REMOTE FORCED COOLING - N.O. INPUT
BI6
ALL BINARYINPUTS MUST BE 24 VAC ONLY.
= SMOKE DETECTOR - N.C. INPUT
BI7
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
AO1 = BUILDING PRESSURE CONTROL VFD OR
NOTE:
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
ALL BINARYINPUTS MUST BE 24 VAC ONLY.
AO2
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
AO1 = BUILDING PRESSURE CONTROL VFD OR
AO3
= MODULATING COOLING/DIGITALSCROLL
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
AO2
= MODULATING HEATING SIGNAL
AO4
= RETURN AIR DAMPERACTUATOR
(0-10 VDC OR 2-10 VDC)
(0-10 VDC)
AO3
= MODULATING COOLING/DIGITALSCROLL
AO5
= RETURN AIR BYPASS DAMPERACTUATOR
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
AO4
= RETURN AIR DAMPERACTUATOR
GND
= GROUND FOR ANALOG OUTPUTS
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
GND
AO5
= RETURN AIR BYPASS DAMPERACTUATOR
(0-10 VDC)
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
GND
= GROUND FOR ANALOG OUTPUTS
AI2
= INDOOR AIR RH SENSOR (0-5 VDC)
GND
= GROUND FOR ANALOG OUTPUTS
A3
= ECONOMIZER FEEDBACK
I
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
GND
= GROUND FOR ANALOG INPUTS
= INDOOR AIR RH SENSOR (0-5 VDC)
AI2
GND
= GROUND FOR ANALOG INPUTS
= CO2 (0-10 VDC)
AI3
= BUILDING STATIC PRESSURE (0-5 VDC)
AI4
= GROUND FOR ANALOG INPUTS
GND
= GROUND FOR ANALOG INPUTS
GND
I2C
EXPANSION
www.orioncontrols.com
AAON No.:
www.orioncontrols.com
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
WattMaster Label
#LB102034-01-A
R69190
RELAY1
RELAY2
RELAY1
RELAY3
RELAY2
RELAY4
RELAY3
RELAY
RELAY4
COMMON
RELAY COMMON
Rev.: 1L
I2C
EXPANSION
VCM
Modular Cable
Connect To RNE
Controller
Figure 17: OE333-23-EM – VCM-X Expansion Module for RNE Input Wiring
26
RNE Modular Controller Field Technical Guide
INSTALLATION AND WIRING
VCM-X Expansion Module Output Wiring for the RNE Controller
The expansion modules can be used individually or together to provide the required inputs and outputs for your specifi c applications.
The VCM-X Expansion Module must be connected to 24 VAC as shown in the wiring diagram below. Please see Table 1 on page 17 for correct VA requirements to use when sizing the transformer(s) used for power ­ing the expansion module.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.
24 VAC
GND
10 VA Minimum
Power Required For
VCM-X Expansion
Module
VCM-X Expansion
Module
POLARITY
WARNING
OBSERVE
24 VAC POWER
24 VAC POWER ONLY
ONLY
WARNING!POLARITY MUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILL BE DAMAGED
MUST BE OBSERVED OR THE BOARD WILL BE DAMAGED
PR OUT GND
+V SIG GND
RELAY1 = RELAY3 =
RELAY2 = RELAY4 =
ITIS SUGGESTED THATYOU WRITE THE DESCRIPTION OF THE RELAYOUTPUTS YOUARE USING IN THE BOXES PROVIDEDABOVE WITHA PERMANENT MARKER (SHARPIE®)
JUMPER SETTINGS
www.aaon.com
VCM-X Expansion Module
Orion No.:OE333-23-EM
TO VCM-X INPUT
OE333-23-EM-AVCM-X EXPANSION MODULE
TERMINALS AI5 & GND
PR OUT
TO VCM-X INPUT
GND
TERMINALS AI5 & GND
SUCTION PRESSURE TRANSDUCER CONNECTION FOR HVAC UNITS WITHOUT DIGITALCOMPRESSOR
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY1 = RELAY 3 =
BI1 = EMERGENCY SHUTDOWN - N.C. INPUT BI2
RELAY2 = RELAY 4 =
BI3 BI4
ITIS SUGGESTED
BI5
BI1 = HOOD ON - N.O. INPUT
THATYOU WRITE THE DESCRIPTION OF THE RELAYOUTPUTS YOUARE USING IN THE BOXES PROVIDEDABOVE WITHA PERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
MUST BE SETAS
JUMPER SETTINGS
ANALOG INPUT
= DIRTY FILTER - N.O. INPUT
BI2
BI6
= PROOF OF FLOW - N.O. INPUT
BI3
BI7
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI8
= REMOTE FORCED HEATING - N.O. INPUT
BI5
= REMOTE FORCED COOLING - N.O. INPUT
BI6
NOTE:
BI7
= SMOKE DETECTOR - N.C. INPUT
ALL BINARY INPUTS MUSTBE 24 VAC ONLY.
BI8
= REMOTE DEHUMIDIFICATION - N.O. INPUT
SHOWN FOR
PROPER
ANALOG INPUT
NOTE:
AO1 = BUILDING PRESSURE CONTROL VFD OR
OPERATION
ALL BINARYINPUTS MUST BE 24 VAC ONLY.
MUST BE SETAS
AO2
SHOWN FOR
PROPER
JUMPER
AO1 = BUILDING PRESSURE CONTROL VFD OR
OPERATION
AO3
SETTINGS
AO2
THERM
AO4
ANALOG INPUT
4-20mA
AI1
JUMPER
0-10V
AO3
AO5
SETTINGS
0-5V
THERM
THERM
AO4
GND
4-20mA
4-20mA
AI1
AI2
0-10V
GND
0-10V
AO5
0-5V
0-5V
THERM
THERM
GND
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
4-20mA
4-20mA
AI2
AI3
GND
0-10V
AI2
0-10V
0-5V
0-5V
A3
I
THERM
AI4
THERM
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
4-20mA
4-20mA
GND
AI3
AI4
0-10V
AI2
= INDOOR AIR RH SENSOR (0-5 VDC)
0-10V
GND
0-5V
AI3
= CO2 (0-10 VDC)
0-5V
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
THERM 4-20mA
GND
AI4
0-10V
GND
I2C
0-5V
EXPANSION
Note:
All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only. 1 Amp Maximum Load.
I2C
EXPANSION
= DIRTY FILTER - N.O. INPUT = PROOF OF FLOW - N.O. INPUT = REMOTE FORCED OCCUPIED - N.O. INPUT = REMOTE FORCED HEATING - N.O. INPUT = REMOTE FORCED COOLING - N.O. INPUT = HOOD ON - N.O. INPUT = REMOTE DEHUMIDIFICATION - N.O. INPUT
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING/DIGITALSCROLL
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= MODULATING HEATING SIGNAL
= RETURN AIR DAMPERACTUATOR
(0-10 VDC OR 2-10 VDC)
(0-10 VDC)
= MODULATING COOLING/DIGITALSCROLL
= RETURN AIR BYPASS DAMPERACTUATOR
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
= RETURN AIR DAMPERACTUATOR
= GROUND FOR ANALOG OUTPUTS
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= RETURN AIR BYPASS DAMPERACTUATOR
(0-10 VDC) = GROUND FOR ANALOG OUTPUTS = GROUND FOR ANALOG OUTPUTS
= INDOOR AIR RH SENSOR (0-5 VDC) = ECONOMIZER FEEDBACK = BUILDING STATIC PRESSURE (0-5 VDC)
= GROUND FOR ANALOG INPUTS = GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS = GROUND FOR ANALOG INPUTS
I2C
EXPANSION
WattMaster Label
EXPANSION
#LB102034-01
www.orioncontrols.com
AAON No.:
R69190
www.orioncontrols.com
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAYCONTACT
RELAY1
RATING IS 1AMP MAX @ 24 VAC
RELAY2
RELAY1
RELAY3
RELAY2
RELAY4
RELAY3
RELAY COMMON
RELAY4
RELAY COMMON
WattMaster Label
#LB102034-01-A
Rev.: 1L
I2C
VCM
Also please note that when wiring the VCM-X Expansion Module, its contacts must be wired as wet contacts (connected to 24 VAC).
Relay Output Contacts R1 Through R4 May Be User-Configured For The Following:
1 - Heating Stages 2 - Cooling Stages 3 - Warm-up Mode Command (VAV Boxes) 4 - Reversing Valve (Heat Pumps) 5 - Reheat Control (Dehumidification) 6 - Exhaust Fan Interlock 7 - Preheater For Low Ambient Protection 8 - Alarm 9 - Override 10 - Occupied 11 - OA Damper 12 - Heat Wheel 13 - Emergency Heat
Note:
A Total Of 20 Relays Are Available By Adding Relay Expansion Modules. All Expansion Module Relay Outputs Are User Configurable As Listed Above.
R1
Configurable Relay Output #1
R2
Configurable Relay Output #2
R3
Configurable Relay Output #3
R4
Configurable Relay Output #4
A1O
AO2
AO3
AO4
AO5
Either A Building Pressure Damper Actuator Or a Building Pressure Relief Fan VFD Can Be Used,
-
Building Pressure Control
Damper Actuator
1 COM
2 +
3Y1
Building Pressure
Relief Fan VFD
+
COM
Modulating Heating
(0 to 10 VDC
Or 2 to 10 Input)
+
COM
Modulating Chilled Water Valve (0 To 10 Or 2 To 10 VDC Input)
+
COM
Return Air
Damper Actuator
(0-10 VDC)
1 COM
2 +
3Y1
Return Air Bypass
Damper Actuator
(0-10 VDC)
1 COM
2 +
3Y1
Belimo Actuator Wiring
Shown. Consult Factory
Modular Cable
Connect To Next Expansion
Board (When Used)
Notes:
1.) The Modulating Chilled Water Valve Used Must Be Capable Of Accepting Either A 0-10 VDC or 2-10 VDC Input. The Modulating Cooling Output Voltage Is User Configurable For These Voltages. The Modulating Heating Devices Used Must Be Capable of Accepting Either A 0-10 VDC or 2-10 VDC Input. The Modulating Heating Output Voltage Is User- Configurable For These Voltages. These Voltage Outputs Must Also Be Configured When You Are Setting Up The RNE Controller(s) Operating Parameters.
2.) Each Modulating Heating Or Cooling Device Used On The RNE Controller Must Have (1) Relay Output Configured For Each Device Used, In Order To Enable The Modulating Heating And/Or Cooling Device's Sequence. This Relay Output Must Be Configured When Setting Up The RNE Controller Operating Parameters.
Modular Cable
Connect To RNE
Controller
For Other Manufacturer
Wiring Instructions
Figure 18: OE333-23-EM – VCM-X Expansion Module for RNE Output Wiring
RNE Modular Controller Field Technical Guide
27
Loading...
+ 61 hidden pages