General Information ......................................................................................................................................... 3
Data Sharing ................................................................................................................................................................................3
Computer IP Address Set-up for Windows 98, NT, and XP ..........................................................................................................5
Connecting to The PT-Link ...........................................................................................................................................................7
Making Changes to the Confi guration File (confi g.csv) ................................................................................................................7
Upload Confi g.csv from the PT-Link .............................................................................................................................................7
Explicit and Implicit Addressing ....................................................................................................................................................8
Troubleshooting the PT-Link Controller .......................................................................................................... 9
Download Confi g.csv to the PT-Link ..........................................................................................................................................10
Using RUINET ............................................................................................................................................................................13
Data Arrays .................................................................................................................................................... 14
Table 2: VCM-X Modular Data Array for Field Server................................................................................................................14
Table 3: VCM-X WSHP (Tulsa) Data Array for Field Server ......................................................................................................14
Table 4: VCM-X WSHP (Coil) Data Array for Field Server ........................................................................................................15
Table 5: VCM-X Data Array for Field Server..............................................................................................................................15
Table 6: SA Controller Data Array for Field Server ....................................................................................................................16
Table 7: VCM Data Array For Field Server ................................................................................................................................16
Appendix A ..................................................................................................................................................... 17
Figure 23: RJ-45 8P8C Cable for WattMaster Cross Over Networking - WattMaster Part #HZ000136 ....................................17
Appendix B ..................................................................................................................................................... 18
Appendix C - VCM-X Modular and VCM-X WSHP LON Parameters ............................................................... 19
Appendix D - VCM-X LON Parameters ........................................................................................................... 21
Appendix E - SA Controller LON Parameters ................................................................................................ 27
Appendix F - VCM LON Parameters ............................................................................................................... 31
WattMaster Controls, Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
Form: OR-PTLNKLON-TGD-01M Copyright 2010 WattMaster Controls, Inc.
®
LON
and LONWorks® are registered trademarks of Eschelon Corporation.
WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.
This document is subject to change without notice.
PT-Link-LON® Technical Guide
PC
ROTO ESSOR
General Information
The OE368-23-LON, PT-Link-LON, provides bi-directional communication between ONE of the following types of Orion controllers—
VCM-X, SA, VCM, MUA II, or VAV/CAV:
NOTE: The PT-Link-LON device can be used to connect to only
one Orion controller. If more than one Orion controller is
present in a system, each one will require a PT -Link-LON
device for integration with a LON protocol network.
To determine what controller you have, you must look at the label located on the controller EPROM. If the controller label does not match
any of the SS or Y numbers listed above, your controller will not work
with the PT-Link-LON
®
.
Data Sharing
The PT-Link-LON interface provides the following data sharing capabilities:
• Provides values from points on the Orion side of the
gateway to LON® devices as if the values were
originating from LON® objects.
• Allows LON
®
devices to modify point values on the Orion controller side of the PT-Link-LON® by using
standard LON® write services.
Hardware Specifi cations
Table 1 contains the hardware specifi cations for the PT-Link-LON®
interface.
24 VAC
10 VA Maximum
10°F to 149°F
90% RH Non-Condensing
8 oz.
0.20 Dia.
Mounting Hole
Typ. 4 PL.
Mounting
Backplate
WattMaster
CONTROLS, INC
MADE IN THE USA
MM1
EEPROM
C4
U8
EEPROM Chip
U1
C2
EPROM
TRANSLATOR
MODULE
X2
C11
Diagnostic
LED #1
RN1
R2
R1
C21
C22
LED2
C7
U10
RN2
LED1
SF000103
PAL
PROTOCESSOR
TRANSLATORBOARD
YS101982
REV 2
LOOP
C8
WDOG
JP3
PWR
R17
Power
LED
Communications
LED
U4
U11
R12
C19
LON®Protocessor
Module
Service Pin Button
ROTO ESSOR
PC
C20
C9
®
LONWorks
Communications
Wiring Terminal
R4
C12
P1
11.0592
U9
C23
Diagnostic
LED #2
7.00"
7.50"
Figure 1: PT-Link-LON® Board Components and Dimensions
EPROM Chip
Pin 1 Indicator
RAM Chip
Pin 1 Indicator
RAM
U6
C10
C14
C17
SERIAL #
C1
X1
C6C5
LOCAL
R
SH
T
TB1
D3
R23
R9R3R8R6R7
+24VAC
U7
DRIVER
485
C13
TB3
GND
C18
U5
L1
D1
C16
U12
Local Loop
Communications
Wiring Terminal
Local Loop
Communications
Driver Chip
24 VAC Power
Terminals
0.25”
4.00”
4.50"
0.25”
PT-Link Interface3
PT-Link-LON® Technical Guide
Connection and Wiring Information
®
LON Connection
®
To LON Network
Caution: The LON Network
®
Communication Terminal Block
Must Be Disconnected Before
Connecting The Modular Service
Tool. After Programming The
Controller, Disconnect
The Service Tool and Then
Reconnect The Communication
Terminal Block.
Note: All Programming Of
Controllers Must Be Done Using
The Modular Service Tool. The
Modular System Manager Should
Not Be Used On A System That
Has A PT-Link Installed.
PT- Link-LON Interface
®
LON Connection
®
To LON Network
UP
Mode
Selection
CONFIGURATION
BALANCE-TEST
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
ON
PREV
DOWN
ESC
ENTER
13
2
708
DEC
NEXT
CLEAR
654
9
MINUS
-
Modular Service Tool
®
24 VAC
(10 VA)
Line Voltage
T
SHLD
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD
(G) To SHLD (G)&RToR
Controller
Wiring Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.
2.) All communication wiring to be 18 gauge minimum, 2 conductor twisted pair with
shield. Use Belden #82760 or equivalent.
Figure 2: PT-Link-LON® InterfaceWiring
24 VAC
(8 VA)
Line Voltage
4
PT-Link Interface
PT-Link-LON® Technical Guide
Ethernet Cable
Ethernet Cable
Ethernet Hub
Connect Ethernet Cable
To Ethernet Hub Port
Connect Ethernet
Cables To Ethernet
Hub Ports
PT-Link Lon Board
Desktop Or Laptop PC
1
2
3
4
Connect Ethernet Cable To
PT-Link Ethernet Port
MADEINTHE USA
WattMaster
CONTROLS,INC
PROTOCESSOR
REV2
YS101982
PWR
LOOP
LED1
SERIAL#
TRANSLATORBOARD
DRIVER
EEPROM
PAL
RAM
EPROM
T
SH
R
LED2
+24VAC
GND
LOCAL
WDOG
TRANSLATOR
MODULE
485
U9
P1
R2
R1
C23
C22
C21
C20
C9
C18
U10
C12
C11
C2
C10
C4
C7
C8
C1
C13
C6C5
C17
C19
C16
C14
D3
D1
JP3
L1
R9R3R8R6R7
R12
R17
R23
RN1
RN2
TB3
U8
U1
U7
U11
U12
X2
X1
TB1
MM1
U6
U4
R4
U5
11.0592
SF000103
PC
ROTO ESSORPCROTO ESSOR
PC
ROTO ESSOR
Confi guring the PT-Link Controller
PT-Link Hardware Connection
You have two options for connecting the PT-Link to your PC via Ethernet:
1.) You may connect the PT-Link directly to your PC by using
a crossover cable (by others) as shown. See Figure 3 for
details.
2.) You can also connect both your PC and the PT-Link to an
Ethernet Hub with standard CAT5 cables. See Figure 4
for details.
Connect Ethernet
Crossover Cable Directly
To PC Ethernet Card Port
PT-Link Lon Board
EEPROM
WattMaster
CONTROLS,INC
C4
U1
MADEINTHEUSA
C2
MM1
U8
TRANSLATOR
MODULE
ROTO ESSOR
R4
PC
X2
11.0592
C11
C12
U9
C23
C20
C9
P1
Connect Ethernet Crossover
Cable To PT-Link Ethernet Port
Figure 3: Connecting With Crossover Cable
Desktop Or Laptop PC
Ethernet Crossover Cable
EPROM
RAM
RN1
C7
U4
C8
SF000103
U6
C10
PAL
U10
C21
C22
R2
R1
LED2
L1
C14
PROTOCESSOR
TRANSLATORBOARD
YS101982
REV2
C16
WDOG
U11
C17
JP3
RN2
LED1
U12
R12
C19
PWR
LOOP
R17
SERIAL#
C1
X1
C6C5
LOCAL
R
SH
T
TB1
U7
U5
DRIVER
485
R9R3R8R6R7
C13
TB3
D1
GND
+24VAC
D3
R23
C18
Locate a CA T5 cable and plug one end into your computer’s Ethernet
port (use a crossover cable if connecting directly to the PT-Link).
If connecting directly, plug the other end of the Cable into the Ethernet
port on the PT -Link. If connecting through an Ethernet Hub, plug the
other end of the PC cable into the hub, and use a second CAT5 cable
to connect the PT-Link to the hub as well.
Power up the PT-Link by plugging in the power cable. The PT-Link
may take up to three minutes to power up completely. Once the PTLink is powered up, you should notice that the green “GPI05” LED
light on the ProtoCessor Board remains on continuously. See Figur e 19 on page 12 for a diagram showing the location of the ProtoCessor
“GPI05” LED.
Computer IP Address Set-up for
Windows 98, NT, and XP
In order for the PT -Link to communicate properly, it is imperative to
set the IP address of both the PT-Link as well as the computer to be
within the same netmask. You need to change the IP address on your
computer. The following instructions will explain how to confi gure
the IP address for Microsoft
NT and XP computers.
Computer IP Address Set-up for
Windows 98
1.) From the Windows START button select Start->
Setting->Control panel.
2.) Double click on the Network icon.
3.) In the Confi guration window, select the TCP/IP entry.
4.) Select Properties and go to the IP Address tab.
®
Windows 98 and Microsoft® Windows
PT-Link Interface
Figure 4: Connecting With Ethernet Cable & Hub
5.) Select Specify an IP address and then enter the
following information:
a.) IP Address 192.168.1.5
b.) Netmask 255.255.255.0
6.) Select OK until the network confi guration program exits.
7.) You might have to reboot the computer before the IP
address is valid.
5
PT-Link-LON® Technical Guide
Confi guring the PT-Link Controller
Computer IP Address Set-up for Windows
NT or XP
1.) Click<start>; then click<Control Panel>.
2.)
Double-click on the Network Connections icon.
The Network Connections Window will appear.
Figure 5: Network Connections Window
NOTE: If any wireless connections are listed, disable them
by
right-clicking the connection and selecting
<Disable>.
3.) In the Network Connections window, select the Local Area Connections entry. The Local Area Connection Status
Window will appear.
4.) Click <Properties> in the lower left of the window.
The Local Area Connection Properties window will appear.
Figure 7: Local Area Connection Properties Window
5). In the Connection Items list box, be sure the Internet
Protocol (TCP/IP) is checked. Select the Internet Protocol
(TCP/IP) item to highlight it and then
The Internet Protocol Properties window will appear.
click <Properties>.
Figure 6: Local Area Connection Status Window
6
Figure 8: Internet Protocol Properties Window
6).
Type in the following information:
a.) IP address 192.168.1.5
b.) Subnet mask 255.255.255.0
c.) Default Gateway is blank
7.)
Select <OK> until all of the above network confi guration
windows are closed. You may have to
before the new values are valid.
PT-Link Interface
reboot the computer
PT-Link-LON® Technical Guide
Confi guring the PT-Link Controller
Connecting To The PT-Link
In order to communicate and program the PT-Link you will need to
install RUINET software on your computer. If you do not have the
software, it is available for downloading at www.orioncontrols.com in
the software area of the web site. After installing the software, proceed
with the following instructions.
WARNING: Make sure to load RUINET onto your hard drive
and run the program from your hard drive. DO NOT under any
circumstances run RUINET from your cd drive.
If RUINET is in the desktop directory (if it isn’t, locate its directory),
double-click on RUINET , and the RUINET program should run. If you
have only one PT-Link connected to the network, then RUINET will
automatically connect to that particular PT -Link; otherwise, a menu will
appear to allow the selection of the desired PT-Link.
This menu will look similar to the one shown in Figure 9.
Note: If RUINET is unable to establish a connection, there
are a few simple procedures you can perform to try to
determine the problem. To verify your network cables,
observe the “Yellow” LED displayed below “Ethernet Connection” on the PT-Link’s ProtoCessor Module.
This LED should be on if the 10 BaseT cable is good.
Secondly, observe the “Green” LED below “Ethernet Connection”. This LED should be solid while RUINET
is running. If the LEDs are lit as expected, and RUINET
still does not receive replies, then the netmask is probably incorrect. If this does not help, then your Ethernet
setup on your PC is possibly not compatible. Ensure that
you have an Ethernet adapter installed in your software
confi guration and that it is confi gured to run the TCP/IP
protocol. If you are still unable to connect, please contact
WattMaster Controls, Inc.
Making Changes to the Confi guration
File (confi g.csv)
To make changes to the confi guration fi le on the PT-Link, use the pro-
cedures outlined that follow — Upload, Address, Poll, and Download
the Confi guration File.
Figure 9: RUINET PT-Link Selection Menu
Select the required PT-Link by typing the Number or Letter in the left
hand column. You should now have a menu that looks like Figure 10.
You are now ready to send and receive fi les to and from the PT-Link.
Upload Confi g.csv from the PT-Link
The PT-Link contains a confi guration fi le (confi g.csv) that includes
information such as addressing. This fi le can be uploaded from the
PT-Link for modifi cation if needed. The PT-Link also contains an
external interface fi le otherwise called an XIF fi le (fserver.xif). The
XIF fi le includes information such as SNVT names and LON network
information. This fi le can be uploaded for use with LON programming
software. When uploaded, these fi les can be located in the same directory
that the RUINET executable fi le is stored and run from. Be sure when
uploading that the correct fi le is specifi ed in the upload window. Refer
to Figures 11 & 12 for screen details. Refer to Appendix B for details
on uploading XIF fi les.
Figure 10: RUINET PT-Link Main Menu
PT-Link Interface
Figure 11: RUINET PT-Link Main Menu - Upload
7
PT-Link-LON® Technical Guide
Confi guring the PT-Link Controller
From the Main Menu, type “U”. The menu shown in Figure 12 will appear .
Figure 12: RUINET PT-Link Uploading Files
1.) Begin the upload by pressing “U.”
2.) When the upload is completed, open the uploaded fi le with
Microsoft® Notepad. This program is supplied with
Microsoft® Windows. Type “N” to open using Notepad.
Implicit Addressing Commissioning Using
LonMaker
1.) Ensure that the correct fi rmware and latest confi guration is loaded on the PT-Link-LON.
NOTE: Each change in the PT-Link-LON requires re-commis-
sioning of the PT-Link-LON in LonMaker.
2.) Ensure that the PT-Link-LON and the LonMaker machine
are on the same network.
3.) Open the existing Network in LonMaker or create a new
Network.
4.) Click on “Create New Network” and follow the network
wizard, making the following selections:
Network Interface: Choose Network Attached
Management Mode: Choose Onnet unless you are
working offl ineRegistered Plug-ins required: None
5.) Once Visio is open with the Network showing, drag a new
device onto the drawing from the toolbox.
WARNING: Only edit the confi g.sys fi le using Notepad. Do
not use Excel. Using Excel to edit the confi g.sys fi le will corrupt
its contents!
Explicit and Implicit Addressing
Clients can address the PT-Link using explicit or implicit addressing.
Clients using explicit addressing obtain their data transfer parameters
directly from the PT -Link-LON confi guration fi le (confi g.csv). Implicit
addressing is used when a Network Management T ool such as LonMaker®
is used to connect a PT-Link-LON to other LonWorks nodes—the
PT-Link-LON is assigned its data transfer (binding) parameters by the
Network Management Tool.
NOTE: The PT-Link-LON is confi gured from the factory to use
implicit addressing.
Implicit Addressing — Network Manager assigns addresses for
communication and ensures (via address tables in the devices) that
communication connections are known.
Explicit Addressing — Device knows the address of the point in
the remote device and communicates directly without the assistance of
the Network Manager.
6.) Follow the Device Network, making the following
selections:
Enter Device Name: Choose commission device
Specify Device Template: Choose upload from device
Specify Device Channel: Choose Auto Detect
Specify Device Properties: Leave as is (Ping is optional)
Identify Device: Choose service pin
Device Application Image: Leave unchecked
Initial State: Leave as is
7.) Press the service pin on the PT-Link-LON when asked to
do so, and the PT-Link-LON will be commissioned.
8.) Drag a new function block onto the drawing from the
toolbox. Give the function block a name and ensure that it
is allocated to the PT-Link-LON device.
9.) Once the function block is on the drawing, you can drag
input and output variables onto the function block. When
you do this, LonMaker will show you the variables
avail able for binding. Click on the variables you require
(or use the select “all” option), and they will be
commissioned onto the function block.
10.) You are now ready to connect these variables to other
devices by dragging connections from the toolbox and
connecting the variables.
8
PT-Link Interface
Troubleshooting the PT-Link Controller
Explicit Addressing & Domain Table Setup
To use explicit addressing, the client needs to change the factory settings
contained in the PT-Link-LON’s confi guration fi le (confi g.csv). The
following are the steps to change the confi guration fi le from implicit to
explicit addressing:
1.) Upload and open the confi g.csvfi le.
2.) Locate the “Connections” section.
3.) Locate the “Lonworks_Server” column and change the
value from “Implicit” shown in Figure 13 to “Explicit”
shown in Figure 14. You should also change the “Lonworks _Input” and “Lonworks_Outputs” from Update to
Polled.
Figure 13: PT-Link-LON Implicit Confi guration
PT-Link-LON® Technical Guide
Figure 14: PT-Link-LON Explicit Confi guration
In addition, the PT-Link-LON must have its domain, subnet, and node
IDs set. This feature is enabled in the confi guration fi le by fi lling out
the Title and System_Address fi elds of the PT-Link-LON parameters
as follows:
//==================================================
//
// Common Information
//
Bridge
System_Address ,Title
23 ,”:D48:S01:Wattmaster Explicit Lon v1.00d”
Figure 15: PT-Link-LON Domain and Subnet Setting
The Title fi eld must start with “:D”, followed by the domain_id in
hexadecimal notation, followed by “:S”, followed by the subnet_id in
hexadecimal notation, and enclosed by “:”. The domain length is automatically determined by the number of digits in the [domain_id] fi eld.
With 2 hexadecimal digits constituting 1 byte, “:D123456:”, for example,
would have a length of 3.
Once the domain table has been set, the “:Dxx:Sxx:” part of the Title
fi eld will be removed.
Now the Title fi eld will be left with [Title continued…] which may be
the Node self documentation string or any title.
After the changes are done, do not forget to save the fi le, download
the new confi guration fi le, and restart the PT-Link-LON. Refer to the
Download Section that follows.
PT-Link Interface
9
PT-Link-LON® Technical Guide
Troubleshooting the PT-Link Controller
Download Confi g.csv to the PT-Link
NOTE: Before attempting to send fi les to the PT -Link, make sure
that these fi les are in the same directory as the RUINET
utility being used for sending.
Figure 16: RUINET PT-Link Main Menu - Download
NOTE: The utility will indicate when downloading is complete.
DO NOT reset the PT-Link until this message is displayed, as this will corrupt the PT-Link.
2.) Once the download is complete, push <Esc> to get back to
the main menu and use the “!” option (or simply cycle
power to the PT-Link) to put the new fi le into operation.It is possible to do multiple downloads to the PT-Link
before resetting it.
NOTE: The Remote Filename option must always be named
“confi g.csv” for confi gurations; otherwise, they will be
ignored by the PT-Link.
From the Main Menu, type “D”. The menu shown in Figure 17 will appear .
Figure 17: RUINET PT-Link Downloading Files
1.) Begin the download by selecting “D.”
10
PT-Link Interface
PT-Link-LON® Technical Guide
Troubleshooting the PT-Link Controller
PT-Link Board LEDs
The PT -Link-LON® is equipped with LEDs that can be used for troubleshooting. There are four LEDs on the PT -Link board. See Figur e 18 for
the locations of the LEDs on the PT-Link board. The LED descriptions
and functions are listed in the following paragraphs.
PWR LED
When the PT -Link-LON® is powered up, the “PWR” LED should light
up and stay on continuously. If it does not light up, check to be sure
that you have 24 VAC connected to the board, that the wiring connections are tight, and that they are wired for correct polarity. The 24 VAC
power must be connected so that all ground wires remain common. If
after making all these checks the “PWR” LED still does not light up,
please contact WattMaster Controls Technical Support at our Toll Free
number—866-918-1100—for assistance.
LOOP LED
When power is applied to the PT-Link-LON
also light up. The LED should fl icker rapidly, indicating that the PT -Link
is trying to communicate with the controllers on the loop. A “fl icker”
is defi ned as a brief moment when the LED turns off and back on. If the
“LOOP” LED does not operate as indicated above, fi rst power down
the unit and then reapply power. If this does not work, please contact
W attMaster Controls Technical Support at our Toll Free number—866918-1100—for assistance.
®,
the “LOOP” LED will
PT-Link Base
Board
LED2
LED1
Figure 18: PT-Link-LON® LED Locations
PWR
LOOP
LED 1
When power is fi rst applied, “LED 1” will be off temporarily and then
will blink once if it is communicating with the controller. If the LED
is not blinking, there is a communication problem between the HVAC
controller and the PT-Link board. The “COMM” LED on the HVAC
controller also should be solid and will fl icker occasionally indicating
communication with the PT-Link-LON
not fl icker, then there is no communication between the PT Link and
the controller.
®
. If the “COMM” LED does
LED 2
When power is fi rst applied, “LED 2” will be off temporarily and then
will blink slowly indicating that the PT -Link baseboard is communicating
with the Protocessor Module. If “LED 2” does not blink, check that the
Protocessor Module is installed correctly in the PT-Link baseboard.
PT-Link Interface
11
PT-Link-LON® Technical Guide
Troubleshooting the PT-Link Controller
ProtoCessor Module LEDs
PWR LED
When the PT -Link is fi rst powered up, the “PWR” LED should light up
and stay on continuously. See Figure 19. If the LED doesn’t light up,
check that the ProtoCessor is installed correctly and fi rmly connected
to the Base Board.
Protocessor
GPI05 LED
The “GPI05” LED will light up when the Base Board and the ProtoCessor Module have established communications. This can take up to 3
minutes depending on the number of units connected to the PT -Link. If
it fails to light up after 3 minutes, check that the ProtoCessor is installed
correctly and fi rmly to the Base Board.
LON LED
When the unit is fi rst powered up, before commissioning has occurred,
this LED will be blinking to indicate the unit has not been commissioned yet. Once the unit is commissioned, the LED will stay off during
normal operations.
LON
GPI05
LA
TX
RX
PWR
LA LED
When the unit is fi rst powered up, this LED should be blinking constantly .
If this LED is constantly on or constantly off, the Module is not working
properly and needs to be replaced.
TX & RX LEDs
These LEDs work together to indicate that communication is being
established with the desired protocol network. If both LEDs are blinking, then communication is working properly. If both are not blinking,
check the protocol network wiring.
If all of these tests are made and the controller still doesn’t operate,
please contact WattMaster Controls Technical Support at our Toll Free
number—866-918-1100—for assistance.
LON
Figure 19: PT-Link-LON® LED Locations
12
PT-Link Interface
Troubleshooting the PT-Link Controller
Using RUINET
Before continuing with the troubleshooting, make sure the PT-Link is
connected correctly and the RUINET software is installed, running, and
functioning correctly.
Verifying Proper Communications
From the Main Screen, press “O” to go the Connection Overview
Screen. This screen supplies information on communication between the
PT-Link and remote devices. A number of aspect screens are available,
and some of the aspect screens have more than one page. Use the space
bar to toggle between aspects and use the <PgUp> and <PgDn> keys
to toggle between pages of the same aspect. The Connection Overview and Settings Aspect Screen is shown in Figure 20.
The main purpose in this screen is to verify that messages and characters
are being transmitted and received. In addition, it shows the number of
communication errors. If the PT-Link connection “03” is the protocol
connection, verify that is communicating appropriately. If it is not, check
that the PT -Link LEDs are working properly , the unit is wired correctly ,
and the PT-Link is confi gured correctly (Baud Rate, Unit Address &
MAC Address). If the number of errors is constantly increasing, move
to the Error Screen by pressing the <Space Bar> 3 times to fi nd out
the cause of the errors. Use the <PgUp> and <PgDn> keys to toggle
between pages of the Error Screen.
PT-Link-LON® Technical Guide
Figure 20: Connection Overview Screen
Verifying Proper Values
To verify that the correct values for each unit are being communicated
to the PT-Link, move to the Data Array Overview Screen. To get to
the screen, press “A” from the Main Menu. See Figure 21 for screen
details.
In the Data Array Overview Screen (Figure 21) you will be able to
see the data arrays of all the units connected to the PT -Link denoted by
an array name “DA_XXX_IY”—Y being the address of the unit minus
one. The Address of the unit is determined by a set of dip switches.
To view the values being communicated from a specifi c unit, move to
the Data Array Detail Screen (Figure 22) of the unit by entering the
number under which it is listed. For example, for the unit listed in the
third position, enter “03”.
To understand what each value means, look at the Data Array T ables for
the desired unit type, VA V/CAV, MUA II, or VCM. You can change the
writable values from this screen by using the modify command. T o use
the modify command press “M” from the Data Array Detail Screen
and then enter the Offset you want to change followed by a space and
the new value. Example: To change the Cooling Supply Setpoint to 60
in the VAV/CAV, press “M”, enter “58 60”, and then press <Enter>.
This could be useful to prove that the unit can take and keep the setpoints properly.
Use the standard EIA/TIA color code for "CROSS OVER CABLE" as shown.
It isthe same as a standard Cat 5 patch cabling. The outer cable jacket should
not
Be "Orange" in color. This isa straight thru pin 1 to pin 1 cable.
not
RJ-45 Connector as viewed
from the bottom side
White/Orange
1
Orange/White
2
White/Green
3
Blue/White
4
White/Blue
5
Green/White
6
Figure 23: RJ-45 8P8C Cable for WattMaster Cross Over Networking - WattMaster Part #HZ000136
PT-Link Interface
17
PT-Link-LON® Technical Guide
Appendix B
External Interface Files (XIF Files)
At start-up the PT-Link-LON creates an external interface fi le (XIF)
called fServer.xif based on the information contained in the PT-LinkLON’s confi guration fi le (confi g.csv). The PT-Link-LON’ s confi guration
can be changed by uploading and editing the confi g.csv fi le; therefore,
the XIF fi le must be obtained by uploading it from the PT-Link-LON.
The recommended procedure for obtaining the XIF fi le for the PT -Link-
LON is to upload it. Remember that this XIF fi le will change whenever
the confi guration fi le has been changed and downloaded and the PT-
Link-LON restarted. The following are the steps to extract the external
interface fi le (XIF) from the PT-Link-LON:
1.) Start RUINET application.
2.) Select Fieldserver option “1” (this step may be skipped
when application auto detects PT Link).
3.) In the Main Menu select “A” – Data Array Overview.
4.) You should see 2 array items that are labeled wattmstr dump and wattmstr-stats. Ignore these.
5.) You should see 2 additional arrays for the controller
connected.
Example: DA_C162_I0 and DA_C162_I0b.
6.) After connection has been verifi ed, you can now exit to the Main Menu using the escape key.
7.) Type “U” – Upload Confi guration.
8.) Type “O” to select other fi les.
9.) If prompted, press any key to continue.
10.) Type “R” – Remote Filename.
11.) Type “fserver.xif”
12. You should now see the name fserver.xif in the column to
the right.
13. Type “U” to upload the XIF fi le.
14. Once fi nished you will have an .xif fi le available in thesame directory as the RUINET executable fi le you were
running from.
WARNING: For easier confi guration, set the unit address to 1.
5.1.) The “b” at the end of the Data Array Name indicates
that it is a mirror array. You can ignore these.
5.2) Verify that your controller is visible or the XIF will not
be generated.
18
PT-Link Interface
PT-Link-LON® Technical Guide
Appendix C - VCM-X Modular and WSHP LON Parameters
NOTE: The following points for the VCM-X Modular and VCM-
X WSHP Controllers are additional points. All points and
property identifi ers in the VCM-X Controller table (pages
21-26) also apply to the VCM-X Modular and VCM-X
WSHP Controllers.
SNVT s f or the VCM-X Modular
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescriptionLimits
Modulating
Compressor 2
Head
Pressure 1
Head
Pressure 2
Condenser
Fan 1
Condenser
Fan 2
MdCmp2Analog
Output
HdPr1Analog
Output
HdPr2Analog
Output
CdFan1Analog
Output
CdFan2Analog
Output
Current position
of the 2nd Stage
of Compressor
Modulation.
Head Pressure for
1st Compressor
Head Pressure for
2nd Compressor
Condenser Fan 1
Signal Status
Condenser Fan 2
Signal Status
SNVT s f or the VCM-X WSHP (Tulsa)
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescription
Modulating
Compressor 2
Head Pressure 1HdPr1Analog
Head Pressure 2HdPr2Analog
Condenser Fan 1CdFan1Analog
Condenser Fan 2CdFan2Analog
Water Temp. AWaterTpAAnalog
Water Temp. BWaterTpBAnalog
MdCmp2Analog
Output
Output
Output
Output
Output
Output
Output
Current position of the
2nd Stage of Compressor
Modulation.
Head Pressure for
1st Compressor
Head Pressure for
2nd Compressor
Condenser Fan 1
Signal Status
Condenser Fan 2
Signal Status
Current water
temperature of refrigerant for
System A.
Current water
temperature of refrigerant for
System B.
SNVT s f or the VCM-X WSHP (Tulsa)
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescription
Compressor A1
Low Suction
Pressure Alarm
Compressor A1
Lockout Alarm
Compressor A2
Low Suction
Pressure Alarm
Compressor A2
Lockout Alarm
Compressor B1
Low Suction
Pressure Alarm
Compressor B1
Lockout Alarm
Compressor B2
Low Suction
Pressure Alarm
Compressor 4
Lockout Alarm
Low Water
Temperature 1
Alarm
Low Water
Temperature 2
Alarm
Proof of Water 1
Flow Alarm
Proof of Water 2
Flow Alarm
Module
Communications
Alarm
A1LSPAlmBinary
Output
A1LktAlmBinary
Output
A2LSPAlmBinary
Output
A2LktAlmBinary
Output
B1LSPAlmBinary
Output
B1LktAlmBinary
Output
B2LSPAlmBinary
Output
B2LktAlmBinary
Output
LWT1AlmBinary
Output
LWT2AlmBinary
Output
POWF1Alm Binary
Output
POWF2Alm Binary
Output
ComMAlmBinary
Output
Alarm that indicates
Suction Pressure for
Compressor A1 is below the
Low Suction Pressure Cooling
(Heating) Setpoint.
Alarm that indicates
Compressor A1 is locked out.
Alarm that indicates
Suction Pressure for
Compressor A2 is below the
Low Suction Pressure Cooling
(Heating) Setpoint.
Alarm that indicates
Compressor A2 is locked out.
Alarm that indicates
Suction Pressure for
Compressor B1 is below the
Low Suction Pressure Cooling
(Heating) Setpoint.
Alarm that indicates
Compressor B1 is locked out.
Alarm that indicates
Suction Pressure for
Compressor B2 is below the
Low Suction Pressure Cooling
(Heating) Setpoint.
Alarm that indicates
Compressor B2 is locked out.
Alarm that indicates water
temperature is below the
Leaving Water Safety Setpoint
(Heating only) for System A.
Alarm that indicates water
temperature is below the
Leaving Water Safety Setpoint
(Heating only) for System B
Alarm that indicates no Proof
of Water Flow for System A
(A1/A2)
Alarm that indicates no Proof
of Water Flow for System B
(B1/B2)
Alarm that indicates that one
or more Modules are not
communicating with the
VCM-X WSHP Controller.
PT-Link Interface
19
PT-Link-LON® Technical Guide
Appendix C - VCM-X Modular and WSHP LON Parameters
SNVT s f or the VCM-X WSHP (Coil)
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescription
Modulating
Compressor 2
Head Pressure 1HdPr1Analog
Head Pressure 2HdPr2Analog
Condenser
Fan 1
Condenser
Fan 2
Water Temp. AWaterTpAAnalog
Compressor A
Low Suction
Pressure Alarm
Compressor A
Lockout Alarm
Compressor B
Low Suction
Pressure Alarm
Compressor B
Lockout Alarm
Low Water
Temperature
Alarm
Proof of Water
Flow Alarm
Module
Communica-
tions
Alarm
MdCmp2Analog
Output
Output
Output
CdFan1Analog
Output
CdFan2Analog
Output
Output
A1LSPAlmBinary
Output
A1LktAlmBinary
Output
B1LSPAlmBinary
Output
B1LktAlmBinary
Output
LWT1AlmBinary
Output
POWF1AlmBinary
Output
ComMAlmBinary
Output
Current position of the
2nd Stage of Compressor
Modulation.
Head Pressure for
1st Compressor
Head Pressure for
2nd Compressor
Condenser Fan 1
Signal Status
Condenser Fan 2
Signal Status
Current water
temperature.
Alarm that indicates
Suction Pressure for Circuit A
is below the Low
Suction Pressure Cooling
(Heating) Setpoint.
Alarm that indicates Circuit A
Compressors are locked out.
Alarm that indicates
Suction Pressure for Circuit B
is below the Low
Suction Pressure Cooling
(Heating) Setpoint.
Alarm that indicates Circuit B
Compressors are locked out.
Alarm that indicates water tem-
perature is below the Leaving
Water Safety
Setpoint (Heating only).
Alarm that indicates no
Proof of Water Flow.
Alarm that indicates that one
or more Modules are not com-
municating with the VCM-X
WSHP Controller.
20
PT-Link Interface
PT-Link-LON® Technical Guide
Appendix D - VCM-X LON Parameters
SNVT s f or the VCM-X Controller
Binary Output SNVTs are SNVT_lev_disc utput
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescription
Alarm
Status
Control
Status
Occupied/
Mode
Enable
Cooling
Setpoint
Mirror
Control
Temperature
Duct Static
Pressure
Economizer
Position
Occupied/
Mode
Enable
Heating
Setpoint
Mirror
Modulating
Gas Valve
Position
On Board
Relays
Outdoor Air
Dewpoint
Outdoor Air
Humidity
Outdoor Air
Temperature
Outdoor Air
Wetbulb
Reheat
Value
Position
Relief
Pressure
Return Air
Temperature
AlrmStsAnalog
CtrlStsAnalog
ClStAnalog
CtrlTpAnalog
DuctPrAnalog
EcoPosAnalog
HtStAnalog
MdHt-
2Pos
OnRlysAnalog
OaDwptAnalog
OaRhAnalog
OaTpAnalog
OaWtblAnalog
Rt2PosAnalog
RfPrAnalog
RaTpAnalog
Output
Output
Output
Output
Output
Output
Output
Analog
Output
Output
Output
Output
Output
Output
Output
Output
Output
Needed only in
legacy application.
Current operational
status.
Occupied/ Mode
Enable Cooling
Setpoint Mirror.
Current value of the
control temperature
sensor.
Current value of the
duct static pressure
sensor.
Current position
of the economizer
damper.
Occupied/ Mode
Enable Heating
Setpoint
Mirror.
Current position
of MODGAS II
modulating gas
valve control.
Needed only in
legacy application.
Current calculated
outdoor air
dewpoint added on
version 1.09.
Current value of the
outdoor humidity
sensor.
Current value of the
outdoor tempera-
ture sensor.
Current calculated
value of the out-
door wetbulb
temperature.
Current position of
MHGRV modulat-
ing hot gas reheat
valve control.
Current value of the
building pressure
sensor.
Current value of the
return temperature
sensor.
Limits
SNVT s f or the VCM-X Controller
Binary Output SNVTs are SNVT_lev_disc utput
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescription
Indoor
Humidity
Space
Temperature
Current
Supply Air
Setpoint
Supply Air
Temperature
Temperature
Demand
VFD
Blower Fan
VFD
Relief Fan
Application
Software
Version
Alarm
Group 1
Alarm
Group 2
Alarm
Group 3
Dewpoint
Setpoint
Mirror
External
Relays 1-2
External
Relays 3-4
Indoor Rh
Setpoint
Mirror
Modulating
Cool
Position
InRhAnalog
SpcTpAnalog
SaTpStMAnalog
SaTpAnalog
TpDmndAnalog
VfdBw-
Pos
VfdExPosAnalog
AppVerAnalog
AlrmGrp1Analog
AlrmGrp2Analog
AlrmGrp3 Analog
DptStMAnalog
ExRlys12Analog
ExRlys34Analog
InRhStMAnalog
MdClPosAnalog
Output
Output
Output
Output
Output
Analog
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Current value of
the indoor humidity
sensor.
Current value of the
space temperature
sensor.
Current SAT
Cooling or Heating
setpoint if there
is no reset source;
Current calculated
SAT setpoint with
Reset Source.
Current value of the
supply air
temperature sensor.
Based on the
comparison
between the
current Control
Temperature and
the Heating or
Cooling Setpoint
Temperatures. Does
not work for supply
air control
Current position of
the VFD blower fan
signal.
Current position of
the VFD relief
fan signal.
Current version of
the software in the
unit.
Needed only in
legacy application.
Needed only in
legacy application.
Needed only in
legacy application.
Mirror of the DPtSt
“read only.”
Needed only in
legacy application.
Needed only in
legacy application.
Mirror of the
InRhSt “read only.”
Current position of
the modulating
cooling signal
(Chilled water or
digital compressor).
Limits
PT-Link Interface
21
PT-Link-LON® Technical Guide
Appendix D - VCM-X LON Parameters
SNVT s f or the VCM-X Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescription
Modulating
Heat
Position
Unit ModeUnitModeAnalog
Return Air
Level
CO
2
Bypass
Damper
Position
Return
Damper
Position
Coil
Temperature
Outdoor Air
CFM
Exhaust
CFM
Supply Air
CFM
Current
Calculated
OA CFM
setpoint
Dewpoint
Setpoint
Occupied/
Mode
Enable
Cooling
Setpoint
MdHtPosAnalog
CO2LevelAnalog
ByPas-
Dmp
RaDmpAnalog
CoilTpAnalog
OaCFMAnalog
EtCFMAnalog
SaCFMAnalog
OACfm-
StM
DptStAnalog
OcpClStAnalog
Output
Output
Output
Analog
Output
Output
Output
Output
Output4
Output
Analog
Output
Input
Input
Current position of
the modulating
heating signal (hot
water or SCR heat).
Needed only in
legacy application.
Current value of the
CO2 sensor.
Current position of
the bypass damper
signal.
Current position of
the return damper
signal.
Current coil
temperature reading
added on version
1.09.
Current Outdoor
Airfl ow
Measurement
Current Exhaust
Airfl ow
Measurement
Current Supply
Airfl ow
Measurement
Current calculated
Outdoor Air CFM
based on CO
If the outdoor
dewpoint rises
above this setpoint,
the unit will
Dehumidifi cation
If the control tem-
perature rises one
degree above this
setpoint, the control
will activate the
cooling demand.
If the control
temperature is the
Supply Air Sensor,
then the cooling
demand is always
level.
2
activate the
Demand.
active.
Limits
3580
099
SNVT s f or the VCM-X Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescription
Occupied/
Mode
Enable
Heating
Setpoint
Outdoor
Air Sensor
Offset
Return
Air Sensor
Offset
Schedule
Force
Space
Sensor
Offset
SAT/Reset
Source
Cooling
Setpoint
SAT/Reset
Source
Heating
Setpoint
Supply
Air Sensor
Offset
OcpHtStAnalog
Input
OaTpOstAnalog
Input
RaTpOstAnalog
Input
SchdFrcAnalog
Input
SpcTpOstAnalog
Input
SaClStAnalog
Input
SaHtStAnalog
Input
SaTpOstAnalog
Input
If the control
temperature drops
one degree below
this setpoint,
the control will
activate the heating
demand. If the
control
temperature
is the Supply
Air Sensor, then
there is no heating
demand.
If the Outdoor
Temperature Sensor
is reading
incorrectly, you can
use this option to
enter an offset
temperature to
adjust the Sensor’s
Temperature.
If the Return Tem-
perature Sensor is
reading incorrectly,
you can use this
option to enter an
offset temperature
to adjust the Sen-
sor’s T emperature.
0 = Auto/
Unoccupied Mode
1 = Forced On
2 = Forced Off
If the Space
Temperature
Sensor is reading
incorrectly, you can
use this option to
enter an offset
temperature to
adjust the Sensor’s
Temperature.
Supply Air setpoint
or Reset Source
target temperature
in Cooling Mode.
Supply Air setpoint
or Reset Source
target temperature
in Heating Mode.
If the Supply Air
Temperature Sensor
is reading incor-
rectly, you can use
this option to enter
an offset
temperature to
adjust the Sensor’s
Temperature.
Limits
99
-100100
-100100
02
-100100
4080
40200
-100100
22
PT-Link Interface
PT-Link-LON® Technical Guide
Appendix D - VCM-X LON Parameters
SNVT s f or the VCM-X Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescription
Warm Up
Setpoint
Wet Bulb
Setpoint
Coil
Temperature
Setpoint
Relief
Pressure
Setpoint
Indoor
Humidity
Setpoint
Unoccupied
Cooling
Offset
WmupStAnalog
Input
WtblStAnalog
Input
CoilTpStAnalog
Input
RfPrStAnalog
Input
InRhStAnalog
Input
UnClOstAnalog
Input
In a VAV
application, upon
entering the
occupied mode,
the Warm-up
Demand will be
activated if the
return air tem-
perature falls one
degree below this
setpoint.
The economizer is
enabled if the
outdoor tempera-
ture or wetbulb
falls below this
setpoint.
This is the coil
suction temperature target during
dehumidifi cation
mode. Produces
dewpoint in the
supply air
approximately
10°F above this
setpoint.
This is the target
building pressure
to be maintained
by the VFD Relief
signal.
If the indoor
humidity rises
above this set-
point, the unit will
activate the
Dehumidifi cation
Demand.
During the
Unoccupied Mode
of Operation, this
Setpoint spreads
the Occupied
Cooling Setpoint
out by a user
adjustable amount.
If you do not want
Cooling to operate
during the
Unoccupied
Mode, use the
default setting
of 30°F for these
setpoints.
Limits
080
3570
-0.20.2
0100
030
SNVT s f or the VCM-X Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescription
Unoccupied
Heating
Offset
CO
Setpoint
Minimum
Outside Air
Setpoint
Static
Pressure
Setpoint
Preheater
Setpoint
Outdoor
Air CFM
Setpoint
Outdoor Air
CFM Reset
Limit
UnHtOstAnalog
CO2StAnalog
2
MinEcoStAnalog
DuctPrStAnalog
PreHtSpAnalog
OACfmStAnalog
OACfmRsAnalog
Input
Input
Input
Input
Input
Input
Input
During the
Unoccupied Mode
of Operation, this
Setpoint spreads
the Occupied
Heating Setpoint
out by a user
adjustable amount.
If you do not want
Heating to operate
during the Unoccupied Mode, use
the default setting
of 30°F for these
setpoints.
When the CO2
level rises above
the CO2 Protection
Limit Max Level,
the Economizer’s
Minimum Position
will begin to reset
open proportion-
ally between the
CO
Protection
2
Limit Max Level
Setpoint and the
Reset Range
Setpoint.
This is the
minimum position
of the economizer
in the occupied
modes.
This is the target
duct pressure to
be maintained by
the VFD blower
signal.
Low Outside Air
Ambient
Protection Set-
point
Minimum desired
Outdoor Air CFM.
Maximum desired
Outdoor Air CFM
when CO
reaches
2
its reset limit.
Limits
030
03000
1100
0.013
0100
0.10 K 200 K
0.10 K 200 K
PT-Link Interface
23
PT-Link-LON® Technical Guide
Appendix D - VCM-X LON Parameters
SNVT s f or the VCM-X Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescriptionLimits
Bad Supply
Air Sensor
CO
Sensor
2
Installed
Cooling
Enabled
Economizer
Enabled
Fan Start Up
Delay
Fan
Proving
Alarm
Heating
Enabled
High
Supply Air
Temperature
Alarm
Low Supply
Air
Temperature
Alarm
MODGAS
II
Connected
Proof of
Flow
Confi gured
REHEAT II
Connected
SaTpAlmBinary
Output
CO2CfgBinary
Output
ClEnbl Binary
Output
EcoEnblBinary
Output
FanDly Binary
Output
PofAlmBinary
Output
HtEnbl Binary
Output
HiSaAlm Binary
Output
LoSaAlmBinary
Output
MdHt2InsBinary
Output
PofCfgBinary
Output
Rt2InsBinary
Output
Alarm that
indicates a failure
in the
supply air sensor.
Status that
indicates the CO2
function has been
confi gured.
Status that indicates
mechanical cooling
is enabled.
Status that indicates
the economizer is
enabled.
Status that indicates
the fan is
commanded to run,
but it is in the start
up delay mode.
Alarm that
indicates a failure
in the fl ow of the
VFD blower.
Status that
indicates that
mechanical heating
is enabled.
The Supply Air
has risen above
the Hi SAT Cutoff
Setpoint. Heating
stages begin to deac-
tivate and the fan
continues to run.
The Supply Air has
fallen below the Hi
SAT Cutoff Setpoint
and cooling stages
will begin to deactivate. If the unit is in
Economizer, Vent,
or Heating Mode
the Supply Fan will
shut off.
Status that indicates
the MODGAS II
controller is
connected.
Status that indicates
the proof of fl ow
function has been
confi gured.
Status that indicates
the MHGRV
controllers is
connected to the
system.
SNVT s f or the VCM-X Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescriptionLimits
Mechanical
Cooling
Alarm
Mechanical
Heating
Alarm
Dirty Filter
Detected
Control
Temperature
Cool Failure
Control
Temperature
Heat Failure
Outdoor Air
Temperature
Lost
Smoke
Detected
Alarm
Space
Temperature
Sensor Lost
MchClAlmBinary
Output
MchHtAlmBinary
Output
DrtFlAlmBinary
Output
CtrlTpCFBinary
Output
CtrlTpHFBinary
Output
OaTpAlmBinary
Output
SmokeAlmBinary
Output
SpcTpAlmBinary
Output
Compressor Relays
are enabled but
the Supply Air
Temperature has
not fallen 5°F w/in
a user-adjustable
time period. This
does not indicate
compressors are
active and will not
shut the unit down.
Heating Mode has
been initiated but
the Supply Air
Temperature has
not risen 5°F w/in
a user-adjustable
time period. This
does not indicate
heat stages are
active and will not
shut the unit down.
Alarm that indicates
the fi lters are dirty.
This alarm is
activated if the
control temperature
does not get within
5°F to the occupied
cooling setpoint
in an hour in the
cooling mode. This
alarm is not used
in 100% outside air
units or supply air
control.
This alarm is
activated if the
control temperature
does not get within
5°F to the occupied
heating setpoint
in an hour in the
heating mode. This
alarm is not used
in 100% outside air
units or supply air
control.
Alarm that
indicates a failure
in the outdoor air
temperature.
Alarm that indicates
the Smoke sensor
has been activated.
Alarm that indicates
a failure in the
space temperature
sensor.
24
PT-Link Interface
PT-Link-LON® Technical Guide
Appendix D - VCM-X LON Parameters
SNVT s f or the VCM-X Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
ParameterNameObjectDescriptionLimits
On Board
Relay 1
On Board
Relay 2
On Board
Relay 3
On Board
Relay 4
On Board
Relay 5
Expansion
Relay 1
Expansion
Relay 2
Expansion
Relay 3
Expansion
Relay 4
Expansion
Relay 5
Expansion
Relay 6
Expansion
Relay 7
Expansion
Relay 8
Expansion
Relay 9
Expansion
Relay 10
Expansion
Relay 11
Expansion
Relay 12
Expansion
Relay 13
Expansion
Relay 14
Expansion
Relay 15
Expansion
Relay 16
OnRly1Binary
Output
OnRly2Binary
Output
OnRly3Binary
Output
OnRly4Binary
Output
OnRly5Binary
Output
ExRly1Binary
Output
ExRly2Binary
Output
ExRly3Binary
Output
ExRly4Binary
Output
ExRly5Binary
Output
ExRly6Binary
Output
ExRly7Binary
Output
ExRly8Binary
Output
ExRly9Binary
Output
ExRly10Binary
Output
ExRly11Binary
Output
ExRly12Binary
Output
ExRly13Binary
Output
ExRly14Binary
Output
ExRly15Binary
Output
ExRly16Binary
Output
Current status of
relay 1.
Current status of
relay 2.
Current status of
relay 3.
Current status of
relay 4.
Current status of
relay 5.
Current status of
relay 6.
Current status of
relay 7.
Current status of
relay 8.
Current status of
relay 9.
Current status of
relay 10.
Current status of
relay 11.
Current status of
relay 12.
Current status of
relay 13.
Current status of
relay 14.
Current status of
relay 15.
Current status of
relay 16.
Current status of
relay 17.
Current status of
relay 18.
Current status of
relay 19.
Current status of
relay 20.
Current status of
relay 21.
VCM-X PT-Link-LON®
Property Identifi er:
The PT -Link-LON® Link amends the following property identity to the
LON® property identifi er.