OMRON V1000 User Manual

Manual No. I67E-EN-01
EnglishDeutschEspañolFrançaisItaliano
V1000
Compact Current Vector Inverter Model: VZA 200V Class Single-phase 0.12 to 4.0/5.5 kW 200V Class 3-phase 0.12 to 15/18.5 kW 400V Class 3-phase 0.2 to 15/18.5 kW
QUICK START GUIDE
Pyccкий
V1000
Quick Start Guide
1 Safety Instructions and General Warnings . . . . . . . . . . 2
2 Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Keypad Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5 Start Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6 Parameter Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
ENGLISH
ENGLISH
I67E-EN V1000 Quick Start Guide 1

1 Safety Instructions and General Warnings

1 Safety Instructions and General Warnings
Omron Yaskawa Motion Control B.V. (OYMC) supplies component parts for use in a wide variety of industrial applications. The selection and application of OYMC products remain the responsibility of the equipment designer or end user. OYMC accepts no responsibility for the way its products are incorporated into the final system design. Under no circum­stances should any OYMC product be incorporated into any product or design as the exclu­sive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All products designed to incorporate a component part manufactured by OYMC must be supplied to the end user with appropriate warnings and instructions as to the safe use and operation of that part. Any warnings pro­vided by OYMC must be promptly provided to the end user. OYMC offers an express war­ranty only as to the quality of its products in conforming to standards and specifications published in the manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. OYMC assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.

General Warnings

WARNING
• Read and understand this manual before installing, operating or servicing this drive.
• All warnings, cautions, and instructions must be followed.
• All work must be performed by qualified personnel.
• The drive must be installed according to this manual and local codes.
• Heed the safety messages in this manual.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual.
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
The following conventions are used to indicate Safety messages in this manual:
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates a property damage message.
2 I67E-EN V1000 Quick Start Guide

Safety Warnings

1 Safety Instructions and General Warnings
WARNING
Electrical Shock Hazard
• Do not attempt to modify or alter the drive in any way not explained in this manual.
Failure to comply could result in death or serious injury. OYMC is not responsible for any modification of the product made by the user. This product
must not be modified.
• Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains
charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level.
• Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury. Maintenance, inspection, and replacement of parts must be performed only by authorized
personnel familiar with installation, adjustment, and maintenance of AC drives.
• Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
• Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
• Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye
protection before beginning work on the drive.
• Never short the output circuits of the drive.
Do not short the output circuits of the drive. Failure to comply could result in death or serious injury.
Sudden Movement Hazard
• Stay clear of the motor during rotational Auto-Tuning. The motor may start operating suddenly.
During automatic starting of equipment, the machine may start moving suddenly, which could result in death or serious injury.
ENGLISH
I67E-EN V1000 Quick Start Guide 3
1 Safety Instructions and General Warnings
WARNING
• System may start unexpectedly upon application of power, resulting in death or serious injury.
Clear all personnel from the drive, motor, and machine area before applying power. Secure covers, couplings, shaft keys, and machine loads before applying power to the drive.
Fire Hazard
• Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply
before applying power.
• Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire. Attach the drive to metal or other noncombustible material.
• Do not connect AC line power to output terminals U, V, and W.
• Make sure that the power supply lines are connected to main circuit input terminals R/ L1, S/L2, T/L3 (or R/L1 and S/L2 for single-phase power).
Do not connect the AC power line to the output motor terminals of the drive. Failure to comply could result in death or serious injury by fire as a result of drive damage from line voltage application to output terminals.
• Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
CAUTION
Crush Hazard
• Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
Burn Hazard
• Do not touch the heatsink or braking resistor hardware until a powered-down cooling period has elapsed.
4 I67E-EN V1000 Quick Start Guide
1 Safety Instructions and General Warnings
NOTICE
Equipment Hazard
• Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
• Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
• Do not perform a withstand voltage test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
• Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment. Do not connect or operate any equipment with visible damage or missing parts.
• Install adequate branch circuit short circuit protection per applicable codes.
Failure to comply could result in damage to the drive. The drive is suitable for circuits capable of delivering not more than 100,000 RMS symmetrical
Amperes, 240 Vac maximum (200 V Class) and 480 Vac maximum (400V Class).
• Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
• Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive or braking circuit. Carefully review the braking option instruction manual when connecting a braking option to the
drive.
• Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty. OYMC is not responsible for modification of the product made by the user. This product must
not be modified.
• Check all the wiring to ensure that all connections are correct after installing the drive and connecting other devices.
Failure to comply could result in damage to the drive.
• Do not connect unapproved LC or RC interference suppression filters, capacitors, or overvoltage protection devices to the output of the drive.
Using unapproved filters could result in damage to the drive or motor equipment.
ENGLISH
I67E-EN V1000 Quick Start Guide 5
1 Safety Instructions and General Warnings

Precautions for CE Low Voltage Directive Compliance

This drive has been tested according to European standard EN61800-5-1, and it fully com­plies with the Low Voltage Directive. The following conditions must be met to maintain compliance when combining this drive with other devices:
Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC664.
Ground the neutral point of the main power supply for 400 V Class drives.

Precautions for UL/cUL Standards Compliance

This drive is tested in accordance with UL standard UL508C and complies with UL require­ments. The following conditions must be met to maintain compliance when using this drive in combination with other equipment:
Do not install the drive to an area greater than pollution severity 2 (UL standard).
Use UL-listed copper wires (rated at 75° C) and closed-loop connectors or CSA-certified ring connectors. For details refer to the instruction manual.
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. Use a class 2 (UL regulations) power supply for the control circuit termi­nal. For details refer to the instruction manual.
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow will not rise above 30,000 amps maximum at 240 V for 200 V class drives and 480 V for 400 V class drives.
The drive internal motor overload protection is UL listed and in accordance with the NEC and CEC. The setup can be done using the parameters L1-01/02. For details refer to the instruction manual.

Precautions for Using the Safe Disable Function

The drive’s Safe Disable function is designed in accordance with the EN954-1, safety cate­gory 3 and EN61508, SIL2. It can be utilized to perform a safe stop as defined by the EN60204-1, stop category 0 (uncontrolled stop by removal of power). Refer to the instruction manual for details about the application of this function.
6 I67E-EN V1000 Quick Start Guide
2 Mechanical Installation

2 Mechanical Installation

Upon Receipt

Please perform the following tasks after receiving the drive:
• Inspect the drive for damage. If the drive appears damaged upon receipt, contact your sup­plier.
• Verify receipt of the correct model by checking the information on the nameplate. If you have received the wrong model contact your supplier.

Installation Environment

For optimum performance life of the drive, install the drive in an environment that meets the conditions listed below.
Environment Conditions
Installation Area Indoors
-10
° C to +40 ° C (NEMA Type 1)
° C to +50 ° C (Open-Chassis Type)
-10
Ambient Temperature
Humidity 95% RH or less and free of condensation Storage Temperature -20 ° C to +60 ° C
Surrounding Area
Altitude 1000 m or less
Vibration 10 - 20 Hz at 9.8 m/s2, 20 - 55 Hz at 5.9 m/s
Orientation Install the drive vertically to maintain maximum cooling effects.
When using an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
•chlorides
• direct sunlight
2
ENGLISH
I67E-EN V1000 Quick Start Guide 7
2 Mechanical Installation

Installation Orientation and Spacing

Always install the drive in an upright position. Leave space around the unit for proper cooling as shown in the figure on the right.
Note: Several units can be installed closer
together than shown in the figure by using “Side-by-Side” mounting. For details please refer to the instruction manual.
30mm 30mm

Dimensions

d
A
IP20 / Open
Chassis
B
IP20 / Nema
Type
1
W1
H2
Model VZA*
H
H1
Fig. W H D W1 H1 H2 H3 H4 D1 d
B0P1
68 128 76 56 118 5 - - 6.5 M4 0.6 B0P2 68 128 76 56 118 5 - - 6.5 M4 0.7 B0P4 68 128 118 56 118 5 - - 38.5 M4 1.0
W
B0P7 108 128 137.5 96 118 5 - - 58 M4 1.5 B1P5 108 128 154 96 118 5 - - 58 M4 1.5 B2P2 140 128 163 128 118 5 - - 65 M4 2.1 B4P0 under development 20P1 68 128 76 56 118 5 - - 6.5 M4 0.6
A
20P2 68 128 76 56 118 5 - - 6.5 M4 0.6
D1
D
d
W1
H3
20P4 68 128 108 56 118 5 - - 38.5 M4 0.9 20P7 68 128 128 56 118 5 - - 38.5 M4 1.1
H2
21P5 108 128 129 96 118 5 - - 58 M4 1.3 22P2 108 128 137.5 96 118 5 - - 58 M4 1.4 24P0 140 128 143 128 118 5 - - 65 M4 2.1
H
25P5
H1
27P5 140 254 140 122 248 6 13 6.2 55 M5 3.8
2011 180 290 163 160 284 8 15 6.2 75 M5 5.5
140 254 140 122 248 6 13 6.2 55 M5 3.8
B
2015 220 358 187 192 336 7 15 7.2 78 M5 9.2
W
H4
40P4 108 128 99 96 118 5 - - 28 M4 1.0
40P2
108 128 81 96 118 5 - - 10 M4 0.8
40P7 108 128 137.5 96 118 5 - - 58 M4 1.4 41P5 108 128 154 96 118 5 - - 58 M4 1.5
A 42P2 108 128 154 96 118 5 - - 58 M4 1.5 43P0 108 128 154 96 118 5 - - 58 M4 1.5 44P0 140 128 143 128 118 5 - - 65 M4 2.1 45P5 47P5 140 254 140 122 248 6 13 6.2 55 M5 3.8
D1
D
4011 180 290 143 160 284 8 15 6 55 M5 5.2
4015 180 290 163 160 284 8 15 6 75 M5 5.5
140 254 140 122 248 6 13 6 55 M5 3.8
B
Dimensions (mm)
100mm
100mm
Air
Air
Weight
(kg)
8 I67E-EN V1000 Quick Start Guide
3 Electrical Installation
The figure below shows the main and control circuit wiring.
For 1-phase
power supply use
R/L1 and S/L2
Fuses
L1
Power
L2
Supply
L3
Main
Switch
Forward/Stop
Reverse/Stop
External Fault
Fault Reset
Multi-speed 1
Multi-speed 2
Multi-function
digital inputs
(default setting)
2 kΩ
Multi- function pulse / analog inputs
(default: frequency reference)
Safe Disable
inputs
Filter
DC reactor
(option)
Link
R/L1
S/L2
V1000
T/L3
S1
S2
S3
S4
S5
S6
SC
RP
+V
A1
A2
AC
H2
H1
HC
+24 V 8mA
SINK
DIP switch S3
SOURCE
Shielded ground terminal
Pulse Input (max. 32kHz)
Analog input power supply +10.5 Vdc, max. 20 mA
Multi-function analog input 1 0 to 10 V (20 k
Multi-function analog input 2 0 to 10 V (20 k 0/4 to 20 mA (250
Ω
Ω
Terminal resistance
Ω
(120
24 V
0V
)
) or
, 1/2 W)
Thermal
relay
B1+1+2 B2
Ω
)
Braking resistor
(opt)
U/T1
V/T2
W/T3
MA
MB
MC
P1
P2
PC
MP
AM
AC
R+
R
S+
S
IG

3 Electrical Installation

U
V
M
W
Shielded
Cable
Ground
Multi-function relay output 250 Vac / 30 Vdc (10 mA to 1A)
Fault
(default setting)
During run
Frequency agree Photocoupler
common
Pulse train output (max. 32 kHz) (Output frequency)
Analog output 0 to +10 Vdc (2mA) (Output frequency)
Multi-function photo­coupler output 48 Vdc, max. 50 mA (default setting)
Monitor outputs (default setting)
Memobus comm. RS-485/422 max. 115 kBps
ENGLISH
Symbols:
Use twisted pair cables
Use shielded twisted pair cables
Indicates a main circuit terminal
Indicates a control circuit terminal.
I67E-EN V1000 Quick Start Guide 9
3 Electrical Installation

Wiring Specification

Main Circuit
Use the fuses and line filters listed up in the table below when wiring the main circuit. Make sure not to exceed the given tightening torque values.
Model
VZA*
B0P1 B0P2 TRS10R 1.5 M3.5 M3.5 M3.5
A1000-FIV1010-RE A1000-FIV1010-SE B0P4 TRS20R 1.5 M3.5 M3.5 M3.5 B0P7
A1000-FIV1020-RE A1000-FIV1020-SE B1P5 TRS50R 4 M4 M4 M4
B2P2 A1000-FIV1030-RE A1000-FIV1030-SE TRS60R 4 M4 M4 M4 B4P0 under development 20P1 20P2 TRS5R 1.5 M3.5 M3.5 M3.5
A1000-FIV20010-RE A1000-FIV20010-SE
20P4 TRS10R 1.5 M3.5 M3.5 M3.5 20P7 TRS15R 1.5 M3.5 M3.5 M3.5 21P5
A1000-FIV2020-RE A1000-FIV2020-SE 22P2 TRS35R 4 M4 M4 M4
24P0 A1000-FIV2030-RE A1000-FIV2030-SE TRS60R 4 M4 M4 M4 25P5
A1000-FIV2060-RE A1000-FIV2050-SE 27P5
2011
A1000-FIV2100-RE -
2015
40P2
A1000-FIV30005-RE A1000-FIV30005-SE
40P4 TRS5R 2.5 M4 M4 M4 40P7 41P5 TRS20R 2.5 M4 M4 M4
A1000-FIV3010-RE A1000-FIV3010-SE 42P2 TRS20R 2.5 M4 M4 M4
43P0 TRS20R 2.5 M4 M4 M4 44P0 A1000-FIV3020-RE A1000-FIV3020-SE TRS30R 4 M4 M4 M4 45P5
A1000-FIV3030-RE A1000-FIV3030-SE 47P5
4011
A1000-FIV3050-RE -
4015
EMC Filter Type
Rasmi Schaffner
(Ferraz)
TRS5R 1.5 M3.5 M3.5 M3.5
TRS35R 2.5 M4 M4 M4
TRS5R 1.5 M3.5 M3.5 M3.5
TRS25R 2.5 M4 M4 M4
A6T70 A6T100 A6T150 A6T200
TRS2.5R 2.5 M4 M4 M4
TRS10R 2.5 M4 M4 M4
A6T50
A6T60
A6T70
A6T80
Main Fuse
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<1>
Recom.
Motor
cable
[mm²]
<1> For UL compliance a different fuse type has to be used. For details refer to the instruction manual.
Tightening Torque Values
Tighten the main circuit terminals using the torque values provided by the table below.
Terminal Size M3.5 M4 M5 M6 M8
Tightening Torque [Nm] 0.8 to 1.0 1.2 to 1.5 2.0 to 2.5 4.0 to 5.0 9.0 to 11.0
Main Circuit Terminal Sizes
R/L1,S/L2,T/L3,
U/T1,V/T2,W/T3,
- , +1, +2
6M4M4M5 10 M4 M4 M5 16 M6 M5 M6 25 M8 M5 M6
4M4M4M5
6M4M4M5 10 M5 M5 M5 10 M5 M5 M6
B1, B2 GND
10 I67E-EN V1000 Quick Start Guide
3 Electrical Installation
Control Circuit
The control terminal board is equipped with screwless terminals. Always use wires within the specification listed below. For safe wiring it is recommended to use solid wires or flexi­ble wires with ferrules. The stripping length respectively ferrule length should be 8 mm.
Wire Type Wire size
Solid 0.2 to 1.5 mm² Flexible 0.2 to 1.0 mm² Flexible with ferrule 0.25 to 0.5 mm²

EMC Filter Installation

This drive has been tested in accordance with European standards EN61800-3. In order to comply to the EMC standards, wire the main circuit as described below.
1. Install an appropriate EMC noise filter to the input side.See the list above or refer to the instruction manual for details.
2. Place the drive and EMC noise filter in the same enclosure.
3. Use braided shield cable for the drive and motor wiring
4. Remove any paint or dirt from ground connections for minimal ground impedance
5. Install an AC reactor at drives smaller than 1 kW for compliance with the EN61000-3-2. Refer to the instruction manual or contact your supplier for details
Cable clamp
N
L1
PE
Panel or mounting wall
Grounding Surface (remove any paint)
Metal plate
Cable clamp
L2
L1
L3
PE
Panel or mounting wall
Grounding Surface (remove any paint)
Metal plate
ENGLISH
N
EMC Filter
Wiring distance as
short as possible
E
L1
R/L1S/L2 T/L3
Cable shield
grounding clamp
U/T1 V/T2
M
W/T3
Braid shielded motor cable
Ground shield at motor side
Drive
Grounding
Surface
(remove any
paint)
EMC Filter
E
L3
L1
L2
Wiring distance as
short as possible
R/L1S/L2 T/L3
R/L1S/L2 T/L3
Cable shield
grounding clamp
U/T1 V/T2
U/T1 V/T2
M
W/T3
W/T3
Braid shielded motor cable
Ground shield at motor side
Drive
Grounding
Surface
(remove any
paint)
EMC Standards Compliant Wiring of Single- and Three Phase Units
I67E-EN V1000 Quick Start Guide 11
3 Electrical Installation

Main and Control Circuit Wiring

Wiring the Main Circuit Input
Consider the following precautions for the main circuit input.
• Use only circuit breakers that have been designed specifically for drives.
• If using a ground fault circuit breaker, make sure that it can detect both DC and high fre­quency current.
• If using an input switch is used, make sure that the switch does not operate not more than once every 30 minutes.
• Use a DC reactor or AC reactor on the input side of the drive:
• To suppress harmonic current.
• To improve the power factor on the power supply side.
• When using an advancing capacitor switch.
• With a large capacity power supply transistor (over 600 kVA).
Wiring the Main Circuit Output
Consider the following precautions for the output circuit wiring.
• Do not connect any other load than a 3 phase motor to the drives output.
• Never connect a power source to the drives output.
• Never short or ground the output terminals.
• Do not use phase correction capacitors.
• If using a contactor between the drive and motor, it should never be operated when the drive is outputting a voltage. Operating while there is voltage output can cause large peak currents, thus tripping the over current detection or damage the drive.
Ground Connection
Take the following precautions when grounding the drive.
• Never share the ground wire with other devices such as welding machines, etc.
• Always use a ground wire, that complies with electrical equipment technical standards. Keep ground wires as short as possible. Leakage current is caused by the drive. Therefore, if the distance between the ground electrode and the ground terminal is too long, potential on the ground terminal of the drive will become unstable.
• When using more than one drive, do not to loop the ground wire.
Control Circuit Wiring Precautions
Consider the following precautions for wiring the control circuits.
• Separate control circuit wiring from main circuit wiring and other high-power lines.
• Separate wiring for control circuit terminals MA, MB, MC (contact output) from wiring to other control circuit terminals.
12 I67E-EN V1000 Quick Start Guide
3 Electrical Installation
• For external control power supply use a UL Listed Class 2 power supply.
• Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults.
• Ground the cable shields with the maximum contact area of the shield and ground.
• Cable shields should be grounded on both cable ends.
Main Circuit Terminals
Ter min al Typ e Function
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3 Drive output Connects to the motor.
B1, B2 Braking resistor For connecting a braking resistor or the braking resistor unit option.
+1, +2
+1, –
(2 terminals)
Main circuit power supply input
DC reactor connec­tion
DC power supply input
Ground Terminal
Main Circuit Terminals
The figure below shows the control circuit terminal arrangement. The drive is equipped with screwless terminals
Connects line power to the drive. Drives with single-phase 200 V input power use terminals R/L1 and S/ L2 only (T/L3 is not used).
Linked at shipment. Remove the link to install a DC choke.
For connecting a DC power supply.
For 200 V class: Ground with 100 Ω or less For 400 V class: Ground with 10 Ω or less
S2 S1
ENGLISH
R+ R- S+ S- IG
P1 P2 PC A1 A2 +V AC AM AC MP
S1 S2 S3 S4 S5 S6 SC HC H1 H2 RP
S3
MA MB MC
There are three DIP switches, S1 to S3, located on the terminal board
SW1 Switches analog input A2 between voltage and current input SW2 Enables or disables the internal RS422/485 comm. port terminal resistance.
Used to select sourcing (PNP)/sinking (NPN, default) mode for the digital inputs (PNP requires
SW3
external 24 Vdc power supply)
I67E-EN V1000 Quick Start Guide 13
3 Electrical Installation
Control Circuit Terminals
Typ e No. Terminal Name (Signal) Function (Signal Level), Default Setting
Multi­Function Digital Inputs
Multi­Function Analog/ Pulse Inputs
Safe Disable Inputs
Multi­Function Relay Output
Multi­Function PHC Output
Monitor Output
MEMO­BUS/ Commu­nication
S1 toS6Multi-function digital input 1 to 6
SC Multi-function input common Sequence common
RP Pulse train input
+V Analog input power supply +10.5 V (max allowable current 20 mA) A1 Multi-function analog input 1 A2 Multi-function analog input 2 AC Frequency reference common 0 V HC Safe Disable Input common +24 V (max 10 mA allowed) H1 Safe Disable Input 1 One or both open: Drive output disabled (time from input
H2 Safe Disable Input 2
MA N.O. (fault) MB N.C. output (fault)
MC Digital output common
P1 Photocoupler output 1 P2 Photocoupler output 2
PC Photocoupler output common
MP Pulse train output 32 kHz (max) AM Analog monitor output 0 to 10 Vdc (2 mA or less), Resolution: 1/1000 (10 Bit)
AC Monitor common 0 V R+ Communications input (+) R– Communications input (–) S+ Communications output (+)
S- Communications output (–)
NOTICE! The terminals HC, H1, H2 are used for the Safe Disable function which
cuts the output voltage in less than 1 ms if at least one of the inputs H1 or H2 is opened. It is designed in accordance with the EN954-1, safety category 3 and EN61508, SIL2. It and can be utilized to perform a safe stop as defined by the EN60204-1, stop category 0. Do not remove the wire link between HC, H1, or H2 unless the Safe Disable function is used.
Photocoupler inputs, 24 Vdc, 8 mA Note: Drive preset to sinking mode (NPN). When using source mode, set DIP switch S3 to “SOURCE” and use an external 24 Vdc (±10%) power supply.
Response frequency: 0.5 to 32 kHz, Duty: 30 to 70%, High:
3.5 to 13.2 V, Low: 0.0 to 0.8 V, input impedance: 3 kΩ)
0 to +10 Vdc (20 kΩ) resolution 1/1000 0/4 to 20 mA (250 Ω) resolution: 1/500 (A2 only)
open to drive output switch off is less than 1 ms) Both Closed: Normal operation
Digital relay output 30 Vdc, 10 mA to 1 A 250 Vac, 10 mA to 1 A
Digital photocoupler output 48 Vdc, 0 to 50 mA
MEMOBUS/Modbus communication.: RS-485 or RS-422, 115.2 kBps (max)
14 I67E-EN V1000 Quick Start Guide
4 Keypad Operation

4 Keypad Operation

LED Operator and Keys

The LED operator is used to program the drive, to start/ stop it, and to display fault information. The LEDs indi­cate the drive status.
Keys and Functions
Display Name Function
Data Display Area Displays the frequency reference, parameter number, etc.
ESC Key Returns to the previous menu.
Moves the cursor to the right. Resets a fault.
Starts the drive in the LOCAL mode. The Run LED
• is on, when the drive is operating the motor.
• flashes during deceleration to stop or when the frequency reference is 0.
• flashes quickly the drive is disabled by a DI, the drive was stopped using a fast stop DI or a run command was active during power up.
Switches drive control between the operator (LOCAL) and the control circuit terminals (REMOTE). The LED is on when the drive is in the LOCAL mode (operation from keypad).
Flashing: The drive is in an alarm state. On: The drive is in a fault state and the output is stopped. On: The motor rotation direction is reverse. Off: The motor rotation direction is forward. On: The drive is ready to operate the motor. Off: The drive is in the Verify, Setup, Parameter Setting or Auto tuning mode. On: The output frequency is displayed on the data screen. Off: Anything else than the output frequency is displayed on the data screen.
RUN
STOP
ALM
REV
DRV
FOUT
RESET Key
RUN Key
Up Arrow Key Scrolls up to select parameter numbers, setting values, etc.
Down Arrow Key Scrolls down to select parameter numbers, setting values, etc.
STOP Key Stops the drive.
ENTER Key Selects modes, parameters and is used to store settings.
LO/RE Selection Key
ALM LED Light
REV LED Light
DRV LED Light
FOUT LED Light
STOP
ENGLISH
I67E-EN V1000 Quick Start Guide 15
4 Keypad Operation

Menu Structure and Modes

The following illustration explains the operator keypad menu structure.
Key operation description
Turn the power on (DRV flashes)
Forward Selection Reverse Selection
:
:
:
Output Frequency
DRV LED is on.
A Run command will start the motor.
DRV LED is off.
The motor can not be started.
Output Current
Output Voltage
Monitor Display
Verify Menu
Setup Mode
Parameter Setting Mode
Auto-Tuning
XX
XXXX
XX
:
The Monitor Displays are used to
XX
read out drive data like terminal status, output frequency, fault information etc.
XX
XX
The Verify Menu lists up all parameters which are unequal to the default setting.
XX
XX
The Setup Mode can be used to set up a minimum list of parameters necessary to run the
XX
application.
XX
In the Parameter Setting Mode all drive parameters can be set up.
XX
Auto-Tuning measures the motor data for optimal performance of the drive/motor combination.
XX
16 I67E-EN V1000 Quick Start Guide
5Start Up

5 Start Up

Drive Setup Procedure

The illustration below shows the basic setup procedure. Each step is explained more detailed on the following pages.
START
Intstall and wire the drive as explained.
Turn the power on.
Initialize the drive if necessary using parameter A1-01.
Set the control mode.
Perform Auto-Tuning or set the motor data manually.
* b1-01, b1-02 for frequency reference and RUN command source * H1-xx, H2-xx, H3-xx, H4-xx, H6-xx to configure the I/Os * Frequency reference values * C1-xx, C2-xx for Acceleration/Deceleration times and S-curves
Run the motor without load, check the operation and verify, if the
upper controller (e.g. PLC,...) commands to the drive work as
Set/check the basic parameters:
desired.
ENGLISH
Connect the load, run the motor and check the operation
Fine tune and set application parameters (e.g. PID,...) if necessary.
Final check the operation and verify the settings.
Drive is ready to run the application
I67E-EN V1000 Quick Start Guide 17
5 Start Up

Power On

Before turning on the power supply,
• Make sure all wires are connected properly.
• Make sure no screws, loose wire ends or tools are left in the drive.
• After turning the power on, the drive mode display should appear and no fault or alarm should be displayed.

Control Mode Selection (A1-02)

There are three control modes available. Select the control mode that best suits the applica­tions the drive will control.
Control Mode Parameter Main Applications
V/f Control
Open Loop Vector Control (OLV)
PM Open Loop Vector Control
A1-02 = 0
(default)
A1-02 = 2
A1-02 = 5
• General variable speed applications, particularly useful for running multi­ple motors from a single drive
• When replacing a drive in which parameter settings are unknown
• General variable speed applications
• Applications requiring high precision, high speed control
• Derated torque-load applications employing permanent magnet motors (SPM, IPM) and energy savings.
Auto-Tuning (T1-)
Auto-Tuning automatically sets up the motor data relevant drive parameters. Three different modes are supported
Tuning Mode Parameter
Rotational Auto-Tuning
Terminal resistance tuning
Rotational Auto-Tuning for Energy Saving
T1-01 = 0 OLV
T1-01 = 2
T1-01 = 3 V/f control
Control
Mode
OLV, V/f
control
Description
Perform when setting the drive to operate in Open Loop Vector control. The motor must be able to rotate without load during the tuning process in order to achieve a high accuracy.
Perform in V/f control if the motor cable is long or if the cable has been changed.
Perform when using Energy Saving or Speed Search.The motor must be able to rotate without load in order to achieve a high tuning accuracy.
CAUTION
Never touch the motor until the Auto-Tuning is finished. Even thought the motor may not be rotating when Auto-Tuning, voltage is still applied to the motor during the tuning process.
18 I67E-EN V1000 Quick Start Guide
5 Start Up
For Auto-Tuning enter the Auto-Tuning menu and perform the steps shown in the figure below. The number of name plate data to be entered depends on the selected type of Auto­Tuning. This example shows Rotational Auto-Tuning.
Drive mode
display
Enter the Auto-
Tuning Mode
Select the tuning
method
ENGLISH
Set up all name
plate data
The tuning start display appears
During the tuning the
DRV LED flashes
After successful tuning
“End” is displayed
If Auto-Tuning can not be performed for some reason (no-load operation impossible etc.), then set up the maximum frequency and voltage in the E1- parameters and enter the motor data manually into the E2- parameters.
NOTICE! The Safe Disable inputs must be closed during Auto-Tuning.
I67E-EN V1000 Quick Start Guide 19
5 Start Up

Reference and Run Source

The drive has a LOCAL and a REMOTE mode. The LED in the LO/RE key indicates the drive status.
Status Description LO/RE LED
LOCAL The Run/ Stop command and the frequency reference are entered at the operator keypad. ON
REMOTE
The Run command source entered in parameter b1-02 and the frequency reference source entered in parameter b1-02 are used.
OFF
If the drive is operated in the REMOTE mode, make sure that the correct sources for the fre­quency reference and run command are set in parameters b1-01/02 and that the drive is in the REMOTE mode.

I/O Setup

Multi-Function Digital Inputs (H1-)
The function of each digital input can be assigned in the H1- parameters. The default set­ting functions can be seen in the connection diagram on page 9.
Multi-Function Digital Outputs (H2-)
The function of each digital output can be assigned in the H2- parameters. The default setting functions can be seen in the connection diagram on page 9. The setting value of these parameters consist of 3 digits, where the middle and right digit set the function and the left digit sets the output characteristics (0: Output as selected; 1: Inverse output).
Multi-Function Analog Inputs (H3-)
The function of each analog input can be assigned in the H3- parameters. The default setting of both inputs is “Frequency reference”. Input A1 is set for 0 to 10V input and A2 is set for 4-20 mA input. The addition of both input values builds the frequency reference.
NOTICE! If the input signal level of input A2 is switched between voltage and
current, make sure that DIP switch S1 is in the correct position and parameter H3-09 is set up correctly.
Monitor Output (H4-)
Use the H4- parameters to set up the output value of the analog monitor output and to adjust the output voltage levels. The default monitor value setting is “Output frequency”.
20 I67E-EN V1000 Quick Start Guide
5 Start Up

Frequency Reference and Acceleration/ Deceleration Times

Frequency Reference Setup(b1-01)
Set parameter b1-01 according to the frequency reference used.
b1-01 Reference source Frequency reference input
0 Operator keypad
1 Analog input Apply the frequency reference signal to terminal A1 or A2. 2 Serial Comm. Serial Communications using the RS422/485 port 3 Option Board Communications option card 4 Pulse input Set the frequency reference at terminal RP using a pulse train signal.
Set the frequency references in the d1- parameters and used digital inputs to switch over between different reference values.
Acceleration/ Deceleration Times and S-Curves
There are four sets of acceleration and deceleration times which can be set in the C1- parameters. The default activated accel/ decel times are C1-01/02. Adjust these times to the appropriate values required by the application. If necessary S-curves can be activated in the C2- parameters for softer accel/ decel start and end.

Test Run

Perform the following steps to start up the machine after all parameter settings have been done.
1. Run the motor without load and check if all input, outputs and the sequence work as desired.
2. Connect the load to the motor.
3. Run the motor with load and make sure that there is no vibrations, hunting or motor stalling occurs.
After taking the steps listed above, the drive should be ready to run the application and per­form the basic functions. For special setups like PID control etc. refer to the instruction man­ual.
ENGLISH
I67E-EN V1000 Quick Start Guide 21

6 Parameter Table

6 Parameter Table
This parameter table shows the most impor­tant parameters. Default settings are bold type. Refer to the instruction manual for a complete list of parameters.
Par. Name Description
Initialization Parameters
Access
A1-01
Level Selection
Control
A1-02
Method Selection
Initialize
A1-03
Parameters
Operation Mode Selection
Frequency
b1-01
Reference Selection
Run
b1-02
Command Selection
Selects which parameters are accessible via the digital operator. 0:Operation only 1:User Parameters
2:Advanced Access Level
Selects the Control Method of the drive.
0: V/f Control
2: Open Loop Vector (OLV) 5: PM Open Loop Vector (PM) Note: Not initialized with A1-03!
Resets all parameters to default. (returns to 0 after initialization) No Initialize 1110: User Initialize (The user must first set user parameter values and then store them using parame­ter o2-03) 2220: 2-Wire Initialization 3330: 3-Wire Initialization
0:Operator - d1- values
1:Analog input A1 or A2
2:Serial Com - RS-422/485 3:Option board 4:Pulse Input (Terminal RP)
0:Operator - RUN and STOP keys
1:Terminals - Digital Inputs
2:Serial Com - RS-422/485 3:Option board connected
Par. Name Description
Selects the stopping method when the run command is removed.
0:Ramp to Stop
1:Coast to Stop 2:DC Injection Braking to Stop 3:Coast with Timer (a new run
command is ignored if received before the timer expires)
0:Reverse enabled
1:Reverse prohibited
Switches the output phase order.
0:Standard
1:Switch phase order
DC Injection Braking
Sets the frequency at which DC Injection Braking starts when Ramp to Stop (b1-03 = 0) is selected. If b2-01< E1-09, DC Injection Braking starts at E1-09.
Sets the DC Injection Braking cur­rent as a percentage of the drive rated current. In OLV the DC excitation current is determined by E2-03.
Sets the time of DC Injection Brak­ing at start in units of 0.01 seconds. Disabled when set to 0.00 seconds.
Sets the DC Injection Braking time at stop. Disabled when set to 0.00 seconds.
Acceleration/ Deceleration
Sets the acceleration time 1 from 0 to the max. output frequency.
Sets the deceleration time 2 from the max. output frequency to 0.
b1-03
b1-04
b1-14
b2-01
b2-02
b2-03
b2-04
C1-01
C1-02
Stopping Method Selection
Reverse Operation Selection
Phase Order Selection
DC Injection Braking Start Fre­quency
DC Injection Braking Current
DC Inj. Braking Time/DC Excitation Time at Start
DC Inj. Braking Time at Stop
Accel Time 1
Decel Time 1
22 I67E-EN V1000 Quick Start Guide
6 Parameter Table
Par. Name Description
C1-03
to
C1-08
Accel/Decel Times 2 to 4
Set the accel/ decel times 2 to 4 (set like C1-01/02)
C2-01 S-Curve 1 S-curve at acceleration start.
C2-02 S-Curve 2 S-curve at acceleration end.
C2-03 S-Curve 3 S-curve at deceleration start.
C2-04 S-Curve 4 S-curve at deceleration end.
Slip Compensation
• Increase if the speed is lower than the frequency reference
• Decrease if the speed is higher than the frequency reference.
• Decrease the setting when the slip compensation is too slow.
• Increase the setting when the speed is not stable.
C3-01
C3-02
Slip Com­pensation Gain
Slip Com­pensation Delay Time
Torque Compensation
• Increase this setting when the torque response is slow
• Decrease this setting when speed/ torque oscillations occur.
• Increase this setting when speed / torque oscillations occur.
• Decrease the setting when the torque response is too slow.
C4-01
C4-02
Torque Compensa­tion Gain
Torque Compensa­tion Delay Time
Duty Mode and Carrier Frequency
0: Heavy Duty (HD)
Constant torque applications
1:Normal Duty (ND)
Variable torque application
1:2.0 kHz 2:5.0 kHz 3:8.0 kHz 4:10.0 kHz 5:12.5 kHz 6:15.0 kHz 7 to A: Swing PWM1 to 4 F: User defined
C6-01
C6-02
Normal/ Heavy Duty Selection
Carrier Fre­quency Selection
Frequency References
d1-01
to
d1-16
Frequency Reference 1 to 16
Set the multi-speed references 1 to 16
d1-17 Jog Speed Jog speed
Par. Name Description
V/f Pattern
Input
E1-01
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-13
Voltage Set­ting
Max. Out­put Freq.
Max. Out­put Voltage
Base Fre­quency
Middle Out­put Freq.
Mid. Out­put Voltage
Min. Out­put Freq.
Min. Out­put Voltage
Base Voltage
Input Voltage
For a linear V/f characteristics, set the same values for E1-07 and E1-
09. In this case, the setting for E1­08 will be disregarded. Ensure that the four frequencies are set according to these rules or OPE10 fault will occur:
E1-04 E1-06 E1-07 E1-09
Output voltage
(E1-05) (E1-13)
(E1-08)
(E1-10)
Motor Data
Motor
E2-01
Rated Current
Motor
E2-02
Rated Slip
Motor
E2-03
No-Load Current
E2-04 Motor Poles
Motor Line-
E2-05
to-Line Resistance
Motor
E2-06
Leakage Inductance
Automatically set during Auto-Tuning.
Motor rated slip in hertz (Hz). Automatically set by Rotational Auto-Tuning.
Magnetizing current in Ampere. Automatically set by Rotational Auto-Tuning.
Number of motor poles. Automatically set by Auto-Tuning.
Sets the phase-to-phase motor resistance in ohms. Automatically set by Auto-Tuning.
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. Automatically set by Auto-Tuning.
(E1-04)(E1-06)(E1-07)(E1-09)
Output frequency
ENGLISH
I67E-EN V1000 Quick Start Guide 23
6 Parameter Table
Par. Name Description
Digital Input Settings
DI S1 to
H1-01
S6
to
Function
H1-06
Selection
A list of the major functions can be found at the table end.
H2-01DOMA/MB
Function
DO P1
H2-02
Function
DO P2
H2-03
Function
Major functions are listed at the end of the table.
A1 Signal
H3-01
Level Sel.
A1 Func-
H3-02
tion Sel.
H3-03 A1 Gain
H3-04 A1 Bias
A2 Signal
H3-09
Level Selection
A2 Func-
H3-10
tion Sel.
H3-11 A2 Gain
H3-12 A2 Bias
H4-01AMMonitor
Selection
H4-02 AM Gain
H4-02 AM Bias
Selects the function of terminals S1 to S6.
Digital Output Settings
Set the function for the relay output MA-MB-MC.
Sets the function for the photocou­pler output P1.
Sets the function for the photocou­pler output P2.
Analog Input Setting
0:0 to +10 V (neg. input is zeroed)
1:0 to +10 V (bipolar input)
Assign a function to terminal A1.
Sets the input value in % at 10 V analog input.
Sets the input value in % at 0 V analog input.
0:0 to +10 V (neg. input is zeroed) 1:0 to +10 V (bipolar input)
2:4 to 20 mA (9 bit input)
3:0 to 20 mA
Assign a function to terminal A2.
Sets the input value in % at 10 V /20 mA analog input.
Sets the input value in % at 0 V / 0 mA / 4 mA analog input.
Analog Input Setting
Enter value equal to U1- monitor values. Example: Enter “103” for U1-03.
Sets terminal AM output voltage equal to 100% monitor value.
Sets terminal AM output voltage equal to 0% monitor value.
Par. Name Description
Pulse Input Setting (Free. ref. input)
H6-02
H6-03
H6-04
H6-06
H6-07
L1-01
L1-02
L3-01
L3-02
L3-04
L3-05
RP Input Scaling
Pulse Train Input Gain
Pulse Train Input Bias
MP Monitor Sel.
MP Monitor Scaling
Motor Overload Prot. Sel.
Motor Overload Prot. Time
Stall Prevention Selection during Accelera­tion
Stall P rev. Level dur­ing Accel.
Stall P rev. Selection during Decel.
Stall P rev. Selection during Run
Sets the number of pulses (in Hz) that is equal to 100% input value.
Sets the input value in % at pulse input with H6-02 frequency.
Sets the input value in % at 0 Hz pulse input frequency.
Pulse Output Setting
Enter value equal to U- monitor values. Example: Enter “102” for U1-02.
Sets the number of output pulses when the monitor is 100% (in Hz).
Motor Overheat Protection
Sets the motor overload protection. 0:Disabled
1:Standard fan cooled motor
2:Standard blower cooled motor 3:Vector motor
Sets the motor overload protection time in min. Normally no change is necessary.
Stall Prevention
0:Disabled - Motor accelerates at
active acceleration rate and may stall with too heavy load or too short accel time.
1:General Purpose - Hold
acceleration when current is above L3-02.
2:Intelligent - Acceleration in the
shortest possible time.
Sets the current level for stall pre­vention during acceleration.
0:Disabled - Deceleration as set.
OV might occur.
1:General Purpose - Deceleration
is hold if DC bus voltage rises high.
0:Disabled - Motor stall or
overload might occur.
1:Decel Time 1 - Reduce speed
using C1-02.
24 I67E-EN V1000 Quick Start Guide
6 Parameter Table
Par. Name Description
L3-06
Stall P rev. Level dur­ing Run
Sets the current level at which stall prevention during run starts to operate.
Auto-Tuning
0:Rotational Auto-Tuning 2: Terminal resistance only 3: Rotational Auto-Tuning for Energy Saving
Sets the motor rated power (kW).
Sets the motor rated voltage (V).
Sets the motor rated current (A).
Sets the motor base frequency (Hz).
T1-01
T1-02
T1-03
T1-04
T1-05
Auto-Tun­ing Mode Selection
Rated Power
Rated Vo l t a g e
Rated Current
Base Frequency
T1-06 Motor Poles Sets the number of motor poles.
T1-07 Base Speed Sets the motor base speed (RPM).
T1-11
Motor Iron Loss
Iron loss for determining the Energy Saving coefficient. If unknown leave it on default.
Monitor Description
U1-01 Frequency Reference (Hz)
U1-02 Output Frequency (Hz)
U1-03 Output Current (A)
U1-05 Motor Speed (Hz)
U1-06 Output Voltage Reference (Vac)
U1-07 DC Bus Voltage (Vdc)
U1-08 Output Power (kW)
U1-09 Torque Reference (% of motor rated torque)
Monitor Description
Input Terminal Status
U1-10 = 0000000
U1-10
1: Digital input 1
(terminal S1 enabled)
1: Digital Input 2
(terminal S2 enabled)
1: Digital Input 3
(terminal S3 enabled)
1: Digital Input 4
(terminal S4 enabled)
1: Digital Input 5
(terminal S5 enabled)
1: Digital Input 6
(terminal S6 enabled)
. . .
Output Terminal Status
U1-11 = 000
1: Relay Output
U1-11
Drive Status
U1-12 = 00000000
U1-12
U1-13 Terminal A1 input level
U1-14 Terminal A2 input level
Soft Starter Output (fref after accel./decel.
U1-16
ramps)
U1-18 OPE Fault Parameter
U1-24 Pulse Input frequency
(terminal MA-MC closed MB-MC open)
1: Open Collector Output 1
(terminal P1) enabled
1: Open collector Output 2
(terminal P2) enabled
1: During run 1: During zero-speed
1: During REV 1: During fault reset
signal input
1: During speed agree
1: Drive ready
1: During alarm
detection
1: During fault
detection
ENGLISH
I67E-EN V1000 Quick Start Guide 25
6 Parameter Table
Monitor Description DI/DO
Fault Trace
U2-01 Current Fault
U2-02 Previous Fault
U2-03 Frequency Reference at Previous Fault
U2-04 Output Frequency at Previous Fault
U2-05 Output Current at Previous Fault
U2-06 Motor Speed at Previous Fault
U2-07 Output Voltage at Previous Fault
U2-08 DC Bus Voltage at Previous Fault
U2-09 Output Power at Previous Fault
U2-10 Torque Reference at Previous Fault
U2-11 Input Terminal Status at Previous Fault
U2-12 Output Terminal Status at Previous Fault
U2-13 Drive Operation Status at Previous Fault
U2-14 Cumulative Operation Time at Previous Fault
U2-15 Soft-Starter Speed Reference at Previous Fault
U2-16 Motor q-Axis Current at Previous Fault
U2-17 Motor d-Axis Current at Previous Fault
Fault History
U3-01
Lists the most recent fault that occurred
to
through the fourth most recent fault.
U3-04
U3-05
Accumulated operation time at the most recent
to
fault through the fourth most recent fault.
U3-08
U3-09 to
Lists the fifth most recent fault that occurred
U3-14
through the tenth most recent fault.
Accumulated operation time at fifth most
U3-15 to
recent fault through the tenth most recent
U3-20
fault.
* The following faults are not recorded in the error log:
CPF00, 01, 02, 03, UV1, and UV2.
Sel.
3 Multi-step speed reference 1
4 Multi-step speed reference 2
5 Multi-step speed reference 3
6
7 Accel/decel time selection 1
F Not used (Set when a terminal is not used)
14 Fault reset (Reset when turned ON)
20 to 2F
0
1 Zero Speed
2 Speed Agree
6 Drive Ready
EFault
F Not used
10 Minor fault (Alarm) (ON: Alarm displayed)
Description
Digital Input Function Selections
Jog frequency command (higher priority than multi-step speed reference)
External fault; Input mode: N.O. contact / N.C. contact, Detection mode: Normal/during operation
Digital Output Function Selections
During Run (ON: run command is ON or volt­age is being output)
26 I67E-EN V1000 Quick Start Guide
7 Troubleshooting

7 Troubleshooting

General Fault and Alarms

Faults and alarms indicate problems in the drive or in the machine.
An alarm is indicated by a code on the data display and the flashing ALM LED. The drive output is not necessarily switched off.
A fault is indicated by a code on the data display and the ALM LED is on. The drive output is always switched off immediately and the motor coast to stop.
To remove an alarm or reset a fault, trace the cause, remove it and reset the drive by pushing the Reset key on the operator or cycling the power supply.
NOTICE! This lists up the most important alarms and faults only. Please refer to
LED Display ALM FLT Cause
Base Block
Control Fault
Control Circuit
External Fault
External Fault
External Faults
Ground Fault
Safe Disable
the instruction manual for a complete list.
The software base block function is assigned to one of the digital inputs and the input is off. The drive does not accept Run commands.
The torque limit was reached during deceleration for longer than 3 sec. when in Open Loop Vector control
• The load inertia is too big.
• The torque limit is too low.
• The motor parameters are wrong.
There is a problem in the drive’s control circuit.
A forward and reverse command were input simultaneously for longer than 500 ms. This alarm stops a running motor.
• An external fault was triggered by an external device via one of the digital inputs S1 to S6.
• The digital inputs are set up incorrectly.
Ground leakage current has exceeded 50% of the drives rated output current.
• Cable or motor insulation is broken.
• Excessive stray capacitance at drive output.
Both Safe Disable inputs are open. The drive output is safely disabled and the motor can not be started.
Fault
Option
to
An external fault was tripped by the upper controller via an option card.

to
ENGLISH
I67E-EN V1000 Quick Start Guide 27
7 Troubleshooting
LED Display ALM FLT Cause
Safe Disable
Fault
Output Phase
Loss
Overcurrent
Heatsink
Overheat
or
Motor
Overload
Drive
Overload
DC
Overvoltage
Input Phase
Loss
Braking
Transistor
Fault


Drive output is disabled while only one of the Safe Disable inputs is open. (normally both input signals H1 and H2 should be open)
• One channel is internally broken and does not switch off, even if the external signal is removed.
• Only one channel is switched off by the upper controller.
• Output cable is disconnected or the motor winding is damaged.
• Loose wires at the drive output.
• Motor is too small (less than 5% of drive current).
• Short circuit or ground fault on the drive output side
• The load is too heavy.
• The accel./decel. times are too short.
• Wrong motor data or V/f pattern settings.
• A magnetic contactor was switched at the output.
• Surrounding temperature is too high.
• The cooling fan has stopped.
• The heatsink is dirty.
• The airflow to the heatsink is restricted.
• The motor load is too heavy.
• The motor is operated at low speed with heavy load.
• Cycle times of accel./ decel. are too short.
• Incorrect motor rated current has been set.
• The load is too heavy.
• The drive capacity is too small.
• Too much torque at low speed.
DC bus voltage rose too high.
• The deceleration time is too short.
• Stall prevention is disabled1.
• Braking chopper / resistor broken.
• Unstable motor control in OLV.
• Too high input voltage.
• Input voltage drop or phase imbalance.
• One of the input phase is lost.
• Loose wires at the drive input.
The internal braking transistor is broken.
Fault Reset
During Run
DC
Undervoltage
Fault reset was input when a run command was active.

The voltage in the DC bus fell below the undervoltage detection level (L2-05).
• The power supply failed or one input phase has been lost.
• The power supply is too weak.
28 I67E-EN V1000 Quick Start Guide
7 Troubleshooting
LED Display ALM FLT Cause
Controller
Undervoltage
DC Charge
Circuit Fault
The drives controller power supply voltage is too low.
The charge circuit for the DC bus is broken.

Operator Programing Errors

An Operator Programming Error (OPE) occurs when an inapplicable parameter is set or an individual parameter setting is inappropriate. When an OPE error is displayed, press the ENTER button to display U1-18 (OPE fault constant). This monitor will display the parame­ter that is causing the OPE error.
LED Operator
Display
oPE01
oPE02
oPE03
oPE05
oPE07
oPE08
oPE10
Drive capacity and value set to o2-04 do not match.
Parameters were set outside the allowable setting range.
A contradictory setting is assigned to multi-func­tion contact inputs H1-01 through to H1-0
• The same function is assigned to two inputs (this excludes “External fault” and “Not used”)
• Input functions which require the setting of other input functions were set alone.
• Input functions that are not allowed to be used simultaneously have been set.
• The run command source (b1-02) or frequency reference source (b1-01) is set to 3 but no option board is installed.
• The frequency reference source is set to pulse input but H6-01 is not 0.
Settings to multi-function analog inputs H3-02 and H3-10 and PID functions conflict.
• H3-02 and H3-10 are set to the same value (this excludes settings “0” and “F”)
• PID functions have been assigned to both ana­log inputs and the pulse input at the same time.
A function has been set that cannot be used in the control mode selected (might appear after control mode change)
The V/f pattern setting is incorrect.
Cause Corrective Action
Correct the value set to o2-04.
Set parameters to the proper values.
6 .
• Fix any incorrect settings.
• Refer to the instruction manual for more details.
• Install the required option board.
• Correct the values set to b1-01 and b1-02.
• Fix any incorrect setting.
• Refer to the instruction manual for more details.
• Fix any incorrect setting.
• Refer to the instruction manual for more details.
• Check the V/f pattern settings.
• Refer to the instruction manual for more details.
ENGLISH
I67E-EN V1000 Quick Start Guide 29
7 Troubleshooting

Auto-Tuning Errors

LED Operator
Display
Er-01
Er-02
Er-03
Er-04
Er-05
Er-08
Er-09
Er-11
Er-12
End1
End2
End3
Cause Corrective Action
Motor data fault The input motor data are not valid (e.g. the base frequency and base speed do not fit). Minor Fault
• The wiring is faulty.
• The load is too heavy.
The STOP button was pressed and Auto-Tuning was canceled.
Resistance fault
• Wrong input data.
• Auto tuning exceeded the given time frame.
• Calculated values out of range.
No-Load Current Error
• Incorrect data was entered.
• Auto tuning took too long.
• Calculated values out of range.
Rated Slip Error
• Wrong data input.
• Auto tuning exceeded the given time frame.
• Calculated values out of range.
Acceleration error The motor did not accelerate for the specified acceleration time.
Motor speed fault. The torque reference was too high.
Current detection error
• One or all output phases are lost.
• Current is either too low or exceeds the drives rating.
• The current sensors are faulty.
Rated current alarm
• The torque reference exceeded 20% during Auto-Tuning.
• The calculated no-load current is above 80% of the motor rated current.
Motor iron-core saturation alarm
• Calculated core saturation values out of range.
• Incorrect data was entered.
Rated current alarm Check the input data and repeat tuning.
Re-enter the data and repeat Auto-Tuning.
• Check the wiring.
• Check the load. Always perform Auto-Tuning with the load decoupled from the motor.
Repeat the Auto-Tuning.
• Check the input data.
• Check the wiring.
• Re-enter the data and repeat the Auto-Tuning.
• Increase the acceleration time C1-01.
• Check the torque limits L7-01 and L7-02.
• Increase the acceleration time (C1-01).
• If possible, disconnect the load.
• Check the wiring.
• Make sure, that the drive rating fits to the motor.
• Check the load. (Auto-Tuning should have been performed without the load connected).
• Replace the drive.
• Check the V/f pattern setting.
• Perform Auto-Tuning without the load con­nected.
• Check the input data and repeat Auto-Tuning.
• Check the input data.
• Check the motor wiring.
• Perform Auto-Tuning without load connected.
30 I67E-EN V1000 Quick Start Guide
OMRON EUROPE B.V.
Y
Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 www.omron-industrial.com
Austria
Tel: +43 (0) 1 80 19 00 www.omron.at
Belgium
Tel: +32 (0) 2 466 24 80 www.omron.be
Czech Republic
Tel: +420 234 602 602 www.omron.cz
Denmark
Tel: +45 43 44 00 11 www.omron.dk
Finland
Tel: +358 (0) 207 464 200 www.omron.fi
Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands.
France
Tel: +33 (0) 1 56 63 70 00 www.omron.fr
Germany
Tel: +49 (0) 2173 680 00 www.omron.de
Hungary
Tel: +36 (0) 1 399 30 50 www.omron.hu
Italy
Tel: +39 02 32 681 www.omron.it
Middle East & Africa
Tel: +31 (0) 23 568 11 00 www.omron-industrial.com
Netherlands
Tel: +31 (0) 23 568 11 00 www.omron.nl
Norway
Tel: +47 (0) 22 65 75 00 www.omron.no
Poland
Tel: +48 (0) 22 645 78 60 www.omron.com.pl
Portugal
Tel: +351 21 942 94 00 www.omron.pt
Russia
Tel: +7 095 745 26 64 www.omron.ru
Spain
Tel: +34 913 777 900 www.omron.es
Sweden
Tel: +46 (0) 8 632 35 00 www.omron.se
Switzerland
Tel: +41 (0) 41 748 13 13 www.omron.ch
Turkey
Tel: +90 (0) 216 474 00 40 Pbx www.omron.com.tr
United Kingdom
Tel: +44 (0) 870 752 08 61 www.omron.co.uk
Manufacturer
YASKAWA ELECTRIC CORPORATION
ASKAWA
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevand regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure to follow all procedures and submit all relevant documen­tation according to any and all rules, regulations and laws may apply. Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2007 OMRON Yaskawa Motion Control. All rights reserved.
Note: Specifications subject to change without notice. Manual No. I67E-EN-01
Loading...