
New Product
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Protective Cover
(Electrode Holders for the PS
or BF Series)
Mounting Piece
(Electrode Holder for the PS Series)
Separator (to prevent contact between electrodes)
Conductive Level Controller
K8AK-LS
Ideal for Liquid Level Control in
Industrial Facilities and Equipment.
• Self-holding circuit implemented with circuit processing that is
not depending on external wiring.
• Switch between water supply and discharge with a DIP switch
setting.
• Sensitivity adjustment of operating resistance from 10 to 100 kΩ
for application to a wide range of liquids.
• Prevents chattering of relay contacts that occurs with ripples.
• Easy wiring with ferrules.
•Use 2 × 2.5 mm
• Applicable as a floatless switch.
2
solid wire or 2 × 1.5 mm2 ferrules.
Refer to Safety Precautions on page 7.
Ordering Information
Power supply voltage Model
24 VAC/DC K8AK-LS1 24 VAC/DC
100 to 240 VAC K8AK-LS1 100−240 VAC
Accessories (Order Separately)
●Electrode Holders/Underwater Electrodes
Application
Model PS-3S/-4S/-5S
Appearance
For general-purpose use, such as
water supply lines
For areas with
limited space
PS-31
SUS304, 300 mm
For liquids with
low resistance
BF-1 BF-3/-5 BS-1 BS-1T PH-1/-2
When mounting
strength is required
●Electrode Rods
Electrode Rods are available in sets with the connection nuts, lock nuts, and tightening screws.
For resistance to
high-temperature
or high-pressure
liquids
For resistance
against corrosion
SUS
HAS
titanium
For installation at
long distances
from the liquid level
Application Purified water service, industrial water, and sewage
Model F03-60 SUS304 F03-60 SUS316
●Others
Item Model
Purified water service, industrial water, sewage, and weak
alkaline solutions
F03-11
F03-12
F03-14 1P (one pole)
F03-14 3P (three poles)
F03-14 5P (five poles)
1

K8AK-LS
Ratings and Specifications
Ratings Specifications
Power supply voltage
Voltage across electrodes
Power consumption
Operating resistance 10 to 100 kΩ (variable)
Reset resistance 250 kΩ max.
Response time Approx. 0.1 to 10 s (variable)
Length of cable
Indicators PWR: Green, RY: Yellow
Output contact ratings
Ambient operating
temperature
Storage temperature −25 to 65°C (with no condensation or icing)
Ambient humidity 25% to 85% (with no condensation)
Storage humidity 25% to 85% (with no condensation)
Altitude 2,000 m max.
Terminal screw
tightening torque
Case color N1.5
Case material PC and ABS, UL 94 V-0
Weight Approx. 150 g
Mounting Mounts to DIN Track.
Dimensions 22.5 × 90 × 100 mm (W×D×H)
24 VAC 50/60 Hz or 24 VDC
100 to 240 VAC 50/60 Hz
5 V p-p (Approx. 20 Hz)
24 VAC/DC: 2.0 VA/1.1 W max.
100 to 240 VAC: 4.6 VA max.
100 m max. (fully insulated 3-core 0.75-mm
tyre cable, 600 V)
Rated load
Resistive load
5 A at 250 VAC
5 A at 30 VDC
Maximum switching capacity: 1,250 VA, 150 W
Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life:
5 A at 250 VAC or 30 VDC: 50,000 operations
3 A at 250 VAC/30 VDC: 100,000 operations
−20 to 60°C (with no condensation or icing)
0.49 to 0.59 N·m
2
cab-
Operating voltage
range
Installation environment
Approved standards EN 61010-1
EMC EN 61326-1 Industrial electromagnetic environment
Safety standards
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance 100 m/s2, 3 times each in 6 directions along 3 axes
Degree of protection Terminals: IP20
85% to 110% of rated voltage
Installation category II, pollution level 2
UL 508 (Recognition),
Korean Radio Waves Act (Act 10564),
CSA: C22.2 No.14, CCC: GB14048.5
20 MΩ min.
Between all external terminals and the case
Between all power supply terminals and all input
terminals
Between all power supply terminals and all output
terminals
Between all input terminals and all output terminals
2,000 VAC for 1 min
Between all external terminals and the case
Between all power supply terminals and all input
terminals
Between all power supply terminals and all output
terminals
Between all input terminals and all output terminals
1,500 V power supply terminal common/normal
mode
Square-wave noise of ±1-μs/100-ns pulse width with
1-ns rise time
Frequency: 10 to 55 Hz, acceleration 50 m/s
10 sweeps of 5 min each in X,Y, and Z directions
2
2

Connections
Terminal Diagram
K8AK-LS1 100-240VAC
AB
K8AK-LS
Control Output
Relay output
250 VAC, 5 A (resistive load)
30 VDC, 5 A (resistive load)
Relay Output
Common
11 14 12
11 14
E1 E2 E3
B Power Supply Voltage
100 to 240 VAC 24 VAC/DC
A2
A1
A2A1
A1
(No polarity)
Note: 1. Do not connect anything to terminals that are shaded in gray.
2. Use the recommended ferrules if you use twisted wires.
Wiring Example
L1
Three-phase
power supply
L2
L3
12
A Water Level Inputs
LS1
E1 E2 E3
Water or
other liquid
A2
Power
supply voltage
12
14
11
E1 E2 E3
A2
A1
A1 A2
Power supply
AC/DC
Motor
Pump
Water or
other liquid
Source of liquid
Pump motor protection mechanisms have been omitted.
3

K8AK-LS
Timing Charts
●DIP Switch Pin 1: OFF (Automatic Liquid
Supply Operation)
Power supply voltage A1-A2
Electrode terminals E2-E3
Electrode terminals E1-E3
Control output terminals 11-14
(operation indication)
P
OFF (stop)
ON (start)
•
When the liquid level falls to E2 (indicator turns ON), the pump starts.
1
E
E
2
When the liquid level rises above E1 (indicator turns OFF), the pump stops.
E
3
Operation indicator OFF
Operation indicator ON
●DIP Switch Pin 1: ON (Automatic Liquid
Discharge Operation)
Power supply voltage A1-A2
Electrode terminals E2-E3
Electrode terminals E1-E3
Control output terminals 11-14
(operation indication)
E
1
E
2
E
3
•
When the liquid level reaches E1 (indicator turns ON), the pump starts.
OFF (stop)
When the liquid level falls below E2 (indicator turns OFF), the pump stops.
Operation indicator ON
ON (start)
Operation indicator OFF
P
4