If a temperature sensor is damaged or the SSR
is short circuited in a furnace, the controller has
no means of stopping rises in temperature.
An internal alarm can help, but there is still some
risk if the controller fails. This risk is eliminated
by the built-in redundancy of the K8AB-TH alarm
unit which can automatically switch off the power
to the furnace.
Temperature rises due to heat dissipation from
SSRs within a cabinet can be too high for efficient
operation. Simple ON/OFF control with the
K8AB-TH can protect against overheating without
the necessity and expense of running the fans
continuously.
LEA_K8AB-TH_01_EN_INT
Although we strive for perfection, Omron Europe
BV and/or its subsidiary and affiliated companies do
not warrant or make any representations regarding
the correctness or completeness of the information
described in this document. We reserve the right to
make any changes at any time without prior notice.
Power supply
Alarm setting
Input (current temperature)
Alarm (red) indicator
Non-fail safe,
Alarm (relay) output
Fail safe,
Alarm (relay) output
Power supply
Alarm setting
Input (current temperature)
Alarm (red) indicator
Latch reset (see note)
Non-fail safe,
Alarm (relay) output
Fail safe,
Alarm (relay) output
Note: The output latch is reset using the reset button on the front or the external input terminal.
Hysteresis 2°C
Hysteresis 2°C
Output Latch Enabled
Output Latch Disabled
Output latch function with (front button) latch reset,
SV protection and the choice of fail-safe/non-fail-safe relay operation.
Benefits of K8AB-TH
temperature-monitoring relay:
• Flexibility: simple and intelligent
features for temperature alarm.
• Easy to set up, field-configurable DIP
switch for multi-input and unit selection.
• Space-saving design, compact and slim
(22.5 mm wide) DIN-rail & direct panel
mounting.
• Only 4 application-specific models,
high- and low-temperature range,
24 V or 100-240 V.
• Change-over type output relay, with or
without latching and front button reset.
• Self protecting against power or unit
failure thanks to selectable relay
fail-safe mode.
• Clear status indication;
one LED for power and SV protection,
one LED for alarm and unit condition.
For control
Temperature guard non latching
Temperature ‘policeman’ latching
K8AB-TH models
Model Supply voltage Setting accuracy Temperature setting range Input type
K8AB-TH11S 100 to 240 VAC
1°C/°F 0 to 399°C/°F Thermocouple (K, J, T, E) / PT100
K8AB-TH11S 24 VAC/VDC
K8AB-TH12S 100 to 240 VAC
10°C/°F 0 to 1700°C/0 to 3200°F Thermocouple (K, J, T, E, B, R, S, PLII)
K8AB-TH12S 24 VAC/VDC
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 www.omron-industrial.com
Austria
Tel: +43 (0) 1 80 19 00
www.omron.at
Belgium
Tel: +32 (0) 2 466 24 80
www.omron.be
Czech Republic
Tel: +420 234 602 602
www.omron.cz
Denmark
Tel: +45 43 44 00 11
www.omron.dk
Finland
Tel: +358 (0) 9 549 58 00
www.omron.fi
France
Tel: +33 (0) 1 56 63 70 00
www.omron.fr
Germany
Tel: +49 (0) 2173 680 00
www.omron.de
Hungary
Tel: +36 (0) 1 399 30 50
www.omron.hu
Italy
Tel: +39 02 32 68 777
www.omron.it
Middle East & Africa
Tel: +31 (0) 23 568 11 00
www.omron-industrial.com
Netherlands
Tel: +31 (0) 23 568 11 00
www.omron.nl
Norway
Tel: +47 (0) 22 65 75 00
www.omron.no
Poland
Tel: +48 (0) 22 645 78 60
www.omron.pl
Portugal
Tel: +351 21 942 94 00
www.omron.pt
Russia
Tel: +7 495 745 26 64
www.omron.ru
Spain
Tel: +34 913 777 900
www.omron.es
Sweden
Tel: +46 (0) 8 632 35 00
www.omron.se
Switzerland
Tel: +41 (0) 41 748 13 13
www.omron.ch
Turkey
Tel: +90 (0) 216 474 00 40
www.omron.com.tr
United Kingdom