open collector)
L7:Linear output, 0 to 5 VDC (see note)
L8:Linear output, 0 to 10 VDC (see note)
L9:Linear output, 0 to 5 VDC + 5 transistor outputs (NPN open
collector)
L10: Linear output, 0 to 10 VDC + 5 transistor outputs (NPN open
collector)
FLK1: Communication RS-232C (see note)
FLK2: Communication RS-485 (see note)
FLK3: Communication RS-422 (see note)
FLK4: RS-232C + 5 transistor outputs (NPN open collector)
FLK5: RS-485 + 5 transistor outputs (NPN open collector)
FLK6: RS-422 + 5 transistor outputs (NPN open collector)
Period MeterK3NPB-193
Ordering Information
■ Base Unit
Input typeNPN/Voltage pulsePNP
Supply voltage100 to 240 VAC12 to 24 VDC100 to 240 VAC12 to 24 VDC
Basic Models
These models provide a
present value LED and
front-panel control keys. Can
be connected to any Output
Board, or can be used for
display only without an
Output Board.
Set Value LED Models
These models provide a
present value LED, set value
LED, and front-panel control
keys. Can be connected to
Relay, Transistor, or
Combination Output Boards.
■ Available Output Board Combinations
Output typeOutput configurationOutput boardsBase units
Relay contact3 outputs: H, PASS, L (SPDT)K31-C1YesYes
5 outputs: HH, H, L, LL (SPST-NO), and PASS (SPDT)K31-C2YesYes
5 outputs: HH, H, L, LL (SPST-NC), and PASS (SPDT)K31-C5YesYes
Transistor5 outputs (NPN open collector)K31-T1YesYes
5 outputs (PNP open collector)K31-T2YesYes
BCD (see note)5-digit output (NPN open collector)K31-B2Yes---
Linear4 to 20 mA DCK31-L1Yes---
1 to 5 VDCK31-L2Yes--1 mV/10 digitsK31-L3Yes--0 to 5 VDCK31-L7Yes--0 to 10 VDCK31-L8Yes---
Communication boards
(see note)
Combination output and
communication boards
RS-232CK31-FLK1Yes--RS-485K31-FLK2Yes--RS-422K31-FLK3Yes--BCD output + 5 transistor outputs (NPN open collector)K31-B4YesYes
4 to 20 mA + 5 transistor outputs (NPN open collector)K31-L4YesYes
1 to 5 V + 5 transistor outputs (NPN open collector)K31-L5YesYes
1 mV/10 digits + 5 transistor outputs (NPN open collector)K31-L6YesYes
0 to 5 VDC + 5 transistor outputs (NPN open collector)K31-L9YesYes
0 to 10 VDC + 5 transistor outputs (NPN open collector)K31-L10YesYes
RS-232C + 5 transistor outputs (NPN open collector)K31-FLK4YesYes
RS-485 + 5 transistor outputs (NPN open collector)K31-FLK5YesYes
RS-422 + 5 transistor outputs (NPN open collector)K31-FLK6YesYes
K3NP-NB1AK3NP-NB2AK3NP-PB1AK3NP-PB2A
K3NP-NB1CK3NP-NB2CK3NP-PB1CK3NP-PB2C
BasicSet Value
LED Display
Note: For details, refer to the Communication Operation Manual.
B-194Period Meter K3NP
Specifications
■ Ratings
Supply voltage100 to 240 VAC (50/60 Hz); 12 to 24 VDC
Operating voltage range85% to 110% of supply voltage
Power consumption (see note)15 VA max. (max. AC load with all indicators lit)
Sensor power supply80 mA at 12 VDC±10%
Insulation resistance20 MΩ min. (at 500 VDC) between external terminal and case.
Dielectric strength2,000 VAC for 1 min between external terminal and case.
Noise immunity±1,500 V on power supply terminals in normal or common mode ±1 µs, 100 ns for square-wave noise
Vibration resistanceMalfunction: 10 to 55 Hz, 0.5-mm for 10 min each in X, Y, and Z directions
Shock resistance
Ambient temperatureOperating:−10°C to 55°C (with no icing)
Ambient humidityOperating: 25% to 85% (with no condensation)
EMC(EMI)EN61326+A1Industry
Approved standardsUL508, CSA22.2;
WeightApprox. 400 g
Note: A K3NP with DC supply voltage requires approximately 1 A DC as control power supply current the moment the K3NP is turned ON. Do not
forget to take this into consideration when using several K3NP units. When the K3NP is not in measuring operation (e.g., the K3NP has been
just turned ON or is operating for startup compensation time), the display will read “00000” and all outputs will be OFF.
10 W max. (max. DC load with all indicators lit)
Insulation provided between inputs, outputs, and power supply.
Insulation provided between inputs, outputs, and power supply.
with 1 ns
Destruction: 10 to 55 Hz, 0.75-mm for 2 hrs each in X, Y, and Z directions
2
Malfunction: 98 m/s
Destruction: 294 m/s
Storage:−20°C to 65°C (with no icing)
Emission Enclosure:CISPR 11 Group 1 class A: CISRP16-1/-2
Emission AC Mains:CISPR 11 Group 1 class A: CISRP16-1/-2
(EMS)EN61326+A1Industry
Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2)
Immunity Fast Transient Noise:EN61000-4-4:2 kV (power line) (level 3)
Immunity Burst Noise:1 kV line to line (I/O signal line)
Immunity Surge:EN61000-4-5:1 kV line to line
Immunity Conducted Disturbance EN61000-4-6:3 V (0.15 to 80 MHz) (level 2)
Immunity Voltage Dip/Interrupting EN61000-4-11:0.5 cycles, 0, 180°, 100% (rated voltage)
Conforms to EN61326+A1, EN61010-1 (IEC61010-1)
Conforms to VDE0106/P100 (finger protection) when the terminal cover is mounted.
Max. displayed digits5 digits (0 to 99999)
Display7-segment LED
Polarity displayNot available
Zero displayLeading zeros are not displayed.
Prescale function
HOLD functionsMax. value (peak) hold, Min. value (bottom) hold
External controlHOLD (Process value held)
Other functionsVariable linear output range (for models with linear outputs only) (see note)
Output configurationRelay contact output (3 or 5 outputs)
Delay in comparative
outputs (at transistor output)
Linear output response time 40 ms max.
Degree of protectionFront panel: NEMA4 for indoor use (equivalent to IP66)
Memory protectionNon-volatile memory (EEPROM) (possible to rewrite 100,000 times)
Note: The linear output range cannot be set when connected to a 1 mV/10-digit Linear Output Board.
Voltage pulse (50 kHz max., ON/OFF pulse width: 9 µs min., ON voltage: 4.5 to 30 V/OFF voltage: −30 to 2 V)
Open collector (50 kHz max., ON/OFF pulse width: 9 µs min.)
Connectable Sensors
ON residual voltage: 3 V max.
OFF leakage current: 1.5 mA max.
Load current:Must have switching capacity of 20 mA min.
±0.08%rdg±1 digit
Operating mode 1: Passing speed10 ms to 3,200 seconds
Operating mode 2: Cycle20 ms to 3,200 seconds
Operating mode 3: Time difference10 ms to 3,200 seconds
Operating mode 4: Elapsed time10 ms to 3,200 seconds
Operating mode 5: Length measurement 0 to 4G count (32-bit counter)
Operating mode 6: Interval0 to 4G count (32-bit counter)
Programming via front-panel key inputs. (0.0001 x 10
Can be set using prescale value teaching.
RESET (Maximum/minimum data reset)
BANK (Selection of one bank out of 4 banks of set values)
(Selection of one bank out of 4 banks of prescale values)
Remote/Local processing (available for communications output models only)
Maximum/Minimum value data reset with front panel keys
Comparative output pattern selection
Time unit display
Security
Transistor output (NPN and PNP open collector), BCD (NPN open collector)
Parallel BCD (NPN open collector) + transistor output (NPN open collector)
Linear output (4 to 20 mA, 1 to 5 V) + transistor output (NPN open collector)
Communication functions (RS-232C, RS-485, RS-422)
Communication functions (RS-232C, RS-485, RS-422) + transistor output (NPN open collector)
20 ms max.
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Must be able to dependably switch a load current of 5 mA max.
−9
to 9.9999 x 109, decimal point can be set freely)
B-196Period Meter K3NP
■ Input/Output Ratings
Relay Contact Output
(Incorporating a G6B Relay)
ItemResistive load (cosφ = 1)Inductive load (cosφ = 0.4, L/R = 7 ms)
Rated load5 A at 250 VAC; 5 A at 30 VDC1.5 A at 250 VAC, 1.5 A at 30 VDC
Rated carry current5 A max. (at COM terminal)
Max. contact voltage380 VAC, 125 VDC
Max. contact current5 A max. (at COM terminal)
Max. switching capacity1,250 VA, 150 W375 VA, 80 W
Min. permissible load
(P level, reference value)
Mechanical life50,000,000 times min. (at a switching frequency of 18,000 times/hr)
Electrical life
100,000 times min. (at a rated load switching frequency of 1,800 times/hr)
12 to 24 VDC
+10%
/
–15%
Input current with no-voltage input10 mA
Signal levelON voltage: 1.5 V max.
Rated load voltage
Max. load current10 mA
Leakage current100 µA max.
OFF voltage: 3 V min.
12 to 24 VDC
+10%
/
−15%
Timers
Linear Output
Item4 to 20 mA1 to 5 V1 mV/10 digits (see note)
Resolution4,096
Output error±0.5% FS±1.5% FS
Permissible load resistance600 Ω max.500 Ω min.1 KΩ min.
Note: For the 1 mV/10-digit output, the output voltage changes for every 40 to 50 increment in the display value.
■ Communications Specifications
ItemRS-232C, RS-422RS-485
Transmission method4-wire, half-duplex2-wire, half-duplex
Synchronization methodStart-stop synchronization
Baud rate1,200/2,400/4,800/9,600/19,200/38,400 bps
Transmission codeASCII (7-bit)
CommunicationsWriteComparative set value, prescaling value, remote/local programming, reset control of maximum/mini-
ReadProcess value, comparative set value, maximum value, minimum value, model data, error code, and
For details, refer to Communication Operation Manual.
mum values, and other setting mode items excluding communications conditions.
others
Period MeterK3NPB-197
Connections
■ Terminal Arrangement
Output unit
Output
unit
Input
unit
Terminal Numbers
18 19 20 21 22 23 24 25 26
10 11 12 13 14 15 16 17
123456789
Input Unit
12 VDC
80 mA
Signal input terminal
NPN Inputs
External
sensor
power
supply (+)
Input A
Input B
External
sensor
power
supply (−)
+12 V
10
820 Ω
1
820 Ω
2
11
GND
Input unit
100 to 240 VAC
or 12 to 24 VDC
Note: Check the power supply specifications of the
model used before connecting the power supply.
Recommended 24VDC power supply;
eg. OMRON S8VS
Voltage Pulse Inputs
+12 V
10 k Ω
3
Input A
Input B
10 k Ω
4
11
GND
590 Ω
590 Ω
+12 V
Internal circuits
Note: Terminals 7 to 13 are connected internally.
Terminals 7 and 11 are mutually isolated.
When inputting the external control signals through the open
collector:
Transistor Inputs:
ON: Residual voltage must be 3 V max.
OFF: Leakage current must be 1.5 mA max.
The switching capacity must be 20 mA or greater.
When the external signal input is short-circuited, a voltage of
approximately 5 V will be applied to between the terminals 5 to
7 and the COM terminal, and a current of approximately 18 mA
(nominal value) will flow.
PNP-input Models
External
sensor
power
supply (+)
Input A
Input B
External
sensor
power
supply (−)
+12 V
10
1
820 Ω
590 Ω
+12 V
2
820 Ω
11
GND
590 Ω
GND
Internal circuits
GND
820 Ω
820 Ω
GND
GND
+12 V
590 Ω
+12 V
590 Ω
Internal circuits
(NPN Linear 2-wire Output)
10 1 1
1234
+12 V
INAINB
0 V
Note: When the contact is short-
NPN output sensor
Note: Connect the + side of the NPN
linear 2-wire input to terminal 1
and the − side to terminal 11.
B-198Period Meter K3NP
Contact OutputVoltage OutputPNP Open Collector OutputNPN Open Collector Output
10 11
1234
INAINBGND
Contact
circuited, a current of approximately 13 mA will flow at a voltage of approximately 12 V.
Input resistance: 10 kΩ
10 11
+12V
1234
INA INB
0 V
Voltage pulse output sensor
Note: With voltage pulse input
not from a 3-wire sensor,
connect the + side to terminal 3 and the − side to
terminal 11.
+12V
10 11
1234
INAINB
0 V
PNP output sensor
Output Units
K31-C1: Relay (3 Outputs)
Outputs (5 A max. at 250 VAC)
HPASSL
1819202122232425 26
K31-C5: Relay (5 Outputs)
18 1920212223242526
Outputs (5 A max. at 250 VAC)
H
HHPASSL
LL
K31-T2: Transistor (PNP Open Collector)
Outputs (50 mA max. at 24 VDC)
HHH PASS LLL COM
181920212223242526
K31-L1, L2, L3,-L4, -L5, -L6, -L7, -L8, -L9,
-L10: Linear
(Terminals 21 to 26 are provided only on K31-L4,
-L5, -L6, -L9, -L10.)
L1, L4: 4 to 20 mA
L2, L5: 1 to 5 V
L3, L6: 1 mV/10 digit
L7, L9: 0 to 5 VDC
L8, L10: 0 to 10 VDC
• D-sub 9P connectors for RS-232C output (K31-FLK4) (order
separately)
Plug: XM2D-0901
Hood: XM2D-0911
SD
RD
SG
K31-FLK3, -FLK6: RS-422
(The right connector is provided only on K31-FLK6)
Output NPN Tr.
(50 mA max. at 24 VDC)
SDB
LL
6
789
12345
H
HH
COM
PASS
L
Terminator
ON
OFF
RS-422
RS-422
RDA
6
789
1
2345
RDB
SDA
SG
K31-FLK4: RS-232C + Transistor (NPN Open Collector)
Output NPN Tr.
RS-232C
87
9
5
4321
SG
SD
(50 mA max. at 24 VDC)
6
RD
87
9
5
4321
L
PASS
COM
LL
6
H
HH
Period MeterK3NPB-199
■ Block Diagram
Power supply
for sensor
Sensor A
Sensor B
GND
Control input
Control power
supply
Input circuit
Control input
circuit
Power supply
circuit
Frequency
measurement
circuit
Waveform
adjustment
circuit
Voltage stabilizing
circuit
Voltage stabilizing
circuit
Voltage stabilizing
circuit
Key
switch
8-bit
microcomputer
Power supply for
sensor (input circuit)
Frequency measurement circuit
Waveform adjustment circuit
8-bit microcomputer
Control input circuit
LED
Output
circuit
B-200Period Meter K3NP
Operation
■ Main Functions
Output Pattern Selection c-out
The patterns of comparative output are selectable according to the
level change. Select the pattern according to the application.
Standard Output
Set value HH
Set value H
Set value L
Set value LL
Comparative output HH
Comparative output H
PASS
Comparative output L
Comparative output LL
Zone Output
Set value HH
Set value H
Set value L
Set value LL
Comparative output HH
Comparative output H
PASS
Comparative output L
Comparative output LL
Level Output
Set value HH
Set value H
Set value L
Set value LL
Remote/Local Selection r-l
Select remote programming when performing all settings through the
host devices and select local programming when performing settings
through key operation.
Prescaling
Input pulses are converted into desired values.
Timers
Comparative output HH
Comparative output H
Comparative output L
Comparative output LL
PASS
Note: The following setting conditions must be satisfied, otherwise no
zone output will turn ON correctly.
LL < L < H < HH
Linear Output Range lset
A linear output range can be set as required. A value corresponding
to the maximum output value and that corresponding to the minimum
output value can be set.
20 mA
Output
4 mA
Lower
limit
Upper
limit
For the 4- to 20-mA
output type
Display
Period MeterK3NPB-201
■ BCD Output Timing Chart
A request signal from an external device (such as a Programmable Controller) is required to read BCD data.
Single Sampling Data Output
Pulse with a width of no less than 20 ms.
REQ.
Max.
Min.
All data "high"All data "high"Data
DATA
DATA
VALID
Approximately 30 ms after the REQ signal rises, a sample is taken and the DATA VALID signal is output. Read the data when the DATA VA LID
signal is ON.
The DATA VALID signal will turn OFF in 40 ms, and then in 16 ms, the data will go OFF.
Models with a BCD output have an open collector output configuration so that wired-OR connection is possible.
K3NP (1)
K3NP (2)
K3NP (3)
(no more than 50 ms.)
Approx. 30 ms
Programmable
controller
40 ms
16 ms
DATA (incl. POL and OVER)
and DATA VALID are wired-OR
processed.
The RUN, HH, H, PASS, L, and
LL signals are always output
regardless of the status of the
REQ signal. Do not OR-wire
these signals.
REQ.
(1)
REQ.
(2)
REQ.
(3)
DATA
DATA
VALID
(1)(2)
***
*The period between the DATA VALID signal and the
REQ signal should be no less than 20 ms max.
(3)
Continuous Data Output
REQ.
Max.
Min.
All data "high"
DATA
DATA
VALID
Approx.
30 ms
The K3NP outputs each measurement at an interval of 64 ms when a REQ signal is ON continuously.
If the HOLD signal is ON at the moment the DATA output is switched from Data 1 to Data 2 or vice versa, the output BCD data will be either Data
1 or Data 2 according to the timing of the HOLD signal. However, output data will never be below.
Data 1Data 2
40ms40ms
24ms
64ms64ms
24ms
B-202Period Meter K3NP
Example of Connection to Programmable Controller
+5 V
K3NP
240 Ω
240 Ω
1. COMMON
2. 1
3. 2
0
10
4. 4
5. 8
23. DATA VALID
24. RUN
25. COMMON
26. REQUEST
PC (SYSMAC)
DC Input Unit
COM
IN
IN
IN
IN
IN
IN
Transistor Output Boards
OUT
Timers
Internal circuit
240 Ω
240 Ω
30. RESET
31. POLARITY
(Polarity: +, −)
OUT
COM
(0 V)
24 VDC
+24 V
DC power supply*
0 V
Internal circuit
* Recommended
Power supply;
eg. OMRON S8VS
Internal circuit
Period MeterK3NPB-203
Example of Connection to Display Unit
K3NP
1.COMMON
2.1
3.2
0
10
4.4
5.8
23.DATA VALID
24.RUN
25.COMMON
+5V
240 Ω
240 Ω
26.REQUEST
2
10
Connected
1
10
240 Ω
240 Ω
30.RESET
31.POLARITY
(Polarity: +, −)
V
D
O
V
B
A
C
O
LE
DP
8
M7E-01D@N2 or M7E-01H@N2
M7E Digital Display Unit
D
8
C
B
A
V
LE
DP
SEC
O
V
B
A
C
D
O
LE
DP
8
B-204Period Meter K3NP
■ Output Operation Timing in RUN Mode (Relay or Transistor Outputs)
The following timing chart is for a 5-comparative Output Board when the standard output pattern in selected.
HH set value
H set value
L set value
LL set value
RESET
HH comparative output
H comparative output
PASS output
L comparative output
LL comparative output
0
Display
Reset display
Display value
%%%%%
Note: Because measuring is not continuous, the comparative output turns ON when the measuring operation is completed.
Timers
■ Operating Modes
The K3NP provides 6 operating modes for converting input pulses to display values. The mode can be selected via key operations on the front
panel.
The time between pulses or the pulse ON time is measured using the
internal system clock, and time and other display values are calculated accordingly.
Example: F1 Passing Speed
INA
INB
T
System
clock
Operating mode no.Use
01Passing speed
02Cycle
03Time difference
04Elapsed time
05Length measurement
06Interval
The time (T) between the INA pulse and the INB pulse is counted
using the internal system clock.
If the count between the pulses is 100,000, then
T = System clock pulse (0.5 µs) x 100,000
= 0.05 s
For operating mode 1 (Passing Speed), 1/T x 60 (m/min) is used.
The display value is thus 1/0.05 s x 60, or 1,200 (m/min)
Period MeterK3NPB-205
Operating Mode 1: Passing Speed
The inverse of the time between input A coming ON and input B
coming ON is multiplied by 60 and displayed.
A 20-ms recovery time (T
ment operation.
Input A
) is required at the start of each measure-
R
Application Example
Measuring the Speed of Workpieces between Points A
and B
Input B
T
T
T
1
2
R
T
3
T
R
T
4
T
R
Hold input
Display
1/T1 x 601/T2 x 601/T4 x 60
Units: mm/s; m/s; m/min; km/h; etc.
Operating Mode 2: Cycle
The period (T) of input A is displayed.
The K3NP is in measuring operation during every other period of
input A ON.
Input A
T1T
T
T
3
2
4
T
5
Hold input
Display
T
1
T
2
T
5
Units: s; min; h, min, s; min, s, 1/10 s; etc.
Operating Mode 3: Time Difference
The time between input A turning ON and input B turning ON is displayed.
A 20-ms recovery time (T
ment operation.
) is required at the start of each measure-
R
Application Example
Measuring the Rate at which Parts are Fed
Application Example
Measuring the Time Required
for Workpieces to Pass from
Point A to Point B
Can be Used with Prescaling to Measure Lengths of
Steps
Input A
Input B
T
T
2
T
1
R
T
3
T
R
T
4
T
R
Hold input
Display
T
1
T
3
Units: s; min; h, min, s; min, s, 1/10 s; etc.
Operating Mode 4: Elapsed Time
The time (T) that input A is ON is displayed.
A 20-ms recovery time (T
ment operation.
Input A
Hold input
Display
Units: s; min; h, min, s; min, s, 1/10 s; etc.
) is required at the start of each measure-
R
T
T
1
2
T
R
T
T
1
T
R
3
T
3
T
4
Application Example
Monitoring the Time That
a Press is Activated
Controlling the Time
That a Valve is Open
Communication
output
B-206Period Meter K3NP
Operating Mode 5: Length Measurement
The number of pulses received on input A while input B is ON is displayed.
12345612345
Input A
Input B
Hold input
Application Example
Measuring Workpiece Length
BCD
To PC
Timers
Display
Units: mm; cm; m; etc.
65
Operating Mode 6: Interval
The number of pulses received on input A between two pulses on
input B is displayed.
123456123456
Input A
Input B
Hold input
Display
Units: mm; cm; m; etc.
66
Application Example
Measuring Slot Spacing
H
PA SS
L
Pass/fail
determination
Period MeterK3NPB-207
Nomenclature
1. SV Display
2. PV Display
3. Comparative Output
Status Indicators
4. SV Display Status
5. ESC Key
6. Mode Key
NameFunctions
1. SV displayDisplays the set value or parameter. Available for Set Value LED Models only.
2. PV displayDisplays the process value in addition to the maximum value or parameter.
3. Comparative output
status indicators
4. SV display statusIndicates which comparative set value is currently on the SV display.
5. ESC KeyUsed to return to the RUN mode from the Setting, Protect, or Maintenance mode.
6. Mode KeyUsed to enter the Setting mode.
7. Status indicatorsHOLD:Lit when HOLD input is ON.
8. Teaching indicatorLit when the teaching function is enabled and flashes when the K3NP is in teaching operation.
9. RESET/TEACH KeyThe measurement data, maximum value, and minimum value are reset by pressing this key.
10. Up Key and Shift KeyThe digit being set is scrolled by pressing the Shift Key. The set value increases by one whenever the Up Key is
Displays the status of comparative output.
The process value, maximum value, or minimum value to be displayed can be selected.
Used to allow the PV display to indicate set values sequentially. Available for Basic Models only.
Used to indicate set values sequentially on the SV display. Available for Set Value LED Models only.
MAX:Lit when the maximum value is indicated on the PV display.
MIN:Lit when the minimum value is indicated on the PV display.
PROG:Lit or flashes while parameters are being set.
Teaching is available when the teaching function is enabled.
pressed.
7. Status Indicators
8. Teaching Indicator
9. RESET/TEACH Key
10. Up Key and Shift Key
B-208Period Meter K3NP
Engineering Data
Derating Curve for Sensor Power Supply
Timers
Max. current (mA)
Ambient temperature (°C)
Dimensions
Note: All units are in millimeters unless otherwise indicated.
PV Display
14.2
8.2
Note:
The derating curve shown is for standard installation.
The derating curve depends on the mounting direction.
Panel Cutouts
+0.8
45
−0
+0.8
92
−0
75
Note: The K3NP uses M3.5 terminals.
A terminal cover is provided.
120
Period MeterK3NPB-209
Precautions
!WARNING
Do not touch any of the terminals while the power is being supplied. Doing so may result in electric shock.
!Caution
Do not allow metal objects or conductive wire cuttings to enter the
product. Doing so may result in electric shock, fire, or malfunction.
!Caution
Do not attempt to take the product apart or touch any internal parts
while the power is being supplied. Doing so may result in electric
shock.
!Caution
Do not use the product in locations subject to flammable or explosive gases. Doing so may result in explosion.
!Caution
The lifetime of output relays varies greatly with the switching capacity and conditions. Consider the actual operating conditions,
and use the relays within the rated load without exceeding the
number of operations specified as the rated electrical life. Using
relays beyond their rated electrical life may result in contact deposit or burning.
!Caution
Do not use loads exceeding the rated value. Doing so may result
in damage or burning.
!Caution
Use a power supply voltage within the specified range. Not doing
so may result in damage or burning.
!Caution
Use settings that are appropriate for the control system. Discrepancies between the settings and the actual control conditions may
result in unexpected operation leading to damage or accidents.
!Caution
Be sure to tighten terminal screws to the specified torque.
Specified torque for M3.5 screws: 0.74 to 0.90 N·m
Loose screws may result in burning or malfunction.
■ Application Precautions
• Use a power supply voltage within the specified range. Not doing
so may result in damage or burning.
• Be sure to perform wiring correctly, verifying the terminal names.
Incorrect wiring may result in burning.
• Be sure to tighten the screws on the terminal block properly.
• Do not connect anything to unused terminals.
■ Correct Use
Long-term Use
Use all products within the specified ranges. When using inside a
control panel, ensure that the temperature around the product, rather
than the temperature around the control panel, does not exceed the
specified temperature range. Electronic products, such as this product, have a lifetime that is dependent on the lifetime of internal electronic components, as opposed to the lifetime related to the number
of relay switching operations. The lifetime of these components varies with the temperature; the higher the temperature, the shorter the
lifetime. Therefore, the product lifetime can be extended by lowering
the internal temperature of the product.
When several Period Meters are mounted close together (either horizontally or vertically), the internal temperature of the Period Meters
may rise, leading to a reduction in the lifetime. In this case, take measures to cool the Period Meters, such as installing fans. Ensure, however, that the terminals are not cooled as this may lead to incorrect
measurement.
Operating Environment
Do not use the product in locations subject to temperatures or humidity levels above the specified ranges, or in locations subject to condensation.
Do not use the product in locations subject to severe shocks or vibrations.
Separate the product from machines that generate high-frequency
noise, such as high-frequency welding machines and high-frequency
sewing machines.
Do not use the product in locations subject to dust or corrosive
gases.
Do not use the product outdoors or in locations subject to direct sunlight.
Operation
When using models with comparative outputs, if an error occurs at
the Period Meter, comparative output may not operate correctly. We
therefore recommend that you consider providing an alarm system
separately as a countermeasure.
Parameter settings that allow the functions to operate properly are
made, using the setting menu, at the factory prior to delivery. When
using the product, change the settings as required for the application.
Mounting
Recommended panel thickness is 1 to 3.2 mm.
B-210Period Meter K3NP
Panel
Attach the mounting bracket on the left and right sides of the Period
Meter as shown in the illustration above and gradually tighten each
screw evenly in turn by considering the balance of the tightening
force until the ratchets start slipping without being further tightened.
Mount the Period Meter as horizontally as possible.
Unit Label (Provided)
No product is shipped with the unit label attached. Select a unit label
from the sheet provided and attach it to the Period Meter.
Waterproof Specifications
Products for which the degree of protection is not specified or models
with IP@0 degree of protection do not have waterproof specifications.
Noise Countermeasures
Separate the product as far as possible from machines that generate
high-frequency noise, such as high-frequency welding machines and
high-frequency sewing machines, and machines that generate
surges.
Attach surge absorbers or noise filters to noise-generating peripheral
devices (in particular, devices with inductance such as motors, transformers, solenoids, and magnet coils).
Line filter
K3NP
Power input
+
K3NP
Signal
input
−
Surge absorber
In order to prevent inductive noise, wire the lines connected to the
terminal block separately from power lines carrying high voltages or
large currents. Also, do not wire in parallel to, or in the same cable as
power lines. There are other methods that are effective for reducing
noise, such as running wires along ducts and using shield lines.
When using a noise filter for the power supply, check the voltage and
current and install as close to the Period Meter as possible.
Power input
Timers
Inductive Noise Countermeasure for Input
Line
Analog Input
+
Signal
input
Two-conductor shield wire
Temperature Input
In order to prevent the influence of induction, separate the lead wire
joining the temperature sensor and the Period Meter from power and
load lines.
Using the product near radios, television sets, or other wireless
devices may result in reception interference.
Processor
−
Period MeterK3NPB-211
Operating Procedures
■ Operation in RUN Mode
Reset
The initial status before any measurements were made can be
returned to using the RESET/TEACH Key . (This status is
RESET
/TEACH
referred to as the "reset status.") The status of the K3NP when it is in
the reset status is as follows:
Display: All 5 digits in the PV display are 0 (00000).
Comparative output: HH, H, PASS, L, and LL outputs are all OFF.
Maximum/minimum values: These values are reset.
Checking the Bank Number
Press the Shift Key for 1 s min. during measurement to display
the bank number in the PV display. (The display will return to the
measurement value if there is no key operation for 5 seconds.)
Bank Selection
BANK1
BANK2
COM
• Switch between the comparative set values and the prescaling val-
ues for banks 1 to 4 using the BANK 1 and BANK 2 signals.
• The relationship between the BANK 1 and BANK 2 signals and the
Note: If the prescale value bank is set to OFF, then the prescaling val-
ue for each bank is fixed.
Confirming Maximum and Minimum
Values
Press the ESC Key during measurement to display the maximum and minimum values.
Measurement
value
Press the RESET/TEACH Key while the maximum or minimum
Maximum
value
RESET
/TEACH
Minimum
value
value is displayed to reset the value. (This is not possible, however, if
maximum/minimum value reset was prohibited in Protect Mode.)
Confirming and Setting Comparative Set Values
When the measurement value, the maximum value, or the minimum value is displayed, press the Mode Key repeatedly to display the comparative set values in the order HH, H, L, and LL. (With models that have an SV display, the comparative set values are displayed in the SV display.)
Measurement value
Maximum value
Minimum value
Comparative
set value HH
No key operation for 5 s
Comparative
set value H
No key operation for 5 sNo key operation for 5 s
Note: When a comparative set value is displayed, it can be changed using the Up Key and Shift Key (if key protection is OFF).
Comparative
set value L
Comparative
set value LL
No key operation for 5 s
B-212Period Meter K3NP
■ Setting Procedures
The K3NP has four modes: RUN mode for normal operations, Setting mode for initial parameter input, Protect mode for lock-out configuration, and
Maintenance mode for initializing set values. The parameters that are accessible on any individual K3NP will vary depending on the Output Board
installed. Refer to the K3NP Operation Manual for details.
RUN Mode:Remains in this mode under normal operation.
Setting Mode:Used for making initial settings.
Protect Mode:Used for locking the front key operation or parameter changes.
Maintenance Mode:Used for initializing set values.
The process value or the max./min. value can be monitored.
Using the front panel keys, the comparative set value can be changed and max./min. values reset can be performed.
Includes settings for four menus (Set value (sUset), prescaling (pscl), setup (setup), option (opt)) and the output test.
When power is ON
Power ON
+
Maintenance mode
ESC
RUN mode
ESC
+
1 s
Timers
ESC
1 s
Setting mode
sUset - Program set values
s.bank Select bank no. of set values
sU*.hh Enter set value HH of bank 1
sU*. h Enter set value H of bank 1
sU*. l Enter set value L of bank 1
sU*. ll Enter set value LL of bank 1
Note: The above is an example when the bank number is set to 1.
pscl - Display prescaling
p.bank Select bank no. of prescale values
ps*.ax Set the mantissa (X) of the prescale value of input A
ps*.ay Set the exponent (Y) of the prescale value of input A
decp.* Select decimal point
Note: The above is an example when the bank number is set to 1.
setup - Program operating mode/input sensor/serial communications
funcSpecify operating mode
inaSelect a sensor type of input A
inbSelect a sensor type of input B
timeSelect the display time unit
u-noEnter the unit no. for the host
bpsSelect the baud rate
lenSelect the word bit length
sbitSelect the stop bits
prtySelect the parity bits
opt - Supplementary settings related to display or control
c-outSelect the output pattern
lset.h Enter the upper limit (H) of linear output range
lset.l Enter the lower limit (L) of linear output range
r-lSelect the remote/local programming
test - Generating simulated input for testing the output function
ESC
Protect mode
prot - Program lock-out configuration
allEnable all key protection
sUsetEnable set value change prohibition
resetEnable prohibition of all the measurement data and
max./min. value reset using the front panel keys
secrSpecify the menus to be protected against setting in the
setting mode
Period MeterK3NPB-213
■ Initial Settings■ Parameters
h.mm.55
Power ON
Press the Mode Key for 1 s min. to move to the Setting
Mode.
Select the setup menu ( ) with the Mode Key
and set the operating mode, the input type, the time unit, and
other settings.
If required, set a prescale value in the prescaling menu
( ).
Set comparative set values in the set value menu ( ).
Make settings in the option menu ( ) as required.
If necessary, generate simulated input for testing the output
function in output test ( ).
After completing all the settings, press the
ESC Key to return to RUN Mode.
Power ON
RUN Mode
Refer to Operation in RUN Mode.
Setting Mode
1 s
Set value menu
1 s
Comparative set
value bank
Comparative
set value HH
Comparative
set value H
Comparative
set value L
Comparative
set value LL
Press the ESC Key and Up Key
for 1 s.
(See note 1.)
(See note 1.)
(See note 1.)
(See note 1.)
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
−
−
0
−
0
−
0
−
0
Measurement starts.
Prescaling
To display the passing speed between two points based on
input pulses, the time measured internally must be multiplied
by a fixed coefficient. The value of this coefficient will depend
on the distance between the two points and the display unit.
This coefficient is called the "prescale value." (Refer to the
Operation Manual for details.)
Time Unit Setting
Setting
Set in the prescaling menu
Seconds
Minutes
Minutes and seconds
Hours, minutes, and seconds
h.mm.55
Meaning
Selecting the Sensor Type
NO: Voltage
NC: Voltage
pulse H
pulse L
No-contact or
voltage pulse
input
Contact input
Note: If there are large discrepancies
in the display select or .
Note, however, that the
maximum counting frequency is
30 Hz.
Output test
B-214Period Meter K3NP
func
f1
Changing Set Values
5cal
p5cl
By pressing the Shift Key while a parameter is displayed, the set value can be
changed (setting status). The PROG status indicator will flash. Change the set
value as required, and press the Mode Key to register the setting and move to
the next parameter.
Timers
Protect Mode
Prescaling menu
1 s
Prescale value
bank (See note 2.)
Input A prescale
value mantissa
Input A prescale
value exponent
Decimal point
(See note 1.)
(See note 1.)
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
(See note 1.)
No key operation for 5 s
func
Next parameter
−
−
−
Setting Status
If there is no key operation for
5 seconds, the setting is
registered and the parameter
is displayed again.
Setup menu
−
−−
Change the set value
using the Up Key and
f1
the Shift Key .
PROG flashes.
1 s
Operating
mode
Input A
sensor type
Input B sensor
type (See note 4.)
Time unit
(See note 3.)
Communications
unit number
Baud rate
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
1200/2400/4800/
9600 /19200/38400bps
No key operation for 5 s
−
−
Option menu
1 s
Output pattern
Upper limit (H) of
linear output range
Lower limit (L) of
linear output range
Remote/local programming
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
No key operation for 5 s
//
−
0
−
0
/
Word bit length
Stop bits
Parity bits
No key operation for 5 s
No key operation for 5 s
7 /8bit
1/ 2 bit
//
• In the Setting Mode, measurement stops and all
outputs turn OFF.
• Depending on the output type of the model used,
some parameters (indicated in ) are not displayed (and hence cannot be set).
• If the operating mode is changed, the prescale val-
ues and linear output range parameters will be reset to their initial values. Set the operating mode
first.
Note 1: A number in the range 1 to 4 will be displayed.
2: Set a number in the range 2 to 4 to set more than one
prescale value (i.e., to display measurements in more than
one unit).
3. These parameters will be displayed if F2, F3, or F4
(i.e., operating mode 2, 3, or 4) is set. If a parameter other than
is set, the prescaling menu ( ) will not be displayed.
5cal
4: This parameter will be displayed if F1, F3, F5, or F6 is
selected.
p5cl
Settings displayed in reverse colors are defaults.
Period MeterK3NPB-215
prot
all
sUset
reset
secr
kpon
kpoff
Power ON
prot
all
sUset
secr
reset
kpon
kpoff
kpon kpoff
0 1 2
RUN Mode
Press the ESC Key
and Up Key for 1 s.
· Measurement stops in Protect Mode.
· Depending on the output type of the model used, some parameters (indicated in ) are not
displayed (and hence cannot be set).
Protect Mode
(See
note.)
kponkpoff
Set value change
prohibition
sUset
Displayed only for
models with
comparative outputs.
Reset prohibition
reset
Protect menu
prot
All key protection
1 s
Key-protection ON:
Key-protection OFF:
all
Menu displayParameter displayMeaning of parameterSetting rangeSetting key
All key protection:
All key operations are prohibited in
prot
prot
Press the Mode Key
to display the parameter.
all
all
Next parameter:
Setting:
RUN Mode. (If all key protection is
ON, only the key for going to Protect
Mode is enabled.)
Set value change prohibition:
sUset
sUset
Next parameter:
Setting:
Changes to comparative set values
are prohibited in RUN Mode. (Displayed only for models with comparative outputs.)
Menus protected
in Setting Mode
secr
Note: Press the Shift Key to make it
possible to set or change parameters.
Key protection ON:
Key protection OFF:
Use the Up Key to
change the setting.
➤
kpon kpoff
Use the Mode Key
ting and move to the
next parameter.
kpon
kpoff
(See note.)
➤
to enable the set-
Reset prohibition:
Press the ESC Key
to return to the menu.
reset
reset
Next parameter:
secr
secr
Next parameter:
Setting:
Setting:
Resetting using the front panel keys
is prohibited. (Resetting by external
signals is not prohibited.)
Menus protected in Setting Mode:
Setting operations in Setting Mode
are prohibited in the way shown below.
Setting menuSetting
012
Set value menu×
Prescaling menu×
00 /1/
Use the Up Key to
change the setting.
➤
➤
➤
0 1 2
Use the Mode Key
to enable the set-
2
ting and move to the
next parameter.
Setup menu××
Option menu×
Note: If there is no key operation for 5 seconds, the setting is automatically registered.
B-216Period Meter K3NP
■ Troubleshooting
When an error occurs, error details will be displayed in the PV display. Take the appropriate countermeasures according to the error displayed.
ContinuesContinuesContinuesContinuesIf an attempt to change a setting
BCD outputCommunications
in "H" status)
in "H" status)
in "H" status)
The OVER signal
turns ON.
output
OFFOFFReset the power. If the same error
OFFOFFReset the power while holding
OFFOFF
Continues
The OVER or UN-
DER signal turns
ON.
Linear
output
occurs, repair is necessary.
down the ESC Key, the Up Key, and
the RESET/TEACH Key. The settings will be returned to their default
values. If the same error occurs, repair is necessary.
(minimum
value)
ContinuesTake steps to ensure that the input
Reset the power. If the same error
occurs, repair is necessary. If normal operation is restored, it is possible that the original error was
caused by the influence of noise.
Check that there are no sources of
noise in the vicinity.
values and display values are within the allowable ranges.
using key operations is made with
the remote/local selection set to remote, this error will flash for 3 s. To
enable settings to be changed, set
the remote/local selection to local.
Timers
Period MeterK3NPB-217
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. N088-E1-02
In the interest of product improvement, specifications are subject to change without notice.
B-218Period Meter K3NP
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.