Omron K3MA-L 100-240VAC, K3MA-L-C 100-240VAC, K3MA-L 24VAC/VDC, K3MA-L-C 24VAC/VDC User Manual

Temperature Meter K3MA-L K-45
Panel
indicators
Temperature Meter
K3MA-L
Highly Visible LCD Display with 2-color (Red and Green) LEDs
• Front-panel key operation for easy setting.
• Average processing function suppresses flicker.
• Temperature input shift and temperature unit selection func­tions.
• Easy confirmation of max/min display.
• Short 80-mm depth (measured from edge of face plate).
• Finger protective cover (standard equipment) protects against electric shock.
• Water- and dust-proof NEMA4X (IP66 equivalent) front panel.
• Recognized to conform to U.S. and Canadian requirements un­der the Component Recognition Program of UL.
• CE marking.
Model Number Structure
Model Number Legend
1. Input Type
L: Platinum-resistance thermometer or thermocouple
2. Output Type
None: No output C: With relay contact output (SPDT)
3. Supply Voltage
100-240VAC:100 to 240 VAC 24VAC/VDC:24 VAC/VDC
Ordering Information
List of Models
Accessories (Order Separately)
12 3
K3MA-L-@
Input type Supply voltage Output Model
Platinum-resistance thermometer or thermocouple
100 to 240 VAC None K3MA-L 100-240VAC
1 relay contact output (SPDT) K3MA-L-C 100-240VAC
24 VAC/VDC None K3MA-L 24VAC/VDC
1 relay contact output (SPDT) K3MA-L-C 24VAC/VDC
Name Shape Model
Splash-proof Soft Cover K32-49SC
Hard Cover K32-49HC
K-46 Temperature Meter K3MA-L
Specifications
Ratings
K3MA-L 100-240VAC, K3MA-L-C 100-240VAC K3MA-L 24VAC/VDC, K3MA-L-C 24VAC/VDC
Supply voltage 100 to 240 VAC 24 VAC (50/60 Hz), 24 VDC Operating voltage range 85% to 110% of the rated supply voltage Power consumption
(under maximum load)
6 VA max. 4.5 VA max. (24 VAC)
4.5 W max. (24 VDC)
Insulation resistance 20 M min. (at 500 VDC) between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Dielectric strength 2,000 VAC for 1 min between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Noise immunity ±1,500 V on power supply terminals in normal or com-
mon mode.
±1 µs, or 100 ns for square-wave noise with 1 ns.
±480 V on power supply terminals in normal mode. ±1,500 V in common mode. ±1 µs, or 100 ns for square-wave noise with 1 ns.
Vibration resistance
Vibration: 10 to 55 Hz, Acceleration: 50 m/s
2
5 min each in X, Y, and Z directions for 10 sweeps.
Shock resistance
150 m/s
2
(100 m/s2 for relay contact outputs) 3 times each on 3 axes, 6 directions.
Ambient temperature Operating:−10°C to 55°C (with no condensation or icing)
Storage:25°C to 65°C (with no condensation or icing)
Ambient humidity Operating:25% to 85% (with no condensation) Approved safety standards UL3121-1, conforms to EN61010-1 (Pollution degree 2/overvoltage category II)
Conforms to VDE0106/P100 (finger protection)
EMC (EMI)EN61326+A1Industry
Emission Enclosure:CISPR 11 Group 1 class A: CISRP16-1/-2 Emission AC Mains:CISPR 11 Group 1 class A: CISRP16-1/-2
(EMS)EN61326+A1Industry Immunity ESD:EN61000-4-2:4 kV contact discharge 8 kV air discharge Immunity RF-interference:EN61000-4-3:10 V/m (amplitude-modulated, 80 MHz to 1 GHz)
Electrical Fast Transient Noise:EN61000-4-4:2 kV (power line) Immunity Burst Noise:1 kV line to line (I/O signal line)
Immunity Surge:EN61000-4-5:1 kV (power line) 2 kV line to ground (power line) Immunity Conducted Disturbance:EN61000-4-6:3 V (0.15 to 80 MHz) Immunity Voltage Dip/Interrupting:EN61000-4-11:0.5 cycle, 0, 180°, 100% (rated voltage)
Weight Approx. 200 g
Temperature Meter K3MA-L K-47
Panel
indicators
Characteristics
Note: The indication accuracy of the K thermocouple at a temperature of 200 to 1300°C is ±2°C ±1 digit maximum.
The indication accuracy of the T and N thermocouples at a temperature of −100°C or less is ±2°C ±1 digit maximum. The indicator accuracy of the U and L thermocouples at any temperature is ±2°C ±1 digit maximum. The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted. The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.
Measuring Ranges
Platinum-resistance Thermometer
Thermocouple
Indication accuracy (at 23±5°C) (See note.)
Thermocouple: (±0.5% of indication value or ±1°C, whichever greater) ±1 digit max.
Platinum-resistance thermometer: (±0.5% of indication value or ±1°C, whichever greater) ±1 digit max.
Input Thermocouple: K, J, T, E, L, U, N, R, S, B
Platinum-resistance thermometer: JPt100, Pt100 Measurement method Double integral method Sampling period 500 ms Display refresh period Sampling period (sampling times multiplied by number of averaging times if average processing is se-
lected.) Max. displayed digits 4 digits (1999 to 9999) Display 7-segment digital display, Character height: 14.2 mm Polarity display ” is displayed automatically with a negative input signal. Zero display Leading zeros are not displayed. Input shift Input shift equivalent to the setting value supported for all points within the sensor measurement range. Hold function Max hold (maximum value), Min hold (minimum value) Hysteresis setting Programmable with front-panel key inputs (0001 to 9999). Other functions Display color change (green (red), green, red (green), red)
Average processing (simple average OFF/2/4/8 operations)
Setting change lockout
Parameter initialization Output Relay contact (SPDT) Delay in comparative outputs 1 s max. Degree of protection Front panel: NEMA4X for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00 + finger protection (VDE0106/100) Memory protection Non-volatile memory (EEPROM) (possible to rewrite 100,000 times)
Input Pt100 JPt100
Range °C 200 to 850 199.9 to 500.0 0.0 to 100.0 199.9 to 500.0 0.0 to 100.0
°F 300 to 1500 199.9 to 900.0 0.0 to 210.0 199.9 to 900.0 0.0 to 210.0
Parameter 01234
Input K J T E L U N R S B
Range °C −200
to 1300
20.0 to
500.0
100 to 850
20.0
to
400.0
200 to 400
199.9 to
400.0
0 to 600
100 to 850
200 to 400
199.9 to
400.0
200 to 1300
0 to 1700
0 to 1700
100 to 1800
°F 300
to 2300
0.0 to
900.0
100 to 1500
0.0
to
750
300 to 700
199.9 to
700.0
0 to 1100
100 to 1500
300 to 700
199.9 to
700.0
300 to 2300
0 to 3000
0 to 3000
300 to 3200
Parameter56789101112131415161718
K-48 Temperature Meter K3MA-L
Input/Output Ratings
Relay Contact Output
Connections
Terminal Arrangement
Block Diagram
Item Resistive load (cosφ = 1) Inductive load (cosφ = 0.4, L/R = 7 ms)
Rated load (UL ratings) 5 A at 250 VAC, 5 A at 30 VDC 1.5 A at 250 VAC, 1.5 A at 30 VDC Rated carry current 5 A max. (at COM terminal) Max. contact voltage 400 VAC, 150 VDC Max. contact current 5 A (at COM terminal) Max. switching capacity 2,000 VA, 192 W 375 VA, 30 W Min. permissible load
(P level, reference value)
10 mA at 5 VDC
Mechanical life 20,000,000 times min. (at a switching frequency of 1,200 time/min)
Electrical life (at an ambient temperature of 20°C)
100,000 times min. (at a rated load switching frequency of 10 time/min)
Power supply
Output terminals
Input terminals
+
++
100- to 240-VAC type or 24-VAC/VDC type* (No polarity for 24-VDC connection.)
Models with comparative output
For thermocouple input
For platinum­resistance thermometer input
OUT1
A
B
B
A1
A2
E1
E2
E3
E4
E5
E6
E4
E5
E6
*Recommended DC power supply: eg. OMRON S8VS
Terminal No. Name Description
Operation power Connects the operation power supply. Thermocouple or platinum-resistance ther-
mometer input
Connects the thermocouple or platinum-resis­tance thermometer input.
Outputs Outputs the relay outputs.
A1 A2
-
E4 E6
-
E5
-
E1 E2
,
E3
-
X
5 V 12 V
Input Input
Micro­computer
Key
Display
Output circuit
Contact output (See note.)
Constant voltage circuit
Power supply circuit
EEPROM
Note: Relay output models only.
Temperature Meter K3MA-L K-49
Panel
indicators
Operation
Main Functions
Input Types and Ranges
Note: The initial value is “5: thermocouple K (200 to 1300°C/300 to 2300°F).”
Temperature Unit Selection
Either centigrade (°C) or fahrenheit (°F) can be selected as the tem­perature unit.
OUT Types (Comparative Output Models Only)
OUT 1 can be set to operate in one of the three following modes in accordance with the compared values:
Upper limit (High Acting):
The output is turned ON when the measurement value is greater than its set value.
Lower limit (Low Acting):
The output is turned ON when the measurement value is less than its set value.
Upper and lower limits (Outside Band Acting):
An upper limit (H set value) and lower limit (L set value) can be set independently. The output is turned ON when the measurement value is greater than the upper-limit set value or less than the lower-limit set value.
Parameter Setting Input type Meaning
in-t 0 Platinum-resistance
thermometer
Pt100 200 to 850°C 300 to 1500°F 1 199.9 to 500.0°C 1999 to 900.0°F 2 0.0 to 100.0°C 0.0 to 210.0°F 3 JPt100 199.9 to 500.0°C 199.9 to 900.0°F 4 0.0 to 100.0°C 0.0 to 210.0°F 5 Thermocouple K 200 to 1300°C 300 to 2300°F 6 20.0 to 500.0°C 0.0 to 900.0°F 7J−100 to 850°C −100 to 1500°F 8 20.0 to 400.0°C 0.0 to 750.0°F 9T−200 to 400°C −300 to 700°F 10 199.9 to 400.0°C 199.9 to 700.0°F 11 E 0 to 600°C 0 to 1100°F 12 L 100 to 850°C 100 to 1500°F 13 U 200 to 400°C 300 to 700°F 14 199.9 to 400.0°C 199.9 to 700.0°F 15 N 200 to 1300°C 300 to 2300°F 16 R 0 to 1700°C 0 to 3000°F 17 S 0 to 1700°C 0 to 3000°F 18 B 100 to 1800°C 300 to 3200°F
Parameter Setting Meaning
d-u
cDisplay in °C. fDisplay in °F.
Parameter Setting Meaning
out 1.t
hi Upper limit: Alarm op-
erates at upper limit.
lo Lower limit: Alarm op-
erates at lower limit.
hi-lo Upper and lower lim-
its: Alarm operates at upper and lower lim­its.
Upper Limit (High Acting) Lower Limit (Low Acting)
OUT1 value
Measurement value
ON
OFF
Output
OUT1 value
Hysteresis
Hysteresis
Hysteresis
Hysteresis
Upper and Lower Limits (Outside Band Acting)
OUT1 upper-limit value
OUT1 lower-limit value
ON
OFF
Output
ON
OFF
Output
Measurement value
Measurement value