Immunity RF-interference:EN61000-4-3:10 V/m (amplitude-modulated, 80 MHz to 1 GHz)
Electrical Fast Transient Noise:EN61000-4-4:2 kV (power line)
Immunity Burst Noise:1 kV line to line (I/O signal line)
Immunity Surge:EN61000-4-5:1 kV (power line)
Immunity Conducted Disturbance:EN61000-4-6:3 V (0.15 to 80 MHz)
Immunity Voltage Dip/Interrupting:EN61000-4-11:0.5 cycle, 0, 180
(100 m/s2 for relay contact outputs) 3 times each on 3 axes, 6 directions.
Rated load5 A at 250 VAC, 5 A at 30 VDC1.5 A at 250 VAC, 1.5 A at 30 VDC
Rated carry current5 A max. (at COM terminal)
Max. contact voltage400 VAC, 150 VDC
Max. contact current5 A (at COM terminal)
Max. switching capacity2,000 VA, 192 W375 VA, 36 W
Min. permissible load
(P level, reference value)
Mechanical life20,000,000 times min. (at a switching frequency of 1,200 time/min)
Electrical life
(at an ambient temperature of 20
10 mA at 5 VDC
100,000 times min. (at a rated load switching frequency of 10 time/min)
C)
2
■ Measuring Ranges
Platinum-resistance Thermometer
InputPt100JPt100
Range
Parameter
C
F
-
200 to 850
-
300 to 1500
-
199.9 to 500.00.0 to 100.0
-
199.9 to 900.00.0 to 210.0
-
199.9 to 500.00.0 to 100.0
-
199.9 to 900.00.0 to 210.0
Thermocouple
InputKJTELUNRSB
Range
C-
200
-
to
1300
F-
300
to
2300
Parameter
■ Characteristics
20.0
to
500.0
0.0
to
900.0
-
100
to
850
-
100
to
1500
-
20.0
to
400.0
0.0
to
750
-
200
to
400
-
300
to
700
-
199.9
to
400.0
-
199.9
to
700.0
0
to
600
0
to
1100
-
100
to
850
-
100
to
1500
-
200
to
400
-
300
to
700
-
199.9
to
400.0
-
199.9
to
700.0
-
200
to
1300
-
300
to
2300
0
to
1700
0
to
3000
0
to
1700
0
to
3000
K3MA-LK3MA-L
100
to
1800
300
to
3200
Indication accuracy (at 235C)
(See note.)
InputThermocouple: K, J, T, E, L, U, N, R, S, B
Measurement methodDouble integral method
Sampling period500 ms
Display refresh periodSampling period (sampling times multiplied by number of averaging times if average processing
Max. displayed digits4 digits (
Display7-segment digital display, Character height: 14.2 mm
Polarity display“
Zero displa yLeading zeros are not displayed.
Input shiftInput shift equivalent to the setting value supported for all points within the sensor measurement
Hold functionMax hold (maximum value), Min hold (minimum value)
Hysteresis settingProgrammable with front-panel key inputs (0001 to 9999).
Other functionsDisplay color change (green (red), green, red (green), red)
OutputRelay contact (SPDT)
Delay in comparative outputs1 s max.
Enclosure ratingsFront panel: NEMA 4X for indoor use (equivalent to IP66)
Memory protectionNon-volatile memory (EEPROM) (possible to rewrite 100,000 times)
Thermocouple:
(
0.5% of indication value or 1C, whichever greater) 1 digit max.
Platinum-resistance thermometer:
(
0.5% of indication value or 1C, whichever greater) 1 digit max.
Platinum-resistance thermometer: JPt100, Pt100
is selected.)
-
1999 to 9999)
-
” is displayed automatically with a negative input signal.
range.
Average processing (simple average OFF/2/4/8 operations)
Setting change lockout
Parameter initialization
Rear case: IEC standard IP20
Terminals: IEC standard IP0 0 + finger protection (VDE0106/100)
Note: The indication accuracy of the K thermocouple at a temperature of -200 to 1300C is 2C1 digit maximum.
The indication accuracy of the T and N thermocouples at a temperature of
The indicator accuracy of the U and L thermocouples at any temperature is
The indication accuracy of the B thermocouple at a temperature of 400
The indication accuracy of the R and S thermocouples at a temperature of 200
-
100C or less is 2C1 digit maximum.
2C
C or less is unrestricted.
1 digit maximum.
C or less is 3C1 digit maximum.
3
K3MA-LK3MA-L
Nomenclature
2. Operation indicators
1
Max
Min
3. Level indicator
4. MAX/MIN key
NameFunctions
1. Main indicatorDisplays current values, parameters, and set values.
2. Operation indicators
3. Level indicatorDisplays the current level that the K3MA-L is in. (See below for details.)
4. MAX/MIN KeyUsed to display the MAX and MIN values when a measurement value is being displayed.
5. Level KeyUsed to change the level.
6. Mode KeyUsed to allow the main indicator to indicate parameters sequentially.
7. Shift KeyUsed to enable a set value to be changed. When changing a set value, this key is used to move along the digits.
8. Up KeyUsed to change a set value. Used to set or clear a forced-zero function when a measurement value is being dis-
1Lit when output 1 is ON.
SVLit when a set value is being displayed or changed.
MaxLit when the main indicator is showing the MAX value.
MinLit when the main indicator is showing the MIN value.
R0 to 1700C0 to 3000F
S0 to 1700C0 to 3000F
B100 to 1800C300 to 3200F
K3MA-LK3MA-L
200 to 850C
199.9 to 500.0C
199.9 to 500.0C
200 to 1300C
20.0 to 500.0C0.0 to 900.0F
100 to 850C
20.0 to 400.0C0.0 to 750.0F
200 to 400C
199.9 to 400.0C
100 to 850C
200 to 400C
199.9 to 400.0C
200 to 1300C
-
300 to 1500F
-
1999 to 900.0F
-
199.9 to 900.0F
-
300 to 2300F
-
100 to 1500F
-
300 to 700F
-
199.9 to 700.0F
-
100 to 1500F
-
300 to 700F
-
199.9 to 700.0F
-
300 to 2300F
Note: The initial value is “
Temperature Unit Selection
Either centigrade (C) or fahrenheit (F) can be selected as the
temperature unit.
ParameterSettingMeaning
#4"
OUT Types (Comparative Output Models Only)
OUT 1 can be set to operate in one of the three following modes
in accordance with the compared values:
• Upper limit (High Acting):
The output is turned ON when the measurement value is greater
than its set value.
• Lower limit (Low Acting):
The output is turned ON when the measurement value is less
thermocouple K (-200 to 1300C/-300 to 2300F).”
Display in C.
%
Display in F.
• Upper and lower limits (Outside Band Acting):
An upper limit (H set value) and lower limit (L set value) can be
set independently.
The output is turned ON when the measurement value is greater
than the upper-limit set value or less than the lower-limit set value.
ParameterSettingMeaning
.433'(
Upper limit: Alarm
operates at upper
limit.
+.
Lower limit: Alarm
operates at lower
limit.
'(+.
Upper and lower
limits: Alarm operates at upper and
lower limits.
than its set value.
Upper Limit (High Acting)Lower Limit (Low Acting)Upper and Lower Limits
(Outside Band Acting)
OUT1 value
Measurement
value
Output
ON
OFF
Hysteresis
Measurement
value
OUT1 value
Output
Hysteresis
ON
OFF
OUT1 upper-limit
value
Measurement
value
OUT1 lower-limit
value
Output
Hysteresis
ON
OFF
Hysteresis
5