Ω min. (at 500 VDC) between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Insulation provided between inputs, outputs, and power supply.
±1,500 V on power supply terminals in normal or com-
mon mode.
±1 µs, or 100 ns for square-wave noise with 1 ns.
Vibration: 10 to 55 Hz, Acceleration: 50 m/s
5 min each in X, Y, and Z directions for 10 sweeps.
2
150 m/s
Storage:
Conforms to VDE0106/P100 (finger protection)
Emission Enclosure:CISPR 11 Group 1 class A: CISRP16-1/-2
Emission AC Mains:CISPR 11 Group 1 class A: CISRP16-1/-2
(EMS)EN61326+A1 Industry
Immunity ESD:EN61000-4-2: 4 kV contact discharge
Immunity RF-interference:EN61000-4-3: 10 V/m (amplitude-modulated, 80 MHz to 1 GHz)
Electrical Fast Transient Noise:EN61000-4-4: 2 kV (power line)
Immunity Burst Noise:1 kV line to line (I/O signal line)
Immunity Surge:EN61000-4-5: 1 kV (power line)
Immunity Conducted Disturbance: EN61000-4-6: 3 V (0.15 to 80 MHz)
Immunity Voltage Dip/Interrupting: EN61000-4-11: 0.5 cycle, 0, 180
(100 m/s2 for relay contact outputs) 3 times each on 3 axes, 6 directions.
−10°C to 55°C (with no condensation or icing)
−25°C to 65°C (with no condensation or icing)
2
4.5 W max. (24 VDC)
±480 V on power supply terminals in normal mode.
±1,500 V in common mode.
±1 µs, or 100 ns for square-wave noise with 1 ns.
Display7-segment digital display, Character height: 14.2 mm
Polarity display“
Zero displayLeading zeros are not displayed.
Scaling functionProgrammable with front-panel key inputs (range of display:
Hold functionMax hold (maximum value), Min hold (minimum value)
Hysteresis settingProgrammable with front-panel key inputs (0001 to 9999).
Other functionsScaling teach function
OutputRelays: 2 SPST-NO
Delay in comparative outputs750 ms max.
Degree of protectionFront panel: NEMA4X for indoor use (equivalent to IP66)
Memory protectionNon-volatile memory (EEPROM) (possible to rewrite 100,000 times)
Voltage pulse (5 kHz max., ON/OFF pulse width: 90
0 to 2 V)
Open collector (5 kHz max., ON/OFF pulse width 90
Connectable Sensors
ON residual voltage:2.5 V max.
OFF leakage current: 0.1 mA max.
Load current:Must have switching capacity of 15 mA min.
Must be able to dependably switch a load current of 5 mA max.
±0.1%FS ±1 digit (at 23±5°C)
−19999 to 99999)
−” is displayed automatically with a negative input signal.
The decimal point position can be set as desired.
Display color change (green (red), green, red (green), red)
OUT type change (upper limit, lower limit, upper/lower limit)
Average processing (simple average OFF/2/4/8 operations)
Auto-zero time
Startup compensation time
Setting change lockout
Parameter initialization
Display auto-return time
Rear case: IEC standard IP20
Terminals: IEC standard IP00 + finger protection (VDE0106/100)
µs min., ON voltage: 4.5 to 30 V/OFF voltage:
µs min.)
−19999 to 99999).
■ Measuring Ranges
No-voltage Contact/Open Collector Inputs
InputMeasuring rangeMeasuring accuracyDisplayable range
No-voltage contact (30 Hz max.) with
ON/OFF pulse width of 15 ms min.
Open collector (5 kHz max.) with
ON/OFF pulse width of 90
inp0 to 99999Input value for dspdp%.%%%%Display four digits after decimal point
dsp-19999 to 99999Display value for inp%%.%%%Display three digits after decimal point
%%%.%%Display two digits after decimal point
%%%%.%Display one digit after decimal point
%%%%%No decimal point
The initial value will change depending on the
Note:
pulse frequency selection.
Display value
DISPLAY
•
The decimal point can be optionally displayed.
•
When displaying the decimal point, consider the
number of digits to follow the decimal point prior to
setting the scaling display value.
•
If
is set to 30, the initial setting for the
p-fre
decimal display will be
000.00
.
INPUT
Input value
Teaching with actual values is possible.
Instead of setting by inputting with the Up Key and Shift Key, current values can be
input as scaling input values for teaching. This is useful for making settings while checking the
operation status of the K3MA-F.
6Frequency/Rate Meter K3MA-F