Temperature Controllers
E5CSV
Easy Setting Using DIP Switch and Simple
Functions in DIN 48 × 48 mm-size
Temperature Controllers
• Easy setting using DIP switch.
• Models with two alarms added to Series, ideal for temperature
alarm applications.
• Universal-input (thermocouple/platinum resistance
thermometer) models also available.
• Clearly visible digital display with character height of 13.5 mm.
• Models available with black in addition to white cases.
• RoHS compliant.
Model Number Structure
CSM_E5CSV_DS_E_7_1
Refer to Safety Precautions for All Temperature
Controllers.
Refer to E5CS/E5CSV Operation for
operating procedures.
■ Model Number Legend
Models with Terminal Blocks
E5CSV-@@@@-@
1. Control Outputs
R: Relay
Q: Voltage for driving SSR
2. Alarm Outputs
Blank: No alarm
1: 1 alarm
2: 2 alarms
Note: A functional explanation is provided here for illustration, but models are not necessarily available for all possible combinations. Refer to
1234 5
3. Input
KJ: Thermocouple
P: Platinum resistance thermometer
T: Thermocouple/platinum resistance
thermometer (universal-input)
Ordering Information when ordering.
Examples
• Relay control output, without alarm, thermocouple input, light gray case: E5CSV-RKJ-W
• Relay control output, one alarm output, platinum resistance thermometer input, black case: E5CSV-R1P-W
4. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
5. Case Color
Blank: Black
W: Light gray
1
E5CSV
Ordering Information
■ List of Models
Case Color: Light Gray, Thermocouple or Platinum Resistance Thermometer,
Power Supply Voltage: 100 to 240 VAC
Size Type Control
E5CSV
48 × 48mm
Terminal block ON/OFF or
modes
PID
Alarms Outputs Model with
1 Relay E5CSV-R1KJ-W E5CSV-R1P-W
Voltage (for driving SSR) E5CSV-Q1KJ-W E5CSV-Q1P-W
thermocouple
Model with platinum
resistance
thermometer
Case Color: Light Gray, Thermocouple, Power Supply Voltage: 24 VAC/VDC
Size Type Control
E5CSV
48 × 48mm
Terminal block ON/OFF or
modes
PID
Alarms Outputs Model with
thermocouple
1 Relay E5CSV-R1KJD-W
Case Color: Light Gray, Universal-input, Power Supply Voltage: 100 to 240 VAC
Size
E5CSV
48 × 48mm
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller
User’s Manual” (Cat. No. H140-E1-01).
Type Control
Terminal block ON/OFF or
modes
PID
Alarms Outputs Model with universal-
0Relay E5CSV-RT
Voltage (for driving SSR) E5CSV-QT
1Relay E5CSV-R1T
Voltage (for driving SSR) E5CSV-Q1T
2 (See note.) Relay E5CSV-R2T
Voltage (for driving SSR) E5CSV-Q2T
input (thermocouple
or platinum resistance
thermometer)
Case Color: Black, Universal-input, Power Supply Voltage: 24 VAC/VDC
Size
E5CSV
48 × 48mm
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller
User’s Manual” (Cat. No. H140-E1-01).
Type Control
Terminal block ON/OFF or
modes
PID
Alarms Outputs Model with universal-
0Relay E5CSV-RTD
Voltage (for driving SSR) E5CSV-QTD
1Relay E5CSV-R1TD
Voltage (for driving SSR) E5CSV-Q1TD
2 (See note.) Relay E5CSV-R2TD
Voltage (for driving SSR) E5CSV-Q2TD
input (thermocouple
or platinum resistance
thermometer)
■ Accessories (Order Separately)
Protective Cover
Type Model
Hard Protective Cover Y92A-48B
Terminal Cover
Model
E53-COV10
Terminal Cover
(For Controllers after the design change scheduled for October 2010)
Model
E53-COV17
Note: The E53-COV10 Terminal Cover cannot be mounted to
Controllers that are manufactured after the design change
scheduled for October 2010
Rubber Packing
Model
Y92S-29
Note: The Rubber Packing is provided with the Digital Controller.
2
Specifications
■ Ratings
Supply voltage 100 to 240 VAC, 50/60 Hz
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 100 to 240 VAC: 5 VA
Sensor input Thermocouple input type: K, J, L
Control
output
Control method ON/OFF or 2-PID (with auto-tuning)
Alarm output SPST-NO, 250 VAC, 1A (resistive load)
Setting method Digital setting using front panel keys
Indication method 7-segment digital display (character height: 13.5 mm) and deviation indicators
Other functions • Setting change prohibit (key protection)
Ambient operating temperature −10 to 55°C (with no condensation or icing); with 3-year guarantee: −10 to 50°C
Ambient operating humidity 25% to 85%
Storage temperature −25 to 65°C (with no condensation or icing)
Note: 1. Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
Relay output SPST-NO, 250 VAC, 3A (resistive load)
Voltage output (for driving the SSR) 12 VDC, 21 mA (with short-circuit protection circuit)
2. Models for 24 VAC/DC can also be manufactured.
24 VAC, 50/60 Hz; 24 VDC
24 VAC: 3 VA, 24 VDC: 2 W
Platinum resistance thermometer input type: Pt100, JPt100
Universal-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100
• Input shift
• Temperature unit change (°C/°F)
• Direct/reverse operation
• Temperature range, Sensor switching (K/J/L, Pt100/JPt100)
• Switching is performed between a thermocouple and platinum resistance thermometer for universal-input models.
• Control period switching
• 8-mode alarm output
• Sensor error detection
E5CSV
■ Characteristics
Setting accuracy Thermocouple (See note 1.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Indication accuracy
(ambient temperature of 23°C)
Influence of temperature R thermocouple inputs: (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Influence of voltage
Hysteresis (for ON/OFF control) 0.2% FS (0.1% FS for universal-input (thermocouple/platinum resistance thermometer) models)
Proportional band (P) 1 to 999°C (automatic adjustment using auto-tuning/self-tuning)
Integral time (I) 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning
Derivative time (D) 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Alarm output range Absolute-value alarm: Same as the control range
Control period 2/20 s
Sampling period 500 ms
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Vibration
resistance
Shock resistance Malfunction
Life expectancy Electrical 100,000 operations min. (relay output models)
Weight Approx. 120 g (Controller only)
Degree of protection Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 1,000,000)
EMC EMI Radiated: EN 55011 Group 1 Class A
Approved standards UL 61010-1 (listing)
Conformed standards EN 61326, EN 61010-1, IEC 61010-1
Note: 1. The following exceptions apply to thermocouples.
• U, L: ±2°C ±1 digit max.
• R: ±3°C ±1 digit max. at 200°C or less
2. The following exceptions apply to platinum resistance thermometers.
Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max.
Malfunction
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Destruction
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Other thermocouple inputs: (±1% of PV or ±4°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Other: 0 to input setting range full scale (°C or °F)
Alarm hysteresis: 0.2°C or °F (fixed)
2
10 to 55 Hz, 20 m/s
2
min., 3 times each in 6 directions
100 m/s
2
300 m/s
min., 3 times each in 6 directions
EMI Conducted: EN 55011 Group 1 Class A
ESD Immunity: EN 61000-4-2: 4 kV contact discharge (level 2)
Radiated Electromagnetic Field Immunity: EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
Conducted Disturbance Immunity: EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity: 2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
Surge Immunity: EN 61000-4-5: Power line: Normal mode 1 kV; Common mode 2 kV
Voltage Dip/Interrupting Immunity: EN 61000-4-11 0.5 cycle, 100% (rated voltage)
CSA C22.2 No.1010-1
VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.
for 10 min each in X, Y, and Z directions
8 kV air discharge (level 3)
10 V/m (900 MHz pulse modulated)
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
3