Omron E5AJ-A2HB, E5AJ-A2H01, E5AJ-A2H02, E5AJ-A2HM, E5CJ-R Operation Manual

...
E5J Temperature Controller
Operation Manual
Cat. No. Z103-E3-1
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
DANGER Indicates information that, if not heeded, is likely to result in loss of life or serious
!
injury.
WARNING Indicates information that, if not heeded, could possibly result in loss of life or
!
serious injury.
Caution Indicates information that, if not heeded, could result in relatively serious or mi-
!
nor injury, damage to the product, or faulty operation.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for any­thing else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
OMRON, 1998
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permis­sion of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the informa­tion contained in this publication.
Note Indicates information of particular interest for efficient and convenient operation
of the product.
1, 2, 3...
1. Indicates lists of one sort or another, such as procedures, checklists, etc.
v

TABLE OF CONTENTS

SECTION 1
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 Features 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 Models 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Specifications 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Sensor and Mode Settings9. . . . . . . . . . . . . . . . . . . . . . . .
2-1 Disassembly 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Output Units 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Internal Switch Settings 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
Settings Before Operation 17. . . . . . . . . . . . . . . . . . . . . . . . .
3-1 Nomenclature 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Setting Flowchart 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 List of Parameters 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Parameters on Display Level 0 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 Parameters on Display Level 1 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4
Fuzzy Self-tuning 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1 Fuzzy Self-tuning Operation 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Troubleshooting 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Terminology 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 5
Installation and Wiring 35. . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1 Installation 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Wiring 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Terminal Arrangement 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 6
Troubleshooting 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 Error Display and Output 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Troubleshooting 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 7
Event Input Function 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1 Event Input Function 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 8
Heater Burnout Detection 49. . . . . . . . . . . . . . . . . . . . . . . . .
8-1 Heater Burnout Detection 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2 Heater Burnout Procedures 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3 Wiring the Current Transformer 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-4 Heater Burnout Alarm Value 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 9
Engineering Level Settings 55. . . . . . . . . . . . . . . . . . . . . . . .
9-1 Engineering Level 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-2 Engineering Level Parameter List 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-3 Engineering Level Parameters 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
vii
TABLE OF CONTENTS
SECTION 10
Auto-tuning 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-1 Starting Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-2 Conditions that Prevent Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-3 Force-ending Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-4 Changing Parameters during Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendices
A Dimensions/Mounting Holes 65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index 69. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision History 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
viii
About this Manual:
This manual describes the installation and operation of the Thermac E5J Temperature Controller and includes the sections described below.
Please read this manual carefully and be sure you understand the information provided before attempting to install and operate the Thermac E5J Temperature Controller.
Section 1 Section 2
necessary before turning on the Thermac E5J Temperature Controller.
Section 3
operating the Thermac E5J Temperature Controller.
Section 4
to the characteristics of the device for ideal temperature control.
Section 5 Section 6 Section 7 Section 8
taken at the time of heater burnout, as well as the method of obtaining heater burnout alarm values.
Section 9
should be changed only when the values set before shipping do not suit the application. After these pa­rameters are changed on the engineering level, record the contents of the changes for your future refer­ence.
Section 10
The perature Controller Units.
describes the specifications and basic features of the Thermac E5J Temperature Controller. describes the sensor and mode settings of the Thermac E5J Temperature Controller that are
describes the settings of the Thermac E5J Temperature Controller that are necessary before
provides the procedures required to adjust all PID constants using fuzzy self-tuning according
describes the installation and wiring of the Thermac E5J Temperature Controller.
describes the troubleshooting of the Thermac E5J Temperature Controller. describes how the event input function of the Thermac E5J Temperature Controller works. describes the basic features of heater burnout detection and necessary steps that should be
describes the parameters that can be changed on the engineering level. These parameters
describes how to execute auto-tuning.
Appendix
provides the dimensions and mounting specifications for the various Thermac E5J Tem-
!
WARNING Failure to read and understand the information provided in this manual may result in
personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
ix
SECTION 1

Introduction

This section describes the specifications and basic features of the Thermac E5J Temperature Controller.
1-1 Features 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 Models 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Specifications 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-1 Ratings 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-2 Characteristics 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Models
Section 1-2
1-1 Features
The basic features of the Thermac E5J Temperature Controller are outlined below.
Fuzzy Self-tuning When using a conventional temperature controller for ideal temperature control,
it is necessary to adjust the PID constants of the temperature controller accord­ing to the controlled device. The Thermac E5J Temperature Controller incor­porates a fuzzy self-tuning function, thus allowing ideal temperature control without any adjustment of the PID constants. The user needs only to set the E5J to the desired temperature for ideal temperature control.
Auto-tuning Auto-tuning is also available. It is useful when appropriate results are not
obtained through fuzzy self-tuning. (Refer to
Section 10 Auto-tuning
Event Input Function It is possible to select a set point out of a maximum of two set values on the
E5CJ-B and four set values on the E5AJ-B via their event input terminals from the PCs connected to these Temperature Controllers. The control opera­tion of the E5AJ-B via can be stopped with an event input signal.
Watertight Construction The E5J can be used in places where water is sprayed onto the E5J, be-
cause the front panel of the E5J assures IP54 when the E5J is panel­mounted (except for front panel of the E5CJ, which assures IP50). If greater wa­tertightness is required, use the Y92A-N, a dedicated watertight cover (sold separately).
.)
Advanced PID
The E5 J incorporates an advanced PID function, which is also incorporated by the Thermac X Temperature Controller. The advanced PID function prevents temperature overshooting the moment the Temperature Controller starts oper­ating, assures a short startup time, and performs ideal temperature control by quickly responding to external disturbances.
Output Units The E53-R Relay Unit, E53-Q, E53-Q3, and E53-Q4 Voltage Output Units for
driving SSRs, and E53-C3, E53-C3D, E53-V34, and E53-V35 Linear Output Unit can be connected to any E5J Temperature Controller (except the E5CJ) with ease according to the desired output configuration and application.
1-2 Models
The thermocouples and platinum resistance thermometers listed in the follow­ing table can be connected to any Thermac E5J Temperature Controller.
Input
Temperature range (°C)
INPUT
Factory-set to 2 (K)
Selectable internally.
1300 1000 800 600 400 200 100 0 –100 –200
Setting no.
Platinum resistance thermometer
JPt100
650.0
–199.9 –200
0.8 1.9 2 3 4 5 6 7
Pt100
650.0
KJ T L U N
1300
–200–199.9 –199.9 –199.9
850
–100
Thermocouple
400.0
–100
1300
850
400.0
2
Models
Section 1-2
E5AJ (Standard Model with Communications Function)
96 X 96mm
Alarm 2 relay output points with heater burnout alarm (see note 1) Event input 2 points (set point selection, RUN/STOP) (see note 2) Control output Replaceable Output Unit (sold separately) Model Communications function --- E5AJ-A2HB
RS-232C E5AJ-A2H01 RS-422 E5AJ-A2H02 RS-485 E5AJ-A2H03
Communications Board add-on model E5AJ-A2HM
Note 1. No heater burnout alarm is output if the E53-C3 Current Output Unit is used
with the E5AJ.
2. The event input function is not incorporated by models that have a commu­nications function.
E5EJ (Standard Model with Communications Function)
48 X 96mm
Alarm 2 relay output points with heater burnout alarm (see note 1) Event input 2 points (set point selection, RUN/STOP) (see note 2) Control output Replaceable Output Unit (sold separately) Model Communications function --- E5EJ-A2HB
RS-232C E5EJ-A2H01 RS-422 E5EJ-A2H02 RS-485 E5EJ-A2H03
Communications Board add-on model E5EJ-A2HM
Note 1. No heater burnout alarm is output if the Linear Output Unit is used with the
E5EJ.
2. The event input function is not incorporated by models that have a commu­nications function.
3
6 (at C)
Specifications
Section 1-3
E5CJ (Simple and Standard Models)
48 X 48mm
Type Simple model type Standard model
type
Alarm --- 2 replay output points with the same
common. (see note 1) Heater burnout alarm --- Yes (see note) Event input --- 1 point (set point
selection)
Model Control output Relay output E5CJ-R E5CJ-R2 E5CJ-R2HB
Voltage output E5CJ-Q E5CJ-Q2 E5CJ-Q2HB Current output E5CJ-C E5CJ-C2 E5CJ-C2B
Note No heater burnout alarm is output if a current control output is used.
Communications Boards
Note For details, refer to the
Communications RS-232C RS-422 RS-485
Model E53-J01 E53-J02 E53-J03
E5AJ/E5EJ Communications Manual (Z102).
1-3 Specifications
1-3-1 Ratings
E5J
Item Specification
Supply voltage 100 to 240 VAC, 50 or 60 Hz 24 V AC/DC,
50 or 60 Hz Operating voltage range 85 to 110% of supply voltage Power consumption E5AJ 10 VA (at 100 VAC) to
14 V A (at 240 VAC)
E5EJ 10 VA (at 100 VAC) to
14 V A (at 240 VAC)
E5CJ 10 VA (at 100 VAC) to
12 V A (at 240 VAC)
Input Thermocouples (K, J, T, L, U, and N) and platinum
resistance thermometers (JPt100 and Pt100) CT input Dedicated CT (E54-CT1 or E54-CT3) Control output E5AJ/E5EJ Replaceable Output Unit (sold separately)
E5CJ Relay output SPST-NO, 3 A at 250 VAC (resistive load)
Voltage output 20 mA at 12 VDC (with short-circuit protection) Current output 4 to 20 mA DC with a load of 600 max. and a
resolution of approx. 2600 Control mode ON/OFF or advanced PID with fuzzy self-tuning and
auto-tuning Alarm output E5AJ/E5EJ 2 SPST-NO relay output points, 3 A at 250 VAC
(resistive load)
E5CJ 2 SPST-NO relay output points (with the same common),
1 A at 250 VAC (resistive load) Setting method Digital setting with Up Key and Down Key
10 V A (at 24 VAC) 6 W (at 24 VDC)
4
Specifications
Item Specification
Indication method E5AJ All digital indication (PV: Red, 15 mm; SV: Green,
10.5 mm)
E5EJ All digital indication (PV: Red, 14 mm; SV: Green,
9.5 mm)
E5CJ All digital indication (PV: Red, 12 mm, SV: Green 8.0
mm) Event input Contact input: ON: 1 k max. OFF: 100 k min.
No-contact input: ON: residual voltage of 3 V max; OFF:
current leakage of 1 mA max. Other function Key protect
Cooling operation/Heating operation
Heater burnout alarm
Model with event input (E5J-B)
Set point selection (set point x 2)
RUN/STOP (E5AJ-B and E5EJ-B only)
Ambient operating temperature –10°C to 55°C (with no condensation) Ambient operating humidity 35 to 85% Storage temperature –25°C to 65°C (with no condensation)
Section 1-3
Output Units
Model Specification
E53-R Relay Output Unit SPDT (SPST-NO when used with the
E5J), 5 A at 250 VAC (resistive load)
E53-Q Voltage Output Unit NPN, 40 mA at 12 VDC (with
short-circuit protection)
E53-Q3 Voltage Output Unit NPN, 20 mA at 24 VDC (with
short-circuit protection)
E53-Q4 Voltage Output Unit PNP, 20 mA at 24 VDC (with
short-circuit protection)
E53-C3 Linear Output Unit 4 to 20 mA DC with a load of 600
max. (with a resolution of approximately 2600 when used with the E5J) (see note)
E53-C3D Linear Output Unit 0 to 20 mA DC with a load of 600
max. (with a resolution of approximately 2600 when used with the E5J)
E53-V34 Linear Output Unit 0 to 10 VDC with a load of 1 k min.
(with a resolution of approximately 2600 when used with the E5J)
E53-V35 Linear Output Unit 0 to 5 VDC with a load of 1 k min.
(with a resolution of approximately 2600 when used with the E5J)
Note The E53-C cannot be used.
Current Transformer (CT)
Item Specification
Maximum continuous heater current 50 A Dielectric strength 1,000 VAC Vibration resistance 50 Hz, approx. 98 m/s2 (10G) Weight E54-CT1: Approx. 11.5 g
E54-CT3: Approx. 50 g
5
Specifications
Section 1-3
1-3-2 Characteristics
E5J
Item Specification
Indication accuracy ±0.5% or ±1°C whichever is larger ± 1 digit max.
Thermocouple K, T, or N at a temperature of –100°C; thermocouple U at ± 2°C ± 1
digit max. Hysteresis (for ON/OFF control) 0.1 to 999.9°C/° F (in units of 0.1°C/°F) Proportional band 0.1 to 999.9°C/°F (in units of 0.1°C/°F) Integral time 0 to 3999 s (in units of 1 s) Derivative time 0 to 3999 s (in units of 1 s) Control period Relay or voltage output:1 to 99 s (in units of 1 s) Manual reset value (I = 0) 0.0 to 100.0% (in units of 0.1%) Alarm setting range With K, J, L, or N input: –1999 to 9999° C/°F (in units of 1°C/°F)
With JPt100, Pt100, T, or U input: –199.9 to 999.9° C/°F (in units of 0.1°C/°F) Sampling period 500 ms Output refresh period 500 ms Display refresh period 500 ms Insulation resistance 20 M min. at 500 VDC (measured with an Output Unit) Dielectric strength 2000 VAC, 50/60 Hz for 1 min. between charged terminals different from each other
in polarity Vibration
resistance Shock resistance Malfunction 196 m/s2 (20G) 3 times each in 3-axis 6 directions (98 m/s2 (10G) for the relay)
Weight E5AJ Approx. 360 g; mounting bracket: approx. 65 g
Enclosure rating Front panel: E5AJ/E5EJ: IEC standard IP54
Memory Protection Non-volatile memory EMC Emission Enclosure: EN55011 Group 1 class A
Approved standards UL1092, CSA C22.2 No. 142
Malfunction 10 to 55 Hz, 9.8 m/s2 (1G) 10 min. in X, Y, and Z directions Destruction 10 to 55 Hz, 19.6 m/s2 (2G) 2 hr. in X, Y, and Z directions
Destruction 294 m/s2 (30G) 3 times each in 3-axis 6 directions
E5EJ Approx. 280 g; mounting bracket: approx. 65 g E5CJ Approx. 170 g; adapter: approx. 10 g
E5CJ: IEC standard IP50 (see note 1) Rear case: IEC standard IP20 Terminals: IEC standard IP00
Emission AC Mains: EN55011 Group 1 class A Immunity ESD: EN61000-4-2:4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3) 10 V/m (pulse modulated,
900 MHz) Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: EN61000-4-4:2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1) (see note 2) Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is mounted.
Note 1. The model numbers of the exclusive watertight covers conforming to IP66,
NEMA4 are as follows: For E5AJ: Y92A-96N; For E5CJ: Y92A-48N; For E5EJ: Y92A-49N
2. Basic insulation is between the input and output.
6
Specifications
Section 1-3
Output Unit
Heater Burnout Alarm
Note 1. Use the K2CU-FA-GS (with gate input terminals) for the detection of
Model with Communications Function
Model Life expectancy
E53-R Relay Output Unit Mechanical 10,000,000 times min.
Electrical 100,000 times min.
Item Specification
Max. heater current Single-phase 50 A VAC (see note 1) Heater current value display accuracy ±5% FS ± 1 digit max. Heater burnout alarm setting range 0.1 to 49.9 A (in units of 0.1 A)
Min. detection ON time 190 ms (see note 3)
(see note 2)
three-phase heater burnout.
2. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and al­ways ON if the alarm is set to 50.0 A.
3. No heater burnout detection or heater current value measurement is pos­sible if the control output is ON for less than 190 ms.
Refer to the
Interface RS-232C, RS-422, RS-485 Communications method Half duplex Synchronization method Start-stop synchronization
Communications speed 1200, 2400, 4800, 9600, and 19200 bps Communications
item
E5AJ/E5EJ Communications Manual (Z102)
Item Specification
(non-synchronization)
Writing to Thermac J
Reading from Thermac J
Set point, alarm value, heater burnout alarm value, proportional band, derivative time, integral time, and input shift value
Process value, set point, alarm value, heater burnout alarm value, heater current value, proportional band, derivative time, integral time, output value, input shift and error code
for details.
7
SECTION 2

Sensor and Mode Settings

This section describes the sensor and mode settings of the Thermac E5J Temperature Controller that are necessary before turning on the Thermac E5J Temperature Controller.
2-1 Disassembly 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Output Units 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Internal Switch Settings 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-1 Internal Switch Positions 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-2 Input Type Selector Setting 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-3 Alarm Mode Setting 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-4 Standby Sequence 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-5 Function Selector Settings 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-6 Key Protection Switch Settings 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
Output Units
2-1 Disassembly
2-2 Output Units
Section 2-2
Before turning on the E5J, set its sensor type and control mode with the inter­nal selectors. Refer to the following illustrations for disassembling the E5J to access the internal switch settings.
Hook
Press the hook and pull the front panel.
After setting the internal switches, insert the internal mechanism into the case until the front panel snaps with the hook.
Select the Output Unit according to the application and mount the Output Unit into the socket on the E5J PCB of the as shown in the following illustration. The E5CJ does not require an Output Unit. Refer to ratings of the E5J.
1-3 Specifications
for the output
Bracket
Output Unit
Socket
Output Units The following Output Units are available.
Model Rating
E53-R Relay Output Unit SPDT, 5 A at 250 VAC (resistive load) E53-Q Voltage Output Unit NPN model, 40 mA at 12 VDC (with short-circuit
protecting circuit)
E53-Q3 Voltage Output Unit NPN model, 20 mA at 24 VDC (with short-circuit
protecting circuit)
E53-Q4 Voltage Output Unit PNP model, 20 mA at 24 VDC (with short-circuit
protecting circuit) E53-C3 Linear Output Unit 4 to 20 mA DC with a load of 600 max. E53-C3D Linear Output Unit 0 to 20 mA DC with a load of 600 max. E53-V34 Linear Output Unit 0 to 10 VDC with a load of 1 k min. E53-V35 Linear Output Unit 0 to 5 VDC with a load of 1 k min.
After mounting the Output Unit, be sure to secure it with the mounting bracket provided with the Output Unit.
If the E53-C3, E53-C3D, E53-V34, and E53-V35 Linear Output Unit is used for control output, no heater burnout alarm is available.
Each Voltage Output Unit is used for driving an SSR as shown in the following illustrations.
10
Internal Switch Settings
NPN Model: E53-Q (40 mA at 12 VDC) and E53-Q3 (20 mA at 24 VDC)
++
LOAD INPUT
PNP Model: E53-Q4 (20 mA at 24 VDC)
LOAD INPUT
SSR
––
++
SSR
––
Section 2-3
2-3 Internal Switch Settings
2-3-1 Internal Switch Positions
E5AJ
Top view
E5EJ
Top view
ALM2
Alarm mode selector 2
ALM1
Alarm mode selector 1
PROTECT
Key protection switch
INPUT
Input type selector
ALM2
Alarm mode selector 2
PROTECT
Key protection switch
ALM1
Alarm mode selector 1
INPUT
Input type selector
ALL OFF SP
ALL OFF SP
Bottom view
FUNCTION
Function selector
FUNCTION
Function selector
11
Internal Switch Settings
E5CJ
Top view
ALM2
Alarm mode selector 2
Section 2-3
Bottom view
ALM1
Alarm mode selector 1
INPUT
Input type selector
FUNCTION
Function selector
PROTECT
Key protection switch
SP OFF ALL
Note The E5CJ with no alarm does not incorporate ALM1 or ALM2.
2-3-2 Input Type Selector Setting
The input type selector is factory-set to 2 (K). Refer to the following table for the selection of the desired sensor.
INPUT
Selector no. Input Set temperature range Specified temperature range
°C °F °C °F
0, 8 JPt100 –199.9 to 650.0 –199.9 to 999.9 –199.9 to 735.0 –199.9 to 999.9 1, 9 Pt100 –199.9 to 650.0 –199.9 to 999.9 –199.9 to 735.0 –199.9 to 999.9 2 K –200 to 1300 –300 to 2300 –350 to 1450 –560 to 2560 3 J –100 to 850 –100 to 1500 –195 to 945 –260 to 1660 4 T –199.9 to 400.0 –199.9 to 700.0 –199.9 to 460.0 –199.9 to 790.0 5 L –100 to 850 –100 to 1500 –195 to 945 –260 to 1660 6 U –199.9 to 400.0 –199.9 to 700.0 –199.9 to 460.0 –199.9 to 790.0 7 N –200 to 1300 –300 to 2300 –350 to 1450 –560 to 2560
Note The resistance of the JPt100 at a temperature of 100°C is 139.16 and that of
the Pt100 at a temperature of 100°C is 138.50 .
1, 2, 3...
1. To use Fahrenheit, set function selector 4 to ON, which is usually set to OFF.
2. Insert the internal mechanism into the case.
3. Turn on the E5J so that d-u will be displayed on the process value display. Then press the Up Key so that f will be displayed on the set value display .
4. Turn off the power in two seconds.
5. Draw the internal mechanism from the case and set function selector 4 to OFF and turn on the E5J.
12
Internal Switch Settings
2-3-3 Alarm Mode Setting
ALM1 and ALM2 are both factory-set to 2 (upper limit alarm). Refer to the follow­ing table for the selection of the desired alarm mode.
Section 2-3
ALM2 ALM1
Selector
Alarm mode Alarm output Setting range
no.
Positive alarm set
value
Negative alarm set
value
0 No alarm function OFF --­1 Upper and lower limit
alarm (deviation)
XSPX
Always ON –1999 to 9999 or –199.9
to 999.9 (the decimal position varies with the input type)
2 Upper limit alarm
(deviation)
3 Lower limit alarm
(deviation)
4 Upper and lower limit
SP
X
SP
XSPX
X
Always OFF
X
SP
X
SP
range alarm (deviation)
5 Upper and lower limit
XSPX
Always OFF alarm with standby sequence (deviation)
6 Upper limit alarm with
standby sequence (deviation)
7 Lower limit alarm with
standby sequence (deviation)
8 Absolute value upper
limit alarm
9 Absolute value lower
limit alarm
X
SP
X
SP
X
0
X
0
X
SP
X
SP X
0 X
0
If the alarm mode switch is set to 1 to 7, the alarm value is set with the deviation width from the set point as shown in the following diagram.
Alarm value
10°C/°F
Set point (SP)
100°C/°F
If the alarm mode switch is set to 8 or 9, the alarm value is set with the absolute value from 0°C/°F as shown in the following diagram.
Alarm value
110°C/°F
0°C/°F
13
Internal Switch Settings
2-3-4 Standby Sequence
The alarm output is ON the moment the E5J is turned on because the process value is within the alarm range. To prevent this, select a mode with a standby sequence. If a mode with a await sequence is selected, the alarm output will not be ON even if the process value is within the alarm range unless the process value once goes out of the alarm range. The following diagram shows the opera­tion of the E5J in lower limit alarm mode with a standby sequence.
OFF point due to alarm hysteresis
It is possible to change the alarm hysteresis (set to 0.2°C before shipping) on the engineering level.
2-3-5 Function Selector Settings
All the function selector pins are factory-set to OFF.
Section 2-3
Standby sequence releasing point
Alarm point
Alarm output
ON OFF
To set these pins to
FUNCTION
ON, use a small flat­blade screwdriver.
Refer to the following table for function switch setting.
Pin no. 1 2 3 4
Output Cooling operation (Normal) ON --- --- --­operation Heating operation (Reverse) OFF Control ON/OFF control --- ON See note mode Advanced PID --- OFF ON
Advanced PID with fuzzy self-tuning --- OFF OFF
Level Engineering level --- --- --- ON
Normal operation --- --- --- OFF
Note The E5J will be in ON/OFF control mode regardless of the setting of pin 3 if pin
2 is set to ON.
Output Operation (Pin 1)
Heating Operation If pin 1 of the E5J is set to OFF, when the process temperature is lower than the
set point, the E5J will operate so that the heater output will increase.
Cooling Operation If pin 1 of the E5J is set to ON, when the process temperature is higher than the
set point, the E5J will operate so that the output of cooling water will increase.
Control Mode (Pins 2 and 3)
ON/OFF Control The ON/OFF control is also called two-position operation. Advanced PID Set the E5J in this mode for P, PI, or PD control or if the most suitable PID
constants for the controlled device are already known.
Advanced PID with Fuzzy Self-tuning
Set the E5J in this mode so that Fuzzy self-tuning adjusts the PID constants to the most suitable values according to the controlled device for ideal temperature control. Refer to
Section 4 Fuzzy Self-tuning
for details.
Level (Pin 4)
14
Set pin 4 to ON if it is necessary to change any parameter on the engineering level. Set this pin to OFF for normal operation.
Internal Switch Settings
2-3-6 Key Protection Switch Settings
The key protection switch is used to prohibit parameter changes as shown in the following table. The key protection switch is factory-set to OFF.
Mode Protection
SP
OFF All keys are available. ALL Prohibits all set value changes. The Level Key, Down Key, and
Prohibits all set value changes except the set point. The Level Key is not available. The Down Key and Up Key are available only for set point setting.
Up Key are not available.
Section 2-3
SP OFF ALL
PROTECT
15
SECTION 3

Settings Before Operation

This section describes the settings of the Thermac E5J Temperature Controller that are necessary before operating the Thermac E5J Temperature Controller.
3-1 Nomenclature 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Setting Flowchart 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 List of Parameters 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Parameters on Display Level 0 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 Parameters on Display Level 1 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
Nomenclature Section 3-1
3-1 Nomenclature
The following is the front panel of the E5AJ-A2HB. The front panels of the E5EJ and E5CJ are similar to the front panel of the E5AJ-A2HB.
Process Value (PV) display
Displays not only the process value but also indicates the pa-
Stop indicator
Lit when the E5J is not operating. The E5CJ does not incorporate this indicator.
Output indicator
Lit when the control output is ON. This indicator is, however, not lit when the E5J has a current out­put.
Level Key
Press for 1 s minimum to change lev­els to set different groups of parame­ters.
Display Key
Use this key when shifting the display to the next parameter.
rameter being displayed on the SV display and error messages.
Down Key and Up Key
The Down Key, when pressed, decreases the set tempera­ture or other parameters. The value successively decreases when the Down Key is held down for 1 s minimum. The Up Key, when pressed, increases the set temperature or other parameters. The value successively increases when the Up Key is held down for 1 s minimum. The value set will be ef­fective on pressing the Display Key or Level Key or 2s after it is set if Display Key or Level Key is not pressed.
Set Value (SV) display
Displays the set temperature and other parameters.
Alarm 1 indicator
Lit when alarm output 1 is ON.
Alarm 2 indicator
Lit when alarm output 2 is ON.
Heater burnout alarm
Lit when there is heater burnout. Once heater burnout is detected, the alarm output will be on hold.
Note Refer to the
E5AJ/E5EJ Communications Manual
models incorporating a communications function.
for the operation of E5J
18
Setting Flowchart
Section 3-2
3-2 Setting Flowchart
The Thermac E5J Temperature Controller starts control at the set point and continues controlling even while set values are being input for each display level. Therefore, when operating the E5J after inputting all the set values, turn the power supply to the Temperature Controller off and then on again.
All parameters for the E5J Temperature Controller are divided into three levels according to how frequently they are used.
Display Level 0 Parameters that are changed frequently are ranked as display level 0 parame-
ters.
Display level 1 Parameters that are not changed frequently are ranked as display level 1 pa-
rameters.
Engineering Level Parameters that are changed with only a few applications are ranked as engi-
neering level parameters.
OFF ON
Level Key Press for 1 s min.
Display level 0 Display level 1
Set point setting
Alarm 1 setting
Alarm 2 setting
Each parameter is set with the Up Key or Down Key. Each value set will be effective on pressing the Display Key or Level Key or 2 s after it is se­lected if Display Key or Level Key is not pressed. No value can be, however, changed when the key protection switch is ON.
The parameters in parentheses are changed if their initial values are changed on the engineering level.
Level Key Press for 1 s min.
Output display
Control period setting
Hysteresis setting
Set point 0 setting
Set point 1 setting
(Set point 2 setting)
(Set point 3 setting)
(Input shift value setting)
Heater current value display
Heater burnout alarm setting
Proportional band setting
Integral time setting
Derivative time setting
Manual reset value setting
Pin 4 of the func-
tion selector
Engineering level
°C/°F selection
Stable range
Alpha
Automatic return of display mode
Standby sequence reset method
Input shift display selection
Alarm 1 hysteresis
Alarm 2 hysteresis
Set point lower limit
Set point upper limit
Event input 2 function selection
Refer to
Settings
on the engineering level and how to change them.
Section 9 Engineering Level
for details on each parameters
19
List of Parameters
3-3 List of Parameters
Display Level 0
Display Name Setting range Setting
--- Process value display and set point setting
AL-1 Alarm set value 1 –1999 to 9999 °C/°F
AL-2 Alarm set value 2 –1999 to 9999 °C/°F
To go to the next level, press the Level Key for 1 s min.
Note The values shown in Fahrenheit are applicable only for E5J--F Mod-
els.
Set point lower limit to set point upper limit (°C/°F)
The decimal position varies with the kind of input.
The decimal position varies with the kind of input.
Section 3-3
Remarks
before
shipping
0 The present set point is
displayed and can be changed if the E5J incorporates an event input function
0 Not displayed if alarm mode
switch 1 is set to 0.
0 Not displayed if alarm mode
switch 2 is set to 0.
Display Level 1
Display Name Setting/Display
0 Output value
display
CP Control period 1 to 99 s 20 Displayed and can be set if
HYS Hysteresis 0.1 to 999.9 °C/°F 1.0 (1.8) Displayed and can be set
SP-0 Set point 0 Set point lower limit
SP-1 Set point 1 Set point lower limit
SP-2 Set point 2 Set point lower limit
SP-3 Set point 3 Set point lower limit
in-S Input shift value –199.9 to 999.9 °C/°F 0.0 Displayed and can be set if
0.0 to 100.0 %
to set point upper limit (°C/°F)
to set point upper limit (°C/°F)
to set point upper limit (°C/°F)
to set point upper limit (°C/°F)
Range
Setting
before
shipping
the E5J in PID control operation has relay control output or voltage control output.
when the E5J is in ON/OFF control operation.
0 For models incorporating an
event input function.
0 For models incorporating an
event input function.
0 For models incorporating an
event input 2 function. Displayed and can be set if
the default value is changed on the engineering level.
0 For models incorporating an
event input 2 function. Displayed and can be set if
the default value is changed on the engineering level.
the default value is changed on the engineering level.
Remarks
20
List of Parameters
Section 3-3
Display RemarksSetting
Ct Heater current
Hb Heater burnout
P Proportional band 0.1 to 999.9 °C/°F 8.0 (14.4) Displayed and can be set
8.0
i Integral time 0 to 3999 s
d Derivative time 0 to 3999 s
oFr Manual reset value 0.0 to 100.0 % 50.0 Displayed and can be set if
Name
value display
alarm value
Setting/Display
Range
0.0 to 55.0 A If the current exceeds
55.0 A, ffff will be displayed on the set value display.
0.0 to 50.0 A
0.0: Always OFF
50.0: Always ON
0: No integral
operation
0: No derivative
operation
before
shipping
0.0 For models incorporating a
233 Displayed and can be set
40 Displayed and can be set
For models incorporating a heater burnout alarm.
Nothing is displayed if the E5J has current control output.
heater burnout alarm. Nothing is displayed if the
E5J has current control output.
when the E5J is in advanced PID operation.
when the E5J is in advanced PID operation.
when the E5J is in advanced PID operation.
the integral time is set to 0 when the E5J is in advanced PID operation.
Note The value in the parentheses is the E5J--F setting before shipping.
21
Parameters on Display Level 0
3-4 Parameters on Display Level 0
Note: The process value will not be displayed if the
alarm mode switch is set to 0 or if the E5J does not incorporate any alarm.
Section 3-4
The value set before shipping appears
(Set point setting)
Displays when the E5J incorporates an alarm function (see note).
(Alarm 1 setting)
Displays when the E5J incorporates an alarm function (see note).
(Alarm 2 setting)
Set Point Setting (°C or °F) It is possible to alter the present set point (SP0 or SP1). al1 and al2 (°C or °F) The alarm mode is factory-set to the upper limit alarm (deviation). It is possible to
change the alarm mode with the alarm mode selector. Refer to
Mode Setting
. The alarm value can be set with the deviation width or absolute
2-3-3 Alarm
value according to the alarm mode.
Deviation alarm Absolute value alarm
Upper and lower limit alarm, upper limit alarm, lower limit alarm and upper and lower limit range alarm.
Set with the deviation width from the set point
Alarm value
10°C/°F
Set point (SP) 100°C/°F
Absolute value upper limit alarm and absolute value lower limit alarm.
Set with the absolute value from 0°C/°F.
Alarm value
110°C/°F
0°C/°F
22
Parameters on Display Level 1
3-5 Parameters on Display Level 1
Section 3-5
The value set before shipping appears
(Output value display)
Displays when the E5J in PID control operation has a relay or voltage output.
(Control period setting)
Displays when the E5J is in ON/ OFF control operation.
(Hysteresis setting)
Displays if the E5J has an event input.
(Set point 0 setting)
(Set point 1 setting)
Displays only if the event input 2 function is used for set point selec­tion (see note 1).
(Set point 2 setting)
(Set point 3 setting)
Displays if the input shift value dis­play is selected (see note 1).
(Input shift value setting)
Displays if the heater burnout alarm function is selected. (see note 2).
(Heater current value display)
(Heater burnout alarm value setting)
Displays when the E5J in ad­vanced PID operation.
8.0
(Proportional band setting)* *In case of °F:
(Integral time setting)
(Derivative time setting)
Displays if I is 0 .
(Manual reset value setting)
14.4
Note 1. Displayed if the initial value is changed on the engineering level.
2. Not displayed if current output is used as control output or a model with no heater burnout alarm function is used.
23
Parameters on Display Level 1
Section 3-5
o Output Value Display The output value is displayed within a range of 0.0% to 100.0%. cp Control Period Setting It is possible to set the control period within a range of 1 to 99 s. The control peri-
od is the period required by the E5J to turn ON and OFF its relay output or volt­age output. The ON period increases in proportion to the output value. If the con­trol period is short, smooth control operation will be possible although a short control period shortens the life of the relay if relay output is used. Therefore, the control period should not be less than 20 s if relay output is used. The following are output examples with an output value of 50.0 %.
5 s 10 s
ON
ON
hys Hysteresis Setting (°C or °F)
sp0, sp1, sp2, and sp3 (E5J-B Only)
OFF
Control period: 10 s Control period: 20 s
It is possible to set the hysteresis for the E5J in ON/OFF control operation with­in a range of 0.1° to 999.9°C/°F.
Heating control (Reverse)
Cooling control (Normal)
ON
OFF
Low temperature Set point High temperature
ON
OFF
Low temperature Set point High temperature
It is possible to set sp-0 (set point 0), sp-1 (set point 1), sp-2 (set point 2), and sp-3 (set point 3) all in Celsius or Fahrenheit regardless of the set point presently se-
OFF
Hysteresis
Hysteresis
lected. To select the set point, open or short-circuit terminals EV1 and EV2. Re-
Section 7 Event Input Function
fer to
for details.
in-s Input Shift Value It is possible to set the input shift value within a range of –199.9° to 999.9°C/°F.
When an input shift value is set, the process value will be the input value added with the shift value.
Example
Input Input shift value Process value
100°C 0 (no compensation) 100°C
10.0 (compensation value) 110°C –10.0 (compensation value) 90°C
ct Heater Current Value Display (E5J-H Only)
hb Heater Burnout Alarm Value Setting (E5J-H Only)
24
After the input shift value is set, the it is effective even if the input shift value dis­play is turned off on the engineering level.
It is possible to set the heater current value within a range of 0.0 to 55.0 A. If the current value exceeds 55.0 A, ffff will be displayed on the set value display. The heater current will be processed and displayed if the control output is ON.
It is possible to set the heater burnout alarm value within a range of 0.0 to 50.0 A, which will be used to detect heater burnout. If the heater burnout alarm value is set to 0.0 A, the heater burnout alarm output will be always OFF. If the heater burnout alarm value is set to 50.0 A, the heater burnout alarm output will be al­ways ON. Refer to
Section 8 Heater Burnout Detection
for details.
When the E5J is in advanced PID with fuzzy self-tuning mode, the following parameters (p, i, d, ofr) will not be displayed (i.e., there is no need to set the following parameters). The fuzzy self-tuning always adjusts the PID constants to the most suitable values according to the characteristics of the controlled de­vice.
Parameters on Display Level 1
p Proportional Band Setting It is possible to set the proportional band within a range of 0.1 to 999.9°C/°F. i Integral Time Setting It is possible to set the integral time within a range of 0 to 3999 s. d Derivative Time Setting It is possible to set the derivative time within a range of 0 to 3999 s.
Section 3-5
ofr Manual Reset Value Setting
It is possible to set the necessary output value when the E5J is in constant op­eration within a range of 0.0% to 100.0%. The E5J will be balanced with a devi­ation between the set point and process value in P or PD control mode. This deviation is called offset. The offset can be removed by changing the manual reset value.
25
SECTION 4

Fuzzy Self-tuning

This section provides the procedures required to adjust all PID constants using fuzzy self-tuning according to the characteris­tics of the device for ideal temperature control.
4-1 Fuzzy Self-tuning Operation 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-1 Step Response Tuning (SRT) 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-2 Disturbance Tuning (DT) 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-3 Hunting Tuning (HT) 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Troubleshooting 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Terminology 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-1 Stable Value, Stable Range, and Stability Judgement Time 32. . . . . . . . . . . . . . . . .
4-3-2 Hunting 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-3 Characteristics and Characteristics Change 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-4 External Disturbance 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-5 Interference 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-6 Startup 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
Fuzzy Self-tuning Operation Section 4-1
4-1 Fuzzy Self-tuning Operation
The fuzzy self-tuning function has three features, step response tuning (SRT), disturbance tuning (DT), and hunting tuning (HT).
4-1-1 Step Response Tuning (SRT)
SRT is used to obtain all PID constants using a step response method when the Temperature Controller starts operations.
SRT is also used when the set point changes value exceeding a set range while the Temperature Controller is operating. After SRT has been executed, no SRT will be executed the next time the Temperature Controller starts operating, un­less the set point has been changed.
Set point
Max. tempera­ture slope R
Dead time L
Tuning at startup
P X 1.27
In step response tuning, control is completely imposed step­wise to measure the maximum temperature slope (R) and dead time (L), and the most ideal PID constants for the de­vice are obtained from R and L.
Output (%)
100
100% imposed step-wise control amount.
Note Be sure to turn on the power supply to the load either before or simultaneously
Advanced PID
with the start of Temperature Controller operation. When using the E5AJ-A2HB or E5EJ-A2HB, you can change the RUN/STOP setting to RUN via event input 2 after supplying power to the load. Dead time will be measured from the time the Temperature Controller starts operating. If a load such as a heater is turned on after the Temperature Control­ler is turned on, dead time longer than the actual value will be measured and inappropriate PID constants will be obtained. If an extremely large amount of dead time is measured, the control amount will be set to 0% for a short period of time before being returned to 100%, and the constants will then be retuned. Retuning is performed only for large amounts of dead time, so be sure to follow the precaution given above when starting operation.
28
Fuzzy Self-tuning Operation Section 4-1
SRT Startup Condition SRT will be ON if the following conditions are satisfied simultaneously when the
Temperature Controller is turned on or the set point is changed.
Imposition Completion Condition of Step Control Amount
PID Constant Refreshing Conditions
At the time the Temperature Controller
starts operating
1) The set point at the time the Temperature Controller starts operating is different from the set point used at the time SRT was last executed (see note).
2) The difference between the set point and the process value at the time the Temperature Controller starts operating is larger than the present proportional band value (P) x 1.27 + 4.
3) The process value at the time the Temperature Controller starts operating is smaller than the set point in reverse operation and larger than the set point in normal operation.
At the time set point is changed
1) The new set point is different from the set point used at the time SRT was executed last (see note).
2) The set point changing range is larger than the present proportional band value (P) x 1.27 + 4.
3) The process value is in stable condition before the set point is changed.
4) A larger set point value is set in reverse operation and a smaller set point is set in normal operation.
Note The last SRT-executed set point is set to 0 before shipping and when changing
from advanced PID control to advanced PID control with fuzzy self-tuning. In order to prevent overshooting, the step controlled amount must be imposed
continuously only while the present deviation is the same as or greater than the value obtained from the proportional band (P)1.27. The step control will not be
applied when the deviation becomes smaller than this value. If the step control amount is applied before the maximum temperature slope (R)
is obtained, SRT will not renew any PID constant. If the proportional band ob­tained from the R and L values that were measured before the imposition had been completed is larger than the present proportional band, the PID constants will be renewed because the measured value is in the direction towards the suit­able proportional band value, and the set point at that time will be the SRT­executed set point.
4-1-2 Disturbance Tuning (DT)
DT is used to measure the control waveform and adjust the PID constants when the measured temperature becomes unstable. When there are control charac­teristic changes after the PID constants are refreshed with SRT or when the PID constants are not suitable to the object to be controlled because SRT was not executed, the PID constants will be adjusted with DT.
DT at the Time of Operation Start and Set Value Change
Set point
PID before tuning PID after tuning
If there is overshooting at the time the Temperature Controller restarts operating after SRT has been executed, DT adjusts the PID constants so that the set point response waveform will be as close as possible to the most ideal response wa­veform aft e r i t i s deemed that there has been a characteristics change in the con­trol system.
Stable range (set to 15.0°C before shipping)
Stability judge­ment time
Measurement of set point response waveform
The set point response waveform at the time the Temperature Con­troller restarts operation will be closer to the most ideal response waveform.
29
Fuzzy Self-tuning Operation Section 4-1
DT at the Time of External Disturbance Response
After the process value reaches the set point and becomes stable, if the process value is disturbed and the disturbance exceeds the stable range, the distur­bance is regarded as external disturbance At the time of disturbance, DT mea­sures the external disturbance waveform and adjusts the PID constants so that the external disturbance waveform will be as close as possible to the most ideal external disturbance response waveform.
Stable range (set to 15.0°C before shipping)
Set point
External disturbance
Stability judge­ment time
Measurement of external disturbance response waveform
External disturbance
The external disturbance response waveform is approaching to the most ideal response waveform even if the same kind of external disturbance reoccurs. The waveform will not, however, change if the most ideal PID constants are already set.
PID after tuningPID before tuning
Startup Conditions of DT DT is used to monitor the control waveform if there is external disturbance or
SRT does not work at the time the Temperature Controller starts operating or at the time of set point change. If the measured waveform is not an ideal waveform, DT will be ON. If either one of the following conditions is satisfied, the control waveform will be monitored.
1, 2, 3...
1. SRT Startup conditions 3 and 4 on page 29 are satisfied but neither 1 nor 2 is satisfied.
2. There has been an external disturbance exceeding the stable range after the process value was in stable condition.
Note The stable range is set to 27°F with the E5J--F.
4-1-3 Hunting Tuning (HT)
If there is hunting due to characteristics changes of the control system, HT is used to measure the hunting waveform and adjust the PID constants to sup­press the hunting.
Set point
PID before tuning PID after tuning
Extreme value
Stable range (set to 15.0°C before shipping)
Measurement of hunting waveform
Startup Conditions of HT HT will be ON when there is hunting with four or more maximum temperature
values while SRT is not being executed.
Note If the periodic temperature changes of the application exceed the stable range
(set to 15.0°C at the factory) due to continuous external disturbance (i.e., the temperature is a ffected by an external disturbance before stabilizing after a pre­vious external disturbance (refer to figure A below)), the user should change the stable range to a value greater than the temperature changing range, otherwise
30
Troubleshooting
Section 4-2
HT may change the PID constants even though the PID constants are ideal for the control system. Refer to
External disturbance
Figure A: Waveform with HT turned ON
External disturbance
9-1 Engineering Level
for details.
Note The stable range is set to 27°F with the E5J--F.
4-2 Troubleshooting
Fuzzy self-tuning may not exhibit its full capability due to the characteristics and conditions of the controlled object.
Refer to the following table for troubleshooting when Unit operation is not smooth.
Phenomenon Probable cause Countermeasure
The temperature does not reach the set point.
T1 T2
Figure B: Waveform with HT turned OFF
The dead time measured was longer than the actual value and inappropriate PID constants were obtained because the load (such as a heater) was turned on after the Temperature Controller started operating. (Refer to details.)
The PID constants were changed from the most ideal value because HT is ON continuously when there was a periodic temperature change larger than the stable range due to an external disturbance. Refer to the note under 4-1-3.
4-3-6 Startup
for
T1<T2
Do the following to execute SRT again.
1) Set the control mode to the advanced PID and set the proportional band to 0.1°C.
2) Set the control mode to the advanced PID with fuzzy self-tuning again.
3) Wait until the temperature of the control system is stable, and then turn on the Temperature Controller and the load simultaneously or turn on the load first for SRT.
Do either one of the following so that HT will not be ON.
Change the stable range to a wider setting than the range of the temperature change and execute SRT again by executing steps 1) to 3) above.
After obtaining the most ideal PID constants by executing steps 1) to
3) above, set the control mode to advanced PID.
31
Terminology
Phenomenon CountermeasureProbable cause
Hunting does not stop. The control period is too long for the
characteristics of the controlled device, which causes hunting in synchronization with the control period.
The temperature is influenced by continuous external disturbance (i.e., the temperature is affected by an external disturbance before a previous disturbance has be stabilized. and it looks as if hunting did not stop at all).
The response fluctuates, becoming good and bad.
The response fails to reach operational requirements.
There is a heater or cooling device not controlled by the control output of the Temperature Controller (e.g., forced heating or cooling is executed using alarm outputs).
There are continuous characteristics changes.
The response speed of the controlled device is so fast that it cannot be retrieved by a sampling period of 500 ms.
The temperature is affected by devices near the system.
Section 4-3
Shorten the control period.
In this case, however, 100% improvement will not be possible because the temperature is influenced by a continuous external disturbance instead of hunting. Change the stable range to a wider setting than the range of the temperature change so that HT will not be ON.
In this case fuzzy self-tuning may not work. Set the control mode to the advanced PID and adjust the PID constants manually.
Do either one of the following.
Adjust the stable range so that fuzzy self-tuning will not be turned ON.
Set the control mode to the advanced PID and adjust the PID constants manually.
The Thermac E5J Temperature Controller cannot support a sampling period of less than 500 ms. Use an ES100-series Digital controller, which has a shorter sampling period.
Fuzzy self-tuning does not support any countermeasure against interference. Set the control mode to the advanced PID and adjust the PID constants manually.
4-3 Terminology
4-3-1 Stable Value, Stable Range, and Stability Judgement Time
If the measured value continuously coincides with the set point, it can be said that the measured value is stable. The measured value will not continuously coincide perfectly with the set point if there is noise inference. It is, however, pos­sible to make the measured value stay within a permissible range called the stable range. Even if the temperature is within the stable range, the Temperature Controller may respond to external disturbance or hunting. Therefore, it cannot be said that the temperature is stable unless the temperature stays within the stage range continuously for a certain time. This time is called stability judge­ment time. Like PID constants, stability judgement time is adjusted with fuzzy self-tuning according to the characteristics of the object to be controlled. Fuzzy
32
Terminology
Section 4-3
self-tuning will not be activated if the temperature is stable because the Temper­ature Controller deems that temperature control is smooth.
Shorter than the stability judgement time.
Set point
4-3-2 Hunting
Set pointSet point
Stable range Stable range
(Set to 15.0°C before shipping)
Stability judgement time
Stable Stable
Note The stable range is set to 27°F with the E5J--F.
If the PID constants are not suitable to the controlled device, the measured value will fluctuate and will not coincide with the set point, this phenomenon is called hunting. Hunting is also called cycling.
4-3-3 Characteristics and Characteristics Change
The angle of the maximum temperature slope (R) of the controlled device (i.e., whether the temperature rise of the device is fast or slow) and the dead time (L) of the controlled device (i.e., how fast the change in the output of the Tempera­ture Controller influences the temperature) vary with the characteristics of the controlled device. The PID constants must be set according to the characteris­tics of the controlled device. A characteristics change is the change of the char­acteristics of the c o n t r o l l e d device due to the change of its thermal capacity and the change of the supply voltage. If there is a characteristics change, the PID constants must be adjusted according to the new characteristics.
4-3-4 External Disturbance
External disturbance is an external factor that disturbs the temperature that has been stable within the most ideal PID constants for the controlled device.
4-3-5 Interference
If devices, such as heaters, controlled by different temperature controllers are physically close to one another, the heaters are mutually influenced and the tem­perature of each heater are affected. This phenomenon is called interference. If there is serious interference, it will be difficult for each temperature controller to control the device, and special controlled methods taking this interference into consideration will be required.
33
Terminology
4-3-6 Startup
Section 4-3
Startup means that the Temperature Controller starts operating. The following conditions are required to operate the Temperature Controller.
The Temperature Controller must be turned ON.
No sensor error has occurred.
If a model with event input 2 is used, event input 2 must be set to RUN.
Event input 2 is set to RUN before shipping.
The Temperature Controller will not start operating until all the above conditions are satisfied.
34

Installation and Wiring

This section describes the installation and wiring of the Thermac E5J Temperature Controller.
5-1 Installation 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-1 Dimensions and Mounting Holes 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-2 Mounting Method 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Wiring 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2-1 Connection 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Terminal Arrangement 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 5
35
Installation Section 5-1
5-1 Installation
Install the E5J in the following places.
1, 2, 3...
1. Where there is little mechanical vibration or shock.
2. Where there is no corrosive gas such as sulfide gas.
3. Where the ambient temperature is within –10° to 55°C.
4. Where there is no high heat radiation.
5. Where there is no high tension lines, welding machines or other devices generating electrical noise.
6. Where the E5J is not influenced by any electromagnetic field.
7. Where there is little dust or oily smoke.
8. Where the E5J is not sprayed with water.
5-1-1 Dimensions and Mounting Holes
Refer to the
Appendix Dimensions and Mounting Holes
.
5-1-2 Mounting Method
E5AJ and E5EJ Open a square hole in the panel to which the E5J is to be mounted, mount the
E5J, attach the two mounting brackets provided with the E5J to the upper and lower sides of the E5J, and secure them with a Phillips screwdriver by turning the Phillips screwdriver clockwise until the ratchets of the mounting brackets click.
Mounting bracket
Panel
Watertight packing
E5CJ Open a square hole in the panel to which the E5CJ is to be mounted, mount the
E5CJ, attach the adapter provided with the E5CJ as shown in the following il­lustration to reduce the space between the E5CJ and panel, and secure the adapter with the tightening screw.
Panel
Adapter
36
Mounting screw
Wiring
5-2 Wiring
Section 5-2
Refer to the terminal arrangements to wire the E5J. Before wiring, observe the following.
1, 2, 3...
1. When connecting extension wires to the thermocouple, use proper compen­sating lead wires.
2. When connecting extension wires to the platinum resistance thermometer, use three low-resistance wires of equal resistance.
3. The power supply must not be influenced by noise. If necessary use a noise filter.
4. All the wires connected to the input circuitry must be separated from the wires connected to the power supply or output circuitry.
5. Use shielded wires where static inductance noise is present.
6. Twist the input wires evenly and closely if there is any electromagnetic in­ductance noise.
5-2-1 Connection
With Solderless Terminals Use solderless terminals for M3.5 screws. The terminal screws are M3.5 x 8 self-
up screws.
7.1 max.
Solder-dipped Leads It is possible to connect solder-dipped leads to the terminals with ease. The
length of each bare lead wire should be 6 to 8 mm.
7.3
6 to 8
For side-by-side mounting, Thermac J-series Temperature Controllers are de­signed so that all the lead wires can be connected to the terminals in the same direction.
37
Terminal Arrangement
5-3 Terminal Arrangement
E5AJ/E5EJ Standard Model
Relay Output Unit
E53-R
8
250 VAC 5 A
100 to 240 VAC, 50 or 60 Hz, 14 V A or 24 VAC, 50 or 60 Hz, 10 VA 24 VDC 6 W
Control outputSee note 1.
Alarm output 2
(ALM2)
(ALM1)
See note 3.
Alarm output 1 (Heater burnout alarm and tem­perature alarm)
10
7
Current Output Unit
+53-C3
8
9 8
7 6 5 4
3 2 1
4 to 20 mA DC
7
– (600 max.)
Voltage Output Unit
+E53-Q
8
12 VDC
7
– (40 mA max.) +E53-Q3
8
– 24 VDC
7
(20 mA max.)
250 VAC 3A
250 VAC 3A
Q4
Write the name of the Output Unit to be used on the name­plate on the side of the case.
20
29 28 27 26 25 24 23 22
21
+
19
+
18 17
16 15
14 13 12 11
CT
Section 5-3
See note 2.
Event input 1 (EV1) Externally selects the set point.
Open Short-circuit
Event input 2 (EV2) Selects RUN or STOP.
Open Short-circuit
A
B
+
B
Use the E54-CT1 with a hole diameter of
5.8 mm or E54-CT3 with a hole diameter of 12 mm (both sold separately).
: Set point 0 : Set point 1
: RUN : STOP
Note 1. The E53-C cannot be used.
2. The event input terminals and voltage output and current output terminals are not insulated.
3. Only the heater burnout alarm will be output from the alarm output 1 termi­nals if alarm mode switch 1 is set to 0. Only the temperature alarm will be output if the heater burnout alarm value is set to 0.0 A.
E5AJ/E5EJ with Communications Function
Relay Output Unit
8
10
7
Current Output Unit
+53-C3
8
9 8
7 6 5 4
3 2 1
4 to 20 mA DC
7
– (600 max.)
Voltage Output Unit
+E53-Q
8 7
– 40 mA max. +E53-Q3
8
– 24 VDC
7
250 VAC 3A
250 VAC 3A
100 to 240 VAC, 50 or 60 Hz, 14 V A or 24 VAC, 50 or 60 Hz, 10 VA 24 VDC 6 W
Control outputSee note 1.
Alarm output 2
(ALM2)
(ALM1)
Alarm output 1
See note 2.
(Heater burnout alarm and tem­perature alarm)
E53-R 250 VAC 5 A
12 VDC
Q4
(20 mA max.)
Write the name of the Output Unit to be used on the name­plate on the side of the case.
Communications terminal
29
28 27 26 25
24
23 22
21
CT
Communications terminal
RS-232C RS-422 RS-485
20
RD SG SD SG
29 19
28 18
27 17
26 16
25
RDB RDA
SG SDA
SDB
20
29 19
28 18
27 17
26 16
25
20 19 18
17 16
20
29 19
28 18
27 17
26 16
25
15 14
13 12 11
A
B
+
B
Use the E54-CT1 with a hole diameter of
5.8 mm or E54-CT3 with a hole diameter of 12 mm (both sold separately).
B(+) A(–)
SG A(–) B(+)
38
Note 1. The E53-C cannot be used.
Terminal Arrangement
E5CJ Standard Model
100 to 240 VAC, 50 or 60 Hz, 12 V A or 24 VAC, 50 or 60 HZ, 10 VA 24 VDC 6 W
See note 2.
(Heater burnout alarm and temperature alarm)
2. Only the heater burnout alarm will be output from the alarm output 1 termi­nals if alarm mode switch 1 is set to 0. Only the temperature alarm will be output if the heater burnout alarm value is set to 0.0 A.
Event input 1 (EV1) Exter­nally selects the set point.
open short-circuit
Alarm output 1
Alarm output 2 1 A (resistive load)
at 250 VAC
(ALM1)
See note 1.
5 4 3
2
1
Control output (OUT)
+
10
12 VDC
9
+
10
9
14
13 12
11
+ –
CT
10
9 8
7
6
Use the E54-CT1 with a hole diameter of 5.8 mm or E54-CT3 with a hole diameter of 12 mm (both sold separately).
Voltage Output Unit (20 mA max.)
Current Output Unit 4 to 20 mA DC (with a load of 600 max.)
Relay Output Unit 3 A (resistive load) at 250 VAC
A
B
B
+
Section 5-3
Note 1. The event input terminals and voltage output and current output terminals
are not insulated.
2. Only the heater burnout alarm will be output from the alarm output 1 termi­nals if alarm mode switch 1 is set to 0. Only the temperature alarm will be output if the heater burnout alarm value is set to 0.0 A.
3. A simple model with no alarm does not incorporate any event input or alarm output. A simple model with an alarm function does not incorporate any event input.
39
This section describes the troubleshooting of the Thermac E5J Temperature Controller.
6-1 Error Display and Output 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Troubleshooting 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 6

Troubleshooting

41
Troubleshooting
6-1 Error Display and Output
The Thermac E5J Temperature Controller incorporates a self-diagnostic func­tion. The following table lists the process values and outputs that the E5J has when errors result.
PV display Error Output Items to be checked
Control
output
Abnormal input OFF (2 mA
max.)
Abnormal memory OFF (2 mA
max.)
Abnormal A/D converter
OFF (2 mA max.)
Alarm
output
Processed as an abnormally high temperature.
OFF
OFF
Whether or not the input has exceeded the possible controlling range (±10% of the set temperature range) (see note).
Whether or not the setting of the input type is incorrect.
Whether or not the input has been incorrectly wired, broken, or short-circuited.
Turn the E5J OFF and ON. If the display does not change, the E5J need repairs. If the display returns to normal, the E5J may have been influenced by noise. Check for noise interference.
Section 6-2
Abnormal calibration data. Displayed for 2 s when the E5J is turned on.
Normal operation (accuracy not guaranteed)
The E5J needs calibration. Contact your OMRON representative.
Note If the input is within the possible controlling range but exceeding the possible
display range (–1999 to 9999), –1999 and
will be displayed if the value is larger than 9999, at which time, the
))))
(((( will be displayed if the value is smaller than
control output and alarm output will work normally.
6-2 Troubleshooting
Refer to the following table for troubleshooting.
Phenomenon Probable cause Countermeasure
Nothing is displayed when the E5J is turned on.
No setting is possible. The key protection switch is set to ON. Set the key protection switch to OFF.
When the Up Key is pressed for set point value setting, the value flashes within the set temperature range and the setting is not possible.
No alarm, heater current value display , or heater burnout alarm is displayed.
The internal mechanism is not inserted properly into the housing.
The power supply is not connected to the power supply terminals properly.
No power is supplied or the supplied power is not within the specified range.
The E5J with a communications function is in remote mode.
The set point limit function is active. Properly set the set point lower limit
The alarm mode switch is set to 0. Select the proper alarm mode.
A Current Output Unit is used for control output.
Properly insert the internal mechanism into the housing.
Properly connect the power supply to the power supply terminals.
Supply a voltage of 85 to 264 VAC to the power supply terminals of the E5J.
The E5J must be in local mode or no front key is available.
and set point upper limit values.
No heater burnout is detected if the Current Output Unit is used for control output.
42
Troubleshooting
Phenomenon CountermeasureProbable cause
The process value is abnormal or not obtained.
No control output is obtained. No Control Output Unit is connected. Connect a Control Output Unit (sold
The heater burnout detecting function is abnormal.
The input polarity is wrong or the connection is wrong.
The input-type setting is incorrect. Properly set the input with the
No compensating lead wires are used for the extension of the thermocouple.
The thermocouple and E5J is connected via wires other than proper lead wires.
The sensor is broken or short-circuited.
The E5J is influenced by noise or other induction.
°C is used instead of °F or vice versa. Use the proper temperature unit. The process value is shifted because
the input shift function is used.
Event input 2 of the E5J is set to STOP.
No Current Transformer (CT) is used. Properly connect the dedicated
The heater burnout alarm value is not proper.
The heater is turned ON or OFF with an output other than the control output.
Properly wire the terminals.
input-type selector. Use proper compensating lead wires.
Use a dedicated thermocouple connector. If a metal material dif ferent from the thermocouple is used to connect the thermocouple and E5J, a temperature error may result.
Use a good sensor.
Separate the input wires as far as possible from the origin of the noise.
Set the input shift value to 0.
separately). Open event input 2 and set the E5J
to RUN.
E54-CT1 or E54-CT3 (sold separately) to the E5J.
Set the proper heater burnout alarm value taking into consideration the fluctuation of the heater supply voltage and measurement error.
Use the control output. Heater burnout detection synchronizes with the control output. Any other output cannot be used.
Section 6-2
Simple Method to Determine Temperature Controller Error or Sensor Error
When Thermocouple is Used If the temperature displayed by the E5J is close to the room temperature when
E5J is short-circuited, the E5J deemed to be normal
E5J is close to 0.0°C when a resistor with a
When Platinum Resistance Thermometer is Used
the input terminals of the and it is presumed that the sensor is broken, short-circuited, or incorrectly wired.
If the temperature displayed by the resistance of approximately 100 is inserted between terminals A and –B of the
E5J and terminals +B and –B of the E5J are short-circuited, the E5J
deemed to be normal and it is presumed that the sensor is broken, short-cir­cuited, or incorrectly wired.
43
SECTION 7

Event Input Function

This section describes how the event input function of the Thermac E5J Temperature Controller works.
7-1 Event Input Function 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-1 Set Point Selection 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-2 RUN/STOP Selection (E5AJ-B, E5EJ-B) 46. . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-3 Signal Input Method 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
45
Event Input Function Section 7-1
7-1 Event Input Function
The E5J-B with an event input function is operated with ease with external relay signal selection.
Set Point Selection It is possible to select one of the set points previously set for control operation. RUN/STOP Selection It is possible to enable the E5AJ-B and E5EJ-B to RUN or STOP.
7-1-1 Set Point Selection
Select the set point by opening or short-circuiting event input 1 (EV1). Refer to the following table. No set point can be selected with key operation.
EV1 Set point to be selected
Open Set point 0 (SP0) Short-circuited Set point 1 (SP1)
The following illustration shows the operation of the E5J-B with its EV1 ter­minal short-circuited (i.e., set point 1 is selected).
EV1
Short-circuit
COM
Set point 0 and 1 (2 and 3) set in advance on display level 1.
Display level 0
Displays the set point currently selected.
Set point 0 (SP0)
Set point 1 (SP1)
Set point 2 (SP2)
Set point 3 (SP3)
SP2 and SP3 can be displayed only when the set point selec­tion is selected with the event input 2 selection (set to RUN/ STOP before shipping) on the engineering level. Refer to
tion 9 Engineering Level Set­tings
The set point on display level 0 and that on display level 1 are synchronized. In the above example, if the set point on display level 0 is changed from 200°C to 250°C, the set point 1 value on display level 1 will also change to 250°C.
7-1-2 RUN/STOP Selection (E5AJ-B, E5EJ-B)
RUN or STOP operation is selected by opening or short-circuiting event input 2 (EV2). Refer to the following table. RUN or STOP operation cannot be selected with key operation.
Sec-
for details.
46
EV2 Operation
Open RUN Short-circuited STOP
When the E5J stops operating, its control output will be 0% and fuzzy self-tun­ing will stop but its alarm output will operate normally.
The operation of the E5J the moment the E5J is turned on is determined by the condition of event input 2.
Event Input Function Section 7-1
7-1-3 Signal Input Method
The event input terminals can be short-circuited using a relay or transistor as shown in the following diagram.
+24 V
Signal Input Types
Internal circuitry
0 V
Contact Input No-contact Input
EV*
COM ON: A resistance of 1 k max.
OFF: A resistance of 100 k min.
470
3 k
VF = 1.2 VF = 0.6
(Open collector)
EV*
COM ON: A residual voltage of 3 V max.
OFF: A current leakage of 1 mA max.
EV*
Flow current: 7 mA approx.
COM
The following table lists the event input terminal numbers for each model.
Model E5AJ/E5EJ E5CJ
Input terminal
EV1 20 14 EV2 19 --­COM 17 13
47
SECTION 8

Heater Burnout Detection

This section describes the basic features of heater burnout detection and necessary steps that should be taken at the time of heater burnout, as well as the method of obtaining heater burnout alarm values.
8-1 Heater Burnout Detection 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2 Heater Burnout Procedures 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3 Wiring the Current Transformer 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-4 Heater Burnout Alarm Value 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-4-1 Setting Examples 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
49
Heater Burnout Procedures
8-1 Heater Burnout Detection
To detect heater burnout, wire one of the lead wires for each heater through the hole of the Current Transformer (CT). The CT generates an AC current accord­ing to the current flow of the lead wire. The Thermac E5J Temperature Control­ler measures the AC current to check the current flowing to the heater. If any one of the heaters burns out, the AC current value will decrease so that the E5J turns its heater burnout alarm ON, comparing the AC current value with the heat­er burnout alarm value.
8-2 Heater Burnout Procedures
The E5J starts heater burnout detection from the moment the E5J is turned on. If any one of the heaters is turned on after the E5J is turned on, the heater burnout alarm output will be ON because the E5J judges that the heater is burnt out. Therefore, all the heaters must be turned on simultaneously with the E5J or before the E5J is turned on. This is essential for smooth temperature control and fuzzy self-tuning.
The E5J will continue temperature control even if the heater burnout alarm is ON because the E5J will continue temperature control using the heaters that are not burnt out.
Heater burnout detection is possible when the control output is ON. No heater burnout detection is, however, possible if the control output is ON for less than 190 ms.
The heater burnout alarm output will be held once the heater burnout is de­tected. To reset the heater burnout alarm output, replace the burnout heater with a good one and take one of the following steps.
Section 8-2
1, 2, 3...
1. Set the heater burnout alarm value to 0.0 A.
2. Turn the E5J off and on.
If the difference between the normal heater current value and heater burnout current value is comparatively small, heater burnout detection will not be stable. For stable detection, the difference must be 1.0 A minimum if the heater current consumption is less than 10.0 A and 2.5 A minimum if the heater current con­sumption is 10.0 A or more.
Heater burnout detection is not possible if the E5J has current output, the heater current is DC, or three-phase heaters are used.
Use the K2CU-FA-GS (with gate input terminals) for three-phase heater burnout. Refer to the K2CU-FA-GS data sheet specifications for details.
If no heater burnout detection is executed or if no CT is used, set the heater burn­out alarm value to 0.0 A. The heater burnout alarm value is factory-set to 0.0 A.
50
Heater Burnout Alarm Value
8-3 Wiring the Current Transformer
Refer to the following diagram for the wiring the CT.
Relay driven with control output
Heater
Section 8-4
To the CT input terminals of the E5J. The CT input terminals have no polarity.
AC power supply
CT
To the CT input terminals of the E5J
8-4 Heater Burnout Alarm Value
To obtain the proper heater burnout alarm value, check the normal heater cur­rent value and heater burnout current value with the heater current value display on display level 1 first and set the heater burnout alarm value to the mean value of these two values. If more than one heater is used, check the burnout value of the heater with the smallest current consumption value.
To heater
CT
Heater burnout alarm value
Normal heater current value
=
Heater burnout
+
current value
2
If the difference between the normal heater current value and heater burnout current value is comparatively small, heater burnout detection will not be stable. For stable detection, the difference must be 1.0 A minimum if the heater current consumption is less than 10.0 A and it must be 2.5 A minimum if the heater cur­rent consumption is 10.0 A or more.
If normal current value 10.0 A Then normal current value – heat burnout current value 1.0 A
If normal current value 10.0 A Then normal current value – heater burnout current value 2.5 A
The heater burnout alarm value can be set within a range of 0.0 to 50.0 A. If the alarm value is set to 0.0 A or 50.0 A, no heater burnout detection is possible. The alarm output is always OFF if the alarm value is set to 0.0 A and always ON if th e alarm value is set to 50.0 A.
51
Heater Burnout Alarm Value
Section 8-4
The normal heater current value should be 50.0 A max. The heater current value can, however, display up to 55.0 A. If the current value exceeds 55.0 A, CT input overflow will result and ffff will be displayed.
CT input overflow
8-4-1 Setting Examples
Example 1 In this example, 1-kW, 2-kW, and 3-kW heaters at 200 VAC are connected in par-
allel.
1, 2, 3...
1. Turn the control output ON and check the normal heater current value from the heater current value display.
Normal current = (1000 + 2000 + 3000) 200 = 30.0 A
Heater current value display
Normal heater current value
Heater Control
output ON
1KW 2KW 3KW
200 VAC
CT
2. Disconnect the heater whose current consumption is smallest and compare the heater current value from the heater current value display.
Heater burnout current = 30.0 – 1000 200 25.0 A
Heater current value display
Heater burnout current value
Heater Control
1KW 2KW 3KW
Disconnect
output ON
200 VAC
CT
Normal current – heater burnout current = 30.0 – 25.0 = 5 A ( 2.5 A)
3. Set the heater burnout alarm value to the mean value of the normal current value and heater burnout current value.
Heater burnout alarm value = (30.0 + 25.0) 2 = 27.5 A
Example 2 In this example, 400-W, 1700-W, and 2000-W heaters at 200 VAC are con-
nected in parallel and the difference between the normal current value and heat­er burnout current value is less than 2.5 A.
1, 2, 3...
1. Obtain the normal current value and heater burnout current value in ad­vance as follows:
Normal current = (400 + 1700 + 2000) 200 = 20.5 A Heater burnout current = 20.5 – 400 200 = 18.5 A Normal current – heater burnout current = 20.5 – 18.5 = 2.0 A (Stable detec-
tion is not possible because the value is not 2.5 A or more.)
2. For stable hater burnout detection, in such a case, increase the number of turns of the wire passing through the CT as if apparent current value in-
52
Heater Burnout Alarm Value
Section 8-4
creases. The displayed heater current value increases in proportion to the number of turns of the wire passing through the CT.
Heater wire
The wire passes through the CT twice.
3. Obtain the heater burnout alarm value using the method in example 1. Apparent normal current = (400 + 1700 + 2000) 200 x 2 = 41.0 A
Normal heater current value
Apparent heater burnout current = (41.0 – 400 200) x 2 = 37.0 A
Heater burnout current value
Normal current – heater burnout current = 41.0 – 37.0 = 4.0 A ( 2.5 A) Heater burnout alarm value = (41.0 + 37.0) 2 = 39.0 A
Heater burnout alarm setting
53
SECTION 9

Engineering Level Settings

This section describes the parameters that can be changed on the engineering level. These parameters should be changed only when the values set before shipping do not suit the application. After these parameters are changed on the engineering level, record the contents of the changes for your future reference.
9-1 Engineering Level 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-2 Engineering Level Parameter List 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-3 Engineering Level Parameters 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
55
Engineering Level Parameter List
9-1 Engineering Level
To go to engineering level, set pin 4 of the internal function switch of the E5J to ON before turning the E5J on. After this setting, set pin 4 of the internal func­tion switch to OFF.
Turn on the E5J.
Set pin 4 of the function switch to ON.
9-2 Engineering Level Parameter List
The following is a list of engineering level parameters.
Section 9-2
This display will appear.
Display Name Setting range Setting before
shipping
d-U °C/°F selection
LEn Data bit length 7: Data length of 7 bits
PrtY Parity check
Sbit Stop bit length 1: 1 bit
S.t-b Stable range 0.1 to 999.9 °C/°F 15.0 (27.0)
15.0
ALFA Alpha 0.00 to 1.00 0.65
rEt Automatic return of
display mode
rESt Standby sequence reset
method
c: °C f: °F
8: Data length of 8 bits
none: No parity eUen: Even odd: Odd
2: 2 bits
0 to 99 s 0: No automatic return
0: Reset method 0 1: Reset method 1
c
7
eUen
2
0
0
User’s remarks
56
in-S Input shift display
ALH1 Alarm 1 hysteresis 0.1 to 999.9 °C/°F 0.2 (0.4)
ALH2 Alarm 2 hysteresis 0.1 to 999.9 °C/°F 0.2 (0.4)
SL-L Set point lower limit
value
off: Not displayed on: Displayed
Set range lower limit to set point upper limit value (see note 1). (°C/°F)
off
–200 (–300)
Engineering Level Parameter List
Section 9-2
Display User’s remarksSetting before
SL-H Set point upper limit
value
EV-2 Event input 2 type
selection
Setting rangeName
Set range lower limit value to set range upper limit value (see note 1). (°C/°F)
0: Set point selection (SP2, SP3)
1: RUN/STOP
shipping
1300 (2300)
1
Note 1. The decimal position varies with the input type.
2. The value in the parentheses is the E5J--F setting before ship­ping.
57
Engineering Level Parameters
9-3 Engineering Level Parameters
15.0
Section 9-3
The value set before shipping appears. (see note 1)
(°C/°F selection)
Displayed if the E5J with a com­munications function is used.
(Data bit length setting)
(Parity check setting)
(Stop bit length setting)
Displayed if the E5J is in advanced PID operation with fuzzy self-tuning.
(Stable range setting)
Displayed if the E5J is in advanced PID operation.
(Alpha setting)
(Automatic return of display mode)
Displayed if the E5J with an alarm function is used (see note 2).
(Standby sequence reset method setting)
(Input shift display selection)
Displayed if the E5J with an alarm function is used (see note 2).
(Alarm 1 hysteresis setting)
Displayed if the E5J with an alarm function is used (see note 2).
(Alarm 2 hysteresis setting)
(Set point lower limit setting)
(Set point upper limit setting)
Displayed if the E5J with event input 2 is used.
(Event input 2 function selection)
58
Note: 1. The E5J--F values set before shipping may be
different. Refer to
2. The value will not be displayed if the alarm mode switch is set to 0 or if the E5J does not incorporate any alarm.
9-2 Engineering Level Parameter List.
Engineering Level Parameters
Section 9-3
rdu °C/°F Selection To change the temperature display unit from °C to °F, press the Up Key so that f
will be displayed in the set value display.
E5J with Communications Function
SV SV
The communications specifications of the E5J are as follows: Data bit length: ASCII 7- (set before shipping) or 8-bit code
c: °C f: °F
Parity check: None, even (set before shipping), or odd Stop bit length: 1 or 2 (set before shipping) Use the following parameters to change the above setting.
len Data Bit Length Use this parameter to change the communications data bit length. prty Parity Check Use this parameter to change the communications parity check.
SV SV
SV
none : None eUen : even odd : odd
sbit Stop Bit Use this parameter to change the stop bit length. s.t-b Stable Range (°C/°F) This parameter is used to decide conditions under which fuzzy self-tuning oper-
ates and can be set within a range of 0.1 to 999.9. If the absolute value of the deviation (the difference between the process value and set point) is within the stable range, temperature control operation is deemed smooth and fuzzy self­tuning will not start.
Stable
Set point
Stable
PID before tuning
It is deemed that the characteristics of the control device have been changed so that the response wave­form is processed to tune the PID constants.
Fuzzy self-tuning
PID after tuning
range
alfa (α) PID Control Type By adjusting internal parameter α of advanced PID within a range of 0.00 to 1.00,
PID control such as derivative preceding PID or proportional preceding PID (I­PD) control will be possible.
α = 0.00 (Derivative preceding PID)
Set point
α = 0.65
α = 1.00
(Proportional preceding PID)
Difference in set point response due to α.
To increase the set point response speed, decrease the value of parameter α. If the value of parameter α is decreased, however, the overshooting value will in­crease.
59
Engineering Level Parameters
Section 9-3
ret Automatic Return of Display Mode (Return Time)
rest Standby Sequence Reset Method
By setting automatic return of display mode, the display will return to the normal operation display (on level 0 displaying the process value or set point) if no key is operated for the time set with this parameter . The return time can be set within a range of 0 to 99 s. If the return time is set to 0 s, this function will not work. The return time is set to 0 s before shipping.
It is possible to select the restart conditions of the standby sequence of the alarm attached with standby sequence. If this parameter is set to 0, the standby se­quence will restart when the set point, alarm value, or input shift value is changed or the moment the E5J starts operating including the moment the E5J is turned on. If this parameter is set to 1, the standby sequence will restart only the moment the E5J is turned on. The following timing chart is an example of a lower limit alarm attached with standby sequence.
Standby sequence releasing point
Standby sequence releasing
OFF point due to alarm hysteresis
Alarm point
(Standby sequence reset method 0)
Alarm output
(Standby sequence reset method 1)
Alarm output
point
Standby sequence restart
Set value change
ins Input Shift Display It is possible to select to display or not to display the input shift function on display
level 1 with this parameter.
alh1 Alarm 1 Hysteresis and alh2 Alarm 2 Hysteresis
SV SV
It is possible to adjust alarm sensitivity with both these parameters within a range of 0.1 to 999.9. Change the alarm sensitivity of the E5J if the alarm output chat­ters.
Upper limit alarm
ON OFF
Low
temperature
Alarm point
Hysteresis
High
temperature
off : Not displayed on : Displayed
Lower limit alarm
ON OFF Low
temperature
Hysteresis
Alarm point
High
temperature
The alarm output will be OFF when the process value is within the alarm hystere­sis range when the E5J restarts (e.g., when the E5J is turned on).
sll Set Point Lower Limit Value (°C/°F) and slh Set Point Upper Limit Value (°C/°F)
It is possible to limit the set point changeable range with both these parameters. For example, if the set point lower limit value is set to 0°C and the set point upper limit value is set to 400°C, the set point can be changed only between 0°C and 400°C.
60
Engineering Level Parameters
Section 9-3
eu2 Event Input 2 Type Selection
It is possible to select the function of event input 2. If 0 (set point value selection) is selected, sp2 and sp3 will be displayed on display level 1 and if 1 is selected RUN/STOP will be selected. When 0 is selected, the set point can be selected from the following.
EV1
20
EV2
19
COM
17
EV1 EV2 Set point to be selected
Open Open SP0 Short-circuit Open SP1 Open Short-circuit SP2 Short-circuit Short-circuit SP3
61
This section describes how to execute auto-tuning.
10-1 Starting Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-2 Conditions that Prevent Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-3 Force-ending Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-4 Changing Parameters during Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 10

Auto-tuning

63
Changing Parameters during Auto-tuning
10-1 Starting Auto-tuning
Auto-tuning can be started by using the following procedure. Use this procedure when appropriate results are not achieved via fuzzy self-tuning.
Section 10-4
1, 2, 3...
1. Turn ON pin 3 of the function selector switch to select the advanced PID con­trol mode (refer to
2. Press the Level Key and the Display Key simultaneously for 1 s or longer to start auto-tuning.
Section 2-3-5
).
10-2 Conditions that Prevent Auto-tuning
You will not be able to start auto-tuning when any of the following conditions ex­ist.
When the control mode is set for ON/OFF control or advanced PID control with fuzzy self-tuning.
When an engineering level parameter is displayed.
When the key protection switch is set to SP
When the remote/local setting is set to remote.
When the RUN/STOP setting is set to STOP.
When a sensor error, memory error, or A/D converter error has occurred.
10-3 Force-ending Auto-tuning
Auto-tuning will be forced to end for any of the following conditions.
When the Temperature Controller is turned off.
When the RUN/STOP setting is changed to STOP.
When a sensor error occurs.
When the Level Key and the Display Key are pressed simultaneously for 1 s or
longer.
or ALL.
10-4 Changing Parameters during Auto-tuning
Parameters cannot be changed during auto-tuning, but the remote/local set­ting can be changed.
The SP also cannot be changed via the event input during auto-tuning, but the event input status can be changed and the SP will be changed after auto-tun­ing has been completed.
Auto-tuning
Open
SP0
SP0 selected.
Auto-tuning started. Scale changes disabled here.
Shorted
SP1 selected.
Set point
Event input terminal
64
SP1
E5AJ
Dimensions
Appendix A
Dimensions/Mounting Holes
96 x 96
Mounting Holes
120 min.
92
12 98
112
+0.8 0
+0.8
92
0
(96 x units – 3.5)
91 x 91
+1 0
+0.8
92
0
Note 1. All dimensions shown are in millimeters.
2. Side-by-side close mounting is not possible for E5AJs equipped with the Watertight Cover (sold sepa­rately).
65
E5EJ
Dimensions
Appendix ADimensions/Mounting Holes
48
96
Mounting Holes
120 min.
45
+0.6 0
12 98
112
+0.8
92
0
(48 x units – 2.5)
44
91
+1 0
+0.8
92
0
Note 1. All dimensions shown are in millimeters.
2. Side-by-side close mounting is not possible for E5EJs equipped with the Watertight Cover sold sepa­rately).
E5CJ
Dimensions
48 x 48
66
9.5
58
100
44.8 x 44.8
Appendix ADimensions/Mounting Holes
Mounting Holes
+0.6
45
60 min.
0
45
+0.6 0
(48 x units – 2.5)
+1 0
+0.6
45
0
Note 1. All dimensions shown are in millimeters.
2. Side-by-side close mounting is not possible for E5CJs equipped with the Watertight Cover (sold sepa­rately).
Terminal Covers
E53-COV02 E5AJ with Terminal Cover
12 115
112
E53-COV04 E5CJ with Terminal Cover
9.5
115
58
67
E53-COV03 E5EJ with Terminal Cover
12 115
112
Appendix ADimensions/Mounting Holes
68

Index

A
advanced PID
function, 2 setting, 14 setting with fuzzy self-tuning, 14
alarm mode
changing, 22 setting. See settings standby sequence. See settings
auto-tuning
force-ending, 64 parameters, 64 preventing, 64 starting, 64
automatic return of display mode. See engineering level
C
communications function, specifications, 7 control period, setting range, 24 CT. See current transformer current transformer
specifications, table, 6 wiring, 51
cycling. See hunting
D
E
engineering level
alarm hysteresis, 60 automatic return of display mode, 60 communications, 59 data bit length, 59 input shift display, 60 parameters, 19 parameters table, 56 parity check, 59 PID control type, 59 selecting temperature display, 59 settings, 56 stable range, 59 standby sequence reset, 60 stop bit, 59
event input 2, 33
selecting, 61
event input function, 2
parameters, 24 selecting RUN/STOP, 46 selecting set point, 46 signal input method, 47
external disturbance, definition, 32
F
features, 2 front panel, features, 18 functions
control mode, 14 level setting, 14 output operation, 14 selector settings, 14
fuzzy self-tuning
features, 28 function, 2
derivative time range, 25 dimensions, 65, 66, 67 display levels
level 1, 23 parameters, 22, 23
displays
engineering level, 19 levels, 19
disturbance tuning
conditions, 29 measuring external disturbance response waveform, 29 measuring set point response waveform, 29 startup conditions, 29
DT. See disturbance tuning
H
heater burnout
detection, 50 procedures, 50
heater burnout alarm
current value, 24 determining value, 51 operating characteristics, 7 parameters, 24 setting examples, 52
setting value, 24 HT. See hunting tuning hunting, definition, 32 hunting tuning, startup conditions, 30 hysteresis, setting range, 24
69
Index
I
installation
mounting, 36
precautions, 36 integral time range, 25 interference, definition, 33 internal switches, sensor type and control mode, 10
K-M
key protection switch, setting, 15 manual reset value, 25 models, 2
Communications Boards, 4
communications function, limitations, 3, 4
standard, 3 mounting. See installation mounting holes, 65, 66, 67
N-O
nomenclature, 18 output unit
life expectancy, 7
npn type, 11
pnp type, 11
selecting, 10
specifications, table, 6
types and models, 2 output value, setting range, 24
set point
See also event input function adjusting changeable range, 60 setting type, 22
settings
advanced PID control, 14 alarm mode selection, 13 functions. See functions fuzzy self-tuning, 14 internal switches, 11, 12 key protection switch, 15 selecting input type, 12 selecting output unit, 10 sensor type and control mode, 10
specifications
general, table, 5 operating characteristics, table, 6
output unit, table, 6 SRT. See step response tuning stability judgement time, 32 stable range, 32 stable value, 32 standby sequence, resetting. See engineering level startup, 33 step response tuning
See also SRT
operating conditions, 28
PID constant refreshing conditions, 29
startup conditions, 28
step controlled amount, 29 STOP, selection, 46 stop bit, changing length. See engineering level
P
parameters
engineering level, 19 levels, 19 setting, 19
tables, 20 PID, setting constants, 32 proportional band range, 25
R
return time, 60 RUN, selection, 46
S
self-diagnostic function, 42
70
T
terminal arrangement, 38 Terminal Covers, 67 troubleshooting, 30
controller and sensor error, 43 table, 42
W
watertight cover, 2 wiring
current transformer, 51 precautions, 37 terminal arrangement, 38, 39 using solder-dipped leads, 37 using solderless terminals, 37

Revision History

E5J Temperature Controller
Operation Manual
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. WZ103-E3-1
Revision
code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version for manuals designated as E1 revisions.
Revision code Date Revised content
Z103-E1-1 November 1993 Original production Z103-E1-1A January 1994 Page 20: Hysteresis row in the table corrected. Note added.
Page 21: Proportional band row in the table corrected. Note added. Page 23: Proportional band setting in the diagram corrected. Page 29: Stable range in both diagrams corrected. Note added. Pages 30, 32: Stable range in top diagram corrected. Page 51: “Heater current value level 1” corrected to “Heater burnout value” in
the equation. Page 56: Stable range, alarm hysteresis 1, alarm hysteresis 2, and set point
lower limit value rows in the table corrected.
Page 57: Note added. Z103-E1-2 March 1994 Major revision. Most of the pages have been changed or revised. Z103-E1-3 June 1995
Z103-E1-4 November 1996 Page 2: Auto-tuning added to
Section 10 Auto-tuning
Page 2:
Page 4: Note 1 corrected.
Page 6: Models added to the Output Units table.
Page 10: Models added to the Output Units table and second sentence after
the table corrected.
Page 28: First note on the page corrected.
Page 38: The polarities for RS-485 in
tion
Page 5: Auto-tuning added to
Page 7:
ratings
Page 38: “+” added to terminals 20 and 19 and “–” added to terminal 17 in the
E5AJ/E5EJ Standard Model terminal arrangement.
Page 39: “+” added to terminal 17 and “–” added to terminal 16 in the E5BJ
terminal arrangement. “+” added to terminal 14 and “–” added to terminal 13 in
the E5CJ Standard Model terminal arrangement.
Pages 65 to 68: Terminal Covers and their dimensions added.
Output Units
.
EMC
and
changed. Notes added also.
added.
corrected.
1-1 Features Control mode
Approved standards
E5AJ/E5EJ with Communications Func-
.
in the table.
added to the top table and
Enclosure
71
Revision History
Revision code Revised contentDate Z103-E1-5 February 1998 Page 4: Supply voltage and power consumption specifications changed.
Page 19: Thermac E5J information added to the beginning of
Flowchart
Pages 38, 39: Terminal arrangement diagrams changed.
Page 56: Information added to
Z103-E3-1 March 1998 All references to model E5BJ removed.
Pages 38,39: Corrected power consumption in terminal arrangement draw-
ings (based on revision E1-5); kept terminal arrangement drawings the same
as revision E1-4.
.
9-1 Engineering Level
.
3-2 Setting
72
Loading...