Omron E5AJ-A2HB, E5AJ-A2H01, E5AJ-A2H02, E5AJ-A2HM, E5CJ-R Operation Manual

...
E5J Temperature Controller
Operation Manual
Cat. No. Z103-E3-1
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
DANGER Indicates information that, if not heeded, is likely to result in loss of life or serious
!
injury.
WARNING Indicates information that, if not heeded, could possibly result in loss of life or
!
serious injury.
Caution Indicates information that, if not heeded, could result in relatively serious or mi-
!
nor injury, damage to the product, or faulty operation.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for any­thing else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
OMRON, 1998
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permis­sion of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the informa­tion contained in this publication.
Note Indicates information of particular interest for efficient and convenient operation
of the product.
1, 2, 3...
1. Indicates lists of one sort or another, such as procedures, checklists, etc.
v

TABLE OF CONTENTS

SECTION 1
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 Features 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 Models 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Specifications 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Sensor and Mode Settings9. . . . . . . . . . . . . . . . . . . . . . . .
2-1 Disassembly 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Output Units 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Internal Switch Settings 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
Settings Before Operation 17. . . . . . . . . . . . . . . . . . . . . . . . .
3-1 Nomenclature 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Setting Flowchart 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 List of Parameters 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Parameters on Display Level 0 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 Parameters on Display Level 1 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4
Fuzzy Self-tuning 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1 Fuzzy Self-tuning Operation 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Troubleshooting 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Terminology 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 5
Installation and Wiring 35. . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1 Installation 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Wiring 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Terminal Arrangement 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 6
Troubleshooting 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 Error Display and Output 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Troubleshooting 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 7
Event Input Function 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1 Event Input Function 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 8
Heater Burnout Detection 49. . . . . . . . . . . . . . . . . . . . . . . . .
8-1 Heater Burnout Detection 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2 Heater Burnout Procedures 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3 Wiring the Current Transformer 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-4 Heater Burnout Alarm Value 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 9
Engineering Level Settings 55. . . . . . . . . . . . . . . . . . . . . . . .
9-1 Engineering Level 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-2 Engineering Level Parameter List 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-3 Engineering Level Parameters 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
vii
TABLE OF CONTENTS
SECTION 10
Auto-tuning 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-1 Starting Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-2 Conditions that Prevent Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-3 Force-ending Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-4 Changing Parameters during Auto-tuning 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendices
A Dimensions/Mounting Holes 65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index 69. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision History 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
viii
About this Manual:
This manual describes the installation and operation of the Thermac E5J Temperature Controller and includes the sections described below.
Please read this manual carefully and be sure you understand the information provided before attempting to install and operate the Thermac E5J Temperature Controller.
Section 1 Section 2
necessary before turning on the Thermac E5J Temperature Controller.
Section 3
operating the Thermac E5J Temperature Controller.
Section 4
to the characteristics of the device for ideal temperature control.
Section 5 Section 6 Section 7 Section 8
taken at the time of heater burnout, as well as the method of obtaining heater burnout alarm values.
Section 9
should be changed only when the values set before shipping do not suit the application. After these pa­rameters are changed on the engineering level, record the contents of the changes for your future refer­ence.
Section 10
The perature Controller Units.
describes the specifications and basic features of the Thermac E5J Temperature Controller. describes the sensor and mode settings of the Thermac E5J Temperature Controller that are
describes the settings of the Thermac E5J Temperature Controller that are necessary before
provides the procedures required to adjust all PID constants using fuzzy self-tuning according
describes the installation and wiring of the Thermac E5J Temperature Controller.
describes the troubleshooting of the Thermac E5J Temperature Controller. describes how the event input function of the Thermac E5J Temperature Controller works. describes the basic features of heater burnout detection and necessary steps that should be
describes the parameters that can be changed on the engineering level. These parameters
describes how to execute auto-tuning.
Appendix
provides the dimensions and mounting specifications for the various Thermac E5J Tem-
!
WARNING Failure to read and understand the information provided in this manual may result in
personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
ix
SECTION 1

Introduction

This section describes the specifications and basic features of the Thermac E5J Temperature Controller.
1-1 Features 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 Models 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Specifications 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-1 Ratings 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-2 Characteristics 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Models
Section 1-2
1-1 Features
The basic features of the Thermac E5J Temperature Controller are outlined below.
Fuzzy Self-tuning When using a conventional temperature controller for ideal temperature control,
it is necessary to adjust the PID constants of the temperature controller accord­ing to the controlled device. The Thermac E5J Temperature Controller incor­porates a fuzzy self-tuning function, thus allowing ideal temperature control without any adjustment of the PID constants. The user needs only to set the E5J to the desired temperature for ideal temperature control.
Auto-tuning Auto-tuning is also available. It is useful when appropriate results are not
obtained through fuzzy self-tuning. (Refer to
Section 10 Auto-tuning
Event Input Function It is possible to select a set point out of a maximum of two set values on the
E5CJ-B and four set values on the E5AJ-B via their event input terminals from the PCs connected to these Temperature Controllers. The control opera­tion of the E5AJ-B via can be stopped with an event input signal.
Watertight Construction The E5J can be used in places where water is sprayed onto the E5J, be-
cause the front panel of the E5J assures IP54 when the E5J is panel­mounted (except for front panel of the E5CJ, which assures IP50). If greater wa­tertightness is required, use the Y92A-N, a dedicated watertight cover (sold separately).
.)
Advanced PID
The E5 J incorporates an advanced PID function, which is also incorporated by the Thermac X Temperature Controller. The advanced PID function prevents temperature overshooting the moment the Temperature Controller starts oper­ating, assures a short startup time, and performs ideal temperature control by quickly responding to external disturbances.
Output Units The E53-R Relay Unit, E53-Q, E53-Q3, and E53-Q4 Voltage Output Units for
driving SSRs, and E53-C3, E53-C3D, E53-V34, and E53-V35 Linear Output Unit can be connected to any E5J Temperature Controller (except the E5CJ) with ease according to the desired output configuration and application.
1-2 Models
The thermocouples and platinum resistance thermometers listed in the follow­ing table can be connected to any Thermac E5J Temperature Controller.
Input
Temperature range (°C)
INPUT
Factory-set to 2 (K)
Selectable internally.
1300 1000 800 600 400 200 100 0 –100 –200
Setting no.
Platinum resistance thermometer
JPt100
650.0
–199.9 –200
0.8 1.9 2 3 4 5 6 7
Pt100
650.0
KJ T L U N
1300
–200–199.9 –199.9 –199.9
850
–100
Thermocouple
400.0
–100
1300
850
400.0
2
Models
Section 1-2
E5AJ (Standard Model with Communications Function)
96 X 96mm
Alarm 2 relay output points with heater burnout alarm (see note 1) Event input 2 points (set point selection, RUN/STOP) (see note 2) Control output Replaceable Output Unit (sold separately) Model Communications function --- E5AJ-A2HB
RS-232C E5AJ-A2H01 RS-422 E5AJ-A2H02 RS-485 E5AJ-A2H03
Communications Board add-on model E5AJ-A2HM
Note 1. No heater burnout alarm is output if the E53-C3 Current Output Unit is used
with the E5AJ.
2. The event input function is not incorporated by models that have a commu­nications function.
E5EJ (Standard Model with Communications Function)
48 X 96mm
Alarm 2 relay output points with heater burnout alarm (see note 1) Event input 2 points (set point selection, RUN/STOP) (see note 2) Control output Replaceable Output Unit (sold separately) Model Communications function --- E5EJ-A2HB
RS-232C E5EJ-A2H01 RS-422 E5EJ-A2H02 RS-485 E5EJ-A2H03
Communications Board add-on model E5EJ-A2HM
Note 1. No heater burnout alarm is output if the Linear Output Unit is used with the
E5EJ.
2. The event input function is not incorporated by models that have a commu­nications function.
3
6 (at C)
Specifications
Section 1-3
E5CJ (Simple and Standard Models)
48 X 48mm
Type Simple model type Standard model
type
Alarm --- 2 replay output points with the same
common. (see note 1) Heater burnout alarm --- Yes (see note) Event input --- 1 point (set point
selection)
Model Control output Relay output E5CJ-R E5CJ-R2 E5CJ-R2HB
Voltage output E5CJ-Q E5CJ-Q2 E5CJ-Q2HB Current output E5CJ-C E5CJ-C2 E5CJ-C2B
Note No heater burnout alarm is output if a current control output is used.
Communications Boards
Note For details, refer to the
Communications RS-232C RS-422 RS-485
Model E53-J01 E53-J02 E53-J03
E5AJ/E5EJ Communications Manual (Z102).
1-3 Specifications
1-3-1 Ratings
E5J
Item Specification
Supply voltage 100 to 240 VAC, 50 or 60 Hz 24 V AC/DC,
50 or 60 Hz Operating voltage range 85 to 110% of supply voltage Power consumption E5AJ 10 VA (at 100 VAC) to
14 V A (at 240 VAC)
E5EJ 10 VA (at 100 VAC) to
14 V A (at 240 VAC)
E5CJ 10 VA (at 100 VAC) to
12 V A (at 240 VAC)
Input Thermocouples (K, J, T, L, U, and N) and platinum
resistance thermometers (JPt100 and Pt100) CT input Dedicated CT (E54-CT1 or E54-CT3) Control output E5AJ/E5EJ Replaceable Output Unit (sold separately)
E5CJ Relay output SPST-NO, 3 A at 250 VAC (resistive load)
Voltage output 20 mA at 12 VDC (with short-circuit protection) Current output 4 to 20 mA DC with a load of 600 max. and a
resolution of approx. 2600 Control mode ON/OFF or advanced PID with fuzzy self-tuning and
auto-tuning Alarm output E5AJ/E5EJ 2 SPST-NO relay output points, 3 A at 250 VAC
(resistive load)
E5CJ 2 SPST-NO relay output points (with the same common),
1 A at 250 VAC (resistive load) Setting method Digital setting with Up Key and Down Key
10 V A (at 24 VAC) 6 W (at 24 VDC)
4
Specifications
Item Specification
Indication method E5AJ All digital indication (PV: Red, 15 mm; SV: Green,
10.5 mm)
E5EJ All digital indication (PV: Red, 14 mm; SV: Green,
9.5 mm)
E5CJ All digital indication (PV: Red, 12 mm, SV: Green 8.0
mm) Event input Contact input: ON: 1 k max. OFF: 100 k min.
No-contact input: ON: residual voltage of 3 V max; OFF:
current leakage of 1 mA max. Other function Key protect
Cooling operation/Heating operation
Heater burnout alarm
Model with event input (E5J-B)
Set point selection (set point x 2)
RUN/STOP (E5AJ-B and E5EJ-B only)
Ambient operating temperature –10°C to 55°C (with no condensation) Ambient operating humidity 35 to 85% Storage temperature –25°C to 65°C (with no condensation)
Section 1-3
Output Units
Model Specification
E53-R Relay Output Unit SPDT (SPST-NO when used with the
E5J), 5 A at 250 VAC (resistive load)
E53-Q Voltage Output Unit NPN, 40 mA at 12 VDC (with
short-circuit protection)
E53-Q3 Voltage Output Unit NPN, 20 mA at 24 VDC (with
short-circuit protection)
E53-Q4 Voltage Output Unit PNP, 20 mA at 24 VDC (with
short-circuit protection)
E53-C3 Linear Output Unit 4 to 20 mA DC with a load of 600
max. (with a resolution of approximately 2600 when used with the E5J) (see note)
E53-C3D Linear Output Unit 0 to 20 mA DC with a load of 600
max. (with a resolution of approximately 2600 when used with the E5J)
E53-V34 Linear Output Unit 0 to 10 VDC with a load of 1 k min.
(with a resolution of approximately 2600 when used with the E5J)
E53-V35 Linear Output Unit 0 to 5 VDC with a load of 1 k min.
(with a resolution of approximately 2600 when used with the E5J)
Note The E53-C cannot be used.
Current Transformer (CT)
Item Specification
Maximum continuous heater current 50 A Dielectric strength 1,000 VAC Vibration resistance 50 Hz, approx. 98 m/s2 (10G) Weight E54-CT1: Approx. 11.5 g
E54-CT3: Approx. 50 g
5
Specifications
Section 1-3
1-3-2 Characteristics
E5J
Item Specification
Indication accuracy ±0.5% or ±1°C whichever is larger ± 1 digit max.
Thermocouple K, T, or N at a temperature of –100°C; thermocouple U at ± 2°C ± 1
digit max. Hysteresis (for ON/OFF control) 0.1 to 999.9°C/° F (in units of 0.1°C/°F) Proportional band 0.1 to 999.9°C/°F (in units of 0.1°C/°F) Integral time 0 to 3999 s (in units of 1 s) Derivative time 0 to 3999 s (in units of 1 s) Control period Relay or voltage output:1 to 99 s (in units of 1 s) Manual reset value (I = 0) 0.0 to 100.0% (in units of 0.1%) Alarm setting range With K, J, L, or N input: –1999 to 9999° C/°F (in units of 1°C/°F)
With JPt100, Pt100, T, or U input: –199.9 to 999.9° C/°F (in units of 0.1°C/°F) Sampling period 500 ms Output refresh period 500 ms Display refresh period 500 ms Insulation resistance 20 M min. at 500 VDC (measured with an Output Unit) Dielectric strength 2000 VAC, 50/60 Hz for 1 min. between charged terminals different from each other
in polarity Vibration
resistance Shock resistance Malfunction 196 m/s2 (20G) 3 times each in 3-axis 6 directions (98 m/s2 (10G) for the relay)
Weight E5AJ Approx. 360 g; mounting bracket: approx. 65 g
Enclosure rating Front panel: E5AJ/E5EJ: IEC standard IP54
Memory Protection Non-volatile memory EMC Emission Enclosure: EN55011 Group 1 class A
Approved standards UL1092, CSA C22.2 No. 142
Malfunction 10 to 55 Hz, 9.8 m/s2 (1G) 10 min. in X, Y, and Z directions Destruction 10 to 55 Hz, 19.6 m/s2 (2G) 2 hr. in X, Y, and Z directions
Destruction 294 m/s2 (30G) 3 times each in 3-axis 6 directions
E5EJ Approx. 280 g; mounting bracket: approx. 65 g E5CJ Approx. 170 g; adapter: approx. 10 g
E5CJ: IEC standard IP50 (see note 1) Rear case: IEC standard IP20 Terminals: IEC standard IP00
Emission AC Mains: EN55011 Group 1 class A Immunity ESD: EN61000-4-2:4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3) 10 V/m (pulse modulated,
900 MHz) Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: EN61000-4-4:2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1) (see note 2) Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is mounted.
Note 1. The model numbers of the exclusive watertight covers conforming to IP66,
NEMA4 are as follows: For E5AJ: Y92A-96N; For E5CJ: Y92A-48N; For E5EJ: Y92A-49N
2. Basic insulation is between the input and output.
6
Specifications
Section 1-3
Output Unit
Heater Burnout Alarm
Note 1. Use the K2CU-FA-GS (with gate input terminals) for the detection of
Model with Communications Function
Model Life expectancy
E53-R Relay Output Unit Mechanical 10,000,000 times min.
Electrical 100,000 times min.
Item Specification
Max. heater current Single-phase 50 A VAC (see note 1) Heater current value display accuracy ±5% FS ± 1 digit max. Heater burnout alarm setting range 0.1 to 49.9 A (in units of 0.1 A)
Min. detection ON time 190 ms (see note 3)
(see note 2)
three-phase heater burnout.
2. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and al­ways ON if the alarm is set to 50.0 A.
3. No heater burnout detection or heater current value measurement is pos­sible if the control output is ON for less than 190 ms.
Refer to the
Interface RS-232C, RS-422, RS-485 Communications method Half duplex Synchronization method Start-stop synchronization
Communications speed 1200, 2400, 4800, 9600, and 19200 bps Communications
item
E5AJ/E5EJ Communications Manual (Z102)
Item Specification
(non-synchronization)
Writing to Thermac J
Reading from Thermac J
Set point, alarm value, heater burnout alarm value, proportional band, derivative time, integral time, and input shift value
Process value, set point, alarm value, heater burnout alarm value, heater current value, proportional band, derivative time, integral time, output value, input shift and error code
for details.
7
SECTION 2

Sensor and Mode Settings

This section describes the sensor and mode settings of the Thermac E5J Temperature Controller that are necessary before turning on the Thermac E5J Temperature Controller.
2-1 Disassembly 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Output Units 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Internal Switch Settings 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-1 Internal Switch Positions 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-2 Input Type Selector Setting 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-3 Alarm Mode Setting 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-4 Standby Sequence 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-5 Function Selector Settings 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-6 Key Protection Switch Settings 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
Output Units
2-1 Disassembly
2-2 Output Units
Section 2-2
Before turning on the E5J, set its sensor type and control mode with the inter­nal selectors. Refer to the following illustrations for disassembling the E5J to access the internal switch settings.
Hook
Press the hook and pull the front panel.
After setting the internal switches, insert the internal mechanism into the case until the front panel snaps with the hook.
Select the Output Unit according to the application and mount the Output Unit into the socket on the E5J PCB of the as shown in the following illustration. The E5CJ does not require an Output Unit. Refer to ratings of the E5J.
1-3 Specifications
for the output
Bracket
Output Unit
Socket
Output Units The following Output Units are available.
Model Rating
E53-R Relay Output Unit SPDT, 5 A at 250 VAC (resistive load) E53-Q Voltage Output Unit NPN model, 40 mA at 12 VDC (with short-circuit
protecting circuit)
E53-Q3 Voltage Output Unit NPN model, 20 mA at 24 VDC (with short-circuit
protecting circuit)
E53-Q4 Voltage Output Unit PNP model, 20 mA at 24 VDC (with short-circuit
protecting circuit) E53-C3 Linear Output Unit 4 to 20 mA DC with a load of 600 max. E53-C3D Linear Output Unit 0 to 20 mA DC with a load of 600 max. E53-V34 Linear Output Unit 0 to 10 VDC with a load of 1 k min. E53-V35 Linear Output Unit 0 to 5 VDC with a load of 1 k min.
After mounting the Output Unit, be sure to secure it with the mounting bracket provided with the Output Unit.
If the E53-C3, E53-C3D, E53-V34, and E53-V35 Linear Output Unit is used for control output, no heater burnout alarm is available.
Each Voltage Output Unit is used for driving an SSR as shown in the following illustrations.
10
Internal Switch Settings
NPN Model: E53-Q (40 mA at 12 VDC) and E53-Q3 (20 mA at 24 VDC)
++
LOAD INPUT
PNP Model: E53-Q4 (20 mA at 24 VDC)
LOAD INPUT
SSR
––
++
SSR
––
Section 2-3
2-3 Internal Switch Settings
2-3-1 Internal Switch Positions
E5AJ
Top view
E5EJ
Top view
ALM2
Alarm mode selector 2
ALM1
Alarm mode selector 1
PROTECT
Key protection switch
INPUT
Input type selector
ALM2
Alarm mode selector 2
PROTECT
Key protection switch
ALM1
Alarm mode selector 1
INPUT
Input type selector
ALL OFF SP
ALL OFF SP
Bottom view
FUNCTION
Function selector
FUNCTION
Function selector
11
Internal Switch Settings
E5CJ
Top view
ALM2
Alarm mode selector 2
Section 2-3
Bottom view
ALM1
Alarm mode selector 1
INPUT
Input type selector
FUNCTION
Function selector
PROTECT
Key protection switch
SP OFF ALL
Note The E5CJ with no alarm does not incorporate ALM1 or ALM2.
2-3-2 Input Type Selector Setting
The input type selector is factory-set to 2 (K). Refer to the following table for the selection of the desired sensor.
INPUT
Selector no. Input Set temperature range Specified temperature range
°C °F °C °F
0, 8 JPt100 –199.9 to 650.0 –199.9 to 999.9 –199.9 to 735.0 –199.9 to 999.9 1, 9 Pt100 –199.9 to 650.0 –199.9 to 999.9 –199.9 to 735.0 –199.9 to 999.9 2 K –200 to 1300 –300 to 2300 –350 to 1450 –560 to 2560 3 J –100 to 850 –100 to 1500 –195 to 945 –260 to 1660 4 T –199.9 to 400.0 –199.9 to 700.0 –199.9 to 460.0 –199.9 to 790.0 5 L –100 to 850 –100 to 1500 –195 to 945 –260 to 1660 6 U –199.9 to 400.0 –199.9 to 700.0 –199.9 to 460.0 –199.9 to 790.0 7 N –200 to 1300 –300 to 2300 –350 to 1450 –560 to 2560
Note The resistance of the JPt100 at a temperature of 100°C is 139.16 and that of
the Pt100 at a temperature of 100°C is 138.50 .
1, 2, 3...
1. To use Fahrenheit, set function selector 4 to ON, which is usually set to OFF.
2. Insert the internal mechanism into the case.
3. Turn on the E5J so that d-u will be displayed on the process value display. Then press the Up Key so that f will be displayed on the set value display .
4. Turn off the power in two seconds.
5. Draw the internal mechanism from the case and set function selector 4 to OFF and turn on the E5J.
12
Internal Switch Settings
2-3-3 Alarm Mode Setting
ALM1 and ALM2 are both factory-set to 2 (upper limit alarm). Refer to the follow­ing table for the selection of the desired alarm mode.
Section 2-3
ALM2 ALM1
Selector
Alarm mode Alarm output Setting range
no.
Positive alarm set
value
Negative alarm set
value
0 No alarm function OFF --­1 Upper and lower limit
alarm (deviation)
XSPX
Always ON –1999 to 9999 or –199.9
to 999.9 (the decimal position varies with the input type)
2 Upper limit alarm
(deviation)
3 Lower limit alarm
(deviation)
4 Upper and lower limit
SP
X
SP
XSPX
X
Always OFF
X
SP
X
SP
range alarm (deviation)
5 Upper and lower limit
XSPX
Always OFF alarm with standby sequence (deviation)
6 Upper limit alarm with
standby sequence (deviation)
7 Lower limit alarm with
standby sequence (deviation)
8 Absolute value upper
limit alarm
9 Absolute value lower
limit alarm
X
SP
X
SP
X
0
X
0
X
SP
X
SP X
0 X
0
If the alarm mode switch is set to 1 to 7, the alarm value is set with the deviation width from the set point as shown in the following diagram.
Alarm value
10°C/°F
Set point (SP)
100°C/°F
If the alarm mode switch is set to 8 or 9, the alarm value is set with the absolute value from 0°C/°F as shown in the following diagram.
Alarm value
110°C/°F
0°C/°F
13
Internal Switch Settings
2-3-4 Standby Sequence
The alarm output is ON the moment the E5J is turned on because the process value is within the alarm range. To prevent this, select a mode with a standby sequence. If a mode with a await sequence is selected, the alarm output will not be ON even if the process value is within the alarm range unless the process value once goes out of the alarm range. The following diagram shows the opera­tion of the E5J in lower limit alarm mode with a standby sequence.
OFF point due to alarm hysteresis
It is possible to change the alarm hysteresis (set to 0.2°C before shipping) on the engineering level.
2-3-5 Function Selector Settings
All the function selector pins are factory-set to OFF.
Section 2-3
Standby sequence releasing point
Alarm point
Alarm output
ON OFF
To set these pins to
FUNCTION
ON, use a small flat­blade screwdriver.
Refer to the following table for function switch setting.
Pin no. 1 2 3 4
Output Cooling operation (Normal) ON --- --- --­operation Heating operation (Reverse) OFF Control ON/OFF control --- ON See note mode Advanced PID --- OFF ON
Advanced PID with fuzzy self-tuning --- OFF OFF
Level Engineering level --- --- --- ON
Normal operation --- --- --- OFF
Note The E5J will be in ON/OFF control mode regardless of the setting of pin 3 if pin
2 is set to ON.
Output Operation (Pin 1)
Heating Operation If pin 1 of the E5J is set to OFF, when the process temperature is lower than the
set point, the E5J will operate so that the heater output will increase.
Cooling Operation If pin 1 of the E5J is set to ON, when the process temperature is higher than the
set point, the E5J will operate so that the output of cooling water will increase.
Control Mode (Pins 2 and 3)
ON/OFF Control The ON/OFF control is also called two-position operation. Advanced PID Set the E5J in this mode for P, PI, or PD control or if the most suitable PID
constants for the controlled device are already known.
Advanced PID with Fuzzy Self-tuning
Set the E5J in this mode so that Fuzzy self-tuning adjusts the PID constants to the most suitable values according to the controlled device for ideal temperature control. Refer to
Section 4 Fuzzy Self-tuning
for details.
Level (Pin 4)
14
Set pin 4 to ON if it is necessary to change any parameter on the engineering level. Set this pin to OFF for normal operation.
Internal Switch Settings
2-3-6 Key Protection Switch Settings
The key protection switch is used to prohibit parameter changes as shown in the following table. The key protection switch is factory-set to OFF.
Mode Protection
SP
OFF All keys are available. ALL Prohibits all set value changes. The Level Key, Down Key, and
Prohibits all set value changes except the set point. The Level Key is not available. The Down Key and Up Key are available only for set point setting.
Up Key are not available.
Section 2-3
SP OFF ALL
PROTECT
15
SECTION 3

Settings Before Operation

This section describes the settings of the Thermac E5J Temperature Controller that are necessary before operating the Thermac E5J Temperature Controller.
3-1 Nomenclature 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Setting Flowchart 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 List of Parameters 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Parameters on Display Level 0 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 Parameters on Display Level 1 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
Nomenclature Section 3-1
3-1 Nomenclature
The following is the front panel of the E5AJ-A2HB. The front panels of the E5EJ and E5CJ are similar to the front panel of the E5AJ-A2HB.
Process Value (PV) display
Displays not only the process value but also indicates the pa-
Stop indicator
Lit when the E5J is not operating. The E5CJ does not incorporate this indicator.
Output indicator
Lit when the control output is ON. This indicator is, however, not lit when the E5J has a current out­put.
Level Key
Press for 1 s minimum to change lev­els to set different groups of parame­ters.
Display Key
Use this key when shifting the display to the next parameter.
rameter being displayed on the SV display and error messages.
Down Key and Up Key
The Down Key, when pressed, decreases the set tempera­ture or other parameters. The value successively decreases when the Down Key is held down for 1 s minimum. The Up Key, when pressed, increases the set temperature or other parameters. The value successively increases when the Up Key is held down for 1 s minimum. The value set will be ef­fective on pressing the Display Key or Level Key or 2s after it is set if Display Key or Level Key is not pressed.
Set Value (SV) display
Displays the set temperature and other parameters.
Alarm 1 indicator
Lit when alarm output 1 is ON.
Alarm 2 indicator
Lit when alarm output 2 is ON.
Heater burnout alarm
Lit when there is heater burnout. Once heater burnout is detected, the alarm output will be on hold.
Note Refer to the
E5AJ/E5EJ Communications Manual
models incorporating a communications function.
for the operation of E5J
18
Loading...
+ 48 hidden pages