CS1W-SCU@@-V1 and
CJ1W-SCU@@-V1
Serial Communications Units
OPERATION MANUAL
SYSMAC CS/CJ Series
Serial Communications Boards and
Serial Communications Units
Operation Manual
Revised February 2008
iv
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator
and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed
the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!DANGERIndicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury. Additionally, there may be property damage.
!WARNINGIndicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury. Additionally, there may be property damage.
!CautionIndicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to
an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PLC” means Programmable Controller. “PC” is used, however, in some Programming Device displays to mean Programmable Controller.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
OMRON, 1999
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1,2,3...
1. Indicates lists of one sort or another, such as procedures, checklists, etc.
This manual describes the installation and operation of the SYSMAC CS/CJ-series CS1W-SCB@@-V1
Serial Communications Boards and CS1W-SCU@@-V1 and CJ1W-SCU@@-V1 Serial Communications Units and includes the sections described on the next page.
The Serial Communications Boards are classified as Inner Boards and the Serial Communications
Unit is classified as a CPU Bus Unit.
Please read this manual and all related manuals listed in the following table carefully and be sure you
understand the information provided before attempting to install and operate a Serial Communications
Board or Unit.
NameCat. No.Contents
SYSMAC CS/CJ-series
CS1W-SCB@@-V1, CS1W-SCU@@-V1,
CJ1W-SCU@@-V1
Serial Communications Boards and
Serial Communications Unit Operation Manual (this
manual)
SYSMAC CS/CJ-series
CS1W-ETN01, CS1W-ETN11, CJ1W-ETN11
Ethernet Unit Operation Manual
W336Describes the use of Serial Communications Unit
and Boards to perform serial communications with
external devices, including the usage of standard
system protocols for OMRON products.
W341Provides information on how to program and operate
CS/CJ-series PLCs using a Programming Console.
W339Describes the installation and operation of the CS-
series PLCs.
W393Describes the installation and operation of the CJ-
series PLCs.
W394Describes the ladder diagram programming functions
and other functions supported by CS-series and CJseries PLCs.
W340Describes the ladder diagram programming instruc-
tions supported by CS-series and CJ-series PLCs.
W342Describes the Host Link and FINS communications
commands used with CS-series and CJ-series PLCs.
W446Provides information on how to use the CX-Program-
mer, a programming device that supports the CSseries and CJ-series PLCs.
W344Describes the use of the CX-Protocol to create proto-
col macros as communications sequences to communicate with external devices.
W343Describes the installation and operation of CS1W-
ETN01, CS1W-ETN11, and CJ1W-ETN11 Ethernet
Unit.
xi
About this Manual, Continued
This manual contains the following sections.
Section 1 introduces the hardware and software functions of the Serial Communications Boards and
the Serial Communications Units, including the communications modes, system configurations, and
specifications.
Section 2 describes the components of the Serial Communications Boards and the Serial Communications Units, the settings required for operation, and the memory allocated in the I/O memory of the
CPU Unit for controlling and monitoring communications.
Section 3 describes how to mounting the Serial Communications Boards and Serial Communications
Units, and how to connect the ports to external devices.
Section 4 describes the procedure and other information required to use Host Link communications.
Section 5 describes the procedure and other information required to use protocol macros.
Section 6 provides an overview of the Serial Gateway, information on I/O memory allocations, and
procedures for using the functions. Information on protocol conversion, routing table requirements, and
communications frames is also provided. The Serial Gateway can be used only for Unit Ver. 1.2 or
later.
Section 7 describes the procedure and other information required to use the no-protocol mode. This
mode is supported for Unit Ver. 1.2 or later only.
Section 8 describes the procedure and other information required to use 1:N NT Links to Programmable Terminals.
Section 9 describes the procedure and other information required to use Modbus-RTU slave mode.
Section 10 describes the procedure and other information required to conduct loopback test to check
the serial ports.
Section 11 describes the troubleshooting and maintenance procedures for the Serial Communications
Boards and the Serial Communications Units.
Appendix A to Appendix Q provide the specifications of the standard system protocols.
Appendix R provides information on using STUP(237) to change serial port settings.
!WARNING Failure to read and understand the information provided in this manual may result in per-
sonal injury or death, damage to the product, or product failure. Please read each section
in its entirety and be sure you understand the information provided in the section and
related sections before attempting any of the procedures or operations given.
xii
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON
representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a
period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NONINFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which
liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS
REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS
WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO
CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
xiii
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the
combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying
ratings and limitations of use that apply to the products. This information by itself is not sufficient for a
complete determination of the suitability of the products in combination with the end product, machine,
system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not
intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses
listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or
uses not described in this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical
equipment, amusement machines, vehicles, safety equipment, and installations subject to separate
industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED
FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any
consequence thereof.
xiv
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other
reasons.
It is our practice to change model numbers when published ratings or features are changed, or when
significant construction changes are made. However, some specifications of the products may be changed
without any notice. When in doubt, special model numbers may be assigned to fix or establish key
specifications for your application on your request. Please consult with your OMRON representative at any
time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when
tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does
not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must
correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and
Limitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no
responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
xv
xvi
PRECAUTIONS
This section provides general precautions for using the CS/CJ-series Serial Communications Boards and Units.
The information contained in this section is important for the safe and reliable application of Programmable
Controllers. You must read this section and understand the information contained before attempting to set up or
operate a PLC system.
6-4EMI Measures for Serial Communications Boards and Units . . . . . xxiii
6-5EMS Measures for Serial Communications Units . . . . . . . . . . . . . . xxiv
7Unit Versions of CS/CJ-series Serial Communications Boards/Units . . . . . . xxiv
8Functions Added in the Unit Version 1.3 Upgrade . . . . . . . . . . . . . . . . . . . . . xxviii
9Functions Added in the Unit Version 1.2 Upgrade . . . . . . . . . . . . . . . . . . . . . xxviii
xvii
Intended Audience1
1Intended Audience
This manual is intended for the following personnel, who must also have
knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
2General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not described in the
manual or applying the product to nuclear control systems, railroad systems,
aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used
improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are
sufficient for the systems, machines, and equipment, and be sure to provide
the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the Unit. Be
sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation.
!WARNING It is extremely important that a PLC and all PLC Units be used for the speci-
fied purpose and under the specified conditions, especially in applications that
can directly or indirectly affect human life. You must consult with your OMRON
representative before applying a PLC System to the above-mentioned applications.
3Safety Precautions
!WARNING Provide safety measures in external circuits (i.e., not in the Programmable
Controller), including the following items, to ensure safety in the system if an
abnormality occurs due to malfunction of the PLC or another external factor
affecting the PLC operation. Not doing so may result in serious accidents.
• Emergency stop circuits, interlock circuits, limit circuits, and similar safety
measures must be provided in external control circuits.
• The PLC will turn OFF all outputs when its self-diagnosis function detects
any error or when a severe failure alarm (FALS) instruction is executed.
As a countermeasure for such errors, external safety measures must be
provided to ensure safety in the system.
• The PLC outputs may remain ON or OFF due to deposition or burning of
the output relays or destruction of the output transistors. As a countermeasure for such problems, external safety measures must be provided
to ensure safety in the system.
• When the 24-V DC output (service power supply to the PLC) is overloaded or short-circuited, the voltage may drop and result in the outputs
xviii
Operating Environment Precautions4
being turned OFF. As a countermeasure for such problems, external
safety measures must be provided to ensure safety in the system.
!WARNING Do not attempt to take any Unit apart while the power is being supplied. Doing
so may result in electric shock.
!WARNING Do not touch any of the terminals or terminal blocks while the power is being
supplied. Doing so may result in electric shock.
!WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do
so may result in malfunction, fire, or electric shock.
!Caution Execute online edit only after confirming that no adverse effects will be
caused by extending the cycle time. Otherwise, the input signals may not be
readable.
4Operating Environment Precautions
!Caution Do not operate the control system in the following places:
• Locations subject to direct sunlight.
• Locations subject to temperatures or humidity outside the range specified
in the specifications.
• Locations subject to condensation as the result of severe changes in temperature.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to shock or vibration.
!Caution Take appropriate and sufficient countermeasures when installing systems in
the following locations:
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power supplies.
!Caution The operating environment of the PLC System can have a large effect on the
longevity and reliability of the system. Improper operating environments can
lead to malfunction, failure, and other unforeseeable problems with the PLC
System. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life
of the system. Follow all installation instructions and precautions provided in
the operation manuals.
xix
Application Precautions5
5Application Precautions
Observe the following precautions when using the PLC System.
!WARNING Always heed these precautions. Failure to abide by the following precautions
could lead to serious or possibly fatal injury.
• Always connect to a ground of 100
connecting to a ground of 100
• Always turn OFF the power supply to the PLC before attempting any of
the following. Not turning OFF the power supply may result in malfunction
or electric shock.
• Mounting or dismounting Power Supply Units, I/O Units, CPU Units,
Serial Communications Units, or any other Units.
• Assembling the Units.
• Setting DIP switches or rotary switches.
• Connecting cables or wiring the system.
• Mounting or dismounting terminal blocks.
!Caution Failure to abide by the following precautions could lead to faulty operation of
the PLC or the system, or could damage the PLC or PLC Units. Always heed
these precautions.
• Fail-safe measures must be taken by the customer to ensure safety in the
event of incorrect, missing, or abnormal signals caused by broken signal
lines, momentary power interruptions, or other causes.
• Take appropriate measures to ensure that the specified power with the
rated voltage and frequency is supplied. Be particularly careful in places
where the power supply is unstable. An incorrect power supply may result
in malfunction.
• Tighten the mounting screws at the bottom of Serial Communications
Units to a torque of 0.4 N
malfunction.
• Leave the label attached to the Unit when wiring. Removing the label may
result in malfunction if foreign matter enters the Unit.
• Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction.
• Always check polarity before wiring RS-422A/485 connectors. The polarity for the SDA/B and RDA/B signals can be different for some external
devices.
• Check to be sure that terminating resistors have been correctly installed
for RS-422A/485 systems before starting operation.
• Disconnect the LG terminal of the Power Supply Unit from the GR terminal when performing insulation and dielectric strength tests.
• Never turn OFF the power supply while writing protocol macro data.
• Wire all connections correctly according to instructions in this manual.
• Check terminal blocks completely before mounting them.
• Double-check all wiring and switch settings before turning ON the power
supply. Incorrect wiring may result in burning.
⋅m. An incorrect tightening torque may result in
Ω or less when installing the Units. Not
Ω or less may result in electric shock.
xx
Application Precautions5
• Be sure that the Bus Connection Unit and other items with locking devices
are properly locked into place. Improper locking may result in malfunction.
• Check the user program for proper execution before actually running it on
the Unit. Not checking the program may result in an unexpected operation.
• Confirm that no adverse effect will occur in the system before attempting
any of the following. Not doing so may result in an unexpected operation.
• Changing the operating mode of the PLC (including the setting of the
startup operating mode).
• Force-setting/force-resetting any bit in memory.
• Changing the present value of any word or any set value in memory.
• Do not install the product near devices generating strong high-frequency
noise.
• Do not drop the product or subject it to excessive vibration or shock.
• Observe the following precautions for communications cables.
• Do not lay communications cables near power lines or high-voltage
lines.
• Always lay communications cables in ducts.
• Do not pull on the communications cables or bend the communications
cables beyond their natural limit. Doing either of these may break the
cables.
• Do not place objects on top of the communications cables or other wiring lines. Doing so may break the cables.
• Before touching a Unit, be sure to first touch a grounded metallic object in
order to discharge any static built-up. Not doing so may result in malfunction or damage.
• Resume operation only after transferring to the new CPU Unit the contents of the DM Area, HR Area, and other data required for resuming
operation. Not doing so may result in an unexpected operation.
• Do not touch circuit boards or the components mounted to them with your
bare hands. There are sharp leads and other parts on the boards that
may cause injury if handled improperly.
• When transporting or storing Boards, wrap them in material that will protect LSIs, ICs, and other components from static electricity and be sure
that they remain within the storage temperature range.
• When creating Host Link FINS command frames using the CMND(490)
instruction, always set the unit number for Host Link incremented by one
(1 to 32) for the remote destination (send destination) node address (word
C+3, bits 08 to 15 of the CMND(490) instruction). Do not set the unit number of the actual Host Link slave (0 to 31). Using the Host Link unit number without incrementing by one will access the PLC with the entered
Host Link unit number less one.
For example, specify the remote PLC with Host Link unit number 2 by
entering 3 for the remote destination node address. If 2 is entered, the
PLC with Host Link unit number 1 will be accessed.
To access a PLC on a Host Link FINS network using the Serial Gateway
from CX-Programmer, however, enter the actual Host Link unit number,
without incrementing by one. (Select Change PLC, click the Display
Serial Gateway Guide Button, and set unit number in the Host Link
SYSWAY Settings field of the Serial Gateway Guide Dialog Box.
xxi
Conformance to EC Directives6
• When the Serial Gateway is executed during protocol macro execution,
the communications sequence contents and the FINS command reception timing may suspend step transition of the communications sequence
(when the next step does not contain the RECEIVE command, the Serial
Gateway will be executed by interrupting the sequence before the next
step, and the step transition will be suspended).
Use the Serial Gateway send start timeout function to monitor at the
source of the FINS command whether step transition in the communications sequence has been suspended due to execution of the Serial Gateway. If the converted command does not start to be sent within the set
time, either retry executing the FINS command or change the communications sequence.
• When using 2-wire RS-422A/485 communications in Protocol Macro
Mode, set only modem controls for the send control parameters, and do
not use RS/CS flow controls.
• The following operations will result if the Serial Gateway is executed either
using a pre-Ver. 1.2 Board/Unit or using a Ver. 1.2 or later Unit/Board without Serial Gateway or protocol macro mode set for serial communications
at the serial port.
• If either NT Link or loopback test mode is used for serial communications, or if protocol macro mode is used with a pre-Ver. 1.2 Board/Unit,
an undefined command response will be returned (end code: 0401
hex).
• If Host Link mode is used for serial communications, the message will
be converted into a FINS command using Host Link slave-initiated
communications and transferred (this will mainly result in a response
timeout being returned, depending on the remote device (end code:
0205 hex))
• If a no-protocol instruction is sent to a pre-Ver. 1.2 Board/Unit or the serial
port of a Board/Unit with Unit Ver. 1.2 or later using a serial communications mode other than no-protocol mode, the following operations will
occur.
• If TXD(236)/RXD(235) is sent to the Board, Auxiliary Area bit A424204
(Inner Board Service Failure Flag) will turn ON.
• If TXDU(256)/RXDU(255) is sent to the Unit and the serial communications mode is set to protocol macro, NT Link, loopback test, or Serial
Gateway mode, an undefined command error (end code: 0401 hex)
will be returned.
If the serial communications mode is set to Host Link mode and the instruction will be converted to a slave-initiated function FINS command
and transferred. (Depending on the remote device, a response timeout
(end code: 0205 hex) is likely to be returned.)
6Conformance to EC Directives
6-1Applicable Directives
•EMC Directives
• Low Voltage Directive
6-2Concepts
EMC Directives
OMRON devices that comply with EC Directives also conform to the related
EMC standards so that they can be more easily built into other devices or the
xxii
Conformance to EC Directives6
overall machine. The actual products have been checked for conformity to
EMC standards (see the following note). Whether the products conform to the
standards in the system used by the customer, however, must be checked by
the customer.
EMC-related performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of
the equipment or control panel on which the OMRON devices are installed.
The customer must, therefore, perform the final check to confirm that devices
and the overall machine conform to EMC standards.
Note Applicable EMS (Electromagnetic Susceptibility) and EMI (Electromagnetic
Interference) standards in the EMC (Electromagnetic Compatibility) standards
are as follows:
Always ensure that devices operating at voltages of 50 to 1,000 VAC and 75
to 1,500 VDC meet the required safety standards for the PLC (EN61131-2).
EN61131-2
EN61000-6-2
EN61000-6-4
(Radiated emission: 10-m
regulations)
6-3Conformance to EC Directives
The CS/CJ-series PLCs comply with EC Directives. To ensure that the
machine or device in which the CS/CJ-series PLC is used complies with EC
directives, the PLC must be installed as follows:
1,2,3...
1. The CS/CJ-series PLC must be installed within a control panel.
2. You must use reinforced insulation or double insulation for the DC power
supplies used for the communications power supply and I/O power supplies.
3. CS/CJ-series PLCs complying with EC Directives also conform to the
Common Emission Standard (EN61000-6-4). Radiated emission characteristics (10-m regulations) may vary depending on the configuration of the
control panel used, other devices connected to the control panel, wiring,
and other conditions. You must therefore confirm that the overall machine
or equipment complies with EC Directives.
6-4EMI Measures for Serial Communications Boards and Units
The CS/CJ-series PLCs conform to the Common Emission Standards
(EN61000-6-4) of the EMC Directives. However, the noise generated from
Serial Communications Board or Unit communications cables may not satisfy
these standards. In such a case, commercially available ferrite cores must be
placed on the communications cable or other appropriate countermeasures
must be provided external to the PLC.
xxiii
Unit Versions of CS/CJ-series Serial Communications Boards/Units7
Recommended Ferrite Cores
The following ferrite core (data line noise filter) is recommended:
0443-164151 by Fair-Rite Products Corp.
Low impedance, 25 MHz: 90
Ω, 100 MHz: 160 Ω
Recommended Mounting Method
Mount the core on one turn of the communications cable, as shown in the following illustration.
Mount the cores as lost to the end of the communications cable as possible,
as shown in the following illustration.
Serial
Communications
Unit/Board
6-5EMS Measures for Serial Communications Units
The immunity testing conditions for the CJ1W-SCU41-V1 Serial Communications Unit are as follows: A ferrite core is mounted on the test cable connected
to the RS-422A/485 port.
Refer to 6-4 EMI Measures for Serial Communications Boards and Units for
information on mounting the ferrite core.
7Unit Versions of CS/CJ-series Serial Communications
Boards/Units
Unit Versions
A “unit version” has been introduced to manage CS/CJ-series Serial Communications Units/Boards according to differences in functionality accompanying
upgrades.
1. Unit Version Notation on Products
The unit version code is provided on the nameplate of the CS-series Serial
Communications Boards and Units for which unit versions are being managed, as shown below for the Loop Control Board. This system applies to
Serial Communications Units or Boards with unit version 1.2 or later.
• Serial Communications Boards
xxiv
Unit Versions of CS/CJ-series Serial Communications Boards/Units7
Example: CS1W-SCB21-V1 CS-series
Serial Communications Board
Nameplate
Unit version 1.3
CS1W-SCB21-V1
SERIAL COMMUNICATION BOARD
• Serial Communications Units
Example: CS1W-SCU21-V1 CS-series
Serial Communications Unit
Nameplate
SERIAL COMMUNICATION UNIT
:
Lot No. 051020 Ver.1.3
OMRON Corporation
CS1W-SCU21-V1
MADE IN JAPAN
Unit version 1.3
2. Confirming Unit Versions with Support Software
CX-Programmer version 5.0 can be used to confirm the unit version in the
Unit Manufacturing Information.
■Boards
In the I/O Table Window, right-click on the CPU Unit, and then select Unit
Manufacturing Information – Inner Board
■Units
1. In the I/O Table Window, right-click on the Serial Communications Unit,
and then select Unit Manufacturing Information.
2. The following Unit Manufacturing Information Dialog Box will be displayed.
Lot No. 051020 0000 Ver.1.3
OMRON Corporation
MADE IN JAPAN
xxv
Unit Versions of CS/CJ-series Serial Communications Boards/Units7
The unit version is displayed.
Example: In this Unit Manufacturing Information Dialog Box, unit version 1.3 is
displayed. Use this dialog box to confirm the unit version of the Serial Communications Unit that is connected online.
3. Using the Unit Version Labels
Unit version labels are provided with the product. These labels can be
attached to the front of previous Serial Communications Boards/Units to differentiate between Serial Communications Boards/Units of different unit versions.
Unit Version Notation
The unit versions are indicated in this manual as follows:
Notation in product
Ver. 1.3 or later after
the lot number
Ver.1.2 after the lot
number
Blank after the lot
number
nameplate
Notation in this manualRemarks
CS/CJ-series Serial Communications Units with unit version 1.3 or later
CS/CJ-series Serial Communications Units with unit version 1.2
Pre-Ver. 1.2 CS/CJ-series
Serial Communications Units
Information for which no particular version is specified
applies to all unit versions.
xxvi
Unit Versions of CS/CJ-series Serial Communications Boards/Units7
Function Support by Unit Version
ProductEarlier version
CS SeriesSerial Communica-
tions Boards
Serial Communications Units
CJ SeriesSerial Communica-
tions Units
Serial gatewayNot supportedSupportedSupported (Same as pre-
Host Link 1:1 linksNot supportedSupportedSupported (Same as pre-
Host Link compatible
device selection
No-protocolNot supportedSupportedSupported (Same as pre-
Protocol
macro
Functions
Standard system protocol additions
MODBUS slave protocol added------Supported
Link word specification data exchange
timing
Reception buffer processing for
PMCR(260) instruction execution
CX-ProgrammerWS02-CXPC1-JV@Ver. 4.0 or earlierVer. 5.0Version 6.1
CS1W-SCB21-V1Pre-Ver. 1.2Unit version 1.2
CS1W-SCB41-V1
CS1W-SCU21-V1Pre-Ver. 1.2Unit version 1.2
CS1W-SCU21-V1
CS1W-SCU41-V1
CS1W-SCU31-V1------Unit version 1.3
CJ1W-SCU31-V1------
(Lot No.: 040617
and later)
(Lot No.: 040617
and later)
Unit version 1.3
Unit version 1.3
(Available April,
2006)
xxvii
Functions Added in the Unit Version 1.3 Upgrade8
8Functions Added in the Unit Version 1.3 Upgrade
Functions Added in Version Upgrade
The following table provides a comparison between the functions provided in
the upgrade to unit version 1.3 or later of CS1W-SCB@@-V1 Serial Communications Boards and CS1W-SCU@@-V1, CJ1W-SCU@@-V1 Serial Communications Units, and the functionality of earlier versions.
ItemPrevious unit versionsUnit version 1.3 and later
Serial communications mode
Modbus-RTU slave modeNot supportedSupported
9Functions Added in the Unit Version 1.2 Upgrade
Upgraded Models
The model numbers of CS-series Serial Communications Units/Boards have
not changed. A “-V1” suffix has been added to the model numbers of CJseries Serial Communications Units with the unit version 1.2 upgrade, as
shown in the following table.
PLCProductSpecificationsModelModel number
CS
Series
CJ
Series
Serial Communications
Boards
Serial Communications
Units
Serial Communications
Units
RS-232C
RS-232C × 1
RS-232C
RS-422A/485
1
RS-232C
RS-232C × 1
RS-232C × 1,
RS-232C × 1
RS-232C
RS-422A/485
1
CS1W-SCB21-V1 →Same
× 1,
CS1W-SCB41-V1 →Same
× 1,
×
CS1W-SCU21-V1 →Same
× 1,
CJ1W-SCU21→CJ1W-SCU21-V1
CJ1W-SCU41→CJ1W-SCU41-V1
× 1,
×
after upgrade to
unit version 1.2
xxviii
Functions Added in the Unit Version 1.2 Upgrade9
Functions Added in Version Upgrade
The following table provides a comparison between the functions provided in
the upgrade to unit version 1.2 or later of CS1W-SCB@@-V1 Serial Communications Boards and CS1W-SCU@@-V1, CJ1W-SCU@@-V1 Serial Communications Units, and the functionality of earlier versions.
Serial communications
mode
ItemEarlier versions
Serial GatewayNot supportedSupported
Host Link1:1 protocolNot supported (1:N
Host Link
compatible
device selection
No-protocolNot supportedSupported, but only when using a CS/CJ-series
(pre-Ver.1.2)
Host Links only)
Not supported (not
completely compatible with C-series
Host Link and CVM1/
CV-series Host Link)
The received FINS command can be converted
into serial communications protocol and then converted into either of the following protocols (using
the Serial Gateway mode).
• CompoWay/F
•Modbus-RTU
• Modbus-ASCII
• Host Link FINS (This protocol can be used to
make the PLC function as the Host Link Master.)
The Serial Gateway can also be used in protocol
macro mode. This option enables, for example, programming or monitoring of a serially connected
PLC from a CX-Programmer that is connected to
the PLC during execution of protocol macros (e.g.,
Host Link Master).
Supported
This protocol functions the same as the 1:1 Host
Link supported by the earlier C200H, C1000H, and
C2000H Series, thereby enabling the use of host
computer programs for 1:1 Host LInks created
using these earlier PLCs.
Note: CS/CJ-series, C200HS/HX/HG/HE(-Z),
@, CQM1@, and CVM1/CV Series all support
CPM
1:N Host Links only. C200H and C500 Host LInk
Units support both 1:1 and 1:N Host Links.
The compatible device mode enables full compatibility of Host Link functions (see note) with C-series
Host Link and CVM1/CV-series Host Link.
Note: E.g., differences in specifications for delimiter
words in response frame data
CPU Unit with unit version 3.0 or later.
(The no-protocol mode that was previously possible only at the built-in RS-232C port of CPU Unit is
now available for the Serial Communications
Boards and Units.)
This protocol is mainly used for communications
with devices that perform input or output only, such
as bar code readers and printers.
This mode enables no-protocol communications
even if the CPU Unit’s built-in RS-232C port is
being used for another application.
Unit version 1.2 or later
xxix
Functions Added in the Unit Version 1.2 Upgrade9
Enhanced
protocol
macro functions
Standard system protocol
ItemEarlier versions
Link word specification data
exchange timing
Reception buffer processing
for PMCR(260) instruction
execution (immediately
before communications
sequence execution)
Baud rate for protocol macro
mode
Host Link C-mode Command
Master
Host Link FINS Command
Master
(pre-Ver.1.2)
On-request I/O
refreshing only
(request to refresh
sent to CPU Unit at
every send/receive
command execution,
and data exchanged
during I/O refresh)
In this method, after
the send command is
executed, a delay
occurs before the
actual message is
sent.
Clearing to zero only Select to clear or hold the contents of the reception
38,400 bps max.
(57,600 bps not supported)
None (protocols must
be created using CXProtocol)
Unit version 1.2 or later
Continuous I/O refreshing (selected in DM Area
settings) is supported in addition to the on-request
I/O refreshing available in earlier models.
Continuous I/O refreshing is performed from the
CPU Unit during protocol macro execution, regardless of requests from the Board/Unit, and data in
the Board/Unit is accessed during send/receive
command execution. When the send command is
executed with this method, the actual message can
be sent immediately.
buffer during full-duplex communications (set in the
allocation DM Area).
This enables the data in the reception buffer
received in the previous communications sequence
to be held after switching the communications
sequence during full-duplex communications.
57,600 bps supported (115,200 bps not supported)
Provided
A Host Link Master can
be used to easily access
the Host Link slave PLC
(e.g., A PLC slave on a
moving body can be
accessed via a WMseries Wireless Modem
in a Host Link.)
Host Link C-mode commands can be used to
access a C-series or CS/
CJ-series PLC slave.
Host Link FINS commands can be used to
access a CS/CJ-series
or CVM1/CV-series PLC
slave.
This protocol can also
be used to access slave
PLCs on the network.
xxx
Mitsubishi Computer Link
Master (A-compatible, 1C
frame, model 1)
CompoWay/F Master---Communications sequences with different send
Provided
Computer Link commands can be used to access a
Mitsubishi PLC (Sequencer CPU Module) slave.
and receive protocols are provided by using send/
receive commands with ASCII conversion.
The communications sequences have been
expanded to include CompoWay/F commands
such as VARIABLE AREA READ/WRITE and
OPERATING INSTRUCTIONS.
SECTION 1
Introduction
This section introduces the hardware and software functions of the Serial Communications Boards and the Serial
Communications Units, including the communications modes, system configurations, and specifications.