Omron CP1H, CP1L, CP1W-ETN01-US Application And Setup Manual

CP1H / CP1L Ethernet to Serial Adapter
APPLICATIONGUIDE
CP1W-ETN01-US
Application and Setup Guide
Revision 1.11
2/11/2009
This document explains the theory, operation & setup of the Omron CP1W-ETN01-US Ethernet to Serial adapter.
The CP1W-ETN01-US is an Ethernet to Serial adapter that allows FINS Ethernet devices to communicate with CP1H and CP1L PLCs. These devices include PCs with CX-Programmer, NS series HMI products, and software packages that use Omron FINS Gateway or Sysmac Gateway communications drivers. The adapter mounts in the Option Board Slot on the front of a CP1H or CP1L PLC, and can be used in all CP1H / CP1L PLCs with an available Option Board Slot.
Because the adapter is an Ethernet to Serial adapter, it will behave with the response characteristics of a serial port, and with throughput and frame length limits associated with serial communications protocols.
The CP1W-ETN01-US adapter converts incoming Omron FINS Ethernet commands to CV Mode Hostlink commands, and delivers the commands to the PLC CPU. The adapter then converts the CV Mode Hostlink response from the PLC CPU back to a FINS Ethernet packet, and delivers it to the originating device (PC or HMI). This conversion process can be used with either FINS UDP or FINS TCP, using UDP or TCP port 9600.
If you will be using CX-Programmer to communicate to the adapter, you must have CX-Programmer Version 8.0 or later installed. CX-One Version 3 includes CX­Programmer 8.0.
Page 2 of 8
Section 2: Applications
The CP1W-ETN01-US is an Ethernet to Serial adapter that has been designed to allow the use of a single operator interface terminal (NS, NSA, Indusoft) as well as a single instance of CX Programmer to communicate simultaneously to a CP1H or CP1L PLC. The adapter will not support more than 2 simultaneous connections.
PLC to PLC communications using Ethernet are not possible, as the adapter only functions as an Ethernet slave device.
Unlike Omron Ethernet modules for CS / CJ PLCs, the CP1W-ETN01-US is not capable of routing messages through multiple FINS networks. The CP1W-ETN01-US must communicate with a PC / NS HMI that is on the same FINS network as the PLC adapter itself.
Page 3 of 8
Loading...
+ 7 hidden pages