Omega Products PX751CA-1 User Manual

SMART PRESSURE TRANSMITTER
HIGH STABILITY, LOW DRIFT
PX751 Series
25 inH2O to 6000 psi
Starts at
$
1875
PX751, $1875, shown smaller than actual size.
Remote Reranging, Access to Difficult-to-Reach or Hazardous Areas
Improved Performance,
Increased Accuracy, Greater Stability and Noise Resistance
Diagnostic Capabilities,
Continuous On-Line Self-Check, Selectable Failure Alarm, Loop Test
Transmitter Data Base
Includes Configuration, Calibration, and Materials
Greater Performance,
Wider Rangeability (100:1), Transmitter Security, Selectable Linear/Square Root Output, Multi-Drop
High Stability and Low
Drift Ensure Accurate Measurements for Years
Fast, Dynamic ResponseTighter Control
and Reduced Maintenance Costs
Pressure and
Temperature Output
Troubleshooting,
Reconfiguring,
Coplanar Design—
Differential, Gage, or
Absolute Pressure!
PX751C coplanar transmitter, $1875, with flange, $150, shown smaller than actual size.
B-235
PX751C SMART TRANSMITTER
LCD Meter Options
The LCD meter can be digitally customized by the user to meet process needs. The meter can be configured to display engineering units, percent of range, or custom user scale, or to alternate between any 2 of these.
Power Supply
The DC power supply should provide power with less than 2% ripple. The transmitter requires a minimum of 250 Ω of loop resistance to communicate with a HartTMbased communicator. With 250 drop, the transmitter will require a minimum of 16 Vdc to output 20 mA.
Diagnostics and Service
The diagnostic and service functions listed here are primarily for use after the transmitter is installed in the field.
The Transmitter Test feature helps verify that the transmitter is operating properly, and can be performed either on the bench or in the field. The transmitter test command initiates an extensive diagnostics routine that can quickly identify potential electronics problems. If the transmitter detects a problem, messages to indicate the source of the problem are displayed on the communicator screen.
The Loop Test feature is designed to verify proper loop wiring and transmitter output, and should only be performed after the user installs the transmitter. This function tests the output of the transmitter, the integrity of the loop, and the operations of any recorders or similar devices installed in the loop.
Calibration
Calibrating a smart transmitter is different from calibrating an analog transmitter. The smart transmitter requires 3 steps: Rerange—sets the 4 and 20 mA points to the desired pressures. Sensor Trim—adjusts the position of the factory characterization curve to optimize the transmitter performance over a specified pressure range or to adjust for mounting effects.
PX751C
(Shown Installed with 3-Valve Manifold)
Analog Output Trim—adjusts the analog output to match the plant standard or the control loop.
Advanced Functions
Cloning: Quickly copies the same
configuration to multiple units. The cloning process involves configuring a transmitter, saving the configuration data, then sending a copy of the data to a separate transmitter. Multidrop: Communication between the host and the transmitter takes place digitally with the analog output of the transmitter deactivated. With HartTMsmart protocol, up to 15 units can be connected on a single pair of twisted wires or over leased phone lines.
B
Burst Mode: Provides faster digital communications to control system by eliminating the time required for the control system to request data from the transmitter. Burst mode applies only to the transmission of dynamic data (pressure and temperature).
Low-Power Option
User-selectable 3-wire 1 to 5 Vdc or 0.8 to 3.2 Vdc outputs are available with the low-power option. The digital signal is superimposed on the voltage signal, available to any host conforming to HartTMprotocol. Low-power units operate on 6 to 12 Vdc with no load.
B-236
PX751C SMART TRANSMITTER
SPECIFICATIONS AND REFERENCE DATA
Specifications
Service:
Liquid, gas and vapor applications
Zero and Span Adjustment:
Zero and span values can be set anywhere within the range limits stated in tables. Span values must be greater than or equal to the minimum span stated in the range limits tables.
4 to 20 mA Models
Output:
2-wire 4 to 20 mA output, user selectable for linear or square root; digital process variable superimposed on 4 to 20 mA signal, available to any host that conforms to the HartTMprotocol
Power Supply:
External power supply required. Standard transmitter operates on 10.5 to 55 Vdc with no load. A minimum of 250 of loop resistance is required to communicate with a Hart
TM
based communicator. With 250 drop, the transmitter will require a minimum of 16 Vdc to output 20 mA.
Load Limitations:
)
Load (Ω
1935
1500
1000
500
0
10.5 20 30 40 55
Communications require a minimum loop resistance of 250 .
1
For CSA approval, power supply must not
exceed 42.2 V.
Operating Region
Voltage (Vdc)
42.4
1
Low Power Models
Output: 3-wire 1 to 5 Vdc or 0.8 to 3.2 Vdc
user selectable. Also user selectable for linear or square root output configuration. Digital process variable superimposed on 4 to 20 mA signal, available to any host that conforms to the HartTMprotocol.
Power Consumption:
3 mA, 18 to 36 mW
Minimum Load Impedance:
100 k (V
Indication:
Optional 2-line, 5-digit LCD meter Overpressure Limits: Transmitters
withstand the following limits without damage:
Gage/Differential Models (CA/CD):
Range 1:
0 to 2000 psig (0 to 13.8 MPa)
Ranges 2 to 5:
0 to 3626 psig (0 to 25 MPa)
OUT
+ wiring)
Absolute Models (CA):
Range 0: 0 to 60 psia (0 to 413.7 kPa) Range 1: 0 to 120 psia (0 to 827.4 kPa) Range 2: 0 to 300 psia (0 to 2070 kPa) Range 3: 0 to 1600 psia (0 to 11030 kPa) Range 4: 0 to 6000 psia (0 to 41370 kPa)
High-Process Temperature Models (HP/HG)
All Ranges, 0 to 3626 psig (0 to 25 MPa) “T” Style Gage and Absolute Models (TA/TG):
Range 1: 0 to 750 psia (0 to 5.2 MPa) Range 2: 0 to 1500 psia (0 to 10.3 MPa) Range 3: 0 to 1600 psia (0 to 11.0 MPa) Range 4: 0 to 6000 psia (0 to 41.4 MPa) Range 5: 0 to 15000 psia (0 to 103.4 MPa)
Static Pressure Limits
Differential Pressure Models Only:
Operates within specification between static line pressure of 0.5 psia and 3626 psig; 2000 psig for range 1 (ranges 2 and 3 for high-accuracy models)
Burst Pressure Limits:
All Except Type T:
10,000 psig (69 MPa)
Type T:
Ranges 1 to 4: 11,000 psi (75.8 MPa) Range 5: 26,000 psig (179 MPa)
Failure Mode Alarm: User selectable to
drive output either high or low when gross transmitter failure is detected
Temperature Limits
Ambient: -40 to 85°C (-40 to 185°F);
with integral meter, -20 to 80°C (-4 to 175°F)
Storage: -46 to 110°C (-50 to 230°F);
with integral meter, -40 to 85°C (-40 to 185°F)
Process Temperature Limits
Differential, Gage and Absolute:
Silicone Fill Sensor1with Coplanar Flange -40 to 250°F Side Flange -40 to 300°F Level Flange
Horizontal Mount -40 to 250°F Vertical Mount -40 to 300°F
Inert Fill Sensor Option10 to 185°F
High-Temperature Models:
Fill Material Temperature Range
D.C. Silicone 200 Inert -50 to 350°F Neobee M-20
Type “T” Gage and Absolute:
Silicone Fill Sensor Inert Fill Sensor
1
1
1
1
-40 to 375°F
0 to 375°F
-40 to 250°F
-22 to 250°F
Humidity: 0 to 100% RH Turn-On Time: Performance within
specifications less than 2.0 seconds after power is applied
Volume Displacement:
<0.08 cm
3
(0.005 in3)
Damping: User selectable from 0 to 36 seconds for one time constant. This software damping is in addition to sensor module response time.
3, 4
2
2
2
2
2
2
PX751H high-process temperature traditional flange differential and pressure gage, $2860, shown smaller than actual size.
All Models
Response Time:
Dead Time (Td): 45 ms nominal Time Constant (Tc): 55 ms Update Rate: 20 times/s minimum
Vibration Effect: < ±0.1% of URL per
gram when tested from 15 to 2000 Hz in any axis relative to pipe-mounted process connection
Power Supply Effect:
<0.005% of calibrated span per volt RFI Effects: ±0.1% of span from 20 to
1000 MHz, and field strength up to 30 V/m
Transient Protection (Optional):
Meets IEEE standard 587, Category B meets IEEE standard 473, surge withstand capability 2.5 kV crest, 1 MHz waveform
Process Connections (All Except Level, High-Pressure Gage and Absolute Models):
1
4-18 NPT on 21⁄8" centers;
1
2-14 NPT on 2, 21⁄8, or 21⁄4" centers
Level Models:
High-Pressure Side: 2, 3 or 4",
Class 150, 300 or 600 flange
50, 80 or 100 mm: PN40 or
High Gage or Absolute Pressure:
1
4-18, 1⁄2-14 female, G1⁄2 A DIN 16288 male (available in stainless steel for ranges 1 to 4) or autoclave type F-250-C (pressure relieved
1
4 OD high pressure tube 60° cone;
9
16-18 gland thread;
available in stainless steel for range 5 only)
Wetted Parts:
Flanges: Plated carbon steel standard;
stainless steel, Hastelloy C or Monel optional (available on PX751C only)
Wetted O-Rings: Glass-filled TFE
Housing: Low-copper aluminum with
polyurethane paint
Cover O-Rings: Buna-N Note: Calibrations at 20°C (68°F) per
ANSI Z210.1
1
Process temperatures above 185°F (85°C) require derating the ambient limits by a 1.5:1 ratio (0.06:1 ratio for Type H).
2
104°C ( 220°F) limit in vacuum service;
71°C (130°F) for pressures below 0.5 psia.
3
71°C (160°F) limit in vacuum service.
4
Not available on model PX751CA.
10
16 flange
B-237
Loading...
+ 5 hidden pages